NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New...

39
Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural - Senior 2020-07-14 11:18 AM 2020-09-11 10:39 AM AA : Q451 Architectural - Associate 2020-07-14 10:25 AM 2020-07-14 4:54 PM Asset Data Question Answer Was the building fully accessible for inspection Yes Principal(s) Information Principal Name William Bassell Organization Academy of American Studies High School - Annex - Queens Did you meet with this Principal? No Did this Principal provide feedback? Yes Summary of Principal's Feedback A Principal questionnaire form was returned with no comments regarding the physical conditions of the building. Custodian Danial Danvers Fireman Was not present Building Square Footage 12000 Comments on the Area Entire Building Leased Comments on the Stories (Floors) plus Basements 2+B Comments on the Number of Classrooms 7 Comments on the Year Built 1935 Student Population 287 Staff Population 21 Weather Fair Facade Photo Corner of 41st Avenue and 28th Street - South view NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2019 - 2020 Q451 PB/A&W Print Date: 9/13/2020 Page 1 of 39

Transcript of NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New...

Page 1: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101

Inspection Id Inspection Type Time In Last Edited

SA : Q451 Architectural - Senior 2020-07-14 11:18 AM 2020-09-11 10:39 AM

AA : Q451 Architectural - Associate 2020-07-14 10:25 AM 2020-07-14 4:54 PM

Asset Data

Question Answer

Was the building fully accessible for inspection Yes

Principal(s) Information

Principal Name William Bassell

Organization Academy of American Studies High School - Annex - Queens

Did you meet with this Principal? No

Did this Principal provide feedback? Yes

Summary of Principal's Feedback A Principal questionnaire form was returned with no commentsregarding the physical conditions of the building.

Custodian Danial Danvers

Fireman Was not present

Building Square Footage 12000

Comments on the Area Entire Building Leased

Comments on the Stories (Floors) plus Basements 2+B

Comments on the Number of Classrooms 7

Comments on the Year Built 1935

Student Population 287

Staff Population 21

Weather Fair

Facade Photo

Corner of 41st Avenue and 28th Street -South view

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 1 of 39

Page 2: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Main Entrance Photo

Facade A - 41st Avenue

Roof Photo

Roof 1 - Northeast view

Have any Systems/Major Building Components been upgraded? Yes

Systems: Vault Doors - replacement; Columns/Beams - repairs

Year: 2020

Systems: Exterior Walls, Windows - repairs

Year: 2017

Systems: Exterior Walls, Bulkhead Exterior Walls - repairs

Year: 2014

Systems: Coping, Roof Drains - replacement; Parapet, Roofing -repairs

Year: 2010

Systems: Exterior Guards, Windows - replacement

Year: 2008

Systems: Roofing - replacement

Year: 1985

Have there been any New Building Additions? No

Tandem Schools? No

Leased Space? Yes

Year Leased 1974

Inspection Full Inspection

Priority Condition

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 2 of 39

Page 3: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

Yes Potential FallingDebris

Deterioratedexterior concretewall is apotential fallingdebris hazard

EXTERIOR |EXTERIORWALLS

East corner ofthe 28th Streetfaçade at the2nd Floor level.

Daniel Danvers Custodian

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? No

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits No Distance between opendoors < 4'

Exterior H/C Lifts No No

Exterior Ramps and Railings No Yes

Interior Routes

Corridor and Lobby H/C Lifts No No

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies Yes

Interior Elevators No

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

Art Rooms No

Auditorium No

Cafeteria No

Classrooms None on Accessible Route Yes No Not on Accessible Route

Computer Rooms No

Gymnasium No

Library No

Main Office Room A101 Yes No Not on Accessible Route

Multi-purpose Room No

Nurse's Room No

Pool No

Science Lab No

Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route

Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 3 of 39

Page 4: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

Rooms & Spaces

Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Does not Exist

AWNINGS AND CANOPIES Inspected

Condition 3 - Fair

Deficiency CONCRETE: MAJOR CRACKS/SPALLING

Roof Plan reference

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 4 of 39

Page 5: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

AWNINGS AND CANOPIES

Deficiency Photo1

Facade A

Violations No violations recorded.

