P-CIMSCADA/HMI
Version 7.70 SP4 HF10
Release Notes
Revision: August 2013
-
8/16/2019 p Cim770sp4 Rln
2/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes
Copyright
The information in this document is subject to change without prior notice and doesnot represent a commitment on the part of AFCON Control and Automation Ltd.,AFCON Software and Electronics Division.
No part of this document may be used or reproduced in any manner whatsoeverwithout written permission from AFCON Control and Automation Ltd., AFCONSoftware and Electronics Division.
The software described in this document is furnished under a license agreement ora non-disclosure agreement.
The software may be used or copied only in accordance with the terms of theagreement. It is against the law to copy this software on any other medium for anypurpose other than the purchaser's personal use.
Copyright 2013 AFCON Control and Automation Ltd., AFCON Software andElectronics Division.
All rights reserved.
Pulse logos are registered trademarks of AFCON Control and Automation Ltd.,AFCON Software and Electronics Division.
Windows is a registered trademark of Microsoft Corporation in the United Statesand other countries.
-
8/16/2019 p Cim770sp4 Rln
3/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 3
Table of Contents
P-CIM Version 7.70 SP4 HF10 ..........................................................................................4
About the P-CIM Version 7.70 SP4 HF10 .............................................................4
Requirements .........................................................................................................5
Software Requirements ...................................................................................5
Minimum Hardware Requirements.................................................................5
Installing P-CIM 7.70 SP4 HF10............................................................................6
P-CIM 7.70 SP4 HF10 New Features...................................................................7
P-CIM 7.70 SP4 HF10 - Solved Issues................................................................12
P-CIM 7.70 SP4 HF10 Known Issues .................................................................18
http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/http://p-cim%207.70%20sp4%20rln.pdf/
-
8/16/2019 p Cim770sp4 Rln
4/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 4
P-CIM Version 7.70 SP4 HF10
About the P-CIM Version 7.70 SP4 HF10
The Hot Fix(HF) for P-CIM 7.70 Service Pack 4 HF10 is a software packagecontaining fixes and corrections for problems that were not answered in ServicePack 4 or previous service packs.
In this Hot Fix 10, problems that were reported to us by our customers as criticalwere assigned the highest priority, examined and fixed quickly and accurately.These solutions were provided to our customers and are presented in this ReleaseNotes document.
Below is a list detailing the solved issues included in the Hot Fix as well as new
features and known issues.
-
8/16/2019 p Cim770sp4 Rln
5/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 5
Requirements
Software Requirements
P-CIM version 7.70 Service Pack 4 HF10 runs on Windows 2000, Windows XP
Professional (SP1/SP2) and Windows 2003 Server.
Minimum Hardware Requirements
Intel Pentium 4
512 MB RAM
40 GB free disk space for initial installation
VGA display card with 128 MB of memory
Parallel printer port or USB
Network adapter and fixed IP address for network applications
Microsoft IIS for P-CIM Web server (for P-CIM Web and/or Supreme ReportWeb portal).
Microsoft Access or SQL server (for P-CIM database and/or Supreme Reportdatabase) Optional.
-
8/16/2019 p Cim770sp4 Rln
6/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 6
Installing P-CIM 7.70 SP4 HF10
NOTE This Hot Fix can only be installed on computers running P-CIM 7.70 ServicePack 4.
P-CIM 7.70 Service Pack 4 Hot Fix 10 is available from the Afcon DVD and bydownloading from the Afcon web site at: (www.afcon-inc.com).
NOTE Make sure that P-CIM 7.70 Service Pack 4 is not running before replacingthe files.
It is recommended to restart the computer before installing the Service Pack 4 HotFix 10.
1 The P-CIM 7.70 Service Pack 4 Hot Fix 10 files are compressed in a .ZIP file.Copy the compressed file to the P-CIM root directory, for example:C\PCIM32
and extract the files into the P-CIM 7.70 installation folder.
2 A folder named Rev contains the Dynamic Trend templates and is included inthe compressed file. Replace the files of existing projects only with thecontents of the Rev folder. For example: C:\PCIM32\Demo.
3 When prompted, click Yes to replace the existing files with the new ones.
http://www.afcon-inc.com/http://www.afcon-inc.com/
-
8/16/2019 p Cim770sp4 Rln
7/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 7
P-CIM 7.70 SP4 HF10 New Features
PQR# List Animation Window
6232, 6195 List Animation Window size is controllable
The List Animation Window is now resizable. StandardWindows Maximize, Minimize, and Restore commandsare available, as well as click-and-drag corner resizing.
PQR# INI File Editor
6230 Find & Replace functions added to INI File Editor
In the INI File Editor, instances of a string may be
searched and replaced as needed. Two levels of Find &Replace are now available:
Find button - Enables find and replace of strings inthe currently selected token.
