Nivo®Guide 3100Two-wire 4 … 20 mA/HART
Rod and cable probe
TDR sensor for continuous level measurement of bulk solids
Technical information / Instruction manual
Document ID: 58879
2
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
Contents58879-EN
-190215
Contents1 About this document ............................................................................................................... 4
1.1 Function ........................................................................................................................... 41.2 Target group ..................................................................................................................... 41.3 Symbols used................................................................................................................... 4
2 For your safety ......................................................................................................................... 52.1 Authorised personnel ....................................................................................................... 52.2 Appropriate use ................................................................................................................ 52.3 Warning about incorrect use ............................................................................................. 52.4 General safety instructions ............................................................................................... 52.5 EU conformity ................................................................................................................... 62.6 NAMUR recommendations .............................................................................................. 62.7 Installation and operation in the USA and Canada ........................................................... 6
3 Product description ................................................................................................................. 73.1 Configuration .................................................................................................................... 73.2 Principle of operation........................................................................................................ 83.3 Packaging, transport and storage ..................................................................................... 83.4 Accessories and replacement parts ................................................................................. 9
4 Mounting ................................................................................................................................. 104.1 General instructions ....................................................................................................... 104.2 Mounting instructions ..................................................................................................... 11
5 Connecting to power supply ................................................................................................. 155.1 Preparing the connection ............................................................................................... 155.2 Connecting ..................................................................................................................... 165.3 Wiring plan, single chamber housing.............................................................................. 175.4 Wiring plan, double chamber housing ............................................................................ 185.5 Switch-on phase............................................................................................................. 19
6 Set up with the display and adjustment module ................................................................ 206.1 Insert display and adjustment module ............................................................................ 206.2 Adjustment system ......................................................................................................... 216.3 Parameter adjustment - Quick setup .............................................................................. 236.4 Parameter adjustment - Extended adjustment................................................................ 236.5 Saving the parameterisation data ................................................................................... 38
7 Diagnostics and servicing .................................................................................................... 397.1 Maintenance .................................................................................................................. 397.2 Status messages ............................................................................................................ 397.3 Rectify faults ................................................................................................................... 427.4 Exchanging the electronics module ................................................................................ 457.5 Exchange or shorten cable ............................................................................................. 467.6 How to proceed if a repair is necessary .......................................................................... 47
8 Dismount................................................................................................................................. 488.1 Dismounting steps.......................................................................................................... 488.2 Disposal ......................................................................................................................... 48
9 Supplement ............................................................................................................................ 499.1 Technical data ................................................................................................................ 499.2 Dimensions .................................................................................................................... 60
3
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
Contents58
879-
EN-1
9021
5
9.3 Trademark ...................................................................................................................... 65
Safety instructions for Ex areasTakenoteoftheExspecificsafetyinstructionsforExapplications.These instructions are attached as documents to each instrument with Ex approval and are part of the operating instructions.
Editing status: 2019-02-05
4
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
1 About this document58879-EN
-190215
1 About this document
1.1 FunctionThis operating instructions provides all the information you need for mounting, connection and setup as well as important instructions for maintenance,faultrectification,theexchangeofpartsandthesafetyof the user. Please read this information before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device.
1.2 Target groupThis operating instructions manual is directed to trained personnel. Thecontentsofthismanualmustbemadeavailabletothequalifiedpersonnel and implemented.
1.3 Symbols usedInformation, tip, noteThis symbol indicates helpful additional information.Caution: If this warning is ignored, faults or malfunctions can result.Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result.Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.
Ex applicationsThis symbol indicates special instructions for Ex applications.
• ListThe dot set in front indicates a list with no implied sequence.
→ ActionThis arrow indicates a single action.
1 Sequence of actionsNumbers set in front indicate successive steps in a procedure.
Battery disposalThis symbol indicates special information about the disposal of bat-teries and accumulators.
5
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
2 For your safety58
879-
EN-1
9021
5
2 For your safety
2.1 Authorised personnelAll operations described in this documentation must be carried out onlybytrained,qualifiedpersonnelauthorisedbytheplantoperator.During work on and with the device, the required personal protective equipment must always be worn.
2.2 Appropriate useNivoGuide 3100 is a sensor for continuous level measurement.Youcanfinddetailedinformationabouttheareaofapplicationinchapter "Product description".Operational reliability is ensured only if the instrument is properly usedaccordingtothespecificationsintheoperatinginstructionsmanual as well as possible supplementary instructions.
2.3 Warning about incorrect useInappropriate or incorrect use of this product can give rise to applica-tion-specifichazards,e.g.vesseloverfillthroughincorrectmountingor adjustment. Damage to property and persons or environmental contamination can result. Also, the protective characteristics of the instrument can be impaired.
2.4 General safety instructionsThis is a state-of-the-art instrument complying with all prevailing regulations and directives. The instrument must only be operated in a technicallyflawlessandreliablecondition.Theoperatorisresponsi-ble for the trouble-free operation of the instrument. When measuring aggressive or corrosive media that can cause a dangerous situation if the instrument malfunctions, the operator has to implement suitable measures to make sure the instrument is functioning properly.During the entire duration of use, the user is obliged to determine the compliance of the necessary occupational safety measures with the current valid rules and regulations and also take note of new regula-tions.The safety instructions in this operating instructions manual, the na-tional installation standards as well as the valid safety regulations and accident prevention rules must be observed by the user.For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbi-traryconversionsormodificationsareexplicitlyforbidden.Forsafetyreasons,onlytheaccessoryspecifiedbythemanufacturermustbeused.To avoid any danger, the safety approval markings and safety tips on the device must also be observed and their meaning read in this oper-ating instructions manual.
6
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
2 For your safety58879-EN
-190215
2.5 EU conformityThedevicefulfilsthelegalrequirementsoftheapplicableEUdirec-tives.ByaffixingtheCEmarking,weconfirmtheconformityoftheinstrument with these directives.
2.6 NAMUR recommendationsNAMUR is the automation technology user association in the process industry in Germany. The published NAMUR recommendations are acceptedasthestandardinfieldinstrumentation.ThedevicefulfilstherequirementsofthefollowingNAMURrecom-mendations:
• NE 21 – Electromagnetic compatibility of equipment• NE 43 – Signal level for fault information from measuring transduc-
ers• NE53–Compatibilityoffielddevicesanddisplay/adjustment
components• NE107–Self-monitoringanddiagnosisoffielddevicesFor further information see www.namur.de.
2.7 Installation and operation in the USA and Canada
This information is only valid for USA and Canada. Hence the follow-ing text is only available in the English language.Installations in the US shall comply with the relevant requirements of the National Electrical Code (ANSI/NFPA 70).Installations in Canada shall comply with the relevant requirements of the Canadian Electrical CodeA Class 2 power supply unit has to be used for the installation in the USA and Canada.
7
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
3 Product description58
879-
EN-1
9021
5
3 Product description
3.1 ConfigurationThetypelabelcontainsthemostimportantdataforidentificationanduse of the instrument:
21
12
13
14
11
10
5
3
6
4
78
9
Fig. 1: Layout of the type label (example)1 Instrument type2 Product code3 Approvals (option)4 Power supply and signal output, electronics5 Protection rating6 Probe length (measurement accuracy optional)7 Process and ambient temperature, process pressure8 Material wetted parts9 Order number10 Serial number of the instrument11 Symbol of the device protection class12 ID numbers, instrument documentation13 CEidentification14 Approval directives (optional)
This operating instructions manual applies to the following instrument versions:
• Hardware from 1.0.0• Software from 1.3.0• OnlyforinstrumentversionswithoutSILqualification
The instrument and the electronics version can be determined via the product code on the type label as well as on the electronics.
• Standard electronics: Type FX80H.-
The scope of delivery encompasses:
• Sensor• Optional accessory• Documentation
– Quick setup guide NivoGuide 3100 – Instructions for optional instrument features – Ex-specific"Safety instructions" (with Ex versions)
Type label
Scope of this operating instructions
Versions
Scope of delivery
8
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
3 Product description58879-EN
-190215
– Ifnecessary,furthercertificates
Information:In this operating instructions manual, the optional instrument features are described. The respective scope of delivery results from the order specification.
3.2 Principle of operationThe NivoGuide 3100 is a level sensor with cable or rod probe for con-tinuous level measurement, suitable for applications in bulk solids.
High frequency microwave pulses are guided along a steel cable or a rod. Upon reaching the product surface, the microwave pulses are reflected.Therunningtimeisevaluatedbytheinstrumentandoutputas level.
3.3 Packaging, transport and storageYour instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test based on ISO 4180.The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.
Transport must be carried out in due consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device.
The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or con-cealed defects must be appropriately dealt with.
Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside.Unless otherwise indicated, the packages must be stored only under the following conditions:
• Not in the open• Dry and dust free• Not exposed to corrosive media• Protected against solar radiation• Avoiding mechanical shock and vibration
• Storage and transport temperature see chapter "Supplement - Technical data - Ambient conditions"
• Relative humidity 20 … 85 %
With instrument weights of more than 18 kg (39.68 lbs) suitable and approved equipment must be used for lifting and carrying.
Application area
Functional principle - level measurement
Packaging
Transport
Transport inspection
Storage
Storage and transport temperature
Lifting and carrying
9
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
3 Product description58
879-
EN-1
9021
5
3.4 Accessories and replacement partsThe display and adjustment module is used for measured value indi-cation, adjustment and diagnosis. It can be inserted into the sensor and removed at any time.Youcanfindfurtherinformationintheoperatinginstructions"Display and adjustment module".
Screwedflangesareavailableindifferentversionsaccordingtothefollowing standards: DIN 2501, EN 1092-1, BS 10, ASME B 16.5, JIS B 2210-1984, GOST 12821-80.Youcanfindadditionalinformationinthesupplementaryinstructionsmanual "Flanges according to DIN-EN-ASME-JIS".
The electronics module NivoGuide is a replacement part for GWR sensors of the NivoGuide series.Youcanfindfurtherinformationintheoperatinginstructionsmanual"Electronics module NivoGuide".
Display and adjustment module
Flanges
Electronics module
10
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
4 Mounting58879-EN
-190215
4 Mounting
4.1 General instructionsOndeviceswithathreadedfitting,thehexagonontheprocessfittingmust be tightened with a suitable wrench.See chapter "Dimensions"forwrenchsize.
Warning:The housing or the electrical connection may not be used for screw-ing in! Tightening can cause damage, e. g. to the rotation mechanism of the housing.
