EX. FC-1
EX. FC-2
EX. FC-3
EX. FC-4
EX. FC-5
EX. FC-6
EX. FC-7
EX. P
SD
SD
F
FACPWW WW WW
FF F F F
SD
CP
EX. AHU-1
AHU-1(RETURN)
EX. AHU-2
EX. RF-2
EX. AHU-1
RF-1(RETURN)
AHU-2(RETURN)
SD
RF-2(RETURN)
EX. DS-AHU-1
EX. MS-AHU-2
EX. MS-P2EX. MS-P1
EX. DS-RF-1
EX. DS-RF-2
EX. MS-RF-2
EX. MS-RF1
EX. MS-AHU-1
EX. DS-AHU-2
EX. DS-P2
EX. DS-P1
EX. PP
GENERAL NOTES:
KEYED NOTES:
115417
191 Mill Lane
Mountainside, NJ 07092
t. 908.232.2860
f. 908.232.2845
Drawn by:
Checked by:
Revision
Number
Revision
Description
Revision
Date
Monmouth County
Parks System
F O R T M O N M O U T H
RECREATION CENTER
HVAC IMPROVEMENTS
2566 Guam Lane
Tinton Falls, NJ 07724
JULY 27, 2017
THE MUSIAL GROUP ARCHITECTURE
OR
IG
IN
AL
IF
IT
IS
R
ED
IT
IS
A
N O
RIG
IN
AL
These drawings may not be reproduced by any means without the express
written consent of the architect.
EACH CONTRACTOR SHALL THOROUGHLY EXAMINE AND BECOME FAMILIAR WITH
ALL CONTRACT DOCUMENTS FOR THE PROJECT AND NOT LIMIT THEIR WORK TO
DRAWINGS REFERENCED FOR INDIVIDUAL TRADES.
Submission or distribution of documents to meet official regulatory
requirements or for similar purposes in connection with the Project is
not to be construed as publication in derogation of the Architect's
reserved rights.
The Drawings, Specifications and other documents prepared by The
Architect for this project are instruments of the Architect's service for use
solely with respect to this project and the Architect shall be deemed the
author of statutory and other reserved rights, including copyright. The
owner shall be permitted to retain copies, including reproducible copies,
of the Architect's drawings. Specifications or other documents shall not
be used by the Owner or others on other projects, for additions to this
Project or for completion of this Project by others, unless the Architect
agrees in writing and with appropriate compensation to the Architect.
Noel S. Musial, A.I.A.
N.Y. 11339N.J. A105415
PA. B 6580CT. 09009
BUSINESS PROPRIETARY INFORMATION
© Copyright 2017
Seal:State of New JerseyCertificate of Authorization
No: 24GA28143600
Matthew C. ZabroskyProfessional Engineer
NJ LicenseNo: 24GE04673800
PINE HILL ENGINEERING LLC99 Baird Road, Millstone Township, NJ 08535
Telephone: (732) 851-4088Email: [email protected]
www.pinehilleng.com
Consultant:
AS NOTED
JL
MZ
ELECTRICAL
DEMOLITION
PARTIAL PLANS
ED101
1
ED101
MECHANICAL ROOM 1 - ENLARGED DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
2
ED101
PARTIAL DEMOLITION PLAN
SCALE: 1/8" = 1'-0"
(TYP. OF 4)
1. ALL EXISTING ELECTRICAL EQUIPMENT, DEVICES, FIXTURES,COMPONENTS, AND WIRE ARE TO REMAIN UNLESS OTHERWISENOTED OR INDICATED.
2. ALL EXISTING FIRE ALARM SYSTEM EQUIPMENT, DEVICES,NOTIFICATION APPLIANCES, COMPONENTS, AND CABLING SHALLREMAIN UNLESS OTHERWISE NOTED OR INDICATED.
3. ALL FIRE ALARM SYSTEM WORK SHALL BE PROVIDED BY THECONTRACTOR UTILIZING THE SERVICES AND PRODUCTS OF THEOWNER'S CURRENT FIRE ALARM SYSTEM MAINTENANCECONTRACTOR FOR ALL MODIFICATIONS MADE TO THE EXISTINGFIRE ALARM SYSTEM AS PART OF THIS CONTRACT. THECONTACT INFORMATION FOR THE OWNER'S CURRENT FIREALARM SYSTEM MAINTENANCE CONTRACTOR IS AS FOLLOWS:
COMPLETE SECURITY SYSTEMS, INC.94 VANDERBURG ROADMARLBORO, NJ 07746P: 800-452-3773W: WWW.COMPLETESECURITYSYSTEMS.COM
REMOVE THE EXISTING BRANCH CIRCUIT WIRING SERVINGTHE EXISTING MECHANICAL EQUIPMENT TO PERMIT ITSREMOVAL. SEE DIAGRAM 1/E601 FOR ADDITIONALREQUIREMENTS.
REMOVE THE EXISTING DUCT SMOKE DETECTORS TOACCOMMODATE MODIFICATIONS TO THE EXISTING DUCT.RE-INSTATE THE EXISTING FIRE ALARM SYSTEM ZONE(S) THATSERVED THE REMOVED DUCT SMOKE DETECTORS ASREQUIRED FOR ALL OTHER EXISTING FIRE ALARM SYSTEMDEVICES CONNECT TO THAT ZONE(S) TO REMAIN IN SERVICEDURING CONSTRUCTION.
REMOVE THE EXISTING LIGHTING FIXTURES AND ASSOCIATEDBRANCH CIRCUIT WIRING WITHIN MECHANICAL ROOM 1. THEEXISTING BRANCH CIRCUIT HOME RUN THAT SERVES THEEXISTING LIGHTING FIXTURES THAT ARE REMOVED SHALLREMAIN AND BE REUSED TO SERVE THE NEW LIGHTINGFIXTURES WITHIN THIS ROOM. IF NEED, PROVIDETEMPORARY LIGHTING DURING DEMOLITION ANDCONSTRUCTION WORK.
REMOVE THE EXISTING SNAP SWITCH DEVICE ANDASSOCIATED COVER PLATE THAT CONTROLS THE LIGHTINGFIXTURES WITHIN MECHANICAL ROOM 1 TO PERMIT ITSREPLACEMENT. THE EXISTING BRANCH CIRCUIT HOME RUNTO THIS DEVICE SHALL REMAIN AND BE REUSED TO SERVETHE NEW LIGHTING FIXTURES WITHIN THIS ROOM. THEEXISTING DEVICE BOX AND AND WIRING MAY BE RE-USEDWHERE PRACTICAL.
DISCONNECT THE EXISTING FAN COIL UNIT VENTILATOR TOPERMIT ITS REMOVAL. THE EXISTING BRANCH CIRCUITWIRING SHALL REMAIN AND BE RE-USED TO SERVE THEREPLACEMENT FAN COIL UNIT.
1
ED101
MECHANICAL ROOM 1
C:\U
sers
\jlan
g\O
neD
rive\
PH
E S
hare
d\Jo
bs\2
017\
1703
0\D
raw
ings
\170
30E
-FP
.dw
g, 7
/27/
2017
10:
01:1
9 A
M, J
osep
h La
ngan
, Pin
e H
ill E
ngin
eerin
g LL
C
115417
191 Mill Lane
Mountainside, NJ 07092
t. 908.232.2860
f. 908.232.2845
Drawn by:
Checked by:
Revision
Number
Revision
Description
Revision
Date
Monmouth County
Parks System
F O R T M O N M O U T H
RECREATION CENTER
HVAC IMPROVEMENTS
2566 Guam Lane
Tinton Falls, NJ 07724
JULY 27, 2017
THE MUSIAL GROUP ARCHITECTURE
OR
IG
IN
AL
IF
IT
IS
R
ED
IT
IS
A
N O
RIG
IN
AL
These drawings may not be reproduced by any means without the express
written consent of the architect.
EACH CONTRACTOR SHALL THOROUGHLY EXAMINE AND BECOME FAMILIAR WITH
ALL CONTRACT DOCUMENTS FOR THE PROJECT AND NOT LIMIT THEIR WORK TO
DRAWINGS REFERENCED FOR INDIVIDUAL TRADES.
Submission or distribution of documents to meet official regulatory
requirements or for similar purposes in connection with the Project is
not to be construed as publication in derogation of the Architect's
reserved rights.
The Drawings, Specifications and other documents prepared by The
Architect for this project are instruments of the Architect's service for use
solely with respect to this project and the Architect shall be deemed the
author of statutory and other reserved rights, including copyright. The
owner shall be permitted to retain copies, including reproducible copies,
of the Architect's drawings. Specifications or other documents shall not
be used by the Owner or others on other projects, for additions to this
Project or for completion of this Project by others, unless the Architect
agrees in writing and with appropriate compensation to the Architect.
Noel S. Musial, A.I.A.
