TRANSFORMERS
Transformers are key elements in power systems. In order to
effectively transmit power over long distances without prohibitive line
losses, the voltage from the generator (a maximum of output voltage ofapproximately 25-30 kV) must be increased to a significantly higher level
(from approximately 150 kV up to 750 kV). Transformers must also be
utilized on the distribution end of the line to step the voltage down (in
stages) to the voltage levels required by the consumer.
Transformers also have a very wide range of applications outside the
power area. Transformers are essential components in the design of DC
power supplies. They can provide DC isolation between two parts of a
circuit. Transformers can be used for impedance matching between sourcesand loads or sources and transmission lines. They can also be used to
physically insulate one circuit from another for safety.
Fundamentally, the transformer consists of two or more windings that
are magnetically coupled using a ferromagnetic core. For a two-winding
transformer, the winding connected to the AC supply is typically referred
to as theprimary while the winding connected to the load is referred to as
thesecondary. A time-varying current passing through the primary coil
produces a time-varying magnetic flux density within the core. According
to Faradays law, the time-changing flux passing through the secondary
induces a voltage in the secondary terminals.
-
7/31/2019 Phan Anh Bien AP Transformers
2/29
IDEAL TRANSFORMER
The basic two-winding (single-phase) transformer is shown below.
To simplify the initial analysis, the transformer will be assumed to be ideal.
The following assumptions are made in the analysis of an ideal transformer:
(1) The transformer windings are perfect conductors (zero winding
resistance).
(2) The core permeability is infinite (the reluctance of the core is
zero).
(3) All magnetic flux is confined to the transformer core (no
leakage flux).
(4) Core losses are assumed to be zero.
The figure above shows the common convention for the primary and
secondary voltage polarities and current directions. The voltage polaritiesand current directions shown above yield positive input power on the
primary and positive output power on the secondary. The actual polarity
relationship between the primary voltage and the secondary voltage is
dictated by the orientation of the primary and the secondary coils. The
transformer voltage relationship is obtained by applying Faradays law.
-
7/31/2019 Phan Anh Bien AP Transformers
3/29
Applying Faradays law to both the primary and the secondary (noting the
possibility of sources applied to either winding), yields
where the line integrals of the electric fields are along the primary and
secondary windings from the ! terminal to the + terminal, and thecorresponding surface integrals of the magnetic flux densities are over the
cross-sections of the primary and secondary coils. The directions of the
differential lengths and differential surfaces are related by the right-handrule. The total magnetic flux passing through the primary coil also passes
through the secondary coil, assuming an ideal transformer (all of the flux
is confined to the transformer core).
Note that the orientations of the given coils yield differential surface
vectors that point in the same direction around the magnetic circuit, such
that
-
7/31/2019 Phan Anh Bien AP Transformers
4/29
Dividing the equations forv1 and v2 gives
where the ratio of the primary turns to the secondary turns (defined as theturns ratio a) is equal to the ratio of the primary and secondary voltages.
According to the turns ratio equation, a transformer with more secondary
turns than primary turns yields a secondary voltage that is larger than the
primary voltage (step-up transformer) while a transformer with fewer
secondary turns than primary turns yields a secondary voltage that is
smaller than the primary voltage (step-down transformer).
If the orientation of one of the transformer coils is reversed, then the
differential surface vectors for the primary and secondary would be in
opposite directions yielding
If we apply Amperes law around the transformer core (clockwise, on
the centerline of the core), we find
Note that withL clockwise, the normal to the surface Sis inward, so that
currents inward are positive and currents outward are negative. The total
enclosed current is then
-
7/31/2019 Phan Anh Bien AP Transformers
5/29
Assuming an ideal transformer core (:r= 4), the magnetic field inside thecore is zero (similar to the fact that the electric field is zero inside a perfectconductor with F = 4, but carries a current on the surface of the conductor).Thus,
The conservation of power relationship for the ideal transformer (power in
equals power out, given no losses) can be stated by multiplying the voltage
ratio by the current ratio:
Assuming sinusoidal excitation, the ideal transformer can be
analyzed using phasor techniques. The ratios of the phasor voltages and
phasor currents satisfy the same turns ratio relationships as the time-domain
values.
-
7/31/2019 Phan Anh Bien AP Transformers
6/29
Note that the complex power relationship is also valid for the ideal
transformer.
