Oisd Paper

download Oisd Paper

of 12

Transcript of Oisd Paper

  • 7/28/2019 Oisd Paper

    1/12

    Principles of Lightning Protection

    For Oil and Gas Installations

    A.J. Surtees, BSc, PhD, MBA, FICD, CEng, MIEE, SMIE (Aust)

    Technical Manager

    ERICO Inc. USA

    MECHANISMS OF LIGHTNING DAMAGE

    There are two basic mechanisms by which lightning may

    enter and cause damage at a site. The first is a direct strike

    where the building or surrounding structures receive a direct

    lightning discharge. The effect is a large increase in the local

    earth potential with subsequent damage to equipment

    connected to outside services via such means as power

    feeders, telephone subscriber lines, data or control cables and

    physical pipelines.

    The second mechanism is due to magnetic or capacitive

    induction where a distant strike may induce large voltage

    transients into power lines, communications lines and the

    pipeline. The US IEEE standard 587 describes typical peak

    amplitudes of voltage and current in power and

    communications lines.

    The mechanism of coupling to a buried pipeline is different.

    The pipe, being insulated presents a high resistance to

    ground and over its length a large capacitance to ground.

    The earth potential rise associated with a ground strike in thevicinity of the pipe, is capacitively coupled to the pipe. This

    potential is transferred in both directions from the point of

    the strike, resulting in local earth potential rises at metering

    stations and other facilities housing such equipment as

    monitoring and telemetry electronics. It is this mechanism

    which is responsible for damage to the sensitive metering

    and electronic equipment. Thus, a strike some hundreds of

    kilometres from a particular site may be responsible for local

    damage.

    The waveform of the transient induced into the pipe is

    modified by the pipe capacitance. This means that protection

    methods which may be effective against the standard 8/20spulse must be reviewed. Our experience is that the pulse rise

    time is slowed, consequently protection networks involving

    series inductive elements are largely ineffective.

    A GENERIC APPROACH TO LIGHTNING

    PROTECTION

    Global Lightning Technologies has developed a generic Six

    Point Plan for the protection of structures or facilities. The

    concept behind the plan is that it prompts the user into

    considering a holistic approach to lightning protection, one

    embracing all aspects of potential damage, from the more

    obvious direct strike to the more subtle mechanisms of

    differential earth potential rises and voltage induction at

    service entry points.

    1. Capture the li ghtni ng stri ke at a preferred and know

    point. This involves the use of an effective air terminal(s) on

    the structure or vessel to be protected. In the design of area

    protection, it is important to realise that many points on the

    structure will be competing for the downward lightning

    leader by launching upward interception streamers. Theeffectiveness of a lightning terminal is the measure of its

    response time in launching such a streamer. The earlier the

    streamer launch with respect to extraneous emission points

    on the surrounding structure, the better the terminal will be

    in ensuring it will take the strike (at a known point) and

    prevent random striking or bypasses to adjacent uncontrolled

    points.

    2. Convey the li ghtning energy to ground in a safe manner

    via a known route. This involves the use of a dedicated

    down conductor, capable of withstanding the full energy of

    the lightning discharge and conveying this to the grounding

    system with minimal danger of side flashing to adjacentearth points. The ability of the down conductor to screen

    adjacent equipment from the large electro magnetic impulse

    associated with the discharge current, which may reach

    energy levels as high as 250kA 8/20s, is also a measure of

    its effectiveness in reducing damage by induction.

    3. Ensure a low impedance earthi ng system to dissipate the

    lightni ng discharge. The need to understand the

    characteristics of an earthing system under impulse

    conditions (associated with the higher Fourier spectral

    components of the lightning discharge), is crucial if an

    effective earth system is to be designed. An effect earth

    system is one in which the potential rise of the surroundingearth is minimised and the rate of potential fall off from the

    injection point is maximised.

    4. Elimi nate earth l oops. Ensuring that a single point

    earthing policy is adopted and that equipotential earth

    bonding is used throughout the installation will help

    eliminate common damage caused by differential earth

    potentials.

    5. Protect service entr y points of power f eeders. This

    involves the installation of voltage clamping devices capable

    of handling the large energy content (kA rating) of the over

  • 7/28/2019 Oisd Paper

    2/12

    voltage surge, as well as reducing the extremely fast rising

    edge (dv/dt and di/dt) of this transient.

    6. Protect service entr y points of data or control li nes. This

    involves the installation of high speed protective barriers. For

    effective voltage limiting, a hybrid circuit is usually

    employed where both speed of activation and energy

    handling capacity are optimised in a multi-stage protective

    module.

    POINT 1. CAPTURE THE LIGHTNING STRIKE

    AT A PREFERRED POINT

    The potential of a direct strike to a communications tower

    servicing a remote telemetry link, an offshore exploration

    platform or even an elevated fuel storage tank may be high

    with the resultant danger of equipment damage or even fire

    as witnessed recently at the Cilacap refinery in Indonesia.

    The design of an effective air terminal to protect such

    structures requires some understanding of the mechanism of

    the lightning discharge.

