Tech. Spec. of AMI for Vietnam Final Report Volume II :
-
.)$*%+'$/0 /$( 12*3$+*/0 452*+6+*/%+'$4 6'& 7" 89/&% :2%2&4
-,"
8*'52This specification covers the functional and technical requirements for single-phasesmart meters within the scope of the A1 customer category.
These meters shall be installed at the clients premises according with the locallegislation and using meter boxes if it would be required.
The technical requirements for the smart meters shall be in conformity withinternational standards IEC and local regulations, moreover comply with quality andperformance requirements set by EVN and PCs.
The technical requirements herein should be used for a tendering process and anymeter manufacturer should be able to provide the goods without any problem. Inthis line, the meters offered shall be completed in all respects as necessary for theireffective and trouble-free operation when connected to the system.
The smart meters shall be provided with related documentation, like, but not
limited to, manufacturer information, product data sheet, material and testingcertificates (where applicable), operational philosophy/manual (where applicable),and maintenance instructions.
-,-
W0'44/&HAMI Advanced Metering Infrastructure
AES Advanced Encryption Standard
AMR Automated Meter Reading
CEN Comit Europen de Normalisation
CENELEC Comit Europen de Normalisation Electrotechnique
EMC Electromagnetic Compatibility
EVN VietNam Electricity
EVNPC EVN Power Corporation
IEC International Electrotechnical Commission
IEEE Institute for Electrical and Electronic Engineering
IP Internet Protocol or Index for Protection
ISO International Organization for Standardization
LV Low Voltage
MDMSMeter Data Management System. When a HES is necessary for thecommunications, then MDMS shall refer to both software plus theinterface between them.
MEP Multipurpose Expansion Port
MOIT Ministry of Industry and Trade
MOST Ministry of Science and Technology
PLC Power Line Carrier
RF Radio Frequency
SMT Surface Mount Technology
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
2/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II A
Wi-Fi Wireless Fidelity
-,;
7550+*/N02 8%/$(/&(4The international community has already defined most of the standards required for
accuracy measurement, tariff, security and load control features, as well as dataexchange for meter reading. However communications standards are still indefining process in most of the countries and each country has selected a differenttechnology. In addition the local standards shall be taken into consideration andshould be included once they are defined. The applicable IEC standards for single-phase meters of this category are:
IEC 62052-11 General requirements: metering equipment.
IEC 62052-21 tariff and load control equipment.
IEC 62052-31 - safety requirements.
IEC 62053-21 - Particular requirements: static meters for active energy
(classes 1 and 2). IEC 62053-61 power consumption and voltage requirements.
IEC 62058-3 Acceptance inspection Part 31: particular requirements forstatic meters for active energy (classes 0.2s, 0.5s, 1 and 2).
IEC 62056 Electricity metering Data exchange for meter reading, tariff andload control.
IEC 60529 (2001) - Degree of protection provided by enclosures (IP Code).
IEC 61000-4-30 Electromagnetic compatibility (EMC) Testing andmeasurement techniques Power quality measurement methods.
EN 50470-1 (2009) Electricity metering equipment (a.c.). Generalrequirements, tests and test conditions. Metering equipment (class indexesA, B and C).
EN 50470-3 (2009) Electricity metering equipment (a.c.). Particularrequirements. Static meters for active energy (class indexes A, B and C).
-,=
.)$*%+'$/0 &2V)+&292$%4Smart meters for category A1 are defined for residential customers with lowconsumptions that use simple tariffs scheme (energy registering only). The metersinstalled in these customer premises are single-phase.
Requirements for single-phase smart meters shall comply with the followingfunctionalities:
-,=,"
X52&/%+'$/0
!"#"$"$
%&'()*'+, (. (/012)*/1 ,(332,'+(/ (4 5(62. 1*'*
The meter shall measure and register active energy in one direction (1-quadrant).
The automatic or on-demand readings should be performed in daily andmonthly basis.
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
3/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II C
!"#"$"!
7(62. 8&*3+'9 */*39:+:
The reference voltage value is 220V. Meter should record under voltage and overvoltage and also power cut. Events related to under voltage and overvoltage should be recorded in the
meter. Threshold of under voltage is from 220 to 165 and for overvoltage is
from 240 to 288. These events won't be recorded unless they continue for equal or much
more time than the time set for under voltage and overvoltage threshold.This time may adjust between 1 to 60 seconds (by 1 sec. steps).
For each under voltage, min. voltage during one period should be detectedand recorded.
For each overvoltage, max. Voltage during one period should be detectedand recorded.
Parameters related to threshold and duration of under voltage andovervoltage should be adjustable locally and remotely.
Events related to power cut should be recorded in the meter as flowing:o For long duration power cuts (more than 3 min), duration time and
date should be recorded.o For short duration power cuts, number of power cuts should be
recorded.
!"#"$";
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
4/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II F
!"#"$"?
@+.)6*.2 A51*'2
The meter shall allow local and remote update of firmware. Software for local operation, diagnostics and reporting on the operation of
the meters, enabling full configuration, provisioning, diagnostics and readoutof metering data and events from the meter.
The software shall provide three levels of access:
o operator mode: readout of metering data (current and historic data,register of events, load profile) and parameters from the meter only;
o service mode: readout and provisioning of the meter using readyprovisioning files, clock setting;
o administration mode: full readout and provisioning of the meter. New software versions shall be able operate equipment previously
purchased by the ordering entity from the supplier. Configuration files from an older software version shall be operable in newer
versions. The software for local operation of the meters shall enable export of
metering data, events and configurations from the meters to text files (TXT,CSV, XML) with a documented structure.
Upgrading of firmware should not stop and affect meter's metrology.
!"#"$"B
C(*1 5.(4+3+/D
Only one season and one tariff shall be in operation during any time.
!"#"$"E
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
5/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II I
Demand limitation for emergency situations:o If the Demand limitation in emergency situation is activated it has
the priority to Demand limitation in normal situations.o Demand limitation for emergency situation is activated when average
transmitted Current from the meter exceeded the emergency
demand limitation (SA) for more than K sec.! S is adjustable from 2 A to 60A, by 2A steps.! K is adjustable from 30 sec. to 120 sec. by 1 sec. steps.
!"#"$"H
73&D */1 73*9
The meter shall be connected since its installed in the customer premise.
-,=,-
?'99)$+*/%+'$4
The smart meters shall be capable of using the communication technology definedin the datasheet. The options shall be either PLC or RF Communications. Thereforethe smart meters shall be equipped with a fixed communication module1deviceaccordingly. Communications shall be in any case compliant with the provisionsincluded in the Technical Specifications for Communications attached to thisdocument.
In either case, the meters could be designed as:
!"#"!"$
I*:2J 7CI )2'2.
The smart meters shall be equipped with a fixed built-in PLC communicationmodem. This communication technology shall provide technical performanceand quality characteristics to transmit and receive data between the smart
meters and a data concentrator locally positioned at the LV distributiontransformer location.
The data readout protocol in the PLC communication and through the metercommunication interfaces shall be compliant with the communicationtechnologies described in the technical specifications for communicationsattached to this document.
The PLC communication units shall be able to establish a self-configured,self-healing PLC network supporting:
o star network topology.o tree network topology.
The appliance of PLC technology shall provide data communication betweensmart meters (data collectors/building gateways) and hub/data
concentrators at the LV distribution transformer locations. The applied PLC technology shall provide data transmission rates up to 2400
bps. The communication module shall ensure effective delivery of messages and
alerts from the meters to the central system in the immediate mode, takinginto consideration physical possibilities connected with the appliedcommunication technology.
