Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a...

65
Jin Shuai Placing of VSC-HVDC Lines in a Meshed AC-Network Master Thesis PSL1202 EEH – Power Systems Laboratory Swiss Federal Institute of Technology (ETH) Zürich Examiner: Prof. Dr. Göran Andersson Superviosr: Markus Imhof & Roger Wiget Zürich, August 29, 2012

Transcript of Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a...

Page 1: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

Jin Shuai

Placing of VSC-HVDC Lines in a Meshed AC-Network

Master Thesis

PSL1202

EEH – Power Systems Laboratory

Swiss Federal Institute of Technology (ETH) Zürich

Examiner: Prof. Dr. Göran Andersson

Superviosr: Markus Imhof & Roger Wiget

Zürich, August 29, 2012

Page 2: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid
Page 3: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

ii

Abstract Many existing High Voltage Alternating Current (HVAC) bulk transmission systems, e. g

in Europe and North America, have reached their capability limits and a significant

increase of transmission capacities is foreseen within the next decades. There are

several reasons calling for an upgrade, where the most significant is the expected

overall increase in consumption of electric energy. Furthermore, the fluctuating nature

of many renewable energy sources, like wind and solar, requires higher transmission

capacities in order to provide the regulating power from other power plants.

The recent developments in semiconductors and control equipment have made the

Voltage Source Converter Based High Voltage direct current (VSC-HVDC) feasible. Due

to the use of VSC technology and Pulse Width Modulation (PWM), VSC-HVDC has a

number of potential advantages as compared with classical HVDC, such as short circuit

current reduction, rapid and independent control of active and reactive power, etc.

With those advantages VSC-HVDC will likely be widely used in future transmission and

distribution systems.

In this thesis, two different algorithms with the objectives to place VSC-HVDC line in

order to reduce power flow contingencies and inter-area oscillations in AC power

system are developed and their effectiveness and validity on both small and complex

AC grid are investigated in the Matlab program.

In chapter2, the thesis studies the causes and possible solutions of power flow

contingencies, an algorithm is developed to identify the optimal placement for VSC-

HVDC line in order to reduce the power flow contingencies in a given AC grid, in

addition, not only the economical optimization of the whole system but also the line

capacity of the VSC-HVDC can be calculated by the algorithm. Its functionality is

verified by testing IEEE14 and IEEE118 bus systems.

Chapter3 describes different oscillation modes in power system, and an algorithm is

developed to specify optimal placement for VSC-HVDC line in order to reduce the inter-

area oscillation in a given AC grid, the algorithm is tested on Kundur second order

system and IEEE Two Area RTS-24 system. The weak connections in testing system are

specified by this algorithm and the oscillation modes in both testing system are

analyzed.

Chpater4 demonstrates some valuable work which is worth to do in the future due to

time limits for this thesis.

Page 4: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

iii

Page 5: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

iv

Contents

ABSTRACT.......................................................................................................................................... II

CONTENTS ........................................................................................................................................ IV

LIST OF FIGURES ............................................................................................................................... VI

LIST OF TABLES ...............................................................................................................................VIII

LIST OF ABBREVIATION ..................................................................................................................... X

PREFACE .......................................................................................................................................... XII

CHAPTER1

INTRODUCTION .................................................................................................................................. 1

1.1 BACKGROUND ................................................................................................................................ 1

1.2 CURRENT SOURCE CONVERTER HVDC .............................................................................................. 1

1.2.1 Configurations of Current Source Converter HVDC ......................................................... 1

1.2.2 Application of Classic HVDC .............................................................................................. 3

1.3 ADVANTAGES & DISADVANTAGES .................................................................................................... 4

1.3.1 Advantages of HVDC ......................................................................................................... 4

1.3.2 Disadvantages of HVDC ................................................................................................... 5

1.4 VSC-HVDC .................................................................................................................................. 6

1.4.1 Components of VSC-HVDC system ................................................................................... 6

1.4.2 Control Strategy of VSC-HVDC .......................................................................................... 7

1.4.3 VSC-HVDC vs. Classical HVDC ........................................................................................... 8

1.4.4 Applications of VSC-HVDC ................................................................................................ 9

CHAPTER2

OPTIMAL PLACEMENT OF VSC-HVDC LINK TO REDUCE POWER FLOW CONTINGENCIES .............. 11

2.1 INTRODUCTION ............................................................................................................................. 11

2.1.1 Causes of Power Flow Contingencies .............................................................................. 11

2.1.2 Possible Solutions ............................................................................................................. 11

2.2 ALGORITHM ............................................................................................................................. 12

2.3 SIMULATION RESULTS ............................................................................................................... 17

2.3.1 Simulation Results on IEEE14 ........................................................................................... 17

2.3.2 Simulation Results on IEEE118 ......................................................................................... 21

2.4 CONCLUSION ........................................................................................................................... 24

CHAPTER3 OPTIMAL PLACEMENT OF VSC-HVDC LINK TO REDUCE INTER-AREA OSCILLATIONS ..................... 25

3.1 INTRODUCTION ............................................................................................................................. 25

3.2 ALGORTHIM ............................................................................................................................. 27

3.2.1 Concept of slow coherency .............................................................................................. 27

3.2.2 Analytical expression ....................................................................................................... 28

3.3 SIMULATION RESULTS ................................................................................................................ 32

3.3.1 Simulation results on Kundur second order system ....................................................... 32

3.3.2 Simulation result on IEEE Two Area RTS-24 system ....................................................... 35

3.4 CONCLUSION ............................................................................................................................ 37

Page 6: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

v

CHAPTER4

CONCLUSIONS AND FUTURE WORK ............................................................................................... 38

4.1 CONCLUSIONS .............................................................................................................................. 38

4.2 FUTURE WORK .............................................................................................................................. 38

APPENDIX A..................................................................................................................................... 40

REFERENCE ....................................................................................................................................... 49

Page 7: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

vi

List of Figures Figure 1-1

(a) Monopolar Long-Distance Transmissions with ground return path [3]

(b) Monopolar Long-Distance Transmissions with metallic return path [3] …………………………………..2

Figure 1-2

(a) Bipolar Transmissions system with ground return [3]

(b) Bipolar Transmissions system without electrodes [3]

(c) In monopolar metallic return operation due to pole failure [3]

(d) In monopolar metallic return operation due to converter failure [3] ............................................... 2

Figure 1-3 Back-to-back converter [3] .......................................................................................................... 3

Figure 1-4 Cost structure [7] .......................................................................................................................... 5

Figure 1-5 A 12-pulse converter for HVDC ................................................................................................... 6

Figure 1-6 A VSC HVDC back-to-back system [8] ...................................................................................... 6

Figure 1-7 A bi-polar two level PWM converter [9] .................................................................................... 7

Figure 1-8 Overall control structure of the VSC-HVDC [10] ....................................................................... 8

Figure 2-1 Example AC system ..................................................................................................................... 13

Figure 2-2 Example system used to clarify BLR ........................................................................................ 14

Figure 2-3 (a),(b) and (c) The relationship of these three factors with Bus Sensitivity Index ............. 16

Figure 2-4 Flow Chart of the Algorithm ..................................................................................................... 17

Figure 2-5 Power flow of IEEE14 system in normal operation ................................................................ 18

Figure 2-6 Power flow of IEEE14 system after installing VSC-HVDC line from Bus1 to Bus3 .............. 19

Figure 2-7 Equivalent treatment to the first VSC-HVDC line .................................................................. 19

Figure 2-8 Power flow of IEEE14 system after installing VSC-HVDC lines from Bus1 to Bus and Bus1

to Bus9 ................................................................................................................................................. 20

Figure 2-9 Generation centre, load centre and power flow of the IEEE118 bus system ...................... 22

Figure 2-10 Overloaded area of the IEEE118 bus system .......................................................................... 22

Figure 2-11 Overloaded area of the IEEE118 bus system with VSC-HVDC .............................................. 24

Figure 3-1 Flow chart of the algorithm ..................................................................................................... 28

Figure 3-2 Norton equivalent input current of generator .................................................................... 29

Figure 3-3 Eigenvalue and stability of system ........................................................................................... 31

Figure 3-4 Kundur second order system [31] ............................................................................................. 33

Figure 3-5 (a) and (b) Participation factor of Kundur second order system ......................................... 35

Figure 3-6 IEEE Two Area RTS-24 system [33] ........................................................................................... 36

Page 8: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

vii

Page 9: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

viii

List of Tables Table 1-1 HVDC projects list around the world during 2000-2010[14] .................................................... 4 Table 1-2 Projects lists of VSC-HVDC .......................................................................................................... 10 Table 2-1 Bus Sensitivity Index for each bus based on the example system ......................................... 15 Table 2-2

(a) Simulation result for the first VSC-HVDC line by Algorithm

(b) Simulation result for the second VSC-HVDC line by Algorithm ....................................................... 18 Table 2-3

(a) Part of Simulation result for the first VSC-HVDC line by verifying method

(b) Part of Simulation result for the second VSC-HVDC line by verifying method .............................. 21

Table 2-4 Simulation results comparison of the developed algorithm and verifying method ......... 21 Table 2-5

(a) A part of load rates of transmission lines in overloaded area without VSC-HVDC line

(b) A part of load rates of transmission lines in overloaded area with VSC-HVDC line from Bus10 to

Bus1 ....................................................................................................................................................... 23 Table 2-6 The simulation results of likely starting and ending terminals............................................ 23 Table 2-7 Part of the simulation results from verifying method ........................................................... 24 Table 3-1 Generating parameters ............................................................................................................... 33 Table 3-2 Simulation results on operation case one ................................................................................ 33 Table 3-3 Simulation results on operation case two ............................................................................... 34 Table 3-4 Oscillation modes in kundur second order system ................................................................. 35 Table 3-5 Part of simulation result on IEEE Two Area RTS-24 system ................................................... 36 Table A - 1 Parameters of VSC-HVDC line in IEEE14 ................................................................................. 40

Table A - 2 Parameters of VSC-HVDC line in IEEE118 ................................................................................ 41 Table A - 3 Simulation Results of after first HVDC line on IEEE14 by verifying method...................... 42 Table A - 4 Simulation Results after installing second HVDC line on IEEE14 by Verifying method ... 43 Table A - 5 Line load rate of IEEE118 before installing VSC-HVDC line .................................................. 44 Table A - 6 Line load rate of IEEE118 after installing VSC-HVDC from Bus10 to Bus 1 ......................... 45 Table A - 7 Simulation Results of IEEE118 by the proposed algorithm .................................................. 46 Table A - 8 Simulation Results of IEEE Two Area RTS-24 system............................................................ 47 Table A - 9 Dynamic data of generators and line parameters for Kundur system ............................ 48

Page 10: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

ix

Page 11: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

x

List of Abbreviation

AVR Automatic Voltage Regulators

BLR Bus Load Rate

CSI Composite Security Index

DGLC Distribution of Generator and Load Center

GTO Gate Turn-off Thyristor

HVAC High Voltage Alternating Current

HVDC High Voltage Direct Current

IGBT Insulated Gate Bipolar Transistor

IGCT Integrated Gate Commutated Thyristors

LFIO Low Frequency Inter-area oscillations

MMC Modular Multilevel Converter

PSS Power System Stabilizer

POD Power Oscillation Damping

PWM Pulse Width Modulation

SVC Static Var Compensator

VSC Voltage Source Converter

Page 12: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

xi

Page 13: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

xii

Preface The research work was carried out at the Power Systems Laboratory of the Department

of Information Technology and Electrical Engineering of the Swiss Federal Institute of

Technology, Zürich (ETH Zürich).

First I would like to thank my supervisors Mr. Markus Imhof and Mr. Roger Wiget at ETH

Zürich and Mr. Dr. Hanno Stagge at RWTH-Aachen for their help, guidance, patience

and encouragement, without which, this thesis would not be possible to finish.

I would also like to thank my examiner at ETH-Zürich Prof. Dr. Göran Andersson for

offering me the opportunity to explore the challenging and promising topic of the VSC-

HVDC technology.

A special thanks to my examiner at RWTH-Aachen Univ.-Prof. Dr. Rik W. De Doncker for

his support to my research project.

Last but not the least; I want to thank my girlfriend Eva Yin for her love and support.