Protect your instrument against moisture ingress through the following measures:
• Use a suitable connection cable (see chapter "Connecting to power supply")
• Tighten the cable gland or plug connector• Whenmountinghorizontally,turnthehousingsothatthecable
gland or plug connector point downward• Lead the connection cable downward in front of the cable entry or
plug connector.
This applies mainly to outdoor installations, in areas where high humidity is expected (e.g. through cleaning processes) and on cooled or heated vessels.To maintain the housing protection, make sure that the housing lid is closed during operation and locked, if necessary.Makesurethatthedegreeofcontaminationspecifiedinchapter"Technical data" meets the existing ambient conditions.
Metric threadsIn the case of instrument housings with metric thread, the cable glands are screwed in at the factory. They are sealed with plastic plugs as transport protection.You have to remove these plugs before electrical connection.
NPT threadIn the case of instrument housings with self-sealing NPT threads, it is not possible to have the cable entries screwed in at the factory. The free openings for the cable glands are therefore covered with red dust protection caps as transport protection. The dust protection caps do notprovidesufficientprotectionagainstmoisture.Prior to setup you have to replace these protective caps with ap-proved cable glands or close the openings with suitable blind plugs.
Make sure before mounting that all parts of the instrument exposed to the process are suitable for the existing process conditions.These are mainly:
• Active measuring component• Processfitting• Process seal
Screwing in
Protection against mois-ture
Cable glands
Suitability for the process conditions
11
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
4 Mounting58
879-
EN-1
9021
5
Process conditions in particular are:
• Process pressure• Process temperature• Chemical properties of the medium• AbrasionandmechanicalinfluencesYoucanfinddetailedinformationontheprocessconditionsinchapter"Technical data" as well as on the type label.
The instrument is suitable for standard and extended ambient condi-tions acc. to IEC/EN 61010-1.
4.2 Mounting instructionsMount NivoGuide 3100 in such a way that the distance to vessel installations or to the vessel wall is at least 300 mm (12 in). In non-metallic vessels, the distance to the vessel wall should be at least 500 mm (19.7 in).During operation, the probe must not touch any installations or the vessel wall. If necessary, fasten the probe end.In vessels with conical bottom it can be advantageous to mount the sensor in the center of the vessel, as measurement is then possible nearly down to the lowest point of the bottom. Keep in mind that measurement all the way down to the tip of the probe may not be pos-sible. The exact value of the min. distance (lower dead band) is stated in chapter "Technical data" of the operating instructions.
Fig. 2: Vessel with conical bottom
Plastic vessel/Glass vesselThe guided microwave principle requires a metallic surface on the processfitting.Therefore,inplasticvessels,etc.,useaninstru-mentversionwithflange(fromDN50)orplaceametalsheet(ø>200mm/8in)beneaththeprocessfittingwhenscrewingitin.Makesurethattheplatehasdirectcontactwiththeprocessfitting.When using the probes without metal vessel wall, e.g. in plastic vessels,themeasuredvaluecanbeinfluencedbystrongelectromag-neticfields(emittedinterferenceaccordingtoEN61326:classA).Use a probe in coax version for applications in liquids.
Suitability for the ambient conditions
Installation position
Type of vessel
12
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
4 Mounting58879-EN
-190215
1 2
Fig. 3: Mounting in non-metallic vessel1 Flange2 Metal sheet
Concrete vesselWhen mounting in thick concrete ceilings, NivoGuide 3100 should be mountedfrontflushtotheloweredge.Inconcretesilos,thedistanceto the wall should be at least 500 mm (20 in).
ø >160�mm(ø >6.3")
Fig. 4: Mounting in concrete silo
Ifpossible,avoidsockets.Mountthesensorflushwiththevesseltop.If this is not possible, use short sockets with small diameter.
Mounting socket
13
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
4 Mounting58
879-
EN-1
9021
5
Higher sockets or sockets with a bigger diameter can generally be used. They can, however, increase the upper blocking distance (dead band). Check if this is relevant for your measurement.In such cases, always carry out a false signal suppression after mounting.Youcanfindfurtherinformationunder"Setup procedure".
hd
d hDN25 ... DN150
> DN150 ... DN200≤ 150 mm (5.91")≤ 100 mm (3.94")
Fig. 5: Mounting socket
Whenweldingthesocket,makesurethatthesocketisflushwiththevessel top.
1 2
Fig.6:Socketmustbeinstalledflush1 Unfavourable mounting2 Socketflush-optimummounting
Before beginning the welding work, remove the electronics module from the sensor. By doing this, you avoid damage to the electronics through inductive coupling.
Donotmounttheinstrumentsinorabovethefillingstream.Makesurethatyoudetecttheproductsurface,nottheinflowingproduct.
Welding work
Inflowingmedium
14
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
4 Mounting58879-EN
-190215
Fig.7:Mountingofthesensorwithinflowingmedium
The reference plane for the measuring range of the sensors is the sealingsurfaceofthethreadorflange.Keep in mind that a min. distance must be maintained below the refer-ence plane and possibly also at the end of the probe - measurement in these areas is not possible (dead band). The length of the cable can be used all the way to the end only when measuring conductive products.Theseblockingdistancesfordifferentmediumsarelistedin chapter "Technical data". Keep in mind for the adjustment that the default setting for the measuring range refers to water.
Theprocessfittingmustbesealedifthereisgaugeorlowpressureinthe vessel. Before use, check if the seal material is resistant against the measured product and the process temperature.Themax.permissiblepressureisspecifiedinchapter"Technical data" or on the type label of the sensor.
If there is a risk of the cable probe touching the vessel wall during operation due to product movements or agitators, etc., the measuring probeshouldbesecurelyfixed.There is an inside thread (M12) in the gravity weight, e.g. for an eye-bolt (optional).Make sure that the probe cable is not completely taut. Avoid tensile loads on the cable.Avoidundefinedvesselconnections,i.e.theconnectionmustbeeithergroundedreliablyorisolatedreliably.Anyundefinedchangeofthis condition can lead to measurement errors.Keep in mind that measurement is not possible below the fastening point.
Measuring range
Pressure
Fasten
15
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
5 Connecting to power supply58
879-
EN-1
9021
5
5 Connecting to power supply
5.1 Preparing the connectionAlways keep in mind the following safety instructions:
• Carryoutelectricalconnectionbytrained,qualifiedpersonnelauthorised by the plant operator
• If overvoltage surges are expected, overvoltage arresters should be installed
Warning:Connect only in the complete absence of line voltage.
Power supply and current signal are carried on the same two-wire cable.Theoperatingvoltagecandifferdependingontheinstrumentversion.Thedataforpowersupplyarespecifiedinchapter"Technical data".Provide a reliable separation between the supply circuit and the mains circuits according to DIN EN 61140 VDE 0140-1.Power the instrument via an energy-limited circuit acc. to IEC 61010-1, e.g. via Class 2 power supply unit.Keepinmindthefollowingadditionalfactorsthatinfluencetheoperat-ing voltage:
• Lower output voltage of the power supply unit under nominal load (e.g. with a sensor current of 20.5 mA or 22 mA in case of fault)
• Influenceofadditionalinstrumentsinthecircuit(seeloadvaluesinchapter "Technical data")
The instrument is connected with standard two-wire cable without screen. If electromagnetic interference is expected which is above the test values of EN 61326-1 for industrial areas, screened cable should be used.Use cable with round cross section for instruments with housing and cable gland. Use a cable gland suitable for the cable diameter to ensurethesealeffectofthecablegland(IPprotectionrating).We generally recommend the use of shielded cable for HART multidrop mode.
Metric threadsIn the case of instrument housings with metric thread, the cable glands are screwed in at the factory. They are sealed with plastic plugs as transport protection.You have to remove these plugs before electrical connection.
NPT threadIn the case of instrument housings with self-sealing NPT threads, it is not possible to have the cable entries screwed in at the factory. The free openings for the cable glands are therefore covered with red dust protection caps as transport protection.
Safety instructions
Voltage supply
Connection cable
Cable glands
16
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
5 Connecting to power supply58879-EN
-190215
Prior to setup you have to replace these protective caps with ap-proved cable glands or close the openings with suitable blind plugs.On plastic housings, the NPT cable gland or the Conduit steel tube must be screwed into the threaded insert without grease.Max. torque for all housings, see chapter "Technical data".
If screened cable is required, we recommend connecting the cable screening on both ends to ground potential. In the sensor, the cable screening must be connected directly to the internal ground terminal. The ground terminal on the outside of the housing must be connected to the ground potential (low impedance).In Ex systems, the grounding is carried out according to the installa-tion regulations.
In electroplating plants as well as plants for cathodic corrosion protec-tionitmustbetakenintoaccountthatsignificantpotentialdifferencesexist. This can lead to unacceptably high currents in the cable screen if it is grounded at both ends.
Information:Themetallicpartsoftheinstrument(processfitting,sensor,concen-tric tube, etc.) are connected with the internal and external ground terminal on the housing. This connection exists either directly via the conductive metallic parts or, in case of instruments with external electronics, via the screen of the special connection cable.Youcanfindspecificationsonthepotentialconnectionsinsidetheinstrument in chapter "Technical data".
5.2 ConnectingThe voltage supply and signal output are connected via the spring-loaded terminals in the housing.Connection to the display and adjustment module or to the interface adapter is carried out via contact pins in the housing.
Information:The terminal block is pluggable and can be removed from the electronics. To do this, lift the terminal block with a small screwdriver and pull it out. When reinserting the terminal block, you should hear it snap in.
Proceed as follows:1. Unscrew the housing lid2. If a display and adjustment module is installed, remove it by turn-
ing it slightly to the left3. Loosen compression nut of the cable gland and remove blind
plug4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires5. Insert the cable into the sensor through the cable entry
Cable screening and grounding
Connection technology
Connection procedure
17
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
5 Connecting to power supply58
879-
EN-1
9021
5
1 2
Fig. 8: Connection steps 5 and 61 Single chamber housing2 Double chamber housing
6. Insert the wire ends into the terminals according to the wiring plan
Information:Solidcoresaswellasflexiblecoreswithwireendsleevesareinsert-eddirectlyintotheterminalopenings.Incaseofflexiblecoreswithoutend sleeves, press the terminal from above with a small screwdriver, the terminal opening is then free. When the screwdriver is released, the terminal closes again.Youcanfindfurtherinformationonthemax.wirecross-sectionunder"Technical data - Electromechanical data".