As a minimum, the meter shall have the following communication interfaces:o for local communication and programming the meter: optical
interface, in accordance with IEC 62056-21.
1This module may be detachable (by means of a RS-485 connector) if the Client request soin the Specifications Data sheet.
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
6/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II E
!"#"!"!
I*:2J K*1+( @.28&2/,9 =2'2.
The radio frequency communication technology shall comply with thedescription of features and international standards in technical specificationsfor communications attached to this document.
The smart meters shall be equipped with a RF network communicationmodule. The RF network communication module in order to transmit and
receive data between the smart meters and a data concentrator in the areashall provide secure communication.
The RF network communication modules shall be able to establish a self-configured, self-healing wireless network supporting:
o star network topology.o tree network topology.o meshed network topology.
The appliance of RF network technology shall provide data communicationbetween:
o smart meters (data collectors/building gateways) and dataconcentrators at the LV distribution transformer locations.
o smart meters (data collectors/building gateways) and meter
repeaters or hub/data repeaters.
!"#"!";
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
7/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II L
The meter shall enable remote synchronization of time:o after installation upon initiation of connection with the
concentrator,o upon request,o on a regular basis period predefined by PCs (from one day to one
month).
-,A,-
:2%2& (24+G$ The meter shall have state-of-the-art surface mount technology (SMT)
components. The cover shall be made of plastic and fitted in such a way that the internal
parts of the meter are accessible only after breaking the meter cover seals. The plastic for the terminal block, meter cover, and base shall be flame-
retardant and UV-stabilized, passing a glow wire test at 960C. The terminal block may be integral with the meter base. Components with critical content materials (mercury, cadmium, cobalt etc.)
should be avoided. A simply separation into different fractions for disposal
(no metal parts molded in plastics) in a recycling process at the end of themeter lifetime should be possible.
The meters shall have conducting terminals suitable for termination ofcurrent and potential leads. The terminals shall have a minimum innerdiameter of 8 mm.
The manner of fixing the conductors to the terminals shall ensure adequateand durable contact such that there is no risk of them coming loose orheating up unduly. Two nickel-plated brass screws shall be provided in eachcurrent terminal for effectively clamping the external leads with thimbles.Each clamping screw shall engage at least 3 threads in the terminals. Theends of the screws shall be such as not to pierce the conductor. Pressurestrips of copper that is nickel or tin-plated shall be fitted in the terminal
holes to reduce the chances of the leads coming loose or heating up in theterminal block.
The terminal cover shall be sealed independently of the meter cover. Theterminal cover shall enclose the actual terminals, the conductor fixingscrews, the external conductors, and their insulation, whereby no part of themeter or cables shall be accessible from the front of the meter.
The fixing screws used on the terminal cover for fixing and sealing shall beretained in the terminal cover.
The terminal block, terminal cover, and meter case shall ensure safetyagainst the propagation of fire or thermal overload of live parts coming intocontact with them.
The meter shall be capable of being sealed in accordance with regulations in
Vietnam.
-,A,;
:2%&'0'GHEach smart meter shall measure the following values;
Active Energy: according to IEC 62053-21 the meter shall be active energy(kWh) metering Class 1 or class B (EN 50470-3:2009).
Active Power: kW.
-,A,=
R02*%&+*/0 Number of Phases: 1+N
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
8/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II #J
Nominal Voltage: standard reference voltage value for direct connection is220V. Meter input voltage range for normal operation should be from 70%to 120% of nominal voltage.
Maximum Voltage: 288V (max. 6 hours) Nominal (Maximum) Current: 5(80)A Single Rate Calibration interval: !4 years Nominal Frequency (fn): according to the Distribution Code of Vietnam, the
nominal frequency of national power system is 50 Hz. Extended operating frequency range: 2%. Voltage circuit with power supply connected: "2W/5VA. Current circuit at basic current Ib: "4VA. Short time over current: !30I max according to IEC for 0.01 sec. Starting current: 0.5% In (IEC 62052-11).
-,A,A
R$Y+&'$92$%/0 Temperature range according to the IEC 6205-11 for the smart meters
should be:
o Limit range of operation for inside of premises: -25C to +55Co Limit range for operation for outside of premises: -25C to +70C
Operation and storage and transport of the meter at the extremes of thistemperature range should only be for a maximum of 6h.
Relative humidity: according to the IEC 6205-11 the meter shall be designedto withstand the following climatic conditions:
o Annual mean: 85%o 60 days spread in a natural manner over a year: 95%o Occasionally on other days: 75%
Protection class: As a minimum the casing shall ensure the degree ofprotection of IP53 according to UNE/EN 60529.
Terminal block: 960C 15C. Terminal cover and meter case: 650C 10C. Duration of application: 30s 1s.
-,A,C
:2*3/$+*/0 Display: The meter shall have an LCD display, comprising 8 segments and
including 2 decimals. The meter display shall be LCD with good contrast andwide viewing angle for easy meter readout. The display image area shall beeasily readable from a distance of approximately 1 meter. It should have awide operating temperature range (industrial grade) and a lifetime of atleast 15 years. The display shall have 8 digits for the cumulative energy,with digit height of 7.5-10 mm. The cumulative readout will be of whole kWh
only, including leading zeros, and shall be the default display at meter powerup. Every numerical element of an electronic display shall be able to show allthe numbers from zero to nine.
General requirements:o Data displayed shall be programmable;o Auto scrolling shall be used for changing displayed data;o Displayed data time duration shall be programmable;o Displayed data programmable parameters should be in destined
configuration file;o Total kWh tariff;o Peak Demand KW;o Current tariff number;o Quadrant indication;
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
9/66
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
10/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II #/
-,A,"3
Record short power cut N All
Internal memory
Register in non-volatilememory
kW, kWh, V, I Required
Register in non-volatilememory
Events/Alerts Required
Time storage Days 60
CommunicationsMeter with Detachable RS-485Communications Module
Required/NotRequired
Meter with integrated PLCModule
Required/NotRequired
Meter with integrated RadioFrequency Module
Required/NotRequired
Communication Interfaces
for Local ReadingOptical interface acc. To IEC62056-21
bps 1200-9600
RMR interface Serial interfaceacc. to IEC
62056-21 to module
bps 1200-9600
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
14/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II #F
Functionalities
SpecificationsUnits Data Confirmed Value
For Meters with Modularcommunication:Modular communicationinterface allowing the
exchange of communicationunits without the breaking ofthe calibration seal.
Required
Multi-channel communicationSimultaneous andindependent communicationvia optical and electricalinterfaces.
Required
Interoperability
Meter to Concentrator Required
Security Features
3 Access levels Required
Meters and MDMS Encrypted Required
Firmware Update
Local and Remote update Required
Load Profiling
Number of channels ofremotely configurable loadprofile data that can becaptured at programmableintervals.