Jin Shuai

Zürich, Swizterland

August 2012

Page 14: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

xiii

Page 15: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

1

Chapter1

Introduction 1.1 Background

Miesbach–Munich Power Transmission in Germany was the first power transmission

system in the world over a long distance. The first transmission of electrical energy

started with direct current around 1880s. At that time the voltage level was limited to

some hundred volts, higher DC voltage cannot be generated due to the limitation of

semiconductor technology; in addition, high transmission voltage is needed for a long

distance power transmission in order to lower the transmission losses over the

overhead line due its ohmic characteristics [1].

In the late 1880s alternating current had first developed in Europe thanks to the work

of Nikola Tesla. In order to limit the transmission losses within an acceptable value, a

new and simple machine called transformer which can step up and step down voltage

was invented in 1886 [1]. After the utilization of transformer in transmission system, AC

technology was used world widely in the aspect of power transmission due to its

overwhelming advantages over DC system in these days.

The situation had not been changed until the 1930s in which high voltage DC became

possible with the development of high power electronic devices such as mercury arc

rectifier. DC power transmission system with high voltage DC which is called High

Voltage Direct Circuit (HVDC) was emerged. Finally, starting in the 1970s, high power

semiconductor devices like power thyristors, Insulated Gate Bipolar Transistor (IGBT),

Integrated Gate Commutated Thyristors (IGCT) and so on advance the development of

new technology like Current Source Converter (CSC) HVDC and Voltage Source based

Converter (VSC) HVDC [2].

1.2 Current Source Converter HVDC

1.2.1 Configurations of Current Source Converter HVDC

The CSC HVDC is also named as classical HVDC. The invention of mercury arc rectifiers

in the 1930s made this technology possible. In 1941, the first commercial HVDC system

was built in Berlin in Germany with +-200kV and 150 A by Siemens [3]. Since then,

several HVDC systems had been established with mercury arc valves and later on

replaced by thyristor valves. With respect to different operational requirement and

design, HVDC systems can be categorized into three different configurations.

Monopole system

Bipolar system

Back to back system

Page 16: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

2

Monopole system

The Figure 1-1 (a) and (b) demonstrate the simplified equivalent circuit of Monopole

transmission system with ground return path and metallic return path respectively.

The technology with a return path through ground electrodes is particularly for a very

long sea cable transmission, however, in other cases, a metallic return path is used due

to the existing infrastructure or environmental constrains.

(a) (b)

Figure 1-1 (a) Monopolar Long-Distance Transmissions with ground return path [3] (b) Monopolar Long-Distance Transmissions with metallic return path [3] Bipolar system

When a higher transmission capacity or transmission voltage is needed the

configuration in Figure 1-2 (a) and (b) are the options. They are combination of two

poles. In such a structure a common low voltage return path only carries a small

current in normal operation due to unbalance, Figure 1-2 (b) will face function problem

when there is pole outage. However, Figure 1-2 (a) can be used to transfer part of the

full power even during maintenance or fault of one pole as be shown in Figure 1-2 (c)

and (d). In general, more than 50% of the transmission capacity can still be used, the

percentage depends on the actual overload capacity of the remaining pole. Comparing

with the monopolar line, bipolar solution is more cost effective because of only one

common return path.

(a) (b)

(c) (d)

Figure 1-2

(a) Bipolar Transmissions system with ground return [3]

(b) Bipolar Transmissions system without electrodes [3]

(c) In monopolar metallic return operation due to pole failure [3]

(d) In monopolar metallic return operation due to converter failure [3]

Page 17: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

3

Different topology structures are utilized to satisfy different operational requirement

and enviromental contraint [3].

Back-to-back Converters

Back-to-back Converters are wildly used for power transmission between two adjacent

asynchronous AC systems to achieve a defined power flow, and its rectifier and inverter

are located in the same station as be shown in Figure 1-3 [3].

Figure 1-3 Back-to-back converter [3]

1.2.2 Application of Classic HVDC

Since the first HVDC transmission system was introduced in 1941. This techonolgy is

widely used due to many advantages including the interconnection of asynchronous

networks, economic benefits, long-distance bulk power delivery and environmental

benefits. In the big background of fast growth in offshore wind farms and other

renewable power stations, HVDC system will lead to a new power grid in the future [4].

With the benefits describled above, HVDC technology is very popluar in booming

economies due their huge electricity demand in some economic fast growing area. In

2006, Power Grid Cooperation of Indian decided to increase the transmission capacity

in Southeast of Indian from 2000MW to 2500MW at the rating of ±500kV. This project

is now online. This upgrade project made the power system more efficient and the

maximum use of the system’s overhead capacity [5].In 2007, the China Southern Power

Grid Company began to construct a ±800kV HVDC system between Yunnan province

and Guangdong province in South of China with the capacity of 5000MW. This is the

world's first ±800kV DC transmission project [5].

Page 18: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

4

Table 1-1 shows the HVDC project around the world during 2000-2010.

HVDC SUPPLIER YEAR

COMMISSIONED

POWER

RATING

(MW)

DC

VOLTAGE

(kV)

LOCATION

ABB 2000 600 ±450 SWEDEN-

POLAND

ABB 2000 3 x 60 ±80 AUSTRALIA

HITACHI 2000 1400 ±250 JAPAN

ABB 2000 1100 ±70 ARGENTINA-

BRAZIL

ABB 2002 2000 ±70 ARGENTINA-

BRAZIL

GEC ALSTHOM 2000 70 20 URUGUAY-

BRAZIL

PIRELLI/ABB 2001 500 400 GREECE-ITALY

SIEMENS 2001 1800 ±500 CHINA

HITACHI/TOSHIBA 2001 300 125 JAPAN

SIEMENS 2001 300 ±300 THAILAND-

MALAYSIA

ABB 2002 330 ±150 U.S.A

ABB 2002 200 ±150 AUSTRALIA

GEC ALSTHOM 2002 500 205 INDIA

ABB 2003 2 x 100 ±13 U.S.A.

SIEMENS 2003 2000 ±500 INDIA

ABB/SIEMENS 2003 3000 ±500 CHINA

ABB 2004 3000 ±500 CHINA

SIEMENS 2004 3000 ±500 CHINA

SIEMENS 2007 3000 ±500 CHINA

ABB 2004 2x40 ±60 NORWAY

SIEMENS 2004 3100 ±400 U.S.A.

SIEMENS 2005 210 ±64 U.S.A.

SIEMENS 2006 500 400 AUSTRALIA

ABB 2006 3000 ±500 CHINA

SIEMENS 2007 660 500 U.S.A.

AREVA 2008 250 ±17.4 CANADA

SIEMENS 2009 2500 500 INDIA

ABB 2009 2x625 315 CANADA

AREVA 2009 3 x 600 3 x 222 SAUDI ARABIA

ABB 2009 300 350 SOUTH AFRICA

SIEMENS 2010 5000 ±800 CHINA

Table 1-1 HVDC projects list around the world during 2000-2010[14]

1.3 Advantages & Disadvantages

1.3.1 Advantages of HVDC

In comparions with High Voltage Alternating Current (HVAC) transmission

line, HVDC transmission line can save aroud 1/3 steel-core aluminium in

total to transmit the same amount of power, because HVDC overhead line

only requires two conductors to transmit the power comparing to three

conductors for HVAC transmssion line. Furthermore, simpler and smaller

tower can be used to carry the transmission lines [6].

Page 19: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

5

A very long marine cable can not be used with HVDC due to the capacitive

characteristics of cables, thereby HVDC is the only solution to transmit

power to island in which case overhead line is not possible. Besides, with

the same insulation thickness and cross section, the transmission capacity

for DC cable is significantly higher than that of AC. Similarly like overhead

DC line, for HVDC, only one cable is required for monopole and two cables

for bipolar but three cables are needed for AC system due to three-phase

transmission.

Back-to-back HVDC links can be used to interconnnect two AC systems with

different operational frequencies without increasing the short-circuit

current level for both connected AC system.

Because of the fast reaction of power electronic devices, active and reactive

power can be controlled rapidly, HVDC systems can be used to improve the

stability and safety of AC systems.

HVDC transmission system has lower losses because of the fewer

conductors and suffering no skin effect.

Better solution to connect renewable energy source such as wind farm to

AC system due to its fast power control.

1.3.2 Disadvantages of HVDC

Cost

As can be seen from Figure 1-4, power electronics devices and converter

transformers are the most expensive part for HVDC transmission system

Sepcially, converter stations are much more expensive than that of the HVAC

stations.

Figure 1-4 Cost structure [7]

Cost Structure

Freight isurance

Converter trasformers

Power electronics

Civil works buildings

Engineering

Erection commissioning

Other equipment

Control

AC filters

Page 20: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

6

Harmonics

In modern HVDC systems, 12-pulse-converter as be shown in Figure1-11 is

normally used which lead to high harmonics to the connected AC systems.

Power quality is impacted by these harmonics, the harmonics are recognized as

one of the biggest problems in HVDC systems, it leads to big filter banks and

higher costs [4].

Figure 1-5 A 12-pulse converter for HVDC

1.4 VSC-HVDC

1.4.1 Components of VSC-HVDC system

The recent development of the modern semiconductor devices such as the IGBT and

IGCT made a new generation of power electric converters possible. These devices,

unlike the conventional thyristors which have no intrinsic turn-off ability, are of the

fully controlled type. A typical VSC-HVDC system, shown in Figure 1-6, is structured by

transformers, AC filters, phase reactors, converters, DC capacitors and DC cable.

Figure 1-6 A VSC HVDC back-to-back system [8]

Transformers

Transformer is used to connect converter and AC system, the most significant function

of it is to adjust the voltage level of AC system to certain level that suitable for the

converter.

AC filters

AC filters are normally functions as AC harmonics filters and reactive power

compensators. The harmonics cause by IGBTs switching operation emitted into the AC

system must be mitigated to prevent other equipment in the system from malfunction.

Page 21: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

7

Phase reactors

Phase reactors have two functions in the system. On one hand, they are used for

controlling the active and reactive power flow by regulating currents through them,

one the other hand they are also used to reduce the high frequency harmonic content

of the AC currents which are caused by switching.

DC capacitors

Capacitors are used to maintain the voltage level and keep the power balance during

transients. The size of these capacitors depends on the desired operating DC voltage.

Converters

Figure 1-7 indicates one of widely used VSC topology in the industry. It contains six

IGBTs in total, with two IGBTs stack on each leg. Besides, a diode is connected in anti-

parallel connection to each IGBT in order to allow bidirectional current flow.

Figure 1-7 A bi-polar two level PWM converter [9]

Assume the reactance of phase reactor is and it is lossless, and only one phase is

taken into account to express the power flow. The calculations of active and reactive

power are expressed in equation1-1 and 1-2 respectively.

(1-1)

(1-2)

Observations from these two equations:

The active power flow between the AC system and the VSC is determined by the

phase angle . When , active power flows into the AC system

otherwise flows out of AC system from the VSC.

The reactive power flow direction is determined by couple of parameters

; the contribution of phase angle is relatively small,

therefore, the main factors are the amplitude of the AC system voltage and

the fundamental part of VSC output voltage . When , the reactive

power flows into the AC system, while the VSC absorbs reactive

power from the AC system.

1.4.2 Control Strategy of VSC-HVDC

By using VSC-HVDC the reactive power, the active power, the AC voltage, the DC

Voltage and the frequency can be controlled. The controllability of VSC-HVDC is out the

Page 22: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

8

scope of this thesis; however, considering the importance of the control strategy, it is

necessary to explain the principle of it. As described in last section, the VSC-HVDC can

control the active and reactive power independently. Both inverter and rectifier can

control the reactive power independently or by the required AC voltage separately. The

active power can be controlled by the DC voltage, the variation of frequency at the AC

side or set manually [10]. As be shown in Figure 1-8, both rectifier and inverter can

choose between AC voltage controller and reactive controller, a reference value for the

controller can be generated by each of these controllers.

Figure 1-8 Overall control structure of the VSC-HVDC [10]

It is easy to understand that there is no possibility for all controllers to be used at the

same time. In different operation conditions different kinds of control strategies are

employed.

In this thesis the controllability will not be explained in detail because of its complexity

and it is out the scope of this work.

1.4.3 VSC-HVDC vs. Classical HVDC

The VSC-HVDC has several main advantages over the Classical HVDC:

VSC-HVDC can independently control the active and reactive power. The

reactive capabilities can be used to control the AC network voltage and

enhanced power quality of AC system [10].

It can lower the risk of commutation failures. The commutation failures is

catastrophic sometime, as the VSC-HVDC uses self-commutating

semiconductor devices, it is no longer necessary to present a sufficiently high

AC voltage [10].

