Peltec TImers 256-480

2
n Relay monitors phase sequence and failure n Designed for monitoring 3-phase primaries n Input from all phases maintains functionality in case of one-phase failure n Input and monitored input voltage: 3 x 480V n Fixed time delay (T1): 500ms n Adjustable time delay (T2): 0 to 10 seconds n Fault indicator: Red LED, plus opening of output relay contact n Relay output form: SPDT (form C) 8 Amps / 250VAC n DIN rail mounting n UL and CE approvals, RoHS compliant MODE OF OPERATION FEATURES SPECIFICATIONS Voltage Monitoring Three-phase monitor confirms correct sequence and detects failure of any one phase. Phase failure results in a flashing red LED and opening of output relay. Green LED indicates presence of supply voltage. Only 2 phases are needed for Control operation. Incorrect phase sequence is indicated by constant red LED and opening of output. A front panel potentiometer adjusts failure indication delay up to 10 seconds. A low voltage condition (60% of nominal) results in immediate failure indication, red LED and open output. Threshold can be set from 70% to 95% with a second front panel adjustment. Supply and measuring .... L1, L2, L3 Measuring terminals ...... L1, L2, L3 Supply/measured voltage . 3x480 V Minimum threshold ....... adjustable, 70%–95% Nominal Cutoff threshold ........... 60% of Nominal Power Consumption (max) .. 2 VA Hysteresis ................. 5% Max. constant voltage..... 3x550 VAC Peak overload <1s ......... 3x600 VAC Time delay t1 .............. 500ms max Time delay t2 .............. adjustable, 0–10s Relay output form ......... SPDT Form C (AgNi) Rated current .............. 8 A/ AC Switching capacity ........ 2500 VA/ AC, 240 W/ DC Inrush current ............. 10 Amps Indication of state ......... Red LED Mechanical life ............ 10 million operations Electrical life............... 100,000 operations Operating temperature ... -20°C to +55°C Storage temperature ...... -30°C to +70°C Dielectric strength ........ 4 kV Operating position ........ any Mounting .................. DIN rail EN 60715 Protection degree ......... IP 40 from front panel Max. cable size ............ 14AWG Standards ................. EN 60255-6, EN 61010-1, UL, CE, RoHS 315-655-8476 n www.peltectimers.com 256-480 VOLTAGE and PHASE MONITOR L1 L2 L3 15-18 red LED green LED Umin UOFF UOFF UOFF t1 Hysteresis t2 10/13/08 200 Series

description

Peltec TImers 256-480 Industrial Electronics

Transcript of Peltec TImers 256-480

Page 1: Peltec TImers 256-480

n Relay monitors phase sequence and failuren Designed for monitoring 3-phase primariesn Input from all phases maintains functionality in case of

one-phase failuren Input and monitored input voltage: 3 x 480Vn Fixed time delay (T1): 500msn Adjustable time delay (T2): 0 to 10 secondsn Fault indicator: Red LED, plus opening of output relay contactn Relay output form: SPDT (form C) 8 Amps / 250VACn DIN rail mountingn UL and CE approvals, RoHS compliant

mode of operation

featUreS

SpeCifiCationS

Voltage monitoring Three-phase monitor confirms correct sequence and detects failure of any one phase. Phase failure results in a flashing red LED and opening of output relay.

Green LED indicates presence of supply voltage. Only 2 phases are needed for Control operation.

Incorrect phase sequence is indicated by constant red LED and opening of output. A front panel potentiometer adjusts failure indication delay up to 10 seconds.

A low voltage condition (60% of nominal) results in immediate failure indication, red LED and open output. Threshold can be set from 70% to 95% with a second front panel adjustment.

Supply and measuring . . . . L1, L2, L3

measuring terminals . . . . . . L1, L2, L3

Supply/measured voltage . 3x480 V

minimum threshold . . . . . . . adjustable, 70%–95% Nominal

Cutoff threshold . . . . . . . . . . . 60% of Nominal

power Consumption (max) . . 2 VA

Hysteresis . . . . . . . . . . . . . . . . . 5%

max. constant voltage . . . . . 3x550 VAC

peak overload <1s . . . . . . . . . 3x600 VAC

time delay t1 . . . . . . . . . . . . . . 500ms max

time delay t2 . . . . . . . . . . . . . . adjustable, 0–10s

relay output form . . . . . . . . . SPDT Form C (AgNi)

rated current . . . . . . . . . . . . . . 8 A/ AC

Switching capacity . . . . . . . . 2500 VA/ AC, 240 W/ DC

inrush current . . . . . . . . . . . . . 10 Amps

indication of state . . . . . . . . . Red LED

mechanical life . . . . . . . . . . . . 10 million operations

electrical life . . . . . . . . . . . . . . . 100,000 operations

operating temperature . . . -20°C to +55°C

Storage temperature . . . . . . -30°C to +70°C

dielectric strength . . . . . . . . 4 kV

operating position . . . . . . . . any

mounting . . . . . . . . . . . . . . . . . . DIN rail EN 60715

protection degree . . . . . . . . . IP 40 from front panel

max. cable size . . . . . . . . . . . . 14AWG

Standards . . . . . . . . . . . . . . . . . EN 60255-6, EN 61010-1, UL, CE, RoHS

315-655-8476 n www.peltectimers.com

256-480Voltage

and pHaSe monitor

L1

L2

L3

15-18

red LED

green LED

UminUOFF

UOFF

UOFFt1

Hysteresis

t2

10/13/08

200 Series

Page 2: Peltec TImers 256-480

featUreS wiring diagram

2747 Route 20 East, Cazenovia, NY 13035315-655-8476 n www.peltectimers.com 10/13/08

peltec256-480 Voltage monitor pHaSe SeqUenCe and failUre

15 18

L2 L3

16

L1

15

16 18 L1

L3 L2

Minimum voltage setting

Fault indicator

Time delay setting