Breathing Air CompressorOperating Procedures
A Guide to Filling SCBA Bottles
With the Bauer UNIII 18H-E3
Compressor / Fill Station
Breathing Air Compressor Rev 2
Training Outline
1. The new breathing air system – what’s thesame, what’s different
2. Prelude: Things to do in preparation forcylinder filling
3. System operation
Fill Station SpecsBauer Compressor Unicus 18H-E3
Pressure 6000 psig
Stages 4
Charging Rate 18 scfm
Motor 15 hp, 1350 rpm
Purification P5 Securus
Air Flow Diagram
Prelude:Electrical Panel Circuit Breaker
Three PhaseCircuit for
Compressor –Leave ON at all
times !
Electrical Disconnect Box –Leave ON unless servicingcompressor.
Compressor – (PowerButton on Controller)Leave in Standby fornormal operation.
Prelude:Check Oil Level
• Set compressor to “OFF”
• Check oil level (Viewthough left-side door)
• Return compressor to“Standby”
Prelude:Cylinder Inspection
• Check hydro test status– Less than 5 years since latest hydro test
• Inspect for physical damage to cylinder– Nothing worse than minor surface scratches,
abrasions, or cuts
– Valve assembly in good condition
• If any problems noted, DO NOT FILL and tagOOS!
• Fill in log sheet with requested information
Prelude:Operation Log Sheet
SCBA Fill Log(4800psi Fill Pressure)
CHECK OIL LEVEL BEFORE STARTING COMPRESSOR!
Date Start Finish
Cylinder Information
Remarks:
Operator
Compressor Hours
Hydrotest Date Initial Pressure, psi
Important: Any cylinder with deep gouges, exposed fiber wraps, a damaged
valve, other signs of obvious damage, or that is 5 years past its last hydrotest
date should be tagged and removed from service!
OSFD Cylinder #
System Operation: Front Panel
Operating Controls - 1
Show Home ScreenCompressor Status
Previous Screen
Screen NameView Next Screen
Panel LightAlarm Off
Operating Controls - 2
Enter this in Log Sheet
Operating Controls - 3
Show AlarmHistory
Operating Controls - 4
Cylinder Filling - 1
• Organize cylinders by grouping similar initialpressures
• Don ear protection• Confirm Fill Station setup
– Bank valves, Fill valves, Bleed valves all closed handtight
– Fill Selector set to “Fill From Banks”
• Load cylinders into fill station– Connect fill whips and open cylinder valves– Close door - Cylinders cannot be filled with door
open!
Cylinder Filling - 2
• Open Bank #1 supply valve; set regulatorpressure to 4800 psi. Open individual fill stationvalves to fill cylinders, at desired rate, to fullpressure of 4800 psi
• If Bank #1 pressure falls below 4800 psi, close it’ssupply valve and open supply valve from Bank #2to continue cylinder filling (note that compressorwill start when any bank pressure drops below5000 psi)
• Repeat with other banks as necessary tocomplete filling
Cylinder Filling - 3
• Close individual fill station valves, open accessdoor, close cylinder valves, open bleed valves
• Disconnect fill whips and remove cylinders
• Place cylinders that had initial pressure over2500 psi back in service or in the “Ready forService” storage area. Cylinders with initialpressure under 2500 psi are returned to the“Need filling” storage area for topping off.
Cylinder Filling - 4
• Fill subsequent cylinders, in similar fashion, inorder of decreasing initial pressures bychoosing the Bank with the lowest pressurestill above the cylinder group being filled
• Check for cylinders needing “top off” (musthave cooled to room temp after initial filling).Fill to 4800 psi per filling procedure and placeback in service.
Cylinder Filling – Completion
• Replace fill whips in their retention slots• Close access door; close (hand tight) all bank, fill,
and bleed valves; reduce regulator setting backto zero.
• Leave Fill Selector valve in the “fill from storage”position
• Wait for compressor to automatically shut down.Bring up “Status 2” screen on the controller andrecord “Total Run Hours” on the SCBA Fill Log.File completed log. Return to “Status 1” screenview. Do not turn off power.