The VSC-HVDC is a better option to creating a DC grid with a number of

converters because of its constant voltage in the grid.

Due to the fast response of the VSC, VSC-HVDC is the best option to connect the

fluctuating renewable energy such as off-shore wind power farm.

Page 23: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

9

The VSC-HVDC technology also has some disadvantages comparing to Classic HVDC.

VSC-HVDC technology is more expensive than Classic HVDC, due to the higher

cost of the converter stations.

VSC-HVDC system has higher converter losses than Classic HVDC because of

the higher switching frequency.

Classical HVDC has higher converter rating than VSC-HVDC technology up to

today because of IGBT has a lower capacity that of the thyristor.

1.4.4 Applications of VSC-HVDC

VSC-HVDC technology is utilising the state of the art semiconductors IGBT, and PWM is

also employed to create the desired voltage waveform, phase angle and magnitude,

which in turn can offer a wide range of applications:

Underwater power connection

VSC-HVDC is a sound option for underground power transmission, especially

underwater cables, the reactive power produced by an AC submarine cable

would take up the entire current-carrying capacity of the conductor above a

certain distance because of capacitive property of AC cable.

City center power distribution

VSC-HVDC is considered as the only alternative to increase capacity over short

distances due to the increasing difficulties in obtaining permission to build new

power lines notably in urban area.

Connecting onshore wind farms and offshore wind farms

By using self-commutated device IGBTs, the VSC converter can connect to very

weak systems like wind farms [11] due to its fast and independent active and

reactive power control .

Connecting asynchronous power system

The power quality will be improved as the VSC-HVDC terminals can control

reactive power in each station in excess of the active power transfer between

stations.

Providing shore power supplies to offshore oil & gas platforms

VSC-HVDC package is flexible to move and easy to set up.

In year 1999, the first commercial VSC-HVDC line with capacity rating of 50MW at

voltage level of 80kV was put into operation. These two 70km undergroud cables are

located between the southern part of Gotland with a Wind farm and the load center in

the city Visby due to difficulties to get permits to build an additional overhead

transmission line [12]. The following table shows some VSC-HVDC projects in the world:

Page 24: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

10

Project In service Power DC voltage Distance Application

GOTLAND

Sweden 1999 50MW 80kV 70km

Wind

Undergrounding

DIRECLINK

Australia 2000 3x60MW 80kV 65km Undergrounding

CROSS SOUND

USA 2002 330MW 150kV 40km Grid reliability

VALLHALL

Norway 2005 2x41MW 60kV 67km Offshore

Nord E.ON 1

Germany 2009 400MW 150kV 203km Offshore wind

Table 1-2 Projects lists of VSC-HVDC

Page 25: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

11

Chapter2 Optimal Placement of VSC-HVDC link to reduce Power Flow Contingencies 2.1 Introduction

On 28th September 2003, a cascading outage of transmission and generation facilities

in Italy resulted in a blackout of almost the whole country; it was the largest blackout in

Italy, affected more than 50 million people [13].

What caused the blackout? A report comes from Italy’s electricity supplier stated that a

power line transfers power from Switzerland to Italy has been tripped due to a tree

flashover. And the circuit breaker refused to reclose the line because of big phase angle

difference across the line due to heavy power flow into Italy. On the border side, two

400kV power lines between France and Italy tripped because of sudden increased

power demand from these two lines. Only in a couple of seconds, the power deficit in

Italy was so big that Italian power grid began to lose synchronism with the rest of

Europe. Finally, the frequency in Italy fall, with a shortage of more than 6000MW

power, and then the whole country’s power grid collapsed. This accident has given out

a warning that overloaded transmission lines cause the cascading outages, which in

further forces the system to collapse [13]. Base on this reality, an algorithm to mitigate

power flow contingencies is demonstrated in this chapter.

2.1.1 Causes of Power Flow Contingencies

Power systems should be well designed and properly operated so that only one outage

or few outages could not result in blackout [14]. In real operation of power grid, there is

high possibility of power flow contingencies due to different kinds of reasons. For the

purpose of solving this issue, the main causes of the power flow contingencies in the

AC transmission system are necessary to be specified. There are several reasons that

cause power flow contingencies in power system:

Line tripping in load centre may lead to overload on other lines in this area.

The improper operation of the power system during the maintenance of

transmission line will lead to power flow contingencies.

High loads in a weak transmission systems

2.1.2 Possible Solutions

Those power flow contingencies can be handled temporarily by the remedial actions

from system operators to alleviate line overloads. With respect to the cause analysis on

Page 26: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

12

transmission line in power system, three main counter measures are analysed and

conducted so as that the safety and stability of power system can obtain.

Rescheduling of generators

Tap changing of transformers

Static Var Compensator (SVC)

The measures mentioned above are the most practiced method to alleviate overload

situation, nevertheless, these approaches mentioned above can not able to eliminate

the problem from the root. For this reason, a necessity of new and innovative solution

is becoming significant.

In the first chapter, the advantages of VSC-HVDC have been already demonstrated.

VSC-HVDC technology can greatly enhance the reliability and transfer capability of the

power systems, and the fast power run-back and instant power reversal can be used if

the transfer capability of the interconnected power systems is constrained by power

flow contingencies [15]. For a bulk power grid, it should be able remain stable and be

capable of withstanding a wide range of disturbances. For this reason, it is very

important that the system be well structured so that the possible power flow

contingencies do not cause worse situation such as cascading outages. A common

method in power system is the N-1 criterion which expresses the capability of the

power system to lose a power system equipment without resulting in a contingency

elsewhere. The VSC-HVDC technology has the advantage of being capable of changing

the active and reactive power instantly and independently. It behaves like an ideal

power generator with flexible working point and without inertia to the grid [15]. Base

on the benefits of this technology, there is no doubt that VSC-HVDC can alleviate

power flow contingencies in a bulk system, however, this solution raised another

problem which is a hot topic in power system research, that is where should the VSC-

HVDC links be installed in order to reduce power flow contingencies in a meshed AC

grid. In section 2.2, a new algorithm is proposed, which can solve the problem. The

validity and effectiveness of this new algorithm is supported by simulation results on

IEEE14 and IEEE118 bus system which are derived from Matpower 4.1 [16].

2.2 Algorithm

The proposed algorithm is deduced from the concept of Composite Security Index (CSI)

given in reference [17]. Composite Security Index is widely applied to select and rank

critical contingency in order to safeguard the system against major outages and

blackouts. It consists of Bus Voltage Security Index (BVSI) and Line Power Security Index

(LPSI) which are based on the concept of Hyper-ellipse inscribed within the Hyper-box

[17]. In this concept, each CSI corresponds to a certain contingency such as outage of

generating unit, transmission lines or buses. The value of CSI indicates the severity of

the corresponding contingency, the higher the index value the more severe the

corresponding contingency is.

, the system is in secure state and there is neither buses nor lines

violation cause by the contingency.

Page 27: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

13

, the system is in unsecure state and there is either buses or lines

violation due to corresponding contingency.

More details about this concept can be found in paper [17]. All the CSI with respect to certain possible contingency in a given power system can be calculated, and the most severe one can be specified easily just by comparing the CSI. The contingency with high CSI should be carefully observed while it causes violations to buses or transmission lines in the system severely. Proper control actions such as installing a VSC-HVDC line around the location of this contingency line can be applied to enhance the stability of the power system. The concept mentioned above can specify and rank critical contingencies effectively, however, such method is not able to point out the optimal placement for VSC-HVDC line. As previously described, the basic theory of this concept provides a significant clue to the development of the new algorithm. In this section, the optimal starting terminal and ending terminal of VSC-HVDC link can be identified by solving the Bus Sensitivity Index (BSI) of each bus in a given system, the higher the BSI of one bus the more likely of the bus to be the starting terminal of the HVDC line, reversely, the bus with lowest BSI is the optimal ending terminal for the HVDC line. The validity and effectiveness of this algorithm is tested in two systems IEEE14 and IEEE118. BSI is a function of three factors: Bus Load Rate (BLR), Distribution of generation and

load centers (DGLC) and Generating cost (GC). The following couple of pages give the

mathematical calculation and theoretical explanations of the algorithm.

Calculation of factor 1: Bus Load Rate (BLR).

Step 1 Read system data of the testing system.

Step 2 Set only one transmission line l (l = 1, 2,…, nl) in outage, nl is the

amount of transmission lines in a given system.

Step 3 Calculate the power flow of the system based on step 2.

Step 4 Calculate the Sensitivity Index of Bus k (k = 1, 2,,…, nb) base on step and

then go back to step 2 until line outage i (i = 1,2,…,nl)

Step 5 Calculate Load Rate of Bus k based on Overall Line Contingencies

In the following, an example AC system consists of two generators, three buses and

four transmission lines is shown, the green arrows show the power flow direction, this

system is used to explain the Concept of Bus Load Rate which determine the optimal

placement for VSC-HVDC.

Figure 2-1 Example AC system

Page 28: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

14

In order to simplify the situation, only symmetric line outages are considered to this

concept, the reasons of doing so are that:

Asymmetric faults are very difficult to analyse especially in a meshed power

grid with a large number of buses and generators even though the most of the

overhead line fault in transmission system belongs to this type

The most severe fault in transmission system is three-phase fault which

belongs to symmetric type.

A thorough understanding of symmetric faults is a good beginning of analysing

asymmetric faults.

In the following Figure 2-2, two generators are connected to Bus1 and load is in Bus3,

and power flows from Bus1 to Bus3 via Bus2.

Figure 2-2 Example system used to clarify BLR

The red value is the load rate of transmission line in a certain operation condition,

which is calculated as

(2-1)

Page 29: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

15

Only steady state is considered for the power flow contingency issue. As be shown in

the example system, the outage line is isolated from the system by circuit breakers in

each contingency case. Four steps are needed to calculate the Load Rate of Bus k (K = 1, 2,

3…, nb) based on contingency i (i = 1, 2, 3…, nl)

1. Find out all transmission lines which are connecting to Bus k (K = 1, 2, 3…, nb),

the Load Rate of Bus k is only related to the load rate and power flow direction

of its connecting lines.

2. Figure out power flow direction of transmission lines which are connecting to

Bus k, name lines through which power flows out of BusK as OUT Lines, and line

flows power into Bus k as IN Lines

3. Load Rate of Bus k according to contingency i is calculated as following

equation2-2:

(2-2)

4. Load Rate of Bus k on Overall Line Contingencies (OLC) is calculated as

∑(

)

(2-3)

Overall Line Contingencies consist of outage of l4 in Contingency b, outage of l3 in

Contingency c, outage of l1 in Contingency d, and outage of l2 in Contingency e in this

example system. Table 2-1 shows the result of Bus Load Rate for each bus based on the

example system: According to Equation 2-3, Bus1 and Bus2 are defined as starting

terminal and Bus3 is the ending terminal for HVDC line.

Bus1 Bus2 Bus3

BLR on Contingency a 0.7+0.8=1.5 1.5-0.7-0.8=0 -1.5

BLR on Contingency b 0.7+0.8=1.5 1.5-0.7-0.8=0 -1.5

BLR on Contingency c 1.5 1.1+0.9-1.5=0.5 -1.1-0.9=-2.0

BLR on Contingency d 1.5 1.1+0.9-1.5=0.5 -1.1-0.9=-2.0

BLR on Overall Line

Contingency 6.0 1.0 -7.0

Table 2-1 Bus Sensitivity Index for each bus based on the example system

Calculation of Factor2: Distribution of Generation and Load Center (DGLC):

Step 6 This factor is associated with the topology structure of the whole power

system, which can be interpreted to the net power of each bus which

equals to the difference of generating capacity and load consummation

Page 30: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

16

as be shown in equation 2-4, this factor is constant to each bus.

if then make ( )

(2-4)

The transmission operators always want to run the system both safely and cost

effectively at the same, even this is not the situation in most cases. Therefore, besides

operating factor BLR and configuration factor DGLC, the economical aspect should also

be introduced to the algorithm.

Calculation of Factor 3: Generating cost (GC)

Step 7 The GC of each bus can be calculated by equation 2-5, in which f(p) is the

generating cost per unit active power, and are the cost

coefficient which are constant.

if then make ( )

(2-5)

Step 1 to step 7 give the way to solve these three factors which can determine the

optimal placement, the following equation explains the contribution of each factors to

the decision of optimal placement .