-
7/31/2019 Phan Anh Bien AP Transformers
7/29
Polarity of Transformer Windings
The operation of the transformer depends on the relative orientation
of the primary and secondary coils. We mark one of the terminals on the
primary and secondary coils with a dot to denote that currents enteringthese two terminals produce magnetic flux in the same direction within the
transformer core.
The equivalent circuit diagram and phasor equations for this idealtransformer are
If either coil orientation is reversed, the dot positions are reversed and the
current and voltage equations must include a minus sign.
-
7/31/2019 Phan Anh Bien AP Transformers
8/29
Input Impedance (Ideal Transformer)
Consider an arbitrary load (Z2) connected to the secondary terminals
of the ideal transformer as shown below.
The input
impedance seen looking into the primary winding is given by
Thus, the input impedance seen looking into the primary of the ideal
transformer is the load impedance times a2. Using this property, the
secondary impedance of the ideal transformer can be reflected to the
primary.
-
7/31/2019 Phan Anh Bien AP Transformers
9/29
In a similar fashion, a load on the primary side of the ideal transformer can
be reflected to the secondary.
-
7/31/2019 Phan Anh Bien AP Transformers
10/29
Example (Ideal transformer)
Determine the primary and secondary currents for the ideal
transformer below ifZs = (18!j4) S and Z2 = (2+j1) S .
The load impedance reflected to the primary of the transformer is
The primary current is then
The primary voltage is
The secondary voltage is
The secondary current is
-
7/31/2019 Phan Anh Bien AP Transformers
11/29
TRANSFORMERRATING
Transformers carry ratings related to the primary and secondary
windings. The ratings refer to the power in kVA and primary/secondary
voltages. A rating of 10 kVA, 1100/110 V means that the primary is rated
for 1100 V while the secondary is rated for 110 V (a =10). The kVA ratinggives the power information. With a kVA rating of 10 kVA and a voltage
rating of 1100 V, the rated current for the primary is 10,000/1100 = 9.09 A
while the secondary rated current is 10,000/110 = 90.9 A.
NON-IDEAL TRANSFORMEREQUIVALENT CIRCUITS
The non-ideal transformer equivalent circuit below accounts for all
of the loss terms that are neglected in the ideal transformer model. The
individual loss terms in the equivalent circuit are:
Rw1,Rw2 - primary and secondary winding resistances
(losses in the windings due to the resistance of the wires)
Xl1,Xl2 - primary and secondary leakage reactances
(losses due to flux leakage out of the transformer core)
Rc1 - core resistance(core losses due to hysteresis loss and eddy current loss)
Xm1 - magnetizing reactance
(magnetizing current necessary to establish magnetic flux
in the transformer core)
-
7/31/2019 Phan Anh Bien AP Transformers
12/29
Using the impedance reflection technique, all the quantities on the
secondary side of the transformer can be reflected back to the primary side
of the circuit. The resulting equivalent circuit is shown below. The primed
quantities represent those values that equal the original secondary quantity
multiplied by a (voltages), divided by a (currents) or multiplied by a2
(impedance components).
Approximate Transformer Equivalent Circuits
Given that the voltage drops across the primary winding resistance
and the primary leakage reactance are typically quite small, the shuntbranch of the core loss resistance and the magnetizing reactance (excitation
branch) can be shifted to the primary input terminal. The primary voltage
is then applied directly across the this shunt impedance and allows for the
winding resistances and leakage reactances to be combined.
-
7/31/2019 Phan Anh Bien AP Transformers
13/29
A further approximation to the transformer equivalent circuit can be
made by eliminating the excitation branch. This approximation removes
the core losses and the magnetizing current from the transformer model.
The resulting equivalent circuit is shown below.
Note that this equivalent circuit
is referred to the primary side of
the transformer (V1 and VN2).This circuit can easily be
modified so that it is referred to
the secondary side of the
transformer (VN1 and V2).
-
7/31/2019 Phan Anh Bien AP Transformers
14/29
DETERMINATION OF EQUIVALENT CIRCUIT PARAMETERS
In order to utilize the complete transformer equivalent circuit, the
values ofRw1,Rw2,Xl1,Xl2,Rc1,Xm1 and a must be known. These values canbe computed given the complete design data for the transformer including
dimensions and material properties. The equivalent circuit parameters can
also be determined by performing two simple test measurements. These
measurements are the no-load(or open-circuit) testand theshort-circuit
test.
No-Load Test - The rated voltage at rated frequency is applied to
the high-voltage (HV) or low-voltage (LV) windingwith the opposite winding open-circuited.
Measurements of current, voltage and real power
are made on the input winding (most often the LV
winding, for convenience).
