SCOPE OF WORK
SYSTEM SIZE:
2.990KW-AC
3.190KW-DC
ROOF MOUNT PV SOLAR
ROOF TYPE:Comp. Shingle
2 X 6 @ 16" O.C. Rafters
ARRAY/ROOF PITCH: 16°
AZIMUTH: 100°,280°
TWO STORY HOUSE
MODULES :
(11) SILEVO TRIEX U290
INVERTER(S) :
(1) ABB PVI-3.0-OUTD -US
PV RAIL:
ZEP SOLAR
PV MOUNT:
ZEP SOLAR
4.5” LAG SCREWS
1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE LATEST CALIFORNIA CODE OF
REGULATIONS (CCR),NATIONAL ELECTRICAL CODE EDITION AND ALL APPLICABLE LOCAL CODES
AND REGULATIONS. (CONSTRUCTION SHALL COMPLY WITH 2016 CBC, CMC, CPC, CEC, CRC,CFC)
2. ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS IN
COMPLIANCE TO UL REQUIREMENTS TO ACCOMMODATE CONDUCTORS SHOWN
3.WHERE WIRE SIZES ARE INDICATED ON PLANS FOR INDIVIDUAL CIRCUITS, THE WIRE SIZE
INDICATED SHALL APPLY TO THE COMPLETE CIRCUIT, UNLESS OTHERWISE NOTED.
4.CONTRACTOR SHALL EXTEND WIRING FROM ALL JUNCTION BOXES, SWITCHES, ETC. AND
MAKE FINAL CONNECTIONS AS REQUIRED TO ALL BUILDING EQUIPMENT REQUIRING
ELECTRICAL CONNECTIONS.
5.DRAWINGS AND DIAGRAMMIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND
WORK INCLUDED. FOLLOW DRAWING AND LAYOUT WORK AND CHECK DRAWINGS OR OTHER
TRADES RELATING TO WORK TO VERIFY SPACE IN WHICH WORK WILL BE INSTALLED. MAINTAIN
HEADROOM AND MINIMUM CODE REQUIRED WORKING CLEARANCES AT ALL TIMES.
6.ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT INCLUDING THOSE THAT ARE EXPOSED
TO OUTSIDE ENVIRONMENT SHALL BE WEATHERPROOF TYPE NEMA 3R.
7.DISCONNECT SWITCHES SHALL BE MOUNTED ON INDIVIDUAL SUPPORTS, OR OTHERWISE
DIRECTLY ON EQUIPMENT, PROVIDED NO MODIFICATION TO EQUIPMENT IS NECESSARY.
8.ALL ELECTRICAL MATERIAL SHALL BE LISTED BY "UL" FOR THE TYPE OF APPLICATION AND "UL"
LABEL SHALL APPEAR ON ALL ELECTRICAL EQUIPMENT.
9.WIRING METHOD SHALL BE EMT ABOVE GROUND MOUNTED IN CONCEALED SPACES (UNLESS
APPROVED OTHERWISE) AND SCHEDULE- 40 PVC FOR BELOW GROUND INSTALLATION UNLESS
NOTED OTHERWISE.
10.AN OSHA APPROVED LADDER PROVIDING ACCESS TO ALL PORTIONS OF THE ARRAY SHALL
BE SECURED IN PRIOR TO REQUESTING INSPECTION.
11.SMOKE ALARMS AND CARBON MONOXIDE DETECTORS WILL MEET THE NECESSARY
REQUIREMENTS PER CRC R314, R315
12.UTILITY COMPANY WILL BE NOTIFIED PRIOR TO ACTIVATION OF THE SOLAR PV SYSTEM.
13.ALL EXTERIOR CONDUIT PAINTED TO MATCH EXTERIOR SURFACE. (IF APPLICABLE)
14. NO PLUMBING, MECHANICAL OR BLDG VENTS TO BE COVERED OR OFFSET AROUND ARRAYS
15.EXISTING PLUMBING VENTS, SKYLIGHTS, EXHAUST OUTLETS, VENTILATION'S INTAKE AIR
OPENINGS SHALL NOT BE COVERED BY THE SOLAR PHOTOVOLTAIC SYSTEM.