Replace button - Enables find and replace of stringsin the currently open file.
PQR# Database Editor
6202 Overwriting existing blocks when importing ASC filesIn the Database Editor, an Overwrite Existing Blocksoption is now available when importing data in ASCII(*.ASC), TSV, or OLEDB format.
Enabling this option allows the overwriting of identicalblocks, in addition to adding new blocks, wheneverimporting data to the P-CIM Database.
PQR# Basic Server>Trace Window
6191 Basic Server>Trace Window size is controllableThe Trace Window (for script debugging) is nowresizable. Standard Windows Maximize, Minimize, andRestore commands are available, as well as click-and-drag corner resizing.
PQR# Progate Editor
6172 Skip First Trigger Data option added
The Skip First Trigger Data option was added to theProgate Editor’s Group Properties dialog box. If this
option is selected, the first instance of trigger conditionswill not cause the data exchange to begin.
-
8/16/2019 p Cim770sp4 Rln
8/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 8
PQR# Database Server
5958 New $lastalarm Variables
A new set of 10 $lastalarm variables —$lastalarm_zn1, $lastalarm_zn2, $lastalarm_zn3,..., $lastalarm_zn10 — were added.
The $lastalarm variable returns only the alarm lastreceived by P-CIM from the entire monitored facility.This new set of variables is useful when your P-CIMapplication is receiving alarms from multiple zones (setup according to your monitored facility’s departmentalorganization). Use these variables to display the lastalarm that occurred in each individual zone (up to 10different zones may be specified).
NOTE $lastalarm is still available for use.
PQR# Hot Redundancy Mode
5954 New $IsPassiveRunning Variable
A new variable, $IsPassiveRunning, was added. Thisvariable enables users to know if the passive server in aHot Redundancy configuration is running.
PQR# P-CIM Scheduler
5947 Disabling a Scheduled ActionTo disable a scheduled action so that it does not occur atits scheduled time, you have to enable a parameter inthe current year’s schedule configuration file — for 2009,this file is named psch2009.ini and is located in theproject root folder.
1 In the psch[+year].ini file, find theDisableMidnight token and change its value to 1 (TRUE).
2 Then, in the Scheduler Editor, change the time of theaction to 0:00:00.
To re-enable the scheduled action, change its scheduledtime in the Scheduler Editor to any other time.
If you want to run the action at 0:00:00, then enter the psch[+year].ini file and change the DisableMidnight token’s value to 0 (FALSE).
-
8/16/2019 p Cim770sp4 Rln
9/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 9
PQR# Advanced Alarm Handler
5920 Triggering Alarm Action By Double-Click Only
An option was added to the Advanced Alarm Handlerwhich enables the triggering of an action only when theuser double-clicks on an alarm entry. Users may set thisoption in the pcimuser.ini configuration file, in the[AlarmWinDBF] section’s UseOnDClickOnly parameter.
1 = Command runs only upon double-click of alarmentry.
0 = Command runs either upon double-click of alarmentry or upon standard Acknowledge or Clearprocedure.
PQR# Operator Workstation
5982 Smart Information support
In the Operator Workstation, it is now possible to displaySmart Information - refreshed real-time data andhistorical trend graphs for advised items that receivedata from analog value, digital value, Boolean, andcalculation blocks.
The Smart Information is accessed by right-clicking on
the relevant object(s). The information displayedincludes:
Symbol ID, Action UP item, Action DOWN item, I/O Text,Visibility, Height, Width, Horizontal and Vertical Position,Horizontal and Vertical Slider, Orientation, Fluid Fill, FillColor, Text Color, and Line Color
-
8/16/2019 p Cim770sp4 Rln
10/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 10
PQR# Operator Workstation
5915 Creating a Customized Context (Right-Click) Menu
It is now possible to design and add a customized menuunder the Historical Trend context (right-click) menu inthe Operator Workstation. Users may set this option inthe pcimuser.ini configuration file, in the[AdditionalCommandMenu] section. The format foradding the commands is as follows:
X1=Y1X2=Y2X3=Y3
In the above structure, the tokens X1, X2, X3, and so on,represent the labels in the menu, depending on the
number of required commands. The values Y1, Y2, Y3,and so on represent the commands to execute.
For example:
[AdditionalCommandMenu]Report=RepData dbf rep1Acknowledge=Set |!AV1.Ack 1Advanced Alarm Handler=C:\Pcim32\ALMH.EXE
The customized menu appears under the Historical
Trend menu.
It is possible to hide the Historical Trend menucommands, and display only the customized menu, if noblocks are selected. To do this, go to the pcimuser.inifile’s [PcimConf] section and set the “MuteHistPopUpMenu“ token to 1.
