NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM...
Transcript of NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM...
Asset: P.S. 105 - QUEENS, 420 BEACH 51 STREET, New York, 11691
Inspection Id Inspection Type Time In Last Edited
SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM
AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53 PM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment 2nd Floor Shower Room (Storage); 1st Floor Locker Room andShower Room (Storage).
Principal(s) Information
Principal Name Laurie Shapiro
Organization P.S./M.S. 105 - Queens
Did you meet with this Principal? No
Did this Principal provide feedback? Yes
Summary of Principal's Feedback A Principal questionnaire form was returned with the followingcomments: 1.The building is in need of an electrical upgrade to supportthe present technology. 2. Some exterior doors and hardware need tobe replaced. 3. The Classrooms are in need of an A/C System.
Custodian Kevin White
Fireman Edward Lewis
Building Square Footage 86000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 3+B
Comments on the Number of Classrooms 43
Comments on the Year Built 1958
Student Population 833
Staff Population 125
Weather Fair
Facade Photo
Corner of Elizabeth Avenue and Beach 51stStreet - Southeast view
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 1 of 49
Main Entrance Photo
Facade A - Beach 51st Street
Roof Photo
Roof 1 - South view
Have any Systems/Major Building Components been upgraded? Yes
Systems: Partial Foundation Walls waterproofing
Year: 2016
Systems: Auditorium Stage rebuilding
Year: 2013
Systems: Exterior Walls repointing and repairs
Year: 2011
Systems: Exterior Modernization Program including Windows,Window Guards replacement (except at Staircases,Auditorium and Gymnasium); Partial Window Lintelsrepainting; Metal/Glass Panels replacement; Parapets andCoping replacement; Perimeter Roofing and Flashingreplacement.
Year: 2010
Systems: Exterior Walls, Parapets, Chimney and Bulkheadrepointing and repairs.
Year: 2009
Systems: Roofing and Flashing replacement
Year: 2000
Have there been any New Building Additions? Yes
Comments on New Building Additions 1963 + 25,000 S.F.
Tandem Schools? No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 2 of 49
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
Yes Tripping Hazard Damagedconcrete stairtread is apotentialtripping hazard.
EXTERIOR |STAIRS/RAMPS: EXTERIOR |STAIRS/RAMPS
South exit ataddition facingBeach ChannelDrive
Kevin White Custodian
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? No
Are SOME floors other than the 1st floor and basement accessible through compliantmeans?
No
Do any of the following spaces exist on the First floor? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs
Yes
For the rooms that do exist, are SOME of them accessible on the 1st floor? Yes
Boys and Girls or Unisex accessible toilets exist on the 1st floor? No
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings Yes Yes
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies No Change in Elevation
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms Room 214 Yes No Not on Accessible Route
Auditorium 1st Floor Yes Yes No Yes
Cafeteria 1st Floor Yes Yes No Yes
Classrooms 1st Floor Yes Yes
Computer Rooms No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 3 of 49
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Rooms & Spaces
Gymnasium 1st Floor Yes Yes No Yes
Library Room 101 Yes Yes
Main Office Room 110 Yes Yes
Multi-purpose Room No
Nurse's Room Room 108 Yes Yes
Pool No
Science Lab Room 106 Yes Yes
Toilet Rooms (Boys) 1st Floor - Inspected Room 115 Yes No Accessory ArrangementClear opening < 32"Sink ArrangementTurning RadiusUrinal ArrangementWater ClosetArrangement
Toilet Rooms (Girls) 1st Floor - Inspected Room 113 Yes No Accessory ArrangementClear opening < 32"Sink ArrangementTurning RadiusWater ClosetArrangement
Toilet Rooms (Staff) 1st Floor - Inspected Rooms 116 and 118 Yes No Accessory ArrangementClear opening < 32"No Lever-type HardwareSink ArrangementTurning RadiusUrinal ArrangementWater ClosetArrangement
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 4 of 49
Question Response
EXTERIOR
AREAWAY Does not Exist
AWNINGS AND CANOPIES Inspected
Condition 2 - Between Good and Fair
Deficiency CONCRETE: MAJOR CRACKS/SPALLING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade E
Violations No violations recorded.
