Page 1: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

Parasolo™ PVC Details

Page 2: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

2

Table of Contents

Detail Number Page Number100A Parafast RhinoBond Staggered Insulation Board Layout Detail 1

100B Parafast Rhinobond Assembly Detail 2

101A Roof Membrane Layout Mechanically Attached 3

101B Roof Membrane Layout Adhered Detail 4

102A Side Lap Detail Mechanically Attached 5

102B Side Lap Detail Fully Adhered System 6

103 Cover Strip End Lap Detail 7

104 End Lap Detail 8

107 Parafast RhinoBond Fastening Zones

Locations Over Approved Steel or Concrete Decks 9

108 Parafast RhinoBond Fastening Zones Locations

Over Wood Decks 10

110A Ridge Detail 11

111A Parafast RhinoBond Standard Fastening Pattern

over Approved Steel or Concrete Decks Detail 12

111B Parafast RhinoBond Standard Fastening Pattern

Over Wood Decks Detail 13

112 Change of Deck Plane Detail 14

113 Valley Detail 15

121 Parafast RhinoBond Insulation Fastening Pattern

Approved Steel or Concrete Decks Detail 16

122 Parafast RhinoBond Insulation Fastening Pattern

Approved Steel or Concrete Decks Detail 17

202 Coated Metal Roof Edge Detail 18

204 Coated Metal Joint Detail 19

205 Paraguard Extruded Edge Detail 20

206 Paraguard M Raised Edge Detail 21

211 Gutter with Coated Metal Edge Detail 22

301 Parapet Wall Flashing with Counter Flashing 23

302 Wall and Curb Flashing with Termination Bar Detail 24

303 New Construction with Wall Cap Detail 25

304 Wall Flashing with Coated Metal Edge Detail 26

307A Alternate Wall Base Termination Detail 27

307B Parafast RhinoBond Base Tie In at Angle Change Detail 28

311 Coated Metal Wall Scupper Detail 29

312 Door Threshold Flashing Detail 30

314 Vertical Wall Edge Termination with Coated Metal Detail 31

315 RhinoBond Wall Flashing Fastening Pattern Detail 32

Page 3: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

3

317A High Wall Flashing Detail - 10 ft Sheet 33

317B High Wall Flashing Detail - 5 ft Sheet 34

317C High Wall Flashing Detail With Plates and Fasteners 35

317D High Wall Flashing Detail - Intermittent fastening 36

318A Termination Details 1-3 37

318B Termination Details 4-5 38

319 Counter Flashing Re-Roof Detail 39

325 Corner Curb Wrap Detail 40

327A Inside Corner Reinforcement - Preformed Corner Detail 41

327D Inside Corner Reinforcement - Field Fabrication Detail 42

328A Inside Corner Fabrication - 2 Step Joint Patch Up Detail 43

328B Inside Corner Fabrication - 2 Step Joint Patch-Down Detail 44

329A Outside Corner Reinforcment - Universal Corner Detail 45

401B Field Fabricated Expansion Joint - Flat Type Detail 46

402B Field Fabricated Expansion Joint - Curb Type Detail 47

403B Field Fabricated Wall Expansion Joint Detail - Flat Type Detail 48

404B Field Fabricated Wall Expansion Joint Detail - Curb Type 49

503A Termination At RTU With Welded Lap 50

503B Termination At RTU With Counter Flashing 51

507 Field-Wrapped Penetration Flashing Detail 52

508 High Temperature Stack Flashing Detail 53

510A Penetration with Parapro Flashing - Option 1 54

510B Penetration with Parapro Flashing - Option 2 55

511 Exposed Wood Equipment Support Sleeper Detail 56

512 Concealed Wood Equipment Support Detail 57

513 Drain - Standard Flashing 58

518 Drain - Severe Sump Target Detail 59

519 Drain - Pre Target Detai 60

520 Drain - Post Target Detail 61

525 Pourable Sealant Pocket 62

526A Conical Pipe Boot (Non-Split) 63

526B Conical Pipe Boot (Split) 64

602 Curb Type Tie-In at Flat Roof Detail 65

604 Heat-Welded Walkway Installation Detail 66

605 Lightning Protection Terminal - Roof Mount Detail 67

607 Lightning Protection Terminal - Wall Mount Detail 68

608 Satellite Dish Mounting Detail 69

Page 4: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

1

PARAFAST STAGGERED INSULATIONBOARD LAYOUT DETAIL

NOTES:

1. REFER TO THE PARASOLO DESIGN & APPLICATION GUIDELINES FOR DETAILED INSTALLATIONREQUIREMENTS.

2. INSULATION BOARDS INSTALLED IN SINGLE OR MULTIPLE LAYERS MUST HAVE THE JOINTS BETWEENTHE BOARDS STAGGERED IN ALL DIRECTIONS A MINIMUM OF 6" (152 mm) BETWEEN LAYERS.

3. INSULATION BOARDS INSTALLED OVER STEEL DECKING MUST HAVE BOARDS PLACEDPERPENDICULAR TO DECK FLUTES WITH EDGES OVER FLUTE SURFACE FOR BEARING SUPPORT.

ROOF INSULATION-FIRST LAYER

APPROVED ROOF DECK ORSUBSTRATE

APPROVED COVERBOARD OR ROOFINSULATION (IF REQUIRED).-SECOND LAYER

SECTION VIEW

SEE NOTE #2

6" MIN.(152 mm)

ROOF DECK

SECOND INSULATION LAYER

FIRST INSULATION LAYER

PLAN VIEW

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

100ATHIS DETAIL APPLIES TO:

08-26-2019FIELD OF ROOF SERIES

R

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 5: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

2

PARAFAST RHINOBOND ASSEMBLYDETAIL

NOTES:

1. REFER TO THE PARAFAST RHINBOND ATTACHMENT TABLES FOR DETAILED INSTALLATIONREQUIREMENTS REGARDING DECK TYPE, PLATE & FASTENER TYPE, AND MIN. EMBEDMENT.

2. TOP LAYER OF INSULATION DOES NOT HAVE TO BE STAGGERED IF BASE LAYER IS STAGGERED.

ROOF INSULATION

PARAFAST RHINOBONDPLATES & FASTENERS

REINFORCED PARASOLO MEMBRANE (SMOOTH ONLY)

METAL DECK

APPROVED COVERBOARD ORSECOND LAYER OF INSULATION IFREQUIRED. SEE NOTE 2

APPROVED FLUTE FILLERIF REQUIRED

AIR/VAPOR RETARDER-AS REQUIRED

PLATE WELDED DETAIL

INDUCTION HEAT-WELD

PARAFAST RHINOBOND 3" (76 mm) PLATE

PVC= BLACK PLATE

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

www.siplast.com

DRAWING #

100BTHIS DETAIL APPLIES TO:

08-26-2019FIELD OF ROOF SERIES

R

PARASOLO ROOF MEMBRANE SYSTEMTM

R

HEAT INDUCTIONSYSTEM

Page 6: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

3

ROOF MEMBRANE LAYOUTMECHANICALLY ATTACHED

1. SEE PARASOLO MECHANICALLY ATTACHED SYSTEM GUIDELINES TO DETERMINE FASTENER SPACING FORVARIOUS DECK TYPES AND WIND UPLIFT REQUIREMENTS, AND FOR REQUIRED NUMBER OF PERIMETERHALF SHEETS.

NOTES:

HEAT-WELDED SEAMS

PARAFAST PLATES & FASTENERS

TYPICAL PARASOLO PERIMETER HALFSHEETS

ALTERNATE

REFERENCE PARASOLO 200 SERIESROOF EDGE FLASHING DETAILS FOREDGE TERMINATION

REFERENCE PARASOLO 300 SERIESPARAPET WALL & CURB FLASHING DETAILSFOR WALL TERMINATION

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

www.siplast.com

DRAWING #

101ATHIS DETAIL APPLIES TO:

08-26-2019PARAPET WALL & CURB SERIES

PARAPET WALL

PAR

APET

WAL

L

PARASOLO MEMBRANE

PARASOLO ROOF MEMBRANE SYSTEMTM

MECHANICALLYATTACHEDSYSTEMS

Page 7: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

4

ROOF MEMBRANE LAYOUT ADHEREDDETAIL

REFERENCE PARASOLO 200SERIES ROOF EDGE FLASHINGDETAILS FOR EDGE TERMINATION

REFERENCE PARASOLO 300 SERIESPARAPET WALL & CURB FLASHINGDETAILS FOR WALL TERMINATION

1. SEE PARASOLO ADHERED SYSTEM TECHNICAL GUIDELINES TO DETERMINE PERIMETER ANDPENETRATION FASTENER SPACING FOR VARIOUS DECK TYPES AND WIND UPLIFT REQUIREMENTS.

NOTES:

PARASOLO MEMBRANE

ALTERNATE

HEAT-WELDED SEAMS

SEE NOTE 1

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

www.siplast.com

DRAWING #

101BTHIS DETAIL APPLIES TO:

09-10-2019PARAPET WALL & CURB SERIES

PARAPET WALL

PAR

APET

WAL

L

PARASOLO ROOF MEMBRANE SYSTEMTM

ADHEREDSYSTEMS

Page 8: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

5

NOTES:

1. FOR HEAT-WELDING LAPS USE 1.5" MIN. (25.4 mm) WELD WITH AUTOMATIC MACHINE WELDERAND 2" MIN. (127 mm) WELD WITH HAND WELDER.

ROOF INSULATION

ROOF DECK/SUBSTRATE

HEAT-WELDED LAP (SEE NOTE #1)

REINFORCED PARASOLO MEMBRANE

SIDE LAP DETAIL MECHANICALLYATTACHED

6" (152 mm)

PARAFAST FASTENERS & PLATES 12" (305 mm) O.C. MAX

REINFORCED PARASOLOMEMBRANE FIELD SHEETS(NOT TO SCALE)

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

www.siplast.com

DRAWING #

102ATHIS DETAIL APPLIES TO:

08-26-2019FIELD OF ROOF SERIESPARASOLO ROOF MEMBRANE SYSTEM

TM

MECHANICALLYATTACHEDSYSTEMS

Page 9: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

6

SIDE LAP DETAIL FULLY ADHEREDSYSTEM

NOTES:

ROOF INSULATION

ROOF DECK/SUBSTRATE

HEAT-WELDED LAP (SEE NOTE #1)

REINFORCED PARASOLO MEMBRANE

1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN.WELD WITH HAND WELDER.

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

www.siplast.com

DRAWING #

102BTHIS DETAIL APPLIES TO:

09-10-2019FIELD OF ROOF SERIES

3" (76 mm)min.