N.Y. 11339N.J. A105415
PA. B 6580CT. 09009
BUSINESS PROPRIETARY INFORMATION
© Copyright 2017
Seal:State of New JerseyCertificate of Authorization
No: 24GA28143600
Matthew C. ZabroskyProfessional Engineer
NJ LicenseNo: 24GE04673800
PINE HILL ENGINEERING LLC99 Baird Road, Millstone Township, NJ 08535
Telephone: (732) 851-4088Email: [email protected]
www.pinehilleng.com
Consultant:
NONE
JL
MZ
ELECTRICAL
SPECIFICATIONS
E001
1. GENERAL
1.01 SCOPE
A. THE GENERAL CONDITION REQUIREMENTS OF THE CONTRACT APPLY TO THE ELECTRICAL WORK.
B. PROVIDE ALL MATERIAL, TOOLS, SUPERVISION AND LABOR REQUIRED FOR THE ELECTRICAL WORK DESCRIBED IN THESE
SPECIFICATIONS AND INDICATED ON THE DRAWINGS.
C. PROVIDE ALL NECESSARY INCIDENTAL MATERIALS AND ACCESSORIES REQUIRED TO MAKE THE WORK COMPLETE IN ALL
RESPECTS, EVEN IF NOT PARTICULARLY INDICATED OR SPECIFIED.
D. OBTAIN ALL PERMITS AND SCHEDULE ALL REQUIRED INSPECTIONS. COPIES OF ALL PERMITS AND INSPECTION
CERTIFICATES SHALL BE SUBMITTED TO THE TENANT FOR RECORD.
E. COORDINATE ELECTRICAL WORK WITH THE WORK OF OTHER TRADES.
F. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF ALL EXISTING AND NEW CONDITIONS AND
MATERIALS WITHIN THE CONSTRUCTION AREA. ANY DAMAGE CAUSED BY THE CONTRACTOR SHALL BE REPAIRED TO
THE TENANT'S SATISFACTION.
1.02 DEFINITIONS
A. FURNISH: TO PURCHASE, PROCURE, ACQUIRE AND DELIVER, COMPLETE WITH RELATED ACCESSORIES.
B. INSTALL: TO ERECT, MOUNT AND CONNECT, COMPLETE WITH RELATED ACCESSORIES.
C. PROVIDE: TO FURNISH AND INSTALL.
D. WIRING: RACEWAY, FITTINGS, SUPPORTS, BOXES, WIRE OR CABLE AND RELATED ITEMS.
E. CONTRACTOR OR ELECTRICAL CONTRACTOR: THE CONTRACTOR FOR THE ELECTRICAL WORK WHICH IS SPECIFIED
HEREIN AND SHOWN ON THE DRAWINGS.
F. TENANT: DCJ BELMAR
1.03 QUALITY ASSURANCE
A. ALL WORK SHALL COMPLY WITH APPLICABLE CODES, REGULATIONS AND STANDARDS GOVERNING THE PROJECT SITE
INCLUDING:
1. THE NEW JERSEY STATE UNIFORM CONSTRUCTION CODE (UCC)
2. 2009 INTERNATIONAL BUILDING CODE, NEW JERSEY EDITION (IBC)
3. NFPA 70 - NATIONAL ELECTRICAL CODE, 2011 EDITION (NEC)
4. ASHRAE STANDARD 90.1-2007 - ENERGY STANDARD FOR BUILDINGS EXCEPT LOW-RISE RESIDENTIAL
5. AMERICANS WITH DISABILITIES ACT (ADA)
B. ALL WORK SHALL BE PERFORMED SAFELY AND IN COMPLIANCE WITH THE CURRENT REQUIREMENTS OF:
1. FEDERAL OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA) INCLUDING:
a. 29 CFR, PART 1910 - OCCUPATIONAL SAFETY AND HEALTH STANDARDS, SUBPART S - ELECTRICAL
b. 29 CFR, PART 1926 - SAFETY AND HEALTH REGULATIONS FOR CONSTRUCTION, SUBPART K - ELECTRICAL
2. NFPA 70E - STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE
C. ALL WORK SHALL BE PERFORMED IN WORKMANLIKE MANNER AND IN ACCORDANCE WITH THE NATIONAL ELECTRICAL
CONTRACTORS ASSOCIATION'S STANDARD OF INSTALLATION (NECA SI).
D. ALL MATERIALS SHALL BE NEW AND LISTED BY A RECOGNIZED TESTING LABORATORY.
1.04 DRAWINGS
A. THE DRAWINGS ARE DIAGRAMMATIC AND ILLUSTRATE THE APPROXIMATE LOCATIONS OF EQUIPMENT, DEVICES,
LIGHTING FIXTURES, OUTLETS, ENCLOSURES, BOXES, RACEWAYS, AND ETCETERA. PRECISE LOCATIONS SHALL BE
COORDINATED IN THE FIELD WITH THE TENANT, CIVIL DRAWINGS, AND THE WORK OF ALL OTHER TRADES AS
CONSTRUCTION PROCEEDS.
B. THE CONTRACTOR SHALL VERIFY ALL INDICATED EXISTING CONDITIONS PRIOR TO STARTING WORK AND REPORT ANY
DISCREPANCIES. THE DRAWINGS REFLECT CONDITIONS WHICH CAN BE REASONABLY INTERPRETED FROM THE
DRAWINGS AND INFORMATION FURNISHED BY THE TENANT. BY COMMENCING WORK, THE CONTRACTOR
ACKNOWLEDGES HIS CONFIRMATION OF ALL EXISTING CONDITIONS AS ACCEPTABLE WITH REFERENCE TO HIS
CONTRACT, SCOPE OF WORK AND BID PRICE SUCH THAT NO ADDITIONAL COMPENSATION SHALL BE FORTHCOMING FOR
UNFORESEEN EXISTING CONDITIONS.
C. IN GENERAL, BRANCH CIRCUIT WIRING IS NOT INDICATED ON THE PLAN DRAWINGS. NUMERALS ADJACENT TO SYMBOLS
FOR EQUIPMENT, DEVICES, LIGHTING FIXTURES, MOTORS, AND ETCETERA DENOTE THE BRANCH CIRCUIT TO WHICH THE
ITEM IS TO BE CONNECTED. BRANCH CIRCUIT NUMBERS THAT ARE CONTAINED WITHIN PARENTHESIS DENOTE A
MULTIPLE POLE BRANCH CIRCUIT BREAKER. LOWER CASE LETTERS ADJACENT TO A DEVICE OR LIGHTING FIXTURE
SYMBOLS DENOTE SWITCH CONTROL.
D. WHERE ELECTRICAL WIRING SYMBOLS ARE SHOWN, HATCH MARKS INDICATE THE QUANTITY OF CONDUCTORS IN THE
BRANCH CIRCUIT. WIRING SYMBOL WITHOUT HATCH MARKS INDICATES TWO WIRES CIRCUITS. HATCH MARKS ARE NOT
USED TO INDICATE EQUIPMENT GROUNDING CONDUCTORS. FOR EQUIPMENT AND ISOLATED GROUND CONDUCTOR
REQUIREMENTS, REFER TO THE GROUNDING AND BOUNDING FOR ELECTRICAL SYSTEMS SECTION OF THIS
SPECIFICATION.
1.05 SUBSTITUTIONS
A. ALL EQUIPMENT AND MATERIALS FURNISHED AND/OR PROVIDED SHALL BE AS SPECIFIED AND PRODUCTS OF THE NAMED
MANUFACTURER(S) IN THE CONTRACT DOCUMENT. THE CONTRACTOR MAY REQUEST AN APPROVAL TO FURNISH
AND/OR PROVIDE EQUIPMENT OR MATERIALS THAT ARE DIFFERENT OR POSSESS DIFFERENT FEATURES AND/OR
ACCESSORIES THAN THOSE SPECIFIED, OR ARE A PRODUCT OF A MANUFACTURER OTHER THAN THOSE NAMED.
B. ALL SUBSTITUTION APPROVAL REQUESTS SHALL BE BY WRITTEN REQUEST.
C. SUBSTITUTION REQUEST SHALL CONTAIN THE PRODUCT DATA AND SHOP DRAWINGS AND A LETTER OF EXPLANATION ON
THE CONTRACTOR'S LETTERHEAD STATING THE CONTRACTOR'S REASONS FOR THE REQUEST, THE BENEFITS THAT THIS
SUBSTITUTION WILL PROVIDE OVER THE SPECIFIED ITEM AND THE COST IMPLICATIONS TO THE CONTRACT.
D. THE ENGINEER SHALL DETERMINE THE ACCEPTABILITY OF ANY SUBSTITUTIONS.
E. IF APPROVED, THE CONTRACTOR ASSUMES ALL RESPONSIBILITY FOR COORDINATING THE WORK OF OTHER TRADES
WHICH MAY BE AFFECTED BY SUBSTITUTIONS, INCLUDING ALL RELATED COSTS.