Number 1
Programmable intervals minutes 1 to 60
Load profile storage capacity values !4 months
with samplesevery 30 min
Automatic change of seasonable timetable
Seasons Number 2
Anti-tampering operation
The meter shall measureenergy with a maximum of3% added error in case ofmissing neutral connection
Required
Inverted wiring of the metershall not influence the energyregistration of the meter
Required
Removal of the cable terminalcover detection Required
Meter housing opening RequiredMeter dismantle RequiredRemoval of meter frominstallation site
Required
DC magnetic field detection RequiredAlarming functionality
Power switch On/Off Required
Meter parameterization Required
Date and time sets Required
Terminal cover removal Required
Meter enclosure tampering Required
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
15/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II #I
Functionalities
SpecificationsUnits Data Confirmed Value
DC Field detection Required
Wiring inversion Required
Current without voltage Required
internal errors Required
communication problems Required
configuration problems Required
power breaks Required
phase errors Required
over voltage Required
under voltage Required
Internal Diagnosis
Auto self-check and diagnosticof the meter
Required
Demand Side ManagementDemand limitation Required
Plug and play
Operative since installation Required
Technical Specifications Units DataConfirmed Value
Metrology
Active energy IEC 62053-21 Class Class 1
Active Power kW Required
Active Energy kWh Required
Current
Minimum Base Current lbaccording to IEC 62052-11
A 5
Maximum current Imaxaccording to IEC
A 60
Starting current according toIEC
%In 0.50%
Short time overcurrent A !30 Imax
Voltage
Standard reference VoltageUn (IEC 60038)
V 220
Voltage range %Un 70%-120%(154V-264V)
Calibration interval Years !4
Voltage failure bridging time s 0.5
Voltage restoration functionstandby after
s "5
Frequency
Nominal frequency Hz 50
Extended operating frequencyrange
% 2
Environmental
Temperature range (limit
operation range) for inside ofpremises installed meters
!C -25C to +55C
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
16/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II #E
Functionalities
SpecificationsUnits Data Confirmed Value
Temperature range (limitoperation range) for installedmeters outside of premises
!C -25C to +70C
Relative humidity as per IEC
62052-11
% 5-95
Protection class according toIEC 60529
IP53
Terminal block !C 960C 15C
Terminal cover and metercase
650C 10C
Duration of application s 30s 1s
Mechanical
Designed wire connections 1-phase 1-phase 2 wire
Lifetime years !15 years
Meter serial number Required
DisplayDimensions: Digitize in valueField "8mm
Required
Display of values:Programmable displaysequence
Required
LCD (Dimensions) 8 segments, 8digits
Required
Material Liquid crystaldisplay
Required
Lifetime years !15 yearsClock and calendar
Accuracy (IEC 62052/54-
21)
Delay +/- 0.5 sec/day
Persian calendar including Leap year, Daylight saving time,summer andwinter clock andtariffs for normaldays, weekend,and publicholidays.
Required
Sealed terminal cover Required
Meter Cover seals At least onevisible seal has tobe provided insuch a way thatthe internal partsof the meter areaccessible onlyafter breakingthe seal(s).
Required
Meter Terminal seals At least onevisible seal haveto be providedand no access tothe terminalsshall be possiblewithout breakingthe seal(s) of the
terminalcover(s).
Required
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
17/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II #L
Functionalities
SpecificationsUnits Data Confirmed Value
Power Consumption
In the voltage circuit withpower supply connected
WVA
"2"5
Current circuit at basic currentlb VA"
4
Insulation Strength
Insulation Strength at 50Hzfor 1 min
kV 4
Pulse voltage 1.2/50s acc.Current and voltage circuits
kV 8
Protection class acc. Class 2
Dimensions and layout
Height mm max 279
Width mm max 170
Depth mm max 81
Net weight kg
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
18/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II /J
;
.)$*%+'$/0 /$( 12*3$+*/0 452*+6+*/%+'$4 6'& 7- 89/&% :2%2&4
;,"
8*'52This specification covers the functional and technical requirements for single andthree phases smart meters within the scope of the A2 customer category. This
category is defined as meters in residential customers with higher consumption thatmay require more complex tariffs and parameters registering.
These meters shall be installed at the clients premises according with the locallegislation and using meter boxes if it would be required.
The technical requirements for the smart meters shall be in conformity withinternational standards IEC and local regulations, moreover comply with quality andperformance requirements set by EVN and PCs.
The technical requirements herein should be used for a tendering process and anymeter manufacturer should be able to provide the goods without any problem. Inthis line, the meters offered shall be completed in all respects as necessary for theireffective and trouble-free operation when connected to the system.
The smart meters shall be provided with related documentation, like, but notlimited to, manufacturer information, product data sheet, material and testingcertificates (where applicable), operational philosophy/manual (where applicable),and maintenance instructions.
;,-
W0'44/&HAMI Advanced Metering Infrastructure
AES Advanced Encryption Standard
AMR Automated Meter Reading
CEN Comit Europen de Normalisation
CENELEC Comit Europen de Normalisation Electrotechnique
EMC Electromagnetic Compatibility
EVN VietNam Electricity
EVNPC EVN Power Corporation
IEC International Electrotechnical Commission
IEEE Institute for Electrical and Electronic Engineering
IP Internet Protocol or Index for Protection
ISO International Organization for Standardization
LV Low Voltage
MDMSMeter Data Management System. When a HES is necessary for thecommunications, then MDMS shall refer to both software plus theinterface between them.
MEP Multipurpose Expansion Port
MOIT Ministry of Industry and Trade
MOST Ministry of Science and Technology
PLC Power Line Carrier
RF Radio Frequency
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
19/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II /#
SMT Surface Mount Technology
TOU Time Of Usage
Wi-Fi Wireless Fidelity
;,;
7550+*/N02 8%/$(/&(4The international community has already defined most of the standards required foraccuracy measurement, tariff, security and load control features, as well as dataexchange for meter reading. However communications standards are still indefining process in most of the countries and each country has selected a differenttechnology. In addition the local standards shall be taken into consideration andshould be included once they are defined. The applicable IEC standards for single-phase meters of this category are:
IEC 62052-11 General requirements: metering equipment.
IEC 62052-21 Part 21: tariff and load control equipment.
IEC 62052-31 - Part 31: safety requirements.
IEC 62053-21 - Particular requirements: static meters for active energy(classes 1 and 2).
IEC 62053-23 - Particular requirements: static meters for reactive energy(classes 2 and 3).
IEC 62053-61 Part 61: power consumption and voltage requirements.
IEC 62058-3 Acceptance inspection Part 31: particular requirements forstatic meters for active energy (classes 0.2s, 0.5s, 1 and 2).
IEC 62056 Electricity metering Data exchange for meter reading, tariff andload control.
IEC 60529 (2001) - Degree of protection provided by enclosures (IP Code).
IEC 61000-4-30 Electromagnetic compatibility (EMC) Testing andmeasurement techniques Power quality measurement methods.
EN 50470-1 (2009) Electricity metering equipment (a.c.). Generalrequirements, tests and test conditions. Metering equipment (class indexesA, B and C).
EN 50470-3 (2009) Electricity metering equipment (a.c.). Particularrequirements. Static meters for active energy (class indexes A, B and C).
;,=
.)$*%+'$/0 &2V)+&292$%4Smart meters for category A2 are defined as single-phase and three-phase.Therefore these functional requirements are collecting functionalities of both smartmeters but with each own explanation in the situations that would be required.Requirements for single and three phases smart meters shall comply with thefollowing functionalities:
;,=,"
X52&/%+'$/0
;"#"$"$ %&'()*'+, (. (/012)*/1 ,(332,'+(/ (4 5(62. 1*'*
The meter shall measure and register active and reactive energy in twodirections (4-quadrants).
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
20/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II //
The automatic or on-demand readings should be performed on daily basis.
;"#"$"!
7(62. 8&*3+'9 */*39:+:
Reference Voltage Un is 220/380V. Meter should record under voltage and overvoltage and also power cut. Events related to under voltage and overvoltage should be recorded in the
meter. Threshold of under voltage is from 240 to 165 and for overvoltage isfrom 240 to 288. And for the three-phase under voltage is from 100 to 57.7and for overvoltage is from 240 to 415.
