PCS-921
description
Transcript of PCS-921
-
5/24/2018 PCS-921
1/4
153read more on www.nrelect.com
The PCS-921 numerical relay provides the protection
of circuit breakers with breaker failure protection, pole
discrepancy protection, dead zone protection, phase/
neutral overcurrent protection, single and/or three-pole
auto-reclosing and synchronism check functions. The PCS-
921 relay employs the programmable logic, configurable I/
O and definable 3-color LEDs to provide flexibility for the
specic applications. Frequency tracking is used to minimize
the sampling error caused by system frequency uctuation.
The PCS-921 relay adopts the advanced multi-processor
platform, providing the interfaces to station bus and process
bus respectively and supporting IEC 61850-8-1 MMS,GOOSE, IEC 61850-9-2 Sampling Value. In addition, RJ-45
faceplate port for testing and setting to make commissioning
and maintenance easier.
PCS-921Circuit Breaker Protection
Functions
Protection and Control
Breaker failure protection (50BF)
Re-tripping the own breaker and tripping the adjacent
breakers will be issued if the external tripping command is
received but the overcurrent element does not drop off. To
improve the sensitivity of generator/transformer protection,
the neutral and negative-sequence overcurrent elements are
provided besides phase overcurrent element.
Pole discrepancy protection (62PD)
The pole discrepancy is detected using the breaker auxiliary
contacts, and the asymmetrical current element could be
selected as an additional criteria.
Dead zone protection (50DZ)
The adjacent breakers will be tripped if the fault between CT
and breaker (dead zone) is detected via the initiating binary
input from external protection, breaker auxiliary contacts and
overcurrent element.
Two stages of phase overcurrent protection (50/51P)
Second harmonic element could be selected to block the
overcurrent element to avoid the maloperation due to
transformer inrush current.
Two stages of neutral overcurrent protection (50/51N)
Second harmonic element could be selected to block the
neutral overcurrent element.
Synchronism check (25)
The criteria could be set as frequency difference, voltage
difference, and phase angle difference. And the checking
condition could be selected as live-bus to dead-line, dead-
bus to live-line or dead-bus to dead-line.
Single and/or three-pole auto-reclosing (79)
Up to 4 shots could be selected for the single-/three- pole
auto-reclosing.
Voltage and current drift auto adjustment
The relay continually and automatically traces the voltage
and current drifts and adjusts the zero point.
Frequency tracking
Frequency tracking is provided to accommodate the
frequency shift in power system.
Monitoring and Measurement
VT circuit supervision (VTS)
CT circuit supervision (CTS)
Self diagnostic
Auxiliary power supervision
Event recorder including 1024 disturbance records, 1024
binary events, 1024 supervision events and 1024 operating
logs
Disturbance recorder including 64 disturbance records
with waveforms (The file format of disturbance recorder is
compatible with international COMTRADE le.)
-
5/24/2018 PCS-921
2/4
Read more on the web
www.nrelect.com154 read more on www.nrelect.com
Counter of circuit breaker operation (single-pole tripping,
three-pole tripping and reclosing)
Communication
Two 10Base-T/100Base-TX (RJ45) ports and two optional
100Base-FX ports with IEC 61850-8-1 MMS and GOOSE for
non-time-critical message, IEC 60870-5-103 over TCP/IP orDNP 3.0
Two RS-485 rear ports with IEC 60870-5-103
Six or Eight 100Base-FX ports with IEC 61850-9-2 Sampling
Value and GOOSE for time-critical message
One RS-485 rear port for clock synchronization
One RS-232 rear port for printer
One faceplate RJ45 port for testing and setting
Clock synchronization via Pulse-Per-Second, IRIG-B and
SNTP
Features
The relay is based on NRs well established and proven
UAPC hardware platform with multi-processor architecture.
The multi CPU technology supports parallel operating
simultaneously.
The two independent data acquisition paths can prevent any
undesired trip caused by component failure. One works as afault detector and the other is designed for protection and its
logic. Tripping outputs are supervised by the fault detector to
prevent a mal-operation.
The sensitive DPFC fault detector element is integrated to
target on the quick response to short-circuit fault.
The relay is compatible with IEC 61850-8-1 MMS, GOOSE
and IEC 61850-9-2 Sampling Value and provides the
independent interfaces for station bus and process bus
respectively.
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage 15% of the nominal auxiliary voltage
Burden
Quiescent condition
-
5/24/2018 PCS-921
3/4
Read more on the web
www.nrelect.com 155read more on www.nrelect.com
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 90% of pickup voltage
Maximum permissive voltage 300Vdc
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input
-
5/24/2018 PCS-921
4/4
Read more on the web
www.nrelect.com156 read more on www.nrelect.com
Minimum receiving power Min. -20dBm Min. -24dBm
System reserve Min +3dB Min +3dB
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON 300K printer
Safety level Isolation to ELV level
- Clock Synchronization Port
Type RS-485
Transmission distance 100M@500VDC
- Electromagnetic Compatibility
1MHz burst disturbance test
Per IEC 60255-22-1:2007
Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Electrostatic discharge test
Per IEC60255-22-2:2008 class IV
For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=801000MHz
Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Fast transient disturbance tests
Per IEC 60255-22-4:2008
Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Surge immunity test
Per IEC 60255-22-5:2008Power supply, AC input, I/O port: class IV, 1.2/50us
Common mode: 4kV
Differential mode: 2kV
Conducted RF Electromagnetic DisturbancePer IEC 60255-22-6:2001
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Power Frequency Magnetic Field ImmunityPer IEC 61000-4-8:2001
class V, 100A/m for 1min, 1000A/m for 3s
Pulse Magnetic Field ImmunityPer IEC 61000-4-9:2001
class V, 6.4/16s, 1000A/m for 3s
Damped oscillatory magnetic eld immunityIEC 61000-4-10:2001
class V, 100kHz & 1MHz100A/m
Auxiliary power supply performance
IEC60255-11: 2008
Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting