PM210 Compact Three Phase Multi Function Power Meter Installation and Operating Manual

description

Power meter PM210 manualPower meter PM210 manualPower meter PM210 manualPower meter PM210 manualPower meter PM210 manualPower meter PM210 manualPower meter PM210 manual

Transcript of PM210 Manual-3.1e

PM210 Compact Three Phase Multi Function

Power Meter

Installation and Operating Manual

MODEL SELECTIONSBasic Model: PM210A

Model Type Description Examples

PM210A-STD-yy Standard 5A model, direct input of up to 10A or use with external CTs. yy = 50 or 60 Hz

PM210A-STD-50HzPM210A-STD-60Hz

PM210A-xx-yy Dedicated CT model, mA input, must always be used with the dedicated CT. xx = 30D, 75D, 100D, 50S, 100S, 200Syy = 50 or 60 HzWarning: This model type is not to be used with standard 5A CTs.

PM210A-100D-50HzPM210A-200S-60Hz

Optional CT selection for PM210A-STD-yy.

Donut type CT (solid core), rating 100A, ratio 100:1

Description

CT-100A Donut type CT (solid core), rating 100A, ratio 100:1

CT-200A Donut type CT (solid core), rating 200A, ratio 200:1

Dedicated CT selection for PM210A-xx-yy.

PM210A-xx-yy xx selections Description

100D CT-100D, dedicated CT, 100A, donut type (solid core), 2000 turns

200D CT-200D, dedicated CT, 200A, donut type (solid core), 2000 turns

50S CT-50S, dedicated CT, 50A, split type, 3000 turns

100S CT-100S, dedicated CT, 100A, split type, 3000 turns

200S CT-200S, dedicated CT, 200A, split type, 3000 turns

INSTALLATIONTerminal Diagram

Panel Cut

Wiring Diagrams

IA+ IA- IB+ IB- IC+ IC- VA VB VC N

A

B

C

3ø3w

Note: KL is not sensitive

K L

SET UP1. Enter the set up mode by pressing both the keys

simultaneously, the display should be showing the

firmware version. The firmware version is read only and cannot be

changed.

2. Press the key again to show then set the desired

RS485 address using the key. The address can be set from 0 to

99.

3. Press the key again to show then set the

desired baud rate using the key. The selectable baud rates are:

1200, 2400, 4800 or 9600.

4. Press the key again to show then set the PT

using a combination of the key to change the digit and the

to move to the next digit. The PT can be set from 1.00 to 4.00, 100 or

200.

5. Press the key again to show then set the CT ratio

using a combination of the key to change the digit and the

to move to the next digit. The CT ratio can be set from 1 to 1000.

For the standard 5A model, set the CT ratio accordingly.

Example 1: using a CT with ratio 100:5, set the CT ratio to 20.

Example 2: using a CT with ratio 200:1, set the CT ratio to 200.

Caution: For the dedicated CT model, the ratio has been factory set and

should not be changed, changing this value may result in an incorrect or

inaccurate reading.

6. Press the key again to show . This shows the

model type of the PM210. “Yes” means that the meter is the standard

5A model, “no” means that the meter is the dedicated CT model.

Caution: Do not change this value, this is factory set, changing this

value may result in an incorrect or inaccurate reading.

7. Press the key again to show . This shows the wiring

type, “3” sets the meter to recognize the wiring as 3 phase 3 wire, “4”

sets the meter to recognize the wiring as 3 phase 4 wire.

8. Press both the simultaneously to leave the setting mode

and return to the normal display mode.

UNIT OPERATIONLED Display

Current Indicator

Voltage Indicator

kW Indicator

Cycle Key

RS485 Transmit Indicator

Next Digit KeyRS485 Receive Indicator

Increment KeyPF Indicator

kVArh Indicator

kWh Indicator

Display IndicatorsIndicator Description

Current: Amps, for each of 3 phases - IA, IB, IC

Voltage: Volts, for each of 3 phases - VA, VB, VC

Power: kW, total of all 3 phases

Real Energy Consumption: kWh

Apparent Power Consumption: kVArh

Power Factor (PF)

Rx RS485 receive activity

Tx RS485 transmit activity

Key Operation

KeyCombination Function

Regular Mode: Cycles between displayable values1. Current - A phase2. Current - B phase3. Current - C phase4. Voltage - A phase5. Voltage - B phase6. Voltage - C phase7. kW8. kWh9. kVARh10. PF

Setting Mode: Save and move to the next parameter

1. Firmware version (read only)

2. RS485 address - 0 to 99

3. Baud rate - 1200, 2400, 4800, 9600

4. PT ratio - 1.00 to 4.00 (0.01 resolution), 100 and 200

5. CT ratio - 1 to 1000 (1 resolution)

6. 5A - Yes (standard 5A) or No (dedicated CT) CAUTION: FACTORY USE ONLY, DO NOT CHANGE

7. Phase - 3 (3 phase 3 wire) or 4 (3 phase 4 wire)

+ Press together to enter or exit setting mode.