These events won't be recorded unless they continue for equal or muchmore time than the time set for under voltage and overvoltage threshold.This time may adjust between 1 to 60 seconds (by 1 sec. steps).
For each under voltage, min. voltage during one period should be detectedand recorded.
For each overvoltage, max. voltage during one period should be detectedand recorded.
Parameters related to threshold and duration of under voltage and
overvoltage should be adjustable locally and remotely. Events related to power cut should be recorded in the meter as flowing:
o For long duration power cuts (more than 3 min), duration time anddate should be recorded.
o For short duration power cuts, number of power cuts should berecorded.
;"#"$";
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
21/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II /:
o Meter Reading;o Meter Configuration;o Firmware upgrade.
Each meter password should have inaccessible and protected codes. The meter must have integrated security of transmitted data against
unauthorized access, for example, authentication, unauthorized reading,
unauthorized command generating, and the malicious delivery of false data,as well as against spying out the line of communication.
The exchange of data between the meters and the metering datamanagement system shall be encrypted as per the provisions in the securitysection.
The meter shall be compatible with the provisions established in the cyber-security section, which also includes the security features of thecommunications and the MDMS.
;"#"$"E @+.)6*.2 A51*'2
The meter shall allow local and remote update of firmware.
Software for local operation, diagnostics and reporting on the operation ofthe meters, enabling full configuration, provisioning, diagnostics and readoutof metering data and events from the meter.
New software versions shall be able operate equipment previouslypurchased by the ordering entity from the supplier.
Configuration files from an older software version shall be operable in newerversions.
The software for local operation of the meters shall enable export ofmetering data, events and configurations from the meters to text files (TXT,CSV, XML) with a documented structure.
Upgrading of firmware should not stop and affect meter's metrology.
;"#"$"G
%&'()*'+, ,O*/D2 (4 :2*:(/*L32 '+)2'*L32
At least 4 seasons shall be definable. A season shall be defined by a month and a day. Season starting at 00:00 hours of the defined day in every year. Shall be superseded when the next season becomes effective. Holidays and weekdays shall be definable during a season. Ending of a maximum demand time interval shall be performed before the
end of a season. If necessary, self-reading shall be performed before a newseason becomes effective.
;"#"$"H
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
22/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II /A
Demand Management system for normal and emergency situations shouldbe remotely activated or deactivated.
It should be possible to record demand deviations and the demand deviationvalue should be recorded in meter with its date and time.
o Meter should record at least 10 recent demand deviations. Demand limitation for normal situations:
o Demand limitation in normal condition should be adjustable whenenergy is transmitted from network to the consumer and vice versa.
o Whenever the average sent or received current exceeded the normaldemand limitation (YA) for more than X sec. the supplier contactorshould be "ready for reconnection".
! Y is adjustable from 2A to 60A, by 2A steps.! X is adjustable from 30 sec. to 120 sec. by 1 sec. steps.
Default value should be 30sec. Demand limitation for emergency situations:
o If the Demand limitation in emergency situation is activated it hasthe priority to Demand limitation in normal situations.
o Demand limitation for emergency situation is activated when average
transmitted Current from the meter exceeded the emergencydemand limitation (SA) for more than K sec.
! S is adjustable from 2A to 60A, by 2A steps.! K is adjustable from 30 sec. to 120 sec. by 1 sec. steps.
;"#"$"$$ 7.2905*9)2/'
The smart meter shall have the possibility of being in prepayment mode. Insuch case, the following requirements are necessary:
o The prepay register shall enable the activation and deactivation ofprepay register locally (with a tool program) and on the level ofCentral System. The prepay register shall be inactive on default.
oThe delivered meter shall have a separate prepay decreasing registerin kWh. The prepay register shall enable the activation anddeactivation of prepay register locally (with a tool program) and onthe level of Central System. The prepay register shall be inactive ondefault.
o The prepay register shall be 24h day register.o The meter shall enable from the level of Central system the following
functions locally and remotely:! Within the activation of prepay, sending to the registers the
volume of energy that was bought in kWh;! Reading the current remaining amount of energy in kWh;! Leaving on registers the volume of energy or zero the
registers in case of prepay deactivation;! Complement integer register on the amount of purchased
energy in kWh remotely and a locally (using software tool);! Setting the minimal threshold of kWh that remains until the
credit will run out. When the meter reached the threshold, itshall be signalized (on the meter or on the display);
! Register of events about exceeding the minimal threshold untilempty credit;
! Register the event about exhausting the credit.o The meter shall provide automated switch-off of the installation after
the credit run out.
;"#"$"$!
73&D */1 73*9 The meter shall be connected since its installed in the customer premise.
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
23/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II /C
;,=,-
?'99)$+*/%+'$4
The smart meters shall be capable of using the communication technology definedin the datasheet. In this section due to the two types of meters single and three
phase- the options shall be either PLC or RF Communications. Therefore the smartmeters shall be equipped with a fixed communication module2device accordingly.Communications shall be in any case compliant with the provisions included in theTechnical Specifications for Communications attached to this document.
In either case, the meters could be designed as:
;"#"!"$
I*:2J 7CI )2'2.
The smart meters shall be equipped with a fixed built-in PLC communicationmodem. This communication technology shall provide technical performanceand quality characteristics to transmit and receive data between the smartmeters and a data concentrator locally positioned at the LV distribution
transformer location. The data readout protocol in the PLC communication and through the meter
communication interfaces shall be compliant with the communicationtechnologies described in the technical specifications for communicationsattached to this document.
The PLC communication units shall be able to establish a self-configured,self-healing PLC network supporting:
o Star network topology.o Tree network topology.
The appliance of PLC technology shall provide data communication betweensmart meters (data collectors/building gateways) and hub/dataconcentrators at the LV distribution transformer locations.
The applied PLC technology shall provide data transmission rates up to 2400bps.
The communication module shall ensure effective delivery of messages andalerts from the meters to the central system in the immediate mode, takinginto consideration physical possibilities connected with the appliedcommunication technology.
As a minimum, the meter shall have the following communication interfaces:o For local communication and programming the meter: optical
interface, in accordance with IEC 62056-21.
;"#"!"! I*:2J K*1+(@.28&2/,9 =2'2.
The radio frequency communication technology shall comply with thedescription of features and international standards in technical specificationsfor communications attached to this document.
The smart meters shall be equipped with a fixed built-in RF networkcommunication module. The RF network communication module in order totransmit and receive data between the smart meters and a dataconcentrator locally positioned in the area shall provide securecommunication.
The RF network communication modules shall be able to establish a self-configured, self-healing wireless network supporting:
o Star network topology.
2This module may be detachable (by means of a RS-485 connector) if the Client request soin the Specifications Data sheet.
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
24/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II /F
o Tree network topology.o Meshed network topology.
The appliance of RF network technology shall provide data communicationbetween:
o Smart meters (data collectors/building gateways) and dataconcentrators at the LV distribution transformer locations.
o Smart meters (data collectors/building gateways) and meterrepeaters or hub/data repeaters.
;"#"!";
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
25/66
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
26/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II /E
o Reactive Power: kVAr.
o Reactive Energy: kVArh.
o 2-Quadrant metering.
o Instant value of voltage and current.
;,A,=
R02*%&+*/0 Single-Phase: Number of Phases: 1+N Single Rate
o Nominal (Maximum) Current: 5(80)Ao Nominal Voltage: 288Vo Calibration interval: !4 yearso Nominal Frequency (fn): according to the Distribution Code of
Vietnam, the nominal frequency of national power system is 50 Hz.o Extended operating frequency range: allowed variations of 0.2 Hz in
normal operating state, and 0.5 Hz in instability situation.o Voltage circuit with power supply connected: "2W/ 5VA.o Nominal Voltage: standard reference voltage value for direct
connection is 240V. Meter input voltage range for normal operationshould be from 80% to 115% of nominal voltage.