PQR# NICEVISION Player
5804 Option to Hide Minimize Button
Users can now remove the Minimize button from theNICEVision Player window. Users may set this option inthe pcimuser.ini configuration file, in the[PcimConf ]section’s NVPlayer_DisableMinimize parameter.
1 = Disable the Minimize button
0 = Hide the Minimize button.
-
8/16/2019 p Cim770sp4 Rln
11/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 11
PQR# P-CIM Hot Redundancy
4621 Collecting Historical Data and Daily Log on PassiveServer
Two new switches were added to the P-CIM application’spfwredun.ini file.
EnableHisOnPassiveServer -
1 = Identical historical data (HIS file) is collectedon both the active and passive servers (defaultsetting).
0 = The historical data is not copied to the passiveserver.
EnableLogOnPassiveServer -
1 = Identical message entries are copied to DailyLog files on both the active and passive servers(default setting).
0 = Messages are not collected in Daily Log fileson the passive server.
-
8/16/2019 p Cim770sp4 Rln
12/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 12
P-CIM 7.70 SP4 HF10 - Solved Issues
PQR# Operator Workstation
6764 Listbox Commands
Listbox commands were not executed when working inthe P-CIM Windows Authentication mode.
In the P-CIM Authentication mode the feature workedproperly.
This problem was fixed.
PQR# Operator Workstation
6399 Idle Action mistakes
There were Idle action mistakes in about 30% of theconfigured number of seconds
For example:
If configured to 10 seconds the action was set after 13seconds.
The Time mistake was fixed.
-
8/16/2019 p Cim770sp4 Rln
13/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 13
PQR# Operator Workstation
6125 Group and Alias caching
A caching mechanism now allows clients to maintainidentical, updated versions of a display located on the P-CIM Server. When enabled, the display’s group file,[displayname].grp, is updated on all clients that accessthat display so that they match the same file on theserver. This ensures synchronization of data between allclients working on the same display.
The following token was added to the project’s pcimuser.ini file:
Token: [PcimConf]
String = WriteAliasToCacheAlias
Value = 0 - Caching is enabled - group file on P-CIMclient is always updated to match the group file on theP-CIM Server. This is the default value.1 - Caching is disabled - each client may maintain adifferent group file for the display.
PQR# P-CIM Text File Server
6573 A Client can now write to the Server alias file
The text file Server automatically wrote to its ownPfwalias.exe file located in its
Util or cache folder, and not to the Server alias file.
Now, the text file Server can write to the Server aliasfile.
PQR# OPC Browser
6535 The OPC Browser immediately closes when P-CIM
starts its shut down process.
The OPC Browser had a 10 seconds closing delay after P-CIM was shut down. The issue is fixed and now the OPCBrowser closes immediately when P-CIM starts its shutdown process.
-
8/16/2019 p Cim770sp4 Rln
14/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 14
PQR# OPC Browser
6109 The OPC Browser supports browsing items whenworking in flat project structure.
The OPC Browser was not able to display project filesthat were saved under the project’s folder and not underthe sub folders.
Now, the OPC Browser can display project files that aresaved under the project’s folder.
PQR# OPC Browser
5833 The OPC Browser and Kepware Client now showthe same/right value
The OPC Browser displayed the wrong switch Link statevalue while the Kepware client showed the right value.PCIM did not start the SNMP service and the clientshowed a different value than that of the OPC Browserand the application.
Now the OPC Browser and the Client show the samestatus values and so does the application.
PQR# P-CIM Redundancy
6452 Secondary Server
The Secondary Server did not take control when theActive server was changed in the redundancyconfiguration.
This problem was fixed.
PQR# P-CIM Database Server
6251 Long data synchronization time after P-CIM Clientreconnects to DBSR
Fixed a problem where, after P-CIM Client reconnectedto the P-CIM Database Server, the Client displayedincorrect data for a long period before it starteddisplaying correct values.
-
8/16/2019 p Cim770sp4 Rln
15/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 15
PQR# PCIM Database Server
6211 P-CIM Client Cannot Connect to More than Nine P-CIMStations
In a P-CIM Server-Client configuration, the clientsucceeds in connecting to only nine P-CIM stations.Attempts to connect to the 10th station or more areunsuccessful.
This problem is now fixed.
PQR# P-CIM Database Server
6131 New $CWeek Variable Added
Previously, the $CWeek variable always incremented on
Sunday (value =“0”), instead of Monday.
The PcimUser.ini file now includes the new parameter:
Section: [PcimDbsr]
Token: NewWeekOnMonday
Values: 0 Week begins on Sunday
1 Week begins on Monday
PQR# Historical Trend
6234 Historical Trend Graph did not display all historical data
Fixed a problem where the historical trend graph did notshow updated historical data, even though the relevantHIS file was collecting historical data.