CHIMNEY Inspected

Material Type(s) Masonry

Condition 3 - Fair

Deficiency BRICK: MINOR CRACKS AND SPALLING

Roof Plan reference

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action RESTITCH

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1

Violations No violations recorded.

Deficiency BRICK: MAJOR / THRU CRACKS

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 5 of 39

Page 6: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

CHIMNEY

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REMOVE AND REBUILD

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1

Violations No violations recorded.

COPING Inspected

Condition 2 - Between Good and Fair

Deficiency METAL: OPEN TRANSVERSE JOINTS WITH DAMAGEDCAULKING

Roof Plan reference

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 6 of 39

Page 7: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

COPING

Deficiency Photo1

Facade A

Violations No violations recorded.

CORNICE Inspected

Condition 2 - Between Good and Fair

Deficiency PRE-CAST CONCRETE: MINOR CRACKS, SPALLING

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D

Violations No violations recorded.

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 5 - Poor

Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 7 of 39

Page 8: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Roof Plan reference

Deficiency Quantity 3

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

EXTERIOR WALLS Inspected

Material Type(s) Masonry, Concrete

Replacement Quantity 8,000

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 5 - Poor

Instance Quantity 8,000

Instance Quantity Uom S.F.

Deficiency BRICK: OPEN JOINTS

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 8 of 39

Page 9: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

EXTERIOR WALLS

Roof Plan reference

Elevation

Deficiency Quantity 1,000

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency CAST IN PLACE / PRE-CAST CONCRETE: MAJORCRACKS/SPALLING

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 9 of 39

Page 10: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Facade D

Violations No violations recorded.

Deficiency BRICK: DETERIORATED MASONRY SILLS

Roof Plan reference

Elevation

Deficiency Quantity 30

Quantity Uom L.F.

Potential Action REMOVE AND REPLACE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 10 of 39

Page 11: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

EXTERIOR WALLS

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B

Violations No violations recorded.

Deficiency CAST IN PLACE / PRE-CAST CONCRETE: MAJORCRACKS/SPALLING

Roof Plan reference

Elevation

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 11 of 39

Page 12: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

EXTERIOR WALLS

Facade A

Violations No violations recorded.

Deficiency STUCCO CEMENT SURFACE: CRACKS, SPALLING

Roof Plan reference

Elevation

Deficiency Quantity 300

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B

Violations No violations recorded.

Deficiency CAST IN PLACE / PRE-CAST CONCRETE: MINOR CRACKS,SPALLED, DETERIORATED REBAR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 12 of 39

Page 13: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

EXTERIOR WALLS

Roof Plan reference

Elevation

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B

Violations No violations recorded.

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 13 of 39

Page 14: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Deficiency Quantity 400

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B

Violations No violations recorded.

Deficiency GLASS BLOCK: OPEN JOINTS

Roof Plan reference

Elevation

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPOINT

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 14 of 39

Page 15: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

EXTERIOR WALLS

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency GLASS BLOCK: RUSTED SUB-FRAME

Roof Plan reference

Elevation

Deficiency Quantity 200

Quantity Uom L.F.

Potential Action REPLACE-IN-KIND

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 15 of 39

Page 16: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

EXTERIOR WALLS

Violations No violations recorded.

Deficiency GLASS BLOCK: CHIPPED/ BROKEN PIECES

Roof Plan reference

Elevation

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE-IN-KIND

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency STUCCO CEMENT SURFACE: WATER INFILTRATION ININSTRUCTIONAL SPACE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 16 of 39

Page 17: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

EXTERIOR WALLS

Roof Plan reference

Elevation

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A - Room 20 shown, Facade B - 1st Floor Men's ToiletRoom similar

Violations No violations recorded.

Deficiency GLASS BLOCK: WATER INFILTRATION IN INSTRUCTIONALSPACE

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 17 of 39

Page 18: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A - Stair A/2

Violations No violations recorded.

EXTERIOR SOFFITS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 3 - Fair

Deficiency BROKEN/ DENTED BLADES

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 18 of 39

Page 19: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

LOUVER

Elevation

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D

Violations No violations recorded.