    THE THUNDERCLOUD ORCUMULO-NIMBUS

    Lightning is a natural phenomenon which develops when the

    upper atmosphere becomes unstable due to the convergence of a

    warm, solar heated, vertical air column on the cooler upper air

    mass. These rising air currents carry water vapour which on

    meeting the cooler air usually condense giving rise to convective

    storm activity. Pressure and temperature are such that the

    vertical air movement becomes self sustaining, forming the basis

    of a Cumulo-nimbus cloud formation with its centre core capable

    of rising to more than 15,000 metres.

    To be capable of generating lightning, the cloud needs to be 3-4

    km deep. The taller the cloud the more frequent the lightning.The centre column of the Cumulo-nimbus can have drafts

    exceeding 120 km/hr creating intense turbulence with violent

    wind shears and consequential danger to aircraft. This same up

    draught gives rise to an electric charge separation which

    ultimately leads to the lightning discharge.

    The surface of the earth is initially negatively charged to the

    order of 5 x 105 C, giving rise to an electric field intensity of

    approximately 0.13 kVm-1. The lower atmosphere takes on an

    opposing positive space charge. As rain droplets carry charge

    away from the cloud, from the earth the storm cloud takes on the

    characteristics of a dipole with the bottom of the cloud negatively

    charged and the top of the cloud positively. It is known from

    waterfall studies that fine precipitation acquires a positive

    electrical charge. Larger particles acquire a negative charge. The

    up draught of the Cumulo-nimbus separates these charges by

    carrying the finer or positive charges to high altitudes. The

    heavier negative charges remain at the base of the cloud and the

    surface of the earth starts to accumulate positive charge. This

    gives rise to the observed phenomenon where more than 90% of

    cloud-to-ground discharges occur between a negatively charged

    cloud and positively charged earth (negative lightning).

    THE LIGHTNING DISCHARGE

    The separation of electrical charge within a cloud allows electric

    potential to increase to a point where a neutralising discharge

    must occurs. The method by which this discharge takes place can

    take on one of five different mechanisms:-

    Cloud-to-cloud

    Cloud-to-air

    Intra-cloud discharges

    Ground-to-cloud discharges and

    Cloud-to-ground strikes.

    Approximately 50% of all lightning discharges are cloud-to-

    ground strikes. Ground-to-cloud discharges are extremely rare

    and generally only occur from high mountain tops or tall man

    made structures.

    Cloud-to-ground discharges are further subdivided into positive

    and negative leader discharges, of which about 90% are of the

    negative category.

    MECHANICS OF THE LIGHTNING STRIKE

    The development of a cloud-to-ground discharge is a two staged

    sequence, with one process being initiated from the cloud while a

    second process is simultaneously being initiated from the groundor earth bound structures. Both mechanisms rely on an excessive

    electron build up with subsequent ionisation and avalanche into

    an electric current flow.

    The Cloud Initiated Discharge - Leader

    As a cloud accumulates charge, the electric field builds up to

    the point where the air starts to breakdown forming an

    ionised discharge called apilot streamer. This initial

    discharge rapidly traverses about 30-50 meters towards the

    ground. The presence of wind shear tends to blow away the

    ionised air, halting the progression momentarily until

    additional negative charge accumulates at the tip of the

    column and air breakdown again occurs, allowing theionisation process to advance a further 30-50 metres. This

    more intense discharge is generally known as thestepped

    leader. The process repeats itself in a series of discrete steps

    with a time interval of roughly 50 s. The course taken by

    each of the steps in the leaders propagation towards the

    ground is determined by the path through the air which

    ionises more easily. This gives rise to the characteristically

    zigzag nature of the cloud-to-ground discharge and the

    branching of the lightning into many "fingers" in an attempt

    to reach ground.

    Being a highly ionised column, the tip of the leader is at

    essentially the same potential as the charged cell from which ithas originated. As this tip approaches the ground, the potential

    gradient further increases accelerating local ground ionisation.

    At this point the potential difference between the leader and the

    earth may be as high as 107 V, resulting in local air breakdown.

    A ground originating discharge then begins to move up towards

    the leader, intercepting at some tens of meters above ground

    level.

    The Earth Bound Discharge - Streamer

    At the ground level, a point discharge such as a sharp metal

    protrusion serves to enhance the electric field intensity as the

    leader tip approaches, to the point where electrons are

  • 7/28/2019 Oisd Paper

    3/12

    accelerated sufficiently to cause ionisation as they collide with

    gas molecules. As the kinetic energy of the electrons is less than

    this ionising potential, additional electrons are released and an

    avalanche discharge results. To start the process, an initial

    liberated electron is required. This can come from the natural

    field intensification due to the presence of a charged cloud or

    from deliberated introduced means such as a radioactive source

    or spark gap. Such techniques of enhancing the emission of free

    ions is the basis of early streamer emission, enhanced-ionisation

    air terminals.

    Once the electric field strength exceeds about 2 kVm-1 the

    number of liberated free ions becomes adequate to cause a

    current to flow which weakens the electric field. This current is

    known as the upwardstreamer currentand can reach

    magnitudes of several tens of amperes and can take the form of a

    faintly luminescent discharge emanating from sharp protrusions.

    Time captured photograph has shown that this upwards steamer

    channel can reach several hundreds of meters as it propagates to

    meet the descending leader.