7. Check the hold of the wires in the terminals by lightly pulling on them
8. Connect the screen to the internal ground terminal, connect the external ground terminal to potential equalisation
9. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable
10. Reinsert the display and adjustment module, if one was installed11. Screw the housing lid back onTheelectricalconnectionisfinished.
5.3 Wiring plan, single chamber housingThe following illustration applies to the non-Ex as well as to the Ex-ia version.
18
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
5 Connecting to power supply58879-EN
-190215
51 2+( ) (-) 6 7 8
4...20mA
2
3
41
Fig. 9: Electronics and connection compartment - single chamber housing1 Voltage supply, signal output2 For display and adjustment module or interface adapter3 For external display and adjustment unit4 Ground terminal for connection of the cable screening
5.4 Wiring plan, double chamber housingThe following illustrations apply to the non-Ex as well as to the Ex-ia version.
5 6 7 8
4...20mA
1 2+( ) (-)
2
1 1
Fig. 10: Electronics compartment - double chamber housing1 Internal connection to the connection compartment2 For display and adjustment module or interface adapter
Electronics and connec-tion compartment
Electronics compartment
19
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
5 Connecting to power supply58
879-
EN-1
9021
5
51 2+( ) (-) 6 7 8
4...20mA Display
2
3
41
Fig. 11: Connection compartment - double chamber housing1 Voltage supply, signal output2 For display and adjustment module or interface adapter3 For external display and adjustment unit4 Ground terminal for connection of the cable screening
5.5 Switch-on phaseAfter connecting the instrument to voltage supply or after a voltage recurrence, the instrument carries out a self-check for approx. 30 s:
• Internal check of the electronics• Indication of the instrument type, hardware and software version,
measurement loop name on the display• Indication of the status message "F 105 Determine measured
value" on the display• The output signal jumps to the set fault current
As soon as a plausible measured value is found, the corresponding current is output to the signal cable. The value corresponds to the actual level as well as the settings already carried out, e.g. factory setting.
Connection compartment
20
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58879-EN
-190215
6 Set up with the display and adjustment module
6.1 Insert display and adjustment moduleThe display and adjustment module can be inserted into the sensor andremovedagainatanytime.Youcanchooseanyoneoffourdiffer-ent positions - each displaced by 90°. It is not necessary to interrupt the power supply.Proceed as follows:1. Unscrew the housing lid2. Place the display and adjustment module on the electronics in the
desired position and turn it to the right until it snaps in.3. Screw housing lid with inspection window tightly back onDisassembly is carried out in reverse order.The display and adjustment module is powered by the sensor, an ad-ditional connection is not necessary.
Fig. 12: Installing the display and adjustment module in the electronics compart-ment of the single chamber housing
21
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58
879-
EN-1
9021
5
1 2
Fig. 13: Installing the display and adjustment module in the double chamber housing1 In the electronics compartment2 In the connection compartment
Note:Ifyouintendtoretrofittheinstrumentwithadisplayandadjustmentmodule for continuous measured value indication, a higher lid with an inspection glass is required.
6.2 Adjustment system
1
2
Fig. 14: Display and adjustment elements1 LC display2 Adjustment keys
• [OK] key:Key functions
22
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58879-EN
-190215
– Move to the menu overview – Confirmselectedmenu – Edit parameter – Save value
• [->] key: – Change measured value presentation – Select list entry – Select editing position
• [+] key: – Change value of the parameter
• [ESC] key: – Interrupt input – Jump to next higher menu
The sensor is operated via the four keys of the display and adjustment module. The individual menu items are shown on the LC display. You canfindthefunctionoftheindividualkeysinthepreviousillustration.When the [+] and [->] keys are pressed quickly, the edited value, or the cursor, changes one value or position at a time. If the key is pressed longer than 1 s, the value or position changes continuously.When the [OK] and [ESC] keys are pressed simultaneously for more than 5 s, the display returns to the main menu. The menu language is then switched over to "English".Approx. 60 minutes after the last pressing of a key, an automatic reset tomeasuredvalueindicationistriggered.Anyvaluesnotconfirmedwith [OK] will not be saved.
After switching on, the NivoGuide 3100 carries out a short self-test where the device software is checked.The output signal transmits a fault signal during the switch-on phase.The following information is displayed on the display and adjustment module during the startup procedure:
• Instrument type• Device name• Software version (SW-Ver)• Hardware version (HW-Ver)
With the [->]keyyoucanmovebetweenthreedifferentindicationmodes.Inthefirstview,theselectedmeasuredvalueisdisplayedinlargedigits.In the second view, the selected measured value and a correspond-ing bar graph presentation are displayed.In the third view, the selected measured value as well as a second selectable value, e.g. the temperature, are displayed.
Adjustment system
Switch-on phase
Measured value indica-tion
23
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58
879-
EN-1
9021
5
6.3 Parameter adjustment - Quick setupTo quickly and easily adapt the sensor to the application, select the menu item "Quick setup" in the start graphic on the display and adjustment module.
The following steps for the quick setup can be reached also in the "Extended adjustment".
• Instrument address• Measurement loop name• Medium type (optional)• Application• Max. adjustment• Min. adjustment• False signal suppression
Youcanfindthedescriptionoftheindividualmenuitemsinthefollow-ing chapter "Parameter adjustment - Extended adjustment".
6.4 Parameter adjustment - Extended adjustmentFor technically demanding measuring points, you can carry out extended settings in "Extended adjustment".
Themainmenuisdividedintofivesectionswiththefollowingfunc-tions:
Setup: Settings, e.g. measurement loop name, medium, vessel, adjustment, signal output, device unit, false signal suppression, linearizationcurveDisplay: Settings, e.g., for language, measured value display, lightingDiagnosis: Information, e.g. on instrument status, pointer, measure-ment reliability, simulation, echo curveAdditional adjustments: Reset, date/time, reset, copy function
Quick setup
Main menu
24
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58879-EN
-190215
Info: Instrument name, hardware and software version, date of manu-facture, instrument features
Note:For optimum adjustment of the measuring point, the individual sub-menu items in the main menu item "Setup" should be selected one after the other and provided with the correct parameters. If possible, go through the items in the given sequence.The procedure is described below.
The following submenu points are available:
The submenu points are described below.
Here you can assign a suitable measurement loop name. Push the "OK" key to start the editing. With the "+" key you change the sign and with the "->" key you jump to the next position.You can enter names with max. 19 characters. The character set comprises:
• Capital letters from A … Z• Numbers from 0 … 9• Special characters + - / _ blanks
In this menu item you select the distance unit and the temperature unit.
For the distance units you can choose between m, mm and ft and for the temperature units °C, °F and K.
In this menu item you can enter the probe length or have the length determined automatically by the sensor system.When choosing "Yes", then the probe length will be determined automatically. When choosing "No", you can enter the probe length manually.
Setup - Measurement loop name
Setup - Units
Setup - Probe length
25
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58
879-
EN-1
9021
5
In this menu item you can select which type of medium you want to measure. You can choose between liquid or bulk solid.
In this menu item you can select the application. You can choose between metallic or non-metallic vessels.
Note:Theselectionoftheapplicationhasaconsiderableinfluenceonallother menu items. Keep in mind that as you continue with the param-eter adjustment, individual menu items are only optionally available.
You have the option of choosing the demonstration mode. This mode is only suitable for test and demonstration purposes. In this mode, the sensor ignores the parameters of the application and reacts immedi-ately to any change.
Inthismenuitem,youcandefinethetypeofmedium(product).This menu item is only available if you have selected level measure-ment under the menu item "Application".
You can choose between the following medium types:
Dielectric con-stant
Medium type Examples
> 3 Cereals,flour Allkindofcereals,wheatflour
1.5 … 3 Granules, cement Lime, gypsum, cement
< 1.5 Dusts, wood chips Wood chips, sawdust
In this menu item, you can enter the max. adjustment for the level.
Adjust the requested percentage value with [+] and store with [OK].
Setup - Application - Type of medium
Setup - Application
Setup - Medium, dielec-tric constant
Setup - Max. adjustment Level
26
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58879-EN
-190215
Enter the appropriate distance value in m (corresponding to the percentage value) for the full vessel. The distance refers to the sensor referenceplane(sealsurfaceoftheprocessfitting).Keepinmindthatthe max. level must lie below the dead band.
In this menu item, you can enter the min. adjustment for the level.
Adjust the requested percentage value with [+] and store with [OK].
Enter the suitable distance value in m for the empty vessel (e.g. distancefromtheflangetotheprobeend)correspondingtotheper-centage value. The distance refers tot he sensor reference plane (seal surfaceoftheprocessfitting).
Todampprocess-dependentmeasuredvaluefluctuations,setanintegration time of 0 … 999 s in this menu item.
The default setting is a damping of 0 s.
A linearisation is necessary for all vessels in which the vessel volume doesnotincreaselinearlywiththelevel-e.g.ahorizontalcylindri-cal or spherical tank, when the indication or output of the volume is required. Corresponding linearisation curves are preprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume.The linearisation applies to the measured value indication and the current output. By activating the appropriate curve, the volume per-centage of the vessel is displayed correctly. If the volume should not be displayed in percent but e.g. in l or kg, a scaling can be also set in the menu item "Display".
Setup - Min. adjustment Level
Setup - Damping
Setup - Linearisation
27
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58
879-
EN-1
9021
5
Warning:If a linearisation curve is selected, the measuring signal is no longer necessarilylineartothefillingheight.Thismustbeconsideredbytheuser especially when setting the switching point on the limit signal transmitter.In the following, you have to enter the values for your vessel, for example the vessel height and the socket correction.
For non-linear vessel forms, enter the vessel height and the socket correction.For the vessel height, you have to enter the total height of the vessel.For the socket correction you have to enter the height of the socket above the upper edge of the vessel. If the socket is lower than the up-per edge of the vessel, this value can also be negative.
+ h
D
- h
Fig. 15: Vessel height and socket correction valueD Vessel height+h Positive socket correction value-h Negative socket correction value
In the menu item "Current output mode" you determine the output characteristics and reaction of the current output in case of fault.
Setup - Current output, mode
28
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58879-EN
-190215
The default setting is output characteristics 4 … 20 mA, fault mode < 3.6 mA.
In the menu item "Current output Min./Max.", you determine the reac-tion of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.