During setting mode, increment digit. No function during regular mode.

During setting mode of PT and CT, move to the next digit. No function during display mode.

SPECIFICATIONS

Standard Type Dedicated CT Type

Electrical

Phase/Wire 3ø3w or 3ø4w

Power Supply 110 or 220 Vac, ±10% (on separate terminals)

Power Consumption

starting current 300 mA, working 35 mA at 110 Vstarting current 200 mA, working 20 mA at 220 V

Rated Current 5A (max 10A) depends on dedicated CT

Input Frequency

50 or 60 Hz - depending on model

Internal Measurement

Phase Voltage 80 to 350 Vac, resolution 0.1 V

Measured Current 8 mA to 5 A (resolution 1 mA) 50 mA to 100 A (resolution 1 mA)

on CT primary

Cumulative Active Energy resolution 0.01 kWh

PF resolution 0.01

Communication Interface

Bus Type RS485

Protocol Modbus/RTU

Baud Rate 1200, 2400, 4800 or 9600 (default)settable via front panel or Modbus

Address 0 to 99

Data Format 8 / None / 1

Physical

Operating Temperature 0 to 60˚C 

Weight 450 gm 400 gm

Mounting DIN panel mount - 92 x 46 mm

Dimensions 110 x 50 x 115 mm (W x H x D)

Front Panel Interface

Display 6 digit 7 segment LED

LED Indicators 8 - A, V, kW, kWh, kVArh, PF, Rx, TX

Function Keys 3 keys

Up Arrow (increment digit)

Right Arrow (select next digit)

Page/Enter

Modes Display Mode or Setting Mode

Front Panel Display ModeParameter Unit Resolution

Current Per Phase - IA, IB, IC Amperes 0.001 A

Phase Voltage Per PhaseVA, VB, VC Volts 0.1 V

Active Power kW 0.001 kW

Parameter Unit Resolution

Cumulative Active Energy kWh 0.1 kWh

Cumulative Reactive Energy kVArh 0.1 kVArh

Power Factor PF 0.001 PF

Front Panel Setting Mode Parameter Values

Firmware Version varies; read-only

RS485 address 0 to 99 (resolution 1); factory default = 0

Baud Rate 1200, 2400, 4800 or 9600; factory default = 9600

PT Ratio 1.00 to 4.00 (resolution 0.01), 100 or 200; factory default = 1.00

CT Ratio 1 to 1000 (by 1 increments)

5A mode YES = 5A standard type, no = dedicated CT typeCAUTION: FACTORY USE ONLY, DO NOT CHANGE

Phase/Wire 3 = 3 phase 4 wire, 4 = 3 phase 4 wire

MODBUS REGISTERS

Real Time Data 1 (one word sized data)AddressName Description Words Format Min Max Default Unit Valid for

0000H V1 Phase R Voltage 1 F6 0 65535 0 0.1 3P4W/3P3W

0001H V2 Phase S Volt 1 F6 0 65535 0 0.1 3P4W/3P3W

0002H V2 Phase T Volt 1 F6 0 65535 0 0.1 3P4W/3P3W

0003H V12 Line R-S Volt 1 F6 0 65535 0 0.1 3P4W/3P3W

0004H V23 Line S-T Volt 1 F6 0 65535 0 0.1 3P4W/3P3W

0005H V32 Line T-R Volt 1 F6 0 65535 0 0.1 3P4W/3P3W

0006H I1 Phase R Amp 1 F7 0 65535 0 0.001 3P4W/3P3W

0007H I2 Phase S Amp 1 F7 0 65535 0 0.001 3P4W/3P3W

0008H I3 Phase T Amp 1 F7 0 65535 0 0.001 3P4W/3P3W

0009H P KW Total 1 F8 0 65535 0 0.001 3P4W/3P3W

000AH Q KVAR Total 1 F8 0 65535 0 0.001 3P4W/3P3W

000BH S KVA Total 1 F8 0 65535 0 0.001 3P4W/3P3W

000CH F Hz 1 F10 0 65535 0 0.1 3P4W/3P3W

000DH PF PF 1 F9 0 65535 0 0.01 3P4W/3P3W

000EH reserved 3P4W/3P3W

000FH reserved 3P4W/3P3W

Real Time Data 2 (two word sized data)AddressName Description Words Format Min Max Default Unit Valid for