PARASOLO ROOF MEMBRANE SYSTEMTM

ADHEREDSYSTEMS

Page 10: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

7

NOTES:

ROOF INSULATION

ROOF DECK/SUBSTRATE

REINFORCED PARASOLO MEMBRANE

HEAT-WELDED LAP (SEE NOTE #1)

COVER STRIP END LAP DETAIL

PARASOLO FLASHING STRIP ACCESSORY OR 8" (203 mm) WIDEREINFORCED PARASOLO MEMBRANE

THIS DETAIL REQUIRED FOR ALLFLEECE-BACK MEMBRANES ANDOPTIONAL FOR ALL OTHER LISTEDSYSTEMS BELOW

PARASOLO T-JOINT COVERPATCHES REQUIRED IFFIELD FABRICATED STRIP IS80 MIL REINFORCEDPARASOLO MEMBRANE.

REINFORCED PARASOLOMEMBRANE FIELD SHEETS(NOT TO SCALE)

8" (203 mm)

2" (51 mm)

2" (51 mm)

1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITHHAND WELDER.

PARAFAST PLATES ANDFASTENERS (MECHANICALLYATTACHED SYSTEMS ONLY)

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

103THIS DETAIL APPLIES TO:

08-26-2019FIELD OF ROOF SERIES

TM

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 11: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

8

END LAP DETAIL

NOTES:

ROOF INSULATION

ROOF DECK/SUBSTRATE

HEAT-WELDED LAP (SEE NOTE #2)

REINFORCED PARASOLO MEMBRANE

REINFORCED PARASOLOMEMBRANE FIELD SHEETS(NOT TO SCALE)

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

104THIS DETAIL APPLIES TO:

08-26-2019FIELD OF ROOF SERIES

3" (76 mm)MINIMUM

1. PARASOLO T-JOINT PATCH REQUIRED FOR 80 MIL PARASOLO MEMBRANE, REFER TO PARASOLO DETAIL 105.

2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 12: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

9

FIELD OF ROOF SERIES

PARAFAST RHINOBOND INSULATIONFASTENING ZONES/LOCATIONS APPROVED

STEEL OR CONCRETE DECKS

CO

RN

ER

CORNERRAISED ROOF EDGEOR PARAPET WALL

1. SEE PARASOLO SYSTEM GUIDELINES IN SPECIFICATIONS TO DETERMINE FIELD PERIMETER, AND CORNERFASTENER PLACEMENT FOR VARIOUS DECK TYPES AND WIND UPLIFT REQUIREMENTS.

2. IF A PORTION OF A BOARD EXTENDS INTO ANOTHER ZONE, IT MUST DEFER TO THE ZONE OF THE GREATERFASTENING PATTERN.

NOTES:

8'(2.44 m)

PERIMETER

4'(1.22 m)

4'(1.22 m)

4'(1.22 m)

4'(1.22 m)

FIELD

PER

IMET

ERFI

ELD

FIELD

PERIMETER

CORNER

ZONE LEGEND

6 FASTENERS PER BOARD

12"

36"

36"

12"

12" 12"24"

12"

36"

36"

12"

12"

8"

16"

8"

12" 12"24"

16"

16"

16"

16"

9 FASTENERS PER BOARD

12 FASTENERS PER BOARD

CORNERC

C

B

A

B

PERIMETERB

FIELDA

TRANSITION

SEE NOTE #2

PERIMETERFASTENING

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

www.siplast.com

DRAWING #

107THIS DETAIL APPLIES TO:

08-27-2019

RR

12" 12" 12"

PARASOLO ROOF MEMBRANE SYSTEMTM

HEAT INDUCTIONSYSTEMS

Page 13: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

10

PARAFAST RHINOBOND INSULATIONFASTENING ZONES/LOCATIONS, APPROVED

WOOD DECKS

CO

RN

ER

CORNERRAISED ROOF EDGEOR PARAPET WALL

1. SEE PARASOLO SYSTEM GUIDELINES IN SPECIFICATION MANUAL TO DETERMINE FIELD, PERIMETER ANDCORNER FASTENER PLACEMENT FOR VARIOUS DECK TYPES AND WIND UPLIFT REQUIREMENTS.

2. IF A PORTION OF A BOARD EXTENDS INTO ANOTHER ZONE, IT MUST DEFER TO THE ZONE OF THE GREATERFASTENING PATTERN.

NOTES:

8'(2.44 m)

PERIMETER

4'(1.22 m)

4'(1.22 m)

4'(1.22 m)

4'(1.22 m)

FIELD

PER

IMET

ERFI

ELD

FIELD

PERIMETER

CORNER

ZONE LEGEND

8 FASTENERS PER BOARD

12"

24"

12"

12" 12"24"

6"

24"

6"

12 FASTENERS PER BOARD

16 FASTENERS PER BOARD

CORNERC

C

B

A

B

PERIMETERB

FIELDA

TRANSITION

SEE NOTE #2

8"

12" 12"24"

12"6"

PERIMETERFASTENING

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

www.siplast.com

DRAWING #

108THIS DETAIL APPLIES TO:

08-27-2019FIELD OF ROOF SERIES

R

24"

24"

12" 12" 6"

16"

16"

16"

16"

16"

8"

24"

24"

PARASOLO ROOF MEMBRANE SYSTEMTM

R

HEAT INDUCTIONSYSTEMS

Page 14: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

11

RIDGE DETAIL

ROOF DECK/ SUBSTRATE

ROOF INSULATION

FOR MECHANICALLY ATTACHEDSYSTEMS OVER 2:12 USE A HALF SHEETOF MEMBRANE AS A CAP

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

110ATHIS DETAIL APPLIES TO:

08-28-2019

REFER TO APPROPRIATEPARASOLO LAP DETAIL

FIELD OF ROOF SERIESPARASOLO ROOF MEMBRANE SYSTEM

TM

Page 15: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

12

PARAFAST RHINOBOND STANDARDFASTENING PATTERN

APPROVED STEEL AND CONCRETE DECKS

NOTES:

1. REFERENCE SPECIFIC SYSTEM/INSULATION TYPE AND THICKNESS REQUIREMENTS.

2. REFER TO THE PARAFAST RHINOBOND APPLICATION AND SPECIFICATION MANUAL FOR FASTENER AND DECKREQUIREMENTS.

3. CONTACT SIPLAST FOR RECOMMENDED FASTENING FREQUENCIES TO MEET SPECIFIC TESTING, CODE AGENCYOR GUARANTEE REQUIREMENTS.

12"

36"

36"

12"

12" 24" 12" 12" 24" 12"

16"

16"

4' 4'

8' 8'

CORNER AREAPERIMETER AREAFIELD AREA

6 FASTENERS PERBOARD

12 FASTENERS PERBOARD

8"

8"

16"

16"

16"

12"

12"

12" 12"4'

8'

9 FASTENERS PERBOARD

36"

36"

12"12"

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

www.siplast.com

DRAWING #

111ATHIS DETAIL APPLIES TO:

08-28-2019FIELD OF ROOF SERIES

R R

PARASOLO ROOF MEMBRANE SYSTEMTM

(1 FASTENER PER 5.33 sq ft) (1 FASTENER PER 3.56 sq ft) (1 FASTENER PER 2.7 sq ft)

HEAT INDUCTIONSYSTEMS

Page 16: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

13

NOTES:

FIELD OF ROOF SERIES

PARAFAST RHINOBOND STANDARDFASTENING PATTERN

APPROVED WOOD DECKS

CORNER AREAPERIMETER AREAFIELD AREA

12"

12"

12" 24" 12"4'

8'

8 FASTENERS PERBOARD

12"

12"

12"

12"

12"

12"

12"

12"

6" 6"4'

8'

16 FASTENERS PERBOARD

12"

12"

12"

12"

12"

12"

12" 12" 12"12" 24" 12"

16"

16"

4'

8'

12 FASTENERS PERBOARD

8"

8"

16"

16"

16"

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

www.siplast.com

DRAWING #

111BTHIS DETAIL APPLIES TO:

08-28-2019

RR

PARASOLO ROOF MEMBRANE SYSTEMTM

1. REFERENCE SPECIFIC SYSTEM/INSULATION TYPE AND THICKNESS REQUIREMENTS.

2. REFER TO THE PARAFAST RHINOBOND APPLICATION AND SPECIFICATION MANUAL FOR FASTENER AND DECKREQUIREMENTS.

3. CONTACT SIPLAST FOR RECOMMENDED FASTENING FREQUENCIES TO MEET SPECIFIC TESTING, CODE AGENCYOR GUARANTEE REQUIREMENTS.

(1 FASTENER PER 4 sq ft) (1 FASTENER PER 2.7 sq ft) (1 FASTENER PER 2 sq ft)

HEAT INDUCTIONSYSTEMS

Page 17: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

14

ROOF DECK/ SUBSTRATE

NOTES:

HEAT-WELD LAP (SEE NOTE #2)

CHANGE OF DECK PLANE DETAIL

PARAFAST PLATES & FASTENERSAT SPECIFIED FASTENING PATTERN.

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

112THIS DETAIL APPLIES TO:

08-28-2019PARAPET WALL & CURB SERIES

REINFORCED PARASOLOMEMBRANE

REINFORCED PARASOLOMEMBRANE

ROOF INSULATION

1. ALL OTHER SLOPES 1:12 OR GREAT NEED TO BE FASTENED AT ANGLE CHANGE.

2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINEWELDER AND 2" MIN. WELD WITH HAND WELDER..

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 18: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

15

VALLEY DETAIL

ROOF DECK/ SUBSTRATE

ROOF INSULATION

NOTES:

HEAT-WELDED LAP (SEE NOTE #2)

REINFORCED PARASOLO MEMBRANE

1. FOR MECHANICALLY ATTACHED SYSTEMS, VALLEYS MUST BE ADHERED USING APPROVED SPECIFICPARASOLO ADHESIVE.

2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELDWITH HAND WELDER.

PARASOLO ADHESIVE

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

113THIS DETAIL APPLIES TO:

08-28-2019FIELD OF ROOF SERIES

REINFORCED PARASOLO MEMBRANE

PARAFAST FASTENERS & PLATES PERSPECIFIED FASTENING PATTERN

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 19: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

16

FIELD OF ROOF SERIES

12"

36"

36"

12"

12" 24" 12"4'

8'

CORNER AREAPERIMETER AREA*FIELD AREA

6 FASTENERS PERBOARD

12"

18"

18"

12"

12" 12"4'

8'

15 FASTENERS PERBOARD

18"

18"

12"12"

12"

18"

18"

12"

12" 24" 12"4'

8'

10 FASTENERS PERBOARD

18"

18"

PARAFAST RHINOBOND INSULATIONFASTENING PATTERN

APPROVED STEEL AND CONCRETE DECKS

NOTES:

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

www.siplast.com

DRAWING #

121THIS DETAIL APPLIES TO:

09-06-2019

RR

1. REFERENCE SPECIFIC SYSTEM/INSULATION TYPE AND THICKNESS REQUIREMENTS.

2. PARAFAST RHINOBOND PLATE-WELDED SYSTEM IS NOT ACCEPTABLE FOR GYPSUM, CEMENTITIOUS WOODFIBER OR OSB.

3. REFER TO THE PARAFAST RHINOBOND APPLICATION AND SPECIFICATIONS FOR FASTENER AND DECKREQUIREMENTS.

4. CONTACT SIPLAST FOR RECOMMENDED FASTENING FREQUENCIES TO MEET SPECIFIC TESTING, CODEAGENCY, OR GUARANTEE REQUIREMENTS.

