BNC PLENUM FAN with Backward Curved Wheels
BNC Series
PLENUM FAN with Backward Curved Wheels
Kruger Ventilation Industries Asia Co Ltd certifies that the BNC Series shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.
1
BNC Series
BNC Series Plenum Fans – Backward curved wheels
Kruger Plenum Fans are designed for air handling application where the fan wheel operates without housing, inside a plenum. This results in saving of space normally occupied by the fan housing, transition and diffusers. The fan wheel pressurizes the entire plenum in which the fan is installed. This allows air ducts to be directly connected from any direction to the plenum. The compact size of the plenum fan makes it an excellent selection for retrofit and replacement application and for variable air volume systems. There are three types of BNC Series, i.e. BNC-R (regular type), BNC-P (high pressure ratio type), BNC-Q (high volume ratio type).
NOMENCLATURE MODEL:BNC-R 450 / D I
Fan operation class -- I , II & III
Drive mode --'D' - Direct Driven 'B' - Belt Driven Fan model Fan type -- P, R, Q
TYPE / OPERATING LIMIT
Direct Driven 'D' This type is supplied with no belts nor pulley and therefore minimal maintenance is required. It is a compact, space saving design with motor directly connected to wheel. This construction is mainly for cleanroom, with or without VFD, since there is an absence of belt residue which may contaminate the airstreams.
Fan Size : 315 to 1,800 Volume : 3,000 to 300,000 m3/h Total Pressure : up to 4,500 Pa
Belt Driven 'B' No bearings in the fan inlet to affect performance. Separate base for motor mounting is required.
Fan Size : 315 to 1,800 Volume : 3,000 to 300,000 m3/h
Total Pressure : up to 4,500 Pa Drawings and dimension data of belt driven are available upon request.
TECHNICAL SPECIFICATION Wheel
The wheels of BNC series have backward curved blades manufactured in mild steel with polyester powder coating finish. Shaft
Shafts are manufactured from C45 carbon steel using an automatic process for positioning and cutting of the keyways. All dimensional tolerances of the shaft are fully checked to ensure a precision fit. All shafts are then coated with an anti-corrosion varnish after assembly.
Each fan type has its maximum operating speed and power due to its mechanical design. The operating limit of BNC series is set according to the requirement of class I, II and III limit as defined in AMCA standard 99. The BNC series is available in Direct Driven and Belt Driven, Type D, B as follow:
2
BNC Series
Bearing
Bearings used are either deep groove ball bearings with an adapter sleeve, or spherical roller bearings sealed at both sides for different duty application. The bearings are lubricated for life and maintenance-free. If re-lubrication is necessary, it is recommended to use lithium base grease suitable for all temperatures within the operational limits.
Balancing Quality
All wheels are statically and dynamically balanced to ISO1940 and AMCA 204 – G2.5 standard.
All fans after assembly are trim-balanced to ISO1940 and AMCA 204 - G2.5 standard.
Other standard rather than G2.5 is available upon request.
ACCESSORIES Inlet Guard
Inlet guards may be a requirement in some industrial safety regulations. These are available upon request.
Motor Selection
The power curves shown on each performance graph represents the absorbed power at the shaft of the fan measured in kW.
To determine the power of the motor to be installed, a correction factor should be applied to compensate for the transmission loss.
For conversion to horsepower (HP), use multiplying factor 1.34.
3
6
Motor power output (kW)
Cor
rect
ion
Fact
or, %
mot
or p
ower
out
put
8
0.45
1.5
1
0.2
0.3
2
3
4
6
0.6
0.75 1.5
2.2 3
4.5
40
10
15
20
30
60
80100
7.5 15
22.5 30 45 7560 150
225
300
450
2 Pole
4 & 6 Pole
BNC Series
PERFORMANCE
The performance data shown on each diagram is derived from tests conducted in accordance with AMCA Standard 210 Fig 15 Installation type A (free inlet and free outlet condition). Ratings refer to standard air density with the total pressure as a function of the air volume, using logarithmic scale.
It is essential that, the same installation type and test standards are used at all times, when comparing fan performance. According to ISO 12759/AMCA 205, BNC series can be classify as FEG 80 based on fan peak efficiency. The following is the explanation of FEG classification:
1. Fan size is the impeller diameter in mm. 2. The fan peak efficiency shall be calculated from the fan (total)
pressure. 3. If this method is used for a direct driven fan, the fan efficiency is the
impeller efficiency. 4. The FEG label for a given fan size is assigned when the fan peak
efficiency is equal or lower than the efficiency at the grade upper limit and higher than efficiency at the grade upper limit of the next lower grade for the fan size.
