alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

Transcript of Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK –...

Page 1: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

alpha connect

Operating ManualBACnet / ModBus

UK

83055700cUK – Translation into English of the original German operating manual

Page 2: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

2 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

Contents

1 Configuringthebuildingservicesmanagementsystem(GLT) ..................................31.1 Requirements:..............................................................31.2 Followingtheconfiguration ..................................4

1.3 Enablingwithadongle ...........................................4

1.4 Completionoftheconfiguration ........................4

2 alphaconnecttool ..........................................................52.1 Languageselection...................................................5

2.2 Networkcardselection ...........................................5

2.3 Menubar .........................................................................52.4 Executiontypes ...........................................................5

2.5 Additionalalphaconnectfunctions..................9

2.6 SaveIBNlog–Part1 ..............................................9

2.7 SaveIBNlog–Part2 ..............................................9

2.8 SaveIBNlog–Part3 ..............................................9

2.9 Theversioninformationwindow(autoupdate) ...........................................................................10

2.10 Whatyoushouldnote: ..........................................10

3 BACnet.....................................................................................11

3.1 Term .................................................................................11

3.2 Functions .....................................................................11

3.3 Objects ...........................................................................11

3.4 Objectsprovided ......................................................11

3.5 Services .........................................................................13

3.6 Supportedfunctions ...............................................13

3.7 Transportsystems/transmissionroutes ...14

3.8 Datapoints ...................................................................14

3.9 DatarequiredforBACnetintegration(checklist): ....................................................................14

3.10 BACnetprotocolinformation .............................15

3.11 Productdescription: ................................................15

3.12 StandardObjectTypesSupported: ...............15

3.13 DataLinkLayerOptions: .....................................16

3.14 NetworkingOptions: ...............................................16

3.15 CharacterSetsSupported: ................................16

3.16 Descriptionofthedatapoints ...........................17

3.17 BACnetObjectlist ...................................................22

4 ModBus ...................................................................................23

4.1 Term .................................................................................23

4.2 Functions.......................................................................23

4.3 Register ..........................................................................24

4.4 Connection ...................................................................24

4.5 Datapoints ...................................................................24

4.6 Discreteinputs(readonly) .................................24

4.7 Inputregister(readonly) .....................................24

4.8 Coils .................................................................................25

4.9 Holdingregister .........................................................26

4.10 Configuration ..............................................................27

Page 3: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

3Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

1 Configuringthebuildingservicesmanagementsystem(GLT)

BACnet is availablewith software versionV1.60andhigher, ModBus with V1.74/V2.74/V3.76/V4.76 andhigher.

ThefollowingdisplaycanbeseenundertheService->Information->BACnetmenuitemofanunconfiguredsystem:

Thedisplaymeansthatalphaconnectisnotconfiguredandnotactivated.

If the point BACnet is missing under "Service" ->"Information", thesoftwareversionof thecontroller isolderthanV1.60.

NOTE.As soon as ModBus is available, the menuitem is no longer called BACnet but GLT(buildingservicesmanagementsystem).

1.1 Requirements:Fortheconfigurationthecomputermustbeconnectedtoafunctioningnetworkordirectlytotheheatpumptobeconfigured.

The computer must have an IP address, which it iseitherassignedbythecontrollerwithactivatedDHCPserver (->VariantA),byanotherDHCPserver in the

network (->VariantB),orwhich isassignedmanually(->VariantC).

VariantA: HeatpumpcontrollerasDHCPserverTheDHCPserver isactivatedat thecontrollerunderService->SystemControl->WebServer.

ThePCmustthenbeconfiguredastheDHCPclient.

VariantB: HeatpumpcontrollerasDHCPclientThe DHCP client is activated at the controller underService->SystemControl->WebServer.

The PCmust then also be configured as theDHCPclient. The PC and heat pump controller are thenassignedtheIPaddressesbyanexistingDHCPserverinthenetwork(e.g.arouter).

VariantC:ManualconfigurationoftheIPsettingsThe IP settings are set up at the controller underService->SystemControl->IPaddress.

An IP address, different to that of the controller IP,mustthenbesetinthesamenetworkatthePC.

Page 4: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

4 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

Example:

HeatpumpcontrollerhastheIPaddress192.168.1.5->PChastheIPaddress192.168.1.10.

NOTE.IfthebroadcastaddressissetincorrectlytheheatpumpcontrollerisnotfoundviaBACnet!

IfthenetworkissetupcorrectlytheGLTconfigurationcanbecarriedoutwiththehelpofalphaconnect.

1.2 FollowingtheconfigurationIftheconfigurationwascarriedoutusingthetool,thedisplay (for BACnet) looks like this and the GLT isactivatedfor4hoursfortesting:

Theremainingtesttimeisdisplayedinthetitlerowandthesetvaluesbelowit.

If thefourhourshaveexpiredtheGLT isdeactivatedagainandcanberestartedusingthetoolifnecessary.

1.3 EnablingwithadongleUSBdonglewithalicenceisrequired.

If this is inserted into the heat pump controller a GLT_Iconappearsonthemainscreen.

If this is selected a confirmation prompt appears,whether theGLTshouldbeactivatedpermanentlyornot:

Thestill-availablelicencesaredisplayed,forexample:

Onconfirmationa licence isenabledfromthedongleandthefollowingdisplayappears:

The following display can now be seen under theService->Information->GLTmenuitem:

ForBACnet:

ForModBus:

NOTE.ItispossibletoswitchbetweenModBusandBACnetatanytime.

1.4 CompletionoftheconfigurationIf the configurationwas carried outwithVariantA orB (controller as DHCP client or DHCP server), theIP data should now be entered manually accordingto Variant C. You are usually given this data by thebuildingservicesmanagementsystemengineer.

THE CONFIGURATION IS COMPLETED

Page 5: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

5Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

2 alphaconnecttoolThe alpha connect tool is located on the USB stick,withwhichtheseinstructionswereenclosed.

2.1 LanguageselectionWhentheprogramisrunforthefirsttimethelanguageselection window is displayed automatically. If thelanguageistobechangedatalaterdatethelanguageselectionwindowcanbeopenedagainviatheOptionmenu.

Laterversionsof theprogrammaycontainadditionallanguages.

1

2

1 Selectlanguage 2 Confirm

2.2 NetworkcardselectionThe program detects the correct network cardautomaticallyanddoesnothavetobeconfiguredanyfurther.

Ifdetectionisnotpossible(severalnetworkcardsandIPaddresses),amessageopensandthenetworkcardselectionwindow(inEnglish)opens.