    The Main Discharge Or Return Stroke

    Once the ionised channel has been completed by the junction of

    the streamer and the leader, the build up of positive charge in the

    earth flows upwards along the ionised discharge channel to

    neutralise the large negative charge in the cloud giving rise to

    what is known as the return stroke. Alternatively, the process

    can be described using conventional electron flow as, electrons

    migrating from the negative cloud to the positive earth. This is

    characterised by a rapidly increasing electric current whose rate

    of rise is typically 1010 amperes/sec.

    Peak currents averaging around 30 kA appear typical with

    minimum currents being about 3 kA. Maximum discharges

    exceeding 200kA have been recorded.

    It is also possible to have consecutive discharges down the same

    channel. This occurs when the initial discharge neutralises the

    localised charge cell in the cloud that initiated the stroke. Nearby

    charge cells then flash across to the ionised channel and use it to

    discharge to ground. In this manner up to 16 discharges have

    been observed using the one channel.

    The average energy released in a discharge is 55 kWhr, a

    significant amount of energy by modern generation standards.

    The danger of the discharge lies in the fact that all the energy is

    expended in only 100-300 microseconds and that the peak

    discharge current is reached in only 1 to 2 microseconds.

    The following parameters are typical of the return stroke:-

    Upward speed of return stroke is typically one-third to one-

    half the speed of light near the ground and decreases as it

    approaches the cloud.

    Total time between ground and cloud < 100s

    Peak current in first return stroke about 30kA

    Time to peak < 10ms

    Leader channel is heated to 30 000K

    All charge contained in leader and branches is deposited to

    ground down same channel.

    Subsequent restrikes take on the following parameters:

    Peak currents from 20 to 400kA

    Time between return strokes 3 to 100ms

    Number of return strokes 1 to 15, average of 4

    Rising times even faster, typically a few nanoseconds.

    These are some of the parameters which make lightning difficult

    to control. The need to ensure that the lightning discharge is

    effectively captured using a well designed early streamer

    emission terminal is the key to such control.

    THE DYNASPHERE EARLY STREAMER EMISSION AIR

    TERMINAL

    The result of many years of theoretical and ongoing field

    research is the DYNASPHEREEarly Streamer Emission

    Terminal. This product provides the design engineer with an air

    termination relatively free of space charges which is capable of

    creating photo-ionisation and which concentrates electric field to

    release free electrons on the approach of a lightning leader.

    The Dynasphere is a passive air terminal which requires no

    external power source, relying solely on the energy contained in

    the approaching leader for its dynamic operation. This

    remarkable terminal has the ability to concentrate only thatelectric field which occurs in the millisecond time slots as the

    leader charge approaches the ground.

    The principle of operation relies on the capacitive coupling of the

    outer sphere of the terminal to the approaching leader charge,

    which in turn raises the voltage of the spherical surface. This rise

    in voltage produces a field concentration across the insulated air

    gap between the outer sphere and central grounded finial. As the

    leader continues to approach the voltage on the sphere rises until

    a point is reached where the air gap breaks down. This

    breakdown creates local photo-ionisation and the release of

    excess free electrons. These then accelerate under the intensified

    field to initiate an avalanche condition and the formation of astreamer current begins.

    Unlike the Dynasphere, pointed rods and other types of

    enhancement terminals tend to create a corona space charge

    above the emission point which serves to reduce the electric field

    there by inhibiting streamer initiation. Also, unlike other air

    terminals using battery or corona generated discharges, the

    Dynasphere is radio-quiet only producing a spark discharge as

    the leader approaches.

    CONVENTIONAL APPROACH TO CALCULATION OF THE

    PROTECTION RADIUS

    In 1901, the British Lightning Committee formed to address theprotection which a Faraday rod would afford. After much debate,

    it was resolved that this would be the area falling under a 450

    cone drawn from the tip of the rod. Experience over the years has

    highlighted many deficiencies associated with this method,

    where lightning has bypassed air terminals and struck within the

    safe area.

    The deficiencies associated with this approach are depicted in

    Figure 1. It was for this reason that the rolling sphere concept ofprotection for taller structures was introduced in the late 1970s.

  • 7/28/2019 Oisd Paper

    4/12

    Figure 1. Lightning enters the "cone of protection" (Franklin

    Rod method of protection) due to the inability of the

    structure to launch a streamer.

    COLLECTION VOLUME METHOD

    The over simplification of the cone of protection approach

    has prompted research into a more scientific approach to the

    calculation of the effective protection radius afforded by a

    lightning terminal. One such model is that of the Collection

    Volume.

    The derivation of the collection volume design concept can be

    understood by considering the approach of the downward

    leader. The charge Q distributed along this leader causes rapid

    increase in electric field between it and ground points. When a

    critical field value is reached, the ground point launches an

    upward intercepting leader. The distance at which this occurs is

    called the Striking Distance. The critical electrical field is

    dependent on both leader charge and distance from the ground

    point. Figure 2 shows how it is possible to form striking

    distance hemispheres around an isolated ground point. The

    greater the leader charge, the greater the striking distance.

    Unfortunately, this simplistic approach of creating striking

    distance hemispheres is not infallible in practice. Regard must be

    taken of the relative velocities of the approaching leaders.

    Figure 2 shows how it is possible to reach critical electric field

    and launch an upward leader. If the downward leader is near the

    periphery of the sphere, its velocity may carry it onward to

    intercept another upward leader. Therefore, it is possible for the

    downward leader to enter a striking distance hemisphere without

    interception.