Short-Circuit Test - Either the LV or HV winding is short-circuited and
a voltage at rated frequency is applied to the
opposite winding such that the rated current results.
Measurements of current, voltage and real power
are made on the input winding (most often the HV
winding, for convenience, since a relatively low
voltage is necessary to obtain rated current under
short-circuit conditions).
-
7/31/2019 Phan Anh Bien AP Transformers
15/29
Example (Equivalent circuit parameters / no-load / short-circuit tests)
The approximate equivalent circuit parameters for a single-phase
10kVA, 2200/220, 60 Hz transformer are required.
The rated currents and voltages for the transformer windings are:
VH,rated= 2200 V IH,rated= 10000/2200 = 4.55 A
VL,rated= 220 V IL,rated= 10000/220 = 45.5 A
No-load and short-circuit tests are performed on the transformer with the
following results:
No-load test (HV winding open, VL = VL,rated= 220 V)
IL = 2.5 A,PL = 100 W
Short-circuit test (LV winding shorted,IH=IH,rated= 4.55 A)
VH= 150 V,PH= 215 W
(a.) Determine the approximate equivalent circuit parameters from the test
data (use the approximate equivalent circuit that includes core losses).
Draw the equivalent circuit for this transformer referred to the LV side.
(b.) Draw the equivalent circuit for this transformer referred to the HV
side. (c.) From the no-load test results, express the excitation current as a
percentage of the rated current in the LV winding. (d.) Determine the
power factor for the no-load and short-circuit tests.
Referred to LV side Referred to HV side
-
7/31/2019 Phan Anh Bien AP Transformers
16/29
Equivalent circuit for no-load test (determineRcL andXmL)
-
7/31/2019 Phan Anh Bien AP Transformers
17/29
Equivalent circuit for short-circuit test (determineReqHandXeqH)
The values measured on the HV winding (primary) in the short-circuit
test need to be referred to the LV side. Note that our turns ratio is given by
-
7/31/2019 Phan Anh Bien AP Transformers
18/29
(a.)
Referred to LV side
(b.) To obtain the same equivalent circuit referred to the HV side(primary), we simply multiply all impedances by a2 (100). The
resulting equivalent circuit is
Referred to HV side
(c.) From the no-load test results, the total excitation current is 2.5 A
while the rated current in the LV winding is 45.5 A. Thus the
excitation current is (2.5/45.5) or 5.5% of the rated current.
-
7/31/2019 Phan Anh Bien AP Transformers
19/29
-
7/31/2019 Phan Anh Bien AP Transformers
20/29
TRANSFORMERVOLTAGE REGULATION
For a given input (primary) voltage, the output (secondary) voltage
of an ideal transformer is independent of the load attached to the secondary.
As seen in the transformer equivalent circuit, the output voltage of arealistic transformer depends on the load current. Assuming that the
current through the excitation branch of the transformer equivalent circuit
is small in comparison to the current that flows through the winding loss
and leakage reactance components, the transformer approximate equivalent
circuit referred to the primary is shown below. Note that the load on the
secondary (Z2) and the resulting load current (I2) have been reflected to the
primary (ZN2, IN2).
The percentage voltage regulation (VR) is defined as the percentage change
in the magnitude of the secondary voltage as the load current changes from
the no-load to the loaded condition.
The transformer equivalent circuit above gives only the reflected secondary
voltage. The actual loaded and no-load secondary voltages are equal to the
loaded and no-loaded refelcted secondary values divided by the turns ratio.
-
7/31/2019 Phan Anh Bien AP Transformers
21/29
Thus, the percentage voltage regulation may be written in terms of the
reflected secondary voltages.
According to the approximate transformer equivalent circuit, the reflected
secondary voltage under no-load conditions is equal to the primary voltage,
so that
The secondary voltage for the loaded condition is taken as the rated
voltage.
Inserting the previous two equations into the percentage voltage regulation
equation gives
Note that this equation is defined in terms of the voltages given in the
transformer approximate equivalent circuit. Also note that the rated
secondary voltage reflected to the primary is the rated primary voltage.
To determine the percentage voltage regulation, we may use the reflected
secondary voltage as the voltage reference,
and determine the corresponding value of *V1* from the approximateequivalent circuit.