1.06 AS-BUILT DRAWINGS
A. THE CONTRACTOR SHALL PREPARE AND SUBMIT, AS AN INFORMATIONAL SUBMITTAL, RECORD AS-BUILT DRAWINGS
AFTER COMPLETION OF THE WORK INDICATING ALL ALTERATIONS, ADDITIONS AND/OR DELETIONS TO THE SYSTEMS AS
DESIGNED AND AS SHOWN ON THE CONTRACT DOCUMENTS.
B. THE AS-BUILT DRAWING SUBMISSION SHALL INCLUDE ONE (1) REPRODUCIBLE ORIGINAL DRAWING SET, AND THREE (3)
FULL SIZE HARD COPY DRAWING SETS.
C. AS-BUILT CONDITIONS OF ALL UNDERGROUND SHALL BE DIMENSIONED TO COLUMN CENTER LINES OR OTHER
PERMANENTLY IDENTIFIABLE LOCATIONS.
1.07 OPERATION AND MAINTENANCE MANUALS
A. PREPARE AND SUBMIT TO THE OWNER, OPERATION AND MAINTENANCE MANUALS AS REQUIRED BY THE INDIVIDUAL
SPECIFICATION SECTIONS BELOW.
B. OPERATION AND MAINTENANCE MANUAL SUBMITTALS SHALL BE PREPARED ON A JOB_SPECIFIC BASIS WITH ALL
SUBMITTED INFORMATION PLACED HEAVY_DUTY 3_RING BINDERS. BINDERS SHALL BE LABELED WITH JOB_SPECIFIC
INFORMATION AND IDENTIFY THE TYPE OF EQUIPMENT FURNISHED AND/OR PROVIDED. BINDER SHALL INCLUDE THE
FOLLOWING AS A MINIMUM:
1. DETAILED TABLE OF CONTENTS
2. EQUIPMENT LIST THAT INCLUDES THE SUPPLIER'S CONTACT INFORMATION AND THE MANUFACTURERS ORDER NUMBER
3. MANUFACTURER'S OPERATION AND MAINTENANCE MANUALS OR INFORMATION SHEETS FOR EACH ITEM PROVIDED
4. SPARE PARTS INFORMATION
5. EQUIPMENT DRAWINGS
6. TEST REPORTS
7. MANUFACTURER'S WARRANTY
8. CONTRACTOR'S WARRANTY ON INSTALLATION
1.08 TESTING AND COMMISSIONING
A. AT THE COMPLETION OF THE ELECTRICAL WORK, COMPLETELY TEST THE ENTIRE ELECTRICAL INSTALLATION FOR
PROPER OPERATION. CORRECT ALL DEFICIENCIES FOUND.
B. PERFORM ADDITIONAL TESTING AND COMMISSIONING AS REQUIRED BY THE INDIVIDUAL SPECIFICATION SECTIONS
BELOW.
C. PREPARE AND SUBMIT, AS AN INFORMATIONAL SUBMITTAL, CERTIFICATES OF COMPLETION AND TEST REPORTS AS
REQUIRED BY THE INDIVIDUAL SPECIFICATION SECTIONS BELOW.
1.09 TRAINING
A. PROVIDE TRAINING SERVICES ON THE OPERATIONS AND MAINTENANCE OF THE EQUIPMENT AND MATERIALS FURNISHED
AND/OR PROVIDED AS REQUIRED BY THE INDIVIDUAL SPECIFICATION SECTIONS BELOW.
1.10 WARRANTY
A. EQUIPMENT, MATERIALS AND WORKMANSHIP OF THE ELECTRICAL INSTALLATION SHALL BE WARRANTED BY THE
CONTRACTOR FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE OF THE WORK BY THE TENANT.
B. THE CONTRACTOR SHALL PROMPTLY CORRECT, REPAIR AND/OR REPLACE ANY AND ALL BREAKS, FAILURES OR WEAR
DUE TO FAULTY MATERIALS, WORKMANSHIP OR EQUIPMENT.
C. PROVIDE ADDITIONAL WARRANTY(S) FOR EQUIPMENT AND MATERIAL AS REQUIRED BY THE INDIVIDUAL SPECIFICATION
SECTIONS BELOW.
2. COMMON WORK RESULTS FOR ELECTRICAL
2.01 BASIC ELECTRICAL METHODS
A. PROVIDE BRANCH CIRCUIT WIRING FOR ALL ITEMS INDICATED OR NOTED ON THE DRAWINGS IN ACCORDANCE WITH THE
SPECIFICATIONS AND INFORMATION INDICATED ON THE DRAWINGS.
B. EXTERIOR INSTALLATIONS TO BE WEATHER PROOF IN ALL RESPECTS.
C. EXTERIOR EQUIPMENT AND MATERIAL SHALL BE PAINTED OR FINISHED TO PREVENT CORROSION, COLOR TO BE
SELECTED BY THE TENANT.
D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING ASSOCIATED WITH THE ELECTRICAL
WORK. FINISHED OPENINGS SHALL MATCH EXISTING ADJACENT CONSTRUCTION AND FINISHES.
E. ALL EQUIPMENT AND MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS AND INSTALLATION INSTRUCTIONS.
F. INDICATED SIZES OF ALL CIRCUIT COMPONENTS (CIRCUIT BREAKERS, CONDUCTORS DISCONNECT SWITCHES, ETCETRA)
SERVING MECHANICAL EQUIPMENT SHALL BE CONFIRMED WITH NAMEPLATE REQUIREMENTS OF THE ACTUAL
EQUIPMENT TO BE INSTALLED. ELECTRICAL CONTRACTOR SHALL ADJUST CIRCUIT COMPONENT SIZES TO MEET THE
REQUIREMENTS OF THE EQUIPMENT PURCHASED.
3. ELECTRICAL POWER CONDUCTORS AND CABLES
3.01 CONDUCTORS AND CABLES
A. CONDUCTORS SHALL BE SOLID COPPER FOR SIZE 10 AWG AND SMALLER, AND STRANDED COPPER FOR SIZE 8 AWG AND
LARGER.
B. CONDUCTOR INSULATION SHALL BE TYPES THHN/THWN-2 RATED FOR 90° CELSIUS.
3.02 CONDUCTOR INSULATION APPLICATION AND WIRING METHODS
A. FEEDERS INSTALLED EXPOSED IN EXTERIOR LOCATIONS SHALL CONSIST OF TYPE THHN/THWN-2 SINGLE CONDUCTORS
IN RACEWAY.
B. BRANCH CIRCUITS INSTALLED EXPOSED IN INTERIOR LOCATIONS SHALL CONSIST OF TYPE THHN/THWN-2, SINGLE
CONDUCTORS IN RACEWAY.
C. BRANCH CIRCUITS INSTALLED CONCEALED IN INTERIOR LOCATIONS SHALL CONSIST OF TYPE THHN/THWN-2, SINGLE
CONDUCTORS IN RACEWAY.
D. BRANCH CIRCUITS INSTALLED EXPOSED IN EXTERIOR LOCATIONS SHALL CONSIST OF TYPE THHN/THWN-2, SINGLE
CONDUCTORS IN RACEWAY.
E. BRANCH CIRCUITS INSTALLED IN CONCRETE OR UNDERGROUND SHALL CONSIST OF TYPE THHN/THWN-2, SINGLE
CONDUCTORS IN RACEWAY.
F. CONNECTIONS TO VIBRATING EQUIPMENT SHALL CONSIST OF PULLED CONDUCTORS IN LIQUID TIGHT FLEXIBLE STEEL
CONDUIT WHERE INSTALLED IN EXTERIOR LOCATIONS.
G. GROUND CONDUCTORS SHALL BE INSULATED WHERE INSTALLED WITHIN AN ABOVE GRADE RACEWAY AND
UN-INSULATED WHERE INSTALLED BELOW GRADE OR IN DIRECT CONTACT WITH EARTH.
H. ALL SINGLE POLE 15 AND 20 AMPERE BRANCH CIRCUITS SERVING RECEPTACLES OR LIGHTING SHALL BE TWO WIRE
CIRCUITS PROVIDING AN INDIVIDUAL GROUNDED CIRCUIT (NEUTRAL) CONDUCTOR FOR EACH UNGROUNDED (HOT)
CIRCUIT CONDUCTOR. DO NOT SHARE NEUTRAL CONDUCTORS.
I. CONTRACTOR FOR ELECTRICAL WORK MAY COMBINE BRANCH CIRCUITS INTO A COMMON RACEWAY WHERE FEASIBLE.
CONTRACTOR SHALL DERATE CONDUCTOR SIZED INDICATED IN ACCORDANCE WITH ARTICLE 310-16, NOTE 8 OF THE
NATIONAL ELECTRICAL CODE. GROUNDED CIRCUIT CONDUCTORS (NEUTRALS), SHALL BE CONSIDERED A CURRENT
CARRYING CONDUCTOR, FOR THE PURPOSES OF DERATING.
