PCT 40 experiment
-
Upload
paoloasequia -
Category
Documents
-
view
1 -
download
0
description
Transcript of PCT 40 experiment
Proportional pressure input with on/off controller using Normally Closed Solenoid
Valve
Asequia, Christian PaoloBayeta, Sheena ClaireCimafranca, Emmanuel
Limo, MariettaPalen, Ian Arnold
Patica, Hazel Dawn
INTRODUCTION Objective:
To control the level in a process vessel using an on/off controller connected to a pressure sensor, with a Normally Closed solenoid valve (SOL2) controlling outflow from the vessel.
Overview: The proportional pressure control method in this
exercise consists of a pressure sensor with an output proportional to the pressure exerted on the sensor. The output is sent to an on/off controller that controls a Normally Closed solenoid valve.
Methodology
Turn main power ON and Run
SoftwareSet PSV to 75%
Set Sampling to automatic @ 10s
interval and continuous duration
Setting the on/off
controllerDisturbances
Feed RateEffect of Inlet
and Outlet Flow Rates
Set Point
METHODOLOGY : SETTING ON/OFF CONTROLLER
Set Proportional Band, Integral Time and Derivative Time to 0.
Set Point Value = 200mm Data logging to automatic and 10 s interval Partially Close Drain Valve Begin Data loggingNote the behavior of Sol 2 as level approaches set point
Continue data logging until stable values for magnitude and height are reached.
METHODOLOGY : DISTURBANCES Create New Results Sheet Begin data logging Allow the fluid level oscillations to settle their original values
Finish Data logging Create new results sheet Begin data logging Close the SOL3 valve Allow the fluid level oscillations to settle their original values
Finish Data logging
METHODOLOGY : SET POINT Alter set point to 100mm begin data logging Allow the oscillations in fluid level to reach steady values of magnitude and duration.
Finish Data logging Create a new results sheet Repeat procedure varying the set point to 150mm, 200mm and 300mm.
METHODOLOGY : FEED RATE Create new results sheet begin data logging Change Inlet feed rate by adjusting the pressure regulator on the inlet of the pipe of the apparatus
Allow the oscillations in fluid level to reach steady values of magnitude and duration.
Alter the feed rate. Continue to reduce feed rate until fluid level in the vessel does not return to set point
finish data logging
METHODOLOGY : EFFECT OF INLET AND OUTLET FLOW RATES Decrease the Outflow rate begin data logging Continue logging until the oscillations about the set point value reach stable values.
finish data logging create new results sheet Increase outflow rate repeat procedure 2-4 Return drain valve to a partially closed position
RESULTS AND DISCUSSION:ON/OFF
0 10 20 30 40 50 60 700
50
100
150
200
250Level vs. Time
Level vs. Time
RESULTS AND DISCUSSION:DISTURBANCE(1)
0 10 20 30 40 50 60 70180
185
190
195
200
205
210Disturbance (1)
Level vs. time
RESULTS AND DISCUSSION:DISTURBANCE(2)
0 5 10 15 20 25 30180
190
200
210
220
230
240
250
239
Disturbance (2)
level vs. time
RESULTS AND DISCUSSION:100mm Setpoint
0 20 40 60 80 100 1200
50
100
150
200
250
Set Point (100mm)
level vs. time
RESULTS AND DISCUSSION:150mm Setpoint
0 5 10 15 20 25 300
20
40
60
80
100
120
140
160
180
SetPoint (150mm)
level vs time
RESULTS AND DISCUSSION:Effect of Feed Rate
0 10 20 30 40 50 60 70 800
50
100
150
200
250
Effect of Feed Rate
level vs time