-
7/31/2019 Phan Anh Bien AP Transformers
22/29
The voltagesV1 andVN2 in the approximate equivalent circuit are related by
where
The reflected secondary current can be written as
The expression forV1 becomes
We can draw the phasor diagram relating the voltages V1 and VN2 to
determine how the phase angles of the load and the transformer impedanceaffect the percentage voltage regulation. Note that the percentage voltage
regulation can be positive or negative and the sign ofVR is affected by the
phase angle in the expression above. Thus, the power factor of the load
will affect the voltage regulation of the transformer.
-
7/31/2019 Phan Anh Bien AP Transformers
23/29
The percentage voltage regulation is positive if*V1* > V1,ratedand negativeif*V1* < V1,rated. Note that with the limits on the angles of
the worst case scenario for the percentage voltage regulation occurs when
or when the load has a lagging power factor with the power factor angle
equal to the transformer impedance angle ofZeq1.
-
7/31/2019 Phan Anh Bien AP Transformers
24/29
Example (Transformer voltage regulation)
Using the transformer for which the approximate equivalent circuits
were found based on no-load and short-circuit test results, determine the
percentage voltage regulation for (a.) a load drawing 75% of rated currentat a power factor of 0.6 lagging (b.) a load drawing 75% of rated current at
a power factor of 0.6 leading.
The approximate equivalent circuit for the transformer (10kVA,
2200/220, 60 Hz) referred to the high voltage winding was found to
be (neglecting the excitation branch of the model)
Assume:Primary = HV winding
Secondary = LV winding
a =N1/N2 = 10
VH,rated= 2200 V
IH,rated= 10000/2200 = 4.55 A
VL,rated= 220 V
IL,rated= 10000/220 = 45.5 A
(a.) The reflected voltage VLN on the HV side is given by
so that the circuit to be analyzed becomes
-
7/31/2019 Phan Anh Bien AP Transformers
25/29
Based on the information provided in the problem statement, the
magnitude of the load current (and thus the current ILN) is 0.75 timesthat of the rated value.
The phase angle ofILN is given by the load power factor.
so that the phasor current ILN is
The voltage VHand VLN are related by
The percentage voltage regulation is thus
(b.) For the leading power of 0.6, 2i = +53.13o so that the phasor currentILN is
and VH is given by
-
7/31/2019 Phan Anh Bien AP Transformers
26/29
The voltage regulation is
The percentage voltage regulation results for these two cases shows
that if this transformer is providing 75% of rated current (3.41 A-rms) to
a load with a power factor of 0.6 lagging, and the load is suddenly
removed, the load voltage magnitude rises from 220 V to 230.70V. For the
load with a power factor of 0.6 leading, the load voltage magnitude drops
from 220 V to 213.79 V.
-
7/31/2019 Phan Anh Bien AP Transformers
27/29
TRANSFORMEREFFICIENCY
The efficiency (0) of a transformer is defined as the ratio of the outputpower (Pout) to the input power (Pin). The output power is equal to the input
power minus the losses (Ploss) in the transformer. The transformer losspower has two components: core loss (Pcore) and so-called copper loss (Pcu)
associated with the winding resistances. The transformer efficiency in
percent is given by
Assuming a relatively constant voltage source on the primary of the
transformer, the core loss can be assumed to be constant and equal to power
dissipated in the core loss resistance (Rc1
) of the equivalent circuit for the
no-load test. The copper loss in a transformer may be written in terms of
both the primary and secondary currents, or in terms of only one of these
currents based on the relationshipI2 = aI1.
The output power of the transformer can be written in terms of the
secondary voltage and current (real part of output complex power).
-
7/31/2019 Phan Anh Bien AP Transformers
28/29
The transformer efficiency, written in terms of secondary values, is
It can be shown that the maximum transformer efficiency occurs when the
core losses equal the copper losses and the power factor is unity.
Example (Transformer efficiency)
Using the transformer for which the approximate equivalent circuits
were found based on no-load and short-circuit test results, determine (a.)
the transformer efficiency at 75% of rated output power with a power factor
of 0.6 lagging (b.) the output power at maximum efficiency, the value of
maximum efficiency, and at the percentage of full load power where
maximum efficiency occurs.
(a.) The rated power for this transformer is 10 kW at a power factor of
unity. IfPout is 75% of the rated value at a power factor of 0.6, then
From the no-load test, the core losses werePcore = 100 W. The copper
losses for this transformer are
The transformer efficiency is
-
7/31/2019 Phan Anh Bien AP Transformers
29/29
(b.) At maximum efficiency YPCu=IL2ReqL =Pcore = 100 W,PF= 1
The maximum efficiency is
The maximum efficiency occurs at