1

2

3

1 Currentlyselectednetworkcard 2 IPdataofthecurrentnetworkcard 3 Statusdisplay.Onlynetworkcardswith

greenstatusaresuitable.

2.3 Menubar

File: ExittheprogramandcreatetheEDEfiles.

Options: Changing the language,switchingbetweendefault and expert mode and selecting the networkcard.

Tools: Creating GLT files and the broadcastcomputer

2.4 ExecutiontypesTherearetwotypesofexecutionforthisprogram:

-Defaultmode(guidedinstallation),whichisactivatedbydefault

-Expertmode,inwhichalloptionsaredisplayedinawindow.

Executiontype:DefaultmodeBydefault, intheStartwindowabroadcast isstartedto all heat pumps in the same network (immediateenvironment) and they are listed in a list with theirserialnumber,IPandstatus.

512

3

4

1 IP information 2 Search function 3 Heat pumps found 4 Open manual input 5 Selection information

Page 6: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

6 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

IPinformation

The IP information is solely to provide informationto the user. It shows the current IP of the selectednetworkcard.

Searchfunction

The search bar shows the search progress. Click"Search"torestartthesearch.

If the search ends without having found a heatpump to display, thewindow formanual input opensautomatically.

Heatpumpsfound

This list enables oneof theheat pumps found to beselected. The extended data is displayed followingselectioninthe"Selectioninformation"windowandtheconfigurationandtestbuttonsbecomeavailable.

Thestatusisalwaysoneofthesestates:Not possible:GLTisnotpossiblewiththiscontrollerfirmware.Pleaseperformanupdate.Possible:GLTispossiblebutnotyetactivated.Test run:GLThasbeenconfiguredandisrunningintestmode.Activated:GLThasalreadybeenactivatedonthiscontroller.

SelectioninformationwindowThewindowshowsfurtherinformationontheselectedheatpumpandallowstheGLTtobeconfiguredaswellasdirecttestingoftheheatpump.

The device name is the alias of the heat pump onthe BACnet level; accordingly, unconfigured BACnetsystems do not return any names. Irrelevant forModBus.

ConfiguringisonlypossibleforsystemsinwhichGLTispossible inprinciple;direct testing isonlyavailableforsystemswithalreadyconfiguredGLT.

ConfigurationwindowAllotherwindowshaveacounterpart inExpertmodeandarethereforeexplainedthereingreaterdetail.

However, in default mode there is always a buttonlabelled "Back",whichenables return to thepreviouswindow.

SwitchingtoExpertmodeTo switch to Expert mode, you can either use the"Options" -> "Expert mod" menu or the keyboardshortcut"CTRL+E".

ProceedasfollowstoswitchfromExportmodebacktoDefaultmode.

Page 7: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

7Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

Executiontype:ExpertExpertmodeconsistsoffourdifferentblocks,eachofwhich is explained individually in the following. Theblocks correspond to the individual steps of defaultmode.

ManualinputManual inputenablesdirectselectionofaheatpumpinthenetwork.Subnetmask,broadcastandgatewayareallacceptedbythecurrentlyselectednetworkcardandcanalsonotbechanged. In the"IP"field,enterthe same numbers as you can see under Service/SystemControl/IPaddress.

If the DHCP server is activated on the controller,alternatively you can set the checkmark at "DHCP Server active"toenteradefaultconfiguration.

Check also whether the port is correct. By default,youcanremovethecheckmarkfromthedefaultport;otherwise,pleaseentertheportofthecontrollerinthe"Port"field(bydefault"47808"forBACnet).

Then click "Test connection". If everything has beenenteredandconnectedcorrectly, the text turnsgreenand changes to "Connection test successful". Fromnowtheotherstepsareavailable.

ConfigurationIn the configuration block you can make varioussettings. After clicking "Save & Test" the GLT isactivatedandatestrunisstartedonthisheatpump.

InsystemsinwhichModBus/TCPisnotyetavailable,BACnetispreselectedandcanbeconfigureddirectly.

forBACnet: forModBus:

Overviewoftheconfigurationoptions:• Off: GLT is possibly licensed but not activated.

Control listensneither toBACnetnor toModBusqueries.

• BACnet/IP: GLT is configured on BACnet andlistens to theportgivenunder"BACnetPort",bydefault47808

• ModBus/TCP:GLTisconfiguredonModBusandlistenstoTCPPort502forincomingconnections.Thedevicename isusedsolely for identificationpurposesbyAlphaConnectandhasnoeffectontheGLT.

• TheNAD is an additional network address. TheGLT only responds to commands sent to thisaddress. Exception: The value 0 is accepted as"Broadcast"(ModBus).

• Theindividualoptionsunder"Writable Settings" correspond to the data points of the heat pumpwhich are writable in principle; a checkmarkmeans"writable".

• The"BACnet Port"fieldgivestheportviawhichthecontrollercanbereachedbyBACnet.(Default:47808)

• The other text fields are used to identify thesysteminthenetwork.

Page 8: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

8 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

Testrun–Part1Duringthetestrun,thestatuswindowshownbelowisdisplayed forBACnet, and illustrates the current teststatus.Itmustbeclosedmanuallywhenthetestrunisfinished.

ItdoesnotappearwithModBus.

Testrun–Part2Duringthetest,theprogramsearchesforthecurrentlyset system.With BACnet this is done via aWho Is (broadcast), with ModBus the system is addresseddirectly. If thesetheatpump is included in the listofresults,thesettingwassuccessful.

Thistestcanberepeatedbyclicking"Update".

NOTE.With ModBus the current system only isalways displayed; with BACnet all thosefoundinthenetworkaredisplayed.

Testrun–Part3If a device is selected from the list, the programautomatically queries the list of data points from thisdevice,aswellasthecurrentvalues.

ExampleofaBACnetdevice:

NOTE.Ifadevicehas toomanydatapoints,errorscanoccur.

ExampleofaModBusdevice:

NOTE.The displayed values correspond to allavailable data points; however, it is notpossible to query the names, resolution orunitsofthedatapointsviaModBus.

Page 9: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

9Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

2.5 Additionalalphaconnectfunctions

Click "Save IBN record" to open a file selectionwizard,which savesall relevant dataof the selecteddeviceinCSVformat.

2.6 SaveIBNlog–Part1This block is only used if you want to save the IBNrecord. In thiswindow you canenter peripheral dataonthecurrentprojectandsaveit/printitout.

Indefaultmodethisblock isonlyopened ifyouwanttosavetheIBNrecordattheendofthetestroutine.Italsoincludesthe"Save"button.