5. For any fan sizes larger than 1016 mm, the values of the grade upper limits are the same as for a size of 1016 mm.
6. No labels are considered for the fans with the fan peak total efficiency below FEG50.
7. The values of efficiencies are calculated for fan sizes in the preferred R40 Series.
8. Not all fan sizes in preferred numbers shown.
Fan Efficiency Grades (FEG) for Fans without Drives (SI) – ISO 12759/AMCA 205
4
BNC Series
NOISE
The noise levels shown on each diagram refer to the sound power, "A-weighted" values and the data are obtained at the outlet side from tests conducted in accordance to AMCA Standard 300. The noise levels are determined as follow: n Sound power level - ("A" scale): Lw (A) as catalogue n Octave band spectrum: Lw = Lw(A) + Lw rel. dB [refer to Kruger for more details]
n Sound pressure level:
a) free field Lp(A) = Lw(A) - (20log10d) -11
b) room conditions Lp(A) = Lw(A) - (20log10d) -7
where d = distance of fan (m)
5
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 4.6 10 20
M.RPM 3000 3890 4900
γ = 1.2 kg/m3
BNC-R 400
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 Q [m3/s]
1000 5000 100002000 3000 5000020000 30000 Q [m3/h]
1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
0.5 1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
7000
Pt [Pa]
kW
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
N [rpm]
1150
1300
1450
1600
1800
2000
2200
2500
2800
3000
3250
3550
3890 4150
4500
4900
η [%] 40 52 65 72 61 38 18
75
8085
90
95
100
105
110
115
Lw (A) [dB(A)]
Air Volume
Outlet Velocity
Dynamic Pressure
Total Pressure
Fan Speed
Absorbed Power
Total Efciency
Sound Power Level
3Q=5000m /h
V=8.8m/s
Pd=48Pa
Pt=900Pa
N=2200rpm
W=1.7kW
=72%
Lw(A)=92.5dB(A)
5000
8.8
48
1.7
92.5
900
FEG 80
6
BNC Series
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
7
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 2.2 5 9.7
M.RPM 3500 4600 5800
γ = 1.2 kg/m3
BNC-P 315
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]
500 1000 5000 100002000 3000 20000 30000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 10000 Pd [Pa]
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
0.16
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
N [rpm]
1450
1600
1750
1900
2100
2300
2450 2600
3000
3200
3500
3900
4250
4600
5000
5400
5800
η [%] 40 50 61 68 61 44 25
75
80
85
90
95
100
105
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
8
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 2.4 5.2 10.4
M.RPM 3550 4600 5800
γ = 1.2 kg/m3
BNC-R 315
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]
500 1000 5000 100002000 3000 20000 30000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
0.16
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
N [rpm]
1450
1600
1750
1900
2100
2300
2500
2850
3150
3550
4000
4300
4600
4900 5200 5500 5800
η [%] 40 49 60 68 60 42 24
75
80
85
90
95
100
105
110
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 3 6.5 13
M.RPM 3700 4800 6100
γ = 1.2 kg/m3
BNC-Q 315
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]
500 1000 5000 100002000 3000 5000020000 30000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
0.18
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
N [rpm]
1450
1600
1750
1900
2100
2300
2550
2850
3300
3700
4000
4300 4550 4800
5300
5700
6100
η [%] 39 48 60 67 58 39 22
80
85
90
95
100
105
110
Lw (A) [dB(A)]
FEG 80
9
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
10
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 3 6 11.5
M.RPM 3100 4000 5000
γ = 1.2 kg/m3
BNC-P 355
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]
500 1000 5000 100002000 3000 20000 30000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 Pd [Pa]
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
N [rpm]
1150
1300
1450
1600
1800
2000
2200 2200
2500
2800
3100
3350
3700
4000
4300
4650
5000
η [%] 40 51 62 69 61 45 26
75
80
85
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
11
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 3 6.8 13.3
M.RPM 3180 4150 5200
γ = 1.2 kg/m3
BNC-R 355
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]
1000 5000 100002000 3000 5000020000 30000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
0.14
0.2
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
N [rpm]
1150
1300
1450
1600
1800
2000
2200
2500
2800
3180
3450
3750
4150
4500 4800
5200
η [%] 41 52 64 70 61 42 22
70
75
80
85
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 4 8.6 17
M.RPM 3370 4370 5500
γ = 1.2 kg/m3
BNC-Q 355
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]
500 1000 5000 100002000 3000 5000020000 30000 Q [m3/h]
1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
0.5 1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
0.16
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
N [rpm]
1150
1300
1450
1600
1800
2000
2200
2500
2800
3180 3370
3800
4100 4370
4900
5500
η [%] 37 47 60 69 57 37 19
70
7580
85
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
12
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
13
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 3.3 7.2 14
M.RPM 2750 3550 4450
γ = 1.2 kg/m3
BNC-P 400
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]
1000 5000 100002000 3000 5000020000 30000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 Pd [Pa]
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
N [rpm]
1150
1300
1450
1600
1800
2000
2200
2500
2800
3000
3250
3550
3890
4150
4450
η [%] 40 51 64 72 64 46 27
75
80
85
90
95
100
105
110
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
14
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 4.6 10 20
M.RPM 3000 3890 4900
γ = 1.2 kg/m3
BNC-R 400
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 Q [m3/s]
1000 5000 100002000 3000 5000020000 30000 Q [m3/h]
1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
0.5 1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
7000
Pt [Pa]
kW
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
N [rpm]
1150
1300
1450
1600
1800
2000
2200
2500
2800
3000
3250
3550
3890 4150
4500
4900
η [%] 40 52 65 72 61 38 18
75
8085
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 5 11 22