Thefollowingcircumstancescauseinterferingreflectionsandcaninfluencethemeasurement:
• High mounting sockets• Vessel internals such as struts• Deflectors,etc.Note:A false signal suppression is only recommended with liquid applica-tions.
A false signal suppression detects, marks and saves these false signals to ensure that they are ignored in the level measurement.This should be done with the lowest possible level so that all potential interferingreflectionscanbedetected.Proceed as follows:
Enter the actual distance from the sensor to the product surface.
All interfering signals in this section are detected by the sensor and stored.Keep in mind that with covered probe only false signals in the uncov-ered area of the probe are detected.
Note:Check the distance to the product surface, because if an incorrect (too large) value is entered, the existing level will be saved as a false signal. The level would then no longer be detectable in this area.
If a false signal suppression has already been created in the sensor, the following menu window appears when selecting "False signal suppression":
Setup - Current output Min./Max.
Setup - False signal sup-pression
29
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58
879-
EN-1
9021
5
The instrument carries out an automatic false signal suppression as soon as the probe is uncovered. The false signal suppression is always updated.The menu item "Delete" is used to completely delete an already cre-ated false signal suppression. This is useful if the saved false signal suppression no longer matches the metrological conditions in the vessel.
In the menu item "Lock/unlock adjustment", you can protect the sen-sorparametersagainstunauthorizedorinadvertentmodification.ThePIN is activated/deactivated permanently.With active PIN, only the following adjustment functions are possible without entering a PIN:
• Select menu items and show data• Read data from the sensor into the display and adjustment module
Caution:In delivery status, the PIN is 0000.CallourservicedepartmentifyouhavemodifiedandforgottenthePIN.
In the main menu point "Display", the individual submenu points should be selected one after the other and provided with the correct parameters to ensure the optimum adjustment of the display options. The procedure is described in the following.The following submenu points are available:
The submenu points are described below.
This menu item enables the setting of the requested national lan-guage.
In delivery status, the sensor is set to English.
Lock/unlock setup - Ad-justment
Display
Display - Menu language
30
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58879-EN
-190215
Inthismenuitem,youdefinetheindicationofthemeasuredvalueonthedisplay.Youcandisplaytwodifferentmeasuredvalues.Inthismenuitem,youdefinemeasuredvalue1.
The default setting for the displayed value 1 is "Filling height Level".
Inthismenuitem,youdefinetheindicationofthemeasuredvalueonthedisplay.Youcandisplaytwodifferentmeasuredvalues.Inthismenuitem,youdefinemeasuredvalue2.
The default setting for the displayed value 2 is the electronics tem-perature.
Inthismenuitem,youdefinethedisplayformatofthemeasuredvalueonthedisplay.Youcandefinedifferentdisplayformatsforthetwo measured values.Youcanthusdefinethenumberofdecimalpositionsthemeasuredvalue is displayed with.
The default setting for the display format is "Automatic".
Theintegratedbackgroundlightingcanbeswitchedoffviatheadjustment menu. The function depends on the strength of the supply voltage, see "Technical data".To maintain the function of the device, the lighting is temporarily switchedoffifthepowersupplyisinsufficient.
In delivery status, the lighting is switched on.
In this menu item, the device status is displayed.When the instrument displays a failure message, you can here get detailed information on the failure reason.
Display - Displayed value 1
Display - Displayed value 2
Display - Display format
Display - Backlight
Diagnostics - Device status
31
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58
879-
EN-1
9021
5
The respective min. and max. measured value is saved in the sen-sor. The two values are displayed in the menu item "Peak values, distance".
In another window you can reset the peak value.
The respective min. and max. measured values are saved in the sensor. The two values are displayed in the menu item "Peak values, measurement reliability".Themeasurementcanbeinfluencedbytheprocessconditions.Inthis menu item, the measurement reliability of the level measure-ment is displayed in mV. The higher the value, the more reliable the measurement.
In another window you can reset the peak value.
The respective min. and max. measured values are saved in the sensor. The values are displayed in the menu item "Peak values Ad-ditional".This menu item displays the peak values of the electronics tempera-ture as well as the dielectric constant.
In another window you can carry out a reset of the two peak values separately.
Information:Ifoneofthedisplayvaluesflashes,thereisactuallynovalidvalueavailable.
Diagnostics - Peak val-ues, Distance
Diagnostics - Peak values measurement reliability
Diagnostics - Peak val-ues, Additional
32
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58879-EN
-190215
The menu item "Echo curve" shows the signal strength of the echoes over the measuring range in V. The signal strength enables an evalua-tion of the quality of the measurement.
Withthefollowingfunctionsyoucanzoompartsectionsoftheechocurve.
• "X-Zoom": Zoom function for the meas. distance• "Y-Zoom":1,2,5and10xsignalmagnificationin"V"• "Unzoom":Resetthepresentationtothenominalmeasuringrange
withoutmagnification
In this menu item you can simulate measured values via the current output. This allows the signal path to be tested, e.g. through down-stream indicating instruments or the input card of the control system.
Select the requested simulation variable and set the requested value.
Caution:During simulation, the simulated value is output as 4 … 20 mA current value and digital HART signal.
Push the [ESC] key to deactivate the simulation.
Information:The simulation is terminated automatically 60 minutes after the activa-tion of the simulation.
With the menu item "Setup" the echo curve it is possible to save at the time of setup. This is generally recommended; for using the Asset Management functions it is necessary. If possible, the curve should be saved with a low level in the vessel.This allows you to detect signal changes over the operating time.
Diagnostics - Echo curve
Diagnosis - Simulation
Diagnostics - Echo curve memory
33
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58
879-
EN-1
9021
5
The function "Echo curve memory" enables storing echo curves of the measurement.Under the sub-menu item "Echo curve memory" you can store the current echo curve.
In this menu item, the internal clock of the sensor is set.
After a reset, certain parameter adjustments made by the user are reset.
Note:After this menu window, the reset process is carried out. No further safety inquiry follows.
The following reset functions are available:Delivery status: Restores the parameter settings at the time of ship-mentfromthefactory,incl.order-specificsettings.Anystoredfalsesignal suppression or user-programmed linearisation curve, as well as the measured value memory, are deleted.Basic settings: Restores the parameter settings, incl. special param-eters, to the default values of the respective instrument. Any stored false signal suppression or user-programmed linearisation curve, as well as the measured value memory, are deleted.The following table shows the default values of the instrument. De-pending on the instrument version or application, all menu items may notbeavailableorsomemaybedifferentlyassigned:
Additional settings - Date/Time
Additional settings - Reset
34
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58879-EN
-190215
Menu - Setup
Menu Menu item Default value
Setup Lock adjustment Released
Measurement loop name Sensor
Units Distanceunit:order-specificTemperatureunit:order-specific
Probe length Länge der Messsonde factory set-ting
Type of medium Bulk solid
Application Level in the metallic vessel
Medium, dielectric constant Cereals,flour,sand/>3
Superimposed gas phase Yes
Setup Max. adjustment - Level 100 %
Max. adjustment - Level Distance: 0.000 m(d) - note block-ing distances
Min. adjustment - Level 0 %
Min. adjustment - Level Distance: Probe length - take dead band into account
Setup Integration time - Level 0.0 s
Linearisation type Linear
Linearisation - Socket correction 0 mm
Linearisation - Vessel height Probe length
Setup Scaling variable - Level Volume in l
Scaling unit - Level Litres
Scaling format - Level Without decimal positions
Scaling level - 100 % corresponds to 100
Scaling level - 0 % corresponds to 0
Setup Current output, output variableFirst HART variable (PV)
Lin. percent - Level
Current output - Output characteristics 0 … 100 % correspond to 4 … 20 mA
Current output - Reaction in case of fault ≤3.6mA
Current output - Min. 3.8 mA
Current output - Max. 20.5 mA
Current output 2 - Output variableSecond HART variable (SV)
Distance - Level
Current output 2 - Output characteristics 0 … 100 % correspond to 4 … 20 mA
Current output 2 - Reaction in case of fault ≤3.6mA
Current output - Min. 3.8 mA
Current output - Max. 20.5 mA
35
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58
879-
EN-1
9021
5
Menu Menu item Default value
Setup Third HART variable (TV) Measurement reliability, level
Fourth HART variable (QV) Electronics temperature
Menu - Display
Menu Menu item Default value
Display Language Selected language
Displayed value 1 Filling height Level
Displayed value 2 Electronics temperature
Display format 1 Automatically
Display format 2 Automatically
Backlight Switched on
Menu - Additional adjustments
Menu Menu item Default value
Additional adjustments PIN 0000
Date Actual date
Time Actual time
Time - Format 24 hours
Probe type Device-specific
The instrument settings are copied with this function. The following functions are available:
• Read from sensor: Read data from sensor and save in the display and adjustment module
• Write to sensor: Save data from the display and adjustment mod-ule back into the sensor
The following data or settings for adjustment of the display and ad-justment module are saved:
• All data of the menu "Setup" and "Display"• In the menu "Additional adjustments" the items "Reset, Date/Time"• Special parameters
The copied data are permanently saved in an EEPROM memory in the display and adjustment module and remain there even in case of power failure. From there, they can be written into one or more sen-sors or kept as backup for a possible electronics exchange.
Additional settings - Copy instrument settings
36
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58879-EN
-190215
Note:Before the data are stored in the sensor, a check is carried out to determineifthedatafitthesensor.Ifthedatadonotfit,afaultsignalis triggered or the function is blocked. When data are being written into the sensor, the display shows which instrument type the data originate from and which TAG-no. this sensor had.
Tip:We recommend to save the instrument adjustments. In case of an electronics exchange the saved parameter adjustment data relieve this process.
Since scaling is very extensive, scaling of the level value was divided into two menu items.
In menu item "Scaling variable"youdefinethescalingvariableandthe scaling unit for the level value on the display, e.g. volume in l.
In menu item "Scaling format"youdefinethescalingformatonthedisplay and the scaling of the measured level value for 0 % and 100 %.
Since scaling is very extensive, scaling of the level value was divided into two menu items.
In menu item "Current output, variable" you specify which measured variable the current output refers to.
Additional settings - Scal-ing level
Additional settings - Scaling level - Scaling variable
Additional settings - Scal-ing level - Scaling format
Additional settings - Cur-rent output
Additional settings - Current output - Current output, meas. variable
37
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58
879-
EN-1
9021
5
In menu item "Current output, adjustment" you can assign a respec-tive measured value to the current output.