*THE FIELD OF ROOF ATTACHMENTS ABOVE EQUATE TO FM 1-90 RATINGS

PARASOLO ROOF MEMBRANE SYSTEMTM

(1 FASTENER PER 5.33 sq ft)

HEAT INDUCTIONSYSTEMS

(1 FASTENER PER 3.2 sq ft) (1 FASTENER PER 2.13 sq ft)

Page 20: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

17

FIELD OF ROOF SERIES

NOTES:

CORNER AREAPERIMETER AREA*FIELD AREA

12"

12"

12" 24" 12"4'

8'

8 FASTENERS PERBOARD

12"

12"

12"

12"

12"

12"

12"

18"

18"

12"

12" 12"4'

8'

15 FASTENERS PERBOARD

18"

18"

12"12"

12"

18"

18"

12"

8'

20 FASTENERS PERBOARD

18"

18"

6" 6"4'

12" 12" 12"

PARAFAST RHINOBOND INSULATIONFASTENING PATTERN

APPROVED STEEL AND CONCRETE DECKS N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

www.siplast.com

DRAWING #

122THIS DETAIL APPLIES TO:

09-06-2019

RR

1. REFERENCE SPECIFIC SYSTEM/INSULATION TYPE AND THICKNESS REQUIREMENTS.

2. PARAFAST RHINOBOND PLATE-WELDED SYSTEM IS NOT ACCEPTABLE FOR GYPSUM, CEMENTITIOUS WOODFIBER OR OSB.

3. REFER TO THE PARAFAST RHINOBOND APPLICATION AND SPECIFICATIONS FOR FASTENER AND DECKREQUIREMENTS.

4. CONTACT SIPLAST FOR RECOMMENDED FASTENING FREQUENCIES TO MEET SPECIFIC TESTING, CODEAGENCY, OR GUARANTEE REQUIREMENTS.

*THE FIELD OF ROOF ATTACHMENTS ABOVE EQUATE TO FM 1-120 RATINGS

PARASOLO ROOF MEMBRANE SYSTEMTM

(1 FASTENER PER 4 sq ft)

HEAT INDUCTIONSYSTEMS

(1 FASTENER PER 2.13 sq ft) (1 FASTENER PER 1.2 sq ft)

Page 21: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

18

NOTES:

ROOF INSULATION

ROOF DECK/SUBSTRATE

HEAT-WELDED LAP (SEE NOTE #1)

HEAT-WELDED LAP (MIN. 2" WELD)

PARASOLO COATED METAL EDGE (SEE NOTE#3)

CONTINUOUS CLEAT SECURED WITH RING SHANKROOFING NAILS @ 12" (305 mm) O.C.

WOOD NAILER SECURED TO DECK.

REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)

COATED METAL ROOF EDGE DETAIL

FOR ALTERNATE TAPERED ROOFEDGE, USE TAPERED INSULATION

8" (203 mm) WIDE PARASOLO FLASHING STRIPHEAT-WELDED

1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELDWITH HAND WELDER.

2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY.THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLYACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.

3. CONTACT THE SIPLAST TECHNICAL DEPARTMENT FOR INFORMATION REGARDING THE APPROPRIATEPROFILES AND GAUGES FOR CLEAT AND PARASOLO METAL.

RING SHANK GALVANIZED NAIL @ 3"(77 mm) O.C. STAGGERED 2" MINIMUMFROM OUTSIDE EDGE OF METAL.

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

202THIS DETAIL APPLIES TO:

09-06-2019ROOF EDGE SERIESPARASOLO ROOF MEMBRANE SYSTEM

TM

Page 22: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

19

USE 2" (52 mm) FOILTAPE OR DUCT TAPEAS BOND BREAKERPARASOLO COATEDMETAL DRIP EDGE

1/4" (6.35 mm) EXPANSION

WOOD NAILER SECUREDTO DECK

ROOF INSULATION

ROOF DECK/SUBSTRATE

CONTINUOUS CLEATSECURED WITH RINGSHANK ROOFING NAILS @12" (305 mm) O.C.

REINFORCED PARASOLOMEMBRANE

COATED METAL JOINT DETAIL

STEP 1.

STEP 2.

STEP 3.

8" (203 mm) WIDE PARASOLOFLASHING STRIP OR 6" (152 mm) WIDE PARASOLOMEMBRANE HEAT WELDED

6" (152 mm) WIDE PARASOLOJOINT TREATMENT

SPACE

EXTEND MIN 2" (52 mm)

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

204THIS DETAIL APPLIES TO:

08-28-2019ROOF EDGE SERIES

HEAT-WELDED LAP(MIN. 2" WELD)

HEAT-WELDED LAP(MIN. 2" WELD)

PARASOLO ROOF MEMBRANE SYSTEMTM

1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOPFABRICATION AND JOB-SITE ASSEMBLY. THESE COMPONENTSSHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TOGENERALLY ACCEPTED INDUSTRY PRACTICES, STANDARDS, ANDAPPROVALS.

2. CONTACT SIPLAST FOR INFORMATION REGARDING THE APPROPRIATEPROFILES AND GAUGES FOR CLEAT AND PARASOLO METAL.

NOTES:

Page 23: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

20

PARAGUARD EXTRUDED EDGEDETAIL

ROOF DECK/SUBSTRATE

ROOF INSULATION

WOOD NAILER SECURED TO DECK

REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)

EXTRUDED RETAINING CLEAT(FASTEN THROUGH PRE-PUNCHED HOLESIN EXTERIOR FACE)

NOTES:

PARAGUARD EXTRUDED EDGE

PARASOLO FLEXSEAL CAULK GRADESEALANT

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

205THIS DETAIL APPLIES TO:

09-10-2019ROOF EDGE SERIES

1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY.THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLYACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.

2. FASCIA FASTENERS ARE PROVIDED WITH THE PARAGUARD EXTRUDED EDGE SYSTEM.

3. IF THE BOTTOM ROW OF FASTENERS ALIGN WITH A SUBSTRATE OTHER THAN A NAILER, ANAPPROPRIATE AND APPROVED FASTENER SHALL BE USED.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 24: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

21

PARAGUARD M RAISED EDGEDETAIL

ROOF DECK/SUBSTRATE

ROOF INSULATION

HEAT-WELDED LAP (MIN 2" WELD)

METAL FORMED RAIL FACE FASTENED12" 9305 mm) O.C.

WOOD NAILER SECURED TO DECK

REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)

PARAGUARD M RAISED EDGE

METAL CONTINUOUS CANT DAMFASTENED 6" (305 mm) O.C.

NOTES:

REINFORCED PARASOLO MEMBRANE

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

206THIS DETAIL APPLIES TO:

08-31-2019ROOF EDGE SERIES

SECTION

1. THE CARPENTRY WORK SHOWN DEPICTS JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/INSTALLED ACCORDING TO GENERALLYACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.

2. REFER TO THE PARAGUARD ROOF PERIMETER SYSTEMS INSTALLER'S GUIDEFOR INFORMATION ON PRODUCTS, SIZING, AND INSTALLATION OF THEPARAGUARD SYSTEM.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 25: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

22

GUTTER WITH COATED METAL EDGEDETAIL

ROOF DECK/SUBSTRATE

ROOF INSULATION

SHEET METAL GUTTER BY OTHERS

WOOD NAILER SECURED TO SUBSTRATE

CONTINUOUS CLEAT SECURED WITH RINGSHANK ROOFING NAILS @ 12" (305 mm) O.C.

PARASOLO COATED METAL EDGE(SEE NOTE #4)

REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)

8" (203 mm) WIDE PARASOLOFLASHING STRIP HEAT-WELDED

RING SHANK GALVANIZED NAILS @ 3" (77 MM)O.C. STAGGERED 2" MINIMUM FROM OUTSIDEEDGE OF METAL.

HEAT-WELDED LAP (MIN. 2" WELD)

NOTES:

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

211THIS DETAIL APPLIES TO:

09-06-2019ROOF EDGE SERIES

HEAT-WELDED LAP (SEE NOTE #1)

1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.

2. REFER TO PARASOLO DETAIL 204 FOR COATED METAL JOINTS.

3. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.

4. CONTACT THE SIPLAST TECHNICAL DEPARTMENT FOR INFORMATION REGARDING THE APPROPRIATE PROFILES ANDGAUGES FOR CLEAT AND PARASOLO METAL.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 26: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

23

PARASOLO FASTENERS & PLATES 12"(305 mm) O.C.

24" - 54" (610 mm -1.37 m)REQUIRES BONDING ADHESIVE

ROOF DECK/SUBSTRATE

ROOF INSULATION

HEAT-WELDED LAP (SEE NOTE #1)

PARASOLO WATER BLOCK SEALANT

PARAFAST TERMINATION BAR FASTENED 8"(203 mm) O.C. W/PARAFAST FASTENERS

REINFORCED PARASOLO MEMBRANE

NOTES:

PARASOLO FLEXSEAL CAULK GRADE SEALANT

PARASOLO BONDING ADHESIVE(SEE FLASHING KEY)

REGLET OR SURFACE-MOUNT COUNTERFLASHING BY OTHERS(REQUIRED FOR EXTENDED-LENGTHGUARANTEE)

4" (1

02 m

m) M

IN.

8" (2

03 m

m)

PARAPET WALL FLASHING WITHCOUNTER FLASHING

PARASOLO FLEXSEAL CAULK GRADESEALANT

WOOD NAILER SECURED TO DECK(OPTIONAL)

ALTERNATE BASEREFER TO DETAIL 307A

min

.

UP TO 24" (610 mm) DRY HUNG

FLASHING KEY

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

301THIS DETAIL APPLIES TO:

09-06-2019PARAPET WALL & CURB SERIES

1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN.WELD WITH HAND WELDER.

2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITEASSEMBLY. THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDINGTO GENERALLY ACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 27: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

24

PARAFAST FASTENERS & PLATES12" (305 mm) O.C.

NOTES:

PARASOLO WATER BLOCK

PARAFAST TERMINATION BARFASTENED 6" (152mm) O.C.

ROOF DECK/SUBSTRATE

HEAT-WELDED LAP (SEE NOTE #1)

ROOF INSULATION

REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)

ALTERNATE BASEREFER TO PARASOLO DETAIL 307A

WALL AND CURB FLASHING WITHTERMINATION BAR DETAIL

PARASOLO FLEXSEAL CAULK GRADESEALANT

PARASOLO ADHESIVE(SEE FLASHING KEY)

24" - 54" (610 mm -1.37 m)REQUIRES BONDING ADHESIVE

UP TO 24" (610 mm) DRY HUNG

FLASHING KEY

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

302THIS DETAIL APPLIES TO:

08-31-2019PARAPET WALL & CURB SERIES

8" (2

03 m

m) M

IN.