16.ALL EQUIPMENT SHALL BE LISTED AND LABELED BY A RECOGNIZED ELECTRICAL TESTING
LABORATORY AND INSTALLED PER THE LISTING REQUIREMENTS AND THE MANUFACTURER'S
INSTRUCTIONS. [NEC 690.4(D)]
17.ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED, INCLUDING ALL ROOF MOUNTED
TRANSITION BOXES AND SWITCHES.
18.PAINT PV CONDUIT TO MATCH THE DWELLING EXTERIOR.
19.CONTACT THE SERVICING UTILITY BEFORE POWERING ON THE PHOTOVOLTAIC SYSTEM.
1. COVER PAGE2. PLOT PLAN/ROOF PLAN3. RAFTER SIDE VIEW4. ELECTRICAL DIAGRAM5. WARNING LABELS6. SPECS7. SPECS8. SPECS9. SPECS10. SPECS11. SPECS12. SPECS
VICINITY MAP
INDEX SHEET
SUNROOF VIEW AERIAL VIEW
GOVERNING CODES
GENERAL NOTES
PROJECT DESCRIPTION
THIS ROOF-MOUNTED PHOTOVOLTAIC (PV) SYSTEM IS TO BE INSTALLED AT THE
SINGLE FAMILY RESIDENTIAL IN LYNWOOD, CALIFORNIA.
THE ENERGY PRODUCED BY THE PV SYSTEM SHALL BE INTERCONNECTED WITH THE
UTILITY GRID THROUGH THE EXISTING ON-SITE ELECTRICAL EQUIPMENT VIA A
BACK-FED BREAKER IN THE MAIN SERVICE PANEL.
OWNER / ADDRESS
*
*
Lynwood CA 90262
PHONE:*
OCCUPANCY R3 /
TYPE 5 STRU.
APN#: *
CONTRACTOR
Home Owner Builder
*
Lynwood CA 90262
PHONE:*
STATE TYPE : -
STATE LICENSE# : -
EXPIRATION DATE : -
DATE: 01/10/18
REVISION :
© C
op
yrig
ht 2017-S
olar P
V P
erm
it
SYSTEM SIZE
2.990 KW-AC
3.190 KW-DC
REVISION :
PAGE INFORMATION
STAMP/ SIGNATURE :
MODULES :
(11) SILEVO TRIEX U290
DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General
Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.
INVERTER(S) :
(1) ABB PVI-3.0-OUTD-US
TITLE:
COVER PAGE
PV-01
www.solarpvpermit.com
Prepared by:
N
ALL MODULES AND RAIL ARE LISTED BY UNDERWRITER'S LABORATORIES
FOR ELECTRICAL AND FIRE SAFETY(CLASS A FIRE RATING)
NOTE:
1) NO DISCHARGE OF ANY POLLUTANTS TO ANY STORM DRAIN SYSTEM.
2) UL 1703 FOR MODULES & UL 1741 FOR INVERTERS PER CITY SOLAR
REQUIREMENTS.
THIS PROJECT SHALL COMPLY WITH THE :
2016 CA BUILDING CODE 1507.17, 1509.7, 3111
2016 CA PLUMBING CODE
2016 CA RESIDENTIAL CODE R331, R908
2016 CA ENERGY CODE
2016 CA MECHANICAL CODE
2016 CA FIRE CODE 605.11
2016 CA ELECTRICAL CODE - 2014 NEC -110, 240, 250, 690, 705
ORDINANCES OF THE CITY OF LYNWOOD
P
/L
4
7
'-6
"
P
/L
4
7
'-6
"
P
/L
1
3
8
'