The project data is saved over the runtime of theprogram and is automatically available when theprogramisre-opened.

2.7 SaveIBNlog–Part2

Installer

Thiswindowappearsifyouclickoneofthe"Change"buttons in the project informationwindow. It enablesvariousinformationtobeentered,whichcanbesaved;howeveronlythenameandfirstnamearedisplayedinthemainwindow.

2.8 SaveIBNlog–Part3

Project

Fortheprojectsettingthe"Firstname"fieldisblockedand the "Name" field becomes "Project name". Thisis done for clarity reasons only and has no practicalbackground.

Additionalfunctions(ModBus)The ModBus configuration can be saved using theTools→"SaveModBusConfiguration"menu item. InthefileinCSVformat(MSExcel-compatible)youcanthenviewwhichdatahasbeenreadoutandwhetheritiswritableornot.

Page 10: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

10 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

Additionalfunctions(BACnet)TheTools -> "SaveEDEFiles" item can be used tooutputtheEDEfilesrelevantforthebuildingservicesmanagement system engineer according to theBACnetstandardforthecurrentlyconfiguredsystem.

2.9 Theversioninformationwindow(autoupdate)

The program information provides a quick overviewofthecurrentversionof theprogram,thedate itwascreated and two options for updating the programautomatically.

1

2

3

4

1Givesthecurrentversionnumberoftheprogram.

2Givesthedateonwhichtheprogramwascreated.

3 Updatestheprogram,providedanupdateisavailable.

4Ifactivated,theprogramtriestoupdateitselfautomaticallywhenitisstarted.

Confirmationdialog.Performtheupdate?

2.10 Whatyoushouldnote:• With V1.xx & V2.xx the licence is saved on the

masterboard,withV3.xx&V4.xxitissavedonthecontrol unit, i.e. if the corresponding componenthas to be replaced a new licence is required(contactcustomerservice!).

• Configurationissavedoncontrolunit;intheeventofadefecttheGLTmustbereconfigured.

• If the outside temperature is preset the outsidetemperature sensor in the device must bedisconnected.

• If theconnectionbetweenWPandGLT fails thedevice carries on running with the most recententries.

• IfpumpswhicharenormallycontrolledbytheWPcontroller are controlled by an external controlsystem:

->contactthefactorytodiscusstheinterface

• Ifthedeviceisnotfoundviaalphaconnect

->checktheIPandportsetting

-> check the broadcast address with the broad-cast calculator in alpha connect under Tools ->BroadcastCalculator

Page 11: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

11Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

3 BACnet

3.1 TermThe abbreviation "BACnet" stands for "BuildingAutomation and Control network". BACnet isan independent data transmission protocol for"open communication in data networks of buildingautomationandbuildingcontrol"with theobjectiveof"interoperability", i.e. theabilityofdevices insystemsto work with those of other manufacturers, acrosssystems.BACnet is basedonstandardisedservices,objectsand functionsand is continuouslyadapted tonew requirements and added to in various interestgroupsworldwide.

NOTE.TheBACnetdeviceIDmustbeuniqueinthecompleteBACnetnetwork!

3.2 Functions• Integration in a higher-level building services

controlsystemwithBACnet/IP

• Alltemperaturescanbereadout.

• Outdoortemperature,returnsetpointtemperatureandthethreemixingcircuitsetpointtemperaturescanbepreset.

• Faults can be read out with error number anddescription.

• FaultscanbeacknowledgedviaBACnet.

• Current operating state and the number ofcompressorscurrentlyrunningcanbereadout.

• Alloperatingmodescanbepreset:

Heatingmode

Domestichotwatermode

Coolingmode

Ventilationmode

Swimmingpoolmode

Mixingcircuit2mode

Mixingcircuit3mode

• Number of released compressors can bepredefined(Block,1VD,2VD)

• Thecurrentheatquantitiescanbereadout.

Heatingheatquantity

Hotwaterheatquantity

• DateandtimeoftheheatpumpcontrollercanbesynchronisedviaBACnet.

• DevicecanberestartedviaBACnet.

3.3 ObjectsThedata in aBACnet device is divided into objects.Eachobjecthasspecificproperties.

Example:

There is an outdoor temperature object with theproperties:

B A C n e tname

Germanname Example:

Objecttype Objecttype AnaloginputO b j e c tname

Objectname Outdoor tempera-ture

Present val-ue

Currentvalue 25.4

Unit Unit °CDescription Description Current outdoor

temperature... ... ...

Other objects would include, for example, flowtemperature,numberofcompressorsrunning,heatingmode…

3.4 ObjectsprovidedThevalueswhichare tobeprovidedvia theBACnetprotocolareassignedBACnetobjecttypes.Atpresentthere are 37 different object types in the BACnetstandard.Themostimportantare:

Analoginput -AnalogOutput -Analogvalue -Multi-StateInput -Multi-StateValue -BinaryInput -BinaryOutput -Accumulator (Count/metervalueinput)

Analog inputs, for example, represent a specificmeasuredvaluewithcorrespondingpropertiessuchasname,unit,statusordescriptionoftheobject.

Page 12: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

12 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

Allvalues fromtheconceptwhichare tobereadoutorchangedareassignedoneobject typeeach inthefollowingdescription.

TheBinary Inputobjectspecifiesanobjecttype,whoseproperties represent external visible characteristicsof thedatapoint forabinary input. It isaphysicalorhardwaredatapoint,whichcanonlyassumeoneoftwouniquestatesasaswitchingoractuatingcommand.IntheBACnetstandardthestatesarecalled"active"and"inactive".

Thebinaryinputshereare:• Self-resettingfault

• Non-self-resettingfault

The Binary Output object specifies an objecttype, whose properties represent external visiblecharacteristicsofthedatapointforabinaryoutput. Itis a physical or hardwaredatapoint,which canonlyassume one of two unique states as a switching oractuatingcommand.IntheBACnetstandardthestatesarecalled"active"and"inactive".

Thebinaryoutputshereare:• Errorreset

The Analog Input object is an object type whichrepresentsthepropertiesofananaloghardwareinput.For example, a sensor for measuring temperaturecan be connected to this input. If there are severalanalog inputs in a device, several other instancesofthesameobjecttypearecreatedwithdifferentObject_Identifiers. The pickup device (sensor) can assumeanyvaluewithinitsmeasuringrange.