Inthismenuitemyoucanselectthetypeandsizeofyourprobefroma list of all possible probes. This is necessary to adapt the electronics optimally to the probe.
ThesensorofferstheHARTmodes"Analogue current output" and "Fix current (4 mA)". In this menu item you determine the HART mode and enter the address with Multidrop mode.In the mode "Fixed current output" up to 63 sensors can be operated on one two-wire cable (Multidrop operation). An address between 0 and 63 must be assigned to each sensor.If you select the function "Analogue current output" and also enter an address number, you can output a 4 … 20 mA signal in Multidrop mode.In the mode "Fixed current (4 mA)"afixed4mAsignalisoutputinde-pendently of the actual level.
The default setting is "Analogue current output" and the address 00.
In this menu item you gain access to the protected area where you can enter special parameters. In exceptional cases, individual parameterscanbemodifiedinordertoadaptthesensortospecialrequirements.Change the settings of the special parameters only after having con-tactedourservicestaff.
Additional settings - Current output - Current output, adjustment
Additional settings - Probe type
Additional settings - HART mode
Additional settings - Spe-cial parameters
38
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module58879-EN
-190215
In this menu, you read out the instrument name and the instrument serial number.
In this menu item, the hardware and software version of the sensor is displayed.
In this menu item, the date of factory calibration of the sensor as well as the date of the last change of sensor parameters are displayed via the display and adjustment module.
In this menu item, the features of the sensor such as approval, pro-cessfitting,seal,measuringrange,electronics,housingandothersare displayed.
Example for displayed sensor features.
6.5 Saving the parameterisation dataWe recommended writing down the adjustment data, e.g. in this op-erating instructions manual, and archiving them afterwards. They are thus available for multiple use or service purposes.
If the instrument is equipped with a display and adjustment module, the parameter adjustment data can be saved therein. The procedure is described in menu item "Copy device settings".
Info - Instrument name
Info - Instrument version
Info - Factory calibration date
Info - Sensor character-istics
On paper
In the display and adjust-ment module
39
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
7 Diagnostics and servicing58
879-
EN-1
9021
5
7 Diagnostics and servicing
7.1 MaintenanceIf the device is used properly, no special maintenance is required in normal operation.
The cleaning helps that the type label and markings on the instrument are visible.Take note of the following:
• Use only cleaning agents which do not corrode the housings, type label and seals
• Use only cleaning methods corresponding to the housing protec-tion rating
7.2 Status messagesThe instrument features self-monitoring and diagnostics according to NE 107 and VDI/VDE 2650. In addition to the status messages in the following tables there are more detailed error messages available under the menu item "Diagnostics" via the display and adjustment module.
The status messages are divided into the following categories:
• Failure• Function check• Outofspecification• Maintenance requirement
and explained by pictographs:
41 2 3Fig. 16: Pictographs of the status messages1 Failure - red2 Outofspecification-yellow3 Function check - orange4 Maintenance - blue
Failure: Due to a malfunction in the instrument, a fault message is output.This status message is always active. It cannot be deactivated by the user.Function check: The instrument is being worked on, the measured value is temporarily invalid (for example during simulation).This status message is inactive by default.Outofspecification: The measured value is unreliable because an instrumentspecificationwasexceeded(e.g.electronicstemperature).
Maintenance
Cleaning
Status messages
40
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
7 Diagnostics and servicing58879-EN
-190215
This status message is inactive by default.Maintenance:Duetoexternalinfluences,theinstrumentfunctionislimited.Themeasurementisaffected,butthemeasuredvalueisstill valid. Plan in maintenance for the instrument because a failure is expected in the near future (e.g. due to buildup).This status message is inactive by default.
CodeText mes-sage
Cause Rectification DevSpec State in CMD 48
F013no measured value avail-able
• Sensor does not detect an echo during operation
• Process component or probe contaminated or defective
• Check for correct mounting and/or parameter settings
• Clean or exchange process component or probe
Bit 0 of Byte 0 … 5
F017Adjustment span too small
• Adjustmentnotwithinspecifi-cation
• Change adjustment accord-ingtothelimitvalues(differ-ence between min. and max. ≥10mm)
Bit 1 of Byte 0 … 5
F025Error in the linearizationtable
• Index markers are not con-tinuously rising, for example illogical value pairs
• Check values of the lineari-zationtable
• Delete/create a new lineari-zationtable
Bit 2 of Byte 0 … 5
F036No operable software
• Failed or interrupted software update
• Repeat software update• Check electronics version• Exchanging the electronics• Send instrument for repair
Bit 3 of Byte 0 … 5
F040Error in the electronics
• Hardware defect • Exchanging the electronics• Send instrument for repair
Bit 4 of Byte 0 … 5
F041Probe loss
• Probe mechanically defec-tive
• Check probe and exchange, if necessary
Bit 13 of Byte 0 … 5
F080General soft-ware error
• General software error • Disconnect operating voltage briefly
Bit 5 of Byte 0 … 5
F105Measured value is deter-mined
• The instrument is still in the start phase, the measured value could not yet be determined
• Wait for the end of the switch-on phase
• Duration depending on the version and parameter adjustment max. 5 min.
Bit 6 of Byte 0 … 5
F260Error in the calibration
• Error in the calibration car-ried out in the factory
• Error in the EEPROM
• Exchanging the electronics• Send instrument for repair
Bit 8 of Byte 0 … 5
F261Error in the instrument settings
• Error during setup• Error when carrying out a
reset• False signal suppression
faulty
• Carry out a reset• Repeat setup
Bit 9 of Byte 0 … 5
Failure
41
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
7 Diagnostics and servicing58
879-
EN-1
9021
5
CodeText mes-sage
Cause Rectification DevSpec State in CMD 48
F264Installation/Setup error
• Error during setup • Check for correct mounting and/or parameter settings
• Check probe length
Bit 10 of Byte 0 … 5
F265Measurement function dis-turbed
• Sensor no longer carries out a measurement
• Carry out a reset• Disconnect operating voltage briefly
Bit 11 of Byte 0 … 5
F267No executable sensor soft-ware
• Sensor cannot start • Exchanging the electronics• Send instrument for repair
No communication possible
Tab. 5: Error codes and text messages, information on causes as well as corrective measures
CodeText mes-sage
Cause Rectification DevSpecState in CMD 48
C700Simulation ac-tive
• A simulation is active • Finish simulation• Wait for the automatic end
after 60 mins.
"Simulation Active" in "Stand-ardizedStatus0"
Tab. 6: Error codes and text messages, information on causes as well as corrective measures
CodeText message
Cause Rectification DevSpecState in CMD 48
S600Impermissible electronics tem-perature
• Temperature of the processing electronicsinthenon-specifiedsection
• Check ambient temperature• Insulate electronics• Use instrument with higher tem-
perature range
Bit 8 of Byte 14 … 24
S601Overfilling
• Level echo in the close range not available
• Reduce level• 100 % adjustment: Increase value• Check mounting socket• Remove possible interfering
signals in the close range• Use coaxial probe
Bit 9 of Byte 14 … 24
S602Level within the search range, compensation echo
• Compensation echo superim-posed by medium
• 100 % adjustment: Increase value Bit 10 of Byte 14 … 24
S603Impermissible operating voltage
• Operatingvoltagebelowspecifiedrange
• Check electrical connection• If necessary, increase operating
voltage
Bit 11 of Byte 14 … 24
Tab. 7: Error codes and text messages, information on causes as well as corrective measures
Function check
Outofspecification
42
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
7 Diagnostics and servicing58879-EN
-190215
CodeText message
Cause Rectification DevSpecState in CMD 48
M500Error in the deliv-ery status
• The data could not be restored during the reset to delivery status
• Repeat reset• LoadXMLfilewithsensordata
into the sensor
Bit 0 of Byte 14 … 24
M501Error in the non-active line-arisation table
• Index markers are not continu-ously rising, for example illogical value pairs
• Check linearisation table• Delete table/Create new
Bit 1 of Byte 14 … 24
M504Error at a device interface
• Hardware defect • Exchanging the electronics• Send instrument for repair
Bit 4 of Byte 14 … 24
M505no measured val-ue available
• Sensor does not detect an echo during operation
• Check and correct mounting and/or parameter adjustment
Bit 5 of Byte 14 … 24
• Process component or probe contaminated or defective
• Clean or exchange process com-ponent or probe
M506Installation/Set-up error
• Error during setup • Check and correct mounting and/or parameter adjustment
• Check probe length
Bit 6 of Byte 14 … 24
M507Error in the in-strument settings
• Error during setup• Error when carrying out a reset• False signal suppression faulty
• Carry out reset and repeat setup Bit 7 of Byte 14 … 24
Tab. 8: Error codes and text messages, information on causes as well as corrective measures
7.3 Rectify faultsThe operator of the system is responsible for taking suitable meas-ures to rectify faults.
Thefirstmeasuresare:
• Evaluation of fault messages via the adjustment device• Checking the output signal• Treatment of measurement errors
Connect a multimeter in the suitable measuring range according to the wiring plan. The following table describes possible errors in the current signal and helps to eliminate them:
Error Cause Rectification
4 … 20 mA signal not sta-ble
• Fluctuations of the measured variable • Set damping via the display and adjustment module depending on the instrument
Maintenance
Reaction when malfunc-tion occurs
Procedure for fault recti-fication
Check the 4 … 20 mA signal
43
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
7 Diagnostics and servicing58
879-
EN-1
9021
5
Error Cause Rectification
4 … 20 mA signal missing • Electrical connection faulty • Check connection according to chapter "Connection steps" and if necessary, correct according to chapter "Wiring plan"
• Voltage supply missing • Check cables for breaks; repair if necessary
• Operating voltage too low or load resistance too high
• Check, adapt if necessary
Current signal greater than 22 mA or less than 3.6 mA
• Electronics module in the sensor defective
• Exchange the instrument or send it in for repair
The below tables show typical examples for application-relevant measurement errors. There are two measurement errors:
• Constant level• Filling• Emptying
The images in column "Error pattern" show the real level as a broken line and the level displayed by the sensor as a continuous line.
