FRI 7../6 Gas Pressure RegulatorInstallation Instructions
Table of Contents
USA CDN
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . Page 1Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1Attention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2Lock-up Pressure Parameters. . . . . . . . . . . . . . Page 3Regulator Orifice Diameters . . . . . . . . . . . . . . . Page 3Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3Mounting & Installation . . . . . . . . . . . . . . . . . . . Page 4Pressure Taps . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5Breather Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6Vent Limiting Device & Vent Line Connection Page 6Operation & Maintenance . . . . . . . . . . . . . . . . . Page 7Flow Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8Outlet pressure springs . . . . . . . . . . . . . . . . . . . Page 9Dimensions & Part Numbers . . . . . . . . . . . . . . . Page 9
Approvals
1, 2, 3 ... = Action• = Instruction
Explanation of symbols
Attention
On completion of work on the pressure regulator, perform a leakage and function test.
Please read the instruction be-fore installing or operating. Keep the instruction in a safe place. You find the instruction also at www.dungs.com If these instructions are not heeded, the result may be personal injury or damage to property.Any adjustment and application-specific adjustment values must be made in accordance with the equipment manufacturers instructions.
IFGCCSAUL
ANSINFPA
This product is intended for installations covered by, but not limited to, the following codes and standards: NFPA 86, CSD-1, ANSI Z21.13, UL 795, NFPA 85, CSA B149.3, NFPA 37 or CSA B149.1.
Breather plug
Never close Breather hole!
Breather hole
Safetyfirst
O.K.
The installation and maintenance of this product must be done under the supervision of an ex-perienced and trained specialist. Never perform work if gas pres-sure or power is applied, or in the presence of an open flame.
Accessories & Replacement . . . . . . . . . . . . . . . Page 10
3 … 102 … 10
MC
• Ka
rl D
ungs
, Inc
. • F
RI G
as P
ress
ure
Regu
lato
r • E
ditio
n 20
17.0
7 • P
/N 2
6140
0
Specification
Max. Operating Pressure (MOP)7 PSI (500 mbar) UL & CE5 PSI (350 mbar) CSAMax. Body Pressure (MOP)15 PSI (1bar)
Ambient / Fluid Temperature• +5 °F to +150 °F for up to 7 PSI for regulatingbehavior(≈-15...65°C) (+/-10%ofsetpoint)• -40°Fto+150°F• CSACertifiedfor-40°Fto+150°Fupto5PSI:Diaphragmsaresuit-able for the low temperature, but there may be out of range regulat-ingbehavior.
• -15°Cto+70°CappliestotheCEMarking.
GasesDry, natural gas, propane, butane;other noncorrosive gases.Suitableforupto0.1%byvolume,dryH2S.A “dry” gas has a dew point lowerthan+15°Fanditsrelativehumidityislessthan60%.Materials in contact with GasHousing:AluminumSealingsonvalveseats:NBR-basedrubber
°F
0-40
+150
FRI/6 Gaspressureregulator(lock-uptype)withintegratedgasfilterinonehousing.TheFRI/6seriesregulatormounts directlytotheDMV701,702and703seriesvalves.Suitableasstand-alonewhenusingtwoflanges.
Gas
Maximum pressure drop and gas velocityThemaximumpressure drop is lit-mitedbythecelocityofthegas.Donotexceedagasvelocityof30meters/s.
Strainer23Mesh,installedinthehousingFilterMesh <0.05 mm, installed in thehousing
Hysteresis and DroopHysteresis/repeatabilityislessthan10%forupto7PSI inlet.Averagedroopat20:1turndownis10%forup to 7 PSILock-Up Rating• TheFRImeetstheANSIZ21.80/CSA6.22asClassI,whichallowslockupratingnotmorethan150%or5in.W.C.,whicheverisgreater.
• TheFRImeetsEN88-1asSG30,whichallowslock-upashighas+30%oftheoutletpressure.
• See lock-upPressureParameteronpage2formoredetails
Body Size SizeFRI705/6&707/6 1/2“-1“NPTFRI710/6&712/6 1“-2“NPT
[PSI]
Vent Limiting Device and Vent Line ConnectionThe FRI/6 has an internal, factoryinstalled vent limiter, which limitstheescapeofgas to less than0.5CFH@5PSI incaseatmosphericdiaphragm ruptures. Vent limitingdevicealsocomplieswithEN88-1&ISO2355-1.Ventingrequiredunlessotherwiseacceptedbytheauthorityhavingjurisdiction.