M.RPM 2900 3750 4750
γ = 1.2 kg/m3
BNC-Q 400
.3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 Q [m3/s]
1000 5000 100002000 3000 5000020000 30000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
N [rpm]
1150
1300
1450
1600
1800
2000
2200
2500
2900
3200
3500
3750
4100
4400
4750
η [%] 43 53 66 72 59 37 20
75
80
85
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
15
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
16
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 4.3 9.5 19
M.RPM 2450 3170 4000
γ = 1.2 kg/m3
BNC-P 450
.3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]
1000 5000 100002000 3000 5000020000 30000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 Pd [Pa]
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
N [rpm]
950
1100
1250
1400
1600
1750
1950
2200
2450
2750
3170
3500
3750
4000
η [%] 48 58 70 77 69 54 39
70
75
80
85
90
95
100
105
110
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
17
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 4.6 10.6 21.5
M.RPM 2470 3200 4050
γ = 1.2 kg/m3
BNC-R 450
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30 Q [m3/s]
1000 5000 100002000 3000 50000 10000020000 30000 Q [m3/h]
1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
7000
Pt [Pa]
kW
0.25
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
15
N [rpm]
950
1100
1250
1400
1600
1750
1950
2200
2470
2750
3200
3500
3800 4050
η [%] 40 51 64 74 64 41 23
75
80
85
90
95
100
105
110
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 6.1 13.6 27.5
M.RPM 2600 3400 4300
γ = 1.2 kg/m3
BNC-Q 450
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30 Q [m3/s]
1000 5000 100002000 3000 50000 10000020000 30000 Q [m3/h]
1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
0.5 1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
7000
Pt [Pa]
kW
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
15 18.5
N [rpm]
950
1100
1250
1450
1600
1750
1950
2200
2400
2600
2850
3100
3400
3700
4000
4300
η [%] 38 49 63 73 60 36 18
80
85
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
18
. - Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
19
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 5.3 11.5 23.2
M.RPM 2200 2850 3600
γ = 1.2 kg/m3
BNC-P 500
.3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 Q [m3/s]
1000 5000 100002000 3000 5000020000 30000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
15
N [rpm]
800
900
1000
1100
1250
1450
1600
1800
2000
2200
2400
2600
2850
3150
3400 3600
η [%] 41 52 66 74 61 41 25
70
75
80
85
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
11
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
20
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 6 13 27
M.RPM 2220 2880 3650
γ = 1.2 kg/m3
BNC-R 500
.3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30 Q [m3/s]
1000 5000 100002000 3000 50000 10000020000 30000 Q [m3/h]
1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
7000
Pt [Pa]
kW
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
15 18.5
N [rpm]
800
900
1000
1100
1250
1450
1600
1800
2000
2150
2400
2600
2880
3150
3400
3650
η [%] 40 51 64 74 64 41 23
75
80
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 7.6 16.7 33.5
M.RPM 2350 3050 3850
γ = 1.2 kg/m3
BNC-Q 500
.3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30 40 Q [m3/s]
1000 5000 100002000 3000 50000 10000020000 30000 Q [m3/h]
.8 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
0.5 1 5 10 50 100 500 1000 500010000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
7000
Pt [Pa]
kW
0.28
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
15
18.5 22 25
N [rpm]
800
900
1000
1100
1250
1450
1600
1800
2000
2150
2350
2600
2850 3050
3400
3850
η [%] 38 49 63 73 60 36 18
85
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
21
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
22
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 6.4 13.4 26.7
M.RPM 1950 2500 3150
γ = 1.2 kg/m3
BNC-P 560
.4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30 Q [m3/s]
5000 100002000 3000 50000 10000020000 30000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 Pd [Pa]
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
0.33
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
15
18.5
N [rpm]
800
900
1000
1100
1250
1450
1700
1950
2250
2500
2900
3150
η [%] 42 52 64 74 66 48 26
80
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
23
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 7.1 15.6 31.5
M.RPM 1950 2540 3200
γ = 1.2 kg/m3
BNC-R 560
.4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30 40 Q [m3/s]
5000 100002000 3000 50000 10000020000 30000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
7000
Pt [Pa]
kW
0.33
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
15
18.5
22
N [rpm]
700
800
900
1000
1100
1250
1450
1700
1950
2250
2540
2900
3200
η [%] 45 56 68 75 64 45 25
75
80
85
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
24
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 9 20.5 40.8
M.RPM 2050 2700 3400
BNC-Q 560
.4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30 40 50 Q [m3/s]
5000 100002000 3000 50000 10000020000 30000 Q [m3/h]
1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
0.5 1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
7000
Pt [Pa]
kW
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
15
18.5 22 25
N [rpm]
700
800
900
1000
1100
1250
1450
1750
2050
2250
2500
2700
3000
3400
η [%] 42 53 66 74 61 40 20
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
γ = 1.2 kg/m3
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
25
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 7.4 16 33
M.RPM 1700 2200 2800
γ = 1.2 kg/m3
BNC-P 630
.6 .8 1 2 3 4 5 6 8 10 20 30 40 Q [m3/s]
5000 100003000 50000 10000020000 30000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 Pd [Pa]
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
N [rpm]
700
800
950
1150
1250
1450
1700
1900
2050
2200
2500
2800
η [%] 50 60 70 75 66 50 30
85
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
15
18.5
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
26
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 9 19 38