Theanaloginputsinclude:• Flowtemperature

• Returntemperature

• Hotgastemperature

• Heatsourcesinputtemperature

• Heatsourcesoutputtemperature

• Mixingcircuit1temperature

• Return,externaltemperature

• Roomremoteadjustertemperature

• Mixingcircuit2temperature

• Roomremoteadjuster2temperature

• Mixingcircuit3temperature

• Roomremoteadjuster3temperature

• Solarcollectortemperature

• Solarstoragetanktemperature

• Externalenergysourcetemperature

• Supplyairtemperature

The Analog Value object is used to output analogvalues (voltages, currents, temperatures) on ahardware connection of a BACnet device. It is aphysicalorhardwaredatapoint.Thecontrollingdevice(actuator) can assume any value between 0 and100%within its range of control, which is convertedfromthephysicaloutputasacontrolcommandintoacorrespondingcurrentorvoltagevalue.Forexample,itcanbeusedtosendtheoutdoortemperaturefromacentralweatherstationtoallBACnetdevices.

Theanalogvaluesoftheheatpumpcontrollerare:• Outdoortemperature

• Returnsetpointtemperature

• Mixingcircuit1setpointtemperature

• Mixingcircuit2setpointtemperature

• Mixingcircuit3setpointtemperature

TheMulti-State Inputobjectspecifiesanobjecttype,whose object properties represent externally visiblecharacteristicsofadatapointforseveralbinaryinputs,connected by an arbitrary binary logic within theBACnet device. The object is derived from physicalor virtual data points, e.g. the limit value messagesof several analog inputs or from a mathematicalcalculation. The "Present Value" is an integer whichrepresentsastate.

Multi-stateinputsare:

• Operatingstate

• Off / with 1 VD / with 2 VDs (currently runningcompressors)

The Multi-State Value object specifies an objecttype, whose object properties represent externallyvisiblecharacteristicsofadatapointforseveralbinaryoutputs,connectedbyanarbitrarybinary logicwithintheBACnetdevice.Theobjectisderivedfromphysicalorvirtualdatapoints,e.g.for"active/inactivestatesofseveralbinaryoutputsorthevalueofananalogoutput.The"PresentValue"isanintegerwhichrepresentsthestate.

Page 13: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

13Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

Multi-statevalueshereare:• Block/Release1VD/Release2VDs

• Heatingmode

• Domestichotwatermode

• Coolingmode

• Ventilationmode

• Swimmingpoolmode

• Mixingcircuit2mode

• Mixingcircuit3mode

The Accumulator object specifies an object typewhose properties represent externally visiblecharacteristics of a measurement pulse counter forpulsegeneratingmeasuringdevices, e.g. for kilowatthoursorheatquantitymeasurement.ItisaphysicalorhardwaredatapointfortheGA"Count"function.

Count(meter)valueinputshereare:• Heatingheatquantity

• Domestichotwaterheatquantity

• Swimmingpoolheatquantity

• Totalheatquantity

3.5 ServicesWithBACnet,dataisexchangedviadefinedservices.

Examples:• Readingproperties(readproperty)

• Writingproperties(writeproperty)

• Readseveralproperties(readpropertymultiple)

• Searchingfordevices(who-is,i-am)

• Timesynchronisation

• Restarttheunit(reinitializedevice)

• ...

3.6 SupportedfunctionsThe BACnet profile: "BACnet Application SpecificController"(B-ASC)issupported.

AB-ASC is a configurable automation device. It canbe intended for special applications and supportsprogramsproducedbythemanufacturer.

A more precise list of which BACnet InteroperabilityBuildingBlocks(BIBBs)wereimplementedforthiscanbeseeninthefollowingtable.

DS-RP-B D M -DDB-B

DS-WP-B D M -DOB-BD M -DCC-B

Meaningoftheindividualabbreviationsinthetable:

DS-RP-B – Data Sharing-ReadProperty-B Aclientcanreadoutavaluefromthecontroller.

DS-WP-B – Data Sharing-WriteProperty-BAclientcanwriteavalueonthecontroller.

DM-DDB-B – Device Management-Dynamic Device Binding-B

Aclientsearches for informationaboutotherdevicesin the GA network and interprets correspondingannouncements(Who-Is/I-Am).

DM-DOB-B – Device Management-Dynamic Object Binding-B

A client searches the GA network for addressinformationaboutBACnetobjects(Who-Has,I-Have).

DM-DCC-B – Device Management-DeviceCommunicationControl-B

The client exerts control over the communicationbehaviourofthecontroller.In addition to the required BIBBs others are alsocurrentlysupported:

DS-RPM-B – Data Sharing-ReadPropertyMultiple-B

Aclientcanreadoutseveralvaluesfromthecontrolleratthesametime.

DS-COV-B – Data Sharing COV-BThe client subscribes for information about value

changesfromtheheatpumpcontroller.

DM-TS-B or DM-UTC-B – Device Management-TimeSynchronization or Device Management-UTCTimeSynchronization-B

Theclientprovidestimesynchronisationwiththelocal/UTCworldtime.

DM-RD-B – Device Management-ReinitializeDevice-B

Theclientinstigatesthecontrollertoperformawarmorcoldstartofthesoftware.

Page 14: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

14 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

3.7 Transportsystems/transmissionroutes

In the BACnet standard there are various datatransmissionroutes,suchasEthernetorserialinterface/port(RS232)ordifferenttwo-wireorradio(wireless)solutions.

WeuseBACnet / IPovertheEthernetinterfaceoftheheatpumpcontroller.