PQR# Advanced Alarm Handler
6215 Only Functional Branch in Advanced Alarm HandlerSelected After TSV File Import
Following import of a database in TSV file format, onlythe Functional branch is selected in the Advanced AlarmHandler, regardless of whether the block is also assignedto the Location branch. This problem is now fixed.
-
8/16/2019 p Cim770sp4 Rln
16/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 16
PQR# Supreme Reports
6139 Supreme Report Malfunctions Due to Errors in Logger
Errors in Supreme Report's Logger, such as incorrectdata path, cause Supreme Report to stop functioningduring report generation.
This problem is now fixed.
PQR# P-CIM Network /Web
6097 The string type value is now displayed in the P-CIMClient
The String type value is now supported in a P-CIMnetwork using a Modbus driver. The Time Register
address string can be displayed on the P-CIM Client orthe P-CIM Web Client.
The PcimUser.INI [PcimDBSR]SupportTextOverNetwork=1 switch is used toovercome the problem.
PQR# P-CIM Communication Setup
6081 P-CIM Communication Ports 126-128 are reservedfor internal use.
Ports 126, 127, and 128 are reserved for internal use byP-CIM. P-CIM prevents user assignment of these ports.The P-CIM Communication Setup does not allow users todefine these ports in their driver configurations.
PQR# P-CIM History OLEDB Collector
6065 The OLEDB Collector module worked only whenthe Regional Settings was English.
Records of collected data that included values with
decimals are not written to the database. This issueoccurred in regions where the decimal separator is acomma instead of a period, i.e., Spanish, Russian, etc.).
The issue is fixed and records of collected data arewritten to the database when the Regional Settings is setto other languages other than English.
-
8/16/2019 p Cim770sp4 Rln
17/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 17
PQR# P-CIM Web - Supreme Report
4573 Error closing report from Adobe Reader v7.05 MEedition
When closing the P-CIM Web portal while a report isopen in Adobe Reader v7.05 ME edition, a bad sector isreferenced in the computer memory causing an error.This problem has been fixed.
PQR# Supreme Report Runtime
4527 Incorrect login information caused Supreme Report tostop responding
When trying to open Supreme Report in runtime withincorrect login information (user name, password),Supreme Report stopped running and could only becleared from memory by ending the drt.exe process inthe Windows Task Manager. This problem has beenfixed.
-
8/16/2019 p Cim770sp4 Rln
18/19
P-CIM Ver. 7.70 SP4 HF10 Release Notes 18
P-CIM 7.70 SP4 HF10 Known Issues
PQR# P-CIM Database Import
6215 After importing a Database, blocks which wereconfigured to be attached to both the Functional andLocation trees are attached to the Functional tree only.
PQR# P-CIM Supreme Report
6218 Supreme Report did not record string type tags using theP-CIM native driver with the Supreme Report history.
PQR# P-CIM Project Pack settings
6219 The Project Pack settings were not saved in the Backupsettings. After the Project Backup and Restore procedurethe settings were lost.
PQR# P-CIM SEK
6344 Viewer Only License
In No SEK stations with Viewer Only settings(Pcim.ini,[PWEM],ViewerOnly=1) or stations with
Viewer Only keys, the writing commands:
Set
Inc
Dec
Inv
will be blocked.
These Autoaction activities are always performedwithout being dependent on the Vieweronly mode.
PQR# Updating P-CIM License
6425 When uploading a PUF file and the Extra drivers optionis added, the option is not saved on the SEK.
PQR# Digital Value Block
6634 The Digital Value block value address, including PLC and
ValueOK dot field, (for example, 1:1:40888.valueOK)always returns 0.
-
8/16/2019 p Cim770sp4 Rln
19/19
PQR# P-CIM Database Server
6711 Alarm Wait
The Alarms were generated before an Alarm Wait time
period was finished.
PQR# P-CIM Communication Setup
6081 P-CIM Communication Ports 126-128 Reserved forInternal Use
Ports 126, 127, and 128 are reserved for internal use byP-CIM. However, instead of blocking user assignment ofthese ports, the P-CIM Communication Setup allowsusers to define these ports in their driver configurationsanyway, thereby causing database malfunction.
PQR# P-CIM Startup
4682 P-CIM starts up twice on Windows 2000 Server systems
On computers running Windows 2000 Server, twoinstances of P-CIM modules were starting up andrunning at the same time. This caused inconsistencies indata collection and historical data presentation.
PQR# Operator Workstation
2202 Selecting Time Format HH:MM:SSTo display the time in format HH:MM or HH:MM:SS (withleading zero when applicable), set the Text Animationproperties as follows:
Use Format - Advanced
Mask Type - Simple
Category - Short Time (for HH:MM) orLong Time (for HH:MM:SS)