12
Leve
l
time0
Fig. 17: The broken line 1 shows the real level, the continuous line 2 shows the level displayed by the sensor
Note:• Wherever the sensor displays a constant value, the reason could
also be the fault setting of the current output to "Hold value"• If the level indication is too low, the reason could be a line resist-
ance that is too high
Measurement error with constant level
Fault description Cause Rectification
1. Measured value shows a too low or too high level
Leve
l
time0
• Min./max. adjustment not correct • Adapt min./max. adjustment
• Incorrect linearisation curve • Adapt linearisation curve
• Running time error (small measure-ment error close to 100 %/serious error close to 0 %)
• Repeat setup
Treatment of measure-ment errors
44
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
7 Diagnostics and servicing58879-EN
-190215
Fault description Cause Rectification
2. Measured value jumps towards 100 %
Leve
l
time0
• Due to the process, the amplitude of the product echo decreases
• A false signal suppression was not carried out
• Carry out a false signal suppression
• Amplitude or position of a false signal has changed (e.g. buildup); false sig-nal suppression no longer matches
• Determine the reason for the changed false signals, carry out false signal suppression, e.g. with buildup
Measurementerrorduringfilling
Fault description Cause Rectification
3. Measured value remains in the area of the bottom duringfilling
Leve
l
time0
• Echo from the probe end larger than the product echo, for example, with productswithεr < 2.5 oil-based, solvents, etc.
• Check parameter "Medium" and "Ves-sel height", adapt if necessary
4. Measured value remains momentarily unchanged duringfillingandthenjumpsto the correct level
Leve
l
time0
• Turbulence on the product surface, quickfilling
• Check parameters, change if neces-sary, e.g. in dosing vessel, reactor
5. Measured value jumps sporadically to 100 % dur-ingfilling
Level
time0
• Changing condensation or contamina-tion on the probe
• Carry out a false signal suppression
6. Measured value jumps to ≥100%or0mdistance
Leve
l
time0
• Level echo is no longer detected in the close range due to false signals in the close range. The sensor goes intooverfillprotectionmode.Themax.level (0 m distance) as well as the statusmessage"Overfillprotection"are output.
• Eliminate false signals in the close range
• Check installation conditions• Ifpossible,switchoffthefunction"Overfillprotection"
45
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
7 Diagnostics and servicing58
879-
EN-1
9021
5
Measurement error during emptying
Fault description Cause Rectification
7. Measured value remains unchanged in the close range during emptying
Leve
l
time0
• False signal larger than the level echo• Level echo too small
• Eliminate false signals in the close range
• Remove contamination on the probe. After having removed the source of the false signals, the false signal suppres-sion must be deleted.
• Carry out a new false signal suppres-sion
8. Measured value remains reproducible in one position during emptying
Leve
l
time0
• Stored false signals in this position are larger than the level echo
• Delete false signal suppression• Carry out a new false signal suppres-
sion
Depending on the reason for the fault and the measures taken, the steps described in chapter "Setup" must be carried out again or must be checked for plausibility and completeness.
7.4 Exchanging the electronics moduleIf the electronics module is defective, it can be replaced by the user.In Ex applications, only instruments and electronics modules with ap-propriate Ex approval may be used.
If there is no electronics module available on site, the electronics module can be ordered through the agency serving you. The electron-icsmodulesareadaptedtotherespectivesensoranddifferinsignaloutput or voltage supply.The new electronics module must be loaded with the default settings of the sensor. These are the options:
• In the factory• Or on site by the user
In both cases, the serial number of the sensor is needed. The serial numbers are stated on the type label of the instrument, on the inside of the housing as well as on the delivery note.Whenloadingonsite,theorderdatamustfirstbedownloadedfromthe Internet (see operating instructions "Electronics module").
Caution:Allapplication-specificsettingsmustbeenteredagain.That'swhyyouhave to carry out a fresh setup after exchanging the electronics.Ifyousavedtheparametersettingsduringthefirstsetupofthesen-sor, you can transfer them to the replacement electronics module. A fresh setup is then not necessary.
Reaction after fault recti-fication
46
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
7 Diagnostics and servicing58879-EN
-190215
7.5 Exchange or shorten cableThe cable (meas. part) of the probe can be exchanged, if necessary. To loosen the meas. cable you need a fork spanner with spanner width 13.1. Loosenthemeasuringcablebyapplyingaforkspannertotheflat
surfaces (SW 13), provide counterforce with another fork spanner (SW 13)
2. Screw out the loosened measuring cable by hand.3. Place the enclosed new double washer onto the thread.
Caution:Make sure that the two components of the double washer remain together.
4. Screw the new measuring cable carefully by hand onto the thread ontheprocessfitting.
5. Exert counterforce with the second fork spanner and tighten themeasuringcableontheflatsurfaceswithatorqueof20Nm(15 lbf ft).
Fig. 26: Exchanging the measuring cable
Information:Pleasemaintainthespecifiedtorquesothatthemax.tensilestrengthof the connection remains.
6. Enter new probe length and if necessary the new probe type and then carry out a fresh adjustment (see "Setup procedure, Carry-ing out min. adjustment - Carrying out max. adjustment").
The measuring cable of the probe can be shortened individually.1. Mark the requested length with mounted measuring cable.2. Loosen the three pins on the gravity weight
Cable ø 6: hexagon 43. Remove the pins4. Pull the cable out of the gravity weight
Exchanging the cable
Shorten cable
47
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
7 Diagnostics and servicing58
879-
EN-1
9021
5
5. Shortenthecablewithacut-offwheelormetalsawatthemark-ing.Takenoteofthespecificationsinthefollowingillustrationwhen shortening the cable.
6. Shift the cable into the gravity weight (according to the drawing)Plastic coated cable: remove coating according drawing to 70 mm (2.76 in).
7. Fasten the cable with three pins, torque 20 Nm (14.75 lbf in)8. Enter new probe length and then carry out a fresh adjustment
(see "Setup procedure, Carrying out min. adjustment - Carrying out max. adjustment").
31
2 2
A B
45 m
m
(1.7
7")
150
mm
(5
.91"
)
70 m
m
(2.7
6")
150
mm
(5
.91"
)
Fig. 27: Shortening the cable probe - Cable ø 6 mm1 Threaded pins2 Thread M12 for eye-bolt
7.6 How to proceed if a repair is necessaryIf it is necessary to repair the instrument, please contact the agency serving you.
48
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
8 Dismount58879-EN
-190215
8 Dismount
8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel or pipeline, high temperatures, cor-rosive or toxic products etc.
Take note of chapters "Mounting" and "Connecting to voltage supply" and carry out the listed steps in reverse order.
8.2 DisposalThe instrument consists of materials which can be recycled by spe-cialised recycling companies. We use recyclable materials and have designed the electronics to be easily separable.
WEEE directiveThe instrument does not fall in the scope of the EU WEEE directive. Article 2 of this Directive exempts electrical and electronic equipment from this requirement if it is part of another instrument that does not fall in the scope of the Directive. These include stationary industrial plants.Pass the instrument directly on to a specialised recycling company and do not use the municipal collecting points.If you have no way to dispose of the old instrument properly, please contact us concerning return and disposal.
49
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58
879-
EN-1
9021
5
9 Supplement
9.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.4435Materials, wetted parts
Ʋ Processfitting 316L and PPS GF 40 Ʋ Process seal on the instrument side (cable/rod leadthrough)
FKM(SHSFPM70C3GLT),FFKM(Kalrez6375),EPDM (A+P 70.10-02)
Ʋ Process seal On site (instruments with thread: Klingersil C-4400 is enclosed)
Ʋ Inner conductor (up to the separation cable/rod)
316L
Ʋ Rod: ø 16 mm (0.63 in) 316L Ʋ Cable: ø 4 mm (0.157 in) 316 (1.4401) Ʋ Cable: ø 6 mm (0.236 in), PA coated Steel(galvanized),PAcoated Ʋ Cable: ø 6 mm (0.236 in) 316 (1.4401) Ʋ Cable: ø 11 mm (0.433 in), PA coated Steel(galvanized),PAcoated Ʋ Gravity weight (optionally available) 316L
Materials, non-wetted parts Ʋ Aluminium die-cast housing Aluminium die-casting AlSi10Mg, powder-coated (Basis:
Polyester) Ʋ Stainless steel housing (electropol-ished)
316L
Ʋ Second Line of Defense (optional)1) Borosilicate glass GPC 540 Ʋ Seal between housing and housing lid Silicone SI 850 R Ʋ Inspection window in housing cover (optional)
Polycarbonate (with Ex d version: glass)
Ʋ Ground terminal 316L Ʋ Cable gland PA, stainless steel, brass Ʋ Sealing, cable gland NBR Ʋ Blind plug, cable gland PA
Second Line of Defense (optional)The Second Line of Defense (SLOD) is a second level of the process separation in the form of a gas-tight feedthrough in the lower part of the housing, preventing product from penetrating into the housing.
Ʋ Supporting material 316L Ʋ Glass potting Borosilicate glass GPC 540 Ʋ Contacts Alloy C22 (2.4602) Ʋ Helium leak rate < 10-6 mbar l/s Ʋ Pressure resistance See process pressure of the sensor
1) Only with Ex-d version.
50
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58879-EN
-190215
Conductive connection Betweengroundterminal,processfittingandprobeProcessfittings
Ʋ Pipe thread, cylindrical (ISO 228 T1) G¾, G1, G1½ (DIN 3852-A) Ʋ Pipe thread, conical (ASME B1.20.1) ¾ NPT, 1 NPT, 1½ NPT Ʋ Flanges DIN from DN 25, ASME from 1"
Weight Ʋ Instrument weight (depending on processfitting)
approx. 0.8 … 8 kg (0.176 … 17.64 lbs)
Ʋ Rod: ø 16 mm (0.63 in) approx.1580g/m(17oz/ft) Ʋ Cable: ø 4 mm (0.157 in) approx.78g/m(0.84oz/ft) Ʋ Cable: ø 6 mm (0.236 in), PA coated approx.180g/m(1.9oz/ft) Ʋ Cable: ø 6 mm (0.236 in) approx.80g/m(0.86oz/ft) Ʋ Cable: ø 11 mm (0.433 in), PA coated approx.320g/m(3.44oz/ft) Ʋ Gravity weight for cable ø 4 mm (0.157 in) and ø 6 mm (0.236 in), PA coated
325g(11.46oz)
Ʋ Gravity weight for cable ø 6 mm (0.236 in) and ø 11 mm (0.433 in), PA coated
780g(27.51oz)
Probe length L (from seal surface) Ʋ Rod: ø 16 mm (0.63 in) up to 6 m (19.69 ft) Ʋ Trimming accuracy (rod) ±(1 mm + 0.05 % of the rod length) Ʋ Cable: ø 4 mm (0.157 in) up to 75 m (246.1 ft) Ʋ Cable: ø 6 mm (0.236 in), PA coated up to 65 m (213.3 ft) Ʋ Cable: ø 6 mm (0.236 in) up to 75 m (246.1 ft) Ʋ Cable: ø 11 mm (0.433 in), PA coated up to 65 m (213.3 ft) Ʋ Trimming accuracy - cable ±(2 mm + 0.05 % of the cable length)
Lateral load with rod: ø 16 mm (0.63 in) 30 Nm (22.13 lbf ft)Max. tensile load
Ʋ Cable: ø 4 mm (0.157 in) 12 KN (2698 lbf) Ʋ Cable: ø 6 mm (0.236 in), PA coated 8 KN (1798 lbf) Ʋ Cable: ø 6 mm (0.236 in) 30 KN (6744 lbf) Ʋ Cable: ø 11 mm (0.433 in), PA coated 30 KN (6744 lbf)
Thetensileforceofsolidsaresubjectofanormalfluctuationrange.Forthisreason,thedetermineddiagram value of the following diagrams must be multiplied with safety factor 2.
