PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
-
Upload
1969mazhar -
Category
Documents
-
view
290 -
download
13
Transcript of PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
1/65
60Hz(R22)
SR-6RMG2-02A
Saudi Arabia
General Wall Mounted
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
2/65
2 GENERAL WALL MOUNTED
GENERAL WALL MOUNTED
Contents
1. Models Line up .............................................................................6
2. Nomenclature ...............................................................................7
3. Features & Benefits......................................................................8
4. Specifications .............................................................................10
5. Dimensional Drawings...............................................................17
6. Wiring Diagrams.........................................................................22
7. Refrigerant Cycle Diagram ........................................................33
8. Capacity Tables ..........................................................................34
9. Capacity Coefficient factor........................................................41
10. Air Velocity and Temperature Distribution(Reference Data).......................................................................43
11. Controller ..................................................................................44
12. Installation ................................................................................47
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
3/65
3
SR-6RMG2-02A
GENERAL WALL MOUNTED
Test condition of international standard
KSC ISO ARI AHAM AS SSA 9306 5151 210/240 1861.1 385
Indoor
DBC(F) 27.0 27.0 26.7(80) 26.7(80) 27.0 29.0
Cooling WBC(F) 19.5 19.0 19.4(67) 19.4(67) 19.0 19.0
CapacityOutdoor
DBC(F) 35.0 35.0 35.0(95) 35.0(95) 35.0 46.0
WBC(F) 24.0 24.0 23.9(75) 23.9(75) 24.0 24.0
Indoor
DBC(F) 20.0 20.0 21.1(70) 21.1(70) 21.0 21.0
Heating WBC(F) 15.0 15.0 15.6(60) 15.6(60) 15.0 15.5
CapacityOutdoor
DBC(F) 7.0 7.0 8.3(47) 8.3(47) 7.0 7.0
WBC(F) 6.0 6.0 6.1(43) 6.1(43) 6.0 6.0
Indoor
DBC(F) 32.0 32.0 26.7(80) 32.2(90) 32.0 29.0Maximum
WBC(F) 23.0 23.0 19.4(67) 22.8(73) 23.0 19.0Cooling
Outdoor DBC(F) 43.0 43.0 46.1(115) 43.3(110) 43.0 54.0
Operating WBC(F) 26.0 26.0 23.9(75) 25.6(78) 26.0 24.0
Indoor
DBC(F) 27.0 27.0 26.7(80) 26.7(80) - -Maximum
WBC(F) 19.0 19.0 19.4(67) 22.8(73) - -Heating
Outdoor
DBC(F) 21.0 24.0 23.9(75) 23.9(75) - -Operating
WBC(F) 15.0 18.0 18.3(65) 18.3(65) - -
EnclosureIndoor
DBC(F) 27.0 27.0 26.7(80) 26.7(80) 27.0 27.0
Sweat / WBC(F) 24.0 24.0 23.9(75) 23.9(75) 24.0 24.0
CondensateOutdoor
DBC(F) 27.0 27.0 26.7(80) 26.7(80) 27.0 27.0
Disposal WBC(F) 24.0 24.0 23.9(75) 23.9(75) 24.0 24.0
Freeze-up/ Indoor DBC(F) 21.0 21.0 19.4(67) 21.1(70) 21.0 21.0
Low WBC(F) 15.0 15.0 13.9(57) 15.6(60) 16.0 16.0
Temperature
Outdoor DBC(F) 21.0 21.0 19.4(67) 21.1(70) 21.0 21.0
WBC(F) 15.0 15.0 13.9(57) 15.6(60) 16.0 16.0
KS : Korea Standard AS : Australia Standard
ISO : International Standard Organization SSA : Saudi Arabian StandardARI : Airconditioning and Refrigeration InstituteAHAM : Association of Home Appliance Manufacturers
CLASSIFICATION
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
4/65
4
SR-6RMG2-02A
GENERAL WALL MOUNTED
General Description
Split type of Air Conditioners are known by the category name of Wall Mounted Type of units.These units can beeasily installed in a small space and have exceptional Cooling capacity.Designed for Low-noise operation,itensures a pleasant air conditioned environment.
LG Offers various types of units to its customers to suit for the best application and requirement.The following are
the important categories offered by LG :1) General Wall Mounted Type Units : Units with Simplicity in design.
2) Art Cool Units : A new concept of cooling introduced by LG in the field of Air Conditioning.
3) New Gas Models : These models uses HCFC free refrigerant to provide a healthy environment to the world.
Some of the Important Features of these units are listed below :
1) Providing Health to the Customers : By having Filters such as Plasma Filter which is capable of removing MicroOrganisms up to 0.1 microns.
2) Long Term Money Saving : By providing Features such as Gold Fin,Plasma Fin, Auto Clean etc. to maintain thesame performance for years.
3) Best Comfort : With Features such as Sleep Mode,Timer,Auto Restart etc.
These Units are available with many standard and optional features which gives our Customers the choice to selectthe unit of their own desire.For details refer to the Detailed specification followed after this description.
LG Electronics Inc.Air Conditioning & Energy Solution Company
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
5/65
5
SR-6RMG2-02A
GENERAL WALL MOUNTED
Publication historyPDB No. Product Name Notes Publication in
SR-6RMG2-01A SRAC 4Models Dec. 2012
SR-6RMG2-02A SRAC 10 Models May. 2013
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
6/65
6
Models Line up SR-6RMG2-02A
GENERAL WALL MOUNTED
1. Models Line upGeneral Wall Mounted
Edition Capacity Chassis Type Factory Model Buyer Model
#1
18K SC C/O GS-C182C4B2
H/P GS-H182C4B2
24K SC C/O GS-C242C4B2
H/P GS-H242C4B2
#2
12K SE C/O GS-C122E5B2
H/P GS-H122E5B2
18K S5
C/O GS-C1825SA3
H/P GS-H1825SA3
C/O GS-C1825NB2
H/P GS-H1825NB2
24K S5
C/O GS-C2425SA3
H/P GS-H2425SA3
C/O GS-C2425NB2
H/P GS-H2425NB2
-
-
-
-
S122NC
S122NH
S182SC
S182SH
S182NC
S182NH
S242SC
S242SH
S242NC
S242NH
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
7/65
7
Nomenclature SR-6RMG2-02A
GENERAL WALL MOUNTED
2. Nomenclature Identification Rule
Serial Number
FunctionB: 4Way
Look/Color
Chassis NameC: SC
Electric Rating2: 220V, 60Hz
CapacityEX) '18' 18,000Btu/h Class
Model TypeC: Cooling OnlyH: Heat Pump
Product TypeS: Split
Refrigerant TypeG: R22
Supply Method Diving and Type-: SET
G S C- 81 2 C 4 B 1
Chassis Look ClassificationSC 4 ICE-E (White)
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
8/65
8
Features & Benefits SR-6RMG2-02A
GENERAL WALL MOUNTED
3. Features & Benefits
SmokeAway GoldFin TropicalCompressor
StylishDesign
Quick & EasyInstallation
Skew Fan DualProtection Filter
Vane &Louver
Extreme Durability
The advanced tropical compressor withstandsextreme weather conditions, enabling theproduct to operate despite high outside tem-perature.
By adopting gold plated fins in the exteriorunit, the heat exchanger is protected from cor-rosion and wear from external conditions.
The combination of tropical compressor,and the gold fin in the exterior unit allcontribute in the improved durability of LG airconditioner.
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
9/65
9
Features & Benefits SR-6RMG2-02A
GENERAL WALL MOUNTED
Power Cooling
Perfect Health Care
Energy Saving
Stylish Design
Quick & Easy Installation
20m Windblast : Strong and cool windblastcovers the distance of 20m.
Optimized Airflow : The interior of the com-pressor in the outdoor unit has been construct-ed to minimze the sound produced when oper-ating.
The cool airflow reaches thedistance of 15m to all corners ofthe room, keeping the space cooland comfortable regardless ofoutside temperature.
Smoke Away : 3 million ionsspread from diffusion charger and 3M MicroProtection filter remove smoke particle asmuch as air-purifier removes.* Test Results
Size of Area : 30m 3, CADR : 135
Dual Protection Filter : Dual Protection Filterinitially captures dust in the air that comes into the air conditioner.
Filter : While being easy to main-tain, the powerful plasma filtration system ofLG air conditioner protects the user from odorand any harmful substances floating in air.
3M Multi Protection Filter : 3M MultiProtection filter captures dust, virus and aller-gen and deactivates the captured virus andallergen by unique technologies of LG and 3M.
Various filtration system protects the userfrom all harmful substances including odor,bacteria, and allergen
Inverter V : The advanced inverter technologyof LG enables the user of the air conditioner touse more and save more.
State of the art heat exchanger, air outlet,compressor, and inverter technology providethe world s highest energy efficiency
The design of LG air conditioners are stylish ina way that is incomparable to others. Think of
it not just as an air conditioner, but an objetthat will lighten up your living room.
LG air conditioners are not just refreshinglyefficient, but also exceptionally elegant indesign
Perfect finishing / Bigger tubing space / Installationplate improvement / Detachable bottom cover / Elevated service valve / Installation support clip / Compatible with inverter multi system
Installation has never been easier as with thedelicately designed installation elements ofLG air conditioners
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
10/65
10
Specifications SR-6RMG2-02A
GENERAL WALL MOUNTED
4. SpecificationsGeneral Wall Mounted(#1)
Note:
O : Applied, - : No relation* For circuit breaker rating, please conform to local standards wherever necessary.
Some of functions are slightly different depending upon models.The specification may be subject to change without notic for purpose of improvement.
Model Name (LG) GS-C182C4B2 GS-H182C4B2Pet Name Gold Plus Gold Plus
Cooling Capacity (T1) W 5,250 5,130Btu/h. 17,914 17,504
Heating Capacity (H1) W - 5,250Btu/h. - 17,914
Power Input Normal Cooling W 2,050 2,150Heating W - 1,750Running Current(Normal)
Cooling A 9.6 10.0Heating A - 8.0
EERW/W 2.56 2.39
Btu/h.W 8.74 8.14(STAR) 3 2
COP W/W - 3.00
Power Factor Cooling % 97% 98%Heating % - 99%
Cooling Capacity (T3) W 4,600 4,450Btu/h. 15,696 15,184Power Input (T3) W 2,500 2,450Running Current (T3) A 11.5 11.5
EER W/W 1.84 1.82Btu/h.W 6.28 6.20Power Factor % 98.81 96.84
Power Input (Max) Cooling W 2,900 2,900Heating W - 1,890Running Current(Max)
Cooling A 13.5 13.5Heating A - 8.9
Power Factor Cooling % 97.64 97.64Heating % - 96.53Power Supply / V / Hz 1/220/60 1/220/60
Air Circulation Indoor m3/min(CFM),Max 13.0 (460) 13.0 (460)
Outdoor m3/min(CFM),Max 45 (1,590) 45 (1,590)
Moisture Removal /h. 1.9 1.9Noise Level(SoundPressure,1m)
IndoordB(A)3,High 43 43dB(A)3,Med 40 40dB(A)3,Low 37 37
Outdoor dB(A)3,Max 56 56
Refrigerant Charge Type R22 R22g 970 970
Compressor
Type ROTARY ROTARYModel QJ278KCF QJ278KCFMaker LG LGCapacity kcal/h.(Btu/h.) 5,744(19,600) 5,744(19,600)Motor Type PSC PSCMotor Input W 1,867 1,867Oil Type SUNISO 4GSI or NOC NM56 SUNISO 4GSI or NOC NM56Oil Charge cc 500 500O.L.P Name INTERNAL INTERNAL
Blower Motor Type Cross Flow Fan Cross Flow FanOutput W 22 22
Fan MotorType Axial fan Axial fanMotor Type AC Induction AC InductionMotor Output W 64 64
Circuit Breaker A 20 20Power Cord AWG#:P*mm2 3x1.5 3x2.0Connecting Cable AWG#:P*mm2 3x1.5 3x2.0+2x0.75Connecting Tube(. Socket Flare)
Liquid Side mm(in) 6.35(1/4") 6.35(1/4")Gas Side mm(in) 15.88(5/8") 15.88(5/8")Length,std m(in) 5(196) 5(196)
Drain Hose (O.D , I.D) mm(in) 21.5,16 (0.85,0.63) 21.5,16 (0.85,0.63)
Dimension
Indoor(W*H*D)
mm 1030*320*245 1030*320*245inch 40.5*12.6*9.6 40.5*12.6*9.6
Outdoor(W*H*D)
mm 870*655*320 870*655*320inch 34.25*25.79*12.6 34.25*25.79*12.6
Net Weight Indoor kg(lbs) 12.6(27.8) 13(28.7)Outdoor kg(lbs) 40.5(89.3) 42(92.6)Stuffing Quantity In+Out 20/40ft/HC/Truck 57/124/139/- 57/124/139/-Tool Code In+Out SC+UE SC+UE
Functions
AIR FLOW
Air supply outlet 1 1Airflow direction control(left & right) Auto AutoAirflow direction control(up & down) Auto AutoAuto swing(left & right) Auto AutoAuto swing(up & down) Auto AutoAirflow steps(fan/cool/heat) 3/4/- 3/4/3Chaos swing Yes YesChaos wind(auto wind) Yes YesJet cool(Power wind) Yes Yes
Air purifyingDeodorizing filter (Allergy & H1N1 Filter) - -Plasma air purifier - -Prefilter(washable / anti-fungus) Yes Yes
ReliabilityHot start - YesSelf diagnosis Yes YesSoft dry operation Yes Yes
Convenience
Setting Temperature, Cooling 18 - 30 18 - 30Setting Temperature, Heating - 16 - 30Auto changeover - YesAuto cleaning Yes YesAuto operation(artificial intelligence) Yes -Auto restart operation Yes YesForced operation Yes YesSleep mode Yes YesSetting Temperature Range (Cooling) 18-30 18-30Setting Temperature Range (Heating) 16-30 16-30Temperature Increment 1 1Timer(Hr) Yes (24h On/Off) Yes (24h On/Off)
Individualcontrol
Wireless remote controller(simple) - -Wireless LCD remote control Yes(Type1) Yes(Type1)
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
11/65
11
Specifications SR-6RMG2-02A
GENERAL WALL MOUNTED
Note:
O : Applied, - : No relation* For circuit breaker rating, please conform to local standards wherever necessary.