Bus Sensitivity Index (BSI):

(2-6)

To any system the bus with highest positive Sensitivity Index is defined as the optimal

starting terminal of VSC-HVDC link and the bus with the lowest negative Sensitivity

Index is considered as the optimal ending terminal for this HVDC line. x, y and z are the

contribution factors, if x=y=z=1, the factor has the relationship with BLR in

Figure 2-3 (a), the other two factors are directly proportional to which

determines the optimal placement, as be shown in Figure 2-3 (b) and (c).

Figure 2-3 (a),(b) and (c) The relationship of these three factors with Bus Sensitivity Index

Page 31: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

17

In Figure 2-4, the flow chart of the algorithm is demonstrated.

Figure 2-4 Flow Chart of the Algorithm

2.3 Simulation Results

The testing systems IEEE14 and IEEE118 are derived from Matpower 4.1, which is an open

sourcing package of MATLAB M-files for solving power flow and optimal power flow

problem.

2.3.1 Simulation Results on IEEE14

Basic introduction of IEEE14 bus system

IEEE14 bus system has 14 buses, 21 transmission lines and 3 Var Compensators

connecting to Bus3, Bus6 and Bus8 which only generate reactive power. In this system

the biggest and cheapest generator is located in Bus1 which is circled out in red and the

load centre is circled out in blue, In order to verify the algorithm’s validity, six

overloaded lines are set manually in order to test the performance of the algorithm, as

be shown in Figure 2-5, the green arrows represent the power flow direction. The

Page 32: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

18

column on the left side displays the load rate in every transmission lines, where the

overloaded lines are bigger than 1.

Figure 2-5 Power flow of IEEE14 system in normal operation

Simulation results on IEEE14

The algorithm has been tested on IEEE14 by setting x=y=z=0. Table 2-2 (a) shows the

simulation results by the proposed algorithm explained in section 2.2, Bus1 has the

highest Sensitivity Index with 72.7 in contrast to the lowest Sensitivity index in Bus3

with BSI equals to -40.15, therefore optimal placement from bus 1 to bus 3 for a VSC-

HVDC line can be identified, the other possible placements such as Bus1 to Bus9, Bus1

to Bus14, Bus1 to Bus9 and Bus1 to Bus10 are also displayed in the table.

(a) (b)

Table 2-2 (a) Simulation result for the first VSC-HVDC line by Algorithm

(b) Simulation result for the second VSC-HVDC line by Algorithm

A VSC-HVDC is installed in the optimal placement from Bus1 to Bus3 in the IEEE14

system in order to reduce the overloaded lines. After installing the VSC-HVDC line, the

Page 33: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

19

amount of overloaded transmission lines is reduced to 1 from 6 in Figure 2-6 without

VSC-HVDC line. The power transmission through the VSC-HVDC line is calculated as

77MW by optimal power flow with fixed generating capacity for all generators except

for the one on slack bus. The VSC-HVDC line parameters show in Table A-1 in Appendix

A.

Figure 2-6 Power flow of IEEE14 system after installing VSC-HVDC line from Bus1 to Bus3

The VSC-HVDC line is capable of reducing the power flow contingencies dramatically;

however, only one VSC-HVDC line is not sufficient to eliminate all overloaded lines,

which means a second line should be taken in to account. For this reason the algorithm

has been executed again to the IEEE14 with one VSC-HVDC line from Bus1 to Bus3,

where an equivalent treatment to the first VSC-HVDC line has been executed in Figure

2-7. In this equivalent treatment the VSC-HVDC line is replaced by a generator G at

ending terminal Bus3 and a load at starting terminal Bus1, and the size of the

equivalent generator and load equal to the real power flow through the HVDC line [18].

Figure 2-7 Equivalent treatment to the first VSC-HVDC line

The optimal placement for the second VSC-HVDC line from Bus1 to Bus9 is calculated

by the algorithm, and the other possibility such as bus2 to bus9, Bus1 to Bus14 and bus1

to bus4 are also shown in Table 2-2 (b).

Page 34: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

20

Adding the second VSC-HVDC line either in the calculated placement from Bus1 to Bus9

or can eliminate the power flow contingencies, the power flow situations after

installing the second VSC-HVDC line are shown in Figure 2-8, from which a conclusion

can be made that the proposed algorithm is capable of determining the optimal

placement for VSC-HVDC line to reduce power flow contingencies in AC system

effectively.

Figure 2-8 Power flow of IEEE14 system after installing VSC-HVDC lines from Bus1 to Bus

and Bus1 to Bus9

Verification of the algorithm In order to evaluate the effectiveness and validity of the proposed algorithm a verifying method is introduced in this section. The verifying method is executed by implementing the VSC-HVDC line randomly between any two buses and the optimal placement can be deduced by comparing the amount of overloaded lines, the situation with the minimum amount of overloaded lines with respect to the optimal placement for VSC-HVDC line. Table 2-3 (a) and (b) provide part of the simulation results from verifying method,

where the optimal placement and other candidates for the first and second VSC-HVDC

lines have been pointed out, in addition, the economical optimisation of the whole

system is also achieved by installing VSC-HVDC lines in the identified optimal

placements where with the biggest and cheapest generating unit. The complete

simulation results by the verifying method is exhibited by Table A-3 and A-4 in

Appendix A

Page 35: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

21

(a) (b)

Table 2-3 (a) Part of Simulation result for the first VSC-HVDC line by verifying method

(b) Part of Simulation result for the second VSC-HVDC line by verifying method

By comparing the simulation results of proposed algorithm and the verifying method

as shown in Table 2-4, the accuracy and effectiveness of the developed algorithm can

be determined although they do not agree with each completely. The algorithm is also

implemented on big system IEEE 118 in next section

Optimal

placement Algorithm Verifying method

First line Bus1 to Bus3 Bus1 to Bus3

Other candidates

Bus1 to Bus9,

Bus1 to Bus14,

Bus1 to Bus4…

Bus1 to Bus4,

Bus1 to Bus9,

Bus1 to Bus14…

Second line Bus1 to Bus9 Bus1 to Bus9

Other candidates

Bus2to Bus9,

Bus1 to Bus4,

Bus1 to Bus3…

Bus2 to Bus9,

Bus1 to Bus4,

Bus1 to Bus6…

Table 2-4 Simulation results comparison of the developed algorithm and verifying

method

2.3.2 Simulation Results on IEEE118

Basic introduction of IEEE118 As shown in Figure 2-9, IEEE118 system has 118 buses 187 transmission lines and 57

generators, the generator centres are circled out by red lines and the load centres are in

blue areas, green arrows indicate the power flow. According to power flow calculation,

there is almost no power exchange between the left part and right part of the system.

Bear the same reason as what have done to IEEE14 system, several line capacities are

set manually so that overloaded line exists in normal operation

Page 36: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

22

Figure 2-9 Generation centre, load centre and power flow of the IEEE118 bus system

Zoom into the overloaded area in the upper left of IEEE118 system, as shown in Figure 2-

11, where 6 red lines are overloaded and green arrows indicate power flow direction.

Table 2-5 (a) and (b) show only a part of the load rates of transmission lines in this area

before and after installing of HVDC line, the whole load rates of transmission lines can

be read in Table A-5 and TableA-6 in Appendix A.

Figure 2-10 Overloaded area of the IEEE118 bus system

Page 37: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

23

(a) (b)

Table 2-5

(a) A part of load rates of transmission lines in overloaded area without VSC-HVDC line

(b) A part of load rates of transmission lines in overloaded area with VSC-HVDC line from

Bus10 to Bus1

Simulation results on IEEE118

Table 2-6 shows part of the likely terminals in IEEE118 system in descending order for

starting terminals and ascending order for ending terminals, among which Bus 10 has

the highest sensitivity index at 182 in contrast to smallest index in Bus 1 at -124;

therefore, the optimal placement for VSC-HVDC is from Bus 10 to Bus 1. The complete

simulation results are in table A-7 in Appendix A.

Table 2-6 The simulation results by the proposed Algorithm

After installing the VSC-HVDC line with parameters is shown as in Table A-2 in

Appendix A in the calculated optimal placement, the 7 overloaded lines are eliminated

by the VSC-HVDC line with 82MW power flow from Bus10 to Bus1, which is shown as in

Figure 2-12, and Table 2-7 shows how much the VSC-HVDC line alleviated the power

flow contingencies in IEEE118 system.

Page 38: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

24

Figure 2-11 Overloaded area of the IEEE118 bus system with VSC-HVDC

Verification of the algorithm

Like what has done in last section, verification on the proposed algorithm is necessary

so that the functionality of it can be judged. Similar to the verifying method on IEEE14

system, VSC-HVDC line is randomly placed in any two buses and the optimal placement

is identified by comparing the amount of overloaded lines.

Table 2-7 Part of the simulation results from verifying method

Table 2-7 shows part of the related simulation results from verifying method, the

placements with smallest amount of overloaded lines are from Bus10 to Bus1 , the same

as the proposed algorithm.

2.4 Conclusion

The effectiveness and accuracy of the proposed algorithm explained in section 2.2 can

be proved by the verifying method mentioned in section 2.2, the simulation results of

these two method are consistent with each other. The proposed algorithm can not only

utilized successfully in small system but can also spread to much more complex system

like IEEE118, according to the excellent performance of the algorithm on testing system

IEEE14 and IEEE118, a reasonable prediction can be made that the proposed algorithm is

capable of applying to more complicated power system with thousand buses in real life.

In addition, the economical optimization of the whole system is also achieved by the

proposed algorithm.

Page 39: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

25

Chapter3 Optimal Placement of VSC-HVDC link to reduce Inter-area Oscillations 3.1 Introduction

With the development of new technologies such as power electronics in nowadays,

more and more loads, generators and other control equipments are added, which

stepped up the complexity and nonlinearity of power systems. These result in many

instability issues such as voltage, phase angle and frequency related problem which

can lead to partial or complete blackout of the system. The importance of these

problems should be never overlooked, even though they seldom cause eventually

blackout and collapse individually.

To maintain synchronism is challenging for complex power system when it subjected

to large disturbances such as loss of tie lines, large load increase, and loss of generators,

because some machines tend to speed up while some others slow down so as to adjust

to post disturbance operation. There is a high possibility for some generating units lose

synchronism with the grid if no control mechanism exists in the system to keep

electrical speed within the safe speed constraint. For this reason, fast exciter or

Automatic Voltage Regulators (AVR) can be introduced in the system as the

countermeasures to eliminate this phenomenon. However, the fast AVR is only able to

give the “coarse adjustment” to limit the electrical speed of generating units and not

capable of maintaining synchronism by controlling the first swing [19]. Therefore,

Power System Stabilizer (PSS) or VSC-HVDC can be used to offer “fine adjustment” to

damp out power oscillations that are also known as electromechanical or low

frequency oscillations.

Oscillations mode are inherent characteristics of power system, it could lead to partial

or full blackout of the system without proper control as it happened in many practical

power systems. There are several different categories of oscillation modes in power

system:

Intra-plant mode oscillations

The Intra-plant mode oscillation happens among machines in the same power

generation site at 2.0 to 3.0 Hz which depends on the generating unit capacity and

connecting reactance, the rest of the system is not affected.

Torsional mode oscillations

This mode is also called high frequency oscillation which is related to turbine generator shaft system in the frequency range of 10-46 Hz. The oscillation is normally caused by a multi-stage turbine generator and its connecting series compensated line [20]. Low Frequency Oscillation (LFO)

Low frequency oscillations are machines rotor angle oscillations in frequency range

from 0.1 -2.0 Hz

Page 40: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

26

The root cause of electrical power oscillations are the unbalance between power

demand and available power at a period of time. In the earliest era of power system

development, the power oscillations are almost non observable because generators are

closely connected to loads, but nowadays, large demand of power to the farthest end of

the system that forces to transmit huge power through a long transmission line, which

results an increasing power oscillations. The phenomenon involves mechanical

oscillation of the rotor phase angle with respective to a rotating frame. Increasing and

decreasing phase angle with a low frequency will be reflected in power transferred

from a synchronous machine as phase angle is strong coupled to power transferred.

The LFO can be classified as local and inter-area mode [21].

Local plant mode oscillations

In this oscillation mode, only one machine swings against the rest of the system in the

frequency range of 1.0 to 2.0 Hz depending on output power and the impedance

connecting to the machine. The affection of this oscillation is localized to the generator

and the connection line, the rest of system maintains unaffected.