M.RPM 1720 2230 2800
γ = 1.2 kg/m3
BNC-R 630
.5 .6 .8 1 2 3 4 5 6 8 10 20 30 40 50 Q [m3/s]
5000 100002000 3000 50000 10000020000 30000 200000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
7000
Pt [Pa]
kW
0.38
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
15
18.5 22
N [rpm]
600
700
800
950
1150
1250
1450
1720
1900
2050
2230
2500
2800
η [%] 47 57 68 75 67 46 27
80
85
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 11 24 50
M.RPM 1800 2350 3000
γ = 1.2 kg/m3
BNC-Q 630
.5 .6 .8 1 2 3 4 5 6 8 10 20 30 40 50 60 Q [m3/s]
5000 100002000 3000 50000 10000020000 30000 200000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
15
18.5 22 25 30
N [rpm]
700
800
950
1150
1300
1450
1600
1800
2000
2150
2350
2700
3000
η [%] 42 53 67 75 62 41 22
80
85
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
27
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
28
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 9.7 21.3 42.3
M.RPM 1520 1980 2490
γ = 1.2 kg/m3
BNC-P 710
.8 1 2 3 4 5 6 8 10 20 30 40 50 Q [m3/s]
5000 100003000 50000 10000020000 30000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 Pd [Pa]
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
15
18.5 22
N [rpm]
600
650
700
750
850
950
1150
1350
1520
1750
1980
2250
2490
η [%] 50 60 70 75 66 50 30
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
29
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 11 25 49
M.RPM 1530 1990 2500
γ = 1.2 kg/m3
BNC-R 710
.6 .8 1 2 3 4 5 6 8 10 20 30 40 50 60 Q [m3/s]
5000 100002000 3000 50000 10000020000 30000 200000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
7000
Pt [Pa]
kW
0.37
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
15
18.5 22
30
N [rpm]
500
600
700
800
950
1150
1300
1450 1530
1750
1990
2150 2300
2500
η [%] 47 57 68 75 67 46 27
80
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 13.8 31.2 62.7
M.RPM 1600 2100 2650
γ = 1.2 kg/m3
BNC-Q 710
.6 .8 1 2 3 4 5 6 8 10 20 30 40 50 60 Q [m3/s]
5000 100002000 3000 50000 10000020000 30000 200000 Q [m3/h]
11 2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
15
18.5 22 25 30
37
N [rpm]
600
700
800
950
1150
1300
1450
1600
1750
1900
2100
2350
2650
η [%] 42 53 67 75 62 41 22
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
30
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
31
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 12.3 26.7 53
M.RPM 1350 1750 2200
γ = 1.2 kg/m3
BNC-P 800
1 2 3 4 5 6 8 10 20 30 40 50 60 Q [m3/s]
5000 10000 50000 10000020000 30000 200000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11 N [rpm]
500
600
700
800
950
1150
1250
1350
1450
1600
1750
1950
2220
η [%] 50 60 70 75 66 50 30
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
1518.5
22 25
30
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
32
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 14.6 31.5 62
M.RPM 1370 1770 2220
γ = 1.2 kg/m3
BNC-R 800
.8 1 2 3 4 5 6 8 10 20 30 40 50 60 80 Q [m3/s]
5000 100003000 50000 10000020000 30000 200000300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
7000
Pt [Pa]
kW
0.55
0.75
1.1
1.5
2
3
4
5.5
7.5
11
15
18.5 22 25 30
37
N [rpm]
500
600
700
800
950
1150
1250
1370 1450
1600
1770
1950
2220
η [%] 47 57 68 75 67 46 27
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 18.7 38.8 79.4
M.RPM 1450 1850 2350
γ = 1.2 kg/m3
BNC-Q 800
.8 1 2 3 4 5 6 8 10 20 30 40 50 60 80 Q [m3/s]
5000 100003000 50000 10000020000 30000 200000300000 Q [m3/h]
1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
0.5 1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
0.75
1.1
1.5
2
3
4
5.5
7.5
11
15
18.5 22 25 30
37 45
55
N [rpm]
500
600
700
800
950
1150
1300
1450
1650
1850
2100
2350
η [%] 42 53 67 75 62 41 22
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
33
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
34
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 15.3 33.5 67.4
M.RPM 1170 1520 1920
γ = 1.2 kg/m3
BNC-P 900
1 2 3 4 5 6 8 10 20 30 40 50 60 80 Q [m3/s]
5000 10000 50000 10000020000 30000 200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 Pd [Pa]
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
1.1
1.5
2
3
4
5.5
7.5
11
15
19 22
N [rpm]
500
600
700
800
950
1170
1300
1450 1520
1750
1920
η [%] 45 56 67 75 69 52 31
80
85
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
30
37
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
35
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 18 39 78
M.RPM 1210 1570 1980
γ = 1.2 kg/m3
BNC-R 900
2 3 4 5 6 8 10 20 30 40 50 60 80 100 Q [m3/s]
5000 10000 50000 10000020000 30000 200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
1.1
1.5
2
3
4
5.5
7.5
11
15
19 22
30
37 45
55
N [rpm]
500
600
700
800
950
1100
1210
1450
1570
1750
1980
η [%] 46 56 67 76 66 47 29
85
90
95
100
105
110
115
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 22.2 46.5 97.7
M.RPM 1250 1600 2050
γ = 1.2 kg/m3
BNC-Q 900
2 3 4 5 6 8 10 20 30 40 50 60 80 100 Q [m3/s]
5000 10000 50000 10000020000 30000 200000300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
1.1
1.5
2
3
4
5.5
7.5
11
15
18.5 22 25 30
37 45 55
N [rpm]
500
600
700
800
950
1100
1250
1450
1600
1750
2050
η [%] 44 54 66 75 63 42 23
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
36
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
37
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 19.3 42.4 86.5
M.RPM 1060 1380 1750
γ = 1.2 kg/m3
BNC-P 1000
2 3 4 5 6 8 10 20 30 40 50 60 80 100 Q [m3/s]
5000 10000 50000 10000020000 30000 200000300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 Pd [Pa]
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
1.1
1.5
2
3
4
5.5
7.5
11
15
18.5 22
N [rpm]
400
450
500
550
600
650
700
750
850
950
1060
1250
1380
1600
1750
η [%] 45 56 67 75 69 52 31
75
80
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
25 30
37
45
55
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
38
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 21.4 47 94
M.RPM 1080 1400 1770
γ = 1.2 kg/m3
BNC-R 1000
2 3 4 5 6 8 10 20 30 40 50 60 80 100 Q [m3/s]
5000 10000 50000 10000020000 30000 200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