PARAPETS Inspected

Material Type(s) Masonry

Replacement Quantity 1,800

Replacement Uom C.F.

InspectedInstance on Roof 1

Instance Condition 5 - Poor

Instance Quantity 1,800

Instance Quantity Uom C.F.

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 500

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 19 of 39

Page 20: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

PARAPETS

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B

Violations No violations recorded.

Deficiency BRICK: MINOR CRACKS, SPALLING

Roof Plan reference

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 Facade B

Violations No violations recorded.

Deficiency BRICK: OUT OF PLUMB

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 20 of 39

Page 21: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

PARAPETS

Roof Plan reference

Deficiency Quantity 500

Quantity Uom C.F.

Potential Action REMOVE AND REBUILD

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 Facade D

Violations No violations recorded.

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 5,000

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Does not Exist

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF BARRIER Does not Exist

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on Modified Bitumen: Roof 1

Instance Condition 3 - Fair

Instance Quantity 5,000

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 1985

Source of Installation Custodial Staff

Deficiency MODIFIED BITUMEN: ROOFING: BEYOND USEFUL LIFE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 21 of 39

Page 22: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Deficiency Location/Instance Modified Bitumen: Roof 1

Deficiency Quantity 5,000

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

ROOFING DRAINS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Specialties Inspected

BULKHEAD/PENTHOUSE Inspected

Condition 4 - Between Fair and Poor

Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOORAND FRAME

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE DOOR AND FRAME

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED LINTELS

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 22 of 39

Page 23: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Roof Plan reference

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: BRICKCRACKS/SPALLING

Roof Plan reference

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 23 of 39

Page 24: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Deficiency Photo1

Roof 1

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE CEILING: PLASTERDAMAGED/DETERIORATED

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1

Violations No violations recorded.

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

DUNNAGE STEEL Does not Exist

SKYLIGHT/ROOF VENT Does not Exist

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 24 of 39

Page 25: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

RAILINGS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

STAIRS/RAMPS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

WINDOWS Inspected

Replacement Quantity 2,000

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 4 - Between Fair and Poor

Deficiency STEEL: MAJOR RUSTING

Roof Plan reference

Elevation

Deficiency Quantity 400

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 25 of 39

Page 26: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

EXTERIOR

WINDOWS

LINTELS Inspected

Facade D

Violations No violations recorded.

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Double Hung: Facades A, B, D

Instance Condition 3 - Fair

Instance Quantity 2,000

Instance Quantity Uom S.F.

Installation Year 2008

Source of Installation Custodial Staff

Deficiency ALUMINUM - DOUBLE HUNG: INOPERABLE BALANCE

Roof Plan reference

Elevation

Deficiency Quantity 60

Quantity Uom EACH

Potential Action REPLACE BALANCES

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 3 - Fair

Deficiency STEEL COLUMNS/BEAMS: MINOR RUSTING

Deficiency Location/Instance Basement

Deficiency Quantity 10

Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 26 of 39

Page 27: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

INTERIOR

STRUCTURAL

COLUMNS/BEAMS/BEARING WALLS

Potential Action REPAIR AND REPAINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations No violations recorded.

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING

Deficiency Location/Instance Basement

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations No violations recorded.

FLOOR STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Basement

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 27 of 39

Page 28: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE

Deficiency Photo1

Boiler Room

Violations No violations recorded.

Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS

Deficiency Location/Instance Basement

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Concrete

Condition 2 - Between Good and Fair

Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED

Deficiency Location/Instance Basement

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 28 of 39

Page 29: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS Inspected

Deficiency Photo1

Boiler Room

Violations No violations recorded.

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Inspected

Foundation Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Slab Structure Inspected

Condition 3 - Fair

Deficiency METAL DECK AND CONCRETE: DETERIORATED

Deficiency Location/Instance Basement

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations No violations recorded.

Vault/Ash Hoist Doors and Framing Inspected

Condition 3 - Fair

Deficiency MINOR RUSTING

Deficiency Location/Instance Basement Storage Room egress doors

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 29 of 39

Page 30: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

INTERIOR

STRUCTURAL

VAULTS-BUNKERS

Vault/Ash Hoist Doors and Framing

Deficiency Photo1

Facade D

Violations No violations recorded.

