Overview of Substation

download Overview of Substation

of 38

Transcript of Overview of Substation

  • 8/3/2019 Overview of Substation

    1/38

  • 8/3/2019 Overview of Substation

    2/38

    THE ASSEMBLY OF APPARATUS USED TO CHANGE SOMECHARACTERISTICS (I.E. VOLTAGE A.C TO D.C., FREQUENCY, POWER

    FACTOR) OF ELECTRIC SUPPLY IS CALLED A SUBSTATION

    SUBSTATION

    GENERATING TRANSMISSION DISTRIBUTION

  • 8/3/2019 Overview of Substation

    3/38

  • 8/3/2019 Overview of Substation

    4/38

  • 8/3/2019 Overview of Substation

    5/38

    A Transformer is a static piece of apparatus by

    means of which electric power in one circuit is

    transformed into electric power of the same frequencyin another circuit.

  • 8/3/2019 Overview of Substation

    6/38

  • 8/3/2019 Overview of Substation

    7/38

    Circuit breakers are mechanical devices

    designed to close or open contact members, thus

    closing or opening of an electrical circuit under

    normal and abnormal conditions.

    There are two methods of arc extinction in circuit breakers. High resistance method

    Low resistance or Current zero interruption

    SF6 Circuit Breaker :

    PNEUMATIC mechanism is used

    Short circuit earthing current is 40KA

    Operating impulse with stand voltage is 1425KV

    Operating sequence is 0 0.3 sec CO - 3 min CO

    Air pressure is 31.5 bar

    SF6 GAS pressure is 7.0 bar

  • 8/3/2019 Overview of Substation

    8/38

  • 8/3/2019 Overview of Substation

    9/38

    Isolators are disconnecting switches which can be

    used for disconnecting a circuit under no currentcondition. They are generally installed along with the circuit breaker. A Isolator, can

    be opened after the circuit breaker.

    There are different types of isolators Now let us discuss about two types

    of isolators which are used in this sub-station.

  • 8/3/2019 Overview of Substation

    10/38

    Lightning arresters are equipments

    which are connected between the

    conductor and ground, to discharge the

    excessive voltages to the ground.

    It operates on the fact that a thin film of

    aluminium hydroxide is deposited on the

    aluminium plates immersed in electrolyte acts as

    a high resistance to a low voltage but a low

    resistance to a voltage above a critical value.

  • 8/3/2019 Overview of Substation

    11/38

    Current transformers used in conjunction with

    ammeter, over current relays, etc. which step downs the current

    from high level to low value.

    Core number 1 2 34 5

    Core operation Bus-bar

    protection

    Spare one Used for

    metering

    Main II

    distance

    protection

    Main I

    distance

    protection

    Primary turns 1 1 1 1 1

    Secondary turns 2000 1000 2000 1000 500

    Rated primary

    current 2000A 2000A 2000A 2000A 2000A

    Rated

    secondary

    current

    1A 1A 1A 1A 1A

    Current output --- --- 40VA --- ---

    Accuracy class PS PS 0.5 PS PS

  • 8/3/2019 Overview of Substation

    12/38

    Primary terminal

    Secondary terminal box

    Core container

    Expansion chamber

    Oil level gauge

    Porcelain insulator

    Core

  • 8/3/2019 Overview of Substation

    13/38

    Capacitor Voltage Transformers are used for

    line voltmeters, synchroscopes, protective relays,

    etc. which step downs the voltage from high level to

    low value.

    The capacitors connected in series act likepotential dividers provided the current taken by

    the burden is negligible compared with the current

    passing through the series connected capacitors.

    Core 1: rating is 400kv/3/110/3 used for Main Idistance protection

    Core 2: rating is 400kv/3/110/3 used for Main IIdistance protection

    Core 3: rating is 400kv/3/110/3 used formetering.

  • 8/3/2019 Overview of Substation

    14/38

    Type of

    cooling

    ONAN

    Rated

    power

    63MVAR

    Rated

    voltage

    420KV

    Rated

    current

    82A

    phases 3

    frequency 50Hz

    Impedance 2800Ohm/Ph

    Reactor is an inductive reactance in comparisonto its resistance and is used for limiting short circuit during

    fault conditions.

    Reactors are used to reduce the magnitude ofvoltage disturbances caused by short circuits.

  • 8/3/2019 Overview of Substation

    15/38

    The PLCC (Power line

    carrier communication) equipment

    contains wave-trap, tuning unit,coupling capacitor etc.

