Asset: HS FOR CONST.TRADES,ENGG.,& ARCH-Q, 94-06 104TH STREET, New York, 11416
Inspection Id Inspection Type Time In Last Edited
SA : Q650 Architectural - Senior 2019-04-05 8:00 AM 2019-04-23 12:15 PM
AA : Q650 Architectural - Associate 2019-04-05 8:58 AM 2019-04-05 8:23 PM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment Basement Boys and Girls Shower Rooms were sealed up. Also, aGenerator Enclosure was locked-no key.
Principal(s) Information
Principal Name Lakeisha Gordon
Organization High School for Construction Trades, Engineering, & Architecture -Queens
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal commented that the HVAC system requires frequentrepairs.
Custodian Amin Quanungo
Fireman William Vega
Building Square Footage 136000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 4+B
Comments on the Number of Classrooms 51
Comments on the Year Built 2006
Student Population 1052
Staff Population 65
Weather Fair
Facade Photo
Corner of 104th Street and 94th Avenue -Southwest View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 1 of 30
Main Entrance Photo
Facade A - 104th Street
Roof Photo
Roof 1 - Northeast View
Have any Systems/Major Building Components been upgraded? Yes
Systems: Limited Roofing repairs
Year: 2019
Systems: Limited Roofing repairs
Year: 2012
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
Yes Broken Glass A broken glassblock withexposed sharpedges is apotential safetyhazard.
EXTERIOR |EXTERIORWALLS
Glass block wallof the 95thAvenue façade.
Amin Quanungo Custodian
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 2 of 30
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings No No
Interior Routes
Corridor and Lobby H/C Lifts Yes Yes
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators Yes Yes
Interior Lobby Doors and Hardware Yes
Interior Ramps Yes Yes
Rooms & Spaces
Art Rooms Room 251 Yes Yes
Auditorium 1st Floor Yes Yes Yes Yes
Cafeteria Basement - Staff, Basement - Students Yes Yes Yes Yes
Classrooms 1st-4th Floors Yes Yes
Computer Rooms Rooms 224, 352, 356, 424 Yes Yes
Gymnasium Basement Yes Yes Yes Yes
Library Room 305 Yes Yes
Main Office Room 106 (HSCTEA), Room 143 (P233) Yes Yes
Multi-purpose Room No
Nurse's Room Room B30A Yes Yes
Pool No
Science Lab Rooms 320, 328 Yes Yes
Toilet Rooms (Boys) Basement-4th Floors Yes Yes
Toilet Rooms (Girls) Basement-4th Floors Yes Yes
Toilet Rooms (Staff) Basement-4th Floors Yes Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 3 of 30
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Does not Exist
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Does not Exist
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CORNICE Does not Exist
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 2 - Between Good and Fair
Deficiency ROLL-UP DOOR: DETERIORATED DOOR - MINORDETERIORATION
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 4 of 30
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry, Steel
Replacement Quantity 30,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 30,000
Instance Quantity Uom S.F.
Deficiency BRICK: WATER INFILTRATION IN INSTRUCTIONAL SPACE
Roof Plan reference
Elevation
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 5 of 30
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo1
Facade C - Room 328
Violations No violations recorded.
Deficiency GLASS BLOCK: CHIPPED/ BROKEN PIECES
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE-IN-KIND
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Facade B
Violations No violations recorded.
EXTERIOR SOFFITS Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 6 of 30
Question Response
EXTERIOR
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 12,000
Replacement Uom C.F.
InspectedInstance on All Roofs
Instance Condition 2 - Between Good and Fair
Instance Quantity 12,000
Instance Quantity Uom C.F.
Deficiency No deficiencies recorded
PLAZA DECK Inspected
InspectedInstance on Pavers: Roof 5
Instance Condition 3 - Fair
Instance Quantity 2,000
Instance Quantity Uom S.F.
Installation Year 2006
Source of Installation Custodial Staff
Deficiency PAVERS: PAVERS IN POOR CONDITION
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 5 - Plaza Deck
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 7 of 30
Question Response
EXTERIOR
PLAZA DECK Inspected
Violations No violations recorded.
ROOF Inspected
Roofing Inspected
Replacement Quantity 30,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF BARRIER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on IRMA: Roofs 1-4
Instance Condition 4 - Between Fair and Poor
Instance Quantity 30,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2006
Source of Installation Custodial Staff
Deficiency IRMA: ROOFING: MAJOR ACTIVE ROOF LEAKS ININSTRUCTIONAL SPACE
Roof Plan reference
Deficiency Quantity 250
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 8 of 30
Question Response
EXTERIOR
ROOF Inspected
Roofing
ROOFING
Deficiency Photo1
Roof 1 - Room 404 (Roof 4 - Corridor near Room 358, 2Locations, and Roof 2 - Room 356 similar)
Violations No violations recorded.