P
/L
1
3
8
'DR
IVEW
AY
(E)GARAGE
5416 CLARK ST .
ROOF ACCESS POINT
SITE PLAN : SCALE: 1/16"=1'-0N
9
6
'-1
0
"
6
'-3
"
1
9
'-8
"
VENT / ROOF
OBSTRUCTION (TYP)
ARRAY 1:
QTY:6
TILT:16°
AZIMUTH: 100°
ARRAY 2:
QTY:5
TILT:16°
AZIMUTH: 280°
AC DISCONNECT
PRODUCTION METER
MAIN SERVICE PANEL
INVERTER
ROOF ACCESS POINT
2
5
'-6
"
DRIV
EWAY
ARRAY 1:
QTY:6
TILT:16°
AZIMUTH: 100°
ROOF ACCESS POINT
N
3'-0" FIRE SETBACK
RAPID SHUTDOWN
EMT CONDUIT RUN ON
ROOF OR IN ATTIC
VENT / ROOF
OBSTRUCTION (TYP)
ARRAY 2:
QTY:5
TILT:16°
AZIMUTH: 280°
ROOF PLAN : SCALE: 3/32"=1'-0
ROOF ACCESS POINT
AC DISCONNECT
PRODUCTION METER
MAIN SERVICE PANEL
INVERTER
(E)GARAGE
OWNER / ADDRESS
*
*
Lynwood CA 90262
PHONE:*
OCCUPANCY R3 /
TYPE 5 STRU.
APN#: *
CONTRACTOR
Home Owner Builder
*
Lynwood CA 90262
PHONE:*
STATE TYPE : -
STATE LICENSE# : -
EXPIRATION DATE : -
DATE: 01/10/18
REVISION :
© C
op
yrig
ht 2017-S
olar P
V P
erm
it
SYSTEM SIZE
2.990 KW-AC
3.190 KW-DC
REVISION :
PAGE INFORMATION
STAMP/ SIGNATURE :
MODULES :
(11) SILEVO TRIEX U290
DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General
Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.
INVERTER(S) :
(1) ABB PVI-3.0-OUTD-US
TITLE:
SITE PLAN / ROOF PLAN
PV-02
2x6 RAFTERS @ 16" O.C.
(TYP)
ARRAY 1:
QTY:6
TILT:16°
AZIMUTH: 100°
4'-0"
Max.
ZEP SOLAR
COMP MOUNT
3'-0" 15'-7" 8'-6"
4'-9"
6'-11"
VENT / ROOF
OBSTRUCTION (TYP)
3'-0"
3'-0"
8'-8"
15'-7"
1'-5"
ARRAY 2:
QTY:5
TILT:16°
AZIMUTH: 280°
SCALE: 3/16"=1'-0
2x6 RAFTERS @
16" ON CENTER
5/16"x4-1/2 SS LAG
BOLT @4' O.C. MAX.
W/ 3" EMBEDMENT
OVER EXISTING
SHT'G.
PV MODULES
16°
2x6 RAFTERS @
16" ON CENTER
PV MODULES
COMP. SHINGLE ROOF
COMP. SHINGLE
ZEP SOLAR
COMP MOUNT
ZEPSOLAR
INTERLOCK PLATE
SYSTEM WIGHT
MODULE WIGHT 41.8 lbs
MODULE AREA 18.02 sq/ft
#OF MODULES 11
TOTAL WIGHT 459.8lbs
TOTAL AREA 198.2 sq/ft
LOADING / sqft 2.31 lbs
LOADING (PSF) 27.04 lbs
OWNER / ADDRESS
*
*
Lynwood CA 90262
PHONE:*
OCCUPANCY R3 /
TYPE 5 STRU.
APN#: *
CONTRACTOR
Home Owner Builder
*
Lynwood CA 90262
PHONE:*
STATE TYPE : -
STATE LICENSE# : -
EXPIRATION DATE : -
DATE: 01/10/18
REVISION :
© C
op
yrig
ht 2017-S
olar P
V P
erm
it
SYSTEM SIZE
2.990 KW-AC
3.190 KW-DC
REVISION :
PAGE INFORMATION
STAMP/ SIGNATURE :
MODULES :
(11) SILEVO TRIEX U290
DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General
Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.