51
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58
879-
EN-1
9021
5
1
2A B
1
2
34
5
6
3
4
5
6
6
12
10
8
4
2
0
3
6
5
4
2
1
00 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35
Fig. 28: Max. tensile load with cereals and plastic granules - Cable: ø 4 mm (0.157 in)A CerealsB Plastic granules1 Tensile force in kN (the determined value must be multiplied with safety factor 2)2 Cable length in m3 Vessel diameter 12 m (39.37 ft)4 Vessel diameter 9 m (29.53 ft)5 Vessel diameter 6 m (19.69 ft)6 Vessel diameter 3 m (9.843 ft)
1
2C D
1
2
3
4
5
6
3
4
5
6
20
18
16
14
12
10
8
6
4
2
20
18
16
14
12
10
8
6
4
2
0 00 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35
Fig. 29: Max. tensile load with sand and cement - Cable: ø 4 mm (0.157 in)C SandD Cement1 Tensile force in kN (the determined value must be multiplied with safety factor 2)2 Cable length in m3 Vessel diameter 12 m (39.37 ft)4 Vessel diameter 9 m (29.53 ft)5 Vessel diameter 6 m (19.69 ft)6 Vessel diameter 3 m (9.843 ft)
52
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58879-EN
-190215
1
2A B
1
2
34
5
6
3
4
5
6
12
18
16
14
10
8
6
4
2
0
6
9
8
7
5
4
3
2
1
00 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35
Fig. 30: Max. tensile load with cereals and plastic granules - Cable: ø 6 mm, ø 11 mm, PA coatedA CerealsB Plastic granules1 Tensile force in kN (the determined value must be multiplied with safety factor 2)2 Cable length in m3 Vessel diameter 12 m (39.37 ft)4 Vessel diameter 9 m (29.53 ft)5 Vessel diameter 6 m (19.69 ft)6 Vessel diameter 3 m (9.843 ft)
1
2C D
3
4
5
6
2
3
4
5
6
130
25
20
15
10
5
00 5 10 15 20 25 30 35
30
25
20
15
10
5
00 5 10 15 20 25 30 35
Fig. 31: Max. tensile load with sand and cement - Cable: ø 6 mm, ø 11 mm, PA coatedC SandD Cement1 Tensile force in kN (the determined value must be multiplied with safety factor 2)2 Cable length in m3 Vessel diameter 12 m (39.37 ft)4 Vessel diameter 9 m (29.53 ft)5 Vessel diameter 6 m (19.69 ft)6 Vessel diameter 3 m (9.843 ft)
Thread in gravity weight, e.g. for eye-bolt (cable version)
M 12
Torqueforexchangeablecableorrodprobe(intheprocessfitting) Ʋ Cable: ø 4 mm (0.157 in) 8 Nm (5.9 lbf ft)
53
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58
879-
EN-1
9021
5
Ʋ Cable: ø 6 mm (0.236 in), PA coated 8 Nm (5.9 lbf ft) Ʋ Cable: ø 6 mm (0.236 in) 20 Nm (14.75 lbf ft) Ʋ Cable: ø 11 mm (0.433 in), PA coated 20 Nm (14.75 lbf ft) Ʋ Rod: ø 16 mm (0.63 in) 20 Nm (14.75 lbf ft)
Torque for NPT cable glands and Conduit tubes Ʋ Aluminium/Stainless steel housing max. 50 Nm (36.88 lbf ft)
Input variableMeasured variable Level of solidsMin. dielectric constant of the medium εr≥1.5
Output variableOutput signal 4 … 20 mA/HARTRange of the output signal 3.8 … 20.5 mA/HART (default setting)FulfilledHARTspecification 7Signal resolution 0.3 µAFault signal, current output (adjustable) Lastvalidmeasuredvalue,≥21mA,≤3.6mAMax. output current 21.5 mAStarting current ≤10mAfor5msafterswitchingon,≤3.6mALoad see load under Power supplyDamping (63 % of the input variable), adjustable
0 … 999 s
HART output values according to HART 7 (default setting)2)
Ʋ First HART value (PV) Linearised percentage value, level Ʋ Second HART value (SV) Distance to the level Ʋ Third HART value (TV) Measurement reliability, level Ʋ Fourth HART value (QV) Electronics temperature
Indication value - Display and adjustment module3)
Ʋ Displayed value 1 Filling height Level Ʋ Displayed value 2 Electronics temperature
Resolution, digital < 1 mm (0.039 in)
Measurement accuracy (according to DIN EN 60770-1)Process reference conditions according to DIN EN 61298-1
Ʋ Temperature +18 … +30 °C (+64 … +86 °F) Ʋ Relative humidity 45 … 75 % Ʋ Air pressure +860 … +1060 mbar/+86 … +106 kPa
(+12.5 … +15.4 psig)Mounting, reference conditions
Ʋ Min. distance to internal installations > 500 mm (19.69 in)
2) The output values can be assigned individually.3) The indication values can be assigned individually.
54
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58879-EN
-190215
Ʋ Vessel metallic,ø1m(3.281ft),centricmounting,processfit-tingflushwiththevesselceiling
Ʋ Reflector metallic, ø 1 m Ʋ Medium Bulksolids-cereals,flour,cement(dielectriccon-
stant ~2.0) Ʋ Mounting Probe end does not touch the vessel bottom
Sensor parameter adjustment No gating out of false signals carried out
4
5
3
1
2
4
5
3
1
2
Fig. 32: Measuring ranges - NivoGuide 31001 Reference plane2 Probe length L3 Measuring range4 Upper dead band (see following diagrams - grey section)5 Lower dead band (see following diagrams - grey section)
Typical deviation4) See following diagrams
4) Depending on the installation conditions, deviations may occur which can be corrected by adapting the adjust-ment.
55
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58
879-
EN-1
9021
5
L
0-2�mm
(-0.079")
2�mm (0.079")
15�mm(0.591")
-10�mm (-0.394")
0,3 m(11.811")
0,08 m(3.15")
0,02 m(0.787")
1
Fig. 33: Deviation NivoGuide 3100 in rod version1 Dead band (no measurement possible in this area)L Probe length
0
2�mm(0.079")
-2�mm(-0.079")
15�mm(0.591")
10�mm(0.394")
0,08 m(3.15")
0,3 m(11.811")
0,1 m(3.94")
L
1
Fig. 34: Deviation NivoGuide 3100 in cable version in water1 Dead band (no measurement possible in this area)L Probe length
Repeatability ≤±1mm
VariablesinfluencingmeasurementaccuracySpecificationsforthedigitalmeasuredvalueTemperature drift - Digital output ±3 mm/10 K relating to the max. measuring range or
max. 10 mm (0.394 in)Additional deviation through electromag-netic interference acc. to EN 61326
< ±10 mm (< ±0.394 in)
Specificationsapplyalsotothecurrentoutput5)
Temperature drift - Current output ±0.03 %/10 K relating to the 16 mA span or max. ±0.3 %
5) Also for the additional current output (optional).
56
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58879-EN
-190215
Deviation in the current output due to digital/analogue conversion Ʋ Non-Ex and Ex-ia version < ±15 µA
Additional deviation through electromag-netic interference acc. to EN 61326
< ±150 µA
InfluenceofthesuperimposedgasandpressureonmeasurementaccuracyThe propagation speed of the radar impulses in gas or vapour above the medium is reduced by highpressure.Thiseffectdependsonthesuperimposedgasorvapours.Thefollowingtableshowstheresultingdeviationforsometypicalgasesandvapours.Thespecifiedvalues refer to the distance. Positive values mean that the measured distance is too large, negative values that the measured distance is too small.
Gas phase Temperature Pressure
1 bar (14.5 psig) 10 bar (145 psig) 50 bar (725 psig)
Air 20 °C (68 °F) 0 % 0.22 % 1.2 %
200 °C (392 °F) -0.01 % 0.13 % 0.74 %
400 °C (752 °F) -0.02 % 0.08 % 0.52 %
Hydrogen 20 °C (68 °F) -0.01 % 0.1 % 0.61 %
200 °C (392 °F) -0.02 % 0.05 % 0.37 %
400 °C (752 °F) -0.02 % 0.03 % 0.25 %
Steam (saturated steam)
100 °C (212 °F) 0.26 % - -
180 °C (356 °F) 0.17 % 2.1 % -
264 °C (507 °F) 0.12 % 1.44 % 9.2 %
366 °C (691 °F) 0.07 % 1.01 % 5.7 %
Characteristics and performance dataMeasuring cycle time < 500 msStep response time6) ≤3sMax.filling/emptyingspeed 1 m/min
Products with high dielectric constant (>10) up to 5 m/min.
Ambient conditionsAmbient, storage and transport tempera-ture
-40 … +80 °C (-40 … +176 °F)
Process conditionsFortheprocessconditions,pleasealsonotethespecificationsonthetypelabel.Thelowestvaluealways applies.Themeasurementerrorthroughtheprocessconditionsinthespecifiedpressureandtemperaturerange is < 1 %.
6) Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk solidsapplications,untiltheoutputsignalhastakenforthefirsttime90%ofthefinalvalue(IEC61298-2).