0014HV1

VoltageLow Word

2 F12 0 999.9   0.1V 3P4W/3P3W

0015H Voltage High Word

0016HV2

VoltageLow Word

2 F12 0 999.9   0.1V 3P4W/3P3W

0017H VoltageHigh Word

0018HV3

VoltageLow Word

2 F12 0 999.9   0.1V 3P4W/3P3W

0019H VoltageHigh Word

001AHV12

VoltageLow Word

2 F12 0 999.9   0.1V 3P4W/3P3W

001BH VoltageHigh Word

001CHV23

VoltageLow Word

2 F12 0 999.9   0.1V 3P4W/3P3W

001DH VoltageHigh Word

001EHV31

VoltageLow Word

2 F12 0 999.9   0.1V 3P4W/3P3W

001FH VoltageHigh Word

0020HI1

CurrentLow Word

2 F13 0 999.999   0.001A 3P4W/3P3W

0021H CurrentHigh Word

0022HI2

CurrentLow Word

2 F13 0 999.999   0.001A 3P4W/3P3W

0023H CurrentHigh Word

0024HI3

CurrentLow Word

2 F13 0 999.999   0.001A 3P4W/3P3W

0025H CurrentHigh Word

0026HP

PowerLow Word

2 F14 0 999999   1W 3P4W/3P3W

0027H Power High Word

0028HQ

VArLow Word

2 F14 0 999999   1VAR 3P4W/3P3W

0029H VarHigh Word

002AHS

VALow Word

2 F14 0 999999   1VA 3P4W/3P3W

002BH VAHigh Word

002CHF

FrequencyLow Word

2 F16 0 999   0.1Hz 3P4W/3P3W

002DH FrequencyHigh Word

002EHPF

Power FactorLow Word

2 F15 0 999   0.001 3P4W/3P3W

002FH Power FactorHigh Word

0030HEP+

kWhLow Word

2 F11 0 99999.99   0.01kWh 3P4W/3P3W

0031H kWhHigh Word

0032HEQ+

kVArhLow Word

2 F11 0 99999.99   0.01kVArh 3P4W/3P3W

0033H kVArhHigh Word

Energy Data Address Name Description Words Format Min Max Default Unit Valid for

0040HEP+

kWhLow Word

2 F11 0 99999.99   0.01KWH 3P4W/3P3W

0041H kWhHigh Word

0042HReserved

0043H

0044HEQ+

kVArhLow Word

2 F11 0 99999.99   0.01kVArH 3P4W/3P3W

0045H kVArhHigh Word

0046H

Reserved0047H

0048H

0049H

Detailed Energy DataAddress Name Description Words Format Min Max Unit Valid for

0050HEP1+

kWhLow Word

2 F11 0 99999.99 0.01 kWh 3P4W only0051H kWh

High Word

0052HEP2+

kWhLow Word

2 F11 0 99999.99 0.01 kWh 3P4W only0053H kWh

High Word

0054HEP3+

kWhLow Word

2 F11 0 99999.99 0.01 kWh 3P4W only0055H kWh

High Word

0056HEP+

kWhLow Word

2 F11 0 99999.99 0.01 kWh 3P4W/3P3W0057H kWh

High Word

0058HEQ1+

kVArhLow Word

2 F11 0 99999.99 0.01 kVArh 3P4W only0059H kVArh

High Word

005AHEQ2+

kVArhLow Word

2 F11 0 99999.99 0.01 kVArh 3P4W only005BH kVARrh

High Word

005CHEQ3+

kVArhLow Word

2 F11 0 99999.99 0.01 kVArh 3P4W only005DH kVARrh

High Word

005EHEQ+

kVArhLow Word

2 F11 0 99999.99 0.01 kVArh 3P4W/3P3W005FH kVArh

High Word

0060HP1

WattLow Word

2 F14 0 999999 1 W 3P4W only0061H Watt

High Word

0062HP2

WattLow Word

2 F14 0 999999 1 W 3P4W only0063H Watt

High Word

0064HP3

WattLow Word

2 F14 0 999999 1 W 3P4W only0065H Watt

High Word

0066HP

WattLow Word

2 F14 0 999999 1 W 3P4W/3P3W0067H Watt

High Word

0068HQ1

VArLow Word

2 F14 0 999999 1 VAr 3P4W only0069H VAr

High Word

006AHQ2

VArLow Word

