PMWO 4.2 is available in three sizes for the 800 series ROC; 4‐well, 8‐well and 12‐well.
Select Display 65 to configure Well
Optimization Units.
Configuring the Units for PMWO
Configure the units as required for
your location. Be sure to match the
AGA Gas Volumes with the Meter
Configuration.
The Configuration Screen. Select between Gas Lift and Cyclic Production (Intermitter, Plungers or
RodPump), or select both for a Plunger Assisted Gas Lift (PAGL).
The lower half of the screen
configures the Well’s Core Features.
These are used for all types of well
optimization.
Select the type of Optimization
Method required for this well.
Available options for each type can
then be selected as needed.
Example of a Gas Lift configuration. Be sure to Enable the well to allow the program to Optimize.
Gas Lift with Coleman/Turner Critical
Flow Calculation have been selected
for this well, and the appropriate
tabs and configuration screens are
now available.
Gas Lift Configuration Tab.
Injection Configuration:
Define Meter and PID (see
Notes)
Define Setpoints, Limits and
Step Change Parameters
Define Abort and SSD
Conditions
Select Gas Lift Optimization mode
and product being produced
Production Configuration:
Production/Sales meter is
copied from the core
Define Buyback meter, if
required, and Oil and Water
meters (see Notes)
Example of a Cyclic Well, Conventional Plunger Lift selected with Gas Assisted Plunger Lift (GAPL) option
enabled. Be sure to Enable the well to allow the program to Optimize.
Plunger Lift for Conventional
Plungers with Coleman/Turner
Critical Flow Calculation and Gas
Assist (GAPL) have been selected for
this well, and the appropriate tabs
and configuration screens are now
available.
Plunger Configuration tab. Available for Continuous and Conventional plungers.
Plunger Lift configuration tab:
Define Arrival Switch and
Bumper Spring Depth
Define Non‐Arrival Options
Define other Options when
selected from the General
Tab
Cyclic Triggers tab to configure Open and Close Triggers. Available to all types of Cyclic Types.
Plunger Lift Triggers tab:
Define Vent/GAPL/Abort
Triggers during Lift
Define Afterflow Closing
Triggers
Define Plunger Drop Time
Define Armed Shutin Open
Triggers
Self‐Adjustment Tab
Plunger Lift Triggers Self‐Adjust Tab:
Define one open or close
trigger to auto‐adjust and
the parameters to force the
adjustment
Optional tools to be used as required.
Plunger Special Options tab:
Define as required based on
options enabled on the
General Tab
Foss and Gaul is used to
generate recommended
opening trigger setpoints
based on Plunger
Specifications
Special Closure controls to be used as required.
Plunger Lift Special Closures tab:
Built in Line Pressure Over
rides available
Swabbing, health check of
comports or other devices
and nomination control
available
Real Time and Cyclic Alerts can be used for notification or closure based on well process events.
Plunger Lift Real Time/Cyclic Alerts tab:
Define Alerts as needed and
the action to take when true
The Core Operate Page
Use the Core Operate Page
to monitor well Core
Devices. Typically used on
wells without assisted list or
running PM Automated
Choke Control
The Gas Lift Operate page. Note, if the Well Instance does not have Gas Lift Enabled, the screen is blank.
Gas Lift Operate tab:
Allows monitoring of the
Well during the Gas Lift
Averaging Cycle
Real time Production and
Economic Revenue values
available
Allows Editing of key Gas Lift
Control Points
Gas Lift Operate Completed Cycles Tab
Gas Lift Completed Cycles tab:
Displays the last two
completed gas lift Averaging
Cycles and their production
results
The Cyclic Control Operate page allows monitoring and controlling the well all from one interface. The
stages of the well are color coded to immediately tell which stage of the cycle the well is currently in.
Cyclic Control Operation tab:
Allows easy Monitoring and
control.
Allows tuning of triggers
Allows Starting/Stopping
Allows Manual advancing
Plunger Statistics and Foss and Gaul Calculation Results
Plunger Data tab:
Last 10 Arrival Information
Cycle Stats
Foss and Gaul Calculated results.
(Recommended open trigger
settings is available on the Cycle
Control Tab)
Self‐Adjust Triggers. Tab hidden if Self‐Adjust is not selected.
Plunger Lift Triggers Self‐Adjust Tab:
Define one open or close
trigger to auto‐adjust and
the parameters to force the
adjustment
Real Time and Cyclic Alerts Tab. Tab hidden if Alerts not selected
Plunger Lift Real Time/Cyclic Alerts tab:
Define Alerts as needed and
the action to take when true
Notes:
1. Remote Flow Calculations
1.1. PMWO supports using Flow Calculations from a remote device. They must be stored in a
Softpoint in the following order for PMWO to be able to access all of the values it needs.