J. ALL FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE COLOR CODED TO MEET NATIONAL ELECTRICAL CODE
REQUIREMENTS. COLOR CODING SHALL BE ACCOMPLISHED BY EMPLOYING WIRES WITH COLORED INSULATION OR
APPLYING COLORED ELECTRICAL TAPE AT WIRE TERMINATIONS AND SPLICES. MAINTAIN CONSISTENT COLOR CODING
THROUGHOUT THE PROJECT.
3.03 CONNECTORS AND SPLICES
A. SPLICES, TAPS AND CONNECTIONS FOR CONDUCTORS SIZE 10 AWG AND SMALLER SHALL BE MADE WITH TWIST ON
SPRING TENSIONED TYPE INSULATING CONNECTORS, 3M PERFORMANCE PLUS OR EQUIVALENT.
B. SPLICES, TAPS AND CONNECTIONS FOR CONDUCTORS SIZE 8 AWG AND LARGER USE COMPRESSION TYPE CONNECTORS
OR LUGS, HYDRAULICALLY CRIMPED AND INSULATED WITH APPLIED ELECTRICAL TAPE.
C. TAPE SHALL BE 3M-SCOTCH SUPER 88 VINYL TAPE OR EQUIVALENT.
4. GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
4.01 GENERAL
A. THE ENTIRE ELECTRICAL INSTALLATION SHALL BE GROUNDED IN ACCORDANCE WITH THE REQUIREMENTS OF THE NEC.
B. EQUIPMENT GROUND CONDUCTORS SHALL BE PROVIDED IN ALL FEEDERS AND BRANCH CIRCUITS. WHERE FEEDERS OR
BRANCH CIRCUITS ARE INSTALLED IN METALLIC RACEWAYS, THE RACEWAY SHALL NOT BE UTILIZED AS THE SOLE
EQUIPMENT GROUNDING MEANS BUT SHALL BE SUPPLEMENTED BY AN ADDITIONAL EQUIPMENT GROUND CONDUCTOR
CONTAINED WITHIN THE RACEWAY. EQUIPMENT GROUND CONDUCTORS SHALL CONSIST OF AN INSULATED OR BARE
WIRE.
4.02 GROUND RODS
A. GROUND RODS SHALL BE 3/4" DIAMETER BY 10'-0" LONG, COPPER CLAD STEEL. ALL INACCESSIBLE CONNECTIONS TO
GROUND RODS SHALL BE EXOTHERMICALLY WELDED.
5. HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
5.01 SUPPORTS
A. PROVIDE SUPPORTING DEVICES OF TYPES AND SIZES REQUIRED TO SUIT EACH PARTICULAR INSTALLATION DETAIL. IN
GENERAL, SUPPORTING DEVICES SHALL CONSIST OF THE FOLLOWING:
1. CLEVIS HANGERS: FOR SUPPORTING SINGLE RUNS OF CONDUIT FROM STRUCTURAL MEMBERS.
2. HANGER ROD: MINIMUM 3/8" DIAMETER CONTINUOUSLY THREADED.
3. BEAM CLAMPS: SIZED TO ACCEPT HANGER ROD AND SUITABLY CONFIGURED FOR THE STRUCTURAL MEMBER TO WHICH IT
IS TO BE SECURED.
4. CONDUIT STRAPS: ONE (1) OR TWO (2) HOLE GALVANIZED STEEL.
5. PREFABRICATED METAL FRAMING CHANNEL SUPPORT COMPONENTS: GALVANIZED STEEL CHANNELS, 12 GAUGE, 1-5/8" BY
1-5/8" PERFORATED OR NON-PERFORATED, WITH ACCESSORIES, HOT DIPPED OR ELECTRO GALVANIZED.
6. ANCHORS: LEAD OR STEEL EXPANSION TYPE FOR USE IN MASONRY OR CONCRETE AND TOGGLE TYPE FOR USE IN
DRYWALL CONSTRUCTION.
B. IN WET OR DAMP LOCATIONS, REFRIGERATED AREAS OR ROOMS AND LOCATIONS SUBJECT TO HIGH HUMIDITY OR
LARGE TEMPERATURE VARIATIONS, ALL SUPPORTING DEVICE COMPONENTS SHALL BE HOT DIPPED OR ELECTRO
GALVANIZED.
6. RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
6.01 CONDUIT AND TUBING
A. TYPE RMC, RIGID METAL CONDUITS, SHALL COMPLY WITH ANSI C80.1, RIGID GALVANIZED STEEL CONDUIT.
B. TYPE EMT, ELECTRICAL METALLIC TUBING, SHALL COMPLY WITH ANSI C80.3 AND INSTALLED WITH STEEL COMPRESSION
OR SET SCREW TYPE FITTINGS.
C. TYPE FMC, FLEXIBLE METAL CONDUIT, SHALL BE CONSTRUCTED FROM SINGLE STRIP, FLEXIBLE, CONTINUOUS,
INTERLOCKED AND DOUBLE WRAPPED GALVANIZED STEEL.
D. TYPE LFMC, LIQUID TIGHT FLEXIBLE METAL CONDUIT, SHALL BE TYPE FMC COATED WITH A LIQUID TIGHT JACKET OF
FLEXIBLE POLYVINYL CHLORIDE.
E. TYPE PVC, RIGID POLYVINYL CHLORIDE CONDUIT, SHALL BE SCHEDULE 40 OR SCHEDULE 80 WHERE SPECIFIED OR
NOTED.
F. THE MINIMUM TRADE SIZE OF CONDUIT OR TUBING SHALL BE 3/4-INCH.
G. ALL FITTINGS FOR CONDUITS AND TUBING SHALL BE LISTED FOR THE TYPE AND SIZE RACEWAY WITH WHICH THEY ARE
USED, AND FOR THE APPLICATION AND ENVIRONMENT IN WHICH INSTALLED.
H. JOINT COMPOUND FOR RIGID STEEL CONDUIT SHALL BE LISTED FOR USE IN CABLE CONNECTOR ASSEMBLIES, AND
COMPOUNDED FOR USE TO LUBRICATE AND PROTECT THREADED RACEWAY JOINTS FROM CORROSION AND ENHANCE
THEIR CONDUCTIVITY.
I. CONDUIT AND TUBING INSTALLED IN OUTDOOR LOCATIONS WHERE THEY ARE NOT SUBJECT TO PHYSICAL DAMAGE
SHALL BE TYPE PVC, SCHEDULE 40 OR TYPE EMT.
J. CONDUIT AND TUBING INSTALLED IN OUTDOOR LOCATIONS WHERE THEY ARE SUBJECT TO PHYSICAL DAMAGE SHALL BE
TYPE PVC, SCHEDULE 80 OR TYPE RMC.
K. CONDUIT AND TUBING CONNECTIONS TO VIBRATING EQUIPMENT IN OUTDOOR LOCATIONS SHALL BE TYPE LFMC.
L. CONDUITS AND TUBING INSTALLED IN CONCRETE, UNDER FLOOR SLAB OR UNDERGROUND SHALL BE TYPE PVC,
SCHEDULE 40 OR TYPE RMC.
M. CONDUITS AND TUBING INSTALLED CONCEALED IN INDOOR LOCATIONS OR EXPOSED IN INDOOR LOCATION WHERE THEY
ARE NOT SUBJECT TO PHYSICAL DAMAGE SHALL BE TYPE EMT.
N. CONDUITS AND TUBING INSTALLED IN INDOOR LOCATIONS WHERE THEY ARE SUBJECT TO PHYSICAL DAMAGE SHALL BE
TYPE RMC.
