OPAL-RT RT14 Conference: HIL testing using HYPERSIM

33
Bouna Cisse, P.E., MSc.E. Opal-RT Technologies Inc. [email protected] Workshop on Hardware-in-the-Loop Testing of Transformer Differential Protection using Hypersim Workshop on Hardware-in-the-Loop Testing of Transformer Differential Protection using Hypersim Jean-Philippe Gagnon, Eng. Gentec inc [email protected]

description

Workshop on Hardware-in-the-Loop Testing of Transformer Differential Protection using HYPERSIM, by Gentec and OPAL-RT

Transcript of OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Page 1: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Bouna Cisse, P.E., MSc.E.

Opal-RT Technologies Inc.

[email protected]

Workshop on Hardware-in-the-Loop Testing of

Transformer Differential Protection using Hypersim

Workshop on Hardware-in-the-Loop Testing of

Transformer Differential Protection using Hypersim

Jean-Philippe Gagnon, Eng.

Gentec inc

[email protected]

Page 2: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Collaboration between

CORPORATE PRESENTATION. ALP Protection Relay

Page 3: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Gentec

CORPORATE PRESENTATION.

• Who is Gentec ?

• Our mission

• Expertise and achievements

• Facility and equipment

• ALP series

protection relay

ALP Protection Relay

Page 4: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Who is gentec ?

CORPORATE PRESENTATION.

• Founded in 1959 by Théodore Wildi

• Privately owned company,

headquarters in Quebec City

• Over 125 employees

– Major investment in R&D

• Hydro-Québec strategic partner

• Mission-critical equipment

manufacturing

• Also developed Gentec Electro-Optic

in 1969

• High tech infrastructures

ALP Protection Relay

Page 5: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Our mission

CORPORATE PRESENTATION.

Mission

Gentec designs, produces and markets custom solutions in the

electrical power, data acquisition, signal processing, and

power management fields.

Since 1959, we maintain our leading position through our

customer relationships, as well as the reliability and

ruggedness of our products

ALP Protection Relay

Page 6: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Expertise and achievements

CORPORATE PRESENTATION.

• 55 years expertise in the electrical utility market

• Long life and critical product development

• Multifunctional team with huge experience in creating

custom products, including electronic hardware and

software

• Flexibility toward customer needs

• Quality, rigor of process

ALP Protection Relay

Page 7: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Expertise and achievements

CORPORATE PRESENTATION.

Electronic development

• Acquisition Data IED

• Mission critical equipment to receive field IO’s

• Used in transmission and

Generation station for automation

• Load Shedding IED

• Triggered by underfrequence, over and under voltage event

• Used in electrical network automation

• Remote-controlled

ALP Protection Relay

Page 8: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Expertise and achievements

CORPORATE PRESENTATION.

Electronic development

• Network Disturbance recorder

• Record network disturbance

• High recording capability

• Recloser control

• Regulate network voltage fluctuation

• Urban design to reduce

visual disturbance

ALP Protection Relay

Page 9: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Expertise and achievements

CORPORATE PRESENTATION. ALP Protection Relay

Capacitor bank

• Power quality solution and efficiency solution

• Power factor correction

• Harmonic Filter

Battery Charger

• Utility grade and industrial use

• Built to highest standards

Page 10: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Energy management and lighting

• Central access and management of building energy

efficiency

Expertise and achievements

CORPORATE PRESENTATION. ALP Protection Relay

Page 11: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Quality & Certification

CORPORATE PRESENTATION.

• IPC class 3

• ISO 9001:2008

• Facility Security Clearance: NATO SECRET

• C-TPAT Customs Trade Partnership Against Terrorism

• CSA / UL Certification

ALP Protection Relay

Page 12: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Facility and equipment

CORPORATE PRESENTATION.

• 42,000 ft2

• Electronic Assembly

• Cabinet Assembly

• SMT assembly Lead or Lead-free

• Wave Soldering

• Environment Stress Screening Chambers

• Insulation Test Benches

• In-house Conformal Coating

• AOI inspection and BGA X-Ray

ALP Protection Relay

Page 13: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

ALP series Protection Relay

.

Evolution of the electrical grid

New electrical architecture

New phenomena

New challenges

• Introduction

• Overview of ALP-4000

• Features and benefits

• Hardware and Software Architecture

• Differential Protection

ALP Protection Relay

Page 14: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Introduction

.

Protection Relays are used to protect equipment from being

damaged by undesired electric phenomenon.

Specific protection functions exists for generators

transformers, transmission line, capacitors, etc..

Various type of functions:

- Instantaneous overcurrent (50) - Undervoltage (27)

- Time overcurrent (51) - Overvoltage (59)

- Over/under frequency (81) - Distance (21)

- Differential (87) - etc…

- Directional Power (32)

ALP Protection Relay

Page 15: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Introduction to Protection

.