3 … 102 … 10
MC
• Ka
rl D
ungs
, Inc
. • F
RI G
as P
ress
ure
Regu
lato
r • E
ditio
n 20
17.0
7 • P
/N 2
6140
0PerANSIZ21.80,lock-upisdefinedasanoutletpressurenotmorethan150%or5in.W.C,whicheverisgreater,abovethesetpointafteradownstreamsafetyshutoffvalvecloseswithin2seconds,andthetwofollowingconditionsexist:1.outletpressureissettothehighestsetpointofthespring,and
2.theregulatorissettomaximumcapacityorflowatwhichthe regulatorwill control lockuppressurewithin theac-ceptablelimits.
Thismeansthatinagivenapplication,alockupgreaterthan150%or5in.W.Ccouldoccur,dependingouttheinletpres-sure,theoutletpressureoftheregulator,theflowrateoftheregulator,andthepipevolumedownstreamtheregulatorandupstreamthesafetyshutoffvalve.
PerDUNGS, lock-up is+30%of theoutlet pressure set-tingafterdownstreamshutoffvalveslowlycloseswithin30seconds.Therefore,inagivenapplication,alockupgreaterthan+30%or5in.W.Ccouldoccur,dependingontheinletpressure,theoutletpressureoftheregulator,theflowrateoftheregulator,andthepipevolumedownstreamtheregulatorandupstreamthesafetyshutoffvalve.
If in agivenapplication the lock-uppressure is toohigh,employingoneormoreof the followingshould reduce thelock-uppressure:1.Increasethesizeoftheregulator.2.Increasethepipevolumedownstreamtheregulatorandupstreamthesafetyshutoffvalve.
3.Decreasetheinletpressure.4.Decreasetheouletpressure.5.Reducetheflowrate.6.Removeventline,ifinstalled.
Lock-up Pressure Parameters
Regulator Orifice Diameters
Regulator Type Orifice Diameter (mm)FRI705/6 17.0FRI707/6 24.0FRI710/6 29.0FRI712/6 37.5
Recommended Mounting ProcedureRegulatordomefromverticallyuprighttolyinghorizontally
Mounting
If the flow is not in the same direction of the arrows, the regulator will not operate properly.
5 … 104 … 10
MC
• Ka
rl D
ungs
, Inc
. • F
RI G
as P
ress
ure
Regu
lato
r • E
ditio
n 20
17.0
7 • P
/N 2
6140
0
Mounting & Installation
Recommended Procedure to Mount Flanges1. Makesuretheo-ringsandthegroovesarecleanandin
goodcondition.2. InstalltheFRI/6withthegasflowmatchingthedirection
indicatedbythearrowsonthecasting.3. MounttheFRI/6verticaluprighttohorizontal.4. Cleanthemountingsurfaceoftheflanges.Makesurethey
areingoodcondition.5. AttachtheFRI/6totheflangesusingtheappropriateM6
orM8socketcapboltssupplied.
• Theregulatorcanbemountedeitherupstreamordown-streamoftheDMV.Itcanalsobemountedasastandaloneregulatorusingtwoflangesandtheflangemountingkit.
• Themaingassupplymustbeshutoffbeforestartingtheinstallation.
• Examinetheregulatorforshippingdamage.• Theinsideoftheregulatorandpipingmustbecleanandfreeofdirt.
Recommended Procedure to Mount the FRI/6 regulator to a DMV 701, 702, or 703 series safety shutoff valve.1. Replacetheo-ringinthegrooveonthesideoftheDMV
bodywiththeovalo-ringsuppliedwiththemountingkit.2. Makesuretheovalo-ringandthegroovearecleanand
ingoodcondition.3. InstalltheFRI/6regulatorandDMVseriesvalvewiththe
gasflowmatchingthedirectionindicatedbythearrowsonthebody.
4. AttachtheregulatortotheDMVseriesvalvebodyusingthesocketcapboltssuppliedintheFRI/DMVmountingkit.
5. Usea5mmAllenwrenchfortheFRI705/6&707/6.6. Usea6mmAllenwrenchfortheFRI710/6&712/6.7. Tightentheboltsincrisscrosspattern.8. Donotovertightenthebolts.Followthemaximumtorque
valueslistedbelow.9. Afterinstallationiscomplete,performaleaktesttoverify
thatnoleakageoccurs.