INVERTER(S) :
(1) ABB PVI-3.0-OUTD-US
TITLE:
RAFTER SIDE VIEW
ATTACHMENT DETAIL
PV-03
G
N
L2
L1
M
L2
L1
G
N
M
(N)INVERTER - ABB PVI- 3.0 -OUTD -US
96% CEC EFFICIENCY
3000 Wac CONTINUOUS
MAX OUTPUT CURRENT 14.5Aac
MAX INPUT CURRENT 12.5Adc
ACD
(N)30A AC DISCONNECT
SQUARE-D 2POLE- BLADE TYPE
240V NON-FUSIBLE,NEMA 3R
(N)PRODUCTION METER
(E)GROUNDING
ELECTRODE SYSTEM
L1N L2
(E) BI-DIRECTIONAL
UTILITY METER
1-PHASE, 240 V
TO UTILITY GRID
120/240V
SINGLE PHASE
(E)200A 120/240V
MAIN SERVICE PANEL
(E)200A MCB
200A
(N)20 A, 240 V, 2-P
PV BREAKER
INSTALLED PER
NEC 705.12(D)(7)
- + - + - +
- + - + - +
STRING 1 :
(6)SILEVO TRIEX U290
Voc =68.9V, Vmp = 56.2V
Isc = 5.59A, Imp = 5.19A
RSD
G
1
1
2
INVERTER
ABB PVI-
3.0-OUTD-US
3 3 3
STRING 2 :
(5)SILEVO TRIEX U290
Voc =68.9V, Vmp = 56.2V
Isc = 5.59A, Imp = 5.19A
(N)ABB RAPID SHUTDOWN
UL LISTED, NEMA 4X
MOUNTED ON ROOF
BUS RATING CALCULATION PER 705.12(D)(7)
MAIN PANEL BUS = 200A
MAIN BREAKER = 200A
MAIN BUS X 120% =240A - MAIN BREAKER =
40A AVAILABLE FOR SOLAR
SOLAR BREAKER = 20A OK
NOTES:
-SOLID BARE E.G.C. (FREE-AIR) MOUNTED UNDER ARRAY
-PER NEC 250.120(C): WHERE CONDUCTORS & GROUND WIRE ARE RUN EXPOSED ON ROOF FROM ARRAY TO J-BOX,
CONDUCTORS & BARE GROUND WIRE SHALL BE CONCEALED INSTALL IN CONDUIT
-PER NEC ARTICLE 690.35 INVERTER GROUND FAULT PROTECTION PROVIDED
-ALL GROUNDS AND NEUTRALS BONDED TO EXISTING GROUNDING CONDUCTOR W/ IRREVERSIBLE CRIP CONNECTOR.
-BACKFED BREAKERS MUST BE LOCATED @ OPPOSITE END OF BUS BAR FROM MAIN BREAKER OR MAIN LUG ON GRID SIDE.
WHEN A BACKFED BREAKER IS THE METHOD OF UNTILITY INTERCONNECTION, BREAKER SHALL NOT READ 'LINE OR LOAD'.
-PER CEC 250.64(C): CONDUCTOR SPLICES ONLY ALLOWED WITH COMPRESSION CONNECTORS OR EXOTHERMIC WELDING
-ALL GROUNDS AND NEUTRALS BONDED TO EXISTING GROUNDING CONDUCTOR W/ IRREVERSIBLE CRIP CONNECTOR.
-VERIFY (E) UFER GROUND NEAR MSP. IF (E) UFER IS NOT ACCESSIBLE OR VERIFIABLE, INSTALL A NEW 5/8"Ø X 8' LONG
GROUNDING ROD AND BOND SOLAR SYSTEM EQUIPMENT GROUNDING ACCORDINGLY.
-PRODUCTION METER ADJACENT TO MAIN ELECTRICAL PANEL 10" TO 72" CENTER TO CENTER OF METERS 48" TO 75" ABOVE GRADE LEVEL
OWNER / ADDRESS
*
*
Lynwood CA 90262
PHONE:*
OCCUPANCY R3 /
TYPE 5 STRU.
APN#: *
CONTRACTOR
Home Owner Builder
*
Lynwood CA 90262
PHONE:*
STATE TYPE : -
STATE LICENSE# : -
EXPIRATION DATE : -
DATE: 01/10/18
REVISION :
© C
op
yrig
ht 2017-S
olar P
V P
erm
it
SYSTEM SIZE
2.990 KW-AC
3.190 KW-DC
REVISION :
PAGE INFORMATION
STAMP/ SIGNATURE :
MODULES :
(11) SILEVO TRIEX U290
DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General
Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.