    To cater for this the model requires that a limiting parabola be

    placed on the hemisphere. This parabola is derived from velocity

    factors and completes our collection volume. It can now be

    stated that a downward leader entering such a volume is

    theoretically assured of interception by the ground point

    concerned. Figure 5 also shows how collection volumes become

    larger with increased leader charge. That is, the larger the

    magnitude of the current stroke, the larger the collection volume.

    The collection volume model assumes that all points on the

    structure are potential strike points and as such exhibit their

    own natural collection volumes or attractive radius.

    Figure 2. Collection volume and hemisphere bounded by

    limiting parabola defined by charge on approaching leader.

    THE BENJI CAD PROGRAM

    A proprietary computer program has been developed by

    Global Lightning Technologies Pty. Ltd. which evaluates the

    protection radius afforded by an air terminal under different

    conditions of leader intensity. Known as BENJI after thefounder of lightning research, Benjamin Franklin, the

    program compares the protection radius produced by the air

    terminal to the attractive radii produced by the electric field

    intensification of competing points on the structure (corners

    and edges, antennae, equipment, masts etc). The program

    then optimises the placement, and number of air terminals,

    to ensure that all these competing points lie within the

    protective radius afforded by the ESE terminals.

    The technology upon which the ESE air terminal and

    computer model are based, follows that which is included in

    the Australian / New Zealand Standard NZS/AS1768-1991

    Lightning Protection, Appendix A.

    POINT 2. SAFELY CONVEY THE LIGHTNING

    ENERGY TO GROUND

    Once the lightning discharge has been captured it is necessary to

    covey this energy to the ground in a safe and controlled way.

    Complications such as side flashing to adjacent conductors,inductive coupling of the large electromagnetic pulse onto nearby

    signal lines and control of the excess energy content, need to be

    considered. To this end ERICO has developed a special insluated

    down conductor which comprises carefully selected dielectric

    materials to create a capacitive balance and ensure insulation

    integrity under high impulse conditions. In addition, a

    conductive outer sheath allows electrostatic bonding of the

    building through cable securing saddles. This ERICORE down

    conductor evolved after extensive studies of potential voltage rise

    in structures due to lightning injection.

  • 7/28/2019 Oisd Paper

    5/12

    Figure 3. ERICORE insulated downconductor

    The construction of the ERICORE also serves to reduce the

    mutual inductance. A value of inductance of 1.6H/m is

    normally regarded as quite small. However when a current is

    impressed which is rising at the rate of 100kA/s, the effect of the

    voltage developed due to this inductance (Ldi/dt) becomes

    dominant. As an example, a single 60 metre down conductor

    will rise to a value in excess of 1MV with an average discharge.

    It is for this reason that a number of conductors are frequently

    specified with standard protection methods.

    Some of the practical benefits of ERICORE:-

    It provides the design engineer with the ability to select

    the most convenient lightning route to ground. The down

    conductor can utilise air ducts etc. and be located remote

    from electrical and sensitive electronic equipment.

    The lightning is contained in the 50mm copper core

    conductor and is oblivious to impedance irregularities in

    the structure. The risk of side-flashing is reduced.

    The structure carries only that minimal current which is

    due to capacitive coupling to the main conductor.

    Accordingly, voltages across concrete and reinforcing

    members remain small. This leads to the conclusion that

    no special bonding techniques are required.

    By constraining the lightning injection energy to the core

    of the cable, the amount of radiated field is reduced and

    induction to adjacent cables, such as RF feeders on

    telecommunications towers or data lines, is reduced.

    POINT 3. ENSURE A LOW IMPEDANCE

    GROUNDING SYSTEM

    The importance of ensuring that the grounding system affords a

    low earth impedance and not simply a low resistance must be

    understood. A spectral study of the energy content associated

    with the lightning impulse reveals both a high frequency and low

    frequency component. The high frequency is associated with the

    extremely fast rising front (typically < 10 s to peak current) of

    the lightning impulse while the lower frequency component

    resides in the long, high energy, tail or follow-on current in the

    impulse. The grounding system appears to the lightning impulse

    as a transmission line where wave propagation theory with the

    normal rules of reflection and group velocity, apply.

    Measurement of earth resistance with conventional low

    frequency instruments may not provide results which are

    indicative of the earth systems true effectiveness under

    lightning discharge conditions. ERICO has developed an

    Earth System Analyser in which a fast pulse is injected into

    the earth test point to simulate the performance under

    lightning impulse conditions. The peak current and voltage

    amplitude within an effective measurement interval of

    approximately 500ns is measured and used to calculate the

    effective impedance.

    The magnitude of the current pulse is programmable

    according to the local conditions. The measurement window

    lies with current pulses of 1 to 5A, 10 to 250V (peak) and

    impedance range of 1.5 to 250 ohms. By effectively gating

    off any pulses returning to the instrument after about 500ns,the instrument can be used to isolate distant grounds in a

    complex system (greater than 75m away), allowing only the

    earth-under-test to be measured without the need for

    disconnection.

    The instrument is also capable of providing repetitive pulses

    at 30 second intervals to allow remote tracing of pulse

    currents, their magnitude and flow direction.