57
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58
879-
EN-1
9021
5
Process pressure -1 … +40 bar/-100 … +4000 kPa (-14.5 … +580 psig), dependingontheprocessfitting
Vesselpressurerelatingtotheflangenominal pressure stage
see supplementary instructions manual "Flanges ac-cording to DIN-EN-ASME-JIS"
Process temperature - Cable versions with PA coating
-40 … +80 °C (-40 … +176 °F)
Processtemperature(threadorflangetemperature)withprocessseals Ʋ FKM (SHS FPM 70C3 GLT) -40 … +150 °C (-40 … +302 °F) Ʋ EPDM (A+P 70.10-02) -40 … +150 °C (-40 … +302 °F) Ʋ FFKM(Kalrez6375)-withtempera-ture adapter
-20 … +200 °C (-4 … +392 °F)
1
2
A
B0°C / 32°F
-40°C / -40°F
80°C / 176°F
30°C / 86°F
60°C / 140°F
150°C302°F
100°C212°F
50°C122°F
80°C176°F
-40°C-40°F
Fig. 35: Ambient temperature - process temperature, standard versionA Ambient temperatureB Process temperature (depending on the seal material)1 Aluminium housing2 Stainless steel housing, electropolished
58
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58879-EN
-190215
0°C / 32°F
-40°C / -40°F
80°C / 176°F
40°C / 104°F
60°C / 140°F
200°C392°F
150°C302°F
100°C212°F
50°C122°F
80°C176°F
-20°C-4°F
1
2
A
B
Fig. 36: Ambient temperature - process temperature, version with temperature adapterA Ambient temperatureB Process temperature (depending on the seal material)1 Aluminium housing2 Stainless steel housing, electropolished
Vibration resistance Ʋ Rod probe 1gwith5…200HzaccordingEN60068-2-6(vibration
at resonance) with rod length 50 cm (19.69 in)Shock resistance
Ʋ Rod probe 25 g, 6 ms according to EN 60068-2-27 (mechanical shock) with rod length 50 cm (19.69 in)
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 barCable entry
Ʋ M20 x 1.5 1 x cable gland M20 x 1.5 (cable: ø 6 … 12 mm), 1 x blind plug M20 x 1.5
Ʋ ½ NPT 1 x blind plug NPT, 1 x closing cap (red) ½ NPTWire cross-section (spring-loaded terminals)
Ʋ Massive wire, stranded wire 0.2 … 2.5 mm² (AWG 24 … 14) Ʋ Stranded wire with end sleeve 0.2 … 1.5 mm² (AWG 24 … 16)
Electromechanical data - version IP 66/IP 68 (1 bar)Connection cable
Ʋ Configuration four wires, one suspension cable, braiding, metal foil, cover
Ʋ Wire cross-section 0.5 mm² (AWG 20) Ʋ Wire resistance <0.036Ω/m Ʋ Tensile strength < 1200 N (270 lbf) Ʋ Standard length 5 m (16.4 ft)
59
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58
879-
EN-1
9021
5
Ʋ Max. length 180 m (590.6 ft) Ʋ Min. bending radius 25 mm (0.984 in) with 25 °C (77 °F) Ʋ Diameter approx. 8 mm (0.315 in) Ʋ Colour - Non-Ex version Black Ʋ Colour - Ex-version Blue
Display and adjustment moduleDisplay element Display with backlightMeasured value indication
Ʋ Number of digits 5Adjustment elements
Ʋ 4 keys [OK], [->], [+], [ESC]Protection rating
Ʋ unassembled IP 20 Ʋ Mounted in the housing without lid IP 40
Materials Ʋ Housing ABS Ʋ Inspection window Polyester foil
Functional safety SIL non-reactive
Integrated clockDate format Day.Month.YearTime format 12 h/24 hTimezone,factorysetting CETMax. rate deviation 10.5 min/year
Additional output parameter - Electronics temperatureRange -40 … +85 °C (-40 … +185 °F)Resolution < 0.1 KDeviation ±3 KOutput of the temperature values
Ʋ Indication Via the display and adjustment module Ʋ Analogue Via the current output
Voltage supplyOperating voltage UB
Ʋ Non-Ex instrument 9.6 … 35 V DC Ʋ Ex-ia instrument 9.6 … 30 V DC
Operating voltage UB with lighting switched on Ʋ Non-Ex instrument 16 … 35 V DC Ʋ Ex-ia instrument 16 … 30 V DC
Reverse voltage protection Integrated
60
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58879-EN
-190215
Permissible residual ripple - Non-Ex, Ex-ia instrument Ʋ for 9.6 V< UB < 14 V ≤0.7Veff(16…400Hz) Ʋ for 18 V< UB < 36 V ≤1.0Veff(16…400Hz)
Load resistor Ʋ Calculation (UB - Umin)/0.022 A Ʋ Example - Non-Ex instrument with UB= 24 V DC
(24V-9.6V)/0.022A=655Ω
Potential connections and electrical separating measures in the instrumentElectronics Notnon-floatingReference voltage7) 500 V ACConductive connection Betweengroundterminalandmetallicprocessfitting
Electrical protective measures
Housing material Version Protection acc. to IEC 60529
Protection acc. to NEMA
Aluminium Single chamber IP 66/IP 68 (0.2 bar) Type 6P
Double chamber IP 66/IP 68 (0.2 bar) Type 6P
Stainless steel (electro-pol-ished)
Single chamber IP 66/IP 68 (0.2 bar) Type 6P
Connection of the feeding power supply unit
Networks of overvoltage category III
Altitude above sea level Ʋ by default up to 2000 m (6562 ft) Ʋ with connected overvoltage protection up to 5000 m (16404 ft)
Pollutiondegree(withfulfilledhousingprotection)
4
Protection rating (IEC 61010-1) III
ApprovalsInstruments with approvals can have deviating technical data (depending on the version). For such instruments, the corresponding approval documents must be noted.
9.2 DimensionsThe following dimensional drawings are only an extract of the possible versions.
7) Galvanic separation between electronics and metal housing parts
61
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58
879-
EN-1
9021
5
Aluminium housing
21
ø 84 mm(3.31")
~ 116 mm(4.57")
116
mm
(4.5
7")
M20x1,5M20x1,5/½ NPT
~ 87 mm(3.43")
M16x1,5
ø 84 mm(3.31")
120
mm
(4.7
2")
M20x1,5/½ NPT
Fig. 37: Housing versions with protection rating IP 66/IP 68 (0.2 bar), (with integrated display and adjustment module the housing is 9 mm/0.35 in higher)1 Aluminium - single chamber2 Aluminium - double chamber
Stainless steel housing
~ 59 mm(2.32")
ø 80 mm(3.15")
112
mm
(4.4
1")
M20x1,5/½ NPT
Fig. 38: Housing versions with protection rating IP 66/IP 68 (0.2 bar), (with integrated display and adjustment module the housing is 9 mm/0.35 in higher)1 Stainless steel single chamber (electropolished)
62
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58879-EN
-190215
NivoGuide 3100, cable version ø 4 mm (0.157 in), ø 6 mm (0.236 in), PA coated
L
46 m
m(1
.81"
)22
mm
(0.8
7")
ø 20 mm(0.79")
150
mm
(5.9
1")
ø 4 mm(0.16")
G ¾
SW 36 mm(1.42")
ø 6 mm(0.24")
3
1 2
Fig. 39: NivoGuide 3100, cable ø 4 mm (0.157 in), ø 6 mm (0.236 in) threaded version with gravity weight (all grav-ity weights with thread M12 for eye-bolt)L Sensor length, see chapter "Technical data"1 Cable ø 4 mm (0.157 in)2 Cable ø 6 mm (0.236 in), PA coated3 Joint - cable
63
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58
879-
EN-1
9021
5
NivoGuide 3100, cable version ø 6 mm (0.236 in), ø 11 mm (0.433 in), PA coated
80 m
m(3
.15"
)L
30 m
m(1
.18"
)
ø 30 mm(1.18")
SW 55 mm(2.17")
G1½15
0 m
m (5
.91"
)
ø 6 mm(0.24")
ø 11 mm(0.43")
1 2
3
Fig. 40: NivoGuide 3100, cable ø 6 mm (0.236 in), ø 11 mm (0.433 in) threaded version with gravity weight (all gravity weights with thread M12 for eye-bolt)L Sensor length, see chapter "Technical data"1 Cable ø 6 mm (0.236 in)2 Cable ø 11 mm (0.433 in), PA coated3 Joint - cable
64
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58879-EN
-190215
NivoGuide 3100, rod version ø 16 mm (0.63 in)
80 m
m(3
.15"
)L
30 m
m(1
.18"
)
ø 16 mm(0.63")
SW 55 mm(2.17")
G1½
1
Fig. 41: NivoGuide 3100, rod ø 16 mm (0.63 in), threaded versionL Sensor length, see chapter "Technical data"1 Joint - rod
65
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
9 Supplement58
879-
EN-1
9021
5
9.3 TrademarkAll the brands as well as trade and company names used are property of their lawful proprietor/originator.
66
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
INDEX58879-EN
-190215
INDEX
AAdjustment
– Max. adjustment 25 – Min. adjustment 26
Adjustment system 22Application 25Application area 8
BBacklight 30
CCheck output signal 42Copy sensor settings 35Current output 36Current output, adjustment 37Current output, meas. variable 36Current output, min./max. 28Current output mode 27Curve display
– Echo curve 32
DDamping 26Date of manufacture 38Date/Time 33Default values 33Deviation 43Display format 30
EEcho curve of the setup 32Electrical connection 15, 16Electronics and connection compartment 18Electronics compartment - double chamber housing 18Error codes 41
FFactory calibration date 38False signal suppression 28Faultrectification42Functional principle 8
GGrounding 16
HHART address 37
IInflowingmedium13Installation position 11
KKey function 21
LLanguage 29Linearisation 26Lock adjustment 29
MMain menu 23Measured value indication 30Measurement loop name 24Measurement reliability 31
NNAMUR NE 107
– Failure 40 – Maintenance 42 –Outofspecification41
PPeak value indicator 31Probe length 24Probe type 37
QQuick setup 23
RRead out info 38Repair 47Replacement parts
– Electronics module 9Reset 33
SScaling measured value 36Sensor characteristics 38Sensor status 30Simulation 32Special parameters 37Status messages - NAMUR NE 107 39
TType label 7Type of medium 25
67
Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART
INDEX58
879-
EN-1
9021
5
UUnits 24