Recommended Piping Procedure & Applying Pressure• Usenew,properlyreamedandthreadedpipefreeofchips.• Applygoodqualitypipesealant,puttingamoderateamount onthemalethreadsonly.Ifpipesealantlodgesonthe regulatorseat,itwillpreventproperoperation.IfusingLP gas,usepipesealantratedforusewithLPgas.• Donotthreadpipetoofar.Valvedistortionand/ormalfunc-tionmayresultfromexcesspipeinthevalvebody.
• Applycounterpressureusingaparallel jawwrenchonlytotheflatsontheflangewhenscrewingthepipeintotheflanges.
• Donotovertighten thepipe.Follow themaximumtorquevalueslistedbelow.
• Afterinstallationiscompleteandpressureisapplied,per- formaleaktest.
6. Usea5mmAllenwrenchfortheFRI705/6&707/6.7. FortheFRI710/6&712/6,theretwooptionsforbolts: For 1” and 1 1/4” flanges, the M8 x 35 mm bolts must
be used. For 1 1/2” and 2” flanges, the M8 x 40 mm bolts must
be used.8. Tightentheboltsinacrisscrosspattern.9. Donotovertightenthebolts.Followthemaximumtorque valuesbelow.10.Afterinstallationiscomplete,performaleaktest.
If the flow is not in the same direction of the arrows the regulator will not operate properly.
Recommended Torque for Piping1/2” 3/4” 1” 11/4” 11/2” 2” NPT
pipe375 560 750 875 940 1190 [Ib-in]
Recommended Torque for Mounting BoltsM6 M8 Bolt Size62 134 [Ib-in]
Recommended Torque BoltsM6 M8 Blot Size62 134 [Ib-in]
When first applying pressure, open the inlet manual shutoff valve slowly. Quickly opening
the inlet manual shutoff valve can permanently rup-ture the internal, balancing diaphragm.
5 … 104 … 10
MC
• Ka
rl D
ungs
, Inc
. • F
RI G
as P
ress
ure
Regu
lato
r • E
ditio
n 20
17.0
7 • P
/N 2
6140
0
Pressure TapsFRI pressure ports1, 2, 3 (Ports 2 and 3 arelocatedonflange)
Port1isthreadtypeG⅛asperDINISO228
Ports2and3arethreadtypeG⅛asperDINISO228
AllportscanbeusedwithaccessoriesorA2pressureswitches.
7 … 106 … 10
MC
• Ka
rl D
ungs
, Inc
. • F
RI G
as P
ress
ure
Regu
lato
r • E
ditio
n 20
17.0
7 • P
/N 2
6140
0
Vent Limiting DeviceTheFRI/6seriesregulatorcontainsaninternal,factoryin-stalledventlimitingdevice,whichlimitstheescapeofgastolessthan0.5CFH@5PSIincaseatmosphericdiaphragmruptures.Ventingrequiredunlessacceptedbytheauthorityhavingjurisdiction.
Vent Line Requirements• Followthe localcodeforventsizingandterminationre-quirements.Intheabsenceoflocalcodes,followNationalFuelGasCodeNFPA54,theInternationalFuelGasCodeor theCSAB149.1 installationcode for venting require-ments.
• Terminatetheventtoanapprovedlocation.• Atthepointoftermination,theventlinemustbeprotectedfrominsectsandwaterintrusion.Itishighlyrecommendtoinstallaninsectscreenandterminatethepipewiththeexitfacingdownwardstopreventrainwaterfromentering.
Installation Procedure• Ifventingisrequired,theventlineistobeconnectedtotheupperdomeoftheFRIregulatorasillustrated.
• Removethebeatherplug.• Onindoorinstallationsrequiringventingoutdoors,runthepipingasshortandasdirectaspossible.
• TheventconnectionisG1/4.G1/4to1/4”NPTadapterisavailable:(P/N231944)withreplacablegasket(P/N171260).
Vent Limiting Device & Vent Line Connection
In the absence of venting codes and where vent-ing is required, each regulator must be vented
separately from all other vents.
Breather Plug• AllFRI’shaveabreatherplugthatthreadsintotheregula-tors’sventconnection.
Do not removed plastic breather plug unless venting outdoors is required.
Thisplugisnottheventlimiter,anditpreventsdebrisfromenteringtheupperchamberoftheregulator.Debrisintheupperchamberoftheregulatorwilladverslyaffectregulatorperformance.