1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

1/4" TO 3/4"

Page 28: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

25

PARASOLO ADHESIVE(SEE FLASHING KEY)

PARAFAST FASTENERS & PLATES 12"(305 mm) O.C.

NOTES:

COPING CAP

ROOF DECK/SUBSTRATE

HEAT-WELDED LAP (SEE NOTE #1)

ROOF INSULATION

CONTINUOUS CLEAT

BACK SIDE

ALTERNATE BASEREFER TO PARASOLO DETAIL 307A

12" (305 mm) O.C.

NEW CONSTRUCTION WITH WALL CAPDETAIL

REINFORCED PARASOLO MEMBRANE

WOOD NAILER SECURED TO DECK(OPTIONAL)

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

303THIS DETAIL APPLIES TO:

09-06-2019PARAPET WALL & CURB SERIES

24" - 54" (610 mm -1.37 m)REQUIRES BONDING ADHESIVE

UP TO 24" (610 mm) DRY HUNG

FLASHING KEY

8" (2

03 M

M)

MIN

.

1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.

2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITEASSEMBLY. THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDINGTO GENERALLY ACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.

PARASOLO ROOF MEMBRANE SYSTEMTM

1/4" TO 3/4"

Page 29: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

26

ROOF DECK/SUBSTRATE

PARASOLO ADHESIVE (SEE FLASHING KEY)

PARAFAST FASTENERS & PLATES 12"(305 mm) O.C.

ROOF INSULATION

PARASOLO COATED METAL (SEE NOTE #3)

REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)

NOTES:

CONTINUOUS CLEAT SECURED WITHRING SHANK ROOFING NAILS @ 12"(305mm) O.C.

PARASOLO FLASHING STRIP OR 6" (152 mm)PARASOLO REINFORCED PVC MEMBRANE

GALV. RING SHANK NAIL 3" (77 mm) O.C.STAGGERED.

ALTERNATE BASE

HEAT-WELDED LAP (MIN. 2" WELD)

REFER TO PARASOLO DETAIL 307A

FASTEN 12" (305 mm) O.C.

WALL FLASHING WITH COATED METALEDGE DETAIL

REINFORCED PARASOLO MEMBRANE

WOOD NAILER SECURED TODECK (OPTIONAL)

HEAT-WELDED LAP(SEE NOTE #1)

24" - 54" (610 mm -1.37 m)REQUIRES BONDING ADHESIVE

UP TO 24" (610 mm) DRY HUNG

FLASHING KEY

1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.

2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY.THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLYACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.

3. CONTACT THE SIPLAST TECHNICAL DEPARTMENT FOR INFORMATION REGARDING THEAPPROPRIATE PROFILES AND GAUGES FOR CLEAT AND PARASOLO METAL.

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

304THIS DETAIL APPLIES TO:

08-31-2019PARAPET WALL & CURB SERIESPARASOLO ROOF MEMBRANE SYSTEM

TM

1/4" TO 3/4"

Page 30: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

27

ALTERNATE WALL BASETERMINATION DETAIL

ROOF DECK/SUBSTRATE

HEAT-WELDED LAP (SEE NOTE #3)

ROOF INSULATION

PARAFAST TERMINATION BAR &FASTENERS/ANCHORSFASTENED 8" (203 mm) O.C.

NOTES:

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

307ATHIS DETAIL APPLIES TO:

08-31-2019PARAPET WALL & CURB SERIES

24" - 54" (610 mm -1.37 m)REQUIRES BONDING ADHESIVE

UP TO 24" (610 mm) DRY HUNG

FLASHING KEY

PARASOLO ADHESIVE(SEE FLASHING KEY)

REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)

REINFORCED PARASOLOMEMBRANE

1. PLATES & FASTENERS MAY BE USED IN LIEU OF TERMINATION BAR IN NON-PRESSURIZEDSITUATIONS.

2. THIS DETAIL NEEDS TO BE USED FOR PRESSURIZED SITUATIONS, IN ALL SYSTEMS.

3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN.WELD WITH HAND WELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

PARASOLOWATER BLOCK

SEALANT

Page 31: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

28

PARAFAST RHINOBOND BASE TIE IN ATANGLE CHANGE DETAIL

ROOF DECK/SUBSTRATE

INDUCTION HEAT-WELD

NOTES:

WALL/CURB

REINFORCED PARASOLOMEMBRANE

PARAFAST FASTENERSAND RHINOBOND PLATES12" (305 mm) O.C. MAX

ROOF INSULATION

SEE NOTE #1

INSULATION-FLUTE FILLER IF REQUIRED

APPROVED PARASOLOBONDING ADHESIVE(SEE FLASHING KEY)

REFERENCE PARASOLO300 SERIES PARAPET WALL ANDCURB DETAILS FOR TERMINATION

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

www.siplast.com

DRAWING #

307BTHIS DETAIL APPLIES TO:

08-31-2019PARAPET WALL & CURB SERIES

24" - 54" (610 mm -1.37 m)REQUIRES BONDING ADHESIVE

UP TO 24" (610 mm) DRY HUNG

FLASHING KEY

1. PARAFAST FASTENER & RHINOBOND PLATE MUST BE INSTALLED A MAXIMUM 6" (152 MM) FROMTHE ANGLE CHANGE.

2. REFER TO THE PARAFAST ATTACHMENT TABLES FOR DETAILED INSTALLATION REQUIREMENTSREGARDING DECK TYPE, PLATE & FASTENER TYPE, AND MIN. EMBEDMENT.

PARASOLO ROOF MEMBRANE SYSTEMTM

HEAT INDUCTIONSYSTEMS

R R

Page 32: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

29

ROOF DECK/SUBSTRATE

ROOF INSULATION

PARASOLO FLEXSEAL CAULK GRADE SEALANT

NOTES:

REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)

PREMANUFACTURED OUTSIDE CORNERSHEAT-WELDED (ALL CORNERS)

CONTINUOUS HEAT-WELDED LAP (MIN. 2" WELD)

UNREINFORCED FIELD-FABRICATEDCORNERS - HEAT-WELDED (OPTION 1)

WOOD NAILER SECURED TO DECK(OPTIONAL)

REINFORCED PARASOLO MEMBRANE ORPARASOLO DETAILING MEMBRANE

PARASOLO COATED METAL SCUPPER

CONTINUOUS PERIMETER HEATWELDED LAP (MIN. 2" WELD)

COATED METAL WALLSCUPPER DETAIL

PARAFAST FASTENERS & PLATES 12"(305 mm) O.C.

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

311THIS DETAIL APPLIES TO:

08-31-2019PARAPET WALL & CURB SERIES

PARAFAST FASTENERS 12" (305 mm)O.C. MAX

1. SCUPPERS MUST BE CLOSED OFF ON OUTSIDE OF BUILDING.

2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 33: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

30

PARAFAST FASTENERS & PLATES12" (305 mm) O.C.

NOTES:

THRESHOLD BY OTHERS

ROOF DECK/SUBSTRATE

HEAT-WELDED LAP (SEE NOTE #1)

ROOF INSULATION

PARASOLO WALK PAD (REQUIRED)

REINFORCED PARASOLO MEMBRANE

METAL COUNTERFLASHING

ALTERNATE BASE

DOOR THRESHOLD FLASHING DETAIL

REFER TO PARASOLO DETAIL 307A

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

312THIS DETAIL APPLIES TO:

08-31-2019PARAPET WALL & CURB SERIES

PARASOLO BONDING ADHESIVE(OPTIONAL)

PARASOLO WATER BLOCK ORPARASOLO FLEX SEAL CAULK GRADE

PARASOLO WATER BLOCK ORPARASOLO FLEX SEAL CAULK GRADE

1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.

2. FOR HEIGHTS LESS THAN 8" (203 MM) CONTACT SIPLAST FOR MORE INFORMATION.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 34: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

31

ROOF DECK/SUBSTRATE

REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)

PARAFAST FASTENERS @12" (305 mm) O.C.

ROOF INSULATION

PARASOLO COATED METALEDGING WITH HEMMED EDGE

VERTICAL WALL EDGE TERMINATIONWITH COATED METAL DETAIL

REFERENCE PARASOLO ROOFEDGE FLASHING DETAIL 211 FOREDGE TERMINATION.

HEAT-WELDED LAP (MIN. 2" WELD)

WOOD NAILER SECURED TO DECK(OPTIONAL)

NOTES:

ALTERNATE BASE ATTACHED(SEE PARASOLO DETAIL 307)

REFERENCE PARASOLO300 SERIES PARAPET WALLAND CURB DETAILS FORTERMINATION

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

314THIS DETAIL APPLIES TO:

08-31-2019PARAPET WALL & CURB SERIESPARASOLO ROOF MEMBRANE SYSTEM

TM

1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.

2. CONTACT THE SIPLAST TECHNICAL DEPARTMENT FOR INFORMATION REGARDING THE APPROPRIATE PROFILES ANDGAUGES FOR CLEAT AND PARASOLO METAL.

Page 35: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

32

RHINOBOND WALL FLASHING FASTENINGPATTERN DETAIL

PARAFAST FASTENERS& RHINOBOND PLATES

1. BASE ATTACHMENT TO FOLLOW FIELD OF ROOF APPLICATION

24" O.C.(610 mm)

12" O.C.(305 mm)

12" O.C.(305 mm)

24" O.C.(610 mm)

NOTE:

12" O.C.(305 mm)

12" O.C.(305 mm)

4" O.C.(102 mm)

FROM BASE OF WALLFIRST ROW OF FASTENERS 24" (610 mm) OFF WALL BASECONTINUE 24" (610 mm) UP WALL.

FROM CORNER OF WALLFIRST ROW 4" (102 mm)O.C FROM CORNERTHEN FASTENERS12" (305 mm) O.C.

PLACEMENT LINES TOBE ASSOCIATED WITHFIGURE 1 ABOVE

FIGURE 1

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

315THIS DETAIL APPLIES TO:

08-31-2019PARAPET WALL & CURB SERIES

R

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 36: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

33

12" O

.C.

(305

mm

)

HIGH WALL FLASHING DETAIL10' (3.05 m) WIDE SHEETS

NOTES:

PARAFAST FASTENERS &PLATES FASTENED 12" (305mm) O.C. VERTICALLY UP WALLIN LAPS

ROOF DECK/SUBSTRATE

ROOF INSULATION

HEAT-WELD LAPS(SEE NOTE #3)

REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)

REINFORCED 10' (3.05 m) WIDEPARASOLO MEMBRANE-RUN MEMBRANE WIDTHVERTICALLY UP AND OVERWALL

REFERENCE PARASOLO 300SERIES PARAPET WALL ANDCURB DETAILS FORTERMINATION

20' (3.05 m) MAX

FASTENER SPACING

9' (2

.74

m)

MAX

PARASOLO ADHESIVEREQUIRED

REFERENCE PARASOLO DETAIL 317DFOR VERTICAL SHEET LAYOUT

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

317ATHIS DETAIL APPLIES TO:

09-06-2019PARAPET WALL & CURB SERIES

1. MUST BE FASTENED VERTICALLY ON THE WALL A MINIMUM 10' (3.05 M) FROM ALL ENDS ORCORNERS OF WALL, THEN MAX 20' (6.10 M) THEREAFTER. PARAFAST FASTENERS SPACED 12"(305 MM) O.C.