1.1
1.5
2
3
4
5.5
7.5
11
15
18.5 22 25 30
37 45
55
N [rpm]
400
450
500
550
600
650
700
750
850
950
1080
1250
1400
1600
1770
η [%] 46 56 67 76 66 47 29
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 27 59 122
M.RPM 1120 1450 1850
γ = 1.2 kg/m3
BNC-Q 1000
2 3 4 5 6 8 10 20 30 40 50 60 80 100 Q [m3/s]
5000 10000 50000 10000020000 30000 500000200000300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
1.5
2
3
4
5.5
7.5
11
15
18.5 22 25 30
37
45
55
75
N [rpm]
450
500
550
600
650
700
750
850
950
1120
1300
1450
1650
1850
η [%] 44 54 66 75 63 42 23
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
39
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
40
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 24.5 53 106
M.RPM 950 1230 1550
γ = 1.2 kg/m3
BNC-P 1120
2 3 4 5 6 8 10 20 30 40 50 60 80 100 Q [m3/s]
10000 50000 10000020000 30000 200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 Pd [Pa]
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
2
3
4
5.5
7.5
11
15
18.5
22 25
30
37
45
N [rpm]
400
450
500
550
600
650
750
850
950
1150
1230
1450
1550
η [%] 45 56 67 75 69 52 31
80
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
55
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
41
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 27.5 58.5 118
M.RPM 970 1250 1580
γ = 1.2 kg/m3
BNC-R 1120
2 3 4 5 6 8 10 20 30 40 50 60 80 100 Q [m3/s]
10000 50000 10000020000 30000 500000200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 10000 Pd [Pa]
20
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
2
3
4
5.5
7.5
11
15
18.5 22 25 30
37 45
55
75
N [rpm]
400
450
500
550
600
650
750
850
970
1150
1300
1450
1580
η [%] 46 56 67 76 66 47 29
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 34 74.5 152
M.RPM 1000 1300 1650
γ = 1.2 kg/m3
BNC-Q 1120
2 3 4 5 6 8 10 20 30 40 50 60 80 100 Q [m3/s]
10000 50000 10000020000 30000 500000200000300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
2
3
4
5.5
7.5
11
15
18.5 22 25 30
37
45
55
75 90
N [rpm]
400
450
500
550
600
650
750
850
1000
1150
1300
1450
1650
η [%] 44 54 66 75 63 42 23
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
42
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
43
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 30.3 65.5 135
M.RPM 850 1100 1400
γ = 1.2 kg/m3
BNC-P 1250
3 4 5 6 8 10 20 30 40 50 60 80 100 Q [m3/s]
10000 50000 10000020000 30000 500000200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 Pd [Pa]
50
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
3
4
5.5
7.5
11
15
18.5
22 25
30
37
N [rpm]
400
450
500
550
600
650
750
850
970
1100
1300
1400
η [%] 45 56 67 75 69 52 31
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
45
55
75
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
44
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 34 75 145
M.RPM 870 1130 1420
γ = 1.2 kg/m3
BNC-R 1250
3 4 5 6 8 10 20 30 40 50 60 80 100 200 Q [m3/s]
10000 50000 10000020000 30000 500000200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 10000 Pd [Pa]
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
3
4
5.5
7.5
11
15
18.5
22 25
30
37
45
55
75
90
N [rpm]
400
450
500
550
600
650
750
870
970
1130
1300
1420
η [%] 46 56 67 76 66 47 29
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 42 94 183
M.RPM 890 1170 1460
γ = 1.2 kg/m3
BNC-Q 1250
3 4 5 6 8 10 20 30 40 50 60 80 100 200 Q [m3/s]
10000 50000 10000020000 30000 500000200000300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
1 5 10 50 100 500 1000 5000 10000 Pd [Pa]
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
3
4
5.5
7.5
11
15
18.5 22 25 30
37
45
55
75 90
132
N [rpm]
400
450
500
550
600
650
750
890
1000
1150
1300
1460
η [%] 44 54 66 75 63 42 23
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
45
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
46
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 37 82 170
M.RPM 750 980 1250
γ = 1.2 kg/m3
BNC-P 1400
3 4 5 6 8 10 20 30 40 50 60 80 100 200 Q [m3/s]
50000 10000020000 30000 500000200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 Pd [Pa]
50
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
5.5
7.5
11
15
18.5
22 25
30
37
45
55
N [rpm]
400
450
500
550
600
650
750
870
980
1100
1250
η [%] 45 56 67 75 69 52 31
85
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
75
90
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
47
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 42 91.5 187
M.RPM 770 1000 1270
γ = 1.2 kg/m3
BNC-R 1400
4 5 6 8 10 20 30 40 50 60 80 100 200 Q [m3/s]
50000 10000020000 30000 500000200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 10000 Pd [Pa]
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
5.5
7.5
11
15
18.5 22 25
30
37
45
55
75
90
132
N [rpm]
400
450
500
550
600
650
770
900
1000
1270
η [%] 46 56 67 76 66 47 29
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 53 113 227
M.RPM 800 1030 1300
γ = 1.2 kg/m3
BNC-Q 1400
4 5 6 8 10 20 30 40 50 60 80 100 200 300 Q [m3/s]
50000 10000020000 30000 500000 1000000200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 10000 Pd [Pa]
30
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
5.5
7.5
11
15
18.5 22 25 30
37
45
55
75 90
132
N [rpm]
400
450
500
550
600
700
800
950
1030
1150
1300
η [%] 44 54 66 75 63 42 23
95
100
105
110
115
120
125
Lw (A) [dB(A)]
FEG 80
48
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
49
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 49 108 225
M.RPM 660 860 1100
γ = 1.2 kg/m3
BNC-P 1600
5 6 8 10 20 30 40 50 60 80 100 200 Q [m3/s]
50000 10000020000 30000 500000 1000000200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 Pd [Pa]
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
11
15
18.5
22 25
30
37
45
55
75
132
N [rpm]
400
450
500
550
600
660
750
800
860
950
1100
η [%] 45 56 67 75 69 52 31
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
90
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
50
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 56 121.5 244
M.RPM 680 880 1110
γ = 1.2 kg/m3
BNC-R 1600
6 8 10 20 30 40 50 60 80 100 200 300 Q [m3/s]
50000 10000020000 30000 500000 1000000200000 300000 Q [m3/h]