• TheFRIregulatormustalsobeabletoexchangeairthroughthebreatherholeinordertoproperlyregulate.Donotplugthebreatherhole,andcleanitoutifnecessary.
Breather plug
Breather hole
7 … 106 … 10
MC
• Ka
rl D
ungs
, Inc
. • F
RI G
as P
ress
ure
Regu
lato
r • E
ditio
n 20
17.0
7 • P
/N 2
6140
0Start-Up• Theinletandoutletshutoffvalvesshouldbothbeclosed.
• Slowlyopentheinletmanualshutoffvalvejustenoughto allowinletpressuretograduallybuilduptotheinletofthe regulatoruntilthesystemisfullypressurized.• Slowlyopentheoutletshutoffvalve(s)toallowasmallflow.
Set-Point Adjustment1. Removetheblackadjusmentcover.2. Toincreasetheoutletpressuresetpoint,turntheadjust-
mentspindleclockwisewithascrewdriver.3. Todecreasetheoutletpressuresetpoint,turntheadjust-
mentspindlecounterclockwisewithascrewdriver.4. Alwaysuseanaccuratepressuregaugeconnecteddown- stream from the regulator tomeasure theactualoutlet
pressure.5. Re-installblackadjustmentcover.6. Afteradjustingthesetpointfornormaloperationverifythat thegaspressureregulatoroperatesasintended.
Outlet Pressure Spring Replacement
1. Removetheblackadjustmentcover.2. Releasespringtensionbyturningtheadjustmentspindle completelycounterclockwisewithascrewdriver.3. Removethealuminumcap.4. Removeexistingspringandinsertnewspring.5. Re-installadjustementspindleandadjusttodesiredoutlet pressure.Followthesetpointadjustmentinstructions.6. Re-installtheadjusmentcover,andapplythenewoutlet pressure labelprovidedwithnewoutletpressure range
ontothenameplate.
Filter• Inspectthefilteratleastonceayear.• Replace thefilter if thepressuredropacross thefilter ismorethan4”W.C.
• Replace thefilter if thepressuredropacross thefilter ismorethantwiceashighasthefirstinstallationinspection.
Filter Change1. RemovetheFRI/6byfollowingthemountinginstructions
inreverseorder.2. Removethesupportring.3. Removethefilterinsert.4. Insertanewfilterinsert.5. Pressinthesupportring.6. Re-installtheFRI/6followingthemountinginstructions.7. Performafunctionandleaktest.
Operation & Maintenance
Quickly opening the inlet manual shutoff valve can permanently rupture the internal, balanc-
ing diaphragm.
During start-up, a pressure gauge must be used to read the setpoint of the regulator ourlet pres-
sure. After the safety shutoff valves are closed, the outlet pressure must not exceed the setpoint by more than 30 %. If the outlet pressure exceeds 30 % of the setpoint, see section on page 2 for lock-up pressure.
While adjusting the outlet pressure of the regu-lator, confirm that adjusting the outlet pressure
does not create a hazard to the burner.
Head Injury Risk:Never have head above or near the aluminum
cap when removing regulator spring. The spring ten-sion can be high enough to rapidly eject the aluminum cap with a large force.
Adjustment cover
Adjustment spindle for outlet pressure adjustment
Aluminum Cap. Turn only to remove outlet pressure spring
Spring
Breather plugOutlet
pressure label
Inlet Filter
9 … 108 … 10
MC
• Ka
rl D
ungs
, Inc
. • F
RI G
as P
ress
ure
Regu
lato
r • E
ditio
n 20
17.0
7 • P
/N 2
6140
0
Regulator turndown characteristicswith gas filter / in regulated state.Inlet pressure is 20 in. W.C. and outlet is set to 4 in. W.C.
Aproximate flow increase in CFH (natural gas) when removing the integral filter from the FRI.
Inlet Pressure 20 in. W.C.Outlet Pressure 4 in. W.C.
Flow (CFH) of natural gas; s.p. 0.65 at 60°F
Pres
sure
Dro
p (in
. W.C
.)