CHIMNEY Inspected
Material Type(s) Masonry
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CORNICE Does not Exist
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 5 - Poor
Deficiency METAL: DETERIORATED DOOR AND FRAME - MINORDETERIORATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 5 of 49
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Roof Plan reference
Deficiency Quantity 4
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION
Roof Plan reference
Deficiency Quantity 4
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 6 of 49
Question Response
EXTERIOR
DOORS
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 3 - Fair
Deficiency METAL: BROKEN GLASS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
3rd Floor exit to Roof 2
Violations No violations recorded.
Deficiency METAL: DENTED, MAJOR RUSTING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 7 of 49
Question Response
EXTERIOR
DOORS
TRANSOM/SIDE LIGHT
Deficiency Photo1
Facade C
Violations No violations recorded.
EXTERIOR WALLS Inspected
Material Type(s) Masonry, Steel
Replacement Quantity 35,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 35,000
Instance Quantity Uom S.F.
Deficiency BRICK: MINOR CRACKS AND SPALLING
Roof Plan reference
Elevation
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 8 of 49
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency BRICK: EFFLORESCENCE
Roof Plan reference
Elevation
Deficiency Quantity 2,000
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 1
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 9 of 49
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan reference
Elevation
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
EXTERIOR SOFFITS Does not Exist
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency BROKEN/ DENTED BLADES
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 10 of 49
Question Response
EXTERIOR
LOUVER
Roof Plan reference
Elevation
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 8,000
Replacement Uom C.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 8,000
Instance Quantity Uom C.F.
Deficiency BRICK: EFFLORESCENCE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 11 of 49
Question Response
EXTERIOR
PARAPETS
Roof Plan reference
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 1
Deficiency Photo1 No photo recorded
Violations No violations recorded.
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 39,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
Deficiency DAMAGED/MISSING
Roof Plan reference
Deficiency Quantity 15
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 12 of 49
Question Response
EXTERIOR
ROOF
Roofing
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
Deficiency Photo1
Roof 1
Violations No violations recorded.
ROOF BARRIER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Built-Up: All Roofs
Instance Condition 3 - Fair
Instance Quantity 39,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2000
Source of Installation Custodial Staff
Deficiency BUILT-UP: ROOFING: LOSS OF GRAVEL
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action INSTALL NEW GRAVEL
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 13 of 49
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Deficiency Photo1
Roof 1
Violations No violations recorded.
Deficiency BUILT-UP: FLASHING: PITCH POCKET- POOR CONDITION
Roof Plan reference
Deficiency Quantity 20
Quantity Uom EACH
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 4 - Between Fair and Poor
Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR:CRACKS/SPALLING - MINOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 14 of 49
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 - Bulkhead 3
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOORAND FRAME
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE DOOR AND FRAME
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 15 of 49
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Deficiency Photo1
Roof 1 - Bulkhead 1
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: CMUCRACKS/SPALLING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 - Bulkhead 1
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: CMU OPENJOINTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 16 of 49
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 - Bulkhead 2
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR:EFFLORESCENCE
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 1
Deficiency Photo1 No photo recorded
Violations No violations recorded.
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 17 of 49
Question Response
EXTERIOR
ROOF
Specialties
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Inspected
Material Type(s) Glass
Condition 3 - Fair
Deficiency DAMAGED GUARDS
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
Deficiency BROKEN GLASS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 18 of 49
Question Response
EXTERIOR
ROOF
Specialties
SKYLIGHT/ROOF VENT Inspected
Deficiency Photo1
Roof 1
Violations No violations recorded.
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 3 - Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
RAILINGS Inspected
Condition 4 - Between Fair and Poor
Deficiency DAMAGED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 19 of 49
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
RAILINGS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
STAIRS/RAMPS Inspected
Condition 4 - Between Fair and Poor
Deficiency CONCRETE: CRACKS/SPALLING - MAJOR
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 20 of 49
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Photo1
Facade F
Violations No violations recorded.
Deficiency CONCRETE: WORN-OUT TREAD/RISER/NOSING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade E
Violations No violations recorded.