3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 10000 Pd [Pa]
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
11
15
18.5
22 25
30
37
45
55
75
90
132
160
N [rpm]
400
450
500
550
600
680
750
800
880
950
1110
η [%] 46 56 67 76 66 47 29
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 69 147 306
M.RPM 700 900 1150
γ = 1.2 kg/m3
BNC-Q 1600
5 6 8 10 20 30 40 50 60 80 100 200 300 Q [m3/s]
50000 10000020000 30000 500000 1000000200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 10000 Pd [Pa]
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
11
15
18.5
22 25
30
37
45
55
75
90
132
160
N [rpm]
400
450
500
550
600
650
700
750
800
850
950
1050
1150
η [%] 44 54 66 75 63 42 23
95
100
105
110
115
120
125
Lw (A) [dB(A)]
FEG 80
51
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
52
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 63 140 280
M.RPM 590 770 970
γ = 1.2 kg/m3
BNC-P 1800
6 8 10 20 30 40 50 60 80 100 200 300 Q [m3/s]
50000 10000020000 30000 500000 1000000200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 Pd [Pa]
100
200
300
400
500
1000
2000
3000
4000
5000
Pt [Pa]
kW
11
15
18.5
22 25
30
37
45
55
75
N [rpm]
350
400
450
500
550
590
650
700
770 800
900
970
η [%] 45 56 67 75 69 52 31
90
95
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
90
132
160
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
53
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 69.3 152 302
M.RPM 600 780 980
γ = 1.2 kg/m3
BNC-R 1800
6 8 10 20 30 40 50 60 80 100 200 300 400 Q [m3/s]
50000 10000020000 30000 500000 1000000200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 10000 Pd [Pa]
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
7.5
11
15
18.5
22 25
30
37
45
55
75
90
132
160
200
N [rpm]
300
350
400
450
500
550
600
650
700
780 800
900
980
η [%] 46 56 67 76 66 47 29
100
105
110
115
120
Lw (A) [dB(A)]
FEG 80
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
Op Limit Cl. I Cl. II Cl.III
Type DI DII DIII
M.kW 87 193 385
M.RPM 620 810 1020
γ = 1.2 kg/m3
BNC-Q 1800
5 6 8 10 20 30 40 50 60 80 100 200 300 400 500 Q [m3/s]
50000 10000020000 30000 500000 1000000200000 300000 Q [m3/h]
2 3 4 5 6 8 10 20 30 40 50 60 80 100 V [m/s]
5 10 50 100 500 1000 5000 10000 Pd [Pa]
40
50
100
200
300
400
500
1000
2000
3000
4000
5000
6000
Pt [Pa]
kW
7.5
11
15
18.5 22 25
30
37
45
55
75
90
132
160
200
250
N [rpm]
300
350
400
450
500
550
620
700
750
810
870
950
1020
η [%] 44 54 66 75 63 42 23
95
100
105
110
115
120
125
Lw (A) [dB(A)]
FEG 80
54
- Performance certied is for installation type A – free inlet, free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating kW does not include transmission losses.- Outlet Velocity of Model BNC is calculated in accordance with the fan outlet area as dened in AMCA 210 Annex H, Figure H.4.- Values shown are for outlet Lwo A sound power levels for Installation Type A: free inlet, free outlet.- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301.- Fan Efciency Grade (FEG) is based on peak total efciency in accordance with ISO 12759/ AMCA 205.- Please consult Kruger for fan selection of class III.
BNC 315~630'D'
BNC 'D'
All Dimensions in mm55
P R Q P R Q513 526 536 71543 556 566 80588 601 611 90603 616 626 100643 656 666 112562 575 587 80607 620 632 90622 635 647 100707 720 732 112867 880 892 132629 645 658 90674 690 703 100684 700 713 112779 795 808 132939 955 968 160667 685 703 90712 730 748 100727 745 763 112797 815 833 132972 990 1008 160706 725 747 90746 765 787 100766 785 807 112861 880 902 1321021 1040 1062 160768 790 813 100783 805 828 112883 905 928 1321033 1055 1078 1601063 1085 1108 180825 850 870 100840 865 885 112925 950 970 1321065 1090 1110 1601090 1115 1135 180
471 496 517
355 530 595 628580 340
645 678613 353
6 x 9
714 434
8 x 12
355
803 543
450 630 715
315 490 555 588525 325
Model A B C D E
100 28
330
650 410
120 28
565 365
3106 x 9
730673 393
8 x 9 130 28
400
863 583
140 28
400 580
8 x 12
435
904 624
560 790 875 890820 500
8 x 12 140 28
480
990 670
160 28
500 700 785 800
545
1035 715
8 x 12 160 28630 890 990 990865 545
LF G H
J Wt(Kg)w/o
Fan Type Fan TypeFram
eSize
20
29
38
266 279 289
289 303 315
322 338 351
50
60
76
358 376 394
392 412 434
431 452 476
95
nx Øq
BNC 710~1000'D'
BNC 'D'
All Dimensions in mm
56
P R Q P R Q
888 916 939 112
983 1011 1034 132
1123 1151 1174 160
1148 1176 1199 180
1223 1251 1274 200
1024 1056 1082 132
1159 1191 1217 160
1194 1226 1252 180
689 721 747 200
849 881 907 225
1225 1259 1289 160
1255 1289 1319 180
1325 1359 1389 200
1390 1424 1454 225
1455 1489 1519 250
1291 1329 1362 160
1321 1359 1392 180
1391 1429 1462 200
1446 1484 1517 225
1516 1554 1587 250
Model A B C D E H
J Wt
(Kg)
w/o
Fan Type Fan Type
L Fram
e
Size
F G
710 1000 1100 1100
938 618
522 550 112
1128 808
8 x 12 160 28 600 573
151
1230 910
8 x 12 160 28 660
1130 810
575 607 633
900 1240 1340 1340
1252 912
800 1130 1230 1230
209
1342 1002
12 x 12 170 28 720 630 665 695
261
1434 974
12
x
12 230 28 820
1334 874
713 751 7841000 1390 1515 1520
nx Øq
BNC 1120~1800'D'
BNC 'D'
All Dimensions in mm
57
P R Q P R Q
1410 1454 1491 180
1480 1524 1561 200
1515 1559 1596 225
1604 1639 1676 250
1705 1749 1786 280
1494 1544 1585 180
1564 1614 1655 200
1599 1649 1690 225
1664 1714 1755 250
1789 1839 1880 280
1563 1617 1666 180
1633 1687 1736 200
1678 1732 1781 225
1743 1797 1846 250
1868 1922 1971 280
1695 1768 1821 200
1740 1813 1866 225
1805 1878 1931 250
1895 1968 2021 280
2175 2248 2301 315
1912 1983 2043 225
1977 2048 2108 250
2067 2138 2198 280
2347 2418 2478 315
2722 2793 2853 355
952 1006 1052
807 851 888
872 922 963
408
1780 1180
16 x 16 300 28 1100
408
1540 940
333
1600 1050
12
x
12 275 28 925
1400 1928 2078 2058
1612 1012
1250 1722 1847 1852
1690 1090
14 x 12 300 28 1000
1120 1550 1675 1680
1450 900
Wt
(Kg)
w/o
Fan Type Fan Type
L Fram
e
Size
F GModel A B C D E H
J
1600 2204 2354 2354
1882 1252
18 x 16 315 28 1252 1100 1173 1226 512
2000 1370
1800 2480 2630 2630
2117 1487
32
x
16 315 28 1390 1272 1343 1403 570
2250 1620
nx Øq
58
Op
era
�o
nal
Lim
its
- B
NC
-P
31
53
55
40
04
50
50
05
60
63
07
10
80
09
00
10
00
11
20
12
50
14
00
16
00
18
00
CL.
