SCOPE OF WORK SYSTEM SIZE: 2.990KW-AC 3.190KW-DC ROOF MOUNT PV SOLAR ROOF TYPE:Comp. Shingle 2 X 6 @ 16" O.C. Rafters ARRAY/ROOF PITCH: 16° AZIMUTH: 100°,280° TWO STORY HOUSE MODULES : (11) SILEVO TRIEX U290 INVERTER(S) : (1) ABB PVI-3.0-OUTD -US PV RAIL: ZEP SOLAR PV MOUNT: ZEP SOLAR 4.5” LAG SCREWS 1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE LATEST CALIFORNIA CODE OF REGULATIONS (CCR),NATIONAL ELECTRICAL CODE EDITION AND ALL APPLICABLE LOCAL CODES AND REGULATIONS. (CONSTRUCTION SHALL COMPLY WITH 2016 CBC, CMC, CPC, CEC, CRC,CFC) 2. ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS IN COMPLIANCE TO UL REQUIREMENTS TO ACCOMMODATE CONDUCTORS SHOWN 3.WHERE WIRE SIZES ARE INDICATED ON PLANS FOR INDIVIDUAL CIRCUITS, THE WIRE SIZE INDICATED SHALL APPLY TO THE COMPLETE CIRCUIT, UNLESS OTHERWISE NOTED. 4.CONTRACTOR SHALL EXTEND WIRING FROM ALL JUNCTION BOXES, SWITCHES, ETC. AND MAKE FINAL CONNECTIONS AS REQUIRED TO ALL BUILDING EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS. 5.DRAWINGS AND DIAGRAMMIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED. FOLLOW DRAWING AND LAYOUT WORK AND CHECK DRAWINGS OR OTHER TRADES RELATING TO WORK TO VERIFY SPACE IN WHICH WORK WILL BE INSTALLED. MAINTAIN HEADROOM AND MINIMUM CODE REQUIRED WORKING CLEARANCES AT ALL TIMES. 6.ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT INCLUDING THOSE THAT ARE EXPOSED TO OUTSIDE ENVIRONMENT SHALL BE WEATHERPROOF TYPE NEMA 3R. 7.DISCONNECT SWITCHES SHALL BE MOUNTED ON INDIVIDUAL SUPPORTS, OR OTHERWISE DIRECTLY ON EQUIPMENT, PROVIDED NO MODIFICATION TO EQUIPMENT IS NECESSARY. 8.ALL ELECTRICAL MATERIAL SHALL BE LISTED BY "UL" FOR THE TYPE OF APPLICATION AND "UL" LABEL SHALL APPEAR ON ALL ELECTRICAL EQUIPMENT. 9.WIRING METHOD SHALL BE EMT ABOVE GROUND MOUNTED IN CONCEALED SPACES (UNLESS APPROVED OTHERWISE) AND SCHEDULE- 40 PVC FOR BELOW GROUND INSTALLATION UNLESS NOTED OTHERWISE. 10.AN OSHA APPROVED LADDER PROVIDING ACCESS TO ALL PORTIONS OF THE ARRAY SHALL BE SECURED IN PRIOR TO REQUESTING INSPECTION. 11.SMOKE ALARMS AND CARBON MONOXIDE DETECTORS WILL MEET THE NECESSARY REQUIREMENTS PER CRC R314, R315 12.UTILITY COMPANY WILL BE NOTIFIED PRIOR TO ACTIVATION OF THE SOLAR PV SYSTEM. 