Oil Analysis Report [OLXX03] Demo Company - All Modules

9
1300 736 091 [email protected] www.txmonitor.com Unit 2/15 Hector Street (West), Osborne Park, WA 6017 NEWCASTLE • BRISBANE • DARWIN • PERTH • HAMILTON Oil Analysis Report [OLXX03] Demo Company - All Modules Site 1 Tag Number: PT4545 Saturday, March 5, 2016 This report was prepared by TxMonitor® expressly for the customer as nominated on this page. Neither TxMonitor® nor any person acting in its behalf; a) makes any warranty, express or implied, with respect to the use of any information or methods disclosed in this report, or b) assumes any liability with respect to the use of any information or methods disclosed in this report. Any recipient of this document, by their acceptance or use of this document, releases TxMonitor® and their affiiates from any liability for direct, indirect, consequential or special loss or damage whether arising in contract, warranty, express or implied, tort or otherwise, and irrespective of fault, negligence and strict liability. Email copies of this report are not official unless authenticated and signed by TxMonitor® and are not to be modified in any manner without the express written consent of TxMonitor® . All analyses performed on samples as received and relate only to items tested or sampled. TxMonitor® is responsible for all information in the report except that provided by the customer. Data provided by the customer is clearly identified. In addition, information supplied by the customer can affect the validity of the results. If the test sample deviates from specified conditions and is to proceed to testing, the results may be compromised. Historical results from other laborartories provided by our Clients are included for reference and diagnosis purposes. Sampled in compliance with ISO/IEC 17025 - Testing. The results of the tests, calibrations and/or measurements included in this document are traceable to Australian/National Standards.

Transcript of Oil Analysis Report [OLXX03] Demo Company - All Modules

Page 1: Oil Analysis Report [OLXX03] Demo Company - All Modules

1300 736 [email protected]

Unit 2/15 Hector Street (West), Osborne Park, WA 6017

NEWCASTLE • BRISBANE • DARWIN • PERTH • HAMILTON

Oil Analysis Report [OLXX03]

Demo Company - All Modules

Site 1

Tag Number: PT4545

Saturday, March 5, 2016

This report was prepared by TxMonitor® expressly for the customer as nominated on this page. Neither TxMonitor® nor any person acting in its behalf;

a) makes any warranty, express or implied, with respect to the use of any information or methods disclosed in this report, orb) assumes any liability with respect to the use of any information or methods disclosed in this report.

Any recipient of this document, by their acceptance or use of this document, releases TxMonitor® and their affiiates from any liability for direct, indirect, consequential or special loss or damage whether arising in contract, warranty, express or implied, tort or otherwise, and irrespective of fault, negligence and strict liability.

Email copies of this report are not official unless authenticated and signed by TxMonitor® and are not to be modified in any manner without the express written consent of TxMonitor® .

All analyses performed on samples as received and relate only to items tested or sampled. TxMonitor® is responsible for all information in the report except that provided by the customer. Data provided by the customer is clearly identified. In addition, information supplied by the customer can affect the validity of the results. If the test sample deviates from specified conditions and is to proceed to testing, the results may be compromised.

Historical results from other laborartories provided by our Clients are included for reference and diagnosis purposes.

Sampled in compliance with ISO/IEC 17025 - Testing.

The results of the tests, calibrations and/or measurements included in this document are traceable to Australian/National Standards.

Page 2: Oil Analysis Report [OLXX03] Demo Company - All Modules

Asset Description

Asset Tag: PT4545 Serial No.: 123456

Site: Site 1 Area: Substation 1

Power Rating: 17.50 MVA Voltage: 132kV/11kV Cooling: ODWF Oil Volume:

Asset Class: Power Transformer Manufacturer: Wilson YOM: 1977

Assessment: Caution

Additional interpretation of results are available on TxAnalyser Client Login

Next Sampling Date: Hayley CoulsonLaboratory Manager

IEEE Oil Quality Interpretation Guidelines (C57.106) Statement of Conformity

Guideline Result For a transformer of this age and voltage class.

Acidity < 0.15 0.02 Complies

Colour < 3.5 <0.5 Complies

Water < 25 7 Complies

Interfacial Tension > 30 36 Complies

Breakdown Voltage > 47 64 Complies

Power Factor @ 25°C < 0.5 0.0 Complies

Power Factor @ 100°C < 5 1.4 Complies

PCB < 2 <1 Complies

Specific Gravity < 0.92 0.89 Complies

IEEE DGA Interpretation Guidelines (C57.104-2008)

Guideline Result

Hydrogen < 100 700

Methane < 120 500

Ethane < 65 500

Ethylene < 50 500

Acetylene < 1 25

Carbon Monoxide < 350 99

Carbon Dioxide < 2500 990

TDCG < 720 2325

This sample falls under IEEE TDCG Condition 3.Hydrogen, Methane, Acetylene, Ethylene and Ethane levels are exceedingly elevated. In addition, Doernenburg Ratio and Furans may show a point of concern. Exercise extreme caution. Plan outage.

The 2FAL levels found in the sample (624 PPB) are high for the age of this transformer.