O. CONDUIT AND TUBING CONNECTIONS TO VIBRATING EQUIPMENT IN INDOOR LOCATIONS SHALL BE TYPE FMC.
6.02 WIREWAYS
A. WIREWAYS SHALL BE CONSTRUCTED OF STEEL AND COMPLY WITH ENVIRONMENTAL CONDITIONS AT INSTALLED
LOCATION IN ACCORDANCE WITH THE FOLLOW:
1. INDOOR, DRY AND CLEAN LOCATIONS: NEMA 250, TYPE 1
2. INDOOR LOCATIONS SUBJECT TO DUST, FALLING DIRT, AND DRIPPING NONCORROSIVE LIQUIDS: NEMA 250, TYPE 12
3. OUTDOOR LOCATIONS: NEMA 250, TYPE 3R.
B. PROVIDE WIREWAYS OF SIZED IN ACCORDANCE WITH THE NEC UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
C. PROVIDE WIREWAYS OF THE LENGTH AND CONFIGURATION AS INDICATED ON THE DRAWINGS
D. PROVIDE WIREWAY FITTINGS AND ACCESSORIES AS REQUIRED FOR COMPLETE SYSTEM.
E. PROVIDE NEMA, TYPE 1 WIREWAYS WITH SCREW-COVER TYPE COVERS.
F. WIREWAYS SHALL BE PROVIDED WITH A GRAY POLYESTER POWDER OR ENAMEL FINISH.
6.03 BOXES
A. INTERIOR OUTLET BOXES SHALL BE FABRICATED FROM GALVANIZED SHEET STEEL AND SHALL BE OF TYPES, SHAPES
AND SIZES TO SUIT EACH RESPECTIVE LOCATION AND FUNCTION. BOXES SHALL BE EQUIPPED WITH ALL REQUIRED
ACCESSORIES. MINIMUM INTERIOR OUTLET BOX DIMENSIONS SHALL BE 4" SQUARE BY 1-1/2" DEEP.
B. EXTERIOR WEATHERPROOF OUTLET BOXES SHALL BE PVC OR CORROSION RESISTANT CAST METAL TYPE. BOXES
SHALL BE TYPES, SHAPES AND SIZES NECESSARY TO FULFILL THE REQUIREMENTS OF INDIVIDUAL WIRING SITUATIONS.
BOXES SHALL BE EQUIPPED WITH THREADED CONDUIT HUBS AND GASKETED CORROSION RESISTANT WEATHERPROOF
COVERS TO SUIT THEIR FUNCTION. ALL FASTENERS SHALL BE CORROSION RESISTANT. MINIMUM EXTERIOR
WEATHERPROOF OUTLET BOX DEPTH SHALL BE 1-1/2".
C. JUNCTION AND PULL BOXES SHALL BE FABRICATED FROM CODE GAUGE GALVANIZED SHEET STEEL WITH SCREW ON
COVERS AND WELDED SEAMS.
7. IDENTIFICATION FOR ELECTRICAL SYSTEMS
7.01 NAMEPLATES AND IDENTIFICATION
A. PROVIDE IDENTIFYING NAMEPLATES FOR EACH PIECES OF ELECTRICAL EQUIPMENT INCLUDING PANELBOARDS,
DISCONNECT SWITCHES AND LIGHTING CONTRACTORS.
B. NAMEPLATES SHALL CONSIST OF SELF-ADHESIVE THERMAL TRANSFER LABELS. PANELBOARD NAMEPLATES SHALL
ALSO INDICATE THE EQUIPMENT VOLTAGE AND THE FEEDER SOURCE. DISCONNECT SWITCH AND ENCLOSED CIRCUIT
BREAKER NAMEPLATES SHALL INDICATE THE LOAD SERVED AND THE BRANCH CIRCUIT SOURCE.
C. PANELBOARD IDENTIFYING LETTERING SHALL BE 1" HIGH. ALL OTHER LETTERINGING, VOLTAGE, ETC. SHALL BE 1/4"
HIGH.
D. COMPLETE ALL PANELBOARD DIRECTORIES.
8. LIGHTING CONTROL DEVICES
8.01 DIGITAL TIME SWITCHES
A. DIGITAL TIME SWITCHES SHALL BE THE INTERMATIC INCORPORATED ET8215CPD82, 7-DAY ASTRONOMIC DIGITAL TIME
SWITCH OR AN EQUIVALENT PRODUCT BY TORK.
B. DIGITAL TIME SWITCHES SHALL BE PROGRAMMABLE FOR UP TO FIFTY-SIX (56) ON/OFF SET POINTS FOR INDIVIDUAL
PROGRAMS FOR EACH DAY OF THE WEEK WITH A MANUAL OVERRIDE UNTIL THE NEXT SCHEDULE ON/OFF EVENT.
C. DIGITAL TIME SWITCHES SHALL AUTOMATICALLY ADJUST FOR DAYLIGHT SAVINGS TIME AND HAVE THE ABILITY TO
DISABLE THIS FEATURE.
D. DIGITAL TIME SWITCHES SHALL LOSS OF POWER BACK-UP WITH PERMANENT SCHEDULE RETENTION IN THE MEMORY
MODULE.
E. DIGITAL TIME SWITCHES SHALL OPERATE AT 120-277 VOLTS, AND HAVE A MINIMUM NORMALLY OPEN SWITCH RATING OF
20 AMPERES FOR BALLAST.
F. DIGITAL TIME SWITCHES SHALL BE PROVIDED IN A NEMA 3R GRAY HIGH-IMPACT
UV RESISTANT POLYCARBONATE PLASTIC WITH CLEAR COVER ENCLOSURE.
8.02 PHOTOCELLS
A. PHOTOCELLS SHALL BE TORK 2100 SERIES OR EQUIVALENT, SPECIFICATION GRADE PHOTOCELL FOR CONDUIT
MOUNTING.
B. PHOTOCELLS SHALL BE WEATHERPROOF AND OPERATE AT 120 VOLTS.
9. PANELBOARDS
9.01 GENERAL
A. PANELBOARDS SHALL BE A PRODUCT OF EATON ELECTRICAL, INC. (CUTLER-HAMMER); GENERAL ELECTRIC COMPANY;
SCHNEIDER ELECTRIC (SQUARE-D); OR SIEMENS ENERGY AND AUTOMATION, INC.
B. PANELBOARDS SHALL COMPLY WITH NEMA PB1 AND BE LISTED AND LABEL AS COMPLYING WITH UL 50 AND UL 67.
C. PANELBOARD ASSEMBLIES SHALL BE FULLY RATED TO WITHSTAND MECHANICAL FORCES EXERTED DURING
SHORT-CIRCUIT CONDITIONS WHEN CONNECTED DIRECTLY TO A POWER SOURCE HAVING AVAILABLE FAULT CURRENT
AS INDICATED ON THE DRAWINGS.
D. PANELBOARD INDICATED ON THE DRAWINGS AS BEING USED FOR SERVICE ENTRANCE SHALL BE LISTED AND LABELED
FOR SUCH USE.
E. PANELBOARDS SHALL BE PROVIDED WITH COPPER BUS RATED FOR THE VOLTAGE AND AMPERE CAPACITY AS
SCHEDULED OR INDICTED ON THE DRAWINGS.
F. PANELBOARDS SHALL BE PROVIDED WITH A FULL (100%) RATED NEUTRAL BUS WHERE THE SCHEDULED OR INDICATED
SYSTEM VOLTAGE REQUIRE A NEUTRAL OR A 200% RATED NEUTRAL BUS WHERE AN OVER-SIZED NEUTRAL IS
SCHEDULED OR INDICATED.
G. PANELBOARDS SHALL BE EQUIPPED WITH AN EQUIPMENT GROUND BUS BONDED TO THE PANELBOARD ENCLOSURE.
H. WHERE PANELBOARDS ARE SCHEDULED TO HAVE AN ISOLATED GROUND BUS, THE ISOLATED GROUND BUS SHALL BE
FULLY (100%) RATED, INSULATED FROM THE ENCLOSURE AND IN ADDITION TO THE SYSTEM GROUND BUS.
I. TWO SECTION PANELBOARDS SHALL BE PROVIDED WITH FEED-THRU TYPE LUGS.
J. CIRCUIT BREAKERS SHALL BE MOLDED CASE, INVERSE TIME AND INSTANTANEOUS TRIP, QUICK MAKE - QUICK BREAK
TYPE. ALL CIRCUIT BREAKERS SHALL BE BOLT-ON STYLE. MULTIPLE POLE CIRCUIT BREAKERS SHALL OPEN ALL POLES
SIMULTANEOUSLY, TIED OR BAILED HANDLE BREAKERS WILL NOT BE PERMITTED. MINIMUM CIRCUIT BREAKER
INTERRUPTING RATING SHALL BE 10,000 RMS SYMMETRICAL AMPERES.
K. BACKBOXES SHALL BE CODE GAUGE STEEL COMPLETELY GALVANIZED WITH GUTTERS SIZED IN ACCORDANCE WITH
CODE REQUIREMENTS. TRIM AND DOORS SHALL BE FABRICATED FROM CODE GAUGE STEEL, WITH CONCEALED CAPTIVE
CLAMPING MECHANISM. TRIM SHALL HINGE AWAY FROM THE PANEL BACK BOX AND SHALL BE FLUSH OR SURFACE TYPE
AS SCHEDULED. DOORS COVERING CIRCUIT BREAKERS ARE TO BE FLUSH WITH CONCEALED HINGES WITH FLUSH
CATCH AND LOCK. PROVIDE TWO KEYS PER PANEL, AND ALL PANEL KEYS SHALL BE ALIKE.