13.ALL EXTERIOR CONDUIT PAINTED TO MATCH EXTERIOR SURFACE. (IF APPLICABLE) 14. NO PLUMBING, MECHANICAL OR BLDG VENTS TO BE COVERED OR OFFSET AROUND ARRAYS 15.EXISTING PLUMBING VENTS, SKYLIGHTS, EXHAUST OUTLETS, VENTILATION'S INTAKE AIR OPENINGS SHALL NOT BE COVERED BY THE SOLAR PHOTOVOLTAIC SYSTEM. 16.ALL EQUIPMENT SHALL BE LISTED AND LABELED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY AND INSTALLED PER THE LISTING REQUIREMENTS AND THE MANUFACTURER'S INSTRUCTIONS. [NEC 690.4(D)] 17.ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED, INCLUDING ALL ROOF MOUNTED TRANSITION BOXES AND SWITCHES. 18.PAINT PV CONDUIT TO MATCH THE DWELLING EXTERIOR. 19.CONTACT THE SERVICING UTILITY BEFORE POWERING ON THE PHOTOVOLTAIC SYSTEM. 1. COVER PAGE 2. PLOT PLAN/ROOF PLAN 3. RAFTER SIDE VIEW 4. ELECTRICAL DIAGRAM 5. WARNING LABELS 6. SPECS 7. SPECS 8. SPECS 9. SPECS 10. SPECS 11. SPECS 12. SPECS VICINITY MAP INDEX SHEET SUNROOF VIEW AERIAL VIEW GOVERNING CODES GENERAL NOTES PROJECT DESCRIPTION THIS ROOF-MOUNTED PHOTOVOLTAIC (PV) SYSTEM IS TO BE INSTALLED AT THE SINGLE FAMILY RESIDENTIAL IN LYNWOOD, CALIFORNIA. THE ENERGY PRODUCED BY THE PV SYSTEM SHALL BE INTERCONNECTED WITH THE UTILITY GRID THROUGH THE EXISTING ON-SITE ELECTRICAL EQUIPMENT VIA A BACK-FED BREAKER IN THE MAIN SERVICE PANEL. OWNER / ADDRESS * * Lynwood CA 90262 PHONE:* OCCUPANCY R3 / TYPE 5 STRU. APN#: * CONTRACTOR Home Owner Builder * Lynwood CA 90262 PHONE:* STATE TYPE : - STATE LICENSE# : - EXPIRATION DATE : - DATE: 01/10/18 REVISION : Copyright 2017-Solar PV Permit SYSTEM SIZE 2.990 KW-AC 3.190 KW-DC REVISION : PAGE INFORMATION STAMP/ SIGNATURE : MODULES : (11) SILEVO TRIEX U290 DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them. INVERTER(S) : (1) ABB PVI-3.0-OUTD-US TITLE: COVER PAGE PV-01 www.solarpvpermit.com [email protected] Prepared by: N ALL MODULES AND RAIL ARE LISTED BY UNDERWRITER'S LABORATORIES FOR ELECTRICAL AND FIRE SAFETY(CLASS A FIRE RATING) NOTE: 1) NO DISCHARGE OF ANY POLLUTANTS TO ANY STORM DRAIN SYSTEM. 2) UL 1703 FOR MODULES & UL 1741 FOR INVERTERS PER CITY SOLAR REQUIREMENTS. THIS PROJECT SHALL COMPLY WITH THE : 2016 CA BUILDING CODE 1507.17, 1509.7, 3111 2016 CA PLUMBING CODE 2016 CA RESIDENTIAL CODE R331, R908 2016 CA ENERGY CODE 2016 CA MECHANICAL CODE 2016 CA FIRE CODE 605.11 2016 CA ELECTRICAL CODE - 2014 NEC -110, 240, 250, 690, 705 ORDINANCES OF THE CITY OF LYNWOOD