Some of functions are slightly different depending upon models.The specification may be subject to change without notic for purpose of improvement.
Model Name (LG) GS-C242C4B2 GS-H242C4B2Pet Name Gold Plus Gold Plus
Cooling Capacity (T1) W 6,600 6,600Btu/h. 22,520 22,520
Heating Capacity (H1) W - 6,700Btu/h. - 22,861
Power Input Normal Cooling W 2,650 2,650Heating W - 2,500Running Current(Normal)
Cooling A 12.6 12.6Heating A - 12.0
EERW/W 2.49 2.49
Btu/h.W 8.50 8.50(STAR) 3.00 3.00
COP W/W - 2.68
Power Factor Cooling % 96% 96%Heating % - 95%
Cooling Capacity (T3) W 5,750 5,750Btu/h. 19,620 19,620Power Input (T3) W 3,080 3,080Running Current (T3) A 14.5 14.5
EER W/WBtu/h.W 6.37 6.37Power Factor % 96.55 96.55
Power Input (Max) Cooling W 4,000 4,000Heating W - 2,900Running Current(Max)
Cooling A 18.5 18.5Heating A - 14.0
Power Factor Cooling % 98.28 98.28Heating % - 94.16Power Supply / V / Hz 1/220/60 1/220/60
Air Circulation Indoor m3/min(CFM),Max 16.0(566) 16.0(566)
Outdoor m3/min(CFM),Max 48 (1,695) 48 (1,695)
Moisture Removal /h. 2.5 2.5Noise Level(SoundPressure,1m)
IndoordB(A)3,High 43 43dB(A)3,Med 40 40dB(A)3,Low 37 37
Outdoor dB(A)3,Max 56 56
Refrigerant Charge Type R22 R22g 1550 1550
Compressor
Type ROTARY ROTARYModel QP362KBB QP362KBBMaker LG LGCapacity kcal/h.(Btu/h.) 7,911(27,000) 7,911(27,000)Motor Type PSC PSCMotor Input W 2,571 2,571Oil Type NM56 or SUNISO 4GSI NM56 or SUNISO 4GSIOil Charge cc 700 700O.L.P Name INTERNAL INTERNAL
Blower Motor Type Cross Flow Fan Cross Flow FanOutput W 25.6 25.6
Fan MotorType Axial fan Axial fanMotor Type AC Induction AC InductionMotor Output W 64 64
Circuit Breaker A 30 30Power Cord AWG#:P*mm2 3x2.5 3x2.5Connecting Cable AWG#:P*mm2 3x2.5 3x2.5+2x0.75Connecting Tube(. Socket Flare)
Liquid Side mm(in) 9.52(3/8") 9.52(3/8")Gas Side mm(in) 15.88(5/8") 15.88(5/8")Length,std m(in) 5(196) 5(196)
Drain Hose (O.D , I.D) mm(in) 21.5,16 (0.85,0.63) 21.5,16 (0.85,0.63)
Dimension
Indoor(W*H*D)
mm 1030*320*245 1030*320*245inch 40.5*12.6*9.6 40.5*12.6*9.6
Outdoor(W*H*D)
mm 870*655*320 870*655*320inch 34.25*25.79*12.6 34.25*25.79*12.6
Net Weight Indoor kg(lbs) 13.6(30.0) 13.6(30.0)Outdoor kg(lbs) 50,5(111.33) 50,5(111.33)Stuffing Quantity In+Out 20/40ft/HC/Truck 57/124/139/- 57/124/139/-Tool Code In+Out SC+UE SC+UE
Functions
Air flow
Air supply outlet 1 1Airflow direction control(left & right) Auto AutoAirflow direction control(up & down) Auto AutoAuto swing(left & right) Auto AutoAuto swing(up & down) Auto AutoAirflow steps(fan/cool/heat) 3/4/- 3/4/3Chaos swing Yes YesChaos wind(auto wind) Yes YesJet cool(Power wind) Yes Yes
Air purifyingDeodorizing filter (Allergy & H1N1 Filter) - -Plasma air purifier - -Prefilter(washable / anti-fungus) Yes Yes
ReliabilityHot start - YesSelf diagnosis Yes YesSoft dry operation Yes Yes
Convenience
Setting Temperature, Cooling 18 - 30 18 - 30Setting Temperature, Heating - 16 - 30Auto changeover - YesAuto cleaning Yes YesAuto operation(artificial intelligence) Yes -Auto restart operation Yes YesForced operation Yes YesSleep mode Yes YesSetting Temperature Range (Cooling) 18-30 18-30Setting Temperature Range (Heating) 16-30 16-30Temperature Increment 1 1Timer(Hr) Yes (24h On/Off) Yes (24h On/Off)
Individualcontrol
Wireless remote controller(simple) - -Wireless LCD remote control Yes(Type1) Yes(Type1)
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
12/65
12
Specifications SR-6RMG2-02A
GENERAL WALL MOUNTED
General Wall Mounted(#2)Model Name (LG) GS-C122E5B2 GS-H122E5B2
Pet Name Fresh Fresh
Cooling Capacity (T1) WBtu/h.
Heating Capacity (H1) WBtu/h.
Power Input Normal Cooling WHeating WRunning Current(Normal)
Cooling AHeating A
EERW/W
Btu/h.W
(STAR)COP W/W
Power Factor Cooling %Heating %
Cooling Capacity (T3) WBtu/h.Power Input (T3) WRunning Current (T3) A
EER W/WBtu/h.WPower Factor %
Power Input (Max) Cooling WHeating WRunning Current(Max)
Cooling AHeating A
Power Factor Cooling %Heating %Power Supply / V / Hz
Air Circulation Indoor m3/min(CFM),Max
Outdoor m 3/min(CFM),MaxMoisture Removal l / h.
Noise Level(SoundPressure,1m)
IndoordB(A)+3,HighdB(A)+3,MeddB(A)+3,Low
Outdoor dB(A)+3,Max
Refrigerant Charge Typeg
Compressor
TypeModelMakerCapacity kcal/h.(Btu/h.)Motor TypeMotor Input WOil TypeOil Charge ccO.L.P Name
Blower Motor TypeOutput W
Fan MotorTypeMotor TypeMotor Output W
Circuit Breaker APower Cord AWG#:P*mm 2Connecting Cable AWG#:P*mm 2
Connecting Tube( . Socket Flare)
Liquid Side mm(in)Gas Side mm(in)Length,std m(in)
Drain Hose (O.D , I.D) mm(in)
Dimension
Indoor(W*H*D)
mminch
Outdoor(W*H*D)
mminch
Net Weight Indoor kg(lbs)Outdoor kg(lbs)Tool Code In+Out
Operation Range Cooling(Outdoor) C(F)Heating(Outdoor) C(F)Max. Piping Length m(ft)Max. Elevation Difference m(ft)
Functions
Air flow
Air supply outletAirflow direction control(left & right)Airflow direction control(up & down)Auto swing(left & right)Auto swing(up & down)Airflow steps(fan/cool/heat)Chaos swingChaos wind(auto wind)Jet cool(Power wind)
Air purifyingDeodorizing filter (Allergy & H1N1 Filter)Plasma air purifier
Prefilter(Dual Protection Filter)Reliability
Hot startSelf diagnosisSoft dry operation
Convenience
Setting Temperature, CoolingSetting Temperature, HeatingAuto changeoverAuto cleaningAuto operation(artificial intelligence)Auto restart operationForced operationSleep modeSetting Temperature Range (Cooling)Setting Temperature Range (Heating)Temperature IncrementTimer(Hr)
Individual control Wireless remote controller(simple)Wireless LCD remote control
Note:O : Applied, - : No relation* For circuit breaker rating, please conform to local standards wherever necessary.
Some of functions are slightly different depending upon models.The specification may be subject to change without notic for purpose of improvement.
3,520 3,37212,011 11,506
- 3,520- 12,011
1,200 1,200- 1,150
5.5 5.5- 5.3
2.93 2.8110.01 9.59
6 5- 3.0699% 99%
- 99%3100 3000
10,578 10,2361400 14006.5 6.5
2.21 2.147.56 7.31
97.90 97.901500 1500
- 13506.9 6.9- 6.2
98.81 98.81- 98.97
1/220/60 1/220/6010 10
33 (1,165) 33 (1,165)1.54 1.4540 4034 3430 3048 48
R22 R22850 910
ROTARY ROTARYQK185KBE QK185KBE
LG LG3276 (13,000) 3276 (13,000)
PSC PSC1215 1215
4GSI or NM56 4GSI or NM56350 350
MRA12070-12027 MRA12070-12027Cross Flow Fan Cross Flow Fan
15.1 15.1Axial fan Axial fan
AC Induction AC Induction41 4115 15
3x1.0 3x1.03x1.0 3x1.0+2x0.75
6.35(1/4) 6.35(1/4)12,7(1/2") 12,7(1/2")
5(196) 5(196)21.5,16(0.85,0.63) 21.5,16(0.85,0.63)
890*282*165 890*282*16532.24*11.1*6.5 32.24*11.1*6.5770*540*245 770*540*245
30,31*21,25*9,64 30,31*21,25*9,649.0(19.8) 9.0(19.8)
30.0(66.1) 32.0(70.5)SE+UL SE+UL
21~54(69.8~129.2) 21~54(69.8~129.2)- 1~24(33.8~75.2)
15(49.2) 15(49.2)10(33) 10(33)
1 1Auto AutoAuto AutoAuto AutoAuto Auto3/4/- 3/4/3Yes YesYes YesYes Yes
- -- -
Yes Yes- YesYes YesYes Yes
18 - 30 18 - 30- 16 - 30- Yes
Yes YesYes -Yes YesYes YesYes Yes
18-30 18-30- 16-301 1
Yes (24h On/Off) Yes (24h On/Off)- -
Yes(Type2) Yes(Type2)
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
13/65
13
Specifications SR-6RMG2-02A
GENERAL WALL MOUNTED
Model Name (LG) GS-C1825SA3 GS-H1825SA3Pet Name Smart Smart
Cooling Capacity (T1) WBtu/h.
Heating Capacity (H1) WBtu/h.