2. MAX PARAPET WALL HEIGHT NOT TO EXCEED THE WIDTH OF A 10' (3.05 M) SHEET. PARAPETWALL SHOULD BE NO TALLER THAN 9' (2.74 M) TO USE A FULL 10' (3.05 M) SHEET OF MEMBRANEAS FLASHING.

3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PALTES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

1/4" TO 3/4"

Page 37: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

34

HIGH WALL FLASHING DETAIL5' (1.52 m) WIDE SHEETS

NOTES:

PARAFAST FASTENERS &PLATES FASTENED 12"(305 mm) O.C. VERTICALLYUP WALL

ROOF DECK/SUBSTRATE

ROOF INSULATION

HEAT-WELD LAPS (SEE NOTE #2)

REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)

REINFORCED 5' (1.52 m) WIDEPARASOLO MEMBRANE-RUN MEMBRANE WIDTHVERTICALLY UP AND OVERWALL

REFERENCE PARASOLO300 SERIES PARAPET WALLAND CURB DETAILS FORTERMINATION

5' (1.52 m) WIDE

FASTENER SPACING

REFERENCE PARASOLO DETAIL 317DFOR INTERMITTENT FASTENING

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

317BTHIS DETAIL APPLIES TO:

09-06-2019PARAPET WALL & CURB SERIES

12" O

.C.

(305

mm

)

1. WALL HEIGHTS OVER 10' (3.05 M) HIGH REQUIRE THE ENTIRE WALL TO BE FULLY ADHERED.UNDER 10' (3.05 M) CAN BE DRY HUNG WITHOUT ADHESIVE.

2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PALTES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

1/4" TO 3/4"

Page 38: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

35

PARAFAST FASTENERS &PLATES 12" (305 mm) O.C.

HEAT-WELDED LAP (MIN. 2" WELD)

NOTES:

ROOF INSULATION

PARASOLO ADHESIVE REQUIRED24" - 54" (610 mm - 1.37 m) ONSMOOTH MEMBRANE ONLY.

HEAT-WELDED LAP (SEE NOTE #3)

ROOF DECK/SUBSTRATE

REINFORCED PARASOLOMEMBRANE

ALTERNATE BASEREFER TO PARASOLO DETAIL 307A

HIGH WALL FLASHING DETAIL- WITH PLATES AND FASTENERS

REINFORCED PARASOLOMEMBRANE

PARAFAST FASTENERS &PLATES 12" (305 mm) O.C.

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

317CTHIS DETAIL APPLIES TO:

09-06-2019PARAPET WALL & CURB SERIES

1. 24" (610 MM) MAX. DIMENSION FOR LOOSE-APPLIED FLASHINGS.

2. 54" (1.37 M) MAX. DIMENSION FOR FULLY ADHERED FLASHINGS.

3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

24" - 54" (610 mm -1.37 m)REQUIRES BONDING ADHESIVE

UP TO 24" (610 mm) DRY HUNG

FLASHING KEY

SEE

NO

TES

1 &

2SE

E N

OTE

S1

& 2

1/4" TO 3/4"

Page 39: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

36

HIGH WALL FLASHING DETAIL -INTERMITTENT FASTENING

FOR 5' (1.52 m) WIDE SHEETSREFERENCE PARASOLO DETAIL 317B

PARAFAST FASTENERS &PLATES FASTENED 12" (305mm) O.C. HORIZONTALLY

NOTE:

1. FIRST THREE SHEETS FROM THE CORNER AND FIRST THREESHEETS FROM THE WALL EDGE REQUIRE A ROW OF PARAFASTFASTENERS & PLATES 12" O.C. MID WAY UP THE WALL AS SHOWN.

FOR 10' (3.05 m) WIDE SHEETSREFERENCE PARASOLO DETAIL 317A

NOTE:

1. FIRST SHEET FROM THE CORNER AND FIRST SHEET FROM THE WALL EDGE ARE 10' (3.05 m) WIDE.ALL SHEETS IN BETWEEN ARE 20' (6.10 m) WIDE.

REINFORCED PARASOLOMEMBRANE - 5 FT. (1.52 m)WIDE SHEETS

REINFORCED PARASOLOMEMBRANE

8" (203 mm) PARASOLOFLASHING STRIP HEAT-WELDEDOVER ROW OF FASTENERS.

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

317DTHIS DETAIL APPLIES TO:

09-03-2019PARAPET WALL & CURB SERIESPARASOLO ROOF MEMBRANE SYSTEM

TM

Page 40: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

37

PARASOLO ADHESIVE (OPTIONAL)

REINFORCED PARASOLO MEMBRANE

1. MECHANICAL TERMINATION

METAL SURFACE MOUNTED COUNTER FLASHING

PARASOLO BONDING ADHESIVE (OPTIONAL)

REINFORCED PARASOLO MEMBRANE

2. MECHANICAL TERMINATION

FASTENERS 12" (305 mm) O.C.

PARAFAST TERMINATION BAR

PARASOLO ADHESIVE (OPTIONAL)

3. MECHANICAL TERMINATION (15-YR MAX GUARANTEE)

FASTENERS 6" (152 mm) O.C.

METAL COUNTER FLASHING (MAY BE FACE MOUNTED ALSO)

TERMINATION DETAIL 1-3

PARASOLO FLEXSEAL CAULK GRADE SEALANT

PARASOLO FLEXSEAL CAULK GRADE SEALANT

PARAFAST TERMINATION BAR FASTENED 8" (203 MM)O.C (OPTIONAL)

NOTE: EXISTING COUNTERFLASHING MUST BE IN GOODWORKABLE CONDITION AND TIGHT TO WALL.

FASTENERS 8" (203 mm) O.C.

PARASOLO WATER-BLOCK SEALANT

PARASOLO FLEXSEAL CAULK GRADE SEALANT

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

318ATHIS DETAIL APPLIES TO:

REINFORCED PARASOLO MEMBRANE

09-06-2019PARAPET WALL & CURB SERIES

PARASOLO WATER BLOCK SEALANT

NOTE: EXISTING COUNTERFLASHING MUST BE IN GOODWORKABLE CONDITION AND TIGHT TO WALL.

PARASOLO ROOF MEMBRANE SYSTEMTM

PARASOLO WATER BLOCK SEALANT

PARASOLO WATER BLOCK SEALANT

Page 41: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

38

COPING STONE (BY OTHERS)

PARASOLO ADHESIVE (OPTIONAL)

REINFORCED PARASOLO MEMBRANE

4. COPING STONE TERMINATION

METAL CAP (BY OTHERS)

REINFORCED PARASOLO MEMBRANE

5. CAP FLASHING TERMINATION

PARASOLO WATER BLOCK

PARASOLO ADHESIVE (OPTIONAL)

FASTENERS 12" (305 mm) O.C.

TERMINATION DETAILS 4-5

MORTAR (BY OTHERS)

20 YEAR MAXGUARANTEE

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

318BTHIS DETAIL APPLIES TO:

09-03-2019PARAPET WALL & CURB SERIESPARASOLO ROOF MEMBRANE SYSTEM

TM

Page 42: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

39

HEAT-WELDED LAP (SEE NOTE #1)

PARAFAST FASTENERS & PLATES 12" O.C.

REINFORCED PARASOLO MEMBRANE

ROOF DECK/SUBSTRATE

ROOF INSULATION

METAL COUNTER FLASHING WITHATTACHMENT

8" m

in.

PARASOLO ADHESIVE

COUNTER FLASHING RE-ROOF DETAIL

REINFORCED PARASOLO MEMBRANE

WOOD NAILER SECURED TO DECK

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

319THIS DETAIL APPLIES TO:

09-06-2019PARAPET WALL & CURB SERIES

PARASOLO WATERBLOCK SEALANT

PARASOLO FLEXSEAL CAULK GRADESEALANT

1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATIC MACHINEWELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.

2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY.THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLYACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.

NOTES:

PARASOLO ROOF MEMBRANE SYSTEMTM

PARAFAST TERMINATION BAR FASTENED8" (203 MM) O.C

1/4" TO 3/4"

Page 43: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

40

CORNER CURB WRAP DETAIL

NOTES:

PARASOLO CORNER CURB WRAP

HEAT-WELDED LAP(SEE NOTE #3)

REFER TO PARASOLO 300 SERIESPARAPET AND WALL DETAIL FORTERMINATION

6"

(152 mm)

12"(

305

mm

)

ADJUSTABLE CORNER LAPFOR CORNERS GREATERTHAN OR LESS THAN 90DEGREES

REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)

PARAFAST FASTENERS 12"(305 mm) O.C.

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

325THIS DETAIL APPLIES TO:

09-06-2019PARAPET WALL & CURB SERIES

1. FOUR CORNER CURB WRAP PIECES ARE NEEDED TO COMPLETE. VARYING SIZES MAY BENEEDED TO COMPLETE.

2. CORNER WRAP MAY BE ADHERED OR INSTALLED DRY.

3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

1/4" TO 3/4"

Page 44: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

41

NOTES:

REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)

PARASOLO UNIVERSALCORNER - HEAT-WELDED

CORNER-WELD ORHEAT-WELD MEMBRANEPIECE TO MEMBRANEFLASHING

HEAT-WELDED LAP(SEE NOTE #3)

INSIDE CORNER REINFORCMENT-PREFORMED CORNER DETAIL

PARAFAST FASTENERS &PLATES 12" (305mm) O.C.

ROOF INSULATION

ROOF DECK/SUBSTRATE

HEAT-WELDED LAP (SEE NOTE #3)

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

327ATHIS DETAIL APPLIES TO:

09-06-2019PARAPET WALL & CURB SERIESPARASOLO ROOF MEMBRANE SYSTEM

TM

1. FLASHINGS MAY BE ADHERED OR INSTALLED DRY. SEE MANUAL FOR DIMENSIONS.

2. INSIDE CORNERS MAY ALSO BE FIELD-FABRICATED USING UNREINFORCED MEMBRANE.

3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATIC MACHINE WELDER AND 2"MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.

4. EDGE OF MEMBRANE SHOULD NOT TERMINATE BELOW GUTTER EDGES.

1/4"

TO

3/4

"

Page 45: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

42

CUT A SECTION OF NON-REINFORCEDPARASOLO MEMBRANE. FOLD ALONG LINEAS INDICATED.