L. A BLANK CIRCUIT DIRECTORY CARD SHALL BE PROVIDED WITH EACH PANEL MOUNTED BEHIND GLASS OR CLEAR
PLASTIC IN A FRAME ON THE REAR OF THE PANEL DOOR. CONTRACTOR SHALL RECORD ALL BRANCH CIRCUIT DATA FOR
EACH PANEL ON ITS CIRCUIT DIRECTORY CARD. CIRCUIT DIRECTORY CARD ENTRIES SHALL BE TYPEWRITTEN.
M. BALANCE PANELBOARD PHASE LOADING AS CLOSELY AS POSSIBLE.
10. WIRING DEVICES
10.01 SWITCHES
A. GENERAL USE SNAP SWITCH DEVICES SHALL BE HEAVY-DUTY SPECIFICATION GRADE AND SHALL COMPLY WITH NEMA
STANDARDS FOR GENERAL AND SPECIFIC PURPOSE WIRING DEVICES. THE DEVICE TOGGLE COLOR SHALL BE BLACK.
B. ACCEPTABLE MANUFACTURERS FOR WIRING DEVICES ARE HUBBELL, PASS AND SEYMOUR, BRYANT OR LEVITON.
10.02RECEPTACLES
A. RECEPTACLE DEVICES SHALL BE NEMA 5-20R, HEAVY-DUTY SPECIFICATION GRADE AND SHALL COMPLY WITH NEMA
STANDARDS FOR GENERAL AND SPECIFIC PURPOSE WIRING DEVICES. RECEPTACLE DEVICE COLOR SHALL BE BLACK.
B. DUPLEX GFCI RECEPTACLE DEVICES SHALL BE NEMA 5-20R FEED THROUGH TYPE, CAPABLE OF PROTECTING
DOWNSTREAM DEVICES. THE DEVICE SHALL BE EQUIPPED WITH SOLID STATE GROUND FAULT SENSING AND SIGNALING,
WITH 5 MILLIAMPERE GROUND FAULT TRIP LEVEL. THE DEVICE COLOR SHALL BE BLACK. THE WALL PLATES OF ALL
DUPLEX GFCI RECEPTACLE DEVICES AND OF ALL GFCI PROTECTED DOWNSTREAM RECEPTACLE DEVICES SHALL BE
INSCRIBED WITH 1/8" LETTERING “GFCI PROTECTED”.
C. SPECIAL USE RECEPTACLES SHALL HAVE A NEMA CONFIGURATION AS INDICTED ON THE DRAWINGS. TWIST-LOCK TYPE
SPECIAL USE RECEPTACLES SHALL BE SUITABLE FOR USE WITH HUBBELL WATERTIGHT SAFETY-SHROUD PLUG DEVICES.
D. ACCEPTABLE MANUFACTURERS FOR RECEPTACLE DEVICES ARE HUBBELL, PASS AND SEYMOUR, BRYANT OR LEVITON.
10.03 WALL PLATES
A. WALL PLATES IN UNFINISHED AREAS PLATES FOR SURFACE MOUNTED DEVICES SHALL BE GALVANIZED OR CADMIUM
PLATED STEEL. IN OUTDOORS AND WET AREAS PLATES SHALL BE CAST METAL WITH SPRING HINGED WATERPROOF
CAPS SUITABLY CONFIGURED FOR EACH APPLICATION. PLATES SHALL BE EQUIPPED WITH GASKETS AND CORROSION
RESISTANT FASTENERS. ALL OUTDOOR RECEPTACLE OUTLETS SHALL BE EQUIPPED WITH “WEATHERPROOF WHILE IN
USE” TYPE COVERS.
10.04POST MOUNTED OUTDOOR RECEPTACLE ASSEMBLIES
A. POST MOUNTED OUTDOOR RECEPTACLE ASSEMBLIES SHALL BE THE GPD19, 19-1/2 INCH GARD-N-POST ENCLOSURE BY
ARLINGTON INDUSTRIES, INC. OR EQUIVALENT PRODUCT.
B. RECEPTACLE ASSEMBLIES POST SHALL BE ONE PIECE CONSTRUCTED WITH HEAVY-DUTY, UV-RATED, BLACK PLASTIC.
THE COLORANT SHALL RUN THROUGHOUT THE PLASTIC POST TO ELIMINATE CHIPPING OR COLOR LOSS.
C. RECEPTACLE ASSEMBLIES SHALL BE LISTED FOR OUTDOOR USE AND MEET THE CODE REQUIREMENTS EXTRA-DUTY.
D. RECEPTACLES ASSEMBLIES SHALL BE PROVIDED WITH A NEMA 5-15R, GFCI TYPE, DUPLEX RECEPTACLE; WALL PLATE;
AND EXTRA-DUTY, WEATHERPROOF WHILE IN USE, CLEAR PLASTIC COVER.
E. RECEPTACLE ASSEMBLIES SHALL BE INSTALLED WITH THE BOTTOM OF THE RECEPTACLE DEVICE A MINIMUM OF
4-INCHES ABOVE THE FINISHED GRADE UNLESS OTHERWISE NOTED OR INDICTED.
11. ENCLOSED SWITCHES
11.01GENERAL
A. ENCLOSED SWITCHES SHALL BE A PRODUCT OF EATON ELECTRICAL, INC. (CUTLER-HAMMER); GENERAL ELECTRIC
COMPANY; SCHNEIDER ELECTRIC (SQUARE-D); OR SIEMENS ENERGY AND AUTOMATION, INC.
11.02NON-FUSIBLE SWITCHES
A. NON-FUSIBLE SWITCHES SHALL COMPLY WITH NEMA KS 1, AND LISTED AND LABELED IN ACCORDANCE WITH UL 98.
B. NON-FUSIBLE SWITCHES SHALL BE OF THE RATING INDICATED ON THE DRAWINGS.
C. NON-FUSIBLE SWITCHES SHALL BE 3 POLE UNLESS OTHERWISE NOTED ON THE DRAWINGS.
D. NON-FUSIBLE SWITCHES SHALL BE HORSEPOWER RATED, WITH LOCKABLE HANDLE, AND INTERLOCKED WITH COVER IN
CLOSED POSITION.
E. PROVIDE GENERAL DUTY, TYPE GD, SWITCHES FOR RATING OF 240 VAC, 200 A AND SMALLER:
F. PROVIDE HEAVY DUTY, TYPE HD, SWITCHES FOR RATINGS OF 240 VAC, LARGER THAT 200 A.
G. WHERE NEURAL CONDUCTOR ARE PRESENT WITHIN THE SWITCH ENCLOSURE, PROVIDE NEUTRAL KIT INTERNALLY
MOUNTED; INSULATED, CAPABLE OF BEING GROUNDED AND BONDED; AND LABELED FOR COPPER AND ALUMINUM
NEUTRAL CONDUCTORS.
H. PROVIDE SWITCHES WITH EQUIPMENT GROUND KIT INTERNALLY MOUNTED AND LABELED FOR COPPER AND ALUMINUM
GROUND CONDUCTORS.
I. PROVIDE SWITCHES WITH MECHANICAL LUGS SUITABLE FOR NUMBER, SIZE, TRIP RATINGS, AND CONDUCTOR MATERIAL
AS SPECIFIED OR INDICATED ON THE DRAWINGS.
11.03ENCLOSURES
A. SWITCHES AND CIRCUIT BREAKERS ENCLOSURES SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF NEMA AB 1,
NEMA KS 1, NEMA 250, AND UL 50 WITH ENVIRONMENTAL CONDITIONS AT INSTALLED LOCATION IN ACCORDANCE WITH
THE FOLLOW:
1. INDOOR, DRY AND CLEAN LOCATIONS: NEMA 250, TYPE 1
2. INDOOR LOCATIONS SUBJECT TO DUST, FALLING DIRT, AND DRIPPING NONCORROSIVE LIQUIDS: NEMA 250, TYPE 12
3. WET OR DAMP, INDOOR LOCATIONS: NEMA 250, TYPE 4
4. OUTDOOR LOCATIONS: NEMA 250, TYPE 3R
12. LIGHTING
12.01LIGHTING FIXTURES
A. PROVIDE LIGHTING FIXTURES IN ACCORDANCE WITH THE SCHEDULE AND DESCRIPTIONS ON THE DRAWINGS. LIGHTING
FIXTURE TYPES ARE IDENTIFIED BY SYMBOL ONLY, BY CAPITAL(S) LETTER ADJACENT TO THE LIGHTING FIXTURE
SYMBOL, OR BY NOTE.