INVERTER(S) :
(1) ABB PVI-3.0-OUTD-US
TITLE:
ELECTRICAL DIAGRAM
PV-04
WIRE
TAG#
MAX AMPS X
NEC MULT=
DESIGN AMPS
BREAKER
SIZE AMPS
WIRE TYPE EGC / GRND.SIZE
WIRE RATING IN 90° X
TEMP DERATE X CONDUCTOR
DERATE = DERATE WIRE
TERMINAL
60°C
RATING
CONDUIT SIZE CONDUIT FILL
1 5.59 x 1.5625 =8.7A 20A
(2)
#10PV WIRE
(1)#6 THWN-2
COPPER EGC
40 x 0.65 x 1.0 =26.0 >=8.7 30> =8.7 OPEN AIR
2 5.59 x 1.5625 =8.7A 20A
(4)
#10THWN-2
(1)#8 THWN-2 EGC
40 x 0.65 x 0.8 =20.8 >=8.7 30> =8.7 3/4" EMT FILL: 0.1210, 23%
3 14.5 x 1.25 x =18.1A 20A
(3)
#10THWN-2
(1)#8 THWN-2 EGC
40 x 0.65 x 0.8 =20.8 >=18.1 30> =18.1 3/4" EMT FILL: 0.0999, 19%
TITLE:
WARNING LABELS
PLACARD
PV-05
PLAQUE SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITH
POP-RIVETS OR SCREWS.
POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THEFOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN
WARNINGMIN.6"x6" PLACARD TO GO ON MAIN SERVICE PANEL
AC DISCONNECT
MSP
OWNER / ADDRESS
*
*
Lynwood CA 90262
PHONE:*
OCCUPANCY R3 /
TYPE 5 STRU.
APN#: *
CONTRACTOR
Home Owner Builder
*
Lynwood CA 90262
PHONE:*
STATE TYPE : -
STATE LICENSE# : -
EXPIRATION DATE : -
DATE: 01/10/18
REVISION :
© C
op
yrig
ht 2017-S
olar P
V P
erm
it
SYSTEM SIZE
2.990 KW-AC
3.190 KW-DC
REVISION :
PAGE INFORMATION
STAMP/ SIGNATURE :
MODULES :
(11) SILEVO TRIEX U290
DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General
Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.
INVERTER(S) :
(1) ABB PVI-3.0-OUTD-US
PHOTOVOLTAIC AC DISCONNECT
MAX OPERATION CURRENT 14.5 AMPS
MAX. OPERATION VOLTAGE 240 VOLTS
CAUTION
SOLAR ELECTRIC SYSTEM CONNECTED
CAUTION: AC SOLAR VOLTAGE
WARNING
POWER TO THIS BUILDING IS
ALSO SUPPLIED BY THE
PHOTOVOLTAIC SOLAR SYSTEM
DO NOT TOUCH TERMINALS
WARNING
INVERTER OUTPUT
CONNECTIONS(S),
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
WARNING
ELECTRICAL SHOCK HAZZARD
THE DC CONDUCTORS OF THIS
PHOTOVOLTAIC SYSTEM ARE
UNGROUNDED AND MAYBE ENERGIZED
N
WARNING
PHOTOVOLTAIC POWER SOURCE
PLACED ON INTERIOR AND EXTERIOR AC CONDUIT,
RACEWAYS, ENCLOSURES, CABLE ASSEMBLIES, JUNCTION
BOXES, AND DISCONNECTS. MARKING SHALL BE PLACED ON
INTERIOR AND EXTERIOR AC CONDUIT, RACEWAYS,
ENCLOSURES AND CABLE ASSEMBLIES EVERY 10 FEET
(3048MM), WITHIN 1 FOOT OF TURNS OR BENDS AND WITHIN
1 FOOT ABOVE AND BELOW PENETRATIONS OF
ROOF/CEILING ASSEMBLIES, WALLS OR BARRIERS.