Transcript of NSAMPLE - Solar PV Permitsolarpvpermit.com/Sample/SPVPSample.pdf · if a discrepancy in quantity or...

Page 1: NSAMPLE - Solar PV Permitsolarpvpermit.com/Sample/SPVPSample.pdf · if a discrepancy in quantity or size of conduit, wire, ... single family residential in rancho santa margarita,

SCOPE OF WORK

SYSTEM SIZE:

2.990KW-AC

3.190KW-DC

ROOF MOUNT PV SOLAR

ROOF TYPE:Comp. Shingle

2 X 6 @ 16" O.C. Rafters

ARRAY/ROOF PITCH: 16°

AZIMUTH: 100°,280°

TWO STORY HOUSE

MODULES :

(11) SILEVO TRIEX U290

INVERTER(S) :

(1) ABB PVI-3.0-OUTD -US

PV RAIL:

ZEP SOLAR

PV MOUNT:

ZEP SOLAR

4.5” LAG SCREWS

1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE LATEST CALIFORNIA CODE OF

REGULATIONS (CCR),NATIONAL ELECTRICAL CODE EDITION AND ALL APPLICABLE LOCAL CODES

AND REGULATIONS. (CONSTRUCTION SHALL COMPLY WITH 2016 CBC, CMC, CPC, CEC, CRC,CFC)

2. ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS IN

COMPLIANCE TO UL REQUIREMENTS TO ACCOMMODATE CONDUCTORS SHOWN

3.WHERE WIRE SIZES ARE INDICATED ON PLANS FOR INDIVIDUAL CIRCUITS, THE WIRE SIZE

INDICATED SHALL APPLY TO THE COMPLETE CIRCUIT, UNLESS OTHERWISE NOTED.

4.CONTRACTOR SHALL EXTEND WIRING FROM ALL JUNCTION BOXES, SWITCHES, ETC. AND

MAKE FINAL CONNECTIONS AS REQUIRED TO ALL BUILDING EQUIPMENT REQUIRING

ELECTRICAL CONNECTIONS.

5.DRAWINGS AND DIAGRAMMIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND

WORK INCLUDED. FOLLOW DRAWING AND LAYOUT WORK AND CHECK DRAWINGS OR OTHER

TRADES RELATING TO WORK TO VERIFY SPACE IN WHICH WORK WILL BE INSTALLED. MAINTAIN

HEADROOM AND MINIMUM CODE REQUIRED WORKING CLEARANCES AT ALL TIMES.

6.ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT INCLUDING THOSE THAT ARE EXPOSED

TO OUTSIDE ENVIRONMENT SHALL BE WEATHERPROOF TYPE NEMA 3R.

7.DISCONNECT SWITCHES SHALL BE MOUNTED ON INDIVIDUAL SUPPORTS, OR OTHERWISE

DIRECTLY ON EQUIPMENT, PROVIDED NO MODIFICATION TO EQUIPMENT IS NECESSARY.

8.ALL ELECTRICAL MATERIAL SHALL BE LISTED BY "UL" FOR THE TYPE OF APPLICATION AND "UL"

LABEL SHALL APPEAR ON ALL ELECTRICAL EQUIPMENT.

9.WIRING METHOD SHALL BE EMT ABOVE GROUND MOUNTED IN CONCEALED SPACES (UNLESS

APPROVED OTHERWISE) AND SCHEDULE- 40 PVC FOR BELOW GROUND INSTALLATION UNLESS

NOTED OTHERWISE.

10.AN OSHA APPROVED LADDER PROVIDING ACCESS TO ALL PORTIONS OF THE ARRAY SHALL

BE SECURED IN PRIOR TO REQUESTING INSPECTION.

11.SMOKE ALARMS AND CARBON MONOXIDE DETECTORS WILL MEET THE NECESSARY

REQUIREMENTS PER CRC R314, R315

12.UTILITY COMPANY WILL BE NOTIFIED PRIOR TO ACTIVATION OF THE SOLAR PV SYSTEM.

13.ALL EXTERIOR CONDUIT PAINTED TO MATCH EXTERIOR SURFACE. (IF APPLICABLE)

14. NO PLUMBING, MECHANICAL OR BLDG VENTS TO BE COVERED OR OFFSET AROUND ARRAYS

15.EXISTING PLUMBING VENTS, SKYLIGHTS, EXHAUST OUTLETS, VENTILATION'S INTAKE AIR

OPENINGS SHALL NOT BE COVERED BY THE SOLAR PHOTOVOLTAIC SYSTEM.

16.ALL EQUIPMENT SHALL BE LISTED AND LABELED BY A RECOGNIZED ELECTRICAL TESTING

LABORATORY AND INSTALLED PER THE LISTING REQUIREMENTS AND THE MANUFACTURER'S

INSTRUCTIONS. [NEC 690.4(D)]

17.ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED, INCLUDING ALL ROOF MOUNTED

TRANSITION BOXES AND SWITCHES.

18.PAINT PV CONDUIT TO MATCH THE DWELLING EXTERIOR.