Deficiency STONE: OPEN JOINTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 21 of 49
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 10,000
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 3 - Fair
Deficiency DETERIORATED/TORN-OUT/MISSING
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 22 of 49
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS
Elevation
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade C
Violations No violations recorded.
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Other: All Facades (except All Staircases,Auditorium, Gymnasium)
Instance Condition 2 - Between Good and Fair
Instance Quantity 9,700
Instance Quantity Uom S.F.
Installation Year 2010
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on Aluminum - Other: All Staircases, Auditorium, Gymnasium
Instance Condition 3 - Fair
Instance Quantity 300
Instance Quantity Uom S.F.
Installation Year 1963
Source of Installation Custodial Staff
Deficiency ALUMINUM - OTHER: BEYOND USEFUL LIFE
Deficiency Location/Instance Aluminum - Other: All Staircases, Auditorium, Gymnasium
Deficiency Quantity 300
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 23 of 49
Question Response
EXTERIOR
WINDOWS
WINDOWS
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FLOOR STRUCTURE Inspected
Condition 4 - Between Fair and Poor
Deficiency CONCRETE SLAB ON GRADE: WATER INFILTRATION IN NON-INSTRUCTIONAL SPACE
Deficiency Location/Instance Basement - Fan Room, Corridor, Storage, Shop
Deficiency Quantity 400
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Fan Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Inspected
Foundation Walls Inspected
Condition 3 - Fair
Deficiency CRACKS, SPALLING
Deficiency Location/Instance Basement - Fan Room Access Vault
Deficiency Quantity 30
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 24 of 49
Question Response
INTERIOR
STRUCTURAL
VAULTS-BUNKERS
Foundation Walls
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Fan Room Escape Vault
Violations No violations recorded.
Slab Structure Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Vault/Ash Hoist Doors and Framing Inspected
Condition 5 - Poor
Deficiency DETERIORATED/DAMAGED VAULT/ASH HOIST DOORS ANDFRAMING
Deficiency Location/Instance Basement - Fan Room Access Vault
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Basement - Fan Room Access Vault
Violations No violations recorded.
AUDITORIUM Inspected
InspectedInstance on 1st Floor (400 Seats)
Ceiling
InspectedInstance on 1st Floor (400 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor (400 Seats)
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 25 of 49
Question Response
INTERIOR
AUDITORIUM
Door(s)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed H/C Lift
Does not ExistInstance on 1st Floor (400 Seats)
Fixed Seating
InspectedInstance on 1st Floor (400 Seats)
Condition 3 - Fair
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seats B/2, E/2, F/6, O/1, 3, and others
Deficiency Quantity 18
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Seats O/1, 3
Violations No violations recorded.
Floor Finish
InspectedInstance on 1st Floor (400 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor (400 Seats)
Stage
InspectedInstance on 1st Floor (400 Seats)
Stage Inspected
InspectedInstance on 1st Floor (400 Seats)
Condition 3 - Fair
Deficiency DAMAGED FLOOR
Deficiency Location/Instance Right side
Deficiency Quantity 35
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 26 of 49
Question Response
INTERIOR
AUDITORIUM
Stage
Stage
Deficiency Photo1
Right side
Violations No violations recorded.
Stage Curtain Rigging Inspected
InspectedInstance on 1st Floor (400 Seats)
Condition 1 - Good
Deficiency No deficiencies recorded
Stage Curtains Inspected
InspectedInstance on 1st Floor (400 Seats)
Condition 1 - Good
Deficiency No deficiencies recorded
Walls
InspectedInstance on 1st Floor (400 Seats)
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance Right rear near entrance
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Right rear near entrance
Violations No violations recorded.
Window Curtains/Shades/Blinds
InspectedInstance on 1st Floor (400 Seats)
Condition 1 - Good
Deficiency No deficiencies recorded
CAFETERIA Inspected
InspectedInstance on 1st Floor
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 27 of 49
Question Response
INTERIOR
CAFETERIA
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Center near ductwork, near servery
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center near ductwork
Violations No violations recorded.