IkW
2.2
33
.34
.35
.36
.47
.49
.71
2.3
15
.31
9.3
24
.53
0.3
37
49
63
CL.
IIkW
56
7.2
9.5
11
.51
3.4
16
21
.32
6.7
33
.54
2.4
53
65
.58
21
08
14
0
CL.
IIIkW
9.7
11
.51
41
92
3.2
26
.73
34
2.3
53
67
.48
6.5
10
61
35
17
02
25
28
0
CL.
Irp
m3
50
03
10
02
75
02
45
02
20
01
95
01
70
01
52
01
35
01
17
01
06
09
50
85
07
50
66
05
90
CL.
IIrp
m4
60
04
00
03
55
03
17
02
85
02
50
02
20
01
98
01
75
01
52
01
38
01
23
01
10
09
80
86
07
70
CL.
IIIrp
m5
80
05
00
04
45
04
00
03
60
03
15
02
80
02
49
02
20
01
92
01
75
01
55
01
40
01
25
01
10
09
70
Tem
per
atu
re R
ange
/ M
in. -
20
˚CC
L.I-
CL.
IIIM
ax.˚
C5
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
5
Dia
met
erm
m3
15
35
54
00
45
05
00
56
06
30
71
08
00
90
01
00
01
12
01
25
01
40
01
60
01
80
0
J =
PD
2/4
kgm
20
.13
0.2
20
.34
0.6
21
.07
1.8
82
.99
5.2
79
.52
14
.72
4.7
45
.17
2.4
11
72
34
40
5
Op
era
�o
nal
Lim
its
- B
NC
-R
31
53
55
40
04
50
50
05
60
63
07
10
80
09
00
10
00
11
20
12
50
14
00
16
00
18
00
CL.
IkW
2.4
34
.64
.66
7.1
91
11
4.6
18
21
.42
7.5
34
42
56
69
.3
CL.
IIkW
5.2
6.8
10
10
.61
31
5.6
19
25
31
.53
94
75
8.5
75
91
.51
21
.51
52
CL.
IIIkW
10
.41
3.3
20
21
.52
73
1.5
38
49
62
78
94
11
81
45
18
72
44
30
2
CL.
Irp
m3
55
03
18
03
00
02
47
02
22
01
95
01
72
01
53
01
37
01
21
01
08
09
70
87
07
70
68
06
00
CL.
IIrp
m4
60
04
15
03
89
03
20
02
88
02
54
02
23
01
99
01
77
01
57
01
40
01
25
01
13
01
00
08
80
78
0
CL.
IIIrp
m5
80
05
20
04
90
04
05
03
65
03
20
02
80
02
50
02
22
01
98
01
77
01
58
01
42
01
27
01
11
09
80
Tem
per
atu
re R
ange
/ M
in. -
20
˚CC
L.I-
CL.
IIIM
ax. ˚
C5
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
5
Dia
met
erm
m3
15
35
54
00
45
05
00
56
06
30
71
08
00
90
01
00
01
12
01
25
01
40
01
60
01
80
0
J =
PD
2/4
kgm
20
.13
0.2
30
.36
0.6
41
.12
1.9
53
.11
5.5
31
0.0
15
.42
6.0
47
.07
5.5
12
22
44
42
0
Op
era
�o
nal
Lim
its
- B
NC
-Q
31
53
55
40
04
50
50
05
60
63
07
10
80
09
00
10
00
11
20
12
50
14
00
16
00
18
00
CL.
IkW
34
56
.17
.69
11
13
.81
8.7
22
.22
73
44
25
36
98
7
CL.
IIkW
6.5
8.6
11
13
.61
6.7
20
.52
43
1.2
38
.84
6.5
59
74
.59
41
13
14
71
93
CL.
IIIkW
13
17
22
27
.53
3.5
40
.85
06
2.7
79
.49
7.7
12
21
52
18
32
27
30
63
85
CL.
Irp
m3
70
03
37
02
90
02
60
02
35
02
05
01
80
01
60
01
45
01
25
01
12
01
00
08
90
80
07
00
62
0
CL.
IIrp
m4
80
04
37
03
75
03
40
03
05
02
70
02
35
02
10
01
85
01
60
01
45
01
30
01
17
01
03
09
00
81
0
CL.
IIIrp
m6
10
05
50
04
75
04
30
03
85
03
40
03
00
02
65
02
35
02
05
01
85
01
65
01
46
01
30
01
15
01
02
0
Tem
per
atu
re R
ange
/ M
in. -
20
˚CC
L.I-
CL.
IIIM
ax. ˚
C5
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
5
Dia
met
erm
m3
15
35
54
00
45
05
00
56
06
30
71
08
00
90
01
00
01
12
01
25
01
40
01
60
01
80
0
J =
PD
2/4
kgm
20
.14
0.2
40
.37
0.6
71
.16
2.0
13
.21
5.7
51
0.3
15
.92
7.0
48
.77
8.1
12
62
53
43
4
Max
imu
m A
bso
rbed
Po
wer
Max
imu
m F
an S
pee
d
Wh
eel
Wh
eel
Wh
eel
Max
imu
m A
bso
rbed
Po
wer
Max
imu
m F
an S
pee
d
Max
imu
m A
bso
rbed
Po
wer
Max
imu
m F
an S
pee
d
59
60
K R U G E R G R O U P ( V E N T I L A T I O N )
Edition 1
The company is always improving and developing its products, therefore the company reserves the right of making changes to the illustrated products. Certified dimension can be provided upon request.