CFC 604.11.1& CRC R331.2
CAUTION: SOLAR CUICUIT
PLACED ON ALL AC CONDUITS RACEWAY EVERY 10 FEET
PLACE ON MAIN PANEL
PLACE ON MAIN ELECTRICAL PANEL 690.54
PLACE ON AC DISCONNECT
NEAR GROUND-FAULT INDICATORSTRING INVERTERS
ONLY (Art. 690.5 (C) CEC)
PLACE ON MAIN PANEL & SUB PANELPLACE ON MAIN PANEL
PERMANENT SIGNAGE NOTES:
1. NOT ALL PLACARDS SHOWN MAY BE REQUIRED BY LOCAL AHJ. CONTRACTOR TO VERIFY PLACARD
REQUIREMENTS WITH LOCAL AHJ BEFORE INSTALLATION.
2. ALL PLAQUES AND SIGNAGE REQUIRED BY THE LATEST EDITION OF THE CALIFORNIA ELECTRICAL CODE
AND THE SAN DIEGO AREA ELECTRICAL NEWSLETTER WILL BE INSTALLED AS REQUIRED.
3. ALTERNATE POWER SOURCE PLACARD SHALL BE METALLIC OR PLASTIC, ENGRAVED OR MACHINE
PRINTED LETTERS IN A CONTRASTING COLOR TO THE PLAQUE. THIS PLAQUE WILL BE ATTCHED BY POP
RIVETS OR SCREWS OR OTHER APPROVED METHOD.
4. DIRECTORY PLACARD MARKING CONTENT AND FORMAT: RED BACKGROUND, WHITE LETTERING,
MINIMUM 3/8" LETTER HIEGHT, ALL CAPITAL LETTERS, ARIAL OR SIMILAR FONT, NON BOLD, REFLECTIVE
WEATHER RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT.
541
6 CL
ARK
ST
.
"WARNING"
DUAL POWER SOURCES
SECOND SOURCE IS PHOTO-VOLTAIC SYSTEM
RATED AC OUTPUT CURRENT - 14.5 AMPS
AC NORMAL OPERATING VOLTAGE - 240 VOLTS
INVERTER 1 - 690.14(C0(2), 690.15, 690.53
PV SYSTEM DC DISCONNECT
RATED MAX POWER-POINT CURRENT 10.38 A
RATED MAX POWER-POINT VOLTAGE 384 V
MAXIMUM SYSTEM VOLTAGE 312 V
SHORT CIRCUIT CURRENT 8.94A
PV MODULES
OWNER / ADDRESS
*
*
Lynwood CA 90262
PHONE:*
OCCUPANCY R3 /
TYPE 5 STRU.
APN#: *
CONTRACTOR
Home Owner Builder
*
Lynwood CA 90262
PHONE:*
STATE TYPE : -
STATE LICENSE# : -
EXPIRATION DATE : -
DATE: 01/10/18
REVISION :
© C
op
yrig
ht 2017-S
olar P
V P
erm
it
SYSTEM SIZE
2.990 KW-AC
3.190 KW-DC
REVISION :
PAGE INFORMATION
STAMP/ SIGNATURE :
MODULES :
(11) SILEVO TRIEX U290
DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General
Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.
INVERTER(S) :
(1) ABB PVI-3.0-OUTD-US
TITLE:
SPECS
PV-06
OWNER / ADDRESS
*
*
Lynwood CA 90262
PHONE:*
OCCUPANCY R3 /
TYPE 5 STRU.
APN#: *
CONTRACTOR
Home Owner Builder
*
Lynwood CA 90262
PHONE:*
STATE TYPE : -
STATE LICENSE# : -
EXPIRATION DATE : -
DATE: 01/10/18
REVISION :
© C
op
yrig
ht 2017-S
olar P
V P
erm
it
SYSTEM SIZE
2.990 KW-AC
3.190 KW-DC
REVISION :
PAGE INFORMATION
STAMP/ SIGNATURE :
MODULES :
(11) SILEVO TRIEX U290
DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General
Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.