Power Input Normal Cooling WHeating WRunning Current(Normal)
Cooling AHeating A
EERW/W
Btu/h.W
(STAR)COP W/W
Power Factor Cooling %Heating %
Cooling Capacity (T3) WBtu/h.Power Input (T3) WRunning Current (T3) A
EER W/WBtu/h.WPower Factor %
Power Input (Max) Cooling WHeating WRunning Current(Max)
Cooling AHeating A
Power Factor Cooling %Heating %Power Supply / V / Hz
Air Circulation Indoor m3/min(CFM),Max
Outdoor m 3/min(CFM),MaxMoisture Removal l / h.
Noise Level(SoundPressure,1m)
IndoordB(A)+3,HighdB(A)+3,MeddB(A)+3,Low
Outdoor dB(A)+3,Max
Refrigerant Charge Typeg
Compressor
TypeModelMakerCapacity kcal/h.(Btu/h.)Motor TypeMotor Input WOil TypeOil Charge ccO.L.P Name
Blower Motor TypeOutput W
Fan MotorTypeMotor TypeMotor Output W
Circuit Breaker APower Cord AWG#:P*mm 2Connecting Cable AWG#:P*mm 2
Connecting Tube( . Socket Flare)
Liquid Side mm(in)Gas Side mm(in)Length,std m(in)
Drain Hose (O.D , I.D) mm(in)
Dimension
Indoor(W*H*D)
mminch
Outdoor(W*H*D)
mminch
Net Weight Indoor kg(lbs)Outdoor kg(lbs)Tool Code In+Out
Operation Range Cooling(Outdoor) C(F)Heating(Outdoor) C(F)Max. Piping Length m(ft)Max. Elevation Difference m(ft)
Functions
Air flow
Air supply outletAirflow direction control(left & right)Airflow direction control(up & down)Auto swing(left & right)Auto swing(up & down)Airflow steps(fan/cool/heat)Chaos swingChaos wind(auto wind)Jet cool(Power wind)
Air purifyingDeodorizing filter (Allergy & H1N1 Filter)Plasma air purifier
Prefilter(Dual Protection Filter)Reliability
Hot startSelf diagnosisSoft dry operation
Convenience
Setting Temperature, CoolingSetting Temperature, HeatingAuto changeoverAuto cleaningAuto operation(artificial intelligence)Auto restart operationForced operationSleep modeSetting Temperature Range (Cooling)Setting Temperature Range (Heating)Temperature IncrementTimer(Hr)
Individual control Wireless remote controller(simple)Wireless LCD remote control
Note:O : Applied, - : No relation* For circuit breaker rating, please conform to local standards wherever necessary.
Some of functions are slightly different depending upon models.The specification may be subject to change without notic for purpose of improvement.
5,130 4,99017,504 17,027
- 5,100- 17,391
2,000 2,100- 1,750
9.5 10.0- 8.0
2.57 2.388.75 8.11
3 2- 2.9196% 95%
- 99%4,500 4,300
15,355 14,6722,300 2,450
11 11.51.96 1.766.68 5.99
95.04 96.842,564 2,515
- 2,10012.00 12.0
- 9.697.12 95.27
- 99.431/220/60 1/220/60
13.0 (459) 13.0 (459)33 (1165) 48 (1,695)
1.8 2.040 4037 3734 3454 56
R22 R22720 1000
ROTARY ROTARYQJ278KCF QJ278KCF
LG LG5,744(19,600) 5,744(19,600)
PSC PSC1,867 1,867
4GSI or NM56 4GSI or NM56500 500
INTERNAL INTERNALCross Flow Fan Cross Flow Fan
20.6 20.6Axial fan Axial fan
AC Induction AC Induction41 63.620 20
3x1.5 3x1.53x1.5 3x1.5+2x0.75
6.35(1/4") 6.35(1/4")15.88(5/8") 15.88(5/8")
5(196) 5(196)21.5,16 (0.85,0.63) 21.5,16 (0.85,0.63)
1090*300*180 1090*300*18042.9*11.8*7.09 42.9*11.8*7.09
770*540*245 870*655*32030.3*21.3*9.7 34.25*25.79*12.6
11.5(25.4) 11.5(25.4)34(75.0) 45,5(100.3)S5+UL S5+UE
21~54(69.8~129.2) 21~54(69.8~129.2)- 1~24(33.8~75.2)
15(49.2) 15(49.2)10(33) 10(33)
1 1Manual Manual
Auto AutoManual Manual
Auto Auto-/4/- -/4/3Yes YesYes YesYes Yes
- -- -
Yes Yes- YesYes YesYes Yes
18 - 30 18 - 30- 16 - 30- -- -- -
Yes YesYes YesYes Yes
18-30 18-30- 16-301 1
Yes (7h Off) Yes (24h Off)Yes(Type3) Yes(Type3)
- -
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
14/65
14
Specifications SR-6RMG2-02A
GENERAL WALL MOUNTED
Model Name (LG) GS-C1825NB2 GS-H1825NB2Pet Name Fresh Fresh
Cooling Capacity (T1) WBtu/h.
Heating Capacity (H1) WBtu/h.
Power Input Normal Cooling WHeating WRunning Current(Normal)
Cooling AHeating A
EERW/W
Btu/h.W
(STAR)COP W/W
Power Factor Cooling %Heating %
Cooling Capacity (T3) WBtu/h.Power Input (T3) WRunning Current (T3) A
EER W/WBtu/h.WPower Factor %
Power Input (Max) Cooling WHeating WRunning Current(Max)
Cooling AHeating A
Power Factor Cooling %Heating %Power Supply / V / Hz
Air Circulation Indoor m3/min(CFM),Max
Outdoor m 3/min(CFM),MaxMoisture Removal l / h.
Noise Level(SoundPressure,1m)
IndoordB(A)+3,HighdB(A)+3,MeddB(A)+3,Low
Outdoor dB(A)+3,Max
Refrigerant Charge Typeg
Compressor
TypeModelMakerCapacity kcal/h.(Btu/h.)Motor TypeMotor Input WOil TypeOil Charge ccO.L.P Name
Blower Motor TypeOutput W
Fan MotorTypeMotor TypeMotor Output W
Circuit Breaker APower Cord AWG#:P*mm 2Connecting Cable AWG#:P*mm 2
Connecting Tube( . Socket Flare)
Liquid Side mm(in)Gas Side mm(in)Length,std m(in)
Drain Hose (O.D , I.D) mm(in)
Dimension
Indoor(W*H*D)
mminch
Outdoor(W*H*D)
mminch
Net Weight Indoor kg(lbs)Outdoor kg(lbs)Tool Code In+Out
Operation Range Cooling(Outdoor) C(F)Heating(Outdoor) C(F)Max. Piping Length m(ft)Max. Elevation Difference m(ft)
Functions
Air flow
Air supply outletAirflow direction control(left & right)Airflow direction control(up & down)Auto swing(left & right)Auto swing(up & down)Airflow steps(fan/cool/heat)Chaos swingChaos wind(auto wind)Jet cool(Power wind)
Air purifyingDeodorizing filter (Allergy & H1N1 Filter)Plasma air purifier
Prefilter(Dual Protection Filter)Reliability
Hot startSelf diagnosisSoft dry operation
Convenience
Setting Temperature, CoolingSetting Temperature, HeatingAuto changeoverAuto cleaningAuto operation(artificial intelligence)Auto restart operationForced operationSleep modeSetting Temperature Range (Cooling)Setting Temperature Range (Heating)Temperature IncrementTimer(Hr)
Individual control Wireless remote controller(simple)Wireless LCD remote control
Note:O : Applied, - : No relation* For circuit breaker rating, please conform to local standards wherever necessary.
Some of functions are slightly different depending upon models.The specification may be subject to change without notic for purpose of improvement.
5,130 5,13017,504 17,504
- 5,250- 17,914
2,000 2,050- 1,750
9.5 9.8- 8.0
2.57 2.508.75 8.54
3 3- 3.0096% 95%
- 99%4,500 4,450
15,355 15,1842,300 2,45011.0 11.51.96 1.826.68 6.20
95.04 96.842,564 2,515
- 2,10012.00 12.0
- 9.697.12 95.27
- 99.431/220/60 1/220/60
13.0 (459) 13.0 (459)33 (1165) 48 (1,695)
1.8 240 4037 3734 3454 56
R22 R22720 1000
ROTARY ROTARYQJ278KCF QJ278KCF
LG LG5,744(19,600) 5,744(19,600)
PSC PSC1,867 1,867
4GSI or NM56 4GSI or NM56500 500
INTERNAL INTERNALCross Flow Fan Cross Flow Fan
20.6 20.6Axial fan Axial fan
AC Induction AC Induction41 63.620 20
3x1.5 3x1.53x1.5 3x1.5+2x0.75
6.35(1/4") 6.35(1/4")15.88(5/8") 15.88(5/8")
5(196) 5(196)
21.5,16 (0.85,0.63) 21.5,16 (0.85,0.63)1090*300*180 1090*300*18042.9*11.8*7.09 42.9*11.8*7.09
770*540*245 870*655*32030.3*21.3*9.7 34.25*25.79*12.6
11.5(25.4) 11.5(25.4)34(75.0) 45,5(100.3)S5+UL S5+UE
21~54(69.8~129.2) 21~54(69.8~129.2)- 1~24(33.8~75.2)
15(49.2) 15(49.2)10(33) 10(33)
1 1Auto AutoAuto AutoAuto AutoAuto Auto3/4/- 3/4/3Yes YesYes YesYes Yes
- -- -
Yes Yes- YesYes YesYes Yes
18 - 30 18 - 30- 16 - 30- Yes
Yes YesYes -Yes YesYes YesYes Yes
18-30 18-30- 16-301 1
Yes (24h On/Off) Yes (24h On/Off)- -
Yes(Type2) Yes(Type2)
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
15/65
15
Specifications SR-6RMG2-02A
GENERAL WALL MOUNTED
Note:O : Applied, - : No relation* For circuit breaker rating, please conform to local standards wherever necessary.
Some of functions are slightly different depending upon models.The specification may be subject to change without notic for purpose of improvement.
Model Name (LG) GS-C2425SA3 GS-H2425SA3Pet Name Smart Smart
Cooling Capacity (T1) WBtu/h.
Heating Capacity (H1) WBtu/h.
Power Input Normal Cooling WHeating WRunning Current(Normal)
Cooling AHeating A
EERW/W
Btu/h.W
(STAR)COP W/W
Power Factor Cooling %Heating %
Cooling Capacity (T3) WBtu/h.Power Input (T3) WRunning Current (T3) A
EER W/WBtu/h.WPower Factor %
Power Input (Max) Cooling WHeating WRunning Current(Max)
Cooling AHeating A
Power Factor Cooling %Heating %Power Supply / V / Hz
Air Circulation Indoor m3/min(CFM),Max
Outdoor m3/min(CFM),MaxMoisture Removal l / h.
