Photo/isometric drawing provided by manufacturer Nuaire Thermal Ducting Description of Product This is an assessment of the Nuaire insulated ducting system for a mechanical ventilation system with heat recovery. Nuaire’s new range of thermal duct is specifically designed to comply with 2010 Building Regulations to significantly improve thermal conductivity and thermal resistance of ventilation ducting used in domestic properties and with its unique quick fix clip system can significantly reduce the amount of time required to install a compliant insulated ductwork system. Key Factors Assessed Safety in case of Fire Health, Hygiene and Environmental Safety in Use Energy Economy and heat retention Validity This certificate was first issued on 25 th April 2014 and is valid until 25 th April 2018. Issue Dated 22 nd May 2015 Certificate No: EWW415

Transcript of Nuaire Thermal DuctingNuaire Thermal Ducting Description of Product . This is an assessment of the...

Page 1: Nuaire Thermal DuctingNuaire Thermal Ducting Description of Product . This is an assessment of the Nuaire insulated ducting system for a mechanical ventilation ... Heating and ventilation

Photo/isometric drawing

provided by manufacturer

Nuaire Thermal Ducting

Description of Product

This is an assessment of the Nuaire insulated

ducting system for a mechanical ventilation

system with heat recovery. Nuaire’s new range

of thermal duct is specifically designed to

comply with 2010 Building Regulations to

significantly improve thermal conductivity and

thermal resistance of ventilation ducting used

in domestic properties and with its unique

quick fix clip system can significantly reduce

the amount of time required to install a

compliant insulated ductwork system.

Key Factors Assessed

Safety in case of Fire

Health, Hygiene and Environmental

Safety in Use

Energy Economy and heat retention

Validity

This certificate was first issued on 25th April 2014 and is valid until 25th April 2018.

Issue Dated 22nd May 2015

Certificate No: EWW415

Page 2: Nuaire Thermal DuctingNuaire Thermal Ducting Description of Product . This is an assessment of the Nuaire insulated ducting system for a mechanical ventilation ... Heating and ventilation

Ducting should be insulated where it passes through unheated areas and voids (e.g. loft spaces) with equivalent of at least

25mm of a material having a thermal conductivity of ≤0.04W/(m.K) to reduce the possibility of condensation forming. Where a

duct extends above roof level the section above the roof should be insulated or a condensate trap should be fitted just below

roof level.

The Ducting only has been assessed and will be used in conjunction with an appropriate mechanical ventilation system.

The ducting is satisfactory both in pressure loss and thermal conductance and should only be used in accordance with the

limitations identified below.

Approved document Part B Vol I 2006 Fire safety: section 2.6 and sequence

BS 9991:2011 Fire safety in the design, management and use of residential buildings: clause 32.2

Approved document Part F 2010 Ventilation: section 43.4-4.36, and table 5.2d

The length of pipework is to be designed on an individual basis for each property type for both NTD 204 and NTD 125 systems

Intumescent grills to be fitted at each penetration in fire floors

Not for use if penetrating fire walls

This duct is only suitable for use in a fully designed mechanical ventilation systems

Use rigid duct for the majority of your installation

Should not be installed where it can be crushed

A non-hardening acrylic sealant and aluminium duct tape should be used to connect ductwork.

Nuaire’s CONTRAP should be used with the ductwork to prevent backflow of moisture going to the fan unit.

Page 3: Nuaire Thermal DuctingNuaire Thermal Ducting Description of Product . This is an assessment of the Nuaire insulated ducting system for a mechanical ventilation ... Heating and ventilation

LABC consider that, Nuaire Thermal Ducting, will meet the functional requirements of the Building

Regulations (listed below) if the criteria detailed in this certificate are met;

The Building Regulations 2010 (as amended) England & Wales

Regulation 7 Materials and workmanship

Note: The products are acceptable.

AD B Fire Safety

Note: Subject to limitations detailed below in Conditions section.

AD F Ventilation

Note: Subject to limitations detailed below in Conditions section.

AD L1B Conservation of fuel and power

Note: The thermal insulation performance of this system should be considered in the

context of the contribution made to the overall performance of the roof structure.

The Building Regulations 2010 (as amended) England

AD L1A Conservation of fuel and power

Note: The thermal insulation performance of this system should be considered in the

context of the contribution made to the overall performance of the roof structure.

The Building Regulations 2010 (as amended) Wales

AD L1A Conservation of fuel and power

Note: The thermal insulation performance of this system should be considered in the

context of the contribution made to the overall performance of the roof structure.

The Building (Scotland) Regulations 2004 (as amended)

If you would like to discuss a specific use of the product in Scotland it will require an additional

assessment under the Scottish Building Regulations and accordingly you should contact the

LABSS STAS Administrator at www.labss.org

Page 4: Nuaire Thermal DuctingNuaire Thermal Ducting Description of Product . This is an assessment of the Nuaire insulated ducting system for a mechanical ventilation ... Heating and ventilation

LABC Warranty

This product confirms to the Functional Requirements of the LABC Warranty Technical Manual.

Heating and ventilation contractors association DW/143 ductwork leakage testing

Heating and ventilation contractors association DW/154 specifications for plastic ductwork

BS EN 12667:2001 Thermal performance

BS EN 13501-1:2002 Fire classifications for construction products and building elements

Domestic ventilation compliance guide

BRE test report 293579

BRE test report 293578

Nuaire Ductmaster brochure Environmental product declaration

Neopor brochure raw materials

Neopor Innovation in insulation

Nuaire thermal ducting

Certificate of conformity

Thermal report 1

Thermal report 2

NHBC Standards 2014 Chapter 3.2 `Mechanical ventilation with heat recovery'

LABC Warranty Technical Manual Chapter 9.4 Heating & mechanical services

Page 5: Nuaire Thermal DuctingNuaire Thermal Ducting Description of Product . This is an assessment of the Nuaire insulated ducting system for a mechanical ventilation ... Heating and ventilation

Nuaire Ltd

Western Industrial Estate

Caerphilly

CF83 1NA

Tel: 029 2085 800

Email: [email protected]

Web: www.nuaire.co.uk

Page 6: Nuaire Thermal DuctingNuaire Thermal Ducting Description of Product . This is an assessment of the Nuaire insulated ducting system for a mechanical ventilation ... Heating and ventilation

RD Certificate Number: EWW415 Nuaire Thermal Ducting

Description

This is an assessment of the Nuaire insulated ducting system for a mechanical

ventilation system with heat recovery. Nuaire’s new range of thermal duct is

specifically designed to comply with 2010 Building Regulations to significantly

improve thermal conductivity and thermal resistance of ventilation ducting used

in domestic properties and with its unique quick fix clip system can significantly

reduce the amount of time required to install a compliant insulated ductwork

system.

Scope of Registration

Due to space limitations, the Registered Detail certificate should be consulted

for the full scope of this registration.

Validity

This system has been checked for compliance in accordance with English and Welsh Building Regulations.

LABC Warranty also accepts its use when installed and used in accordance with and in relation to LABC Warranty’s current

Technical Standards.

Registration was first issued on 25/04/14 and is valid until 25/04/18 providing there are no amendments to applicable

regulations.

Issue dated 22/05/2015

Further Information

For more detailed information including access to the full certificate and supporting documents please use this link

http://www.labc.co.uk/our-services/registered-details/eww415-nuaire-thermal-duct

Nuaire Ltd

Western Industrial Estate

Caerphilly

CF83 1NA

Tel: 029 2085 800

Email: [email protected]