Inter-area mode oscillations

This oscillation is normally observed in the scope of the whole system, a large number

of generators are involved. Those involved machines belong to different coherent

groups; generators within a group swing synchronously, oscillated against each other

at 1 Hz or less among these groups [22].

In this chapter inter-area mode oscillations are studied due to its far-ranging influence

to the whole system. This oscillation can also lead to large-scale system disturbances if

cascading outages of transmission lines occur due to oscillatory power swings, like the

black out in Western North America on August 10, 1996, [23]. This accident is caused by

insufficient damping in the system. In the linear model the oscillation is described as a

sinusoid with an exponential decay. The time constant of this exponential decay is a

measure of damping. Even a minor disturbance may excite an expanding oscillation

when damping is negative [24]. The damping of inter-area oscillation is respect to

system characteristics such as grid structure and the operation situation. Hence a full

understanding of the problem would help in identifying countermeasures to handle it.

An advanced benefit of HVDC that has not been widely used is power oscillation

damping (POD) [25]. It is easy to control power flow through line rapidly with fast

acting power electronics such as the IGBT, IGCT and thyristor within the converter

stations. The possibility of implementing HVDC system with POD controllers to damp

inter-area electromechanical oscillations has been demonstrated in paper [25]. The

future power systems are expected to employ large numbers of HVDC lines due to

worldwide interest in large renewable generation sources specially after announcing of

quit nuclear power in Germany. In addition, agreement for new HVAC overhead

transmission lines is becoming increasingly difficult to get because of its bad

performance in long distance and undersea power transmission.

The low frequency oscillation is mainly caused by either high-gain exciters or heavy

power transfers across weak connections. Damping of power system oscillation has

always been a significant consideration for the stable operation of power systems. In

order to increase damping of the system and control power flow in weak connections,

Page 41: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

27

an algorithm with the objective to find out the weak connections in an AC grid where

VSC-HVDC line can be installed to reduce inter-area oscillation is developed.

3.2 Algorthim

3.2.1 Concept of slow coherency

In a meshed AC system, the weak connections are normally located in the interface

among the out-of-step generator groups and they are determined by its topology

structure and real-time operating state. In this chapter, an algorithm based on the slow

coherency theory studied the sensitivity of line parameters to slow mode eigenvaules.

The weak connections can be identified by comparing sensitivity values, the higher the

value the more likely the transmission line to be the weak connection [26].

Slow coherency is originally used for developing of dynamic equivalents for transient

stability studies [27]. In paper [28], [20] and [21] some algorithms like time domain

approach, frequency domain approach and electrical distance method have been

developed to specify the slow coherent generator groups. Two hypotheses have been

made in these methods:

The grouping of slow coherent generators is not sensitive to the severity of

disturbances.

The inter-area oscillation modes among slow coherent groups are independent

of the complexity of generating unit model.

The first assumption is based on the Practical observation experience that the slow

coherency groups of the generators are not radically changed when the clearing time

of a certain disturbance is raised. The second assumption is based on the fact that the

basic network property such as inter-area modes does not change significantly when

different generator model are used [27].

Slow coherency theory is normally utilized to identify the theoretically weak connection

in a power system. Paper [20] concludes that the weakest connection in an

aggregated power system appears among the slow coherent generator groups. In fact,

slow coherency is a physical evidence of a weak connection, which is a network

characteristic [27] . The classical second order generator electromechanical model is

accurate enough to identify the weak connection. In many large power systems, there

always exists some groups with the characteristic that the machines inside one group

tend to swing synchronously, and weak connection normally locates among these

groups.

Generally speaking, the slow coherency theory based grouping method has the

following obvious advantage: The coherent groups of generators based on slow

coherency theory do not impact by varying the size of disturbance and complexity of

system model. Papers [29] and [30] introduced a power system analysis method which

based on singular perturbation and multi-time-scale theory. Even though the method

Page 42: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

28

could not discern the weak connection of the system, it provides a meaningful clue:

connections among coherent groups influenced by slow mode eigenvalues significantly,

and lines within groups are not sensitive to slow mode eigenvalues. Based on this

reality, a weak connection identification algorithm based on the sensitivity of line

parameters to slow mode eigenvalues is demonstrated in this chapter. The basic idea is

to identify the cluster oscillation related slow mode eigenvalues and then calculate the

sensitivity of each line parameters with respect to the slow mode eigenvalues, the line

with the highest sensitivity is considered as the weakest connection in the system [26].

The weak connection is chose as the optimal placement to install VSC-HVDC line so as

to reduce the inter-area oscillations by proper action such as fast power flow control.

Two simplified power system model are utilized without any negative influence to the

simulation result in this chapter

Classical second order generator mode without damping

Constant impedance load mode

3.2.2 Analytical expression

The flow chart of the algorithm can be seen from Figure 3-1

Figure 3-1 Flow chart of the algorithm

The algorithm consists of several steps:

Step 1

Input power system parameters such as the resistance, reactance, conductance and

susceptance of transmission line, transformer ratio and dynamic parameters of

generators etc.

Page 43: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

29

Step 2

Base on step 1 the linearized dynamic mode ̈ can be formed, matrix A is the

key component in this equation, ̈ manifests the second order differentiation of

power angle deviation of generators. The way of calculating matrix A is shown in the

following:

Under the circumstances of applying second order generator mode and constant

impedance load mode, the electromechanical oscillation mode of the power system

can be expressed as [26]:

{

(

)

(3-1)

[ ] Power angle vector of generators

{ } Inertial time constant of generators

[ ] Constant vector of mechanical input power

[ ] Column vector of electrical output power

[ ]

Excitation electromotive force of generator

[

]

Transient reactance of generator

[ ]

Terminal voltage of generator

[ ]

Terminal voltage angle of generator

Number of generators in the system

Norton equivalent input current of generators

The excitation electromotive force and its power angle can be calculated by following

equation:

(3-2)

(

) is the Norton equivalent input current of the generator

bus as be shown in Figure 3-2 , and can be calculated from power flow

calculation and is the power generated by generator:

Figure 3-2 Norton equivalent input current of generator

Page 44: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

30

represents the equivalent input current vector of all buses,

and are the real and imaginary part of the equivalent input current and

only those elements corresponding to generator buses are non-zero.

T is a n x ng dimension matrix, the row k (k = 1…, n; n is the number of bus) is

responding to the Bus k: if there is no generator connecting to Bus k then all elements

in row k are zero; if Bus k with generator i (i =1….,ng; ng is the number of generator)

connected to it then only element and other elements in this row are zero.

Bus admittance matrix

Bus admittance matrix of power system is which including the

equivalent admittance of load, Y, G and B are n x n dimension matrix.

Buses voltage vector

expresses the buses voltage vector , and are the real and

imaginary part the voltage vector respectively:

[ ]

[ ]

(3-3)

[ ] is the voltage angle vector of bus and n is the number of bus

Make [

]

then [

] [

] is linearized as [26]:

[

] [

] [

] (3-4)

, and are the deviations of and separately,

{ }

{ }

(3-5)

{ } { }

{ } { }

(3-6)

Make [

] and [

] , then equation 3-4 can be expressed

as [

] . Linearize equation 3-1 at the equilibrium of the

electromechanical oscillation mode of the system:

Page 45: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

31

[

] (3-7)

, and are the deviations of and separately, make

[

]

[

]

(3-8)

Substitute and into equation B-9:

[

] [

] [

] [

] (3-9)

Substitute [

], and [

] to equation 3-7, the matrix A

of a power system can be calculated by the following equation 3-9 [26]

(3-10)

Step 4

Eigenvalues of matrix A can be calculated in ascending order { } is the

number of generators, { √ √ √ } represent the potential oscillation

modes of the system [26], √ , from which the damping coefficient is

calculated as

√ and the frequency of oscillation in Hertz is

. Figure 3-3

gives relationship between eigenvalue and stability of the system.

Figure 3-3 Eigenvalue and stability of system

In general, is very close to zero which means represents zero oscillation mode. The

slow mode eigenvalues { } (r is the number of slow mode eigenvalue)

are the r smallest eigenvalues. Therefore, the slow mode can be expressed as [26]:

(3-11)

Page 46: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

32

Step 5

Calculate the sensitivities of each transmission line to slow mode

eigenvalues . The sensitivity consists of two factors [26]:

The sensitivity of line susceptance b with respect to slow mode eigenvalues

(3-12)

The sensitivity of line conductance g with respect to slow mode eigenvalues

(3-13)

( ) and are the left and right eigenvector of slow mode , , ,

and are structure matrix, M is a 1 x nb dimension vector; If a transmission line L is connected from Bus i to Bus j, then M (i) = 1, M (j) = -1, the other elements are zero

[

] [

] (3-14)

[

] [

] (3-15)

For a transmission line, the resistance r and reactance x vary in proportion to the line

distance, therefore, conductance g and susceptance b of line are varied in

proportionality factor of -r/x due to

, which conclude to sensitivity

of Line l to slow mode eigenvalues [26]:

(3-16)

By employing the method mentioned above, the weak connection in system can be

specified by comparing the absolute value of sensitivities, the weakest connection

corresponding to highest absolute sensitivity value. The weak connection is defined as

the optimal placement for VSC-HVDC line to reduce the inter-area oscillation in an AC

system. The effectiveness and validity of this algorithm is verified in Kundur second

order system and IEEE Two Area RTS-24 system in next section.

3.3 Simulation results

3.3.1 Simulation results on Kundur second order system

The testing system in Figure 3-4 is derived from [31] , this system has two similar areas

which are connected by a weak connection Bus7 to Bus8 and Bus8 to Bus9. Four

generators with generating parameters in Table 3-1 , and the dynamic data and line

parameters are shown in table Table A-9in Appendix A.

Page 47: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

33

Figure 3-4 Kundur second order system [31]

Table 3-1 Generating parameters

Operation case one

In the first operation case, assume that the load in Bus 7 and Bus 9 equal to each other

with 1367MW, and there is almost no power transmission between two areas, and the

local generators can fulfil the load demand in both areas.

The proposed algorithm is employed to this operation case, table 3-2 shows the

simulation result. It can be seen obviously that transmission lines from Bus 7 to Bus 8

and Bus 9 to Bus 8 are specified as the weak connections due to their high sensitivity

to slow mode eingenvalues. This result is consistent with the reality what has already

been given, which means the algorithm demonstrated in section 3.2 is capable of

identifying weak connection in a given AC networks effectively. The weak connection is

considered as the optimal placement for VSC-HVDC line to reduce the inter-area

oscillations. Big power flow through weak tie is one of the significant causes to inter-

area mode oscillations.

Table 3-2 Simulation results on operation case one

Operation case two

In the second operation case, assume that the load in both Bus 7 and Bus 9 are 967MW

and in is 1767MW, unbalanced power between two areas occurs, 400MW power is

transmitted from area 1 to area 2.

Page 48: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

34

Apply The proposed algorithm to the this operation case, the simulation results in Table

3-3 verified the effectiveness of the algorithm, in this unbalanced case, sensitivity of

lines from Bus9 to bus8 and Bus7 to Bus8 are higher than the first operation case due

to the extra 400MW power flow between these lines, which can conclude that the

algorithm can also reflect the power distribution among the system, especially in weak

connections.

Table 3-3 Simulation results on operation case two

Eigenvalue analysis

In this chapter, the eigenvalue of a linearized power system model can be expressed as

√ , from which the damping coefficient is calculated as

√ and the

frequency of oscillation in Hertz is

,

From right eigenvector and left eigenvectors of eigenvalues, the participation

factor P (ng x ng dimension matrix, ng is the number of eigenvalues) can be deduced by

, it is a measure of the relative participation of one generator’s state in ith

mode and can be used in identifying problematic machines for placement for PSS in

large power system [32]. Figure 3-6 shows the participation factor of four generators

rotor speed in Kundur testing system with respect to four oscillation modes. The higher

the participation factor of one generator to a certain mode, the more the generator

participate in this mode.

(a)

Page 49: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

35

(b)

Figure 3-5 (a) and (b) Participation factor of Kundur second order system

Mode 1 and mode 2 with G1, G2, G3 and G4 participated and oscillation frequency at

0.038 Hz and 0.098Hz are inter-area oscillations, and mode 3 and mode 4 are

considered as local area oscillation modes due to their local machines swing against

each other, as been shown in Figure 3-6 and Table 3-4.