Noise Level(SoundPressure,1m)
IndoordB(A)+3,HighdB(A)+3,MeddB(A)+3,Low
Outdoor dB(A)+3,MaxRefrigerant Charge Typeg
Compressor
TypeModelMakerCapacity kcal/h.(Btu/h.)Motor TypeMotor Input WOil TypeOil Charge ccO.L.P Name
Blower Motor TypeOutput W
Fan MotorTypeMotor TypeMotor Output W
Circuit Breaker APower Cord AWG#:P*mm2Connecting Cable AWG#:P*mm2
Connecting Tube( . Socket Flare)
Liquid Side mm(in)Gas Side mm(in)Length,std m(in)
Drain Hose (O.D , I.D) mm(in)
Dimension
Indoor(W*H*D)
mminch
Outdoor(W*H*D)
mminch
Net Weight Indoor kg(lbs)Outdoor kg(lbs)Tool Code In+Out
Operation Range Cooling(Outdoor) C(F)Heating(Outdoor) C(F)Max. Piping Length m(ft)Max. Elevation Difference m(ft)
Functions
Air flow
Air supply outletAirflow direction control(left & right)Airflow direction control(up & down)Auto swing(left & right)Auto swing(up & down)Airflow steps(fan/cool/heat)Chaos swingChaos wind(auto wind)Jet cool(Power wind)
Air purifyingDeodorizing filter (Allergy & H1N1 Filter)Plasma air purifier
Prefilter(Dual Protection Filter)Reliability
Hot startSelf diagnosisSoft dry operation
Convenience
Setting Temperature, CoolingSetting Temperature, HeatingAuto changeoverAuto cleaningAuto operation(artificial intelligence)Auto restart operationForced operationSleep modeSetting Temperature Range (Cooling)Setting Temperature Range (Heating)Temperature IncrementTimer(Hr)
Individual control Wireless remote controller(simple)Wireless LCD remote control
6,450 6,30022,008 21,496
- 6,650- 22,691
2,500 2,700- 2,600
11.6 12.6- 12.0
2.58 2.338.80 7.96
3 2- 2.5698% 97%
- 98%5,600 5,400
19,108 18,4263,000 3,25013.9 15.21.87 1.666.37 5.67
98.10 97.193,400 3,350
- 3,04016.0 15.7
- 14.096.59 96.99
- 98.701/220/60 1/220/6015.0(530) 15.0 (530)48 (1,695) 48 (1,695)
2.8 2.844 4440 4036 3656 56
R22 R22900 1700
ROTARY ROTARYQP362KBB QP362KBB
LG LG7,911(27,000) 7,911(27,000)
PSC PSC2,571 2,571
4GSI or NM56 4GSI or NM56700 700
INTERNAL INTERNALCross Flow Fan Cross Flow Fan
30 30Axial fan Axial fan
AC Induction AC Induction63.6 63.630 30
3x2.5 3x2.53x2.5 3x2.5+2x0.75
9.52(3/8") 9.52(3/8")15.88(5/8") 15.88(5/8")
5(196) 5(196)21.5,16 (0.85,0.63) 21.5,16 (0.85,0.63)
1090*300*180 1090*300*18042.9*11.8*7.09 42.9*11.8*7.09870*655*320 870*655*320
34.25*25.79*12.6 34.25*25.79*12.612.0(26.5) 12.0(26.5)42,0(92.6) 50,5(111.3)
S5+UE S5+UE21~54(69.8~129.2) 21~54(69.8~129.2)
- 1~24(33.8~75.2)15(49.2) 15(49.2)10(33) 10(33)
1 1Manual Manual
Auto AutoManual Manual
Auto Auto-/4/- -/4/3Yes YesYes YesYes Yes
- -- -
Yes Yes- YesYes YesYes Yes
18 - 30 18 - 30- 16 - 30- -- -- -
Yes YesYes YesYes Yes
18-30 18-30- 16-301 1
Yes (7h Off) Yes (24h Off)Yes(Type3) Yes(Type3)
- -
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
16/65
16
Specifications SR-6RMG2-02A
GENERAL WALL MOUNTED
Model Name (LG) GS-C2425NB2 GS-H2425NB2Pet Name Fresh Fresh
Cooling Capacity (T1) WBtu/h.
Heating Capacity (H1) WBtu/h.
Power Input Normal Cooling WHeating WRunning Current(Normal)
Cooling AHeating A
EERW/W
Btu/h.W
(STAR)COP W/W
Power Factor Cooling %Heating %
Cooling Capacity (T3) WBtu/h.Power Input (T3) WRunning Current (T3) A
EER W/WBtu/h.WPower Factor %
Power Input (Max) Cooling WHeating WRunning Current(Max)
Cooling AHeating A
Power Factor Cooling %Heating %Power Supply / V / Hz
Air Circulation Indoor m3/min(CFM),Max
Outdoor m 3/min(CFM),MaxMoisture Removal l / h.
Noise Level(SoundPressure,1m)
IndoordB(A)+3,HighdB(A)+3,MeddB(A)+3,Low
Outdoor dB(A)+3,Max
Refrigerant Charge Typeg
Compressor
TypeModelMakerCapacity kcal/h.(Btu/h.)Motor TypeMotor Input WOil TypeOil Charge ccO.L.P Name
Blower Motor TypeOutput W
Fan MotorTypeMotor TypeMotor Output W
Circuit Breaker APower Cord AWG#:P*mm 2Connecting Cable AWG#:P*mm 2
Connecting Tube( . Socket Flare)
Liquid Side mm(in)Gas Side mm(in)Length,std m(in)
Drain Hose (O.D , I.D) mm(in)
Dimension
Indoor(W*H*D)
mminch
Outdoor(W*H*D)
mminch
Net Weight Indoor kg(lbs)Outdoor kg(lbs)Tool Code In+Out
Operation Range Cooling(Outdoor) C(F)Heating(Outdoor) C(F)Max. Piping Length m(ft)Max. Elevation Difference m(ft)
Functions
Air flow
Air supply outletAirflow direction control(left & right)Airflow direction control(up & down)Auto swing(left & right)Auto swing(up & down)Airflow steps(fan/cool/heat)Chaos swingChaos wind(auto wind)Jet cool(Power wind)
Air purifyingDeodorizing filter (Allergy & H1N1 Filter)Plasma air purifier
Prefilter(Dual Protection Filter)Reliability
Hot startSelf diagnosisSoft dry operation
Convenience
Setting Temperature, CoolingSetting Temperature, HeatingAuto changeoverAuto cleaningAuto operation(artificial intelligence)Auto restart operationForced operationSleep modeSetting Temperature Range (Cooling)Setting Temperature Range (Heating)Temperature IncrementTimer(Hr)
Individual control Wireless remote controller(simple)Wireless LCD remote control
Note:O : Applied, - : No relation* For circuit breaker rating, please conform to local standards wherever necessary.
Some of functions are slightly different depending upon models.The specification may be subject to change without notic for purpose of improvement.
6,450 6,60022,008 22,520
- 6,850- 23,373
2,500 2,640- 2,600
11.6 12.6- 12.0
2.58 2.508.80 8.53
3 3- 2.6398% 95%
- 98%5,600 5,550
19,108 18,9373,000 3,25013.9 15.21.87 1.716.37 5.83
98.10 97.193,400 3,350
- 3,04016.0 15.7
- 14.096.59 96.99
- 98.701/220/60 1/220/6015.0(530) 15.0 (530)48 (1,695) 48 (1,695)
2.8 2.844 4440 4036 3656 56
R22 R22900 1700
ROTARY ROTARYQP362KBB QP362KBB
LG LG7,911(27,000) 7,911(27,000)
PSC PSC2,571 2,571
4GSI or NM56 4GSI or NM56700 700
INTERNAL INTERNALCross Flow Fan Cross Flow Fan
30 30Axial fan Axial fan
AC Induction AC Induction63.6 63.630 30
3x2.5 3x2.53x2.5 3x2.5+2x0.75
9.52(3/8") 9.52(3/8")15.88(5/8") 15.88(5/8")
5(196) 5(196)
21.5,16 (0.85,0.63) 21.5,16 (0.85,0.63)1090*300*180 1090*300*18042.9*11.8*7.09 42.9*11.8*7.09870*655*320 870*655*320
34.25*25.79*12.6 34.25*25.79*12.612.0(26.5) 12.0(26.5)42,0(92.6) 50,5(111.3)
S5+UE S5+UE21~54(69.8~129.2) 21~54(69.8~129.2)
- 1~24(33.8~75.2)15(49.2) 15(49.2)10(33) 10(33)
1 1Auto AutoAuto AutoAuto AutoAuto Auto3/4/- 3/4/3Yes YesYes YesYes Yes
- -- -
Yes Yes- YesYes YesYes Yes
18 - 30 18 - 30- 16 - 30- Yes
Yes YesYes -Yes YesYes YesYes Yes
18-30 18-30- 16-301 1
Yes (24h On/Off) Yes (24h On/Off)- -
Yes(Type2) Yes(Type2)
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
17/65
17
Dimensional Drawings SR-6RMG2-02A
GENERAL WALL MOUNTED
2 5 0
1 0 3 0
3 2 5 2 1 0
7 0
7 0
6 9
5 6
R i g h t r e a r
p i p
i n g
L e f t r e a r
p i p i n g
I n s t a l l a t i o n P l a t e
M e a s u
r i n g T a p e
M e a s u
r i n g T a p e
H a n g e r
P l a c e a l e v
e l o n r a i s e d t a b
U n i t O u
t l i n e
2 0 7
1 0 5
( U n i
t : m m
)
4 6 0
5 7 0
L i b e r o
R / E
C H A S S I S C O D E : S
C
4
5. Dimensional Drawings5.1 Indoor Unit
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
18/65
18
Dimensional Drawings SR-6RMG2-02A
GENERAL WALL MOUNTED
C H A S S I S C O D E :
S 5
1 0 9 0
1 8 0
1 7 8
3
3 0 0
2
3 0 0
5 3
4 8 . 5
5
4
5 6 7 . 5
1 0 7
2 5 - 5
2 8 . 5
3 4 5
5 0 5 0 x
6 =
3 0 0
5
7 6 . 6
8 2 . 6
1 8 0 3 5
5 0
1 1 7 . 6
5 3 . 2
2 - R 1 6
1
W A L L M O U
N T E D
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
19/65
19
Dimensional Drawings SR-6RMG2-02A
GENERAL WALL MOUNTED
A R T C O O L M i r r o r
D i s p l a y
& s i g n a l r e c e
i v e r
P a r
t N a m e
F r o n
t p a n e l
A i r s u c t
i o n g r
i l l e
I n s t a l
l a t i o n p l a t e
K n o c k o u
t h o l e
F o r p
i p e a n
d c a
b l e
5
N o . 2 4 3 1
R e m a r
k
N o t e
9 1 2
5 0
5 0 * 6 = 3
0 0
3 5 4
5 6 7
2 8
7 1 7 7
1 4 8
1 0 7
2 8 2
2 8 2
5 1
5 3
5 0 3 7
5 1
2 - R 1 6
5
1 6 5
2
4
1 7 1
3
1 . U n i t s h o u
l d b e i n s t a l
l e d i n c o m p l
i a n c e w
i t h t h e
i n s t a
l l a t i o n m a n u a
l
i n t h e p r o d u c
t b o x .
2 . U n i t s h a l
l b e g r o u n d e d
i n a c c o r d a n c e w
i t h t h e
l o c a l r e g u
l a t i o n s o r
a p p
l i c a b
l e n a
t i o n a
l c o d e s .
3 . T h e U n i
t i s p o w e r e d
f r o m
t h e o u
t d o o r u n
i t . T h e r e
f o r e p o w e r c a
b l e
s h o u
l d b e c o n n e c
t e d w
i t h t h e o u
t d o o r u n
i t .
1
C H A S S I S C O D E : S
E
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
20/65
20
Dimensional Drawings SR-6RMG2-02A
GENERAL WALL MOUNTED
5.2 Outdoor Unit
1
G a s
P i p e
C o n n e c t
i o n
P o r
t
P a r
t N a m e
A i r D i c h a r g e
G r i l
l e
L i q u
i d P i p e
C o n n e c t
i o n
P o r
t
C o n
t r o l
B o x
N o . 2 4
E a r
t h S c r e w
5 3 1
R e m a r
k
N o t e
1 . T h e u n
i t s h o u
l d b e i n s t a l
l e d a c c o r d
i n g
t o i n s t a l
l a t i o n m a n u a
l w h i c h
i s
i n t h e p r o
d u c t
b o x .
2 . I n a n a r e a o r a a p a c e
h a v i n g n o p r o p e r a i r c
i r c u l a t
i o n , a n a i r g u i
d e
s h o u
l d b e i n s t a l
l e d i n t h e o u
t d o o r u n
i t .