Deficiency IRMA: ROOFING: DAMAGED INSULATION
Roof Plan reference
Deficiency Quantity 140
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 4
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 9 of 30
Question Response
EXTERIOR
ROOF
Specialties
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist
WINDOWS Inspected
Replacement Quantity 6,000
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Other: All Facades
Instance Condition 2 - Between Good and Fair
Instance Quantity 6,000
Instance Quantity Uom S.F.
Installation Year 2006
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FLOOR STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Does not Exist
AUDITORIUM Inspected
InspectedInstance on 1st Floor (363 Seats)
Ceiling
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 10 of 30
Question Response
INTERIOR
AUDITORIUM
Ceiling
InspectedInstance on 1st Floor (363 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor (363 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed H/C Lift
Does not ExistInstance on 1st Floor (363 Seats)
Fixed Seating
InspectedInstance on 1st Floor (363 Seats)
Condition 2 - Between Good and Fair
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seats B/1, E/101, G/101, 111, K/103, and others
Deficiency Quantity 7
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Seat K/103
Violations No violations recorded.
Floor Finish
InspectedInstance on 1st Floor (363 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor (363 Seats)
Stage
InspectedInstance on 1st Floor (363 Seats)
Stage Inspected
InspectedInstance on 1st Floor (363 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtain Rigging Inspected
InspectedInstance on 1st Floor (363 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtains Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 11 of 30
Question Response
INTERIOR
AUDITORIUM
Stage
Stage Curtains
InspectedInstance on 1st Floor (363 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 1st Floor (363 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor (363 Seats)
CAFETERIA Inspected
InspectedInstance on Basement - Staff (600 SF)
InspectedInstance on Basement - Students
Ceiling
InspectedInstance on Basement - Staff (600 SF)
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Rear
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Rear
Violations No violations recorded.
Door(s)
InspectedInstance on Basement - Staff (600 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement - Students
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on Basement - Staff (600 SF)
Does not ExistInstance on Basement - Students
Floor Finish
InspectedInstance on Basement - Staff (600 SF)
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 12 of 30
Question Response
INTERIOR
CAFETERIA
Floor Finish
Deficiency No deficiencies recorded
InspectedInstance on Basement - Students
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on Basement - Students
Does not ExistInstance on Basement - Staff (600 SF)
Stage
Does not ExistInstance on Basement - Staff (600 SF)
Does not ExistInstance on Basement - Students
Walls
InspectedInstance on Basement - Students
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement - Staff (600 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement - Staff (600 SF)
Does not ExistInstance on Basement - Students
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED - ACTIVELEAK
Deficiency Location/Instance Corridor near Room 358
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 358
Violations No violations recorded.
Deficiency ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK
Deficiency Location/Instance Rooms 328, 356, 404
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 13 of 30
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Room 328
Violations No violations recorded.
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Corridor near Rooms 130, 402, 413, 420
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 413
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET
Deficiency Location/Instance Rooms 208, 356
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 14 of 30
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Room 208
Violations No violations recorded.
Deficiency EPOXY FLOORING: CRACKS/SPALLING
Deficiency Location/Instance Room 320
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 320
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance Corridor near Room 352, Room 352
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 15 of 30
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls Inspected
Room 352
Violations No violations recorded.
Specialties Inspected
Classroom Locker(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Seating Does not Exist
GYMNASIUM Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Office
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Office
Violations No violations recorded.
Door(s)
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Seating
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 16 of 30
Question Response
INTERIOR
GYMNASIUM
Sliding-folding Partition
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage
Does not ExistInstance on Basement
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency MASONRY: CRACKS/SPALLING
Deficiency Location/Instance Near Room B35A2
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Room B35A2
Violations No violations recorded.
Deficiency WALL PADDING: DETERIORATED
Deficiency Location/Instance Near Visitor Locker Room, Near Office, Near Drinking Fountain
Deficiency Quantity 160
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Visitor Locker Room
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement
INTERIOR DOOR HARDWARE Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 17 of 30
Question Response
INTERIOR
INTERIOR DOOR HARDWARE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Rooms B60A, B60J
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room B60J
Violations No violations recorded.
Door(s)
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Inspected
InspectedInstance on Room 305
Built-in Furnishing
InspectedInstance on Room 305
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Ceiling
InspectedInstance on Room 305
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 18 of 30
Question Response
INTERIOR
LIBRARY
Ceiling
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room 305
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Room 305
Condition 2 - Between Good and Fair
Deficiency CARPET: TRIPPING HAZARD - ELECTRICAL OUTLET
Deficiency Location/Instance Room 305E
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Room 305E
Violations No violations recorded.
Walls
InspectedInstance on Room 305
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance Right Side
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Right Side
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 19 of 30
Question Response
INTERIOR
LIBRARY Inspected
Walls
Violations No violations recorded.