Mode Eigenvalues frequency (Hz) Damping Ratio Oscillation mode

1 -0.056 0.038 0 Inter-area

2 -0.376 0.098 0 Inter-area

3 -0.443 0.106 0 Local mode in area 1

4 -0.460 0.110 0 Local mode in area 2

Table 3-4 Oscillation modes in kundur second order system

3.3.2 Simulation result on IEEE Two Area RTS-24 system

Testing the algorithm on the small Kundur second order system successfully does not

mean it could be expanded to big systems. For this reason, in this section the algorithm

is implemented in IEEE Two Area RTS-24 system to verify its effectiveness for big

networks. The testing system is connected by two RTS-24 systems through three weak

tie lines: Bus7 to Bus27, Bus13 to Bus39 and Bus23 to Bus41. The system’s parameters

refer to paper [33].

G 1 0.2026 0.2261 0.5755 -0.0041

G 2 0.2891 0.2571 0.4771 -0.0233

G 3 0.2258 0.1424 0.008 0.6238

G 4 0.2258 0.3745 -0.0606 0.4036

Mode 1 Mode 2 Mode 3 Mode 4

Participation factor

Page 50: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

36

Figure 3-6 IEEE Two Area RTS-24 system [33]

Table 3-5 shows the part of simulation result on IEEE Two Area RTS-24 system, in

descending order, where Bus23 to Bus41 and Bus13 to Bus39 are specified as the

weakest connection in the whole testing system with sensitivity value at 60e-5 and

46e-5 respectively, Bus7 to Bus27 in the third place with relatively lower sensitivity 16e-5

than the first two lines due to its low power transmission around at 12MW. The

simulation result is consistent with the expected outcome. And the complete data refer

to Table A-8 in Appendix A

Table 3-5 Part of simulation result on IEEE Two Area RTS-24 system

From To

Sensitivity on

slow mode 1

(10 x -5)

Sensitivity on

slow mode 2

(10 x -5)

Sensitivity on

slow mode 3

(10 x -5)

Sensitivity on

slow mode 4

(10 x -5)

Total

Sensitivity

(10 x -5)

23 41 1.80 1.80 3.50 60.00 60.00

13 39 5.80 5.80 3.00 37.00 46.00

7 27 2.50 2.50 1.70 13.00 16.00

13 23 1.90 1.90 0.34 9.90 13.00

1 3 3.10 3.10 0.61 6.70 12.00

14 16 1.30 1.30 4.90 18.00 11.00

36 47 9.80 9.80 5.20 0.12 11.00

3 24 0.21 0.21 0.15 10.00 10.00

12 23 2.90 2.90 0.38 3.90 9.00

37 47 7.90 7.90 4.10 0.35 8.60

25 27 3.00 3.00 0.16 1.10 6.80

45 46 3.90 3.90 1.20 0.09 6.00

8 9 0.34 0.34 0.01 5.20 5.90

3 9 0.38 0.38 1.30 5.90 5.30

15 24 0.16 0.16 0.03 4.70 4.80

11 14 0.08 0.08 2.00 2.60 4.50

Page 51: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

37

3.4 Conclusion

Inter-area oscillations are a part of the systematic property of interconnected power

systems. Large-scale power systems with weak connections transmitting large power

tend to exhibit such modes of oscillations. As mentioned in the introduction, these

oscillations are caused by swing among coherent groups. This phenomenon may due to

small disturbances such as varying in loads or may happen as an aftermath of large

disturbances. Low frequency inter-area oscillations (LFIO) are most likely to be the type

of instability especially in interconnected power systems.

Network configuration, generator excitation systems and load characteristics affect the

mode properties of LFIO and stability of inter-area modes interconnected systems. In

addition, the natural frequency and damping of inter-area mode oscillations depend on

the weakness of inter-area ties and the power transmitted through them [31].

Attention has to be paid that the effects resulting from small disturbances might not

be instantaneously recognized, however, over a period time; they may become severe

and furthermore cause collapse of the system.

In this chapter, an algorithm derived from [26] with the function of specify weak

connections in AC power system is tested on Kundur second order system and IEEE Two

Area RTS-24 system, the simulation result shows its effectiveness and validity.

In Kundur second order system transmission lines from Bus7 to Bus8 and Bus8 to Bus9

with highest sensitivity to slow mode eigenvalues are identified as weak connections.

And in IEEE Two Area RTS-24 system the three additional tie line are calculated as the

weak connections by the proposed algorithm.

Page 52: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

38

Chapter4

Conclusions and Future Work This chapter draws conclusions and presents some suggestions for further work.

4.1 Conclusions

The interest on research of VSC-HVDC has been growing after the world’s first VSC-

HVDC installation into Gotland, Sweden, 1997. The recent developments in

semiconductors and control equipment have made VSC-HVDC feasible. Due to the use

of VSC technology and PWM the VSC-HVDC has a number of potential advantages as

compared with classical HVDC, such as short circuit current reduction, rapid and

independent control of active and reactive power, etc. With those advantages VSC-

HVDC will likely be widely used in future transmission and distribution systems. In this

thesis, two different algorithms with the objectives to reduce power flow contingencies

and inter-area oscillations in AC power system are demonstrated.

In chapter 1, some basic structure of classic HVDC systems and their applications are

indicated . The advantages and disadvantages of HVAC, classic HVDC and VSC-HVDC

have been demonstrated. In addition, the application of VSC-HVDC are introduced.

Chapter 2 studies the causes and possible solutions of power flow contingencies; an

algorithm is developed to identify the optimal placement for VSC-HVDC line in order to

reduce the power flow contingencies of an AC grid. This algorithm has been tested on

IEEE14 and IEEE118 bus systems, and its effectiveness and validity have been evaluated

by the verifying method. In addition, the economical optimization of these testing

systems is achieved as well by installing the VSC-HVDC line in the optimal placement

calculated by the proposed algorithm.

Chapter 3 describes different oscillation modes and their causes in power system, and

an algorithm is developed to specify optimal placement for VSC-HVDC line in order to

reduce the inter-area oscillation in a given AC grid The algorithm is tested on Kundur

second order system and IEEE Two Area RTS-24 system, the weak connections in testing

system are specified by this algorithm and the oscillation modes is analysed in Kundur

second order system.

4.2 Future Work

As previously mentioned, modern HVDC systems can transfer up to three times more

power across the same wires and pylons as conventional AC systems, in addition, the

VSC-HVDC has lower short circuit current reduction and more rapid and independent

control of active and reactive power. With those advantages VSC-HVDC will likely be

widely used in future transmission and distribution systems. To further evaluate the

pros and cons of VSC technology for industrial power systems, more research can be

involved in the future work:

Page 53: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

39

The two algorithms introduced in chapter 2 and chapter 3 are far from perfect due to

the knowledge and time limit of the author. However, this does not impact of the

meaning of the work has been done by the author. In order to optimize the algorithm,

some valuable works still need to be considered in the future.

Control scheme of VSC-HVDC in both algorithm

The control strategy as the key part of VSC technology is out the scope of this

thesis due to its complexity

Consideration of asymmetric line contingency

The asymmetric line outage can be considered in the future work in order to

accurate the algorithm in chapter 2

Increase the function of algorithm

Algorithm with function of finding out optimal placement for VSC-HVDC line to

connect renewable energies and asynchronous networks

Combine the two algorithms to one

Combine the two algorithms to one so as to find out the optimal placement

which can reduce power flow contingencies and inter-area oscillations at the

same time

Page 54: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

40

Appendix A Table A - 1 Parameters of VSC-HVDC line in IEEE14

Reactance Phase Reactor R(p.u.) 0

Reactance Phase Reactor X(p.u.) 0.1643

Reactance Transformer R(p.u.) 0

Reactance Transformer X(p.u.) 0.113

Shunt Filter(Mvar) 15.15

Tap 0

Shift 0

AC Converter Voltage(kV) 230

Base MVA Converter 100

P Rectifier(MW) -15.34

P Inverter(MW) 15.34

Q Rectifier(MW) -0.17

Q Inverter(MW) 0.8

P max(MW) 100

P min(MW) -100

Q max(MW) 15

Q max(MW) -15

Udc nominal(pole-groud)kV 80

Udc Rectifier(p.u.) 1.1

Udc Inverter(p.u.) 1.1

Cable Resistance(p.u.) 0.05

Page 55: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

41

Table A - 2 Parameters of VSC-HVDC line in IEEE118

R1 (p.u.) 0

X1 (p.u.) 0.1643

R2 (p.u.) 0

X2 (p.u.) 0.1643

Shunt Filter 1 (Mvar in p.u.) -0.1515

Shunt Filter 2 (Mvar in p.u.) -0.1515

n1 (p.u.) 1

n2 (p.u.) 1

Rdc (p.u.) 0.05

a1 (AC system p.u.) 11.033e-3*30/100

b1 (AC system p.u.) 3.464e-3*30/100

c1 (AC system p.u.) 4.400e-3*30/100

a2 (AC system p.u.) 11.033e-3*30/100

b2 (AC system p.u.) 3.464e-3*30/100

c2 (AC system p.u.) 6.667e-3*30/100

Converter 1 P setpoint (AC system p.u.) 1

Converter 1 Q setpoint (AC system p.u.) -0.0016

Udc setpoint (DC system p.u.) 1.0932829

Converter 2 Q setpoint (AC system p.u.) -0.0403

Uac setpoint converter 1 1

Uac setpoint converter 2 1

Converters Pmin (MW) -100

Converters Pmax (MW) 100

Converters Qmin (Mvar) -15

Converters Qmax (Mvar) 15

Udc min (DC system p.u.) 0.9

Udc max (DC system p.u.) 1.1

Converter 1 control 0

Converter 2 control 0

Page 56: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

42

Table A - 3 Simulation Results of after installing first HVDC line on IEEE14 by verifying

method

From To

Generatio

n Cost

$/hour

Amount

of

Overloade

d lines

1 3 7982 2

1 4 8002 2

1 9 8015 2

1 14 8033 2

1 6 8048 3

1 7 8009 3

1 10 8032 3

1 11 8056 3

1 12 8072 3

1 13 8042 3

1 5 8033 4

1 8 8011 4

2 9 8067 4

1 2 8099 5

2 3 8038 5

2 4 8061 5

2 6 8092 5

2 7 8065 5

2 8 8066 5

2 10 8074 5

2 13 8102 5

5 7 8109 5

5 8 8111 5

5 9 8107 5

5 10 8107 5

5 11 8111 5

5 13 8107 5

5 14 8099 5

2 5 8084 6

2 11 8088 6

2 12 8095 6

2 14 8067 6

3 5 8101 6

4 5 8108 6

4 14 8108 6

5 12 8111 6

6 7 8115 6

6 9 8113 6

6 10 8113 6

6 14 8105 6

3 4 8111 7

3 6 8108 7

3 7 8113 7

3 8 8117 7

3 9 8111 7

3 10 8114 7

3 11 8115 7

3 12 8118 7

3 13 8117 7

3 14 8116 7

4 6 8112 7

4 7 8114 7

4 8 8117 7

4 9 8112 7

4 10 8112 7

4 11 8114 7

4 12 8115 7

4 13 8113 7

5 6 8113 7

6 8 8118 7

6 11 8116 7

6 12 8116 7

6 13 8111 7

7 8 8118 7

7 9 8115 7

7 10 8114 7

7 11 8116 7

7 12 8117 7

7 13 8115 7

7 14 8110 7

8 9 8116 7

8 10 8117 7

8 11 8119 7

8 12 8121 7

8 13 8118 7

8 14 8112 7

9 10 8113 7

9 11 8114 7

9 12 8115 7

9 13 8113 7

9 14 8109 7

12 14 8114 7

13 14 8114 7

11 14 8111 7

10 11 8115 7

12 13 8118 7

11 12 8118 7

10 12 8115 7

11 13 8115 7

10 13 8114 7

10 14 8111 7

Page 57: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

43

Table A - 4 Simulation Results after installing second HVDC line on IEEE14 by Verifying method