BACnet / IP is supported

3.8 DatapointsThe following tables show the data points providedwiththecorrespondingobjecttype.

Default:BACnetobjecttype

Flow OBJECT_ANALOG_INPUT

Return OBJECT_ANALOG_INPUT

Hotgas OBJECT_ANALOG_INPUT

Heatsourceon OBJECT_ANALOG_INPUT

Heatsourceoff OBJECT_ANALOG_INPUT

Mixingcircuit1 OBJECT_ANALOG_INPUT

Externalreturn OBJECT_ANALOG_INPUT

Roomremoteadjuster OBJECT_ANALOG_INPUT

Operatingstate OBJECT_MULTI_STATE_INPUT

Off/with1VD/with2VD OBJECT_MULTI_STATE_INPUT

Outdoortemp. OBJECT_ANALOG_VALUE/INPUT

Mixingcircuit1setpoint OBJECT_ANALOG_VALUE/INPUT

Returnsetpoint OBJECT_ANALOG_VALUE/INPUT

Block/release1VD/Release2VD

OBJECT_MULTI_STATE_VALUE

Heatingmode OBJECT_MULTI_STATE_VALUE/INPUT

Domestichotwatermode OBJECT_MULTI_STATE_VALUE/INPUT

Self-resettingfault OBJECT_BINARY_INPUT

Fault OBJECT_BINARY_INPUT

Errorreset OBJECT_BINARY_OUTPUT

with Comfort board:BACnetobjecttype

Mixingcircuit2 OBJECT_ANALOG_INPUT

Roomremoteadjuster2 OBJECT_ANALOG_INPUT

Mixingcircuit3 OBJECT_ANALOG_INPUT

Roomremoteadjuster3 OBJECT_ANALOG_INPUT

Solarcollector OBJECT_ANALOG_INPUT

Solarstoragetank OBJECT_ANALOG_INPUT

Externalenergysource OBJECT_ANALOG_INPUT

Mixingcircuit2setpoint OBJECT_ANALOG_VALUE/INPUT

Mixingcircuit3setpoint OBJECT_ANALOG_VALUE/INPUT

MK2mode OBJECT_MULTI_STATE_VALUE/INPUT

MK3mode OBJECT_MULTI_STATE_VALUE/INPUT

Coolingmode OBJECT_MULTI_STATE_VALUE/INPUT

Swimmingpoolmode OBJECT_MULTI_STATE_VALUE/INPUT

with ventilation board:BACnetobjecttype

Supplyairtemperature OBJECT_ANALOG_INPUT

Ventilationmode OBJECT_MULTI_STATE_VALUE/INPUT

with heat metering:BACnetobjecttype

Heatingheatquantity OBJECT_ACCUMULATOR

Domestichotwaterheatquantity OBJECT_ACCUMULATOR

Swimmingpoolheatquantity OBJECT_ACCUMULATOR

Totalheatquantity OBJECT_ACCUMULATOR

3.9 DatarequiredforBACnetintegration(checklist):

The following data is required to configure a controlunit:

Example Data

IPaddress 192.168.1.2

Subnetmask 255.255.255.0

Broadcastaddress 192.168.1.255

Gateway 192.168.1.1

UDPport 47808

BACnetDevicename WP1

BACnetDeviceID 1234

Modelname LW...

Location Kasendorf

Devicedescription Heatpump

Accesstodatapoints Readonly Read/write

Outdoortemperature

Returnsetpointtemperature

Page 15: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

15Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

Mixingcircuit1set-pointtemperature

Mixingcircuit2set-pointtemperature

Mixingcircuit3set-pointtemperature

Heatingmode

Domesticwatermode

MK2mode

MK3mode

Coolingmode

Swimmingpoolmode

Ventilationmode

3.10 BACnetprotocolinformationBACnetprotocolrevision:1Rev.10

3.11 Productdescription:The BACnet provides the heat pump controller withaccesstotheheatpump

BACnet Standardized Device Profile (Annex L):

BACnetOperatorWorkstation(B-OWS)

BACnetBuildingController(B-BC)

BACnet Advanced Application Controller (B-AAC)

x BACnetApplicationSpecificController(B-ASC)

BACnetSmartSensor(B-SS)

BACnetSmartActuator(B-SA)

List of all BACnet Interoperability Building BlocksSupported(AnnexK):

DataSharingReadProperty-B DS-RP-BData Sharing Read Property Multi-ple-B

DS-RPM-B

DataSharingWriteProperty-B DS-WP-BDataSharingCOV-B DS-COV-BDevice Management Dynamic De-viceBinding-B

DM-DDB-B

Device Management Dynamic Ob-jectBinding-B

DM-DOB-B

Device Management Device Com-municationControl-B

DM-DCC-B

DeviceManagementTimeSynchro-nization-B

DM-TS-B

DeviceManagementReinitializeDe-vice-B

DM-RD-B

Segmentation Capability:X Segmentedrequestssupported WindowSize:16

X Segmentedresponsessupported WindowSize:16

3.12 StandardObjectTypesSupported:

Analog InputDynamicallyCreatable: No

DynamicallyDeletable: No

ProprietaryProperties: None

OptionalProper-tiesSupported

WriteableProperties

PropertyRangeRestrictions

Description upto48characters

Analog ValueDynamicallyCreatable: No

DynamicallyDeletable: No

ProprietaryProperties: None

OptionalProper-tiesSupported

WriteableProperties

PropertyRangeRestrictions

Description upto48charactersPresent_Value

Binary InputDynamicallyCreatable: No

DynamicallyDeletable: No

ProprietaryProperties: None

OptionalProper-tiesSupported

WriteableProperties

PropertyRangeRestrictions

Description upto48characters

Binary OutputDynamicallyCreatable: No

DynamicallyDeletable: No

ProprietaryProperties: None

Page 16: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

16 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

OptionalProper-tiesSupported

WriteableProperties

PropertyRangeRestrictions

Description upto48charactersPresent_Value

DeviceDynamicallyCreatable: No

DynamicallyDeletable: No

ProprietaryProperties: None

OptionalProper-tiesSupported

WriteableProperties

PropertyRangeRestrictions

Description upto48characters

Multistate InputDynamicallyCreatable: No

DynamicallyDeletable: No

ProprietaryProperties: None

OptionalProper-tiesSupported

WriteableProperties

PropertyRangeRestrictions

Description upto48characters

Multistate ValueDynamicallyCreatable: No

DynamicallyDeletable: No

ProprietaryProperties: None

OptionalProper-tiesSupported

WriteableProperties

PropertyRangeRestrictions

Description upto48characters

AccumulatorDynamicallyCreatable: No

DynamicallyDeletable: No

ProprietaryProperties: None

OptionalProper-tiesSupported

WriteableProperties

PropertyRangeRestrictions

Description upto48characters

3.13 DataLinkLayerOptions:x BACnetIP,(AnnexJ)

BACnetIP,(AnnexJ),ForeignDevice

ISO8802-3,Ethernet(Clause7)

ANSI/ATA878.1,2.5Mb.ARCNET(Clause8)

ANSI/ATA878.1,RS-485ARCNET (Clause8), baudrate(s)____________

MS/TPmaster(Clause9),baudrate(s):

MS/TPslave(Clause9),baudrate(s):

Point-To-Point, EIA 232 (Clause 10), baudrate(s):

Point-To-Point, modem, (Clause 10), baud rate(s):

LonTalk,(Clause11),medium:__________

Other:

3.14 NetworkingOptions: Router,Clause6-Listallroutingconfigurations,

e.g.,ARCNET-Ethernet,Ethernet-MS/TP,etc.

AnnexH,BACnetTunnelingRouteroverIP

BACnet/IP Broadcast Management Device (BBMD)

Does the BBMD support registrations by ForeignDevices?