MEMBRANEUNDERSIDE

FOLDLINE

MEMBRANESURFACE

HEAT-WELD AREAAS SHOWN

REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)

UNFOLD PIECE

FOLD CORNER

PUSH IN

FIELD FABRICATED INSIDECORNER HEAT WELDED INCORNER

1 2 3

4 5 6

INSIDE CORNER REINFORCEMENT -FIELD FABRICATION DETAIL

APPROX. 8" (203 mm)

APPROX. 8"(203 mm)

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

327DTHIS DETAIL APPLIES TO:

09-06-2019PARAPET WALL & CURB SERIES

TM

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 46: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

43

INSIDE CORNER FABRICATION -2 STEP "JOINT PATCH" UP DETAIL

CURB OR WALL

HEAT-WELDED LAP(SEE NOTE #3)

CONTINUOUS HEAT-WELDEDLAP AND ALL SEGMENTS(SEE NOTE #3)

ONE PIECE FOLD WITH "PIGEAR" (DO NOT CUT) ALLSEGMENTS MUST BE WELDEDTO THE VERTICAL FLASHINGS

HEAT-WELDED LAP(SEE NOTE #3)

STEP 1

STEP 2

NOTES:

REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)

CURB OR WALL

REINFORCED PARASOLOMEMBRANE

REINFORCED PARASOLOMEMBRANE

REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)

PARAFAST FASTENERS &PLATES 12" (305 mm) O.C.

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

328ATHIS DETAIL APPLIES TO:

09-06-2019PARAPET WALL & CURB SERIES

1. ALL SEGMENTS OF THE EAR MUST BE WELDED TOGETHER AND WELDED TO THE WALL.

2. CHECK SYSTEM SPECIFICATION FOR GUIDELINES ON ADHERING FLASHINGS.

3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

1/4" TO 3/4"

Page 47: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

44

HEAT-WELDED LAP(SEE NOTE #3)

INSIDE CORNER FABRICATION -2 STEP "JOINT PATCH" DOWN DETAIL

PARASOLO JOINT PATCH ATMEMBRANE OVERLAP

ONE PIECE FOLD WITH "JOINT PATCH"(DO NOT CUT) ALL SEGMENTS MUSTBE WELDED DOWN

1 PIECEMETHOD

2 PIECEMETHOD

REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)

CURB OR WALL

REINFORCED PARASOLOMEMBRANE

NOTES:

HEAT-WELDED LAP(SEE NOTE #3)

PARASOLO JOINT PATCH ATMEMBRANE OVERLAP

ONE PIECE FOLD WITH "JOINTPATCH" (DO NOT CUT) ALLSEGMENTS MUST BE WELDED DOWN

REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)

CURB OR WALL

REINFORCED PARASOLOMEMBRANE

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

328BTHIS DETAIL APPLIES TO:

09-06-2019PARAPET WALL & CURB SERIESPARASOLO ROOF MEMBRANE SYSTEM

TM

1. ALL SEGMENTS OF THE EAR MUST BE WELDED TOGETHER AND WELDED TO THE WALL.

2. CHECK SYSTEM SPECIFICATION FOR GUIDELINES ON ADHERING FLASHINGS.

3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN.WELD WITH HAND WELDER.

Page 48: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

45

ALTERNATEWALL/CURB ATTACHMENT

OUTSIDE CORNER REINFORCEMENT -UNIVERSAL CORNER DETAIL

NOTES:

REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)

PARASOLO UNIVERSALCORNER

HEAT-WELDED LAP(SEE NOTE #3)

REFER TO PARAPET AND WALLDETAIL FOR TERMINATION

STEP 1

STEP 2

HEAT-WELDED LAP(SEE NOTE #3)

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

329ATHIS DETAIL APPLIES TO:

09-06-2019PARAPET WALL & CURB SERIES

1. KEEP FASTENERS BACK FROM CORNER 6" (152 MM) MAX. IN BOTHHORIZONTAL AND VERTICAL APPLICATIONS.

2. CHECK SYSTEM SPECIFICATION FOR GUIDELINES ON ADHERING FLASHINGS.

3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATESWITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD BEYOND FASTENERPLATES WITH HAND WELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

1/4" TO 3/4"

Page 49: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

46

ROOF DECK/SUBSTRATE

ROOF INSULATION

HEAT-WELDED LAP (SEE NOTE #3)

REINFORCED PARASOLO MEMBRANE

TAPERED-EDGE INSULATION

PARASOLO SMOOTH-BACKMEMBRANE ONLY

PARAFAST FASTENERS & PLATES

BATT INSUALTION

BACKER ROD 1-1/2 TIMES OPENING

6" MIN.

HEAT WELDED LAP (SEE NOTE #3)

FIELD FABRICATED EXPANSIONJOINT - FLAT TYPE DETAIL

6" (152 mm) TYPICAL SEAM AREA

NOTES:

WOOD NAILER SECURED TO DECK

WOOD NAILER SECURED TO DECK

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

401BTHIS DETAIL APPLIES TO:

09-04-2019EXPANSION SERIES

1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.

2. FIELD-FABRICATED EXPANSION JOINT SHOULD NOT BE FLEECE-BACK MEMBRANE. USE STANDARD PARASOLOMEMBRANE.

3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATIC MACHINE WELDERAND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 50: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

47

NOTES:

BATT INSULATION

ROOF DECK/SUBSTRATE

REINFORCED PARASOLO MEMBRANE

PARASOLO ADHESIVE

ROOF INSULATION

HEAT-WELDED LAP (MIN. 2" WELD)

FIELD FABRICATED EXPANSIONJOINT - CURB TYPE DETAIL

PARASOLO MEMBRANE

BACKER ROD 1-1/2 TIMES THE OPENING

REINFORCED PARASOLO MEMBRANE

PARAFAST FASTENERS AND PLATES12" (305 mm) O.C.

SECURE MEMBRANE AT TOP OF CURBWITH RING SHANK ROOFING NAILS 12"(305 mm) O.C.

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

402BTHIS DETAIL APPLIES TO:

09-06-2019EXPANSION SERIES

WOOD NAILER SECURED TO DECK

1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.

2. FIELD-FABRICATED EXPANSION JOINT SHOULD NOT BE FLEECE-BACK MEMBRANE. USE PARASOLO SMOOTHMEMBRANE.

3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

HEAT-WELDED LAP (SEE NOTE #3)

Page 51: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

48

NOTES:

FIELD FABRICATED WALL EXPANSIONJOINT DETAIL - FLAT TYPE DETAIL

ROOF DECK/SUBSTRATE

PARASOLO MEMBRANE

PARASOLO ADHESIVE (OPTIONAL)

HEAT-WELDED LAP (MIN. 2" WELD)

REINFORCED PARASOLO MEMBRANE

ROOF INSULATION

BATT INSULATION

HEAT-WELDED LAP (SEE NOTE #2)

REINFORCED PARASOLO MEMBRANE

BACKER ROD 1-1/2 TIMES THEOPENING

PARAFAST FASTENERS AND PLATES12" (305 mm) O.C.

WOOD NAILER SECURED TO DECK

REFERENCE PARASOLO PARAPET WALL &CURB FLASHING DETAILS (300 SERIES) FORWALL OR CURB TERMINATION

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

403BTHIS DETAIL APPLIES TO:

09-06-2019EXPANSION SERIESPARASOLO ROOF MEMBRANE SYSTEM

TM

1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.

2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.

3. FIELD-FABRICATED EXPANSION JOINT SHOULD NOT BE FLEECE-BACK MEMBRANE. USE STANDARD PARASOLOMEMBRANE.

Page 52: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

49

ROOF DECK/SUBSTRATE

PARASOLO ADHESIVE (OPTIONAL)

HEAT-WELDED LAP (MIN. 2" WELD)

REINFORCED PARASOLO MEMBRANE

ROOF INSULATION

BATT INSULATION

PARASOLO ADHESIVE (OPTIONAL)

PARASOLO MEMBRANE

BACKER ROD 1-1/2 TIMES THE OPENING.

HEAT-WELDED LAP (MIN. 2" WELD)

HEAT-WELD LAP (SEE NOTE #2)

PARASOLO MEMBRANE

FIELD FABRICATED WALL EXPANSIONJOINT DETAIL - CURB TYPE

PARAFAST FASTENERS AND PLATES12" (305 mm) O.C.

NOTES:

REFERENCE PARASOLO PARAPET WALL &CURB FLASHING DETAILS (300 SERIES) FORWALL OR CURB TERMINATION

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

404BTHIS DETAIL APPLIES TO:

09-06-2019EXPANSION SERIES

PARAFAST FASTENERS AND PLATES12" (305 mm) O.C.

RING SHANKED GALVANIZED NAILS 12"(305 mm) O.C.

1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESE COMPONENTS SHOULDBE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.

2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HAND WELDER.

3. FIELD-FABRICATED EXPANSION JOINT SHOULD NOT BE FLEECE-BACK MEMBRANE. USE PARASOLO SMOOTH MEMBRANE.

WOOD NAILER SECURED TO DECK

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 53: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

50

TERMINATION AT R.T.U. WITHWELDED LAP DETAIL

ROOF INSULATION

R.T.U.

GALVANIZED ROOF NAILS AT 12" (305 mm)

PARAFAST FASTENERS 12" (305 mm) O.C.

ROOF INSULATION

ROOF DECK/SUBSTRATE

WOOD NAILER THICKNESS OF INSULATION

HEAT-WELDED LAP (SEE NOTE #2)

REINFORCED PARASOLO MEMBRANE

INSULATED METAL CURB

REINFORCED PARASOLO MEMBRANE

REFERENCE PARASOLO PARAPET WALL& CURB FLASHING DETAILS (300 SERIES)FOR BASE TERMINATION

NOTES:

O.C. MAX

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

503ATHIS DETAIL APPLIES TO:

09-06-2019PENETRATION SERIES

1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY.THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLYACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.

2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELDWITH HAND WELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 54: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

51

ROOF INSULATION

R.T.U.

PARAFAST FASTENERS 12" (305 mm) O.C.

ROOF INSULATION

ROOF DECK/SUBSTRATE

WOOD NAILER SECURED TO DECK

HEAT-WELD (SEE NOTE #1)

REINFORCED PARASOLO MEMBRANE

INSULATED METAL CURB

REINFORCED PARASOLO MEMBRANE

REFERENCE PARASOLO PARAPET WALL &CURB FLASHING DETAILS (300 SERIES)FOR BASE TERMINATION

NOTES:

TERMINATION AT EXISTING R.T.U. WITHCOUNTER FLASHING DETAIL

PARAFAST FASTENERS 12" (305 mm) O.C MAX

WOOD NAILER

METAL COUNTER FLASHING OR SLIPFLASHING BY OTHERS 3" (76.2 mm) MIN. FACE.

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

503BTHIS DETAIL APPLIES TO:

09-06-2019PENETRATION SERIES

1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELDWITH HAND WELDER.