7 6 , S
e o n g s a n -
d o n g , C
h a n g w o n
C i t y
, G y e o n g n a m ,
6 4 1 - 7 1 3 , K o r e a
w w w . l g
e . c o m
/ a i r c o n
d i t i o n e r
C H A S S I S C
O D E : U
E
O u t
d o o r U n i
t
U n i
t : m m
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
21/65
21
Dimensional Drawings SR-6RMG2-02A
GENERAL WALL MOUNTED
C H A S S I S
C O D E :
U L
5 4 0
1 0
6 5 4 . 3
7 7 0
4 5
0
2 7 5
4 5 0
2 6 1
5
2 3
5 5 . 3
4
2 4 5
1
5 6
2 4 5
2 8 5
7 7 0
5 1 8 . 4
2 6 7
O u t
d o o r
U n i t
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
22/65
22
Wiring Diagrams SR-6RMG2-02A
GENERAL WALL MOUNTED
6. Wiring Diagrams6.1 Indoor Units
CN-MOTOR
CN-U/D
CN-L/R
CN-OPTION
CN-DISP3
CN-HVB
CN-12V
CN-TH1
CN-DISP2
CN-SUB
Model : GS-C182C4B2, GS-C242C4B2
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
23/65
23
Wiring Diagrams SR-6RMG2-02A
GENERAL WALL MOUNTED
Model : GS-H182C4B2, GS-H242C4B2
CN-U/D
CN-L/R
CN-DISP3
CN-SUB
CN-OPTION
CN-HVB
CN-12V
CN-TH1
CN-DISP2
CN-4WAY
CN-MOTOR
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
24/65
24
Wiring Diagrams SR-6RMG2-02A
GENERAL WALL MOUNTED
Model : GS-H1825SA3, GS-H2425SA3, GS-H1825NB2, GS-H2425NB2 , GS-H122E5B2
MOTOROR
RDB%
B% B%B% B%
P O W E R
GN/YL
GN/YL
B R ( B % / P l a i n e d )
B L ( W H / R i b b e d ) B%
YL
SH-CAPA
TERMINALBLOC%
RY-4WAY
RY-FAN
CN-MOTOR
THERMISTOR
OPTIONPWB ASM.
STEPMOTOR
C N
- T H 1
C N
- U / D C N
- O P T I O N
C N
- L / R
C N - H
V B
C N - 1
2 V
C N
- D I S P 1
DISPLAY
PWB ASM.
P/No : 3854A20427B
TRIAC
MAIN PWB ASM.
CN-N1
CN-N2
CN-4WAY
RY-COMP
TO OUTDOOR UNIT
4 31
( L )
BR
B R B
L B %
R D
G N / Y L
2 ( N )
3
4
1 ( L )
2 ( N )
3
4
FUSE250V T2A
STEPMOTOR
H.V.ASM.
S/W1
AIRCLEAN(PLASMA)
C N
- D I S P 2
CONDUCTIVE
ENCLOSUREMOTOR ONLY
CN-L/R CN-U/D CN-HVB CN-DISP2
CN-DISP1
CN-OPTION
CN-12V
CN-MOTOR
CN-TH1
CN-N1
CN-N2
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
25/65
25
Wiring Diagrams SR-6RMG2-02A
GENERAL WALL MOUNTED
Model : GS-C1825SA3 GS-C2425SA3 GS-C1825NB2 GS-C2425NB2 GS-C122E5B2
CN-MOTOR
CN-N1
CN-N2CN-DISP2(BL)
CN-L/R(BL)
CN-U/D(WH)
CN-HVB(BL)
CN-DISP1(WH)
CN-TH1(WH)
CN-12V(YL)
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
26/65
26
Wiring Diagrams SR-6RMG2-02A
GENERAL WALL MOUNTED
CapacitorTerminal Block
Model : GS-C122E5B2
6.2 Outdoor Unit
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
27/65
27
Wiring Diagrams SR-6RMG2-02A
GENERAL WALL MOUNTED
Capacitor
Terminal Block
Model : GS-H122E5B2
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
28/65
28
Wiring Diagrams SR-6RMG2-02A
GENERAL WALL MOUNTED
CapacitorTerminal Block
Model : GS-C1825SA3, GS-C1825NB2
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
29/65
29
Wiring Diagrams SR-6RMG2-02A
GENERAL WALL MOUNTED
CapacitorTerminal Block
Model : GS-H1825SA3, GS-H2425SA3, GS-H1825NB2, GS-H2425NB2, GS-H182C4B2, GS-H242C4B2
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
30/65
30
Wiring Diagrams SR-6RMG2-02A
GENERAL WALL MOUNTED
CapacitorTerminal Block
Model : GS-C2425SA3, GS-C2425NB2, GS-C182C4B2, GS-C242C4B2
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
31/65
31
Refrigerant Cycle Diagram SR-6RMG2-02A
GENERAL WALL MOUNTED
7. Refrigerant Cycle Diagram
INDOOR UNIT OUTDOOR UNIT
HEATE CHANGE(EVAPORATOR)
HEATE CHANGE(CONDENSER)
COMPRESSORGAS SIDE
LIQUID SIDE
CAPILLARY TUBE
rotcennoCBCPnoitpircseD.COL
Th1 Thermistor for indoor air temperatureCN-TH1
Th2 Thermistor for evaporating temperature
INDOOR UNIT OUTDOOR UNIT
HEATE CHANGE(EVAPORATOR)
HEATE CHANGE(CONDENSER)
COMPRESSOR
ACCUMU%LATOR
GAS SIDE
3-WAY VALVE
LIQUID SIDE
3-WAY VALVE
CAPILLARY TUBE
CHEC VALVE(Heating Model only)
COOLINGHEATING
REVERSINGVALVE(Heating Model Only)
Model : GS-C122*, GS-C182*, GS-C242*
Model : GS-H122*, GS-H182*, GS-H242*
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
32/65
32
Capacity Tables SR-6RMG2-02A
GENERAL WALL MOUNTED
8. Capacity Tables
Model : GS-C182C4B2
Model : GS-H182C4B2
Model : GS-C242C4B2
Cooling capacity
CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14 20 4.40 3.41 1.30 4.30 3.37 1.55 4.10 3.28 1.80 3.98 3.21 1.90 3.83 3.14 2.02 3.74 3.10 2.09
16 22 5.13 3.87 1.32 5.02 3.83 1.57 4.79 3.72 1.83 4.64 3.64 1.93 4.47 3.55 2.05 4.37 3.50 2.1218 25 5.73 4.21 1.34 5.60 4.16 1.59 5.34 4.03 1.86 5.18 3.94 1.96 4.99 3.84 2.08 4.87 3.78 2.1519 27 5.99 4.35 1.37 5.86 4.30 1.62 5.59 4.16 1.89 5.42 4.07 1.99 5.22 3.96 2.12 5.10 3.90 2.1922 30 6.58 4.61 1.38 6.44 4.55 1.64 6.13 4.40 1.91 5.95 4.29 2.02 5.73 4.18 2.14 5.60 4.10 2.2124 32 6.82 4.69 1.40 6.68 4.62 1.66 6.37 4.46 1.94 6.17 4.35 2.04 5.95 4.23 2.17 5.81 4.15 2.25
Indoor AirTemperature
Outdoor Air Temperature : CDB20 25 32 35 40 43
CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14 20 4.40 3.36 1.30 4.30 3.33 1.55 4.10 3.24 1.80 3.98 3.17 1.90 3.83 3.10 2.02 3.74 3.06 2.09
16 22 5.13 3.82 1.32 5.02 3.78 1.57 4.79 3.67 1.83 4.64 3.59 1.93 4.47 3.50 2.05 4.37 3.45 2.1218 25 5.73 4.15 1.34 5.60 4.10 1.59 5.34 3.98 1.86 5.18 3.89 1.96 4.99 3.79 2.08 4.87 3.73 2.1519 27 5.99 4.29 1.37 5.86 4.24 1.62 5.59 4.11 1.89 5.42 4.01 1.99 5.22 3.91 2.12 5.10 3.85 2.1922 30 6.58 4.55 1.38 6.44 4.49 1.64 6.13 4.34 1.91 5.95 4.24 2.02 5.73 4.12 2.14 5.60 4.05 2.2124 32 6.82 4.63 1.40 6.68 4.56 1.66 6.37 4.40 1.94 6.17 4.29 2.04 5.95 4.17 2.17 5.81 4.10 2.25
Indoor AirTemperature
Outdoor Air Temperature : CDB20 25 32 35 40 43
CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14 20 5.70 4.18 1.77 5.58 4.14 2.10 5.32 4.03 2.44 5.16 3.95 2.58 4.97 3.86 2.74 4.86 3.81 2.83
16 22 6.66 4.75 1.80 6.52 4.70 2.13 6.21 4.56 2.48 6.02 4.47 2.62 5.80 4.36 2.78 5.66 4.29 2.8718 25 7.43 5.16 1.82 7.27 5.11 2.16 6.93 4.95 2.52 6.72 4.84 2.66 6.47 4.72 2.82 6.32 4.64 2.9219 27 7.77 5.34 1.85 7.61 5.28 2.20 7.25 5.11 2.56 7.03 4.99 2.70 6.77 4.87 2.87 6.62 4.79 2.9722 30 8.53 5.66 1.88 8.35 5.59 2.23 7.96 5.40 2.60 7.72 5.27 2.73 7.43 5.13 2.91 7.26 5.04 3.0024 32 8.85 5.76 1.91 8.67 5.68 2.26 8.26 5.48 2.63 8.01 5.35 2.77 7.71 5.19 2.95 7.53 5.10 3.05
Indoor AirTemperature
Outdoor Air Temperature : CDB20 25 32 35 40 43
SymbolDB : Dry bulb temperature [C]WB : Wet bulb temperature [C]TC : Total capacity [kW]SHC : Sensible capacity [kW]PI : Power Input [kW]
(Comp.+ indoor fan motor+outdoor fan motor)
Notes1. All capacites are net, evaporator fan motor heat is deducted.2. Indicates nominal capacity.3. Direct interpolation is permissible. Do not extrapolate4. Capacities are based on the following conditions:
- Interconnecting Piping Length 7.5m- Level Difference of Zero.
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
33/65
33
Capacity Tables SR-6RMG2-02A
GENERAL WALL MOUNTED
SymbolDB : Dry bulb temperature [C]WB : Wet bulb temperature [C]TC : Total capacity [kW]SHC : Sensible capacity [kW]PI : Power Input [kW]
(Comp.+ indoor fan motor+outdoor fan motor)
Notes1. All capacites are net, evaporator fan motor heat is deducted.2. Indicates nominal capacity.3. Direct interpolation is permissible. Do not extrapolate4. Capacities are based on the following conditions:
- Interconnecting Piping Length 7.5m- Level Difference of Zero.
Model : GS-H242C4B2
CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14 20 5.70 4.24 1.87 5.58 4.20 2.21 5.32 4.09 2.58 5.16 4.00 2.72 4.97 3.92 2.89 4.86 3.86 2.99
16 22 6.66 4.82 1.90 6.52 4.77 2.25 6.21 4.63 2.62 6.02 4.53 2.76 5.80 4.42 2.94 5.66 4.35 3.0318 25 7.43 5.24 1.93 7.27 5.18 2.28 6.93 5.02 2.66 6.72 4.91 2.80 6.47 4.78 2.98 6.32 4.71 3.0819 27 7.77 5.41 1.96 7.61 5.35 2.32 7.25 5.18 2.71 7.03 5.06 2.85 6.77 4.93 3.03 6.62 4.85 3.1322 30 8.53 5.74 1.98 8.35 5.67 2.35 7.96 5.48 2.74 7.72 5.35 2.89 7.43 5.20 3.07 7.26 5.11 3.1724 32 8.85 5.84 2.01 8.67 5.76 2.38 8.26 5.56 2.78 8.01 5.42 2.93 7.71 5.27 3.11 7.53 5.17 3.22
Indoor AirTemperature
Outdoor Air Temperature : CDB20 25 32 35 40 43
Model : GS-C122E5B2
Model : GS-H122E5B2
Indoor AirTemperature
Outdoor Air Temperature : CDB20.0 25.0 32.0 35.0 40.0 43.0 46.1 57.1
CWB CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI14 2016 2218 2519 2722 3024 32
2.86 0.79 2.79 0.93 2.66 1.09 2.58 1.14 2.49 1.22 2.41 1.26 2.29 1.34 2.12 1.373.33 0.80 3.26 0.95 3.11 1.10 3.01 1.16 2.90 1.24 2.81 1.28 2.66 1.36 2.46 1.383.72 0.81 3.64 0.96 3.47 1.12 3.36 1.18 3.24 1.26 3.13 1.30 2.98 1.37 2.77 1.403.89 0.82 3.81 0.98 3.63 1.14 3.52 1.20 3.39 1.28 3.28 1.32 3.11 1.40 2.88 1.434.27 0.83 4.18 0.99 3.98 1.15 3.86 1.22 3.72 1.29 3.60 1.34 3.41 1.42 3.17 1.454.43 0.85 4.34 1.00 4.13 1.17 4.01 1.23 3.86 1.31 3.73 1.35 3.54 1.44 3.28 1.47
Indoor AirTemperature
Outdoor Air Temperature : CDB20.0 25.0 32.0 35.0 40.0 43.0 46.1 57.1
CWB CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI14 2016 2218 2519 2722 3024 32
2.73 0.79 2.68 0.93 2.55 1.09 2.47 1.14 2.38 1.22 2.30 1.26 2.20 1.34 2.04 1.373.19 0.80 3.12 0.95 2.98 1.10 2.89 1.16 2.78 1.24 2.69 1.28 2.56 1.36 2.37 1.383.56 0.81 3.49 0.96 3.32 1.12 3.22 1.18 3.10 1.26 3.00 1.30 2.87 1.37 2.66 1.403.73 0.82 3.65 0.98 3.48 1.14 3.37 1.20 3.25 1.28 3.14 1.32 2.99 1.40 2.77 1.434.09 0.83 4.00 0.99 3.81 1.15 3.70 1.22 3.56 1.29 3.45 1.34 3.28 1.42 3.05 1.454.24 0.85 4.15 1.00 3.96 1.17 3.84 1.23 3.70 1.31 3.58 1.35 3.40 1.44 3.16 1.47
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
34/65
34
SR-6RMG2-02A
GENERAL WALL MOUNTED
Model : GS-C1825SA3, GS-C1825NB2
Model : GS-H1825SA3
Symbol
DB : Dry bulb temperature [C]WB : Wet bulb temperature [C]TC : Total capacity [kW]SHC : Sensible capacity [kW]PI : Power Input [kW]
(Comp.+ indoor fan motor+outdoor fan motor)
Notes
1. All capacites are net, evaporator fan motor heat is deducted.2. Indicates nominal capacity.3. Direct interpolation is permissible. Do not extrapolate4. Capacities are based on the following conditions:
- Interconnecting Piping Length 7.5m- Level Difference of Zero.