Yes No

3.15 CharacterSetsSupported:Indicatingsupportformultiplecharactersetsdoesnotimplythattheycanallbesupportedsimultaneously.

x ANSIX3.4

IBM/MicrosoftDBCS

ISO8859-1

ISO10646(UCS-2)

ISO10646(UCS-4)

JISC6226

Page 17: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

17Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

3.16 DescriptionofthedatapointsFlow temperature

BACnetObjectType AnaloginputBACnetObjectID 1Unit °CResolution 0.1 °C

Return temperature

BACnetObjectType AnaloginputBACnetObjectID 2Unit °CResolution 0.1 °C

Hot gas temperature

BACnetObjectType AnaloginputBACnetObjectID 3Unit °CResolution 0.1 °C

Heat source on

BACnetObjectType AnaloginputBACnetObjectID 4Unit °CResolution 0.1 °C

Heat source off

BACnetObjectType AnaloginputBACnetObjectID 5Unit °CResolution 0.1 °C

Mixing circuit 1

BACnetObjectType AnaloginputBACnetObjectID 6Unit °CResolution 0.1 °C

External return

BACnetObjectType AnaloginputBACnetObjectID 7Unit °CResolution 0.1 °C

Room remote adjuster

BACnetObjectType AnaloginputBACnetObjectID 8Unit °CResolution 0.1 °C

Mixing circuit 2

BACnetObjectType AnaloginputBACnetObjectID 9Unit °CResolution 0.1 °C

Room remote adjuster 2

BACnetObjectType AnaloginputBACnetObjectID 10Unit °CResolution 0.1 °C

Mixing circuit 3

BACnetObjectType AnaloginputBACnetObjectID 11Unit °CResolution 0.1 °C

Room remote adjuster 3

BACnetObjectType AnaloginputBACnetObjectID 12Unit °CResolution 0.1 °C

Solar collector

BACnetObjectType AnaloginputBACnetObjectID 13Unit °CResolution 0.1 °C

Solar storage tank

BACnetObjectType AnaloginputBACnetObjectID 14Unit °CResolution 0.1 °C

Page 18: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

18 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

External energy source

BACnetObjectType AnaloginputBACnetObjectID 15Unit °CResolution 0.1 °C

Outdoor temperature

BACnet Object-Type

Analoginput Analogvalue

BACnet ObjectID

16 1

Unit °CResolution 0.1 °C

If the outdoor temperature is preset via BACnet ->disconnectsensorinthedevice.

Return setpoint temperature

BACnetObjectType Analoginput AnalogvalueBACnetObjectID 17 2Unit °CResolution 0.1 °C

Mixing circuit 1 setpoint temperature

BACnetObjectType Analoginput AnalogvalueBACnetObjectID 18 3Unit °CResolution 0.1 °C

Mixing circuit 2 setpoint temperature

BACnetObjectType Analoginput Analog val-ue

BACnetObjectID 19 4Unit °CResolution 0.1 °C

Mixing circuit 3 setpoint temperature

BACnetObjectType Analoginput AnalogvalueBACnetObjectID 20 5Unit °CResolution 0.1 °C

Supply air temperature

BACnetObjectType AnaloginputBACnetObjectID 21Unit °CResolution 0.1 °C

Hot water actual temperature

BACnetObjectType AnaloginputBACnetObjectID 22Unit °CResolution 0.1 °C

Hot water setpoint temperature

BACnetObjectType Analoginput AnalogvalueBACnetObjectID 23 6Unit °CResolution 0.1 °C

Temperature, compressor intake

BACnetObjectType AnaloginputBACnetObjectID 24Unit °CResolution 0.1 °C

Temperature, evaporator intake

BACnetObjectType AnaloginputBACnetObjectID 25Unit °CResolution 0.1 °C

Temperature, compressor heater

BACnetObjectType AnaloginputBACnetObjectID 26Unit °CResolution 0.1 °C

Overheating

BACnetObjectType AnaloginputBACnetObjectID 27Unit KResolution 0.1bar

Page 19: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

19Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

Overheating setpoint

BACnetObjectType AnaloginputBACnetObjectID 28Unit KResolution 0.1 K

Pressure HD

BACnetObjectType AnaloginputBACnetObjectID 29Unit °CResolution 0.1 °C

Pressure ND

BACnetObjectType AnaloginputBACnetObjectID 30Unit BarResolution 0.01bar

RBE room temperature, actual

BACnetObjectType AnalogInputBACnetObject-ID 31Unit °CResolution 0,1°C

RBE room temperature, setpoint

BACnetObjectType AnalogInputBACnetObject-ID 32Einheit °CResolution 0,1°C

Current flow

BACnetObjectType AnalogInputBACnetObject-ID 33Unit l/hResolution 1l/h

Heating curve, heating, end pointBACnetObjectType AnalogInput AnalogValueBACnetObject-ID 34 7Unit °CResolution 0,1°C

Heating curve, heating, parallel shift

BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 35 8Unit °CResolution 0,1°C

Heating curve, heating, end point MK 1

BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 36 9Unit °CResolution 0,1°C

Heating curve, heating, parallel shift MK 1

BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 37 10Unit °CResolution 0,1°C

Heating curve, heating, end point MK 2

BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 38 11Unit °CResolution 0,1°C

Heating curve, heating, parallel shift MK 2

BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 39 12Unit °CResolution 0,1°C

Heating curve, heating, end point MK 3

BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 40 13Unit °CResolution 0,1°C

Heating curve, heating, parallel shift MK 3

BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 41 14Unit °CResolution 0,1°C

Page 20: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

20 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

Temperature, plus/minus

BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 42 15Unit °CResolution 0,1°C

Operating state

BACnetObjectType MultistateinputBACnetObjectID 1States 1=Heatingmode

2=Domestichotwater3=Swimmingpool4=EVUoff5=Defrost6=Off7=Externalenergysource

Off / with 1 compressor / with 2 compressors (currently running)