    POINT 4. ELIMINATE EARTH LOOPS

    The current associated with a direct strike is typically 30kA

    but may be as high as 270kA and exhibits a rise time ofmany thousands of amperes per second. When this current is

    discharged through the lightning protection system, the

    potential of the local earth system, with respect to the general

    mass of the earth, will rise to a high level. The actual

    calculation of this earth potential rise depends not only upon

    the resistance of the earth grid but because of the high rates

    of rise involved, also upon the inductance of the discharge

    path.

    Ignoring inductive effects, a simple calculation shows that

    for a good earth resistance of 1 ohm and a discharge

    current of 30kA, the earth potential rise will be 30kV. Given

    that this rise can never be entirely eliminated, the aim in anywell designed lightning protection system is to equalise the

    potential gradient to ensure that all equipment rises

    uniformly in potential. This process is known as Earth

    Potential Equalisation or EPE, and is achieved by bonding all

    separate grounds points into a common ground system.

    In practice, bonding involves connecting together all metallic

    masses at a site with suitable conductors to ensure that they

    are at the same electrical potential. Once bonded, this

    common electrical potential must be matched to that of the

    earth mass itself via a suitable connection to the grounding

    system. This approach ensures that during a voltage

    transient, all equipment within the site will rise and fall

  • 7/28/2019 Oisd Paper

    6/12

    together as the surge current flows and potentially hazardous

    voltages will not develop across the equipment.

    Not only does this offer protection to the equipment housed

    within, but it also ensures that personnel do not come into

    contact with hazardous voltages when touching two pieces of

    separate equipment - the touch potential.

    Effective bonding design usually entails the adoption of a

    single point earthing approach, in which all equipment

    within the shelter is connected to a master bus bar which is

    in turn bonded to the external grounding system at one point

    only. In addition, the respective ground points for all

    services, be they AC mains, telephone, data, coax feeders,

    control signals or RF cables, should enter the shelter at a

    common point - usually via an aluminium gland plate which

    is itself also securely bonded to the external grounding

    system.

    POINT 5. PROTECT SERVICE ENTRY POINTS

    OF POWER FEEDERS

    This involves the installation of voltage clamping devicescapable of handling the large energy content (kA rating) of

    the over voltage surge, as well as reducing the extremely fast

    rising edge (dv/dt and di/dt) of this transient.

    PRINCIPLES OF POWERLINE PROTECTION

    The need for transient protection on power supplies is

    becoming more apparent to the general community as failure

    of equipment due to power lines transients becomes more

    prevalent. This need is recognised by inclusion of new

    requirements in modern surge protection standards such as

    IEEE/ANSI C62.41, AS1768-1991, IEC 61643, IEC1024 and

    BS6651. The question that requires further thought is how

    bestto provide point of entry protection against transientswhich are conveyed along power circuits.

    Experience has shown that failure of equipment due to

    lightning induced surges can be attributed to two basic

    mechanisms - over voltages with their excess energy content

    and the extremely fast rise times associated with the

    lightning impulse. Primary over voltage protection is usually

    provided by Metal Oxide Varistors (MOV) or Spark Gap

    devices (SG). Secondary protection is provided by low pass

    power filtering which serves to reduce the peak let-through

    voltage and the dv/dt of the impressed surge.

    A number of devices and technologies are available for theprotection of the mains power entering a facility, all of which

    require a decision as to the effectiveness offered. Typically

    the devices available fall into two broad categories -shunt

    protection or series hybrid protection.

    SERIES HYBRID (FILTER) VS. SHUNT PROTECTION

    Shuntprotection is the most basic form of protection

    comprising over-voltage clamping devices which act to divert

    the energy from a transient surge down to earth. Series

    hybrid protection combines the energy diverting

    characteristics of a shunt protector with a low pass filter.

    This serves to further reduce the extremely fast rate of rise of

    the voltage transient, further reducing the potential for

    damage to the equipment. Such devices are usually known as

    Power Filters or Surge Reduction Filters (SRF).

    Field experience over the last fifteen years has shown that

    simple shunt protection is generally adequate for the more

    robust types of equipment such as lighting, air conditioning

    and motor plants (pumps), but is inadequate at providing a

    safe level of protection for equipment using semiconductor

    electronics. Where such equipment is connected to the

    mains, SRFs must be used to limit both the magnitude and

    rate of rise of the voltage transient.

    SHUNT PROTECTION

    Shunt protection devices are referred to under a variety of

    names including Transient Voltage Surge Suppressors

    (TVSS), Surge Protective Devices (SPD) or sometimes

    simply as Arrestors. They usually employ Metal Oxide

    Varistors (MOV), air gaps, Silicon Avalanche Diodes (SAD)

    or a combination of these.

    The parameters which specify the performance of surge

    suppressors are the voltage level to which they will clamp a

    typical transient (let-through or residual voltage) and the

    maximum peak current that can be diverted (peak kA rating).

    The let-through voltage of a device is the maximum clamped

    voltage appearing across the device when a surge is diverted.

    The most common test waveform used to specify the

    transient performance of surge suppressors is the 8/20s

    current pulse - Figure 4 and Figure 5. This is usually

    generated from a 6kV 1/50s charged capacitor source.

    Larger voltages are generally used in the generation of very

    large 8/20s pulses. The peak current of the 8/20s

    waveform which should be considered for the testing of point

    of entry protection devices, is specified in ANSI C62.41 as10kA (Category C3). For critical locations or exposed sites

    this figure is often increased.