- Negative sequence can tell how a system is unbalanced

- Zero sequence can tell you about earth fault condition

- Protection relay can add currents to trigger transformer or line

differential protection

- Protection relay can protect from generator overexcitation conditions

(Volt/Hz)

- Infinite possibilities

- Hundred years of evolution in a single box!

ALP Protection Relay

Page 16: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Overview of ALP-4000

.

- Six (6) three phase current inputs

- Two (2) three phase voltage inputs

- Eight (8) fast power outputs

- Sixteen (16) relay outputs

- Sixteen (16) digital inputs

- Two (2) optical Ethernet ports

- One (1) Ethernet maintenance port

- IRIG-B input

- 8 configurable push buttons

- 16 configurable alarm tricolor LEDs

- LCD Display

- -40C to 85C operating temperature

ALP Protection Relay

Page 17: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Overview of ALP-4000

.

- Main functions- 50/51N Overcurrent

- 87U/O/N Differential

- 27 Undervoltage

- 59 Overvoltage

- 81/R Frequency

- DCT Voltage peak detector

- Logical function

- IRIG-B Synchronization

- Disturbance recorder

- Sequence of events recorder

- User friendly configurator

ALP Protection Relay

Page 18: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Web Interface

.

- Monitor through Secure WEB Interface (Encrypted, HTTPS)

- Monitor voltage, current phasor and symmetrical components

(magnitude and phases)

ALP Protection Relay

Page 19: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Web Interface

.

- Download COMTRADE files (data for scope trace)

- Access to the sequence of events

ALP Protection Relay

Page 20: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

- Withstand rough Electric, Temperature and CEM levels

- Built to electric utility highest standard (IEEE, IEC and customer specific)

. ALP Protection Relay

Physical caracteristics

Page 21: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

- Use powerful Digital Signal Processing (DSP)and Central Processing unit (CPU)

- Ultra Fast power output uses transistors (fast switching 2us) combined with relay (high maintained current)

. ALP Protection Relay

Material architecture

Input-Output

-Current

-Voltage

-Digital

-Power

7680Hz

Protection

Calculation

Logic

Settings

Logging

Raw data sampling rate

Page 22: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

. ALP Protection Relay

ALP Configurator

- User friendly interface

- Very flexible

- Large selection of settings for protection functions, timers, latches,

pushbuttons, assignable LEDs, assignable internal variables (over 700+)

Page 23: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

. ALP Protection Relay

ALP4000 Features and benefits

- Secure, rugged and reliable. Comply with the latest utility standards

- Factory acceptance tests completed with Hydro-Quebec

- Protection, Automation, Metering and Monitoring built into 1 unit

- High density of IO cards

Page 24: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

. ALP Protection Relay

ALP4000 Features and benefits

- Unique and very friendly user interfaces and software

- Lower engineering time for equipment setup

- Lower cost of operation

- Cutting edge technology components, very high processing capacity

- Powerful calculation and storage capabilities

- Fast transformer differential restrained action ( 1,4 cycle)

- Address issue of modern transformers inrush with

SAFE Restrained mode

Page 25: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

. ALP Protection Relay

ALP4000 Features and benefits

- Flexibility to adapt to new and modern algorithms

- Can use customer Matlab model to implement new algorithms

- Research lab friendly!

- Modern, powerful, flexible

Page 26: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

. ALP Protection Relay

Protection function

- Transformer Differential (87)

- Need to protect only transformer zone

Transformer

differential

zone

Out of

zone

Out of

zone

Page 27: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

. ALP Protection Relay

Protection function

- Transformer Inrush

- High current created by magnetization of the core

- Harmonic generation (2nd and 4th harmonic monitored)

- Newest transformer have lower losses but are subject to

ultrasaturation

- This leads to lower 2nd harmonic levels (parameter used in

determining inrush conditions)

- You do NOT want to trip in these conditions

Page 28: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

. ALP Protection Relay

Protection function

Page 29: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

. ALP Protection Relay

Protection function

- Set threshold- Minimum differential- UnRestrained value- Slope 1- Slope 2- Break point- Harmonic levels

inrush › 2nd and 4th)overexcitation › 5th

Page 30: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

- Set the 87R restrained (harmonic) level

3 modes of operation (for even harmonic level 2nd and 4th )- Restrained

Increase dual slope characteristics in proportion of even

harmonic detected

- TRADITIONAL (for even harmonic level 2nd and 4th )Blocking enabled if harmonic level is greater than set value

(example block above 15%)

- SAFE (for modern transformers)

verify if fundamental is in phase with 2nd harmonic (to validate

this is not a fault). Lower the blocking level (example 8%)

. ALP Protection Relay

Protection function

Page 31: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

87 Transformer differential

Restrain Mode

SAFE Mode

Page 32: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

. ALP Protection Relay

ALP plateform Development

- New and smaller ALP2000 platform

- Added Feeder protection functions

2014 2015

Page 33: OPAL-RT RT14 Conference: HIL testing using HYPERSIM

Thank you!

WWW.GENTEC.CA