B. LIGHTING FIXTURES SHALL BE UL LISTED AND LABELED.
C. FIXTURES SHALL BE LAMPED AFTER INSTALLATION WITH NEW LAMPS.
D. ALL FLUORESCENT LAMP BALLASTS SHALL BE HIGH POWER FACTOR, CBM LABELED, CLASS P. REFER TO SPECIFIC
BALLAST REQUIREMENTS SPECIFIED. ALL HID LAMP BALLASTS SHALL BE HIGH POWER FACTOR, MULTI-TAP TYPE, OF
RATINGS AS REQUIRED FOR THE PARTICULAR LAMP. HID BALLASTS SHALL BE ENCAPSULATED TYPE WHERE AVAILABLE
AND SHALL BE CAPABLE OF STARTING THEIR LAMPS IN AN AMBIENT TEMPERATURE OF -20 DEG. F.
ELECTRICAL SPECIFICATIONS
C:\U
sers
\jlan
g\O
neD
rive\
PH
E S
hare
d\Jo
bs\2
017\
1703
0\D
raw
ings
\170
30E
-GI.d
wg,
7/2
7/20
17 1
0:01
:09
AM
, Jos
eph
Lang
an, P
ine
Hill
Eng
inee
ring
LLC
ELECTRICAL SYMBOLS
CONTROL PANEL
ELECTRICAL WIRING OR EQUIPMENT
EXISTING ELECTRICAL WIRING OR EQUIPMENT TO REMAIN
EXISTING ELECTRICAL WIRING OR EQUIPMENT TO BE REMOVED
MOTOR (NUMBER INDICATES HORSEPOWER)
CP
PANELBOARD OR LOADCENTER (SURFACE MOUNTED)
ABBREVIATIONSA OR AMP. AMPERE
AWG AMERICAN WIRE GAUGE
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
EMT ELECTRIC METAL TUBING
EX. EXISTING
G OR GND. GROUND
HZ HERTZ
IC INTERRUPTING CURRENT
KAIC THOUSAND AMPERE INTERRUPTING CURRENT
KCMIL THOUSAND CIRCULAR MILLS
KVA KILOVOLT AMPERE
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
MC METAL CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUG ONLY
MIN. MINIMUM
MAX. MAXIMUM
N NEUTRAL
NIC NOT IN CONTRACT
# OR NO.NUMBER
Ø OR PH PHASE
PF POWER FACTOR
PNL PANELBOARD
P POLE
PVC POLYVINYL CHLORIDE CONDUIT
REC. RECEPTACLE
SCH. SCHEDULE
TYP. TYPICAL
V VOLTS
VA VOLT-AMPERES
W WATTS OR WIRE
WP WEATHERPROOF
LIGHTING SYMBOL NOTATIONSSTANDARD DESIGNATIONS FOR ALL LIGHTING FIXTURE SYMBOLS:
A1 FIXTURE TYPE DESIGNATION, SEE LIGHTING FIXTURE
SCHEDULE OR SPECIFICATIONS
2 CIRCUIT NUMBER, "2" INDICATES BRANCH CIRCUIT
b SWITCHED FIXTURE, "b" INDICATES SWITCH CONTROL
A1
b 2
SNAP SWITCH
FUSED DISCONNECT SWITCH (SWITCH RATING AMPERES/FUSERATING AMPERES)F
60/45
COMBINATION MAGNETIC MOTOR STARTER (NEMA SIZE/FUSE RATINGAMPERES - NUMBER OF POLES)
MAGNETIC MOTOR STARTER (NEMA SIZE - NUMBER OF POLES)
WIREWAY (SIZE AS NOTED)WW
FUSE (AMPERE RATING)
NORMALLY OPEN CONTACT
OVERLOAD RELAY
60
DISCONNECT SWITCH (SWITCH RATING AMPERES)60
WALL MOUNTED SINGLE FACED ILLUMINATED EXIT SIGN AND DUALHEAD EMERGENCY LIGHTING FIXTURE WITH SELF-CONTAINEDBATTERY, PROVIDE DIRECTIONAL ARROWS AS INDICATED ON THEPLANS
WALL MOUNTED 4' LINEAR FIXTURE
SUSPENDED OR PENDANT MOUNTED 4' STRIP FIXTURE
DUCT SMOKE DETECTOR AND SAMPLING TUBESSD
PLYWOOD BACKBOARD
FIRE ALARM CONTROL PANELFACP
VARIABLE FREQUENCY DRIVEVFD
NON-FUSED DISCONNECT SWITCH (SWITCH RATING AMPERES/FUSERATING AMPERES)
60
115417
191 Mill Lane
Mountainside, NJ 07092
t. 908.232.2860
f. 908.232.2845
Drawn by:
Checked by:
Revision
Number
Revision
Description
Revision
Date
Monmouth County
Parks System
F O R T M O N M O U T H
RECREATION CENTER
HVAC IMPROVEMENTS
2566 Guam Lane
Tinton Falls, NJ 07724
JULY 27, 2017
THE MUSIAL GROUP ARCHITECTURE
OR
IG
IN
AL
IF
IT
IS
R
ED
IT
IS
A
N O
RIG
IN
AL
These drawings may not be reproduced by any means without the express
written consent of the architect.
EACH CONTRACTOR SHALL THOROUGHLY EXAMINE AND BECOME FAMILIAR WITH
ALL CONTRACT DOCUMENTS FOR THE PROJECT AND NOT LIMIT THEIR WORK TO
DRAWINGS REFERENCED FOR INDIVIDUAL TRADES.
Submission or distribution of documents to meet official regulatory
requirements or for similar purposes in connection with the Project is
not to be construed as publication in derogation of the Architect's
reserved rights.
The Drawings, Specifications and other documents prepared by The
Architect for this project are instruments of the Architect's service for use
solely with respect to this project and the Architect shall be deemed the
author of statutory and other reserved rights, including copyright. The
owner shall be permitted to retain copies, including reproducible copies,
of the Architect's drawings. Specifications or other documents shall not
be used by the Owner or others on other projects, for additions to this
Project or for completion of this Project by others, unless the Architect
agrees in writing and with appropriate compensation to the Architect.
Noel S. Musial, A.I.A.
N.Y. 11339N.J. A105415
PA. B 6580CT. 09009
BUSINESS PROPRIETARY INFORMATION
© Copyright 2017
Seal:State of New JerseyCertificate of Authorization
No: 24GA28143600
Matthew C. ZabroskyProfessional Engineer
NJ LicenseNo: 24GE04673800
PINE HILL ENGINEERING LLC99 Baird Road, Millstone Township, NJ 08535
Telephone: (732) 851-4088Email: [email protected]
www.pinehilleng.com
Consultant:
NONE
JL
MZ
ELECTRICAL
SYMBOLS AND
ABBREVIATIONS
E002
C:\U
sers
\jlan
g\O
neD
rive\
PH
E S
hare
d\Jo
bs\2
017\
1703
0\D
raw
ings
\170
30E
-GI.d
wg,
7/2
7/20
17 1
0:01
:11
AM
, Jos
eph
Lang
an, P
ine
Hill
Eng
inee
ring
LLC
FACPWW WW WW
F F F F
CP
EX. DS-AHU-1
EX. MS-P2EX. MS-P1
EX. DS-AHU-2
EX. DS-P2
EX. DS-P1
EX. PP
VFD
VFD-AHU-1
SD
AHU-1(RETURN)
A
B
A
A
A
B
VFD
VFD-AHU-2
RF-2
RF-1
SD
AHU-2(RETURN)
AHU-2
AHU-1
PP#(20,22,24)
PP#(1,3,5)
TS
EX
CS-CHWP-1
CHWP-1
SD
RF-2(RETURN)
PP#(14,16,18)
PP#(38,40,42)
PP#(13,15,17)
SD
RF-1(RETURN)
VFD
VFD
VFD-RF1DS-RF-1
VFD-RF2
DS-RF-2
FC-2
FC-7
FC-1
FC-3
FC-4
FC-5
FC-6
EX. P
GENERAL NOTES:
115417
191 Mill Lane
Mountainside, NJ 07092
t. 908.232.2860
f. 908.232.2845
Drawn by:
Checked by:
Revision
Number
Revision
Description
Revision
Date
Monmouth County
Parks System
F O R T M O N M O U T H
RECREATION CENTER
HVAC IMPROVEMENTS
2566 Guam Lane
Tinton Falls, NJ 07724
JULY 27, 2017
THE MUSIAL GROUP ARCHITECTURE
OR
IG
IN
AL
IF
IT
IS
R
ED
IT
IS
A
N O
RIG
IN
AL
These drawings may not be reproduced by any means without the express
written consent of the architect.
EACH CONTRACTOR SHALL THOROUGHLY EXAMINE AND BECOME FAMILIAR WITH
ALL CONTRACT DOCUMENTS FOR THE PROJECT AND NOT LIMIT THEIR WORK TO
DRAWINGS REFERENCED FOR INDIVIDUAL TRADES.
Submission or distribution of documents to meet official regulatory
requirements or for similar purposes in connection with the Project is
not to be construed as publication in derogation of the Architect's
reserved rights.