    Figure 4. ANSI C62.41 Category A test pulse - 0.5s 100kHz

    open circuit voltage ring wave.

    Figure 5. ANSI C62.41 Category B test pulse - 1.2/50s

    unidirectional open circuit voltage waveform, and resultant

    8/20s current waveform

  • 7/28/2019 Oisd Paper

    7/12

    In addition to thesingle shotcapability of a surge suppressor,

    consideration needs to be given to the effects of multiple

    strike lightning. As mentioned earlier, statistical results from

    various lightning detection and tracking systems indicate that

    over half of all lightning flashes consist of more than one

    strike. The subsequent re-strikes follow the same lightning

    channel and generally exhibit a faster rate of rise of current

    than the initial strike. These multiple strikes are separated by

    some tens to hundreds of milliseconds. The effect of such

    multi-pulses on surge suppressors is to cause a cumulative

    heating effect which is suspected, rather than the energy in

    the strike itself, as being the cause of many of the recorded

    suppressor failures. At present there is no standard for testing

    under multi-pulse effects, but research carried indicates that

    Metal Oxide Varistors actually fail under applied multipulse

    currents which may only be 75% of the single shot rating of

    the device.

    ARC GAP DIVERTERS

    Air gap arrestors are designed to arc over when transient

    over-voltages occur and then extinguish when the transient

    has passed. They are generally capable of diverting large

    surge currents. The voltage across these devices when an arc

    has formed is very low (typically tens of volts). However, the

    voltage required to cause the arc to form is high, typically

    >3kV The let through voltage seen across such devices is

    characterised by a voltage spike reaching several thousands

    of volts with a steep leading edge (high dv/dt).

    The main problems with the use of such devices stems from

    the large voltage required to force them into conduction. For

    example, co-ordination problems with secondary protection

    can arise where the secondary protection operates at a lower

    voltage level than the arc gap arrestors. Also if a transient

    occurs which is below the strike voltage of the arc gap, then

    no protection is provided.

    Extensive research by ERICO Inc. has revealed novel

    techniques of pre-triggering spark gaps at voltages well

    below their inherent 2kV striking voltage. This research is

    on-going with the view to producing shunt protectors with

    extremely low let-through voltages (

  • 7/28/2019 Oisd Paper

    8/12

    T

    100kA

    30kA

    10kA

    3kA

    40mmMOV

    60mmMOV

    120kAMOVTEC

    1kA

    10 100

    Number of impulses

    Impulse

    magnitude

    1 1000 10000

    Figure 7. Estimate of MOV life - typical MOV specifications

    showing the relationship between the magnitude and number

    of surges which can be safely diverted

    MOV devices are generally rated for the maximum energy

    absorption in one impulse, however as illustrated in Figure 7,

    a large number of smaller impulses will also cause failure of

    the MOV.Increasing the single shot rating of the protective

    devices will significantly increase the lifetime for smaller

    impulses.

    POINT 6. PROTECT SERVICE ENTRY POINTS

    OF DATA OR CONTROL LINES

    The protection of data or signal line circuits generally

    requires a protection circuit capable of extremely fast

    activation (to ensure clamping at the typical tens of volts

    used in most signalling protocols), whilst at the same time

    being able to handle significant surge energies.

    For such purposes, a hybrid type circuit employing a number

    of different components is usually used. Certain of thesecomponents are able to with stand large amounts of current

    but are slow to activate (there by allowing the transient

    voltage to rise to levels significantly higher than their

    clamping voltage), whilst others are extremely fast (allowing

    no overshoot and clamping at the precise voltage required)

    but are only able to withstand tiny amounts of energy before

    self-destructing.

    The following are some of the most commonly encountered

    components used in various signal line protection barriers:-

    Gas Arresters - These devices are available in either a 2

    or 3 leg configuration. They are made of a ceramic tubewhich is filled with an inert gas. When a certain potential

    difference exists between any two of the legs, the arrester

    fires. The breakdown voltages vary from 70V up to 15kV.

    The three leg version enables the surge to be clamped to

    ground irrespective of which line the surge was present

    on. Gas arresters are comparatively slow to activate (often

    several microseconds) so should be used in combination

    with faster devices for optimum protection.

    Metal Oxide Varistors - MOVs are voltage limiting

    devices which clamp the voltage rise of an impressed

    surge once the clamping threshold is exceeded. MOVs

    are faster than gas arrestors at conducting, however on

    their own they are still not fast enough to limit a voltage

    transients to a safe level for typical data circuits operating

    somewhere in the 5-30V region.

    Solid State Devices such as Silicon Avalanche Diodes -

    These are special diodes with extremely fast turn on

    characteristics, typically in the picosecond domain. This

    means that their clamping threshold is extremely well

    defined with very little overshoot. They are available in a

    range of clamping voltages - 7.5, 12, 15, 30, 36 ... 200V

    making them an ideal protection component for data line

    protection.

    GA are able to handle significantly more energy than SADs

    however, as they are slow to turn on, the let-through voltage

    rises to well above the turn on threshold and easily exceeds

    the safe operating limit of most signal/control circuits. It is

    for this reason that a hybrid circuit comprising the above

    three components (designated a level 3 protector) is typically

    used in the design of data protection units.