BACnetObjectType MultistateinputBACnetObjectID 2States 1=Off

2=1compressorisrunning3=2compressorsarerunning

Block / Release 1 compressor / Release 2 compressors

BACnetObjectType MultistatevalueBACnetObjectID 1States 1=Blockheatpump

2=Release1compressor3 = Release 2 compres-sors

Heating mode

B A C n e t ObjectType

Multistateinput Multistatevalue

BACnetObjectID 3 2States 1=Automatic

2=Secondheatgenerator3=Party4=Holidays5=Off

Domestic hot water mode

BACnet Object-Type

Multistateinput Multistatevalue

BACnet ObjectID

4 3

States 1=Automatic2=Secondheatgenerator3=Party4=Holidays5=Off6=Charge

Mixing circuit 2 mode

BACnetObjectType Multistateinput Multistatevalue

BACnetObjectID 6 5States 1=Automatic

2=Secondheatgenerator3=Party4=Holidays5=Off

Mixing circuit 3 mode

BACnetObjectType Multistateinput Multistatevalue

BACnetObjectID 7 6States 1=Automatic

2=Secondheatgenerator3=Party4=Holidays5=Off

Cooling mode

BACnetObjectType Multistateinput Multistatevalue

BACnetObjectID 8 7States 1=Off

2=Automatic

Page 21: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

21Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

Heating heat quantity

BACnetObjectType AccumulatorBACnetObjectID 1Unit kWhResolution 1kWh

Domestic hot water heat quantity

BACnetObjectType AccumulatorBACnetObjectID 2Unit kWhResolution 1kWh

Swimming pool heat quantity

BACnetObjectType AccumulatorBACnetObjectID 3Unit kWhResolution 1kWh

Total heat quantity

BACnetObjectType AccumulatorBACnetObjectID 4Unit kWhResolution 1kWh

Ventilation mode

BACnetObjectType Multistateinput Multistatevalue

BACnetObjectID 9 8States 1=Automatic

2=Party3=Holidays4=Off

Swimming pool mode

BACnetObjectType Multistateinput Multistatevalue

BACnetObjectID 10 9States 1=Automatic

2=Notused3=Party4=Holidays5=Off

Self-resetting fault

BACnetObjectType BinaryinputBACnetObjectID 1States INACTIVE->nofaultACTIVE->fault

In the event of a fault, the error number with acorresponding description is displayed in theDescriptionandintheActiveText

Non-self-resetting fault

BACnetObjectType BinaryinputBACnetObjectID 2States INACTIVE->nofault

ACTIVE->faultIn the event of a fault the error number with acorresponding description is displayed in theDescriptionandintheActiveText

Error reset

BACnetObjectType BinaryoutputBACnetObjectID 1States INACTIVE->normal

ACTIVE->Errorreset

Set1tothisdatapointtoacknowledgeerrors.

Page 22: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

22 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

3.17 BACnetObjectlistThefollowingtableshowstheobjectIDsofthedatapoints:whetheravalueisreadonly(INPUT)orwhetheritisalsowritable(VALUE).

Default:ANALOG

INPUTANALOG VALUE

MULTISTATE INPUT

MULTISTATE VALUE

BINARY INPUT

BINARY OUTPUT

ACCUMU-LATOR

Flow 1

Return 2

Hot gas 3

Heat source on 4

Heat source off 5

Mixing circuit 1 6

External return 7

Room remote adjuster 8

Operating state 1

Off / with 1VD / with 2VD 2

Outdoor temp. 16 1

Return setpoint 17 2

Mixing circuit 1 setpoint 18 3

Block/Release 1VD/Release 2VD 1

Heating mode 3 2

Domestic hot water mode 4 3

Self-resetting fault 1

Fault 2

Error reset 1

Domestic water actual temperature 22

Domestic water setpoint temperature 23 6

RBE room temperature, actual 31

RBE room temperature, setpoint 32

Current flow 33

Heating curve, heating, end point 34 7

Heating curve, heating, parallel shift 35 8

Heating curve, heating, end point MK 1 36 9

Heating curve, heating, parallel shift MK 1 37 10

Heating curve, heating, end point MK 2 38 11

Heating curve, heating, parallel shift MK 2 39 12

Heating curve, heating, end point MK 3 40 13

Heating curve, heating, parallel shift MK 3 41 14

Temperature, plus/minus 42 15

with Comfort board:ANALOG

INPUTANALOG VALUE

MULTISTATE INPUT

MULTISTATE VALUE

BINARY INPUT

BINARY OUTPUT

ACCUMU-LATOR

Mixing circuit 2 9

Room remote adjuster 2 10

Mixing circuit 3 11

Room remote adjuster 3 12

Solar collector 13

Solar storage tank 14

External energy source 15

Mixing circuit 2 setpoint 19 4

Mixing circuit 3 setpoint 20 5

MK2 mode 6 5

MK3 mode 7 6

Cooling mode 8 7

Swimming pool mode 10 9

Page 23: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

23Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

with ventilation board:ANALOG

INPUTANALOG VALUE

MULTISTATE INPUT

MULTISTATE VALUE

BINARY INPUT

BINARY OUTPUT

ACCUMU-LATOR

Supply air temperature 21

Ventilation mode 9 8

with heat metering:ANALOG

INPUTANALOG VALUE

MULTISTATE INPUT

MULTISTATE VALUE

BINARY INPUT

BINARY OUTPUT

ACCUMU-LATOR

Heating heat quantity 1

Domestic hot water heat quantity

2

Swimming pool heat quantity 3

Total heat quantity 4

for heatpumps with LIN- and / or MODBus:ANALOG

INPUTANALOG VALUE

MULTISTATE INPUT

MULTISTATE VALUE

BINARY INPUT

BINARY OUTPUT

ACCUMU-LATOR

Compressor intake 24

Evaporator intake 25

Compressor heater 26

Overheating 27

Overheating setpoint 28

Pressure HD 29

Pressure ND 30

4 ModBus

4.1 TermModBusisanindependentprotocolforcommunicationbetweencomponentsofdifferentmanufacturersandsystems.In industry it isused in its "RTU" formasade factostandardand isusedwidely.TheModBus/TCPstandard isrelativelynewandwasstandardisedin2007.

ModBusisbasedonregisteraccesses,sothateachfunctionisassignedaspecificaddressandcanbechanged/readoutbythe"master".

Theait-DeutschlandGmbHcontrolsupportstheModBus/TCPstandardastheslave.

4.2 Functions• IntegrationinaproprietaryhomenetworkwithModBus/TCP.

• Diversedatapointscanbereadout.

◦ Temperatures

◦ Inputs

◦ Outputs

◦ Operatinghours

◦ Heatquantity

• Diversesetpointsandoperatingmodesaswellastheoutdoortemperaturecanbepredefinedviaahigher-levelGLT.

• Faultscanbeacknowledged.

Page 24: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

24 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

4.3 RegisterThe ModBus/TCP data is provided in the form ofregisters.Fourtypesaresupported:

1. Discrete inputs: Truth values (Boolean values),e.g.inputs.Readonly

2. Coils:Truthvalues(Booleanvalues),e.g.outputs.Writable.

3. Inputregisters: Integervaluesof thecontrol,e.g.temperatures.Readonly.

4. Holding registers: Integer values of the control,e.g.setpointvalues.Writable.

Here the following must be noted: If a value is nolonger to be predefined, a value outside the definedlimits must be transferred. For coils, this means thevalue"0";forholdingregistersitmeansavalueoutsidethelimitsfortherelevantdatapointintheappendix.