2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY.THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLYACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 55: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

52

NOTES:

PARASOLO MEMBRANE TARGET

VENT STACK

STAINLESS STEEL CLAMP

PARASOLO DETAILING MEMBRANE

REINFORCED PARASOLO MEMBRANE

HEAT-WELDED LAP (SEE NOTE #3)

PARASOLO BONDING ADHESIVE

ROOF DECK/SUBSTRATE

ROOF INSULATION

PARASOLO WATER-BLOCK SEALANT

(OPTIONAL)

FIELD-WRAPPED PENETRATIONFLASHING DETAIL

PLAN VIEW

TARGET MADE FROM PARASOLO MEMBRANE

1/2" UP PIPE

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

507THIS DETAIL APPLIES TO:

09-05-2019PENETRATION SERIES

2" (52 mm)

2" (52 MM)

PARASOLO FLEXSEAL CAULKGRADE SEALANT

PARASOLO FASTENERS & PLATES(4 PER PENETRATION)

8" (2

03 m

m)

1"(25.4 mm)

1. FOR INSULATION THICKNESS GREATER THAN 8” (203 MM), AN APPROVED COVERBOARD IS REQUIRED ONMECHANICALLY ATTACHED SYSTEMS ONLY.

2. APPLY HEAT TO UNREINFORCED DETAIL MEMBRANE AND FORM BY HAND PRIOR TO HOT AIR WELDING.

3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATIC MACHINE WELDERAND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 56: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

53

PARAFAST FASTENERS &PLATES 12" (305 mm) O.C.

NOTES:

HEAT-WELDED LAP (SEE NOTE #4)

REINFORCED PARASOLO

METAL BASE

HIGH TEMPERATURE

STAINLESS STEEL CLAMP

RAIN HOOD

PIPE STACK

MEMBRANE

ROOF DECK/SUBSTRATE

PARATHERM ROOF

PLAN VIEW

INSULATION

PARASOLO MEMBRANE TARGET(SEE ABOVE)

HIGH TEMPERATURE STACK FLASHINGDETAIL

TARGET MADE FROM PARASOLOMEMBRANE

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

508THIS DETAIL APPLIES TO:

09-06-2019PENETRATION SERIES

2" (52 mm)

2" (52 MM)

PARASOLO FLEX SEAL CAULKGRADE SEALANT

WOOD NAILER SECURED TODECK (OPTIONAL)

PARASOLO DETAILINGMEMBRANE

1. TO BE USED WHEN TEMPERATURE OF STACK EXCEEDS 160° F.

2. FOR INSULATION THICKNESS GREATER THAN 8” (203 MM), AN APPROVED COVERBOARD IS REQUIRED ONMECHANICALLY ATTACHED SYSTEMS ONLY.

3. APPLY HEAT TO DETAIL MEMBRANE AND FORM BY HAND PRIOR TO INSTALLING.

4. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATIC MACHINE WELDERAND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

PARASOLO WATER-BLOCKSEALANTPARASOLO BONDINGADHESIVE (OPTIONAL)

Page 57: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

54

NOTES:

REINFORCED PARASOLO MEMBRANE

ROOF DECK/SUBSTRATE

ROOF INSULATION

PENETRATION with PARAPROFLASHING - OPTION 1

PLAN VIEW

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #510A

THIS DETAIL APPLIES TO:

09-10-2019PENETRATION SERIES

PARAFAST FASTENERS & PLATES(4 PER PENETRATION)

8" (2

03 m

m)

PARASOLO ROOF MEMBRANE SYSTEMTM

PARAPRO 123 FLASHING SYSTEM(FULLY ADHERE)

PENETRATION(SEE NOTE #1 FOR PREPARATION)

3" MIN.

PARASOLO FLEXSEAL CAULKGRADE SEALANT

PARAPRO 123 FLASHING SYSTEM(FULLY ADHERE)

1. REFER TO SIPLAST PREPARATION GUIDELINES FOR PROPER SURFACE TREATMENT OF ALL MATERIALS PRIOR TO APPLICATION OF PARAPROMATERIALS.

2. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS AND THE PARAPRO 123 FLASHING SYSTEM INSTALLER'SGUIDE SHALL APPLY IN ADDITION TO THE ABOVE DRAWING.

4"

PARASOLO MEMBRANE TARGET

HEAT-WELDED LAP (MIN. 2" WELD)

PARASOLO MEMBRANE TARGET

REINFORCED PARASOLO MEMBRANE

Page 58: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

55

NOTES:

REINFORCED PARASOLO MEMBRANE

ROOF DECK/SUBSTRATE

ROOF INSULATION

PENETRATION with PARAPROFLASHING - OPTION 2

PLAN VIEW

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #510B

THIS DETAIL APPLIES TO:

09-10-2019PENETRATION SERIES

PARAFAST FASTENERS &RHINOBOND PVC PLATES(4 PER PENETRATION)

8" (2

03 m

m)

PARASOLO ROOF MEMBRANE SYSTEMTM

PARAPRO 123 FLASHING SYSTEM(FULLY ADHERE)

PENETRATION(SEE NOTE #1 FOR PREPARATION)

3"

PARASOLO FLEXSEAL CAULKGRADE SEALANT

PARAPRO 123 FLASHING SYSTEM(FULLY ADHERE)

1. REFER TO SIPLAST PREPARATION GUIDELINES FOR PROPER SURFACE TREATMENT OF ALL MATERIALS PRIOR TO APPLICATION OF PARAPROMATERIALS.

2. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS AND THE PARAPRO 123 FLASHING SYSTEM INSTALLER'SGUIDE SHALL APPLY IN ADDITION TO THE ABOVE DRAWING.

REINFORCED PARASOLOMEMBRANE

Page 59: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

56

EXPOSED WOOD EQUIPMENTSUPPORT SLEEPER DETAIL

REINFORCED PARASOLO MEMBRANE

WOOD SLEEPER

WOOD BLOCKING

NOTES:

ROOF DECK/SUBSTRATE

ROOF INSULATION

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

511THIS DETAIL APPLIES TO:

09-05-2019PARAPET WALL & CURB SERIES

PARASOLO WALKWAY PADCONTINUOUS UNDER BLOCKING

1. IF THE INSULATION COMPRESSIVE STRENGTH IS INSUFFIENT FOR THE EQUIPMENT WEIGHT, INSTALL WOODBLOCKING UNDER THE EQUIPMENT CARRYING WOOD SLEEPER, MATCHING THE HEIGHT OF THE INSULATION.

2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 60: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

57

EQUIPMENT SUPPORT BRACKET

HEAT-WELDED LAP (SEE NOTE #2)

SECURED TO DECKEQUIPMENT SUPPORT

PARASOLO ADHESIVE (OPTIONAL)

REINFORCED PARASOLO MEMBRANE

NOTES:

ROOF DECK/SUBSTRATE

ROOF INSULATION

CONCEALED WOOD EQUIPMENTSUPPORT DETAIL

REINFORCED PARASOLO MEMBRANE

PARAFAST FASTENERS & PLATES12" (305 mm) O.C.

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

512THIS DETAIL APPLIES TO:

PARASOLO FLEXSEAL CAULK GRADESEALANT

09-06-2019PENETRATION SERIES

1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.

2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 61: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

58

TAPERED INSULATION

REINFORCED PARASOLO MEMBRANE

DRAIN CLAMP RING

DRAIN STRAINER

NOTES:

ROOF DECK/SUBSTRATE

DRAIN CLAMP RING

DRAIN STRAINER

ROOF DECK/SUBSTRATE

ROOF INSULATION

DRAIN - STANDARD FLASHING DETAIL

PARASOLO WATER-BLOCK SEALANT

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

513THIS DETAIL APPLIES TO:

09-05-2019PENETRATION SERIES

1"

1. A FIELD WELD CANNOT PASS WITHIN 9" (227 MM) OF THE CLAMP RING, OR WITHIN THE DRAIN SUMP ITSELF.

2. MEMBRANE MUST EXTEND MINIMUM 1" (25.4 MM) BEYOND THE BOLT HOLES. THE CLAMPING RING BOLTS MUSTPENETRATE THE MEMBRANE.

3. TAPERED INSULATION TO CREATE A ROOF SUMP MINIMUM 36" (0.914 M) X 36" (0.914 M) IN SIZE. (IF APPLICABLE).

4. USE ONE FULL TUBE OF PARASOLO WATER BLOCK SEALANT PER DRAIN.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 62: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

59

DRAIN BASE

CUT SECTION OFUNREINFORCED PARASOLOMEMBRANE AS SHOWN ANDPOSITIONED INTO DRAIN SUMP.EXTEND MEMBRANE OUT OF DRAINSUMP APPROX. 6" (152 mm).

EXTEND REINFORCED PARASOLOMEMBRANE ONTO MEMBRANE SECTIONPOSITIONED AT DRAIN SUMP AND CUTAS SHOWN TO LAY FLAT IN SUMP. HOTAIR WELD A MIN.OF 2" (52 mm)COMPLETELY SURROUNDING AREA.

MIN. 1-1/2" (38.1 mm) WIDE HEAT-WELD

DRAIN CLAMPING

DRAIN SUMPBOUNDARY

UNREINFORCED PARASOLOMEMBRANE

FIELDMEMBRANECUT TO LAYFLAT IN SUMPAREA

MIN. 1-1/2" (38.1mm) WIDEHEAT-WELD

DRAIN- SEVERE SUMP TARGET DETAIL

MIN. 12" (305 mm)

APPROX. 6" (152 mm)

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

518THIS DETAIL APPLIES TO:

09-05-2019PENETRATION SERIES

TM

3" (76 mm) MIN.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 63: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

60

DRAIN - PRE TARGET DETAIL

PLAN VIEW

DRAIN CLAMP RING

DRAIN STRAINER

ROOF DECK/SUBSTRATE

HEAT-WELDED LAP (SEE NOTE #7)

REINFORCED PARASOLO MEMBRANE

PARAFAST FASTENERS & PLATES 12"(305 mm) O.C.

REINFORCED PARASOLO MEMBRANE(SMOOTH ONLY) TARGET

PARAFAST FASTENERS & PLATES 12"(305 mm) O.C.

PARASOLO WATER BLOCK SEALANT

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

519THIS DETAIL APPLIES TO:

09-05-2019PENETRATION SERIES

NOTES:

1. A FIELD WELD CANNOT PASS WITHIN 9" (227 MM) OF THE CLAMP RING, OR WITHIN THE DRAIN SUMP ITSELF.

2. MEMBRANE MUST EXTEND MINIMUM 1" (25.4 MM) BEYOND THE BOLT HOLES. THE CLAMPING RING BOLTS MUSTPENETRATE THE MEMBRANE.

3. TAPERED INSULATION TO CREATE A ROOF SUMP MINIMUM 36" (0.914 M) X 36" (0.914 M) IN SIZE. (IF APPLICABLE).

4. IF ASPHALT OR ASPHALTIC PRODUCT IS PRESENT, STOP AT BEGINNING OF SUMP AND FLASH WITH FLEECEBACKMEMBRANE.

5. DO NOT RUN SEPARATION SHEET INTO BOWL AREA IF USED IN SYSTEM.

6. USE ONE FULL TUBE OF PARASOLO WATER BLOCK SEALANT PER DRAIN.

7. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATIC MACHINE WELDERAND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.

