    The PCS-921 numerical relay provides the protection

    of circuit breakers with breaker failure protection, pole

    discrepancy protection, dead zone protection, phase/

    neutral overcurrent protection, single and/or three-pole

    auto-reclosing and synchronism check functions. The PCS-

    921 relay employs the programmable logic, configurable I/

    O and definable 3-color LEDs to provide flexibility for the

    specic applications. Frequency tracking is used to minimize

    the sampling error caused by system frequency uctuation.

    The PCS-921 relay adopts the advanced multi-processor

    platform, providing the interfaces to station bus and process

    bus respectively and supporting IEC 61850-8-1 MMS,GOOSE, IEC 61850-9-2 Sampling Value. In addition, RJ-45

    faceplate port for testing and setting to make commissioning

    and maintenance easier.

    PCS-921Circuit Breaker Protection

    Functions

    Protection and Control

    Breaker failure protection (50BF)

    Re-tripping the own breaker and tripping the adjacent

    breakers will be issued if the external tripping command is

    received but the overcurrent element does not drop off. To

    improve the sensitivity of generator/transformer protection,

    the neutral and negative-sequence overcurrent elements are

    provided besides phase overcurrent element.

    Pole discrepancy protection (62PD)

    The pole discrepancy is detected using the breaker auxiliary

    contacts, and the asymmetrical current element could be

    selected as an additional criteria.

    Dead zone protection (50DZ)

    The adjacent breakers will be tripped if the fault between CT

    and breaker (dead zone) is detected via the initiating binary

    input from external protection, breaker auxiliary contacts and

    overcurrent element.

    Two stages of phase overcurrent protection (50/51P)

    Second harmonic element could be selected to block the

    overcurrent element to avoid the maloperation due to

    transformer inrush current.

    Two stages of neutral overcurrent protection (50/51N)

    Second harmonic element could be selected to block the

    neutral overcurrent element.

    Synchronism check (25)

    The criteria could be set as frequency difference, voltage

    difference, and phase angle difference. And the checking

    condition could be selected as live-bus to dead-line, dead-

    bus to live-line or dead-bus to dead-line.

    Single and/or three-pole auto-reclosing (79)

    Up to 4 shots could be selected for the single-/three- pole

    auto-reclosing.

    Voltage and current drift auto adjustment

    The relay continually and automatically traces the voltage

    and current drifts and adjusts the zero point.

    Frequency tracking

    Frequency tracking is provided to accommodate the

    frequency shift in power system.

    Monitoring and Measurement

    VT circuit supervision (VTS)

    CT circuit supervision (CTS)

    Self diagnostic

    Auxiliary power supervision

    Event recorder including 1024 disturbance records, 1024

    binary events, 1024 supervision events and 1024 operating

    logs

    Disturbance recorder including 64 disturbance records

    with waveforms (The file format of disturbance recorder is

    compatible with international COMTRADE le.)

  • 5/24/2018 PCS-921

    2/4

    Read more on the web

    www.nrelect.com154 read more on www.nrelect.com

    Counter of circuit breaker operation (single-pole tripping,

    three-pole tripping and reclosing)

    Communication

    Two 10Base-T/100Base-TX (RJ45) ports and two optional

    100Base-FX ports with IEC 61850-8-1 MMS and GOOSE for

    non-time-critical message, IEC 60870-5-103 over TCP/IP orDNP 3.0

    Two RS-485 rear ports with IEC 60870-5-103

    Six or Eight 100Base-FX ports with IEC 61850-9-2 Sampling

    Value and GOOSE for time-critical message

    One RS-485 rear port for clock synchronization

    One RS-232 rear port for printer

    One faceplate RJ45 port for testing and setting

    Clock synchronization via Pulse-Per-Second, IRIG-B and

    SNTP

    Features

    The relay is based on NRs well established and proven

    UAPC hardware platform with multi-processor architecture.

    The multi CPU technology supports parallel operating

    simultaneously.

    The two independent data acquisition paths can prevent any

    undesired trip caused by component failure. One works as afault detector and the other is designed for protection and its

    logic. Tripping outputs are supervised by the fault detector to

    prevent a mal-operation.

    The sensitive DPFC fault detector element is integrated to

    target on the quick response to short-circuit fault.

    The relay is compatible with IEC 61850-8-1 MMS, GOOSE

    and IEC 61850-9-2 Sampling Value and provides the

    independent interfaces for station bus and process bus

    respectively.

    Technical data

    Power Supply

    Standard IEC 60255-11:2008

    Voltage Range 88 to 300 Vdc or 88 to 264 Vac

    Permissible AC ripple voltage 15% of the nominal auxiliary voltage

    Burden

    Quiescent condition

  • 5/24/2018 PCS-921

    3/4

    Read more on the web

    www.nrelect.com 155read more on www.nrelect.com

    Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA

    Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V

    Dropout voltage 90% of pickup voltage

    Maximum permissive voltage 300Vdc

    Withstand 2000VAC, 2800VDC(continuously)

    Resolving time for logic input

  • 5/24/2018 PCS-921

    4/4

    Read more on the web

    www.nrelect.com156 read more on www.nrelect.com

    Minimum receiving power Min. -20dBm Min. -24dBm

    System reserve Min +3dB Min +3dB

    - Print Port

    Type RS-232

    Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s

    Printer type EPSON 300K printer

    Safety level Isolation to ELV level

    - Clock Synchronization Port

    Type RS-485

    Transmission distance 100M@500VDC

    - Electromagnetic Compatibility

    1MHz burst disturbance test

    Per IEC 60255-22-1:2007

    Common mode: class III 2.5kV

    Differential mode: class III 1.0kV

    Electrostatic discharge test

    Per IEC60255-22-2:2008 class IV

    For contact discharge: 8kV

    For air discharge: 15kV

    Radio frequency interference tests

    Per IEC 60255-22-3:2007 class III

    Frequency sweep

    Radiated amplitude-modulated

    10V/m (rms), f=801000MHz

    Spot frequency

    Radiated amplitude-modulated

    10V/m (rms), f=80MHz/160MHz/450MHz/900MHz

    Radiated pulse-modulated

    10V/m (rms), f=900MHz

    Fast transient disturbance tests

    Per IEC 60255-22-4:2008

    Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns

    Communication terminals: class IV, 2kV, 5kHz, 5/50ns

    Surge immunity test

    Per IEC 60255-22-5:2008Power supply, AC input, I/O port: class IV, 1.2/50us

    Common mode: 4kV

    Differential mode: 2kV

    Conducted RF Electromagnetic DisturbancePer IEC 60255-22-6:2001

    Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz

    Power Frequency Magnetic Field ImmunityPer IEC 61000-4-8:2001

    class V, 100A/m for 1min, 1000A/m for 3s

    Pulse Magnetic Field ImmunityPer IEC 61000-4-9:2001

    class V, 6.4/16s, 1000A/m for 3s

    Damped oscillatory magnetic eld immunityIEC 61000-4-10:2001

    class V, 100kHz & 1MHz100A/m

    Auxiliary power supply performance

    IEC60255-11: 2008

    Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset

    Voltage short interruptions: 100ms for interruption without rebooting