    With any signal or power transmission system employingtwo lines and a separate earth, two types of transient can

    occur:-

    ADifferential Mode transient where the voltage surge

    appears across the two lines independent of their potential

    with respect to earth, and

    A Common Mode transient where the voltage surge is

    common between each line and earth.

    The selection of any data line protector should ensure that

    both Common and Differential modes are eliminated.

    PROTECTION PRACTICES SPECIFIC TO OIL

    AND GAS INSTALLATIONS

    Modern pipeline systems incorporate a range of sophisticated

    computing, instrumentation and communications equipment.

    Unfortunately, pipelines act as very efficient collectors of

    lightning energy, exposing this equipment to a high level of

    risk of damage due to lightning activity. It is essential,

    therefore, that these systems be equipped with adequate

    transient protection to ensure the correct operation of the

    pipeline system.

    Lightning activity and metallurgic effects are particularhazards for long, buried pipelines, producing dangerously

    high voltages along the pipe. For the safety of personnel and

    for the protection of equipment, it is essential to ensure that

    these hazards are safely dissipated to earth.

    Experience has shownthat the most extensive damage is

    generally sustained by equipment electrically connected to

    the pipe. This is to be expected with the pipe acting as a most

    efficient collector of lightning energy. The range of pipeline

    surge protection devices marketed by ERICO Lightning

    Technologies is shown in Error! Reference source not

    found.

  • 7/28/2019 Oisd Paper

    9/12

    Figure 8. Part of ERICO's range of Cathodic

    Protection systems

    It is common practice to sectionalise pipelines by the

    inclusion of insulated joints of the flange or monolithic type.Cathodic Protection (CP) voltage is applied to these pipeline

    sections.

    At metering and scrubber stations, an earthing system is

    generally installed and the out of ground pipe work between

    the insulated joints connected to it. Without protection,

    induced transient pipeline voltages can easily breakdown the

    insulated joint resulting in a permanent low resistance path

    to earth. Flange type insulated joints are particularly

    susceptible.

    There are two common methods of protecting insulated

    joints. Special cell can be used as an electrolytic switchblocking voltages in the cathodic protection range while

    shunting hazardous voltages to ground.

    Such cells require regular maintenance to check electrolyte

    levels as well as careful installation to minimise lead

    inductance for effective lightning protection.

    A second method involves the use of gas arresters electrically

    connected across the insulated joints. When a transient

    voltage exceeds the breakdown voltage of the arrester, the

    gas within the arrester ionises and creates a low impedance

    path to shunt the surge energy to ground. The arrester is self

    restoring reverting to a virtual open circuit. Providing the

    surge rating of the arrester is not exceeded, it will exhibit

    almost unlimited life. Figure 9 illustrates an explosion proof

    100kA 8/20s insulated joint protector.

    Figure 9. IJP unit with surge rating of 100kA and

    housed in an explosion proof enclosure.

    CATHODIC PROTECTION

    Modern switched mode power supplies used for cathodic

    protection are electronically controlled and regulated for

    maximum efficiency and operational accuracy. The CP

    power supply is connected between the pipe and a buriedearth system located perhaps 50-100 metres from the pipe

    and known as a ground bed. Input sensing comes from the

    pipe and a reference ground electrode.

    In an unprotected system surge currents will flow from the

    pipe to points of different potentials such as the ground bed

    and reference cell. There may also be flash overs within

    equipment cubicles caused by the cubicle being connected to

    yet another earth, for example the station earth system.

    Protection of electronic circuitry requires multistage

    protectors with the primary protector being a high energy

    absorption device such as a gas arrester.

    As mentioned previously, gas arresters are relatively slow to

    operate and can allow dangerously high voltages to pass

    before fully conducting. For this reason secondary protectors

    such as MOVs and pulse rated clamping diodes are typically

    used.

    All cabling inputs and outputs from electronic CP power

    supplies require protection with hybrid devices designed to

    divert surge energy to a common ground. This should be the

    station earth mat, to which all metalwork should be bonded.

    As with all transient protection, the philosophy is to create

    an equi-potential plane which will uniformly rise in potential

    with respect to true earth.

  • 7/28/2019 Oisd Paper

    10/12

    Figure 10. Block diagram of a hybrid lightning protection

    unit for a dual CP system

    Under normal operating conditions, the protector is

    transparent to the CPU and electrical isolation between the

    ground bed, the reference earth and the station earth mat, is

    maintained. In the event of a surge on the pipe, the protector

    acts to clamp the potential difference between the anode

    ground bed, the two pipe terminals and the reference earth to

    levels that will not cause damage to the CPU. A heavy duty

    gas arrester is used to divert the transient energy to ground

    via the station earth mat. The protector has been designed for

    use with CP power supplies rated at 20V/5A.

    Installation Considerations

    CPU protectors of this kind should be installed with a

    minimum of lead length between the unit and the CPU.

    Under fast rise time transient conditions, cable inductance

    becomes significant and high transient voltages can be

    developed across long leads. It is essential that the protector

    be grounded to the station earth mat.

    Figure 11. Wiring arrangement for the CPU Protector

    provided by ERICO.