1"

TAPERED ROOF INSULATION

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 64: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

61

DRAIN - POST TARGET DETAIL

NOTES:

ROOF INSULATION

ROOF DECK/SUBSTRATE

REINFORCED PARASOLO MEMBRANE

DRAIN CLAMP RING

DRAIN STRAINER

HEAT-WELDED LAP (SEE NOTE #6)

REINFORCED PARASOLO MEMBRANE(SMOOTH ONLY)

TAPERED ROOF INSULATION(OPTIONAL)

PARASOLO WATER-BLOCK SEALANT

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

520THIS DETAIL APPLIES TO:

09-06-2019PENETRATION SERIES

1"

1. A FIELD WELD CANNOT PASS WITHIN 9" (227 MM) OF THE CLAMP RING, OR WITHIN THE DRAIN SUMP ITSELF.

2. MEMBRANE MUST EXTEND MINIMUM 1" (25.4 MM) BEYOND THE BOLT HOLES. THE CLAMPING RING BOLTS MUSTPENETRATE THE MEMBRANE.

3. TAPERED INSULATION TO CREATE A ROOF SUMP MINIMUM 36" (0.914 M) X 36" (0.914 M) IN SIZE. (OPTIONAL).

4. DO NOT RUN SEPARATION SHEET INTO BOWL AREA IF USED IN SYSTEM.

5. USE ONE FULL TUBE OF PARASOLO WATER BLOCK SEALANT PER DRAIN.

6. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 65: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

62

POURABLE SEALANT POCKET DETAIL

NOTES:

ROOF INSULATION

ROOF DECK/SUBSTRATE

ROOF PROJECTION

QUICK SET NON-SHRINK GROUT INPOCKET UNDER SEALANT

PREMOLDED PARASOLOSEALANT POCKET

PARASOLO REINFORCEDMEMBRANE

PARASOLO APPROVED SEALANTS

HEAT WELD FLANGE MIN.2" (52 mm)

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

525THIS DETAIL APPLIES TO:

09-05-2019PENETRATION SERIESPARASOLO ROOF MEMBRANE SYSTEM

TM

1. ALLOW 2" (52 MM) CLEARANCE AROUND THE PROJECTION. IF MULTIPLE PROJECTIONS, ALLOW 1" (25.4 MM)BETWEEN PROJECTION AND POCKET.

2. THE EXISTING PROJECTION MUST BE CLEAN OF ALL DEBRIS BEFORE INSTALLATION.

3. FOUR PARAFAST FASTENERS & PLATES INSERTED AROUND PENETRATION.

4. IF SEALANT POCKET MUST BE CUT, STRIP IN CUT WITH UNREINFORCED PVC STRIP MIN 4" (102 MM) WIDE AND RUNOUT ONTO DECK SHEET MINIMUM 2" (52 MM).

5. IF PLATES AND FASTENERS ENCROACH INTO THE SEAM AREA OF THE POCKET, THEN A TARGET MUST BE ADDEDFIRST TO COVER FASTENERS.

Page 66: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

63

CONICAL PIPE BOOT (NON-SPLIT)

2" (51 MM) HEAT-WELDEDLAP AROUND PERIMETERBEYOND FASTENER PLATES

PARASOLO FLEXSEALCAULK GRADE SEALANT

EXISTING PENETRATION

PARASOLO CONICALPIPE BOOT

REINFORCED PARASOLOMEMBRANE

ROOF INSULATION

ROOF DECK/SUBSTRATE

NOTES:

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

526ATHIS DETAIL APPLIES TO:

09-05-2019PENETRATION SERIES

STAINLESS STEEL CLAMP

1. FOUR PARAFAST FASTENERS & PLATES AROUND PENETRATION.

2. IF PLATES AND FASTENERS ENCROACH INTO THE SEAM AREA OF THE POCKET, A TARGET MUST BE ADDED FIRSTTO COVER FASTENERS.

3. THIS PRODUCT IS AVAILABLE IN CUSTOM SIZES. CONTACT SIPLAST FOR MORE INFORMATION.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 67: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

64

CONICAL PIPE BOOT (SPLIT)

HEAT-WELDED LAP(MIN. 2" WELD)

2" (51 MM) HEAT-WELDEDLAP AROUND PERIMETERBEYOND FASTENER PLATES

PARASOLO FLEXSEALCAULK GRADE SEALANT

EXISTING PENETRATION

PARASOLO CONICAL PIPEBOOT

REINFORCED PARASOLOMEMBRANE

ROOF INSULATION

ROOF DECK/SUBSTRATE

NOTES:

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

526BTHIS DETAIL APPLIES TO:

09-06-2019PENETRATION SERIES

1. FOUR PARAFAST FASTENERS & PLATES AROUND PENETRATION.

2. IF PLATES AND FASTENERS ENCROACH INTO THE SEAM AREA OF THE POCKET, A TARGET MUST BE ADDED FIRSTTO COVER FASTENERS.

3. THIS PRODUCT IS AVAILABLE IN CUSTOM SIZES. CONTACT SIPLAST FOR MORE INFORMATION.

PARASOLO ROOF MEMBRANE SYSTEMTM

STAINLESS STEEL CLAMP

Page 68: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

65

ROOF INSULATION

REINFORCED PARASOLO MEMBRANE

PARASOLO ADHESIVE

PARASOLO WATER BLOCK SEALANT

METAL CAP BY OTHERS

ROOF DECK/SUBSTRATE

HEAT-WELDED LAP (SEE NOTE #4)

12" (305 mm) O.C. - BOTH SIDESGROMMETTED FASTENERS

NOTES:

USE LIKE MATERIALS ACCORDING TOEXISTING ROOF SYSTEM

ADJACENT ROOF SYSTEM

REINFORCED PARASOLO MEMBRANE

CURB TYPE TIE-IN AT FLAT ROOF

(OPTIONAL)

WOOD NAILERS SET IN SEALANT

PARAFAST FASTENERS & PLATES12" (305 mm) O.C.

WOOD NAILERS FASTENED TO DECK(MUST BE 4" HIGHER THAN FINISHED DECK)

WOOD NAILERS FASTENED TO DECK

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

602THIS DETAIL APPLIES TO:

09-05-2019SPECIAL CONSTRUCTION SERIES

8" (2

03 M

M)

PARASOLO ROOF MEMBRANE SYSTEMTM

1. FOR INSULATION THICKNESS GREATER THAN 8” (203 MM), AN APPROVED COVERBOARD IS REQUIRED ONMECHANICALLY ATTACHED SYSTEMS ONLY.

2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.

3. SIPLAST DOES NOT GUARANTEE THE WATERTIGHT INTEGRITY OF TIE-INS TO MEMBRANE ROOF SYSTEMS BYOTHER MANUFACTURERS.

4. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.

Page 69: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

66

HEAT WELDED WALKWAYINSTALLATION

PARASOLO REINFORCED MEMBRANE

HEAT-WELDED LAP (SEE NOTE #4)

PARASOLO WALKWAY PAD CUT FROM

30" (762 mm)

ROUND CORNERS

NOTES:

ROOF INSULATION

ROOF DECK / SUBSTRATE

HEAT-WELDED AREA 2" (52 mm)CONTINUOUSLY AROUND PERIMETER

6"min

WALKWAY ROLL

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

604THIS DETAIL APPLIES TO:

09-05-2019SPECIAL CONSTRUCTION SERIES

6" (152 MM)

6" (152 MM)

1. DO NOT CROSS SEAMS WITH WALKWAY PADS 6" (152 MM) OFF EACH SEAM.

2. HEAT-WELD EDGE OF WALKWAY PADS CONTINUOUSLY.

3. REQUIRED AT ALL ROOF ACCESS POINTS.

4. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 70: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

67

CABLE LINE/LIGHTNING ROD BASE

HEAT-WELDED LAP (MIN. 2" WELD)

LIGHTNING ROD

HEAT WELD (MIN. 2" WELD)(BOTH SIDES)

A

A

ROOF INSULATIONROOF DECK / SUBSTRATE

SECTION A

REINFORCED PARASOLO MEMBRANE

REINFORCED PARASOLO MEMBRANE6" (152 mm) x 6" (152 mm) PATCH

LIGHTNING PROTECTION TERMINAL -ROOF MOUNT DETAIL N.T.S.

SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

605THIS DETAIL APPLIES TO:

09-05-2019SPECIAL CONSTRUCTION SERIES

5" (127 MM) M

AX

1. DAMAGE TO PARASOLO MEMBRANE EXCLUDED FROM GUARANTEE COVERAGE.

NOTE:

PARASOLO ROOF MEMBRANE SYSTEMTM

Page 71: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

68

LIGHTNING PROTECTION TERMINAL -WALL MOUNT DETAIL

REINFORCED PARASOLOMEMBRANE

PARASOLO FLEXSEALSEALANT AROUND PLATE

PARASOLO WATER BLOCKSEALANT BETWEEN PLATEAND FLASHING MEMBRANE

SUPPORT PLATE

REINFORCED PARASOLOMEMBRANE STRAP HOT AIRWELDED TO FLASHING

REINFORCED PARASOLOMEMBRANE

PARASOLO WATER BLOCKSEALANT BETWEEN PLATEAND FLASHING MEMBRANE

PARASOLO FLEXSEALSEALANT AROUND PLATE

SIDE MOUNT AIR TERMINALBASE

SUPPORT PLATE

SIDE MOUNT LIGHTING RODHOLDER

ALTERNATE ROD WALL MOUNT

TWISTED COPPER ORALUMINUM CABLE

TWISTED COPPER ORALUMINUM CABLE

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

607THIS DETAIL APPLIES TO:

09-05-2019SPECIAL CONSTRUCTION SERIESPARASOLO ROOF MEMBRANE SYSTEM

TM

1. DAMAGE TO PARASOLO MEMBRANE EXCLUDED FROM GUARANTEE COVERAGE.

NOTE:

Page 72: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

69

PARASOLO REINFORCED

PARASOLO WALKWAY PAD

CONCRETE BLOCK WEIGHT

SATELLITE DISH BASE TRAY

ROOF INSULATION

ROOF DECK / SUBSTRATE

MEMBRANE

N.T.S.SCALE:

REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062

(800) 922-8800

ALL SYSTEMS

www.siplast.com

DRAWING #

608THIS DETAIL APPLIES TO:

SATELLITE DISH MOUNTING DETAIL

09-05-2019SPECIAL CONSTRUCTION SERIESPARASOLO ROOF MEMBRANE SYSTEM

TM

Page 73: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

70

Page 74: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

71

Page 75: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

72

Page 76: Parasolo PVC Details - Siplast/media/IcopalUS/PDFs/PVC_Details_2019_R2.pdf · requirements regarding deck type, plate & fastener type, and min. embedment. 2. top layer of insulation

73

September 2019

For information on Siplast Roofing and Waterproofing Systems, scan our QR Code.

Siplast

1000 Rochelle Blvd.

Irving, Texas 75062

469-995-2200

Facsimile: 469-995-2205

In Canada:

201 Bewicke Ave., Suite 208

Vancouver, BC,

Canada V7M 3M7

604-929-7687

Customer Service in

North America:

Toll Free 1-800-922-8800

www.siplast.com