Optimized Chiller Water Plant forChilled Beams System
Execução Implementação Realização
Micah Bowman Daikin Applied Americas
Luciano de A Marcato Daikin Applied - Brasil
24/02/2016 - Rio de Janeiro
![Page 2: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/2.jpg)
ContentsContents
• Chilled Beam– Application– Operation– Benefits– Design Considerations
• Water System Design
• Energy Comparisons / Simulations– Magnetic Bearing Centrifugal Chiller Plant– Premium Efficiency Air-Cooled Inverter Screw Chiller Plant
![Page 3: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/3.jpg)
Chilled Beam ApplicationChilled Beam Application
• The chilled beam system promotes excellent thermal comfort, energyconservation, and efficient use of space due to the high heat capacityof water used as heat transfer medium.
Heat Removal Ratio
WatersideCooling
70%
AirsideCooling
30%
![Page 4: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/4.jpg)
All move the same amount of Energy
Annual Energy Usage
Pumps22%
Tower2%
Chiller33%Fans
43%
Water = Efficient TransportWater = Efficient Transport
1 Ton of Cooling
requires between 400and 550 CFM of air
or
4 GPM of water
42” Duct 5/8” Refrigerant Pipe2” Pipe
![Page 5: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/5.jpg)
Fan Energy Use in BuildingsFan Energy Use in Buildings
“Energy Consumption Characteristics of Commercial Building HVACSystems” - publication prepared for U.S. Department of Energy
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
Central VAV Central CAV Packaged CAV
Des
ign
Load
KW
/SF
Chiller/Compressor
Supply & Return Fans
Chilled Water Pump
Condenser Water Pump
Cooling Tower Fan
Condenser Fan
0
1
2
3
4
5
6
7
Central VAV Central CAV Packaged CAV
Ener
gy U
se K
Wh/
SF
![Page 6: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/6.jpg)
Chilled Beam ApplicationChilled Beam Application
• The operation principle of the system is simple and trouble-free. Thehigh temperature cooling and low temperature heating maximize theopportunity for free cooling and heating.
• Typical applications are cellular and open plans offices, hotel rooms,hospital wards, retail shops, etc. Laboratory applications are alsogood with a few extra considerations (chemicals / gases).
![Page 7: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/7.jpg)
Chilled Beam Operation PrincipleChilled Beam Operation Principle
![Page 8: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/8.jpg)
Chilled Beam Operation PrincipleChilled Beam Operation Principle
1 – Dehumidified Primary Air
2 – Primary Air supply throughbeam nozzles
3 – Induced room air tocirculate by chilled beam heatexchanger by primary airsupply air pattern
4 – Mixed air between primaryand recirculate air
5 – Chilled Water connection
6 – Hot Water Connection
![Page 9: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/9.jpg)
System BenefitsSystem Benefits
•Chilled beams provides benefits in life cycle costs:– Low maintenance cost (no filters, moving parts, condensate pump)– Easy inspection and cleaning of coils and surfaces 4-5 years– Easy maintenance access– Good energy efficiency– Free cooling possible in cold and temperate climate
•Chilled beams operate with a dry cooling coil– No condensate collection system– Primary air should be dehumidified in the air handling unit and/or– Control of water temperatures is needed to avoid condensation
![Page 10: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/10.jpg)
ACTIVE CHILLED BEAM DESIGNCONSIDERATIONS
ACTIVE CHILLED BEAM DESIGNCONSIDERATIONS
Characteristics that favor Active Chilled Beams
• Zones with moderate-high sensible load densities– Where primary airflows would be significantly higher than needed
for ventilation• Buildings most affected by space constraints
– Hi – rises, existing buildings with induction systems• Zones where the acoustical environment is a key design
criteria• Laboratories where sensible loads are driving airflows as
opposed to air change rates• Buildings seeking LEED or Green Globes certification