The Drawings, Specifications and other documents prepared by The
Architect for this project are instruments of the Architect's service for use
solely with respect to this project and the Architect shall be deemed the
author of statutory and other reserved rights, including copyright. The
owner shall be permitted to retain copies, including reproducible copies,
of the Architect's drawings. Specifications or other documents shall not
be used by the Owner or others on other projects, for additions to this
Project or for completion of this Project by others, unless the Architect
agrees in writing and with appropriate compensation to the Architect.
Noel S. Musial, A.I.A.
N.Y. 11339N.J. A105415
PA. B 6580CT. 09009
BUSINESS PROPRIETARY INFORMATION
© Copyright 2017
Seal:State of New JerseyCertificate of Authorization
No: 24GA28143600
Matthew C. ZabroskyProfessional Engineer
NJ LicenseNo: 24GE04673800
PINE HILL ENGINEERING LLC99 Baird Road, Millstone Township, NJ 08535
Telephone: (732) 851-4088Email: [email protected]
www.pinehilleng.com
Consultant:
AS NOTED
JL
MZ
ELECTRICAL
PARTIAL PLANS
E101
1
E101
MECHANICAL ROOM 1 - ENLARGED PLAN
SCALE: 1/4" = 1'-0"
2
E101
PARTIAL PLAN
SCALE: 1/8" = 1'-0"
1. SEE DIAGRAM 1/E601 FOR CIRCUITING OF THE NEW ANDREPLACEMENT MECHANICAL EQUIPMENT WITHIN MECHANICALROOM 1.
2. ALL FIRE ALARM SYSTEM WORK SHALL BE PROVIDED BY THECONTRACTOR UTILIZING THE SERVICES AND PRODUCTS OF THEOWNER'S CURRENT FIRE ALARM SYSTEM MAINTENANCECONTRACTOR FOR ALL MODIFICATIONS MADE TO THE EXISTINGFIRE ALARM SYSTEM AS PART OF THIS CONTRACT. THECONTACT INFORMATION FOR THE OWNER'S CURRENT FIREALARM SYSTEM MAINTENANCE CONTRACTOR IS AS FOLLOWS:
COMPLETE SECURITY SYSTEMS, INC.94 VANDERBURG ROADMARLBORO, NJ 07746P: 800-452-3773W: WWW.COMPLETESECURITYSYSTEMS.COM
VARIABLE FREQUENCY DRIVE (VFD) FURNISHED AS PART OFTHE AIR HANDLING UNIT PACKAGE.
KEYED NOTES:
INSTALL THE VARIABLE FREQUENCY DRIVE (VFD) FURNISHEDWITH THE RETURN FAN UNIT.
CONNECT THE NEW DUCT SMOKE DETECTORS TO THEEXISTING FIRE ALARM SYSTEM ZONE THAT SERVED THEREMOVED DUCT SMOKE DETECTORS.
PROVIDE REPLACEMENT DEVICE TO CONTROL THE NEWLIGHTING FIXTURES PROVIDED WITHIN THE MECHANICALROOM.
COORDINATE THE LOCATIONS OF THE NEW LIGHTINGFIXTURES WITH THE EXISTING FIELD CONDITION AND NEWCONSTRUCTION WITHIN THE MECHANICAL ROOM. CIRCUITTHE NEW LIGHTING FIXTURES TO THE EXISTING BRANCHCIRCUIT THAT SERVE THE LIGHTING FIXTURES THAT WEREREMOVED FROM THE MECHANICAL ROOM VIA THE NEWREPLACEMENT SWITCH DEVICE. EXISTING BRANCH CIRCUITWIRING MAY BE RE-USED WHERE PRACTICAL.
CIRCUIT THE NEW COMBINATION ILLUMINATED EXIT SIGN ANDEMERGENCY LIGHTING UNIT TO THE EXISTING BRANCHCIRCUIT THAT SERVES THE LIGHTING FIXTURES WITHIN THEMECHANICAL ROOM AHEAD OF ALL SWITCHING.
CIRCUIT THE NEW FAN COIL UNIT TO THE EXISTING BRANCHCIRCUIT THAT SERVED THE REMOVED UNIT. EXTEND AND/ORMODIFYING THE EXISTING BRANCH CIRCUIT WIRING ASREQUIRED.
E101
1
(TYP. OF 2)
(TYP. OF 4)
C:\U
sers
\jlan
g\O
neD
rive\
PH
E S
hare
d\Jo
bs\2
017\
1703
0\D
raw
ings
\170
30E
-FP
.dw
g, 7
/27/
2017
10:
01:2
1 A
M, J
osep
h La
ngan
, Pin
e H
ill E
ngin
eerin
g LL
C
115417
191 Mill Lane
Mountainside, NJ 07092
t. 908.232.2860
f. 908.232.2845
Drawn by:
Checked by:
Revision
Number
Revision
Description
Revision
Date
Monmouth County
Parks System
F O R T M O N M O U T H
RECREATION CENTER
HVAC IMPROVEMENTS
2566 Guam Lane
Tinton Falls, NJ 07724
JULY 27, 2017
THE MUSIAL GROUP ARCHITECTURE
OR
IG
IN
AL
IF
IT
IS
R
ED
IT
IS
A
N O
RIG
IN
AL
These drawings may not be reproduced by any means without the express
written consent of the architect.
EACH CONTRACTOR SHALL THOROUGHLY EXAMINE AND BECOME FAMILIAR WITH
ALL CONTRACT DOCUMENTS FOR THE PROJECT AND NOT LIMIT THEIR WORK TO
DRAWINGS REFERENCED FOR INDIVIDUAL TRADES.
Submission or distribution of documents to meet official regulatory
requirements or for similar purposes in connection with the Project is
not to be construed as publication in derogation of the Architect's
reserved rights.
The Drawings, Specifications and other documents prepared by The
Architect for this project are instruments of the Architect's service for use
solely with respect to this project and the Architect shall be deemed the
author of statutory and other reserved rights, including copyright. The
owner shall be permitted to retain copies, including reproducible copies,
of the Architect's drawings. Specifications or other documents shall not
be used by the Owner or others on other projects, for additions to this
Project or for completion of this Project by others, unless the Architect
agrees in writing and with appropriate compensation to the Architect.
Noel S. Musial, A.I.A.
N.Y. 11339N.J. A105415
PA. B 6580CT. 09009
BUSINESS PROPRIETARY INFORMATION
© Copyright 2017
Seal:State of New JerseyCertificate of Authorization
No: 24GA28143600
Matthew C. ZabroskyProfessional Engineer
NJ LicenseNo: 24GE04673800
PINE HILL ENGINEERING LLC99 Baird Road, Millstone Township, NJ 08535
Telephone: (732) 851-4088Email: [email protected]
www.pinehilleng.com
Consultant:
KEYED NOTES:
NONE
JL
MZ
ELECTRICAL
DIAGRAMS AND
SCHEDULES
E601
1
E601
PARTIAL ONE-LINE DIAGRAM
DIAGRAMMATIC
VARIABLE FREQUENCY DRIVE (VFD) FURNISHED AS PART OFTHE AIR HANDLING UNIT PACKAGE.
INSTALL THE VARIABLE FREQUENCY DRIVE (VFD) FURNISHEDWITH THE RETURN FAN UNIT.
PROVIDE NEW FUSES FOR THE EXISTING FUSED DISCONNECTSWITCH AS INDICATED.
EXISTINGPANEL
PP
FROMEX. MDP
EXISTING
60
45
VFD
FANMOTOR
3#8, #6G,3/4"C
3#8, #6G,3/4"C
AHU-1
VFD-AHU-1
EX. AHU-1
EX. MS-AHU-1
EX. DS-AHU-1
EXISTING
60
30
VFD
FANMOTOR
3#10, #10G,3/4"C
3#10, #10G,3/4"C
AHU-2
VFD-AHU-2
EX. AHU-2
EX. MS-AHU-2
EX. DS-AHU-2
EXISTING
VFD
FANMOTOR
3#8, #10G,3/4"C
RF-1
VFD-RF-1
60
DS-RF-1
3#8, #10G,3/4"C
PP#(13,15,17)
EX. DS-RF-1
EX. MS-RF-1
EX. RF-1
VFD
FANMOTOR
3#12, #12G,3/4"C
RF-2
VFD-RF-2
30
DS-RF-2
3#12, #12G,3/4"C
PP#(14,16,18)
EX. DS-RF-2
EX. MS-RF-2
EX. RF-2
CHWP-1
3#12, #12G, 3/4"C
30
15
CS-CHWP-1
PP#(38,40,42)
SIZE 0
REPLACE THE EXISTING CIRCUIT BREAKER WITH THE CIRCUITBREAKER INDICATED.
PROVIDE INDICATED CIRCUIT BREAKER WITHIN THE EXISTINGSPACE.