    PIPELINE POTENTIAL CLAMPING

    Traditionally, large electrolytic capacitors have been used to

    protect pipelines from these hazards. However this method is

    not ideal, particularly in areas of high ambient temperature

    where the de-ratings applied to capacitors make them

    virtually useless.

    The Pipeline Potential Clamp (PPC) is connected between

    the pipeline and ground. A high energy gas discharge tube

    at the front end of the unit protects the pipe and associated

    equipment from lightning and other high energy transients,

    diverting the energy to ground. Inductive filtering and Metal

    Oxide Varistors act as a secondary protection stage,

    dampening the fast rise time and keeping voltages to safe

    levels. A series of diodes are used to protect the pipe from

    AC voltages and telluric effects, clamping the pipe-to-ground

    potential to within safe limits.

    INTRINSIC SAFETY

    The use of lightning protection units in certified hazardous

    areas requires some consideration. Providing LPUs or

    transient barriers contain no energy storage component and

    may be certified as simple apparatus, then they can be

    connected in intrinsically safe circuits on the hazardous side

    without upsetting the integrity of the IS circuit. Intrinsically

    safe barriers incorporating lightning protection on their input

    circuitry are now becoming available.

    Figure 12. A typical gas pipeline metering station showing

    the location of lightning protection units for insulated joints,

    cathodic protection and pipe connected transducers.

  • 7/28/2019 Oisd Paper

    11/12

    GENERIC APPROACH TO THE PROTECTION OF EQUIPMENT

    IN HAZARDOUS AREAS

    All equipment located within hazardous areas which is

    connected to support equipment lying outside the area (ie.

    located within the safe area) should be protected using

    Intrinsically Safe Barriers (ISB). It is preferable that the

    brand of barriers used also incorporate lightning transient

    protection. The barriers must be installed outside the

    confines of the hazardous area ie. in the safe area - Figure 13

    LP E

    Figure 13. Typical installation layout of an intrinsically safe

    area

    Typical equipment requiring protection includes:

    Pressure regulators, digital links

    Pressure release valves, analogue links

    Pressure transducers, 4-20mA links

    Flow computers - RS485 links

    Insulated flanges

    Two options exist for protection of non-certified equipment

    (RTU, modem, charger, batteries, telecom lines etc.) needed

    to support the instrumentation in the zone 1 area. These

    options depend on where the additional equipment is

    located:-

    Support equipment not certified as intrinsically safe and

    located within the zone 1 area, should be installed inside

    intrinsically safe enclosures. Feeders from this equipment to

    the safe area should be protected with ISB devices.

    Support equipment installed outside of the hazardous area,

    should also be protected with Universal Transient Barriers

    (UTB) to ensure that any impressed currents are maintained

    to safe levels.

    When installing lightning protection barriers, it is important

    to ensure that the total loop resistance of the ISB, UTB and

    RTU does not exceed the maximum specified loop resistance.

    Equipment installed within the safe area should be

    referenced to a single point Safe area Earth System (SES).

    All ISBs installed should be referenced to the SES. The SES

    should be bonded to the IES where distances permit (

  • 7/28/2019 Oisd Paper

    12/12

    Appendix

    PARTIAL REFERENCE LIST OF VOLATILE STORAGE FACILITIES

    PROTECTED BY ERICO INC.

    TASMANIA

    Berriedale Sewage Plant, Ellis Point,Berriedale 1

    Comalco Aluminium Powder Plant,Bell Bay 1

    Prince of Wales Sewage Plant, DerwentPark Road 1

    Sewerage Treatment Plant, Burnie 1

    WESTERN AUSTRALIA

    Industrial Plant Kwinana 1

    NEW SOUTH WALES

    Blue Circle Southern Cement - Berrima Plant 1Clarence Colliery Waste Water

    Treatment Tank 1Coal Storage - Hunter Valley 1Griffith City Council -

    Sewage Treatment Plant 2Hunter Valley Open Cut Mine 1Hunter Valley Colliery 2000T CoalStorage Bin 1

    Hunter Valley Open Cut No.1 1Newvale Colliery 1Sydney Water - North Head Sewage

    Treatment Plant 1Tower Colliery - Wilton 1Waterboard -

    Rouse Hill Sewerage Treatment Plant 3Westcliff Colliery Borehole No 1 1Westcliff Colliery - Methane Drainage 6Wingeecarribee Shire Council -

    Moss Vale Sewage Treatment Plant 3

    QUEENSLAND

    Airport Treatment Plant 1OK Tedi Mining, PNG 1QCL Cement Silos, Gladstone &Townsville 2Qld. Cement & Lime, Townsville 1Qld. Cement & Lime Silo, Gladstone 1Racecourse Mill-Sugar Refinery, Mackay 1Surge Bins - Abbot Point Coal 2Thallanga Mine Site 1White Mining, North Goonyella Mine 1

    INDONESIA

    Kaltim Prima Coal 5Kawasan Industri Gresik (Jawa Timur) 3Rumah Sakit Semen Gresik 2Semen Gresik (Persero) Proyek Tuban 2Treatment Centre of Industrial Bureau 1

    TAIWAN

    Chung Chou Sewerage Treatment Bldg 1

    THAILAND

    Egat Mah Moh, Lampang 1Rayong Wire, Rayong 3Sane Chemical, Chonburi. 1TGCI Factory, Saraburi 5The Siam Cement Office, Nakornratchasima 1