4.4 ConnectionModBus/TCP shares the IP address of the controlsystemandcanbereachedviatheTCPport502.

WerecommendthatyouusethefreewareqModMasterforthetest,availableathttp://sourceforge.net/projects/qmodmaster/.

Whenprogrammingnote that someModBusstationsor nodes begin with address "1" but send 0. Ourregistersare0-based.

4.5 DatapointsAll data points are availablewith each configuration;however, they do not always have valid values oreffects. In general the following applies: If the datapointisnotvisibleinthecontroller,thevaluesaretobedeemedinvalid.

4.6 Discreteinputs(readonly)

Name IDEVU 0EVU2 1SWT 2VD1 3VD2 4ZWE1 5ZWE2 6ZWE3 7

4.7 Inputregister(readonly)Name ID Resolution Unit

Meantemperature 0 10 °CFlow 1 10 °CReturn 2 10 °CExternalreturn 3 10 °CHotwatertemperature 4 10 °CMK1flow 5 10 °CFlowMK2 6 10 °CFlowMK3 7 10 °CHotgastemperature 8 10 °CHeatsourceinlettemper-

ature9 10 °C

Heat source outlet tem-perature

10 10 °C

Room remote adjuster 1temperature

11 10 °C

Room remote adjuster 2temperature

12 10 °C

Room remote adjuster 3temperature

13 10 °C

Solar collector tempera-ture

14 10 °C

Solar storage tank tem-perature

15 10 °C

External energy sourcetemperature

16 10 °C

Supplyairtemperature 17 10 °CExtractairtemperature 18 10 °C

Page 25: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

25Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

Name ID Resolu-tion

Unit

Compressorintaketem-perature

19 10 °C

Evaporator intake tem-perature

20 10 °C

Temperature, compres-sorheater

21 10 °C

Overheating 22 10 KelvinOverheatingsetpoint 23 10 KelvinRBEroomtemperature,

actual24 10 °C

RBEroomtemperature,setpoint

25 10 °C

Highpressure 26 100 barLowpressure 27 100 barVD1operatinghours 28 1 Hours(h)VD2operatinghours 29 1 Hours(h)ZWE1operatinghours 30 1 Hours(h)ZWE2operatinghours 31 1 Hours(h)ZWE3operatinghours 32 1 Hours(h)Heat pump operating

hours33 1 Hours(h)

Heatingoperatinghours 34 1 Hours(h)Hot water operating

hours35 1 Hours(h)

Swimming pool operat-inghours

36 1 Hours(h)

Systemstatus 37 0=Heatingmode

1=Domestichotwa-ter

2=Swimmingpool

3=EVUoff

4=Defrost

5=Off

6 = External energysource

Heating heat quantity(High)

38 10 kWh

Heating heat quantity(High)

39 10 kWh

Hot water heat quantity(High)

40 10 kWh

Hot water heat quantity(High)

41 10 kWh

Swimming pool heatquantity(High)

42 10 kWh

Swimming pool heatquantity(High)

43 10 kWh

Total heat quantity(High)

44 10 kWh

Total heat quantity(High)

45 10 kWh

Errormemory 46

4.8 CoilsPleasenote:Allcoilsonlyhaveaneffectif"1"issenttothem.

If"0","Automatic"isassumed.

Name ID DescriptionErrorreset 0 Acknowledges the currently

queuederrorWatchdog 1 Reserved,isnotusedHUP 2 ForcedswitchingonoftheHUP.VEN 3 Forcedswitchingonofthefan.ZUP 4 ForcedswitchingonoftheZUP.BUP 5 ForcedswitchingonoftheBUP.BOSUP 6 ForcedswitchingonoftheBOSUP.ZIP 7 ForcedswitchingonoftheZIP.FUP2 8 Forced switching on of the 2nd

FUP.FUP3 9 Forced switching on of the 3rd

FUP.SLP 10 ForcedswitchingonoftheSLP.SUP 11 ForcedswitchingonoftheSUP.VSK 12 ForcedswitchingonoftheVSK.FRH 13 ForcedswitchingonoftheFRH.

Page 26: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

26 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

4.9 HoldingregisterName ID Resolution Unit Min. Max.

Outdoortemperature 0 10 °C -200 800Returnsetpoint 1 10 °C 150 800MK1flowsetpoint 2 10 °C 150 800MK2flowsetpoint 3 10 °C 150 800MK3flowsetpoint 4 10 °C 150 800Hotwater,setpoint 5 10 °C 150 800Release/block 6 1 0 2Heatingmode 7 1 0 4Hotwatermode 8 1 0 5MK2mode 9 1 0 4MK3mode 10 1 0 4Coolingmode 11 1 0 1Ventilationmode 12 1 0 3Swimmingpoolmode 13 1 0 4SmartGridcontrol 14 1 0 3Heatingcurve,heating,endpoint 15 10 °C 200 700Heatingcurve,heating,parallelshift 16 10 °C 50 350Heatingcurve,heating,endpointMK1 17 10 °C 200 700Heatingcurve,heating,parallelshiftMK1 18 10 °C 50 350Heatingcurve,heating,endpointMK2 19 10 °C 200 700Heatingcurve,heating,parallelshiftMK2 20 10 °C 50 350Heatingcurve,heating,endpointMK3 21 10 °C 200 700Heatingcurve,heating,parallelshiftMK3 22 10 °C 50 350Temperature,plus/minus 23 10 °C -50 50

Page 27: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

27Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH

4.10 ConfigurationFor systems with software versions older than thestatesgivenforModBus/TCP,theconfigurationscreenisasfollows.TheGLTselectionisgreyedout,BACnetispreselectedandcanbeconfigured.

For a ModBus/TCP-compatible device the screenlookssomewhatdifferent:

NOTE.For ModBus TCP only the currently editedclient is displayed under "Devices found"as it isasingleconnection.Thedatapointsdisplayedon the right-handside correspondto all available registers via ModBus/TCP;however, it is not possible to query thenames,resolutionorunitviaModBus

Page 28: Operating Manual - Ait-Nord · alpha connect Operating Manual BACnet / ModBus UK 83055700cUK – Translation into English of the original German operating manual

ait-deutschland GmbHIndustriestraße 395359 Kasendorf, Germany

E [email protected] www.alpha-innotec.de

alpha innotec – an ait-deutschland GmbH brand

UK