INVERTER(S) :
(1) ABB PVI-3.0-OUTD-US
TITLE:
SPECS
PV-07
OWNER / ADDRESS
*
*
Lynwood CA 90262
PHONE:*
OCCUPANCY R3 /
TYPE 5 STRU.
APN#: *
CONTRACTOR
Home Owner Builder
*
Lynwood CA 90262
PHONE:*
STATE TYPE : -
STATE LICENSE# : -
EXPIRATION DATE : -
DATE: 01/10/18
REVISION :
© C
op
yrig
ht 2017-S
olar P
V P
erm
it
SYSTEM SIZE
2.990 KW-AC
3.190 KW-DC
REVISION :
PAGE INFORMATION
STAMP/ SIGNATURE :
MODULES :
(11) SILEVO TRIEX U290
DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General
Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.
INVERTER(S) :
(1) ABB PVI-3.0-OUTD-US
PV-08
TITLE:
SPECS
OWNER / ADDRESS
*
*
Lynwood CA 90262
PHONE:*
OCCUPANCY R3 /
TYPE 5 STRU.
APN#: *
CONTRACTOR
Home Owner Builder
*
Lynwood CA 90262
PHONE:*
STATE TYPE : -
STATE LICENSE# : -
EXPIRATION DATE : -
DATE: 01/10/18
REVISION :
© C
op
yrig
ht 2017-S
olar P
V P
erm
it
SYSTEM SIZE
2.990 KW-AC
3.190 KW-DC
REVISION :
PAGE INFORMATION
STAMP/ SIGNATURE :
MODULES :
(11) SILEVO TRIEX U290
DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General
Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.
INVERTER(S) :
(1) ABB PVI-3.0-OUTD-US
PV-09
TITLE:
SPECS
OWNER / ADDRESS
*
*
Lynwood CA 90262
PHONE:*
OCCUPANCY R3 /
TYPE 5 STRU.
APN#: *
CONTRACTOR
Home Owner Builder
*
Lynwood CA 90262
PHONE:*
STATE TYPE : -
STATE LICENSE# : -
EXPIRATION DATE : -
DATE: 01/10/18
REVISION :
© C
op
yrig
ht 2017-S
olar P
V P
erm
it
SYSTEM SIZE
2.990 KW-AC
3.190 KW-DC
REVISION :
PAGE INFORMATION
STAMP/ SIGNATURE :
MODULES :
(11) SILEVO TRIEX U290
DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General
Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.
INVERTER(S) :
(1) ABB PVI-3.0-OUTD-US
PV-10
TITLE:
SPECS
OWNER / ADDRESS
*
*
Lynwood CA 90262
PHONE:*
OCCUPANCY R3 /
TYPE 5 STRU.
APN#: *
CONTRACTOR
Home Owner Builder
*
Lynwood CA 90262
PHONE:*
STATE TYPE : -
STATE LICENSE# : -
EXPIRATION DATE : -
DATE: 01/10/18
REVISION :
© C
op
yrig
ht 2017-S
olar P
V P
erm
it
SYSTEM SIZE
2.990 KW-AC
3.190 KW-DC
REVISION :
PAGE INFORMATION
STAMP/ SIGNATURE :
MODULES :
(11) SILEVO TRIEX U290
DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General
Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.
INVERTER(S) :
(1) ABB PVI-3.0-OUTD-US
PV-11
TITLE:
SPECS
OWNER / ADDRESS
*
*
Lynwood CA 90262
PHONE:*
OCCUPANCY R3 /
TYPE 5 STRU.
APN#: *
CONTRACTOR
Home Owner Builder
*
Lynwood CA 90262
PHONE:*
STATE TYPE : -
STATE LICENSE# : -
EXPIRATION DATE : -
DATE: 01/10/18
REVISION :
© C
op
yrig
ht 2017-S
olar P
V P
erm
it
SYSTEM SIZE
2.990 KW-AC
3.190 KW-DC
REVISION :
PAGE INFORMATION
STAMP/ SIGNATURE :
MODULES :
(11) SILEVO TRIEX U290
DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General
Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.
INVERTER(S) :
(1) ABB PVI-3.0-OUTD-US
PV-12
TITLE:
SPECS