From To

Generation

Cost

$/hour

Amount of

Overloaded

lines

1 9 8012 0

2 9 8042 0

1 4 8003 1

1 6 8035 1

1 7 8008 1

1 11 8041 1

1 12 8049 1

1 13 8027 1

1 14 8020 1

2 4 8038 1

2 6 8060 1

2 7 8041 1

2 8 8042 1

2 10 8047 1

2 11 8058 1

2 12 8063 1

2 13 8048 1

2 14 8039 1

3 7 8078 1

3 8 8080 1

3 9 8076 1

3 10 8076 1

3 11 8079 1

3 13 8075 1

3 14 8068 1

4 14 8073 1

5 7 8077 1

5 9 8075 1

5 10 8074 1

5 13 8073 1

5 14 8066 1

6 14 8071 1

1 2 8073 2

1 3 8032 2

1 8 8010 2

1 10 8024 2

2 3 8062 2

2 5 8052 2

3 4 8112 2

3 5 8079 2

3 6 8082 2

3 12 8080 2

4 5 8076 2

4 7 8080 2

4 8 8082 2

4 9 8079 2

4 10 8078 2

4 11 8080 2

4 12 8080 2

4 13 8078 2

5 6 8079 2

5 8 8079 2

5 11 8077 2

5 12 8077 2

6 7 8081 2

6 8 8084 2

6 9 8079 2

6 10 8079 2

6 11 8081 2

6 12 8081 2

6 13 8076 2

7 8 8083 2

7 9 8080 2

7 10 8080 2

7 11 8082 2

7 12 8082 2

7 13 8080 2

7 14 8075 2

8 9 8082 2

8 10 8082 2

8 11 8084 2

8 12 8085 2

8 13 8083 2

8 14 8077 2

9 10 8079 2

9 11 8080 2

9 12 8080 2

9 13 8079 2

9 14 8074 2

12 14 8080 2

13 14 8080 2

11 14 8077 2

10 11 8081 2

10 12 8081 2

12 13 8083 2

11 12 8083 2

10 14 8076 2

11 13 8081 2

10 13 8079 2

1 5 8022 3

4 6 8079 3

Page 58: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

44

Table A - 5 Line load rate of IEEE118 before installing VSC-HVDC line

From Bus To Bus Load Rate

1 2 0.691

1 3 1.21

2 12 1.09

3 5 1.18

3 12 0.579

4 5 0.712

4 11 0.665

5 6 0.667

5 11 0.672

6 7 0.663

7 12 0.732

8 9 1.12

8 5 1.02

8 30 0.772

9 10 1.12

11 12 0.711

11 13 0.683

12 14 0.641

12 16 0.459

12 117 0.66

13 15 0.338

14 15 0.461

15 17 0.664

15 19 0.791

15 33 0.444

16 17 0.656

17 18 0.677

17 31 0.754

17 113 0.313

18 19 0.785

19 20 0.467

19 34 0.554

20 21 0.588

21 22 0.636

22 23 0.656

23 24 0.6

23 25 0.689

23 32 0.644

24 70 0.551

24 72 0.73

25 27 0.671

26 25 0.576

26 30 0.653

27 28 0.656

27 32 0.638

27 115 0.671

28 29 0.64

29 31 0.693

30 17 0.688

30 38 0.665

31 32 0.684

32 113 0.648

32 114 0.571

33 37 0.861

34 36 0.68

34 37 0.772

34 43 0.261

35 36 0.709

35 37 0.71

37 39 0.47

37 40 0.445

38 37 0.614

38 65 0.573

39 40 0.38

40 41 0.278

40 42 0.632

41 42 0.905

42 49 0.492

42 49 0.492

43 44 0.581

44 45 0.597

45 46 0.645

45 49 0.657

46 47 0.628

46 48 0.724

47 49 0.978

47 69 0.615

48 49 0.65

49 50 0.655

49 51 0.657

49 54 0.634

49 54 0.634

49 66 0.475

49 66 0.475

49 69 0.599

50 57 0.627

51 52 0.65

51 58 0.583

52 53 0.613

53 54 0.581

54 55 0.748

54 56 0.756

54 59 0.418

55 56 0.88

55 59 0.441

56 57 0.601

56 58 0.363

56 59 0.42

56 59 0.42

59 60 0.56

59 61 0.581

60 61 0.669

60 62 0.406

61 62 0.874

62 66 0.6

62 67 0.579

63 59 0.649

63 64 0.647

64 61 0.222

64 65 0.627

65 66 0.399

65 68 0.613

66 67 0.624

68 69 0.783

68 81 0.752

68 116 0.7

69 70 0.635

69 75 0.649

69 77 0.539

70 71 0.698

70 74 0.723

70 75 0.596

71 72 0.533

71 73 0.789

74 75 0.668

75 77 0.75

75 118 0.685

76 77 0.729

76 118 0.913

77 78 0.783

77 80 0.455

77 80 0.455

77 80 0.455

77 82 0.641

78 79 0.447

79 80 0.515

80 96 0.742

80 97 0.698

80 98 0.551

80 99 0.562

81 80 0.402

82 83 0.497

82 96 0.702

83 84 0.529

83 85 0.53

84 85 0.534

85 86 0.7

85 88 0.533

85 89 0.573

86 87 0.682

88 89 0.601

89 90 0.383

89 90 0.383

89 92 0.352

89 92 0.352

90 91 0.415

91 92 0.409

92 93 0.829

92 94 0.859

92 100 0.877

92 102 0.8

93 94 0.902

94 95 0.763

94 96 0.796

94 100 0.782

95 96 0.905

96 97 0.824

98 100 0.635

99 100 0.942

100 101 0.965

100 103 0.686

100 104 0.671

100 106 0.672

101 102 0.834

103 104 0.738

103 105 0.711

103 110 0.678

104 105 0.656

105 106 0.473

105 107 0.649

105 108 0.725

106 107 0.664

108 109 0.734

109 110 0.807

110 111 0.664

110 112 0.719

114 115 0.235

Page 59: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

45

Table A - 6 Line load rate of IEEE118 after installing VSC-HVDC from Bus10 to Bus 1

From Bus To Bus Load Rate

1 2 0.969

1 3 0.89

2 12 0.8101

3 5 0.723

3 12 0.6294

4 5 0.6556

4 11 0.5805

5 6 0.5937

5 11 0.5926

6 7 0.4811

7 12 0.3258

8 9 0.9449

8 5 0.8559

8 30 0.6959

9 10 0.9432

11 12 0.4667

11 13 0.73

12 14 0.8059

12 16 0.6965

12 117 0.6604

13 15 0.5213

14 15 0.6668

15 17 0.6419

15 19 0.8293

15 33 0.5283

16 17 0.4465

17 18 0.6711

17 31 0.7648

17 113 0.3065

18 19 0.7712

19 20 0.4448

19 34 0.5484

20 21 0.5761

21 22 0.6275

22 23 0.6486

23 24 0.6126

23 25 0.6872

23 32 0.6397

24 70 0.5295

24 72 0.7287

25 27 0.6681

26 25 0.5694

26 30 0.6561

27 28 0.6517

27 32 0.6292

27 115 0.6681

28 29 0.631

29 31 0.7004

30 17 0.6633

30 38 0.6594

31 32 0.6768

32 113 0.6365

32 114 0.5761

33 37 0.8127

34 36 0.6818

34 37 0.768

34 43 0.2626

35 36 0.7129

35 37 0.7088

37 39 0.4719

37 40 0.4471

38 37 0.6102

38 65 0.5699

39 40 0.383

40 41 0.2815

40 42 0.6226

41 42 0.8975

42 49 0.4907

42 49 0.4907

43 44 0.5722

44 45 0.592

45 46 0.6422

45 49 0.6547

46 47 0.6262

46 48 0.7225

47 49 0.9798

47 69 0.6123

48 49 0.6496

49 50 0.6554

49 51 0.6571

49 54 0.6345

49 54 0.6345

49 66 0.4746

49 66 0.4746

49 69 0.596

50 57 0.6274

51 52 0.6505

51 58 0.5832

52 53 0.613

53 54 0.5811

54 55 0.749

54 56 0.7565

54 59 0.4175

55 56 0.8806

55 59 0.4405

56 57 0.6017

56 58 0.3636

56 59 0.42

56 59 0.42

59 60 0.5597

59 61 0.5804

60 61 0.6691

60 62 0.4058

61 62 0.8732

62 66 0.6

62 67 0.5787

63 59 0.649

63 64 0.6464

64 61 0.2218

64 65 0.6272

65 66 0.3988

65 68 0.6245

66 67 0.6246

68 69 0.7784

68 81 0.7498

68 116 0.7002

69 70 0.632

69 75 0.6478

69 77 0.5363

70 71 0.6856

70 74 0.726

70 75 0.5921

71 72 0.5149

71 73 0.7889

74 75 0.6659

75 77 0.749

75 118 0.6852

76 77 0.7285

76 118 0.9144

77 78 0.7825

77 80 0.4552

77 80 0.4552

77 80 0.4552

77 82 0.6409

78 79 0.447

79 80 0.5153

80 96 0.7425

80 97 0.6978

80 98 0.5509

80 99 0.5623

81 80 0.4018

82 83 0.4972

82 96 0.703

83 84 0.529

83 85 0.5295

84 85 0.5343

85 86 0.7003

85 88 0.533

85 89 0.5725

86 87 0.6824

88 89 0.6009

89 90 0.3827

89 90 0.3827

89 92 0.3521

89 92 0.3521

90 91 0.4147

91 92 0.4094

92 93 0.829

92 94 0.8587

92 100 0.8774

92 102 0.8004

93 94 0.902

94 95 0.7631

94 96 0.7964

94 100 0.782

95 96 0.9054

96 97 0.8245

98 100 0.6351

99 100 0.9416

100 101 0.9647

100 103 0.686

100 104 0.6709

100 106 0.6722

101 102 0.834

103 104 0.7379

103 105 0.7108

103 110 0.6777

104 105 0.6558

105 106 0.4734

105 107 0.6486

105 108 0.7247

106 107 0.6643

108 109 0.7337

109 110 0.8074

110 111 0.6644

110 112 0.7194

114 115 0.2506

Page 60: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

46

Table A - 7 Simulation Results of IEEE118 by the proposed algorithm

Bus Bus Sensitivity

Index

Terminal

10 182.11 starting

69 70.19 starting

89 38.96 starting

26 38.86 starting

80 37.04 starting

65 36.11 starting

12 21.18 starting

61 15.59 starting

8 8.78 starting

111 5.09 starting

42 4.83 starting

92 3.98 starting

56 3.96 starting

66 3.61 starting

49 2.3 starting

87 2.28 starting

15 2.13 starting

54 1.69 starting

77 1.34 starting

25 0.96 starting

118 0.46 starting

70 0.36 starting

18 0.27 starting

5 0.23 starting

27 0.12 starting

101 0.12 starting

97 0.08 starting

106 0.08 starting

81 0.04 starting

95 0.04 starting

103 0.04 starting

11 0.03 starting

48 0.03 starting

7 0.02 starting

93 0.02 starting

85 0.01 starting

109 0.01 starting

17 0 starting

24 0 starting

32 0 starting

35 0 starting

37 0 starting

63 0 starting

91 0 starting

102 0 starting

108 0 starting

1 -124.13 ending

116 -41.53 ending

76 -31.39 ending

55 -22.92 ending

74 -21.35 ending

107 -12.57 ending

19 -12.24 ending

99 -9.88 ending

36 -9.28 ending

78 -9.26 ending

112 -9.15 ending

90 -9.13 ending

82 -8.71 ending

62 -5.03 ending

41 -4.99 ending

98 -4.11 ending

3 -3.92 ending

33 -3.65 ending

29 -3.64 ending

86 -3.54 ending

53 -3.02 ending

117 -3 ending

16 -2.77 ending

100 -2.24 ending

34 -1.9 ending

13 -1.83 ending

40 -1.67 ending

115 -1.62 ending

59 -1.47 ending

73 -1.44 ending

2 -1.1 ending

43 -1.1 ending

47 -0.59 ending

114 -0.31 ending

96 -0.29 ending

113 -0.21 ending

72 -0.2 ending

58 -0.19 ending

14 -0.18 ending

104 -0.13 ending

94 -0.11 ending

20 -0.09 ending

79 -0.09 ending

39 -0.08 ending

45 -0.08 ending

88 -0.08 ending

4 -0.04 ending

105 -0.04 ending

31 -0.03 ending

67 -0.02 ending

110 -0.02 ending

21 -0.01 ending

46 -0.01 ending

51 -0.01 ending

52 -0.01 ending

64 -0.01 ending

75 -0.01 ending

83 -0.01 ending

6 0 ending

9 0 ending

22 0 ending

23 0 ending

28 0 ending

30 0 ending

38 0 ending

44 0 ending

50 0 ending

57 0 ending

60 0 ending

68 0 ending

71 0 ending

84 0 ending

Page 61: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

47

Table A - 8 Simulation Results of IEEE Two Area RTS-24 system

From To

Sensitivity on

slow mode 1 (10 x -5)