• THAILAND (Regional HQ) • AUSTRALIA KRUGER VENTILATION INDUSTRIES ASIA CO. LTD. S&P-KRUGER AUSTRALIA PTY LTD
30/159 Moo 1, Sinsakorn Industrial Estate, 2 Cunningham St, Moorebank N.S.W. 2170 Chetsadawithi Road, Khok Kham Mueng, Samuthsakorn 74000, Thailand Tel. +61 2-98227747 Tel. +662 1054298 - Fax +662 0248256-9 Fax. +61 2-98227757 Website: www.krugerfan.com Email: [email protected]
• (BEIJING) • CHINA (GUANGZHOU) BEIJING KRUGER VENTILATION CO. LTD GUANGZHOU KRUGER VENTILATION CO. LTD Level 7, A Block, Rising International Building, 29 JingHai San Road, BDA, No. 9 Huahui Road, Huashan, Huadu,
Beijing, P.R.China 100176 Guangzhou, P.R. China 510880 Tel. +86 10-67881366 - Fax +86 10-67880566 Tel. +86 20-66356635 - Fax +86 20-86786001/86786500
Email: [email protected] Email: [email protected]
• CHINA (SHANGHAI) • CHINA (TIANJIN) SHANGHAI KRUGER VENTILATION CO. LTD TIANJIN KRUGER VENTILATION CO. LTD No. 500 Yuanguo Road, Anting, Jiading, No.168 Anyuan Road, Jingjin Science and Technology Park
Shanghai 201814 P.R. China Wuqing District, Tianjin, China Tel. +86 21-69573266 - Fax +86 21-69573296 Tel. +86 22-22143480/3481 - Fax +86 22-22143482 Email: [email protected] Email: [email protected]
• CHINA (WUHAN) • DUBAI
WUHAN KRUGER VENTILATION CO. LTD KRUGER VENTILATION INDUSTRIES, GULF BRANCH No. 805, Huian Ave, Dongxihu District, Wuhan, Hubei, P.R. China 430000 Jebel Ali Free Zone Area (JAFZA) P.O. Box No. 262949, Dubai, UAE Tel. +86 27- 83248840/83060522/83097505 Tel. +971 4 8819188/8832017 Fax +86 27- 83261886 Fax. +971 4 8832018 Email: [email protected] Email: [email protected]
• HONG KONG • INDIA KRUGER VENTILATION (HONG KONG) LIMITED KRUGER VENTILATION INDUSTRIES (INDIA) PVT LTD Flat C, 9/F, Yeung Yiu Chung (No.8) Industrial Building, Kruger Centre, Mumbai-Nasik Highway, 20 Wang Hoi Road, Kowloon Bay, Kowloon, Hong Kong Kalamgaon, Shahapur, Thane 421601, Maharashtra, India Tel. +852 22469182 - Fax +852 22469187 Tel. +91 9960558899/9975577211 - Fax +91 2527 240075 Email: [email protected] Email: [email protected]
• INDIA (NORTH) • INDONESIA KRUGER VENTILATION INDUSTRIES (NORTH INDIA) PVT LTD P.T. KRUGER VENTILATION INDONESIA Plot No. - 191, Sector - 59, Ballabgarh, Faridabad - 121 004, Haryana, India JL. Teuku Umar No.20, Tel. +91-9958991660/9717449696 Karawaci - Tangerang 15115, Indonesia Fax. +91-1294135820 Tel. +62 21-5512288/5513557 - Fax +62 21-5513502 Email: [email protected] Email: [email protected]
• KOREA • MALAYSIA NEOMATE CO. LTD KRUVENT INDUSTRIES (M) SDN BHD 2-1010, Ace High Tech City B/D, 775 Gyeongin-ro, Lot 850, Jalan Subang 7, Taman Perindustrian Subang, Yeongdeungpo-gu, Seoul, Korea. Postal Code 07299 47500, Subang Jaya, Selangor D.E. Tel. +82-2-2679-2052 - Fax. +82-2-2679-2174 Tel. +603 80743399 - Fax +603 80743388 Email: [email protected] Email: [email protected]
• MYANMAR • PHILIPPINES KRUGER VENTILATION (MYANMAR) CO.LTD KRUGER M&E INDUSTRIES CORPORATION Room No. F21, Thiri Yadanar Whole Sale Market, (Htawunbe) FAPI Compound, E. Rodriguez Ave. Toe Chae Ward, North Okkalapa Township, Yangon. Tunasan, Muntinlupa City 1773, Philippines Tel. +959 763141081/2/3 Tel. +63 2-8622892/4/6/7, 5534059 - Fax +63 2-8622891 Email: [email protected] Email: [email protected]
• SINGAPORE • TAIPEI KRUGER ENGINEERING PTE LTD KRUGER VENTILATION (TAIWAN) CO. LTD No. 10 Buroh Street #06-06, West Connect Building, No. 157, Ping-an Rd, Hengfeng Village, Singapore 627564 Dayuan Shiang Taoyuan County 337, Taiwan Tel. +65 68631191 - Fax +65 68631151 Tel. +886 3-3859119 - Fax +886 3-3859118 Email: [email protected] Email: [email protected]
• THAILAND • VIETNAM KRUGER VENTILATION IND. (THAILAND) CO. LTD KRUGER VENTILATION INDUSTRIES (VIETNAM) CO. LTD 30/105 Moo 1, Sinsakorn Industrial Estate, Lot A7. 2-4, C2 Road, Thanh Thanh Cong IZ, Chetsadawithi Road, Khok Kham Mueng, Samuthsakorn 74000, Thailand Trang Bang Dist. Tay Ninh Province, Vietnam Tel. +662 1050399 - Fax + 662 1050370-2 Tel. +84-276 3585200/01/02 - Fax +84-276 3585199 Email: [email protected] Email: [email protected]
CHINA
Printed in October 2018
CNo.-CAT028.E
October 2018
30/159 Moo 1, Sinsakorn Industrial EstateChetsadawithi Road, Khok Kham Mueng,Samuthsakorn 74000, ThailandTel. +662 1054298 - Fax. +662 0248256-9
Website:www.krugerfan.com
Kruger Ventilation Industries Asia Co., Ltd
1