    The PLCC is mainly

    used for telecommunication, tele-

    portection and tele-monitoring

    between electrical substation

    through power lines at high voltages

    such as 110 kV, 220 kV, 400 kV.

  • 8/3/2019 Overview of Substation

    16/38

    The supply available in nature is alternating which is

    not stored in any form. If the AC supply failed then there is no

    supply to relay coils .This needs availability of DC supply.

    Boost charging:

    When there is a sudden drop in the voltage/also when

    there is considerable fall in voltage the charger will

    automatically switch on to boost charging mode from float

    charging mode.

    Float charging:This is a constant charging mode means these

    batteries will be constantly being charged when there is no

    load it takes less current. And these cells have to be charged

    continuously so that they will not get discharged. As these has

    to supply DC supply when there is a fail in AC supply.

  • 8/3/2019 Overview of Substation

    17/38

    In generating stations, receiving stations and sub-

    stations, the control and relaying equipment is installed in

    control-rooms.

    The panels are divided on the bases of type of the operation it done they are:

    Panel with Mimic Diagram.

    Relay Panel. The type and number of relays depends on requirements.

    Instrument pane. Indicating ammeter, voltmeter, energy meter, their

    selector switches, recording instruments, if any, fitted on instrument panel.

    Synchronizing panel.

    Automatic voltage regulator panel

  • 8/3/2019 Overview of Substation

    18/38

  • 8/3/2019 Overview of Substation

    19/38

  • 8/3/2019 Overview of Substation

    20/38

  • 8/3/2019 Overview of Substation

    21/38

    The Transformer is the main equipment which has to be

    protected mainly in the power system. They are different faults in it,

    these areTHROUGH FAULTS

    INTERNAL FAULTS

    EXTERNAL FAULTS

    INCIPIENT FAULTS

    Incipient faults bellow oil level resulting

    in decomposition of oil, faults between

    phase to phase and ground.

    1. Buchholz relay sounds alarm (Gas

    actuated relay).

    2. Percentage differential protection.

    Saturation of magnetic circuit 1. Over fluxing protection

    2.Over voltage protection

    Earth faults Differential protection.

    Though faults Graded time lag over current relay.

    Overloads Thermal overload relays.

    High voltage surges due to lightning 1. Surge arresters

    2. R-C surge suppressors

  • 8/3/2019 Overview of Substation

    22/38

    Buchholzs relay is gas actuated relay used for

    protecting oil immersed transformer against all types of

    internal faults.

    Buchholz relay is provide for transformers above 500kVA rating.

    Which is fitted in pipe leading to the conservator.

    The minimum operating time of the equipment is 0.2sec.

    Which is inclined in between 10

    0

    to 110

    with the transformer tank. Mercury switch is immersed in it for closing alarm switch.

    It gives alarm when oil level reduced to certain level due to

    internal faults.

  • 8/3/2019 Overview of Substation

    23/38

  • 8/3/2019 Overview of Substation

    24/38

    The DIFFERENT IAL PROTECTION Is used for

    power transformers is based on MERZ-PRICE circulating

    current principle. It responds to vector difference between

    to similar electrical quantities.

    It provides protection against internal phase-to-phase and phase-to-

    earth faults.

    It generally generally used for transformers of rating exceeding 2MVA.

    Mostly the operation is carried out by current difference.

    The two basic requirements of differential relay connections must

    satisfy these are..

    It must not be operated for external or load faults

    It must operate for internal faults

  • 8/3/2019 Overview of Substation

    25/38

    R

    Y

    B

    R

    Y

    BY

    POWER TRANSFORMERC.T C.T

    PILOT WIRES

    TRIP

    COIL

    TRIP

    COIL

    KICK

    FUSES

    RELAY

    OPERATING

    COIL

    For the transformer differential protection an ABB

    make RADSB relay which is fully digitalized numerical relay.

    This protective relay is intended for all types of autotransformers.

  • 8/3/2019 Overview of Substation

    26/38

    Earth Fault Relay connected in residual circuit of

    line CTs provide protection against the earth faults on the

    delta or unearthed star connected windings of the power

    transformers.

    It provide in

    parallel with thesecondaries of

    CTs of protected

    line.

    Operating

    current is 15%of rated winding

    current.

    For this

    protection the

    relay used is

    RADHD

    F-1F-2

    I1

    I2

    Stabilising

    resistor

    CTs

    Earth fault

    relay

    Neutral

    CT

  • 8/3/2019 Overview of Substation

    27/38

    Power transformers directly connected to alternators

    subjected to over excitation which are during start up or shut

    down operation.Over fluxing condition in a transformer can occur during

    system over voltage and / or under frequency conditions (V/F)

    For over fluxing protection the relay here used is ABB made

    RALK.