Sensitivity on

slow mode 2 (10 x -5)

Sensitivity on

slow mode 3 (10 x -5)

Sensitivity on

slow mode 4 (10 x -5)

Total

Sensitivity (10 x -5)

23 41 1.80 1.80 3.50 60.00 60.00

13 39 5.80 5.80 3.00 37.00 46.00

7 27 2.50 2.50 1.70 13.00 16.00

13 23 1.90 1.90 0.34 9.90 13.00

1 3 3.10 3.10 0.61 6.70 12.00

14 16 1.30 1.30 4.90 18.00 11.00

36 47 9.80 9.80 5.20 0.12 11.00

3 24 0.21 0.21 0.15 10.00 10.00

12 23 2.90 2.90 0.38 3.90 9.00

37 47 7.90 7.90 4.10 0.35 8.60

25 27 3.00 3.00 0.16 1.10 6.80

45 46 3.90 3.90 1.20 0.09 6.00

8 9 0.34 0.34 0.01 5.20 5.90

3 9 0.38 0.38 1.30 5.90 5.30

15 24 0.16 0.16 0.03 4.70 4.80

11 14 0.08 0.08 2.00 2.60 4.50

16 19 0.35 0.35 0.05 3.50 4.10

8 10 0.32 0.32 0.10 3.40 3.90

11 13 0.48 0.48 1.40 2.00 3.60

27 48 2.30 2.30 0.94 0.02 3.60

17 22 3.30 3.30 0.98 9.00 3.40

27 33 0.62 0.62 0.02 3.10 3.40

32 33 1.00 1.00 0.44 1.50 3.20

19 20 0.42 0.42 0.09 2.30 3.00

19 20 0.42 0.42 0.09 2.30 3.00

41 46 3.30 3.30 0.29 0.31 3.00

29 34 1.80 1.80 0.25 0.02 2.80

33 36 2.10 2.10 1.30 0.38 2.70

16 17 0.10 0.10 0.85 3.70 2.60

40 41 0.26 0.26 0.13 2.70 2.60

28 33 1.60 1.60 0.29 0.13 2.50

26 30 3.10 3.10 0.72 0.45 2.40

32 34 1.20 1.20 0.45 0.54 2.10

38 40 7.60 7.60 3.10 0.03 2.00

4 9 1.50 1.50 0.81 0.44 1.80

34 36 2.10 2.10 1.00 0.25 1.80

39 48 1.20 1.20 0.49 0.00 1.80

21 22 3.00 3.00 0.18 4.20 1.70

40 43 0.86 0.86 0.84 1.50 1.70

43 44 0.85 0.85 0.79 1.20 1.60

43 44 0.85 0.85 0.79 1.20 1.60

5 10 1.70 1.70 1.10 0.77 1.50

15 16 0.39 0.39 0.99 1.70 1.30

7 8 0.32 0.32 0.01 1.60 1.10

9 12 0.71 0.71 0.02 0.18 1.10

12 13 0.05 0.05 0.10 1.10 1.10

26 28 1.30 1.30 0.34 0.37 1.10

35 37 1.80 1.80 1.50 0.81 0.96

17 18 0.08 0.08 0.13 1.20 0.92

25 29 1.10 1.10 0.24 0.15 0.92

15 21 0.29 0.29 0.17 0.14 0.85

15 21 0.29 0.29 0.17 0.14 0.85

20 23 0.13 0.13 0.04 0.59 0.80

20 23 0.13 0.13 0.04 0.59 0.80

10 12 0.65 0.65 0.11 0.34 0.77

33 35 0.90 0.90 0.29 0.07 0.74

34 35 0.75 0.75 0.36 0.05 0.64

10 11 0.27 0.27 0.06 0.01 0.58

39 45 0.75 0.75 0.07 0.44 0.56

39 45 0.75 0.75 0.07 0.44 0.56

41 42 0.38 0.38 0.22 0.26 0.56

44 47 0.26 0.26 0.24 0.36 0.48

Page 62: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

48

44 47 0.26 0.26 0.24 0.36 0.48

30 34 0.19 0.19 0.02 0.05 0.28

18 21 0.02 0.02 0.01 0.24 0.27

18 21 0.02 0.02 0.01 0.24 0.27

2 4 1.30 1.30 1.00 1.40 0.24

9 11 0.35 0.35 0.30 0.19 0.19

35 38 0.94 0.94 0.11 0.97 0.18

39 40 0.84 0.84 0.49 0.02 0.14

6 10 0.20 0.20 0.13 0.15 0.13

31 32 1.00 1.00 0.71 0.71 0.13

1 5 1.00 1.00 0.91 1.00 0.05

36 37 0.04 0.04 0.03 0.02 0.02

42 45 0.11 0.11 0.04 0.16 0.02

42 45 0.11 0.11 0.04 0.16 0.02

2 6 2.80 2.80 2.50 3.00 0.01

25 26 0.00 0.00 0.00 0.01 0.01

1 2 0.00 0.00 0.00 0.00 0.00

Table A - 9 Dynamic data of generators and line parameters for Kundur system

Page 63: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

49

Reference

[1] "Development of direct current technology," [Online]. Available:

http://www.deutsches-museum.de/en/exhibitions/energy/electric-

power/direct-current/. [Accessed 07 08 2012].

[2] “High-voltage direct current,” wikipedia, [Online]. Available:

http://en.wikipedia.org/wiki/High-voltage_direct_current. [Accessed 07 08 2012].

[3] Siemens AG, “High Voltage Direct Current Transmission-Proven Technology for

Power Exchange,” Erlangen Germany.

[4] Hualei Wang, M.A. Redfern, “The advantages and disadvantages of using HVDC

to interconnect AC networks,” in UPEC, 2010 31st Aug - 3rd Sept 2010.

[5] Jochen Kreusel, Dietmar Retzmann, “Integrated AC/DC Transmission Systems,”

ABB, Siemens, Germany, 2008.

[6] Schmidt, G., Fiegl, B. and Kolbeck.S., “HVDC transmission and the environment,”

Power Engineering Journal, p. 209–210, October 1996.

[7] ANDERSEN, B.R., “HVDC transmission-opportunities and challenges,” in The 8th

IEE International Conference, March 2006.

[8] Mohan N., Undeland T. M., Robbins W. P., Power electronics: converters,

applications and design, New York: Wiley, 1995.

[9] Tang, Guosheng, “Damping subsynchronous reosonance oscillations using a

VSC-HVDC back-to-back system,” University of Saskatchewan, Saskatoon,

Saskatchewan, 07.2006 .

[10] Du CuiQing, “VSC-HVDC for Industrial Power Systems,” Chalmers unversity of

technology, Goeteborg, Sweden, 2007.

[11] “Development and Application of Self- Commutated Converters in Power

Systems,” in IEEE Winter Meeting, Singapore, 01.2000.

[12] “Gotland: the first commercial HVDC Light project,” ABB, [Online]. Available:

http://www.abb.de/industries/ap/db0003db004333/a34c41e0fe23b18cc125774a

0033abbe.aspx. [Accessed 20 08 2012].

[13] A. Berizz, “The Italian 2003 blackout”.

[14] Ian Dobson, Benjamin A., “Number and propagation of line outages in cascading

events in electric power transmission systems”.

[15] Lidong Zhang, Lennart Harnefors, Pablo Rey, “Power System Reliability and

Transfer Capability Improvement by VSC- HVDC,” Power Technologies ABB,

Page 64: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

50

Sweden.

[16] Ray D. Zimmerman, Carlos E. Murillo-Sánchez and Deqiang (David) Gan ,

“Matpower-A MATLAB Power System Simulation Package,” [Online]. Available:

http://www.pserc.cornell.edu/matpower/. [Accessed 20 08 2012].

[17] Nara K., Tanaka K., Shoults R. R., Chen M. S., Van Olinda, “On-line contingency

selection for voltage security analysis,” IEEE Trans. Power Apparat. Syst., Vols. PAS-

104, pp. 847 - 856, April 1985.

[18] Tan Xiaoya, “HVDC-VSC Model for Matpower,” EEH – Power Systems Laboratory,

Zurich, 2012.

[19] K. Prasertwong, N. Mithulananthan, D. Thakur, “Understanding low frequency

oscillation in power systems,” Power and Energy System Group, School of

Information Technology and Electrical Engineering, The University of

Queenslanda, St. Lucia Campus, Brisbane, Qld 4072, Australia.

[20] Padiyar K.R., Analysis of Subsynchronous Resonance in Power Systems, USA:

Kluwer Academic Publishers, 1999.

[21] Pal B.C., “Robust Damping Control of Inter-area Oscillations in Power System

with Super-conducting Magnetic Energy Storage Devices.,” Imperial College of

Science Technology and Medicine, 1999.

[22] Yuwa Chompoobutrgool, Luigi Vanfretti, Mehrdad Ghandhari, “Survey on Power

System Stabilizers Control and their Prospective Applications for Power System

Damping using Synchrophasor-Based Wide-Area Systems.,” KTH Royal Institute

of Technology, Stockholm.

[23] Dmitry N. Kosterev, Carson W. Tylor, William A., “Model Validation for the August

10.1996 WSCC System Outage,” IEEE Transactions on Power Systems, vol. 14, pp.

967-979, August 1999.

[24] Samuelsson Olof, “Power System Damping Structural Aspects of Controlling

Active Power,” Department of Industrial Electrical Engineering and Automation,

Lund Institute of Technology, 1997.

[25] Preece R., “Damping of Inter-are oscillations using WAMS based supplementary

controller installed at VSC based HVDC line,” in PowerTech, 2011 IEEE Trondheim,

19-23 June 2011.

[26] Ni Jingmin, Shen Chen, Li Ying, Tan Wei, “An on-line Weak-connection

identification method for controlled islanding of power system,” Proceedings of

the CSEE, 05.02.2011.

[27] Haibo You, Vijay Vittal, Xiaoming Wang, “Slow Coherency-Based Islanding,” IEEE

Transactions on power systems, vol. 19, February 2004.

Page 65: Placing of VSC-HVDC Lines in a Meshed AC-Network · PDF filePlacing of VSC-HVDC Lines in a Meshed AC-Network ... Voltage Source Converter Based High Voltage direct current ... AC grid

51

[28] Chow, J. H., Time-Scale Modeling of Dynamic Networks with Applications to

Power Systems, New York: Springer-Verlag, 1982.

[29] Avramotic B, Kokotovic P. V., Winkelman J., “Area decomposition for

electromechanical models of power systems,” Automatica, vol. 16, pp. 637-648,

1980.

[30] Kokotovic P V, Avramovic B, Chow J H., “Coherency based decomposition and

aggregation,” Automatica, vol. 18, pp. 47-56, 1982.

[31] P. Kundur, N. J. Balu, Power System Stability and Control, McGraw-Hill, 1993.

[32] Fang Liu, Ryuichi Yokoyama, Yicheng Zhou, Min Wu, “Study on Oscillation

Damping Effects of Power System Stabilizer with Eigenvalue Analysis Method for

the Stability of Power Systems”.

[33] Cliff Grigg, Peter Wong, Paul Allan, Murty Billinton, “The IEEE Reliability Test

System - 1996,” IEEE Transactions on Power System, vol. 14, August 1999.

[34] “Fault (power engineering),” wikipedia, [Online]. Available:

http://en.wikipedia.org/wiki/Fault_(power_engineering). [Accessed 08 08 2012].

[35] Paserba, J., “Analysis and control of power system oscillation,” CIGRE Special

Publication, 1996.

[36] Germond, R. Podmore, “Development of Dynamic Equivalents for Transient

Stability Studies,” System Control, Inc., 04.1977.

[37] R. Sunitha, R. Kumar Sreerama and Abraham T. Mathew, “Electric Power

Components and Systems. Department of Electrical Engineering,” National

Institute of Technology, Calicut, Kerala, India, 15.01.2011.

[38] “HVDC Light® Technical Background: CIGRE Compendium of HVDC Schemes

Throughout the World,” 2005.

[39] Khalil H. K., Nonlinear Systems, 3rd edition, Englewood Cliffs: Prentice-Hall, 2000.

[40] Siemens AG, “The Smart Way: HVDC PLUS – One Step Ahead,” 91058 Erlangen,

Germany, 2011.