Model : GS-H1825NB2
Indoor AirTemperature
Outdoor Air Temperature : CDB20.0 25.0 32.0 35.0 40.0 43.0 46.1 57.1
CWB CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI14 2016 2218 2519 2722 3024 32
4.16 1.31 4.07 1.55 3.88 1.81 3.76 1.91 3.62 2.03 3.51 2.10 3.30 2.20 3.06 2.244.85 1.33 4.75 1.58 4.53 1.84 4.39 1.94 4.23 2.06 4.09 2.13 3.83 2.23 3.56 2.275.42 1.35 5.30 1.60 5.05 1.87 4.90 1.97 4.72 2.09 4.56 2.16 4.31 2.26 4.00 2.315.67 1.37 5.55 1.63 5.29 1.90 5.13 2.00 4.94 2.13 4.78 2.20 4.48 2.30 4.16 2.356.22 1.39 6.09 1.65 5.80 1.92 5.63 2.03 5.42 2.15 5.24 2.23 4.93 2.33 4.57 2.386.46 1.41 6.32 1.67 6.02 1.95 5.84 2.06 5.63 2.19 5.44 2.26 5.10 2.36 4.73 2.41
Indoor AirTemperature
Outdoor Air Temperature : CDB20.0 25.0 32.0 35.0 40.0 43.0 46.1 57.1
CWB CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI14 2016 2218 2519 2722 3024 32
4.05 1.38 3.96 1.63 3.78 1.90 3.66 2.00 3.53 2.13 3.41 2.20 3.15 2.34 2.92 2.394.72 1.40 4.62 1.66 4.40 1.93 4.27 2.03 4.11 2.16 3.98 2.23 3.66 2.37 3.39 2.425.27 1.42 5.16 1.68 4.91 1.96 4.77 2.07 4.59 2.20 4.44 2.27 4.11 2.41 3.81 2.465.51 1.44 5.40 1.71 5.14 1.99 4.99 2.10 4.80 2.23 4.65 2.31 4.28 2.45 3.97 2.506.05 1.46 5.92 1.73 5.64 2.02 5.48 2.13 5.27 2.26 5.10 2.34 4.70 2.48 4.36 2.546.28 1.48 6.15 1.76 5.86 2.05 5.68 2.16 5.47 2.30 5.29 2.37 4.87 2.52 4.52 2.57
Indoor AirTemperature
Outdoor Air Temperature : CDB20.0 25.0 32.0 35.0 40.0 43.0 46.1 57.1
CWB CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI14 2016 2218 2519 2722 3024 32
4.16 1.34 4.07 1.59 3.88 1.86 3.76 1.96 3.62 2.08 3.51 2.15 3.26 2.34 3.02 2.394.85 1.36 4.75 1.62 4.53 1.88 4.39 1.99 4.23 2.11 4.09 2.18 3.78 2.37 3.51 2.425.42 1.38 5.30 1.64 5.05 1.91 4.90 2.02 4.72 2.14 4.56 2.21 4.25 2.41 3.94 2.465.67 1.41 5.55 1.67 5.29 1.95 5.13 2.05 4.94 2.18 4.78 2.25 4.43 2.45 4.10 2.506.22 1.43 6.09 1.69 5.80 1.97 5.63 2.08 5.42 2.21 5.24 2.28 4.86 2.48 4.51 2.546.46 1.45 6.32 1.71 6.02 2.00 5.84 2.11 5.63 2.24 5.44 2.31 5.04 2.52 4.67 2.57
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
35/65
35
SR-6RMG2-02A
GENERAL WALL MOUNTED
Model : GS-C2425SA3, GS-C2425NB2
Model : GS-H2425SA3
Model : GS-H2425NB2
Symbol
DB : Dry bulb temperature [C]WB : Wet bulb temperature [C]TC : Total capacity [kW]SHC : Sensible capacity [kW]PI : Power Input [kW]
(Comp.+ indoor fan motor+outdoor fan motor)
Notes
1. All capacites are net, evaporator fan motor heat is deducted.2. Indicates nominal capacity.3. Direct interpolation is permissible. Do not extrapolate4. Capacities are based on the following conditions:
- Interconnecting Piping Length 7.5m- Level Difference of Zero.
Indoor AirTemperature
Outdoor Air Temperature : CDB20.0 25.0 32.0 35.0 40.0 43.0 46.1 57.1
CWB CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI14 2016 2218 2519 2722 3024 32
5.23 1.64 5.12 1.94 4.88 2.26 4.73 2.38 4.56 2.54 4.41 2.62 4.12 2.86 3.83 2.936.10 1.66 5.97 1.97 5.69 2.30 5.52 2.42 5.32 2.58 5.14 2.66 4.79 2.91 4.44 2.976.81 1.69 6.67 2.00 6.35 2.33 6.16 2.46 5.93 2.61 5.74 2.70 5.38 2.95 4.99 3.017.13 1.72 6.98 2.04 6.65 2.37 6.45 2.50 6.21 2.66 6.01 2.75 5.60 3.00 5.19 3.067.82 1.74 7.66 2.06 7.30 2.40 7.08 2.53 6.82 2.69 6.59 2.78 6.15 3.04 5.70 3.118.12 1.76 7.95 2.09 7.57 2.44 7.35 2.57 7.07 2.73 6.84 2.82 6.37 3.08 5.91 3.15
Indoor AirTemperature
Outdoor Air Temperature : CDB20.0 25.0 32.0 35.0 40.0 43.0 46.1 57.1
CWB CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI14 2016 2218 2519 2722 3024 32
5.11 1.77 5.00 2.10 4.77 2.44 4.62 2.58 4.45 2.74 4.31 2.83 3.97 3.10 3.69 3.175.96 1.80 5.84 2.13 5.56 2.48 5.39 2.62 5.19 2.78 5.02 2.87 4.61 3.15 4.28 3.216.65 1.82 6.51 2.16 6.20 2.52 6.02 2.66 5.80 2.82 5.61 2.92 5.18 3.19 4.80 3.266.96 1.85 6.81 2.20 6.49 2.56 6.30 2.70 6.07 2.87 5.87 2.97 5.39 3.25 5.00 3.327.64 1.88 7.48 2.23 7.13 2.60 6.91 2.73 6.66 2.91 6.44 3.00 5.92 3.29 5.50 3.367.93 1.91 7.76 2.26 7.40 2.63 7.17 2.77 6.91 2.95 6.68 3.05 6.14 3.34 5.69 3.41
Indoor AirTemperature
Outdoor Air Temperature : CDB20.0 25.0 32.0 35.0 40.0 43.0 46.1 57.1
CWB CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI14 2016 2218 2519 2722 3024 32
5.35 1.73 5.24 2.05 4.99 2.39 4.84 2.52 4.66 2.68 4.51 2.77 4.08 3.08 3.79 3.156.25 1.76 6.11 2.08 5.83 2.43 5.65 2.56 5.44 2.72 5.26 2.81 4.74 3.13 4.39 3.196.97 1.78 6.82 2.11 6.50 2.46 6.31 2.60 6.07 2.76 5.87 2.85 5.32 3.17 4.94 3.247.29 1.81 7.14 2.15 6.80 2.51 6.60 2.64 6.35 2.81 6.15 2.90 5.54 3.23 5.14 3.308.00 1.84 7.83 2.18 7.47 2.54 7.24 2.67 6.97 2.84 6.75 2.94 6.09 3.27 5.65 3.348.31 1.86 8.13 2.21 7.75 2.58 7.52 2.71 7.24 2.89 7.00 2.98 6.30 3.32 5.85 3.39
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
36/65
36
SR-6RMG2-02A
GENERAL WALL MOUNTED
Model : GS-H122E5B2
CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16 2.38 0.84 2.80 0.92 3.24 1.00 3.40 1.03 3.56 1.06 3.77 1.08 4.08 1.13 4.50 1.22
18 2.30 0.87 2.71 0.95 3.14 1.03 3.29 1.06 3.45 1.10 3.65 1.11 3.95 1.17 4.36 1.26
20 2.23 0.90 2.63 0.98 3.04 1.07 3.20 1.10 3.35 1.13 3.52 1.15 3.83 1.21 4.23 1.30
22 2.15 0.92 2.54 1.01 2.93 1.10 3.08 1.13 3.23 1.17 3.41 1.19 3.69 1.25 4.08 1.34
24 2.08 0.95 2.45 1.04 2.83 1.13 2.98 1.17 3.12 1.20 3.29 1.22 3.57 1.29 3.94 1.38
Indoor AirTemperature
Outdoor Air Temperature : CWB-10 -5 0 2 4 6 10 15
Model : GS-H182C4B2
Model : GS-H242C4B2
CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16 3.86 1.34 4.55 1.47 5.26 1.60 5.52 1.65 5.79 1.70 6.12 1.72 6.62 1.82 7.31 1.94
18 3.74 1.39 4.40 1.52 5.09 1.65 5.35 1.70 5.60 1.75 5.92 1.78 6.41 1.88 7.08 2.01
20 3.63 1.43 4.27 1.57 4.94 1.71 5.19 1.76 5.44 1.81 5.71 1.84 6.22 1.94 6.86 2.08
22 3.49 1.48 4.12 1.62 4.76 1.76 5.00 1.81 5.24 1.87 5.54 1.90 5.99 2.00 6.62 2.14
24 3.37 1.52 3.98 1.67 4.60 1.81 4.83 1.87 5.06 1.93 5.35 1.96 5.79 2.06 6.39 2.21
Indoor AirTemperature
Outdoor Air Temperature : CWB-10 -5 0 2 4 6 10 15
CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16 5.14 2.02 6.06 2.21 7.01 2.40 7.36 2.48 7.72 2.55 8.15 2.60 8.83 2.73 9.74 2.93
18 4.98 2.09 5.87 2.28 6.79 2.49 7.13 2.56 7.47 2.64 7.90 2.68 8.55 2.83 9.43 3.03
20 4.83 2.16 5.69 2.36 6.59 2.57 6.92 2.65 7.25 2.73 7.62 2.77 8.29 2.92 9.15 3.13
22 4.66 2.23 5.49 2.43 6.35 2.65 6.67 2.73 6.99 2.81 7.38 2.86 7.99 3.01 8.82 3.23
24 4.50 2.29 5.30 2.51 6.13 2.73 6.44 2.81 6.75 2.90 7.13 2.95 7.72 3.10 8.52 3.32
Indoor AirTemperature
Outdoor Air Temperature : CWB-10 -5 0 2 4 6 10 15
SymbolDB : Dry bulb temperature [C]WB : Wet bulb temperature [C]TC : Total capacity [kW]SHC : Sensible capacity [kW]PI : Power Input [kW]
(Comp.+ indoor fan motor+outdoor fan motor)
Notes1. All capacites are net, evaporator fan motor heat is deducted.2. Indicates nominal capacity.3. Direct interpolation is permissible. Do not extrapolate4. Capacities are based on the following conditions:
- Interconnecting Piping Length 7.5m- Level Difference of Zero.
