Oregon Joint Use Violation Examples

21
Oregon Joint Use Oregon Joint Use Violation Examples Violation Examples Stump The Panel Stump The Panel

description

Oregon Joint Use Violation Examples. Stump The Panel. Question 1. Question 2. Question 3. Question 4. Question 5. Question 6. Question 7. Question 8. Question 9. Question 10. Question 1 Answer. Obstruction on pole creates climbing hazard. 217A4. Question 2 Answer. - PowerPoint PPT Presentation

Transcript of Oregon Joint Use Violation Examples

Page 1: Oregon Joint Use  Violation Examples

Oregon Joint Use Oregon Joint Use Violation ExamplesViolation ExamplesOregon Joint Use Oregon Joint Use Violation ExamplesViolation Examples

Stump The PanelStump The PanelStump The PanelStump The Panel

Page 2: Oregon Joint Use  Violation Examples

Question 1Question 1

Page 3: Oregon Joint Use  Violation Examples

Question 2Question 2

Page 4: Oregon Joint Use  Violation Examples

Question 3Question 3

Page 5: Oregon Joint Use  Violation Examples

Question 4Question 4

Page 6: Oregon Joint Use  Violation Examples

Question 5Question 5

Page 7: Oregon Joint Use  Violation Examples

Question 6Question 6

Page 8: Oregon Joint Use  Violation Examples

Question 7Question 7

Page 9: Oregon Joint Use  Violation Examples

Question 8Question 8

Page 10: Oregon Joint Use  Violation Examples

Question 9Question 9

Page 11: Oregon Joint Use  Violation Examples

Question 10Question 10

Page 12: Oregon Joint Use  Violation Examples

Question 1 Answer

Question 1 Answer

Obstruction on pole creates climbing hazard.

217A4

Obstruction on pole creates climbing hazard.

217A4

Page 13: Oregon Joint Use  Violation Examples

Question 2 Answer

Question 2 Answer

“Boxed” pole creates climbing hazard.

213, 236, 237, 238

“Boxed” pole creates climbing hazard.

213, 236, 237, 238

Page 14: Oregon Joint Use  Violation Examples

Question 3 Answer

Question 3 Answer

Inadequate vertical clearance between Power Company

primary riser and communication cable.

239G

Inadequate vertical clearance between Power Company

primary riser and communication cable.

239G

Page 15: Oregon Joint Use  Violation Examples

Question 4 Answer

Question 4 Answer

Inadequate vertical clearance between power supply conductor and

communication cable. Deteriorated pole hardware, standoff bracket rusted and

broken..

235C1, 214A

Inadequate vertical clearance between power supply conductor and

communication cable. Deteriorated pole hardware, standoff bracket rusted and

broken..

235C1, 214A

Page 16: Oregon Joint Use  Violation Examples

Question 5 Answer

Question 5 Answer

Inadequate vertical clearance between power

supply conductor and deck.

234C3d

Inadequate vertical clearance between power

supply conductor and deck.

234C3d

Page 17: Oregon Joint Use  Violation Examples

Question 6 Answer

Question 6 Answer

Inadequate vertical clearance between communication cable

and roadway.

232, Table 232-1

Inadequate vertical clearance between communication cable

and roadway.

232, Table 232-1

Page 18: Oregon Joint Use  Violation Examples

Question 7 Answer

Question 7 Answer

Inadequate mid-span clearance between power supply conductor

and communication cable.

235C2b(1)a

Inadequate mid-span clearance between power supply conductor

and communication cable.

235C2b(1)a

Page 19: Oregon Joint Use  Violation Examples

Question 8 Answer

Question 8 Answer

Fire hydrant has inadequate horizontal clearance from anchor

guy. Down guy in pedestrian area does not have substantial

and conspicuous marker.

231A, 217C

Fire hydrant has inadequate horizontal clearance from anchor

guy. Down guy in pedestrian area does not have substantial

and conspicuous marker.

231A, 217C

Page 20: Oregon Joint Use  Violation Examples

Question 9 Answer

Question 9 Answer Service conductor has inadequate

vertical clearance over roof.

234C3d

Service conductor has inadequate vertical clearance over roof.

234C3d

Page 21: Oregon Joint Use  Violation Examples

Question 10 Answer

Question 10 Answer

Sign has inadequate horizontal clearance from communications

cables at mid-span.

234C, Figure 234-1(b), Table 234-1

Sign has inadequate horizontal clearance from communications

cables at mid-span.

234C, Figure 234-1(b), Table 234-1