Door(s)
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on 1st Floor
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Stage
Does not ExistInstance on 1st Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING
Deficiency Location/Instance Corridor near Rooms 216, 301, 310, 321, 324, Room 126, and others
Deficiency Quantity 200
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 28 of 49
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 324
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency METAL: DAMAGED LOUVER
Deficiency Location/Instance Room 120A
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 120A
Violations No violations recorded.
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 126, 212, 221, 224
Deficiency Quantity 4
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 29 of 49
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s)
Deficiency Photo1
Room 212
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Main Entrance Vestibule
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance Vestibule
Violations No violations recorded.
Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET
Deficiency Location/Instance Rooms 224, 319
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 30 of 49
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Room 319
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Room 224, Corridor near Room 323
Deficiency Quantity 320
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 323
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Corridor near Rooms 211, 301A, 304, 308, Room 212, and others
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 211
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance Corridor near Room 216
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 31 of 49
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Deficiency Photo1
Corridor near Room 216
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Corridor near Room 323
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 323
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 32 of 49
Question Response
INTERIOR
GYMNASIUM
Floor Finish
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Office
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Office
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Near Drinking Fountain
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Drinking Fountain
Violations No violations recorded.
Seating
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Stage
Does not ExistInstance on 1st Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 33 of 49
Question Response
INTERIOR
GYMNASIUM
Walls
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Office
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Office
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 3 - Fair
Deficiency DETERIORATED/TORN-OUT/MISSING
Deficiency Location/Instance Stairs A/2, B/1, C/2, 3 #6/3, and others
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair C/2
Violations No violations recorded.
KITCHEN Inspected
InspectedInstance on 1st Floor (600SF)
Ceiling
InspectedInstance on 1st Floor (600SF)
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 34 of 49
Question Response
INTERIOR
KITCHEN
Ceiling
Condition 3 - Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Office
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Office
Violations No violations recorded.
Deficiency METAL PAN: DAMAGED/MISSING
Deficiency Location/Instance Center, near sink
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Door(s)
InspectedInstance on 1st Floor (600SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 1st Floor (600SF)
Condition 5 - Poor
Deficiency CONCRETE: CRACKS
Deficiency Location/Instance Office
Deficiency Quantity 20
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 35 of 49
Question Response
INTERIOR
KITCHEN
Floor Finish
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Office
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Center, north, south, east, west sides, near Office
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Walls
InspectedInstance on 1st Floor (600SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Inspected
InspectedInstance on Room 101
Built-in Furnishing
InspectedInstance on Room 101
Condition 1 - Good
Deficiency No deficiencies recorded
Ceiling
InspectedInstance on Room 101
Condition 1 - Good
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 36 of 49
Question Response
INTERIOR
LIBRARY
Door(s)
InspectedInstance on Room 101
Condition 1 - Good
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Room 101
Condition 1 - Good
Deficiency No deficiencies recorded
Walls
InspectedInstance on Room 101
Condition 1 - Good
Deficiency No deficiencies recorded
LOCKER ROOM Inspected
InaccessibleInstance on 1st Floor
InspectedInstance on 2nd Floor (24 Lockers)
Alternative use Yes
Ceiling
InspectedInstance on 2nd Floor (24 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 2nd Floor (24 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 2nd Floor (24 Lockers)
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Near Gymnasium stair
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Gymnasium Stair
Violations No violations recorded.
Locker Room Lockers
InspectedInstance on 2nd Floor (24 Lockers)
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 37 of 49
Question Response
INTERIOR
LOCKER ROOM
Locker Room Lockers
Deficiency No deficiencies recorded
Walls
InspectedInstance on 2nd Floor (24 Lockers)
Condition 2 - Between Good and Fair
Deficiency MASONRY: CRACKS/SPALLING
Deficiency Location/Instance Near Gymnasium stair
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Gymnasium stair
Violations No violations recorded.
MULTI-PURPOSE ROOM Does not Exist
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Inspected
InspectedInstance on Room 106
Alternative use No
Fixed Equipment
InspectedInstance on Room 106
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Inspected
InaccessibleInstance on 1st Floor
InaccessibleInstance on 2nd Floor
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Partially
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING
Deficiency Location/Instance Stair C/1
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 38 of 49
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Ceiling
Deficiency Photo1
Stair C/1
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stair B/1
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/1
Violations No violations recorded.