Heating capacity
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
37/65
37
SR-6RMG2-02A
GENERAL WALL MOUNTED
Model : GS-H1825SA3
CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI 16 3.44 1.28 4.05 1.39 4.69 1.52 4.93 1.57 5.16 1.61 5.45 1.64 5.90 1.73 6.52 1.85
18 3.33 1.32 3.93 1.44 4.54 1.57 4.77 1.62 5.00 1.67 5.28 1.70 5.72 1.79 6.31 1.91
20 3.23 1.36 3.81 1.49 4.41 1.62 4.63 1.67 4.85 1.72 5.09 1.75 5.55 1.84 6.12 1.97
22 3.12 1.41 3.67 1.54 4.25 1.67 4.46 1.72 4.67 1.78 4.94 1.81 5.35 1.90 5.90 2.04
24 3.01 1.45 3.55 1.58 4.10 1.73 4.31 1.78 4.51 1.83 4.77 1.86 5.16 1.96 5.70 2.10
Indoor AirTemperature
Outdoor Air Temperature : CWB-10 -5 0 2 4 6 10 15
Model : GS-H1825NB2
CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16 3.54 1.28 4.18 1.39 4.83 1.52 5.07 1.57 5.32 1.61 5.62 1.64 6.08 1.73 6.71 1.85
18 3.43 1.32 4.04 1.44 4.68 1.57 4.91 1.62 5.15 1.67 5.44 1.70 5.89 1.79 6.50 1.91
20 3.33 1.36 3.92 1.49 4.54 1.62 4.77 1.67 5.00 1.72 5.25 1.75 5.71 1.84 6.31 1.97
22 3.21 1.41 3.78 1.54 4.38 1.67 4.59 1.72 4.81 1.78 5.09 1.81 5.51 1.90 6.08 2.04
24 3.10 1.45 3.65 1.58 4.22 1.73 4.44 1.78 4.65 1.83 4.91 1.86 5.32 1.96 5.87 2.10
Indoor AirTemperature
Outdoor Air Temperature : CWB-10 -5 0 2 4 6 10 15
Symbol
DB : Dry bulb temperature [C]WB : Wet bulb temperature [C]TC : Total capacity [kW]SHC : Sensible capacity [kW]PI : Power Input [kW]
(Comp.+ indoor fan motor+outdoor fan motor)
Notes
1. All capacites are net, evaporator fan motor heat is deducted.2. Indicates nominal capacity.3. Direct interpolation is permissible. Do not extrapolate4. Capacities are based on the following conditions:
- Interconnecting Piping Length 7.5m- Level Difference of Zero.
Model : GS-H2425SA3
CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16 4.49 1.90 5.29 2.07 6.12 2.26 6.43 2.33 6.73 2.40 7.12 2.44 7.70 2.57 8.50 2.75
18 4.35 1.96 5.12 2.14 5.93 2.33 6.22 2.40 6.52 2.48 6.89 2.52 7.46 2.65 8.23 2.84
20 4.22 2.02 4.97 2.21 5.75 2.41 6.04 2.48 6.33 2.56 6.65 2.60 7.24 2.74 7.99 2.93
22 4.07 2.09 4.79 2.28 5.54 2.49 5.82 2.56 6.10 2.64 6.44 2.68 6.98 2.83 7.70 3.03
24 3.93 2.15 4.63 2.35 5.35 2.56 5.62 2.64 5.89 2.72 6.22 2.77 6.74 2.91 7.44 3.12
Indoor AirTemperature
Outdoor Air Temperature : CWB-10 -5 0 2 4 6 10 15
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
38/65
38
Capacity Tables SR-6RMG2-02A
GENERAL WALL MOUNTED
Model : GS-H2425NB2
CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16 4.63 1.90 5.45 2.07 6.30 2.26 6.62 2.33 6.94 2.40 7.33 2.44 7.93 2.57 8.76 2.75
18 4.48 1.96 5.28 2.14 6.10 2.33 6.41 2.40 6.72 2.48 7.10 2.52 7.68 2.65 8.48 2.84
20 4.35 2.02 5.12 2.21 5.92 2.41 6.22 2.48 6.52 2.56 6.85 2.60 7.45 2.74 8.23 2.93
22 4.19 2.09 4.93 2.28 5.71 2.49 6.00 2.56 6.28 2.64 6.64 2.68 7.19 2.83 7.93 3.03
24 4.04 2.15 4.76 2.35 5.51 2.56 5.79 2.64 6.07 2.72 6.41 2.77 6.94 2.91 7.66 3.12
Indoor AirTemperature
Outdoor Air Temperature : CWB-10 -5 0 2 4 6 10 15
SymbolDB : Dry bulb temperature [C]WB : Wet bulb temperature [C]TC : Total capacity [kW]SHC : Sensible capacity [kW]PI : Power Input [kW]
(Comp.+ indoor fan motor+outdoor fan motor)
Notes1. All capacites are net, evaporator fan motor heat is deducted.2. Indicates nominal capacity.3. Direct interpolation is permissible. Do not extrapolate4. Capacities are based on the following conditions:
- Interconnecting Piping Length 7.5m- Level Difference of Zero.
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
39/65
39
Capacity Coefficient Factor SR-6RMG2-02A
GENERAL WALL MOUNTED
9. Capacity Coefficient Factor
Model: 9 kBtu/h ~ 26 kBtu/h Cooling Only
Model: 5 kBtu/h ~ 14 kBtu/h Heat Pump
(A)
(A)
Indoor
Indoor
Outdoor
Outdoor
(A)
(A)
Indoor
Indoor
Outdoor
Outdoor
Classification Height
(A)
Capacity Coefficient factorTotal Pipe Length(m)
5 7.5 10 12.5 15
- - - (0.94) (0.93)
- 0.97 0.96 (0.95) (0.94)
0.99 0.98 0.97 (0.96) (0.95)
1.0 0.99 0.98 (0.97) (0.96)
1.0 0.99 0.98 (0.97) (0.96)
0.99 0.98 0.97 (0.96) (0.95)
- 0.97 0.96 (0.95) (0.94)
- - - (0.94) (0.93)
The values in parentheses are valid only for 18~24kBtu models.
10
7
5
0
0
5
7
10
Classification Height(A)
Capacity Coefficient factorTotal Pipe Length(m)
5 7.5 10 12.5 15
- - - - -
- 0.97 0.97 - -
0.99 0.98 0.97 - -
1.0 0.99 0.98 - -
1.0 0.99 0.98 - -
0.99 0.98 0.97 - -
- 0.97 0.97 - -
- - - - -
10
7
5
0
0
5
7
10
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
40/65
40
Operation Range SR-6RMG2-02A
GENERAL WALL MOUNTED
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
CapacitykW (kBtu/h)
Pipe Size[mm(in)] StandardLength m(ft)
Max.Elevation m(ft)
Max.Length m(ft)
Additional Refrigerantg/m(oz/ft)GAS LIQUID
3.5(12) 12.7(1/2) 6.35(1/4) 5(16) 10(33) 15(49) 20(0.22)
5.3(18) 15.88(5/8) 6.35(1/4) 5(16) 10(33) 15(49) 20(0.22)
7.0(24) 15.88(5/8) 9.52(3/8) 5(16) 10(33) 15(49) 30(0.32)
Capacity is based on standard length and maximum allowable length is on the basis of reliability.Additional refrigerant must be charged after 5m.
CAUTION
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
41/65
41
Air Velocity and Temperature Distribution(Reference Data) SR-6RMG2-02A
GENERAL WALL MOUNTED
10. Air Velocity and Temperature Distribution(Reference Data)
Model : GS-C182C4B2, GS-H182C4B2, GS-C1825*,GS-C2425*, GS-H1825*,GS-H2425*
General Wall Mounted 18/24 kBtu/h
CoolingDischarge angle:45
HeatingDischarge angle:50
Air velocity [m/s]2.7m
2m
1m
0m1m2m3m4m5m6m7m8m
Temperature [ C]
2.7m2m
1m
0m1m2m3m4m5m6m7m8m
0.751.25
1.0
1.5
0.5
25 24
23
Air velocity [m/s]2.7m
2m
1m
0m1m2m3m4m5m6m7m8m
Temperature [C]2.7m
2m
1m
0m1m2m3m4m5m6m7m8m
0.751.25
1.0
1.5
0.5
28 29 30
31
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
42/65
42
Controller SR-6RMG2-02A
GENERAL WALL MOUNTED
11. ControllerType 1 (Wireless LCD)
Displayscreen
Controlpanel
Display
screen
Controlpanel
JETCOOL
JETCOOL
C/F[5SEC]
C/F[5SEC]
Control panel Display screen Description
a F Plasma button*: Purifies the air by removingparticles that enter the indoor unit./ 4 Air circulation button*: Used to circulate theroom air without cooling or heating.l = Sleep mode auto button*: Sets the sleep modeauto operation. e y Temperature adjustment buttons: Adjusts theroom temperature when cooling and heating.d - On/Off button: Turns the power on/off.g 7 v Indoor fan speed button: Adjusts the fanspeed.f A CD B E
Operation mode selection button*: Selects theoperation mode.Cooling operation (A ) / Auto operation or autochangeover ( C ) / Dehumidifying operation (D) / Heating operation ( B ) / Air circulation (E )
JETCOOL N
Jet cooling/heating button*: Warms up or coolsdown the indoor temperature within a short peri-od of time.
i j H I Air flow direction button: Adjusts the air flowdirection vertically or horizontally.k S Temperature display button: Displays the roomtemperature.
m n z Timer button: Sets the current time and the start/ end time.cb
u J G P
Functions button*: Adjusts the time and setsthe special functions.J : Auto clean / G: Operates energy saving cool-ing / P : Adjusts the brightness of the indoor unit
displayp - Set/clear button: Sets or cancels functions.r - Reset button: Initialize the air conditioner set-tings.
* Some functions may not be supported, depending on the model.
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
43/65
43
SR-6RMG2-02A
GENERAL WALL MOUNTED
ON OFF
CANCEL
AUTO CLEANSET
1
3
5
4
9
18
10
12
14
16
72
813
15
11
6
Cooling Operation
Auto Operation or Auto Changeover
Healthy Dehumidification Operation
Flip-up door
(opened)
Heating Operation
Signal transmitter
Cooling Model( ), Heat Pump Model( )
1719
Operation Mode
1. START/STOP BUTTONUsed to turn off/on the unit.
2. OPERATION MODE SELECTION BUTTONUsed to select the operation mode.
3. ROOM TEMPERATURE SETTING BUTTONSUsed to select the room temperature.
4. INDOOR FAN SPEED SELECTOR BUTTONUsed to select fan speed in four stepslow, medium, high and CHAOS.
5. JET COOL BUTTONUsed to start or stop the speed cooling.(It operates fan in super high speed in cooling mode)
6. CHAOS SWING BUTTONUsed to stop or start louver movement and set thedesired up/down airflow direction.
7. ON/OFF TIMER BUTTONSUsed to set the time of starting and stoppingoperation.
8. TIME SETTING BUTTONSUsed to adjust the time.
9. TIMER SET/CANCEL BUTTONUsed to set and to cancel the timer operation.
10. SLEEP MODE AUTO BUTTONUsed to set sleep mode auto operation.
11. AIR CIRCULATION BUTTONUsed to circulate the room air without cooling orheating.ENERGY-SAVING COOLING MODE BUTTON(OPTIONAL) For inverter type models
12. ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.13. PLASMA BUTTON(OPTIONAL)
Used to start or stop the plasma-purificationfunction.