Three-Phase: Number of Phases: 3+N Single Rateo Nominal (Maximum) Current: 15(100)Ao Nominal Voltage: 415Vo Calibration interval: !4 yearso Nominal Frequency (fn): according to the Distribution Code of
Vietnam, the nominal frequency of national power system is 50 Hz.o Extended operating frequency range: allowed variations of 0.2 Hz in
normal operating state, and 0.5 Hz in instability situation.
o
Voltage circuit with power supply connected: "2W/ 5VA.o Nominal Voltage: standard reference voltage value for direct
connection is 440V. Meter input voltage range for normal operationshould be from 80% to 115% of nominal voltage.
Current circuit at basic current Ib: "4VA Short time over current: !30I max according to IEC for 0.01 sec. Starting current: 0.5% In (IEC 62052-11).
;,A,A
R$Y+&'$92$%/0 Temperature range according to the IEC 6205-11 for the smart meters
should be:o Temperature range for inside of premises installed meters: -25C to
+55C.o Temperature range for installed meters outside of premises: -25C to
+70C. Operation and storage and transport of the meter at the extremes of this
temperature range should only be for a maximum of 6h. Relative humidity: according to the IEC 6205-11 the meter shall be designed
to withstand the following climatic conditions:o Annual mean: 85%o 60 days spread in a natural manner over a year: 95%o Occasionally on other days: 75%
Protection class: As a minimum the casing shall ensure the degree ofprotection of IP53 according to UNE/EN 60529.
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
27/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II /L
;,A,C
:2*3/$+*/0 Display: The meter shall have an LCD display, comprising 8 segments and
including 2 decimals. The meter display shall be LCD with good contrast andwide viewing angle for easy meter readout. The display image area shall be
easily readable from a distance of approximately 1 meter. It should have awide operating temperature range (industrial grade) and a lifetime of atleast 15 years. The display shall have 8 digits for the cumulative energy,with digit height of 7.5-10 mm. The cumulative readout will be of whole kWhonly, including leading zeros, and shall be the default display at meter powerup. Every numerical element of an electronic display shall be able to show allthe numbers from zero to nine.
General requirements:o Data displayed shall be programmable;o Auto scrolling shall be used for changing displayed data;o Displayed data time duration shall be programmable;o
Displayed data programmable parameters should be in destinedconfiguration file;o Energy Data;o Total kWh tariff;o Peak Demand KW;o Current tariff number;o Quadrant indication;o The status of relay;o Monthly value accompanied by its respective date and time;o Displayed formats: kWh shall have a 6 digits display;o Date &Time: DD/MM/YY 24 h;o High resolution display mode;o Phases existence/non existence;o Phases sequence order;o Negative consumption flag (the flag shall be extinguished after
reading);o Failure indication and code (if any);o Tamper.
Verification LED: the meter shall be equipped with a test output device thatis accessible from the front in the form of a flashing LED in proportion to themeter constant to test accuracy of the meter on site.
Clock and Calendar: The microprocessor-based meter shall have a built-inclock and calendar having an accuracy of at least 0.5 seconds per day inaccordance with IEC 62052-21 / 62054-21, without the assistance of an
external time-synchronizing pulse. The date and time shall be displayed ondemand. The clock shall be synchronized by time signals received throughthe local or remote communication interface and upon national standard.
Sealed terminal cover: according to the Distribution Code the wholemetering system must be sealed to prevent illegal accesses. The cover shallbe made of plastic and fitted in such way that the internal parts of the meterare accessible only after breaking the meter cover seals.
Meter cover seals: At least one visible seal has to be provided in such a waythat the internal parts of the meter are accessible only after breaking theseal(s).
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
28/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II :J
Meter terminal seals: At least one visible seal have to be provided and noaccess to the terminals shall be possible without breaking the seal(s) of theterminal cover(s).
;,A,E
@+92$4+'$4 /$( 0/H')% Single-phase meter:
o Smart meter dimensions shall be such that it can be placed inside thecurrent meter premise.
o Net weight of a smart meter shall be up to 1kg.o Its preferable that the installation triangle is according to the DIN.
Three-phase meter:o Smart meter dimensions shall be such that it can be placed inside the
current meter premise.o Net weight of a smart meter shall be up to 1.5kg.o Its preferable that the installation triangle is according to the DIN.
;,A,F
?'$$2*%+'$ (+/G&/9 /$( %2&9+$/0 9/&T+$G4 Each meter shall be clearly marked with the connection diagram, preferably
shall be placed on the meter or cover of the terminal strap of the meter.
;,A,D
>/%%2&H The meter shall also be provided with lithium battery as a backup. Maintain clock and calendar and anti tampering features of the meters.
Battery charge condition (meter should indicate the battery status anddisplay it on LCD 6 month before complete discharge also battery status
should be readable by meter read).
;,A,"3
Record short power cut N 2, 3, 4, etc.
Internal memory
Register in non-volatile memory kW, kWh, V, I Required
Register in non-volatile memory Events/Alerts Required
Time storage Days 60
Load Profiling
Number of channels of remotelyconfigurable load profile datathat can be captured atprogrammable intervals.
Number !8
Programmable intervals minutes Up to 15min
Load profile storage capacity values !4 months withsamples every 30
minTime of Use
Active Energy Tariffs 4
Maximum Demand Required
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
37/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II :L
Functionalities
SpecificationsUnits Data Confirmed
ValueAutomatic change of seasonable timetable
Seasons Number 12
Communications
Meter with Detachable RS-485Communications Module Required/NotRequiredThree-Phase Meter withintegrated GSM/GPRS modem
Required/NotRequired
Three-Phase Meter withintegrated 2G/3G modem
Required/NotRequired
Three-Phase Meter withintegrated fiber optic modem
Required/NotRequired
Communication Interfacesfor Local Reading
Optical interface acc. To IEC62056-21
bps 1200-9600
RMR interface Serial interfaceacc. to IEC 62056-21 to module
bps 1200-9600
For Meters with Modularcommunication:Modular communicationinterface allowing the exchangeof communication units withoutthe breaking of the calibrationseal.
Required
Multi-channel communicationSimultaneous and independentcommunication via optical andelectrical interfaces.
Required
Interoperability
Meter to Concentrator Required
Meter to MDMS Required
Security Features
3 Access levels Required
Meters and MDMS Encrypted Required
Firmware Update
Local and Remote update Required
Integrated Disconnect/ Reconnect Switch
Maximum Switching current A 100
Maximum overload current A 120/150Short Circuit current < 10 ms
Switching cycles Number 10,000
Maximum Switching Power kVA 27
Customers manualdisconnection
Yes/No
Power demand exceedingManagement
Yes/no Required
Remote controllable Yes/no Required
Anti-tampering operation
The meter shall measure
energy with a maximum of 3%added error in case of missing
Required
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
38/66
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
39/66
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
40/66
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
41/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II A:
Functionalities
SpecificationsUnits Data Confirmed
Valuerating is 250V,5A; fullyisolated.