Max. FlowMin. Flow
TurndownTurndown
Turndown
Turndown
DensityofNaturalgas
Densityofgasusedf =
Type of gas Density[kg/m3] s.g. f
Naturalgas 0.81 0.65 1.00Butane 2.39 1.95 0.58Propane 1.86 1.50 0.66Air 1.24 1.00 0.80
Determining equivalent flow through valves using another gas
Vgasused = V Naturalgas x f° °
At a pressure drop of: FRI 705/6 FRI 707/6 FRI 710/6 FRI 712/60.8in.W.C. 25CFH 50CFH 390CFH 765CFH2.0in.W.C. 35CFH 70CFH 480CFH 940CFH4.0in.W.C. 35CFH 75CFH 575CFH 1180CFH8.0in.W.C. 35CFH 80CFH 700CFH 1510CFH
Flow Curve
9 … 108 … 10
MC
• Ka
rl D
ungs
, Inc
. • F
RI G
as P
ress
ure
Regu
lato
r • E
ditio
n 20
17.0
7 • P
/N 2
6140
0
Order flanges separately.
Type Mounts to DMV Type
NPTFlanges
Order No.
Dimensions [inch]Dimensions[mm]
Weight [lbs] [kg]
a b c d e f g hFRI705/6 DMV701 1/2"-1" 230472 3.6
925.6 141
1.333
6.0152
7.7195
3.896
4.1104
5.5139
2.00,9
FRI707/6 DMV701 1/2"-1" 230473 3.692
5.6 141
1.333
6.0152
7.7195
3.896
4.1104
5.5139
2.00,9
FRI710/6 DMV702/3 1"-2" 230474 4.9124
6.9/8.1176/206
1.845
6.9175
9.3235
5.0126
5.3135
6.7169
3.51,6
FRI712/6 DMV702/3 1"-2" 230475 4.9124
6.9/8.1176/206
1.845
6.9175
9.3235
5.0126
5.3135
6.7169
3.51,6
ab
fh
g
ce
d
approx.1.60"/40mm
Requiredspacefor mounting A2 pressureswitch
FordimensionbFRI710/712:1,11/4in.NPT=6.93"FRI710/712:11/2,2in.NPT=8.11"
Requiredspacefor
changingspring
Dimensions & Part Numbers
Outlet pressure springsSpring Range (W.C.)Spring color
1to3.6brownNotCSA
2 to 5white
2.8to8orange
4to12blue Standard
10 to 22red
12to28yellow
24to44black
40to60pink
60to80greyNotCSA
FRI 705/6 - 707/6 229817 229818 229820 229821 229822 229823 229824 229825 229826FRI 710/6 - 712/6 229842 229843 229844 229845 229846 229847 229848 229849 229850
10 … 10
MC
• Ka
rl D
ungs
, Inc
. • F
RI G
as P
ress
ure
Regu
lato
r • E
ditio
n 20
17.0
7 • P
/N 2
6140
0
Karl Dungs GmbH & Co. KGP.O. Box 12 29D-73602 Schorndorf, GermanyPhone +49 (0)7181-804-0Fax +49 (0)7181-804-166e-mail [email protected] http://www.dungs.com
Karl Dungs, Inc.3890 Pheasant Ridge Drive NESuite 150Blaine, MN 55449, U.S.A.Phone 763 582-1700Fax 763 582-1799e-mail [email protected] http://www.dungs.com/usa/
Wereservetherighttomakemodificationsinthecourseoftechnicaldevelopment.
FlangesType Mounts to DMV Type Flange NPT Order No.FRI705/6-FRI707/6 DMV701 1/2" 222371FRI705/6-FRI707/6 DMV701 3/4" 222368FRI705/6-FRI707/6 DMV701 1" 221999FRI710/6-FRI712/6 DMV702orDMV703 1" 222369FRI710/6-FRI712/6 DMV702orDMV703 11/4" 222370FRI710/6-FRI712/6 DMV702orDMV703 1 1/2" 222003FRI710/6-FRI712/6 DMV702orDMV703 2" 221997
Stand alone mounting kit (one kit included in each FRI box)
Order No. Includes
FRI705/6&FRI707/6 224093 Consistsof8bolts:M6x30;2xo-rings.FRI710/6&FRI712/6 224094 Consistsof8bolts:M8x35for1"NPTand11/4"NPT,
and8bolts:M8x40for11/2"NPTand2".2o-rings
DMV mounting kit (one kit included in each FRI box)
Order No. Includes
FRI705/707onDMV701 219967 4bolts:M6x30and1o-ring.FRI710/6&FRI712/6 219968 4bolts:M8x45and1o-ring
Accessories & Replacement
Filter & Strainer Order No. Includes
FRI705/6&FRI707/6 230440 Strainer & FilterFRI710/6&FRI712/6 230441 Strainer & Filter