14. HORIZONTAL AIRFLOW DIRECTION CONTROLBUTTON (OPTIONAL)Used to set the desired horizontal airflow direction.
15. RESET BUTTONUsed prior to resetting time.
16. 2nd F BUTTONUsed prior to using modes printed in blue at thebottom of buttons.
17. AUTO CLEAN BUTTON(OPTIONAL)Used to set auto clean mode.In some models this button has a 2nd function of LEDluminosity control.
18. HEATER BUTTON(OPTIONAL)(Not available in all models)
19. LCD LUMINOSITY BUTTON(OPTIONAL)Used to adjust LCD luminosity.
To use the functions printed in blue at the bottom of the buttons press 2 nd F button first and then the required functionbutton. Pressing the 2 nd F button activates the blue printed function of the respective button. To cancel the functionpress the 2nd F button again else it will automatically cancel if remains idle after 10 seconds.
NOTE
Type 2 (Wireless LCD)
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
44/65
44
SR-6RMG2-02A
GENERAL WALL MOUNTED
Type 3 (Wireless Simple)
3
1
4
2
5
6
8
7
2
4 1
3
1. OPERATION DISPLAYDisplays the operation conditions.
2. CHAOS SWING BUTTONUsed to stop or start louver movement and setthe desired up/down airflow direction
3. OPERATION MODE SELECTION BUTTONUsed to select the operation mode.
4. OFF TIMER BUTTONUsed to set the time of stopping opertion.
5. START/STOP BUTTONOperation starts when this button is pressed, andstops when the button is pressed again.
6. ROOM TEMPERATURE SETTING BUTTONS
7. INDOOR FAN SPEED SELECTION BUTTON
Used to set the time of starting and stoppingoperation.8. JET COOL
Used to start or stop the speed cooling (Speedcooling operates super high fan speed ingcooling mode.)
(1) Operation Mode
(2) Operation Procedure
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
45/65
45
Installation SR-6RMG2-02A
GENERAL WALL MOUNTED
12. Installation12.1 Installation Map
Vinyl tape (Wide) Apply after carrying out a drainage test. To carry out the drainage
test, remove the air filters and pour water into the heatexchanger.
Saddle
Gas side pipingLiquid side piping
Additional drain pipe
Vinyl tape (Narrow)Drain Hose
Base Plate
Air Outlet
Air Inlet
Connecting cable
Tubing Cover
SleeveBushing-SleevePutty(Gum Type Sealant)Bend the pipe as closelyon the wall as possible,but be careful that itdoesn't break.
Installation plate
* The feature can be changed according to the type of model.
( ) You should purchase the installation parts.
NOTE
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
46/65
46
Installation SR-6RMG2-02A
GENERAL WALL MOUNTED
12.2 Select the best Location
Indoor unit1. There should not be any heat or steam near the unit.
2. Select a place where there are no obstacles around theunit.
3. Make sure that condensation drainage can be convenientlyrouted away.
5. Ensure that the gap between a wall and the left (or right) ofthe unit is more than 100mm. The unit should be installedas high as possible on the wall, allowing a minimum of200mm from ceiling.
6. Use a metal detector to locate studs to prevent unneces-sary damage to the wall.
* The feature can be changed according to the type ofmodel.
Outdoor unit1. If an awning is built over the unit to prevent direct sunlight
or rain exposure, make sure that heat radiation from thecondenser is not restricted.
2. Ensure that the space around the back side and othersides is more than 300mm. The space in front of the unitshould be more than 700mm.
3. Do not place animals and plants in the path of the warmair.
4. Take the weight of the air conditioner into account andselect a place where noise and vibration are minimum.
5. Select a place where the warm air and noise from the airconditioner do not disturb neighbors.
More than 200More than
100
More than 2300
More than100
(Unit : mm)
Install the indoor unit on the wall where the height from the floor is more than 2300mm.
CAUTION
S u n r o o f
Fence orobstacles
More than300
More than300
More than700
More than600
(Unit : mm)
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
47/65
47
Installation SR-6RMG2-02A
GENERAL WALL MOUNTED
2. Measure the wall and mark the centerline. It is also important touse caution concerning the location of the installation plate.Routing of the wiring to power outlets is through the walls typical-ly. Drilling the hole through the wall for piping connections must bedone safely.
The wall you select should be strong and solid enough to preventvibration
1. Mount the installation plate on the wall with type "A" screws. Ifmounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning the center-line using Horizontal meter .
6565
69 56
Rightrearpiping
Leftrearpiping
Installation PlateMeasuring Tape
Measuring TapeHanger
Place a level on raised tabUnit Outline
207105
(Unit : mm)
460 570
Installation Plate
ChassisHook
Type "A" Screws
Drill the piping hole with a 65mm hole core drill. Drill thepiping hole at either the right or the left with the holeslightly slanted to the outdoor side.
5 - 7 m m
( 3 / 1 6 " ~ 5 / 1 6 " )
IndoorWALL
Outdoor
BushingSleeve
12.3 Fixing Installation Plate
12.4 Drill a Hole in the Wall
Use the sleeve to prevent damage for tube assembly.
CAUTION
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
48/65
48
SR-6RMG2-02A
GENERAL WALL MOUNTED
Installation
12.5 Flaring Work
Main cause for gas leakage is due to defect of flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable.1. Use the piping kit accessory or the pipes purchased locally.2. Measure the distance between the indoor and the outdoor unit.3. Cut the pipes a little longer than measured distance.4. Cut the cable 1.5m longer than the pipe length.
Burrs removal1. Completely remove all burrs from the cut cross section of pipe/tube.
2. While removing the burrs, hold the end of the pipe in downward direc-tion in order to avoid dropping burrs into the tubing.
Putting nut on- Remove flare nuts attached to indoor and outdoor units, then put them
on the pipe/tube which have completed its burr removal.(not possible to put them on after finishing flare work)
Flaring work1. Firmly hold copper pipe in a bar with the dimension shown in
table below.2. Carry out flaring work with the flaring tool.
Copperpipe 90 Slanted Uneven Rough
PipeReamer
Point down
Flare nut
Copper tube
Bar
Copper pipe
Clamp handleRed arrow mark
Cone
Yoke
Handle
Bar " A "
Outside diameter A Thicknessmm inch mm mm
6.35 1/4" 1.1~1.3 0.7
9.52 3/8" 1.5~1.7 0.812.7 1/2" 1.6~1.8 0.8
15.88 5/8" 1.6~1.8 1.019.05 3/4" 1.9~2.1 1.0
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
49/65
49
SR-6RMG2-02A
GENERAL WALL MOUNTED
Installation
Check1. Compare the flared work with the figures given below.
2. If a flared section is defective, cut it off and do flaring workagain.
Inclined
Inside is shiny without scratchesSmooth all round
Even lengthall round
Surfacedamaged
Cracked Uneventhickness
= Improper flaring =
12.6 Connecting the pipes
1. Pull the screw caps at the bottom of the indoor unit2. Remove the chassis cover from the unit by loosing 3 screws
3. Pull back the tubing holder.4. Remove the pipe port cover and position the piping.
* The feature can be changed according to the type of model.
Chassis cover
Right
Back side view
Tubing holder
Backwards
Left
Pipe Port
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
50/65
50
SR-6RMG2-02A
GENERAL WALL MOUNTED
Installation
Good case Press the tubing cover and slowly unfold the tubing to downward. And then bend to the left side slowly.
Bad case Following bending case from right to left directly may cause damage to the tubing.
* The feature can be changed according to the type of model.
Installation Information. For right piping. Follow the instruction above.
CAUTION
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
51/65
51
SR-6RMG2-02A
GENERAL WALL MOUNTED
Installation
1. Hook the indoor unit onto the upper portion of the installation plate.( engage the three hooks at the top of the indoor unit withthe upper edge of the installation plate) Ensure that the hooks are properly seated on the installation plate by moving it leftand right
2. Unlock the tubing holder from the chassis and mount between the chassis and installation plate in order to separate the bot-tom side of the indoor unit from the wall.
* The feature can be changed according to the type of model.
Installation plate
1
2
Tubing Holder
12.7 Installation of Indoor Unit
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
52/65
52
Installation SR-6RMG2-02A
GENERAL WALL MOUNTED
3. Insert the connecting cable through the bottom side ofindoor unit and connect the cable
Open the Front Grille Support the Front Grille with supporter Open the Control Cover Connect the connecting cable
Control Cover
Case 1 Case 2 Case 3
4. Tape the tubing pipe, drain hose and the connection cable. Be sure that the drain hose is located at the lowest side of thebundle. Locating at the upper side can cause overflow from the drain pan through the inside of the unit.
* The feature can be changed according to the type of model.
Connecting pipe
Connectingcable
Tape
Drain hose
Indoor Outdoor
Indoor UnitDrain hose
Indoor UnitDrain hose
Insulation(More than 100~300mm
length and 7mm thickness)Extensiondrain hose
Drain hose
Tape
Connecting pipe
Connectingcable
Drain hose
If the extension drain hose is routed inside the room,insulate the hose with an insulation material* so that drip-ping from sweating (condensation) could not damage fur-niture or floors.
Foamed polyethylene or equivalent is recommended.
CAUTION
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
53/65
53
Installation SR-6RMG2-02A
GENERAL WALL MOUNTED
Connecting the installation pipe and drainhose to the indoor unit.1. Align the center of the pipes and sufficiently tighten the
flare nut by hand
2. Tighten the flare nut with a wrench
3. When needed to extend the drain hose of indoor unit,assembly the drain pipe as shown on the drawing
Indoor unit tubing Flare nut Pipes
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
Vinyl tape(narrow)Adhesive
Drain pipe
Indoor unit drain hose
Wrap the insulation material around the con-necting portion.1. Overlap the connection pipe insulation material and the
indoor unit pipe insulation material. Bind them together withvinyl tape so that there may be no gap.
2. Wrap the area which accommodates the rear piping hous-ing section with vinyl tape.
3. Bundle the piping and drain hose together by wrappingthem with vinyl tape sufficient enough to cover where theyfit into the rear piping housing section.
Insulation material
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Vinyl tape(narrow)
Connection pipe
Connecting cableVinyl tape (wide) Wrap with vinyl tape
Indoor unit pipe
Pipe
Outside Diameter Torquemm inch kgfcm Nm
6.35 1/4 180~250 17.6~24.59.52 3/8 340~420 33.3~41.212.7 1/2 550~660 53.9~64.7
15.88 5/8 630~820 61.7~80.419.05 3/4 990~1210 97~118.6
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
54/65
54
SR-6RMG2-02A
GENERAL WALL MOUNTED
Installation
Finishing the indoor unit installation
1. Mount the tubing holder in the original positon.2. Ensure that the hooks are properly seated on the installa-
tion plate by moving it left and right.3. Press the lower left and right sides of the unit against the
installation plate until the hooks engage into their slots(clicking sound).4. Finish the assembly by screwing the unit to the installation
plate by using two pieces of type "C" screws. And assemblea chassis cover.
5. Reconvey the chassis cover in Original place.
Type 'C' screw
Outdoor Unit Installation
1. Remove the tubing cover from the unit by loosening thescrew.
Cover control
Tubing Cover
2. Align the center of the pipings and sufficiently tighten theflare nut by hand.
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
55/65
55
SR-6RMG2-02A
GENERAL WALL MOUNTED
Installation
3. Finally, tighten the flare nut with torque wrench until thewrench clicks.
When tightening the flare nut with torque wrench, ensurethe direction for tightening follows the arrow on thewrench.
Outdoor unit
Gas side
Liquid side
Cap
3-way or2-way valve
3-way valveOutside Diameter Torquemm inch kgfcm Nm
6.35 1/4 180~250 17.6~24.59.52 3/8 340~420 33.3~41.212.7 1/2 550~660 53.9~64.7
15.88 5/8 630~820 61.7~80.419.05 3/4 990~1210 97~118.6
-
8/10/2019 PDB Saudi Split (Titan Gold Plus+Fresh+Smart)
56/65
56
SR-6RMG2-02A
GENERAL WALL MOUNTED
In