Door(s) Inspected
Condition 3 - Fair
Deficiency METAL: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Stair B/1
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 39 of 49
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Door(s) Inspected
Stair B/1
Violations No violations recorded.
Partition Does not Exist
Railings Inspected
Condition 3 - Fair
Deficiency METAL: MISSING
Deficiency Location/Instance Stair on right side of Stage (Exit 7), Exit to Corridor from left side ofStage
Deficiency Quantity 14
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Stair on right side of stage (Exit 7)
Violations No violations recorded.
Stairs and Landings Inspected
Condition 3 - Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Stairs C/1, 3, #6/1, 2
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair #6/2
Violations No violations recorded.
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Stairs C/1, #6/1, Main Entrance Vestibule
Deficiency Quantity 40
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 40 of 49
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair C/1
Violations No violations recorded.
Deficiency STONE: BROKEN/MISSING
Deficiency Location/Instance Stairs A/2, C/2, Exit to Corridor from Auditorium Stage (left side)
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair C/2
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Stairs A/1, 2
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 41 of 49
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Deficiency Photo1
Stair A/2
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance Stair C/1 (both Vestibules)
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair C/1 (Vestibule)
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Inside Room 108, Room 216A
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 42 of 49
Question Response
INTERIOR
TOILET ROOMS - STAFF
Door(s)
Deficiency Photo1
Room 216A
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 5 - Poor
Deficiency RUST - MAJOR
Deficiency Location/Instance 3rd Floor Staff Toilet Room near Room 316
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
3rd Floor Staff Toilet Room near Room 316
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 213, 215, 222A, 223A, 313, 315
Deficiency Quantity 6
Quantity Uom EACH
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 43 of 49
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s)
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 315
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Room 213
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 213
Violations No violations recorded.
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency BROKEN/MISSING
Deficiency Location/Instance Room 215
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 44 of 49
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Stalls
Deficiency Photo1
Room 215
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 3 - Fair
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance North side of Building, Beach Channel Drive
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North side of Building
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 45 of 49
Question Response
SITE
FENCES
Violations No violations recorded.
Deficiency CHAIN LINK: DAMAGED POST/RAIL
Deficiency Location/Instance Beach 51st Street, Beach Channel Drive
Deficiency Quantity 30
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Beach 51st Street
Violations No violations recorded.
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance Beach 51st Street, Beach Channel Drive
Deficiency Quantity 120
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Beach 51st Street
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Elizabeth Street (fenced-off disposal area)
Deficiency Quantity 75
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 46 of 49
Question Response
SITE
PAVING
Student Non-Use
Concrete
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Elizabeth Street
Violations No violations recorded.
Pavers Does not Exist
Student Use Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance North side of Building, Beach 51st Street
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Beach 51st Street
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 47 of 49
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Location/Instance Elizabeth Street, Beach 51st Street, Beach Channel Drive
Deficiency Quantity 425
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Elizabeth Street
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Inspected
InspectedInstance on Along Beach Channel Drive
Benches
Does not ExistInstance on Along Beach Channel Drive
Fence
Does not ExistInstance on Along Beach Channel Drive
Pavement
Does not ExistInstance on Along Beach Channel Drive
Play Equipment
InspectedInstance on Along Beach Channel Drive
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Safety Surfacing
InspectedInstance on Along Beach Channel Drive
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Unpaved Area
Does not ExistInstance on Along Beach Channel Drive
PLAYING SURFACE Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
No
Condition 3 - Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Beach Channel Drive
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 48 of 49
Question Response
SITE
RETAINING WALLS
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Beach Channel Drive
Violations No violations recorded.
SEATING Does not Exist
SITE WALLS (NOT RETAINING WALLS) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS: EXTERIOR Inspected
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Site Cheek/flank Walls Inspected
Condition 2 - Between Good and Fair
Deficiency STUCCO CEMENT SURFACE: CRACKS/SPALLING - MINOR
Deficiency Location/Instance Beach Channel Drive
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Stairs/ramps Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q105
PB/A&W Print Date: 6/21/2019Page 49 of 49