Load Disconnect Contactor Required
Dimensions and layout
Height mm max 300
Width mm max 200
Depth mm max 100
Net weight kg
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
42/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II AA
=
.)$*%+'$/0 /$( 12*3$+*/0 452*+6+*/%+'$4 6'& >?@ 89/&%
:2%2&4
=,"
8*'52
This specification covers the functional and technical requirements for three-phasesmart meters within the scope of the BCD clients category. The category BCD isdefined for Industrial and Construction customers plus Commercial and Agriculturalcustomers as well as the bulk points.These meters shall be installed at the clients premises according with the locallegislation and using meter boxes if it would be required.
The technical requirements for the smart meters shall be in conformity withinternational standards IEC and local regulations, moreover comply with quality andperformance requirements set by EVN and PCs.
The technical requirements herein should be used for a tendering process and anymeter manufacturer should be able to provide the goods without any problem. Inthis line, the meters offered shall be completed in all respects as necessary for theireffective and trouble-free operation when connected to the system.
The smart meters shall be provided with related documentation, like, but notlimited to, manufacturer information, product data sheet, material and testingcertificates (where applicable), operational philosophy/manual (where applicable),and maintenance instructions.
=,-
W0'44/&HAMI Advanced Metering Infrastructure
AES Advanced Encryption Standard
AMR Automated Meter Reading
CEN Comit Europen de Normalisation
CENELEC Comit Europen de Normalisation Electrotechnique
EMC Electromagnetic Compatibility
EVN VietNam Electricity
EVNPC EVN Power Corporation
IEC International Electrotechnical Commission
IEEE Institute for Electrical and Electronic Engineering
IP Internet Protocol or Index for Protection
ISO International Organization for Standardization
LV Low Voltage
MDMS Meter Data Management System
MEP Multipurpose Expansion Port
MOIT Ministry of Industry and Trade
MOST Ministry of Science and Technology
PLC Power Line Carrier
RF Radio Frequency
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
43/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II AC
SMT Surface Mount Technology
TOU Time Of Usage
Wi-Fi Wireless Fidelity
=,;
7550+*/N02 8%/$(/&(4The international community has already defined most of the standards required foraccuracy measurement, tariff, security and load control features, as well as dataexchange for meter reading. However communications standards are still indefining process in most of the countries and each country has selected a differenttechnology. In addition the local standards shall be taken into consideration andshould be included once they are defined. The applicable IEC standards for single-phase meters of this category are:
IEC 62052-11 - General requirements: metering equipment.
IEC 62052-21 Tariff and load control equipment.
IEC 62052-31 - Safety requirements.
IEC 62053-22 - Particular requirements: static meters for active energy(classes 0.2S and 0.5S).
IEC 62053-24 - Particular requirements: static meters for reactive energy(classes 0.5 and 1).
IEC 62053-61 Part 61: power consumption and voltage requirements.
IEC 62058-3 Acceptance inspection Part 31: particular requirements forstatic meters for active energy (classes 0.2s, 0.5s, 1 and 2).
IEC 62056 Electricity metering Data exchange for meter reading, tariff andload control.
IEC 60529 (2001) - Degree of protection provided by enclosures (IP Code).
IEC 61000-4-30 Electromagnetic compatibility (EMC) Testing andmeasurement techniques Power quality measurement methods.
EN 50470-1 (2009) Electricity metering equipment (a.c.). Generalrequirements, tests and test conditions. Metering equipment (class indexesA, B and C).
EN 50470-3 (2009) Electricity metering equipment (a.c.). Particularrequirements. Static meters for active energy (class indexes A, B and C).
=,=
.)$*%+'$/0 &2V)+&292$%4Requirements for three-phase smart meters shall comply with the followingfunctionalities:
=,=,"
X52&/%+'$/0
#"#"$"$
%&'()*'+, (. (/012)*/1 ,(332,'+(/ (4 5(62. 1*'*
The meter shall measure and register active and reactive energy in twodirections forward and reverse energy measurements (4-quadrant).
The automatic or on-demand readings should be performed in 15 minutes,
30 minutes, 1 day and monthly basis.
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
44/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II AF
#"#"$"!
7(62. 8&*3+'9 */*39:+:
Meter should record under voltage and overvoltage and also power cut. Events related to under voltage and overvoltage should be recorded in the
meter. Threshold of under voltage is from 57.7 to 100 and for overvoltage isfrom 240 to 415.
These events won't be recorded unless they continue for equal or much
more time than the time set for under voltage and overvoltage threshold.This time may adjust between 1 to 60 seconds (by 1 sec. steps).
For each under voltage, min. voltage during one period should be detectedand recorded.
For each overvoltage, max. Voltage during one period should be detectedand recorded.
Parameters related to threshold and duration of under voltage andovervoltage should be adjustable locally and remotely.
Events related to power cut should be recorded in the meter as flowing:o For long duration power cuts (more than 3 min), duration time and
date should be recorded.o For short duration power cuts, number of power cuts should be
recorded.
#"#"$";
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
45/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II AI
! Programming the level 3 password and the level 4 password. Each meter password should have inaccessible and protected codes. The meter must have integrated security of transmitted data against
unauthorized access, for example, authentication, unauthorized reading,unauthorized command generating, and the malicious delivery of false data,as well as against spying out the line of communication.
The exchange of data between the meters and the metering datamanagement system shall be encrypted.
The meter shall be compatible with the provisions established in the cyber-security section, which also includes the security features of thecommunications and the MDMS.
#"#"$"?
@+.)6*.2 A51*'2
The meter shall allow local and remote update of firmware. Software for local operation, diagnostics and reporting on the operation of
the meters, enabling full configuration, provisioning, diagnostics and readout
of metering data and events from the meter. New software versions shall be able operate equipment previously
purchased by the ordering entity from the supplier. Configuration files from an older software version shall be operable in newer
versions. The software for local operation of the meters shall enable export of
metering data, events and configurations from the meters to text files (TXT,CSV, XML) with a documented structure.
Upgrading of firmware should not stop and affect meter's metrology.
#"#"$"B C(*1 7.(4+3+/D
At least 8 programmable channels for:o active and reactive interval energy (import and export),o active and reactive cumulative energy (import and export).
Adjustable time interval from 1 to 60 minutes. At least 4 programmable channels for voltage and current as well as active
and reactive power. Measurement type for each channel can be chosen as follows:
o Average;o Minimum;o Maximum.
Adjustable time interval from 1 to 60 minutes. Meter should keep above parameters at least for 31 days. The meter shall include binary relay whose state shall be changed once the
demand overpass a threshold defined by the client.
#"#"$"E R+)2 (4 A:2
Meter should be able to calculate and register costumer's active and reactiveenergy consumption in time intervals as bellow:
o Division of each day in to at least 8 consecutive and adjustable timeintervals;
o Four tariffs for active/reactive energy and Max. Demand & recordthem for normal days and holidays separately and also totally as wellas recording of highest Max. Demand;
! 8 day profiles;! 12 seasons;
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
46/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II AE
! 50 definable special days;! week profile.
#"#"$"G 6+',O
The contactor's operation reasons:o Consumption limitation;o Consumer disconnecting / connecting.
#"#"$"H %&'()*'+, ,O*/D2 (4 :2*:(/*L32 '+)2'*L32
At least 12 seasons shall be definable. A season shall be defined by a month and a day. Season starting at 00:00 hours of the defined day in every year. Shall be superseded when the next season becomes effective. Holidays and weekdays shall be definable during a season. Ending of a maximum demand time interval shall be performed before the
end of a season. If necessary, self-reading shall be performed before a newseason becomes effective.
#"#"$"$T
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
47/66
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
48/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II CJ
The figures of the imprinted serial number shall be of at least 4 mm heightand 2 mm width.
The meter shall maintain accuracy throughout its useful life. These energymeters shall be microprocessor-based, high-precision meters with accuracyclass 2 over its lifespan of 15 years.