![Page 11: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/11.jpg)
ACTIVE CHILLED BEAM DESIGNCONSIDERATIONS
ACTIVE CHILLED BEAM DESIGNCONSIDERATIONS
Characteristics that less favor Active Chilled Beams
• Buildings with operable windows or “leaky” construction– Beams with drain pans could be considered
• Zones with:– Relatively low sensible load densities– Relatively low sensible heat ratios and low ventilation air requirements– High filtration requirements for the re-circulated room air– High latent loads
![Page 12: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/12.jpg)
Primary Air DesignPrimary Air Design
• Central AHU sized to handle:– sensible and latent cooling/heating of the ventilation air– portion of the sensible internal cooling/heating loads
AND– all of the internal and infiltration latent loads
• Primary air delivered continuously to the chilled beams– VAV primary air can be considered for the perimeter if the sensible
loads are high• Chilled beam water coils provide additional sensible
cooling/heating to control zones
![Page 13: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/13.jpg)
Passive Chilled Beams - Exposed TypePassive Chilled Beams - Exposed Type
Photo Courtesy of
![Page 14: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/14.jpg)
Active Chilled Beams Typical InstallActive Chilled Beams Typical Install
Photo Courtesy of
![Page 15: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/15.jpg)
Photo Courtesy of
Active Chilled Beams Typical InstallActive Chilled Beams Typical Install
![Page 16: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/16.jpg)
THE LUXTON-REED CENTERTHE LUXTON-REED CENTER
Photo Courtesy of
![Page 17: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/17.jpg)
THE LUXTON-REED CENTERTHE LUXTON-REED CENTER
Photo Courtesy of
![Page 18: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/18.jpg)
WATER SYSTEM DESIGNWATER SYSTEM DESIGN
![Page 19: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/19.jpg)
Dedicated ChillerDedicated Chiller
T
To chilled beam zones
Bypass Valve
Chilled waterpump
Dedicated chiller11+ COP
CoolingTower
Geothermal Loop
Geothermal HeatPump
64°F
58°F
Photo Courtesy of
![Page 20: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/20.jpg)
Secondary LoopSecondary Loop
ST
Secondary chilled watersupply to beams
Secondary chilledwater return
Supply temperaturemonitor
Primary chilledwater supply
Primary chilledwater return
HeatExchanger
SCHWPump
54°F
45°F
58°F
64°F
T
Photo Courtesy of
![Page 21: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/21.jpg)
ENERGY COMPARISONENERGY COMPARISON
![Page 22: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/22.jpg)
Energy Savings - Compared to VAVEnergy Savings - Compared to VAV
Source Technology Application % Saving*
US Dept. of Energy Report (4/2001) Beams/Radiant Ceilings General 25-30
ASHRAE 2010 Technology Awards Passive Chilled Beams Call Center 41
ACEE Emerging Technologies Report (2009) Active Chilled Beams General 20
ASHRAE Journal 2007 Active Chilled Beams Laboratory 57
SmithGroup Active Chilled Beams Offices 24
*Compared to VAV
“Energy Consumption Characteristics of Commercial Building HVACSystems” - publication prepared for U.S. Department of Energy
![Page 23: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/23.jpg)
FAN COILS VS PASSIVE CB’S VS ACB’SFAN COILS VS PASSIVE CB’S VS ACB’S
![Page 24: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/24.jpg)
Chilled Beam System MaintenanceChilled Beam System Maintenance1 – Air Side Maintenance
Chilled Beams / Primary Air AHU / AHU or FCU ifapplied2 – Chiller Plant3 – Water Distribution System4 – Control System
![Page 25: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/25.jpg)
Energy Analyzer 2 SimulationEnergy Analyzer 2 Simulation
![Page 26: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/26.jpg)
Energy Analyzer 2 SimulationEnergy Analyzer 2 Simulation
910 TR system configured with N+1
Three levels of temperatures.