2 F14 0 999999 1 VAr 3P4W only006BH VAr

High Word

006CHQ3

VArLow Word

2 F14 0 999999 1 VAr 3P4W only006DH VAr

High Word

006EHQ

VArLow Word

2 F14 0 999999 1 VAr 3P4W/3P3W006FH VAr

High Word

0070HS1

VALow Word

2 F14 0 999999 1 VA 3P4W only0071H VA

High Word

0072HS2

VALow Word

2 F14 0 999999 1 VA 3P4W only0073H VA

High Word

0074HS3

VALow Word

2 F14 0 999999 1 VA 3P4W only0075H VA

High Word

0076HS

VALow Word

2 F14 0 999999 1 VA 3P4W/3P3W0077H VA

High Word

0078HPF1

Power FactorLow Word

2 F15 0 1000 0.001 3P4W only0079H Power Factor

High Word

007AHPF2

Power FactorLow Word

2 F15 0 1000 0.001 3P4W only007BH Power Factor

High Word

007CHPF3

Power FactorLow Word

2 F15 0 1000 0.001 3P4W only007DH Power Factor

High Word

007EHPF

Power FactorLow Word

2 F15 0 1000 0.001 3P4W/3P3W007FH Power Factor

High Word

Setup DataAddress Name Description Words Format Min Max Unit

0080H Wiring 3P3W or 3P4W 1 F1 0 1 1

0081HReserved

0082H

0083H Address RS-485 Address 1 F4 0 99 1

0084H Baud Rate Baud Rate 1 F5 0 3 1

0085H PT PT Rate 1 F2 1 200 1

0086H CT CT Rate 1 F3 1 1000 1

0087H

Reserved

0088H

0089H

008AH

008BH

008CH CT Fn Internal 5A CT or External DAE CT 1 F17 0 1 1

008DH Version PM210 firmware version 1 F18

Format TypesFormat No. Format Type Format Definition

F1 Wiring table 1 = 3P3W; 0 = 3P4W

F2 PT ratio PT = Data/100

F3 CT ratio CT = Data

F4 RS485 address Data

F5 Baud rate index 0 = 1200, 1 = 2400, 2 = 4800, 3 = 9600

F6 Voltage Voltage=Data/10 x PT ratio

F7 Current Current=Data/1000 x CT ratio

F8 Power (P, Q, S demand) Power = Data x PT ratio x CT ratio

F9 PF Positive : PF =Data/100

F10 Hz Freq = Data/10

F11 Energy (KWH, KVARH) Energy = {Word(h) x 65536 + word(L)} /100

F12 Voltage

When: 3P4W Voltage = {Word(h) x 65536 + word(L)}/10 x PT ratio

When: 3P3W Voltage ={Word(h) x 65536 + word(L)}/10

F13 Current

When:3P4W Current = {Word(h) x 65536 + word(L)}/1000 x CT ratio

When:3P3W Current = {Word(h) x 65536 + word(L)}/1000

F14 Power (P,Q,S demand)

When:3P4W Power = {Word(h) x 65536 + word(L)} x PT ratio x CT ratio

When:3P3W Power = {Word(h) x 65536 + word(L)}

F15 PF Positive : PF = {Word(h) x 65536 + word(L)}/1000

F16 Hz Freq = {Word(h) x 65536 + word(L)}/10

F17 CT Fn 0: Standard 5A1: External Dedicated CT

F18 PM210 A Version Ver = High byte*10+Low byte

Modbus Protocol ExamplesExample 1 - Read Current command === xx 03 00 00 00 02 CRC(low) CRC(high) response === xx 03 04 xx xx xx xx (2 word) CRC(low) high low byte byte

Example 2 - Write Address command = xx 10 00 83 00 01 02 00 kk CRC(low) CRC(high) response === xx 10 00 83 00 01 CRC(low) CRC(high) high low byte byte

Note: 1. kk = value to write to Address2. Baud Rate values:

a. 00h 1200 bpsb. 01h 2400 bpsc. 02h 4800 bpsd. 03h 9600 bps