IEEE TDCG Condition Code LegendCondition 1: DGA is assessed as satisfactoryCondition 2: DGA gases are above normal operation levelsCondition 3: DGA gases exceed the recommended operation limitsCondition 4: DGA gases exceed the safe operating values

Diagnosis based on Gas Ratios:

CO2/CO ratio: Normal operation Doernenburg: .

Comments

Recommendations

Customer Details

Customer: Demo Company - All Modules Contact: Demo Admin Email: [email protected]

Page 2 of 9

TxMONITOR® - FIRST IN INDEPENDENT TRANSFORMER MANAGEMENT

This document becomes uncontrolled when printed

Unit 2, 15 Hector Street (West), Osborne Park, WA, 6916. Tel: 1300 819 454

Report No.: OLXX03 Client: Demo Company - All ModulesDate: 05/Mar/2016

Oil Analysis Report

Page 3: Oil Analysis Report [OLXX03] Demo Company - All Modules

Analysis Results

Sample Date 29/Feb/2016 24/Feb/2015 23/Jan/2011

Temp °C 35 25 31

Laboratory TxMonitor TxMonitor TxMonitor

Sample ID TX0003 TX002 TX0001

Dissolved Gas Analysis: ± denotes MU

ASTM-D3612 Hydrogen (H₂) PPM (±2) 700 450 350

ASTM-D3612 Methane (CH₄) PPM (±2) 500 250 174

ASTM-D3612 Ethylene (C₂H₄) PPM (±1) 500 50 34

ASTM-D3612 Ethane (C₂H₆) PPM (±2) 500 65 40

ASTM-D3612 Acetylene (C₂H₂) PPM (±2) 25 25 5

ASTM-D3612 Carbon Monoxide (CO) PPM (±30) 99 501 399

ASTM-D3612 Carbon Dioxide (CO₂) PPM (±250) 990 600 2490

ASTM-D3612 Oxygen (O₂) PPM (±55) 600 200 150

ASTM-D3612 Nitrogen (N₂) PPM (±115) 12,850 548 25

TDCG PPM 2,325 1,340 1,003

Oil Quality Tests: ± denotes MU

ASTM-D974 Acidity mgKOH/g (±0.01) 0.02 0.01 0.01

ASTM-D1500 Colour - <0.5 <0.5 <0.5

ASTM-D1533 Water Content PPM (±2) 7 5 6

ASTM-D971 Interfacial Tension mN/m (±2) 36 36 35

AS1767-1999 Breakdown Voltage Avg.kV (±12) 64 65 62

ASTM-D1524 Visual Examination - Clear & Bright Clear & Bright Clear & Bright

ASTM-D924 Power Factor @ 25°C % (±0.01) 0.02 0.01 0.02

ASTM-D924 Power Factor @ 100°C % (±0.01) 1.40 1.20 1.30

Furanic Compounds: ± denotes MU

ASTM-D5837 Furan 52HF PPB (±5) <3 6 6

ASTM-D5837 Furan 2FAL PPB (±5) 624 360 480

ASTM-D5837 Furan FOL PPB (±4) <10 <10 <10

ASTM-D5837 Furan 2ACF PPB (±6) <7 <7 <7

ASTM-D5837 Furan 5M2F PPB (±6) <5 <5 5

Calculated D.P. - 498 566 530

Calculated Remaining Life % 66 75 70

Note: Compliance Statement/Statement of Conformity - When the measurement results are within the appropriate standard guidelines, the standard guideline defines the compliance decision rule to be used and the measurement results meet the specified criteria (Complies). If the measurement result complies with appropriate standard guideline (ie: Complies), but falls outside the standard guideline when the uncertainty of measurement is applied, the client shall decide whether the result Complies or Fails based on the result being within the maximum permissible uncertainty prescribed in the specified criteria of the referenced standard guidelines.

Page 3 of 9

TxMONITOR® - FIRST IN INDEPENDENT TRANSFORMER MANAGEMENT

This document becomes uncontrolled when printed

Unit 2, 15 Hector Street (West), Osborne Park, WA, 6916. Tel: 1300 819 454

Report No.: OLXX03 Client: Demo Company - All ModulesDate: 05/Mar/2016

Oil Analysis Report

Page 4: Oil Analysis Report [OLXX03] Demo Company - All Modules

Analysis Results (cont.)

Sample Date 29/Feb/2016 24/Feb/2015 23/Jan/2011

Temp °C 35 25 31

Laboratory TxMonitor TxMonitor TxMonitor

Sample ID TX0003 TX002 TX0001

Special Tests: ± denotes MU

ASTM-D4243 Paper D.P. - 350 900 875

EPA-8082 PCB PPM (±1) <1 <1 <1

ASTM-D1298 Specific Gravity g/ml 0.89 0.89 0.89

ASTM-D1169 Resistivity @ 25°C GΩ-m (±5) 0.16 0.12 0.15

ASTM-D1169 Resistivity @ 100°C GΩ-m (±5) 0.20 0.18 0.15

ASTM-D2668 DBPC %w/w (±0.01) 0.07 0.16 0.25

ASTM-D2668 TIC %w/w (±0.01) 0.07 0.16 0.25

IEC-60296 IC Classification - Trace inhibited oil

Inhibited oil Inhibited oil

Particle Count:

Particles >4μm 600 1200 1500

Particles >6μm 52 100 132

Particles >21μm 20 56 85

Particles >38μm 2 5 12

Particles >70μm 1 2 5

ISO Code - 15/12/8 16/13/10 20/15/12

Note: Compliance Statement/Statement of Conformity - When the measurement results are within the appropriate standard guidelines, the standard guideline defines the compliance decision rule to be used and the measurement results meet the specified criteria (Complies). If the measurement result complies with appropriate standard guideline (ie: Complies), but falls outside the standard guideline when the uncertainty of measurement is applied, the client shall decide whether the result Complies or Fails based on the result being within the maximum permissible uncertainty prescribed in the specified criteria of the referenced standard guidelines.

Page 4 of 9

TxMONITOR® - FIRST IN INDEPENDENT TRANSFORMER MANAGEMENT

This document becomes uncontrolled when printed

Unit 2, 15 Hector Street (West), Osborne Park, WA, 6916. Tel: 1300 819 454

Report No.: OLXX03 Client: Demo Company - All ModulesDate: 05/Mar/2016

Oil Analysis Report

Page 5: Oil Analysis Report [OLXX03] Demo Company - All Modules

Corrosive Sulphur per ASTM D1275B

Details Class Description Photo

Sample ID: TX0003

Date: 29/02/2016

Non Corrosive 1a - Slight Tarnish Light Orange, almost the same as freshly polished strip

Sample ID: TX002

Date: 24/02/2015

Corrosive 4c - Corrosion Glossy or Jet Black

Sample ID: TX0001

Date: 23/01/2011

Non Corrosive 1a - Slight Tarnish Light Orange, almost the same as freshly polished strip

Page 5 of 9

TxMONITOR® - FIRST IN INDEPENDENT TRANSFORMER MANAGEMENT

This document becomes uncontrolled when printed

Unit 2, 15 Hector Street (West), Osborne Park, WA, 6916. Tel: 1300 819 454

Report No.: OLXX03 Client: Demo Company - All ModulesDate: 05/Mar/2016

Oil Analysis Report

Page 6: Oil Analysis Report [OLXX03] Demo Company - All Modules

Corrosive Sulphur per IEC 62535

Details Class Paper Description Copper Description Photo

Sample ID: TX0003

Date: 29/02/2016

Non Corrosive No deposits visible 1a - Slight Tarnish Light Orange, almost the same as freshly

polished strip

Sample ID: TX002

Date: 24/02/2015

Non Corrosive No deposits visible 4a - Corrosion Transparent Black, Dark Gray or Brown with Peacock Green

barely showing

Sample ID: TX0001

Date: 23/01/2011

Potentially Corrosive

No deposits visible 4b - Corrosion Graphite or lusterless

Black

Page 6 of 9

TxMONITOR® - FIRST IN INDEPENDENT TRANSFORMER MANAGEMENT

This document becomes uncontrolled when printed

Unit 2, 15 Hector Street (West), Osborne Park, WA, 6916. Tel: 1300 819 454

Report No.: OLXX03 Client: Demo Company - All ModulesDate: 05/Mar/2016

Oil Analysis Report

Page 7: Oil Analysis Report [OLXX03] Demo Company - All Modules

Corrosive Sulphur per DIN 51353

Details Class Photo

Sample ID: TX0003

Date: 29/02/2016

Absent

Sample ID: TX002

Date: 24/02/2015

Present

Sample ID: TX0001

Date: 23/01/2011

Absent

Page 7 of 9

TxMONITOR® - FIRST IN INDEPENDENT TRANSFORMER MANAGEMENT

This document becomes uncontrolled when printed

Unit 2, 15 Hector Street (West), Osborne Park, WA, 6916. Tel: 1300 819 454

Report No.: OLXX03 Client: Demo Company - All ModulesDate: 05/Mar/2016

Oil Analysis Report

Page 8: Oil Analysis Report [OLXX03] Demo Company - All Modules

Dissolved Gas Analysis

Trend Charts

Carbon Oxides

Page 8 of 9

TxMONITOR® - FIRST IN INDEPENDENT TRANSFORMER MANAGEMENT

This document becomes uncontrolled when printed

Unit 2, 15 Hector Street (West), Osborne Park, WA, 6916. Tel: 1300 819 454

Report No.: OLXX03 Client: Demo Company - All ModulesDate: 05/Mar/2016

Oil Analysis Report

Page 9: Oil Analysis Report [OLXX03] Demo Company - All Modules

Oil Quality

Furanic Compounds

Page 9 of 9

TxMONITOR® - FIRST IN INDEPENDENT TRANSFORMER MANAGEMENT

This document becomes uncontrolled when printed

Unit 2, 15 Hector Street (West), Osborne Park, WA, 6916. Tel: 1300 819 454

Report No.: OLXX03 Client: Demo Company - All ModulesDate: 05/Mar/2016