The meter shall be capable of displaying the energy readings without the
need for multiplying factors. These readings shall be stored for at least 3billing periods. The billing period shall be programmable to a minimum valueof one month and for energy and maximum demand.
Insulation protection class should be 2. Meter calibration should be kept during its lifetime and there should be no
need for re-calibration. Meter should be protected against Electromagnetic Compatibility (EMC). The meter shall enable remote synchronization of time:
o after installation upon initiation of connection with theconcentrator,
o upon request,o on a regular basis period predefined by PCs (from one day to one
month).
=,A,-
:2%2& (24+G$ The meter shall be DIN or A Base type. The meter shall have state-of-the-art surface mount technology (SMT)
components. The cover shall be made of plastic and fitted in such a way that the internal
parts of the meter are accessible only after breaking the meter cover seals. The plastic for the terminal block, meter cover, and base shall be flame-
retardant and UV-stabilized, passing a glow wire test at 960C. The terminal block may be integral with the meter base.
Components with critical content materials (mercury, cadmium, cobalt etc.)should be avoided. A simply separation into different fractions for disposal(no metal parts molded in plastics) in a recycling process at the end of themeter lifetime should be possible.
The meters shall have conducting terminals suitable for termination ofcurrent and potential leads. The terminals shall have a minimum innerdiameter of 8 mm.
The manner of fixing the conductors to the terminals shall ensure adequateand durable contact such that there is no risk of them coming loose orheating up unduly. Two nickel-plated brass screws shall be provided in eachcurrent terminal for effectively clamping the external leads with thimbles.Each clamping screw shall engage at least 3 threads in the terminals. The
ends of the screws shall be such as not to pierce the conductor. Pressurestrips of copper that is nickel or tin-plated shall be fitted in the terminalholes to reduce the chances of the leads coming loose or heating up in theterminal block.
The terminal cover shall be sealed independently of the meter cover. Theterminal cover shall enclose the actual terminals, the conductor fixingscrews, the external conductors, and their insulation, whereby no part of themeter or cables shall be accessible from the front of the meter.
The fixing screws used on the terminal cover for fixing and sealing shall beretained in the terminal cover.
The terminal block, terminal cover, and meter case shall ensure safetyagainst the propagation of fire or thermal overload of live parts coming intocontact with them.
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
49/66
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
50/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II C/
=,A,C
:2*3/$+*/0 Display: The meter shall have an LCD display, comprising 8 segments and
including 2 decimals. The meter display shall be LCD with good contrast andwide viewing angle for easy meter readout. The display image area shall be
easily readable from a distance of approximately 1 meter. It should have awide operating temperature range (industrial grade) and a lifetime of atleast 15 years. The display shall have 8 digits for the cumulative energy,with digit height of 7.5-10 mm. The cumulative readout will be of whole kWhonly, including leading zeros, and shall be the default display at meter powerup. Every numerical element of an electronic display shall be able to show allthe numbers from zero to nine.
General requirements:o Data displayed shall be programmable;o Auto scrolling shall be used for changing displayed data;o Displayed data time duration shall be programmable;o
Displayed data programmable parameters should be in destinedconfiguration file;o Energy Data;o Total kWh tariff;o Peak Demand KW;o Current tariff number;o Quadrant indication;o The status of relay;o Monthly value accompanied by its respective date and time;o Displayed formats: kWh shall have a 8 digits display;o Date &Time: DD/MM/YY 24 h;o High resolution display mode;o Phases existence/non existence;o Phases sequence order;o Negative consumption flag (the flag shall be extinguished after
reading);o Failure indication and code (if any);o Tamper.
Verification LED: the meter shall be equipped with a test output device thatis accessible from the front in the form of a flashing LED in proportion to themeter constant to test accuracy of the meter on site.
Clock and Calendar: The microprocessor-based meter shall have a built-inclock and calendar having an accuracy of at least 0.5 seconds per day inaccordance with IEC 62052-21 / 62054-21, without the assistance of an
external time-synchronizing pulse. The date and time shall be displayed ondemand. The clock shall be synchronized by time signals received throughthe local or remote communication interface and upon national standard.
Sealed terminal cover: according to the Distribution Code the wholemetering system must be sealed to prevent illegal accesses. The cover shallbe made of plastic and fitted in such way that the internal parts of the meterare accessible only after breaking the meter cover seals.
Meter cover seals: At least one visible seal has to be provided in such a waythat the internal parts of the meter are accessible only after breaking theseal(s).
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
51/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II C:
Meter terminal seals: At least one visible seal have to be provided and noaccess to the terminals shall be possible without breaking the seal(s) of theterminal cover(s).
=,A,E
@+92$4+'$4 /$( 0/H')% Smart meter dimensions shall be such that it can be placed inside the
current meter premise. Net weight of a smart meter shall be up to 1.5kg. Its preferable that the installation triangle is according to the DIN reference.
=,A,F
?'$$2*%+'$ (+/G&/9 /$( %2&9+$/0 9/&T+$G4 Each meter shall be clearly marked with the connection diagram, preferably
shall be placed on the meter or cover of the terminal strap of the meter.
=,A,D
>/%%2&H The meter shall also be provided with lithium battery as a backup. Maintain clock and calendar and anti tampering features of the meters.
Battery charge condition (meter should indicate the battery status anddisplay it on LCD 6 month before complete discharge also battery statusshould be readable by meter read).
=,A,"3
Record short power cut N 2,3,4,etc
Internal memory
Register in non-volatile memory kW, kWh, V, I Required
Register in non-volatile memory Events/Alerts Required
Time storage Days 60
Communications
Meter with Detachable RS-485 Required/Not
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
55/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II CI
Functionalities
SpecificationsUnits Data Confirmed
ValueCommunications Module Required
Meter with integrated 2G/3GModule
Required/NotRequired
Meter with integrated Fiber
Optic Module
Required/Not
RequiredCommunication Interfaces
for Local Reading
Optical interface acc. To IEC62056-21
bps 1200-9600
RMR interface Serial interfaceacc. to IEC62056-21 to module
bps 1200-9600
For Meters with Modularcommunication:Modular communicationinterface allowing the exchangeof communication units without
breaking the calibration seal.
Required
Multi-channel communicationSimultaneous and independentcommunication via optical andelectrical interfaces.
Required
Interoperability
Meter to Concentrator Required
Meter to MDMS Required
Security Features
3 Access levels Required
Meters and MDMS Encrypted Required
Firmware Update
Local and Remote update Required
Load Profiling
Number of channels of remotelyconfigurable load profile datathat can be captured atprogrammable intervals.