1.1.1. Data 1 = DP
1.1.2. Data 2 = Pressure
1.1.3. Data 3 = Temperature
1.1.4. Data 4 = Instantaneous Daily Rate
1.1.5. Data 5 =Accumulated Flow Today
1.1.6. Data 6 =Accumulated Flow Previous Day
1.1.7. Data 7 =Accumulated Flow Month
1.1.8. Data 8 =Accumulated Flow Previous Month
1.1.9. Data 9 =Running Accumulator
1.2. When pointing the Point Definition of a configurable Flow to a Softpoint:
1.2.1. If Rate is selected PMWO will automatically select Data Register 4
1.2.2. If Accumulator is selected PMWO will automatically select Data Register 9
2. Many Point Definition fields will auto‐select the appropriate parameter
2.1. When browsing for AGA meters, select the AGA Type either Orifice or Linear and the correct
Logical Number and PMWO will select the appropriate Parameter.
2.2. When browsing for PID Loops, select the correct logical number and PMWO will select the
appropriate Parameter.
2.3. When selecting Discrete Outputs on the GAPL configuration
2.3.1. If the DO’s Auto Output is selected only One DO can be configured. It is assumed a single
DO opens and closes the GAPL valve.
2.3.2. If the DO’s Momentary Mode is selected a second DO is made available to use for pulse
open and pulse close operation.
3. Well TLP Update Rate
3.1. All calculations and values that must be stored to insure proper boot up without losing
resolution are done every second.
3.2. But in an effort to drastically reduce MPU loading, monitored only parameters are only written
to TLPs based on this setting. The default is 5 seconds. Increasing this time does not affect the
operation of the well, only slows down the updating of monitored values.
4. Insufficient Configuration Error
4.1. This is based on minimum configuration requirements and the type of Gas Lift being used.
4.1.1. Minimum Requirements and Gas only Optimization
4.1.1.1. Production/Sales Meter
4.1.1.2. Injection Meter
4.1.1.3. Injection PID
4.1.2. Maximum Hydrocarbon or Max Revenue
4.1.2.1. Minimum plus Hydrocarbon Meter (or Tank Manager Accumulators)
4.1.2.2. Water recommended for Total Revenue calculation
4.1.3. Maximum Water
4.1.3.1. Minimum Plus Water Meter (or Tank Manager Accumulator)
5. Non‐Optimizing Wells
5.1. Configure Core only and use PM Surface Controls (PMSC) to manage shutdowns
6. PM Auto‐Choke Controlled Wells
6.1. Configure Core only and use PM Surface Controls (PMSC) to manage shutdowns
7. Plunger Assisted Gas Lift (PAGL)
7.1. Defined as: A gas lift well with a plunger to assist with lifting liquids
7.2. Enable Gas Lift and Cyclic on the same instance
7.2.1. Define Cyclic type as Continuous Plunger
7.2.1.1. Define Triggers to run the Continuous Plunger
7.2.2. Configure the Valve Closure and Abort Testing
7.2.2.1. Set the Max Production Closed Minutes greater than the amount of
time the production valve is closed to send the Continuous Plunger back down the
well.
8. Gas Assisted Plunger Lift (GAPL)
8.1. Defined as: A plunger lift well with gas assist to bring the plunger up
8.2. Enable GAPL as one of the options for the Plunger Type
8.2.1. Configure the GAPL Flow Meter
8.2.2. Configure the GAPL Control Valve
8.2.2.1. PID
8.2.2.2. DO (Single or Dual see 2.3)
8.2.3. Define when to use and open the GAPL valve
9. Venting
9.1. Venting is still supported in this version in the same method as in the past.
10. Offset Gain Factor is a new function that will automatically adjust the amount of Injection Setpoint
change at the end of an averaging cycle. It monitors the “Improvement” amount for each averaging
cycle and if the amount of improvement is less than the Max Step Change amount, it will adjust the
Injection Setpoint +/‐ the Improvement * Offset Gain Factor. This will allow smaller step changes to
the injection amount as the well gets closer to steady state operation.
11. Gas Lift Valve Sequencing Auto‐Run is a new feature that allows the operator to select an amount of
time to allow the well to be down and when exceeded will automatically restart the well using the
parameters of the Gas Lift Valve Sequencing function. Allows exercising of the mandrel valves down
hole if the well has been down for too long.