AUDITORIUM Does not Exist

CAFETERIA Does not Exist

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK

Deficiency Location/Instance Room 20

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Room 20

Violations No violations recorded.

Deficiency ACOUSTIC TILES: DAMAGED/MISSING

Deficiency Location/Instance Rooms 12, 14, 21, 22, Corridor near Stair B/1, and others

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 30 of 39

Page 31: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Deficiency Photo1

Room 12

Violations No violations recorded.

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Room 11B

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 11B

Violations No violations recorded.

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Main Entrance Vestibule, Rooms 11A, A101, 14, 15, 23, and others

Deficiency Quantity 9

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 31 of 39

Page 32: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Door(s) Inspected

Room 14

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Corridor near Room 11B

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 11B

Violations No violations recorded.

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Main Entrance Lobby

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance Lobby

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK

Deficiency Location/Instance Room 20

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 32 of 39

Page 33: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Room 20

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Rooms 14, 22

Deficiency Quantity 70

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 14

Violations No violations recorded.

Specialties Does not Exist

GYMNASIUM Does not Exist

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

KITCHEN Does not Exist

LIBRARY Does not Exist

LOCKER ROOM Does not Exist

MULTI-PURPOSE ROOM Does not Exist

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Does not Exist

SCIENCE PREP ROOM Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 33 of 39

Page 34: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

INTERIOR

SHOWER ROOM Does not Exist

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? No

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Stair A/2

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair A/2

Violations No violations recorded.

Partition Does not Exist

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs and Landings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Stair A/2

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 34 of 39

Page 35: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Walls

Deficiency Photo1

Stair A/2

Violations No violations recorded.

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance 2nd Floor Women’s Toilet Room

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

2nd Floor Women’s Toilet Room

Violations No violations recorded.

Floor Finish Inspected

Condition 5 - Poor

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance 1st Floor Men’s Toilet Room

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 35 of 39

Page 36: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

INTERIOR

TOILET ROOMS - STAFF

Floor Finish

Deficiency Photo1

1st Floor Men’s Toilet Room

Violations No violations recorded.

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance 2nd Floor Women’s Toilet Room

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

2nd Floor Women’s Toilet Room

Violations No violations recorded.

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 3 - Fair

Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK

Deficiency Location/Instance 1st Floor Men’s Toilet Room

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 36 of 39

Page 37: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

INTERIOR

TOILET ROOMS - STAFF

Walls

Deficiency Photo1

1st Floor Men’s Toilet Room

Violations No violations recorded.

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance 1st Floor Boys Toilet Room, Girls Toilet Room

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

1st Floor Girls Toilet Room

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 5 - Poor

Deficiency RUST - MAJOR

Deficiency Location/Instance 1st Floor Boys Toilet Room

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 37 of 39

Page 38: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Stalls

Deficiency Photo1

1st Floor Boys Toilet Room

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Does not Exist

Drainage System for Asphalt Does not Exist

Drainage System for Concrete Does not Exist

Drainage System for Soil Does not Exist

DRINKING FOUNTAINS Does not Exist

FENCES Does not Exist

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Does not Exist

Student Use Does not Exist

Site Sidewalks & Walkways Does not Exist

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED CURBS

Deficiency Location/Instance 28th Street, 41st Avenue

Deficiency Quantity 50

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 38 of 39

Page 39: NYC Department of Education · Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q451 Architectural

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Deficiency Photo1

41st Avenue

Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance 28th Street, 41st Avenue

Deficiency Quantity 425

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

41st Avenue

Violations No violations recorded.

Pavers Does not Exist

PLAYGROUNDS Does not Exist

PLAYING SURFACE Does not Exist

RETAINING WALLS Does not Exist

SEATING Does not Exist

SITE WALLS (NOT RETAINING WALLS) Does not Exist

STAIRS/RAMPS: EXTERIOR Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q451

PB/A&W Print Date: 9/13/2020Page 39 of 39