Number !8
Programmable intervals minutes Up to 15min
Load profile storage capacity values !4 months withsamples every 30
minTime of Use
Active Energy Tariffs 4
Maximum Demand Required
Integrated Disconnect/ Reconnect Switch
Reference Current In A 1-5
Maximum Switching current Imax
A 2xIn
Maximum overload current A 120/150
Short Circuit current < 10 ms
Switching cycles Number 10000
Maximum Switching Power kVA 27
Customers manualdisconnection
Yes/No
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
56/66
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
57/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II CL
Functionalities
SpecificationsUnits Data Confirmed
ValueMetrology
Active energy IEC 62053-21 Class Class 0.5 or 0.2
Reactive energy IEC 62053-23 Class Class 1
Active Power kW Required
Active Energy kWh Required
Reactive Power kVAr Required
Reactive Energy kVArh Required
Four-Quadrant Metering IV Required
Instant value of Voltage RequiredInstant value of Current Required
Current
Minimum Base Current lbaccording to IEC
A 15
Maximum current Imaxaccording to IEC
A 2xIn
Starting current according toIEC
%In 0.2%
Short time overcurrent A !30 Imax
Voltage
Standard reference Voltage Un(IEC 60038)
V 57,7/100V240/415V
Operation range %Un 70%-120%
Voltage failure bridging time s 0.5
Voltage restoration Function
standby after
s #5
Calibration interval Years !4
Frequency
Nominal frequency Hz 50
Extended operating frequencyrange
% 2
Environmental
Temperature range (limitoperation range) for inside ofpremises installed meters
!C -25!C to +55!C
Temperature range (limitoperation range) for installed
meters outside of premises
!C -40!C to +70!C
Relative humidity as per IEC62052-11
% 5-95
Protection class according toIEC 60529
IP53
Terminal block !C 960!C 15!C
Terminal cover and meter case 650!C 10!C
Duration of application s 30s 1s
Mechanical
Designed wire connections 3-phase 3-phase 4-wire
Lifetime years !15 years
Display
Dimensions: Digitize in value Required
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
58/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II FJ
Functionalities
SpecificationsUnits Data Confirmed
ValueField "8mm
Display of values:Programmable display sequence
Required
LCD (Dimensions) 8 segments, 8
digits
Required
Material Liquid crystaldisplay
Required
Clock and calendar Accuracy(IEC 62052/54-21)
Delay +/- 0.5 sec/ day
Persian calendar including Leap year, Daylight saving
time, summerand winter clockand tariffs fornormal days,weekend, and
public holidays.
Required
Sealed terminal cover Required
Opening terminal cover
sensor
Required
Meter Cover seals At least onevisible seal hasto be providedin such a way
that the internalparts of themeter are
accessible onlyafter breakingthe seal(s).
Required
Meter Terminal seals At least one
visible sealhave to beprovided and noaccess to theterminals shallbe possiblewithoutbreaking theseal(s) of theterminalcover(s).
Required
Power consumption
In the voltage circuit with
power supply connected
W
VA
#$
#%
Current circuit at basic currentlb
VA #4
Internal Power Consumption
Max. ValueNote: value for powerconsumption is for meterwithout communication modem.
VA 10VA (2W) forvoltage circuit each
phase4VA for phasecurrent circuit
Electromagnetic Compatibility
Contact discharge kV 8
Air discharge kV 15
Current and voltage circuits kV 4
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
59/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II F#
Functionalities
SpecificationsUnits Data Confirmed
ValueAuxiliary circuits >40V kV 2
Insulation Strength
Insulation Strength at 50Hz for1 min
kV 4
Cut-Off Element
Control Relay Single-polevoltage-freelatching relay;maximum loadrating is 250V,5A; fullyisolated.
Required
Load Disconnect Contactor Required
Dimensions and layout
Height mm max 300
Width mm max 200
Depth mm max 100
Net weight kg
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
60/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II F/
A
12*3$+*/0 852*+6+*/%+'$4 6'& :2%2& >'B24
A,"
8*'52
This specification covers the design, manufacturing and testing of a Single andThree Phase Energy Meter Boxes made from Polycarbonate grade A. The Box maycontain one (1) to four (4) meters.
A,- 7550+*/N02 Z'&94
The equipment covered by this specification shall conform to the requirementsstated in latest editions of relevant IEC Standards and shall conform to theregulations of local statutory authorities.
IEC 60529 Degrees of protection provided by enclosures;
IEC 62262 Degrees of protection by enclosures for electrical equipmentagainst external mechanical impacts (IK code);
IEC 85 Thermal evaluation and classification of electrical insulation;
IEC 707 Methods of test for the determination of the flammability of solidelectrical insulating materials when exposed to an igniting;
IEC 695-2 Resistance to heat and fire;
IEC 60439-1 Double insulation;
IEC 947 Low voltage Circuit Breakers;
ISO 14782 Plastics Determination of haze transparent materials.
In case any conflict between standards and this specification, this specification shall
govern.
A,;
12*3$+*/0 &2V)+&292$%4The electrical and mechanical characteristics, materials used, dimensions and othertechnical specifications are detailed below.
A,;,"
R02*%&+*/0 *3/&/*%2&+4%+*4
The following electrical characteristics shall apply:
Dielectric strength up to 5kV;
Rated voltage: 400V;
Frequency: 50Hz;
Type of connection: Single-phase system.
A,;,-
:/%2&+/04
Base and cover of meter boxes are built in polycarbonate transparent grade A, with
additives for U.V. rays and a minimum thickness of 1.5 mm. The material must be
resistant to heat and fire, also be self-extinguishing, according to standard IEC 707
and 695-2-1/0.w.
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
61/66
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
62/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II FA
meters. It should provide a set of three screws No 12 x 1.27 mm galvanized for
each meter box.
Note: The cabinet builder should be addressed to the Laboratory Meter Company
for the respective drilling templates.
?";";"B
I3(:&.2 */1 :2*3+/D 12Z+,2
a) The design of the lid and base to prevent the contour opening once closed
and secured by a cover. The cover in closed position should be overlapped
on base such that direct entry of screwdriver, tool or film is not possible.
b) The cover shall be provided with semi circular / circular gasket of sufficient
size to completely fit to the base. The gasket should be made out of good
quality neoprene rubber.
c) The cover of Transparent Polycarbonate Material shall have lighttransmission of 80% or more (to be tested as per 14782:1999). This will
facilitate photometer reading as well as transparency. This will facilitate
photometer reading as well as transparency.
d) The locking screw should be of sheet metal with triangular head 5 mm per
side. The end cap of the box should have a sealed system, so that may be
evident in the same access by unauthorized persons.
e) The meter box must have the lead seal so that the meter box cannot be
opened without break the seal.
?";";"E
7.('2,'+(/:
a) The Box may include circuit breakers as per the instructions. In case the box
shall include circuit breakers, the same shall include a 63A/2P Circuit
Breaker for each of the meter units.
b) Boxes containing 4 meters shall also have a general circuit breaker of no
less than 220A/2P to protect the entire installation.
?";";"G
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
63/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II FC
General arrangement drawing of the meters box;
Terminal Block dimensional drawing (if any);
Mounting arrangement drawings;
General description of the Box and all components with makes and technical
requirement; Type Test Certificates;
Experience List;
Manufacturing schedule and test schedule.
b) Drawings/documents to be submitted after the award of the contract:
Technical Parameters;
General Arrangement drawings;
Terminal block Dimensional drawings (if any);
Circuit breakers technical parameters;
Mounting arrangement drawing;
Transport/Shipping dimension drawing;
QA &QC Plan;
Routine, Acceptance and Type Test;
Certificates;
Certification on encryption, database security and reliability.
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
64/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II FF
A,;,A
RB/95024 '6 N'B24
?";"?"$
NW*)532 (4 [(W2: I(/:'.&,'+(/ F+)2/:+(/:
One-Meter Box
Four Meters Box
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
65/66
AF-MERCADOS EMI
Tech. Spec. of AMI for Vietnam Final Report Volume II FI
?";"?"!
NW*)532 (4 =(&/'+/D 73*'2
?";"?";
NW*)532 (4 )(&/'+/D '952:
Installations possible to perform on either masonry or wall either fixed to poles orbuilt in into walls or pillars.
-
8/10/2019 Pages From AMI_Final Report_Vol II_Technical Specifications_vF(2)
66/66
AF-MERCADOS EMI
?";"?"#
NW*)532 (4 >2,&.+'9 >,.26