    When the power transformers are over excited

    the leakage flux increases and this results in heavy hysteresis

    and eddy current losses in non-laminated parts of

    transformer. This leads to temperature raise and causes

    insulation failure and hence flash over will occur.

    The main causes for over fluxing are.

  • 8/3/2019 Overview of Substation

    28/38

    The BUS-BAR in electric power stations and

    substations are the one of the most vital elements. The

    bus-bar protection needs special attention because of

    the following reasons.

    Faulty level at bus-bars is very high.

    The fault on the bus-bars would result in widespread supply

    interruption.

    The system stability is adversely affected by fault in bus

    zones.

  • 8/3/2019 Overview of Substation

    29/38

    Method Particulars

    Bus-protection by over current

    relays, of connected circuits.

    High-set instantaneous over current

    relays and earth fault relays, or

    definite time relays.

    Static protection Rapid reliable, no problems of CT

    structure

    Back-up protection Over current protection or distance

    protection.

    Over voltage protection Inverse overvoltage relays

    Surge voltage protection Surge arresters

  • 8/3/2019 Overview of Substation

    30/38

    The principle of operation is the current entering

    and leaving are compared continuously. It involves

    choosing of impedence high enough to stabilize therelay for high fault currents.

    For the busbar protection we are using ABB make RADSS which is

    fully digitalized numerical relay

    This is a high speed , sensitive moderately high impudence

    differential relay.

    Operating time for fault detection is 1-3 m.sec and for tripping 8-13

    msec.

  • 8/3/2019 Overview of Substation

    31/38

    The probability of faults occurrence on the

    overhead lines is much more due to their greater lengths

    and exposure to atmospheric conditions.

    The transmission lines have the following protection schemes.

    Distance protection

    Main I distance protection

    Main II distance protection

    Over voltage protection

    Stage I

    Stage II

    Auto reclosures

    Breaker falure relay

  • 8/3/2019 Overview of Substation

    32/38

    To detect excessive voltage rise on

    transmission lines, usually 400Kv- 800Kv systems. The relay

    would typically be time delayed to prevent unnecessary tripping

    for voltage rise of short duration. The relay can also be used forgenerator over voltage protection.

    For this protection an ABB make RXEG 21 is used

    Main features:

    Flash over protection. >= 97% for operation on over voltage.

    High over load capacity.

    Wide frequency response.

  • 8/3/2019 Overview of Substation

    33/38

    RELAY is an electrical device designed to initiateisolation of part of an electrical installation, or to operate

    an alarm signal, in the event of an abnormal condition or a

    fault.

    1. Circuit Breaker2. Relay

    3. Trip coil of C.B

    4. Trip circuit

    5. Battery

    6. Currenttransformer

    7. Potential

    transformer+ -

  • 8/3/2019 Overview of Substation

    34/38

    When fault occurs CT or PT step-down the corresponding

    parameter(I or V)

    This quantity is passed to the corresponding relay.

    Which produce the magnetic field to close the trip circuit.

    CT

    C.B

    B+ -

    R

  • 8/3/2019 Overview of Substation

    35/38

    After closing of the trip switch closed trip circuit is formed.

    Battery discharge the energy and magnetize the trip-coil

    of the C.B.

    Due to this circuit breaker is opened due to this supply isturned off.

    C.B

    B

    CT

    R

  • 8/3/2019 Overview of Substation

    36/38

    There are basically three types of relays these are..

    Static relays.

    Electromagnetic relays.

    Numerical relays.The Static Relay is a relay which incorporates solid statecomponent like transistors, diodes etc. for the measurement

    of comparison of electrical quantities.

    In Electromagnetic Relays, there are one or more coils,movable elements, contact system etc. The operation of

    such relay depends on whether the operating torque/force

    is greater than the restraining torque/force.

  • 8/3/2019 Overview of Substation

    37/38

    Operation of the Impedance Relay is independent ofthe phase angle between V and I. The operating characteristic

    is a circle with its center at the origin and hence the relay is

    non-directional

    Reactance relay measures V/I sin when ever thereactance measured by the relay is less than the set value

    the relay operates. The operating characteristic on R-X

    diagram.

    Mho relay is a directional impedance relay,also known as admittance relay. Its characteristics on R-X

    diagram is a circle whose circumference passes through

    the origin. This relay is inherently directional and it only

    operates for fault in the forward direction.

  • 8/3/2019 Overview of Substation

    38/38

    ?