LOCKER ROOM Inspected
InspectedInstance on Basement - Boys (490 Lockers)
Alternative use No
InspectedInstance on Basement - Girls (486 Lockers)
Alternative use No
InspectedInstance on Basement - Visitors (31 Lockers)
Alternative use No
Ceiling
Does not ExistInstance on Basement - Visitors (31 Lockers)
Does not ExistInstance on Basement - Boys (490 Lockers)
Does not ExistInstance on Basement - Girls (486 Lockers)
Door(s)
InspectedInstance on Basement - Boys (490 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement - Girls (486 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement - Visitors (31 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Basement - Boys (490 Lockers)
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Near Locker 38
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Locker 38
Violations No violations recorded.
Locker Room Lockers
InspectedInstance on Basement - Boys (490 Lockers)
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 20 of 30
Question Response
INTERIOR
LOCKER ROOM Inspected
Locker Room Lockers
Deficiency DAMAGED UNITS
Deficiency Location/Instance Lockers 368, 376, 409, 474
Deficiency Quantity 4
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Locker 474
Violations No violations recorded.
Walls
InspectedInstance on Basement - Boys (490 Lockers)
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Near Locker 1
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Locker 1
Violations No violations recorded.
MULTI-PURPOSE ROOM Does not Exist
SCIENCE DEMO ROOM Inspected
InspectedInstance on Rooms 310, 316, 332, 336
Alternative use No
Fixed Equipment
InspectedInstance on Rooms 310, 316, 332, 336
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 21 of 30
Question Response
INTERIOR
SCIENCE LAB Inspected
InspectedInstance on Room 320
Alternative use No
InspectedInstance on Room 328
Alternative use No
Fixed Equipment
InspectedInstance on Room 320
Condition 2 - Between Good and Fair
Deficiency CABINETRY: MISSING/DAMAGED
Deficiency Location/Instance Room 320
Deficiency Quantity 2
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 320
Violations No violations recorded.
SCIENCE PREP ROOM Inspected
InspectedInstance on Room 324
Alternative use No
Fixed Equipment
InspectedInstance on Room 324
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SHOWER ROOM Inspected
InspectedInstance on Basement - Visitors
Alternative use Yes
InaccessibleInstance on Basement - Girls
InaccessibleInstance on Basement - Boys
Ceiling
InspectedInstance on Basement - Visitors
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement - Visitors
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Basement - Visitors
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 22 of 30
Question Response
INTERIOR
SHOWER ROOM
Floor Finish
Deficiency No deficiencies recorded
Walls
InspectedInstance on Basement - Visitors
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Partition Does not Exist
Railings Inspected
Condition 3 - Fair
Deficiency METAL: BROKEN BRACKET
Deficiency Location/Instance Stair B/1
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/1
Violations No violations recorded.
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency MASONRY: CRACKS/SPALLING
Deficiency Location/Instance Stair B/1,3,4
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 23 of 30
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Deficiency Photo1
Stair B/4
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Does not Exist
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Room 417
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 417
Violations No violations recorded.
Door(s) Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 24 of 30
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FENCES Inspected
Condition 3 - Fair
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance Schoolyard
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 25 of 30
Question Response
SITE
FENCES Inspected
Deficiency Photo1
Schoolyard
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 3 - Fair
Deficiency LOCALIZED SINK AREA
Deficiency Location/Instance Schoolyard
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 300
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 26 of 30
Question Response
SITE
PAVING
Student Use
Asphalt
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Site Sidewalks & Walkways Inspected
Asphalt Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Near 95th Avenue
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near 95th Avenue
Violations No violations recorded.
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Along 104th Street, Along 95th Avenue
Deficiency Quantity 50
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 27 of 30
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Concrete
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Along 104th Street
Violations No violations recorded.
Pavers Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED CURBS
Deficiency Location/Instance 94th Avenue
Deficiency Quantity 5
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
94th Avenue
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance 104th Street, 94th Avenue, 95th Avenue
Deficiency Quantity 350
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 28 of 30
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Purpose of Action LEVEL 2
Deficiency Photo1
104th Street
Violations No violations recorded.
Pavers Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PLAYGROUNDS Inspected
InspectedInstance on Schoolyard
Benches
Does not ExistInstance on Schoolyard
Fence
Does not ExistInstance on Schoolyard
Pavement
Does not ExistInstance on Schoolyard
Play Equipment
InspectedInstance on Schoolyard
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Safety Surfacing
InspectedInstance on Schoolyard
Condition 2 - Between Good and Fair
Deficiency DETERIORATED/MISSING
Deficiency Location/Instance Schoolyard
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 29 of 30
Question Response
SITE
PLAYGROUNDS
Safety Surfacing
Schoolyard
Violations No violations recorded.
Unpaved Area
Does not ExistInstance on Schoolyard
PLAYING SURFACE Does not Exist
RETAINING WALLS Does not Exist
SEATING Inspected
Benches Inspected
Concrete Does not Exist
Metal/Wood/Plastic Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Bleachers Does not Exist
SITE WALLS (NOT RETAINING WALLS) Inspected
Condition 2 - Between Good and Fair
Deficiency MASONRY UNIT: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Schoolyard, Near 95th Avenue
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q650
PB/A&W Print Date: 6/20/2019Page 30 of 30