Low Temp 5°C DOAS ≈30% (280TR)Medium Temp 10°C AHUs ≈30% (280TR)High Temp 15°C Chilled Beams≈40% (350TR)
![Page 27: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/27.jpg)
Qty 4 x 300T Premium Efficiency VFDAir-Cooled Screw Chillers
![Page 28: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/28.jpg)
Qty 2 x 330T Premium EfficiencyAir-Cooled Screw Chillers
Qty 2 x 290T Premium EfficiencyAir-Cooled Screw Chillers
*one sized as the +1 “joker” chiller
![Page 29: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/29.jpg)
Chilled Water Temp simulationChilled Water Temp simulation
![Page 30: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/30.jpg)
Chilled Water Temp simulationChilled Water Temp simulation
![Page 31: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/31.jpg)
Chilled Water Temp simulationChilled Water Temp simulation
![Page 32: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/32.jpg)
Life Cycle AnalysisLife Cycle Analysis
![Page 33: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/33.jpg)
Life Cycle AnalysisLife Cycle Analysis
Considered Chillers only
![Page 34: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/34.jpg)
Life Cycle AnalysisLife Cycle Analysis
Chillers + Airside + WaterDistribution Systems
![Page 35: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/35.jpg)
Energy Analyzer 2 SimulationEnergy Analyzer 2 Simulation
![Page 36: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/36.jpg)
Energy Analyzer 2 SimulationEnergy Analyzer 2 Simulation
910 TR system configured with N+1
Three levels of temperatures.
Low Temp 5°C DOAS ≈30% (280TR)Medium Temp 10°C AHUs ≈30% (280TR)High Temp 15°C Chilled Beams≈40% (350TR)
![Page 37: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/37.jpg)
Energy Analyzer 2 SimulationEnergy Analyzer 2 Simulation
Qty 4 x Identical MagneticBearing Chillers to handle alltemperature conditions.
![Page 38: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/38.jpg)
Energy Analyzer 2 SimulationEnergy Analyzer 2 Simulation
Qty 2 x Magnetic BearingChillers for DOAS and AHUs
Qty 2 x Magnetic BearingChillers of smaller size forAHUs and Chilled Beams
*one sized as the +1 “joker”chiller
![Page 39: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/39.jpg)
Chilled Water Temp simulationChilled Water Temp simulation
![Page 40: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/40.jpg)
Chilled Water Temp simulationChilled Water Temp simulation
![Page 41: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/41.jpg)
Chilled Water Temp simulationChilled Water Temp simulation
![Page 42: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/42.jpg)
Life Cycle AnalysisLife Cycle Analysis
![Page 43: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/43.jpg)
Life Cycle AnalysisLife Cycle Analysis
Considered Chillers only
![Page 44: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/44.jpg)
Life Cycle AnalysisLife Cycle Analysis
Chillers + Air side + waterdistribution systems
![Page 45: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/45.jpg)
Active Chilled Beams - First CostsActive Chilled Beams - First Costs
• Office Building, Palo Alto, CA
• 80,000 ft2
• Thermostat in each office for beam design
*HPAC Engineering Article “European Technology Taking Hold in the U.S.: Chilled Beams,Peter Rumsey, PE, CEM, FASHRAE, FRMI
“costs were in line with VAV”*
![Page 46: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/46.jpg)
• Office Building, Denver, CO
• 600,000 ft2 design/build renovation
• Elimination of two air handlers per floor due tobeams
*HPAC Engineering Article “European Technology Taking Hold in the U.S.: Chilled Beams,Peter Rumsey, PE, CEM, FASHRAE, FRMI, January 1st 2010
“the chilled-beam system was equal tothe VAV system”*
Active Chilled Beams - First CostsActive Chilled Beams - First Costs
![Page 47: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/47.jpg)
• Lower energy consumption and operating costs asprimary air flow is reduced (by 25-50%)
• Excellent thermal comfort and better IAQ(no dumping in cooling or stratification in heating mode)
• Very low noise levels with typical inlet static pressures of 0.2 in.w.c and there are no fans or motors located in/near theoccupied spaces
• Space savings in ceiling plenums and vertical shaftsdue to drastically reduced ductwork sizes
• Eliminate Fan Powered VAV (no power or maintenance)
• ALWAYS LOOK AS A SYSTEM !
• ALWAYS LOOK FOR LIFE CYCLE COST EVALUATION !
System Benefits
![Page 48: Optimized Chiller Water Plant for Chilled Beams … · Optimized Chiller Water Plant for Chilled Beams System ... – Design Considerations ... – Premium Efficiency Air-Cooled Inverter](https://reader031.fdocuments.net/reader031/viewer/2022021712/5b8a6ec17f8b9a50388c2f96/html5/thumbnails/48.jpg)