19.CONTACT THE SERVICING UTILITY BEFORE POWERING ON THE PHOTOVOLTAIC SYSTEM.

1. COVER PAGE2. PLOT PLAN/ROOF PLAN3. RAFTER SIDE VIEW4. ELECTRICAL DIAGRAM5. WARNING LABELS6. SPECS7. SPECS8. SPECS9. SPECS10. SPECS11. SPECS12. SPECS

VICINITY MAP

INDEX SHEET

SUNROOF VIEW AERIAL VIEW

GOVERNING CODES

GENERAL NOTES

PROJECT DESCRIPTION

THIS ROOF-MOUNTED PHOTOVOLTAIC (PV) SYSTEM IS TO BE INSTALLED AT THE

SINGLE FAMILY RESIDENTIAL IN LYNWOOD, CALIFORNIA.

THE ENERGY PRODUCED BY THE PV SYSTEM SHALL BE INTERCONNECTED WITH THE

UTILITY GRID THROUGH THE EXISTING ON-SITE ELECTRICAL EQUIPMENT VIA A

BACK-FED BREAKER IN THE MAIN SERVICE PANEL.

OWNER / ADDRESS

*

*

Lynwood CA 90262

PHONE:*

OCCUPANCY R3 /

TYPE 5 STRU.

APN#: *

CONTRACTOR

Home Owner Builder

*

Lynwood CA 90262

PHONE:*

STATE TYPE : -

STATE LICENSE# : -

EXPIRATION DATE : -

DATE: 01/10/18

REVISION :

© C

op

yrig

ht 2017-S

olar P

V P

erm

it

SYSTEM SIZE

2.990 KW-AC

3.190 KW-DC

REVISION :

PAGE INFORMATION

STAMP/ SIGNATURE :

MODULES :

(11) SILEVO TRIEX U290

DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General

Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.

INVERTER(S) :

(1) ABB PVI-3.0-OUTD-US

TITLE:

COVER PAGE

PV-01

www.solarpvpermit.com

[email protected]

Prepared by:

N

ALL MODULES AND RAIL ARE LISTED BY UNDERWRITER'S LABORATORIES

FOR ELECTRICAL AND FIRE SAFETY(CLASS A FIRE RATING)

NOTE:

1) NO DISCHARGE OF ANY POLLUTANTS TO ANY STORM DRAIN SYSTEM.

2) UL 1703 FOR MODULES & UL 1741 FOR INVERTERS PER CITY SOLAR

REQUIREMENTS.

THIS PROJECT SHALL COMPLY WITH THE :

2016 CA BUILDING CODE 1507.17, 1509.7, 3111

2016 CA PLUMBING CODE

2016 CA RESIDENTIAL CODE R331, R908

2016 CA ENERGY CODE

2016 CA MECHANICAL CODE

2016 CA FIRE CODE 605.11

2016 CA ELECTRICAL CODE - 2014 NEC -110, 240, 250, 690, 705

ORDINANCES OF THE CITY OF LYNWOOD

Page 2: NSAMPLE - Solar PV Permitsolarpvpermit.com/Sample/SPVPSample.pdf · if a discrepancy in quantity or size of conduit, wire, ... single family residential in rancho santa margarita,

P

/L

4

7

'-6

"

P

/L

4

7

'-6

"

P

/L

1

3

8

'

P

/L

1

3

8

'DR

IVEW

AY

(E)GARAGE

5416 CLARK ST .

ROOF ACCESS POINT

SITE PLAN : SCALE: 1/16"=1'-0N

9

6

'-1

0

"

6

'-3

"

1

9

'-8

"

VENT / ROOF

OBSTRUCTION (TYP)

ARRAY 1:

QTY:6

TILT:16°

AZIMUTH: 100°

ARRAY 2:

QTY:5

TILT:16°

AZIMUTH: 280°

AC DISCONNECT

PRODUCTION METER

MAIN SERVICE PANEL

INVERTER

ROOF ACCESS POINT

2

5

'-6

"

DRIV

EWAY

ARRAY 1:

QTY:6

TILT:16°

AZIMUTH: 100°

ROOF ACCESS POINT

N

3'-0" FIRE SETBACK

RAPID SHUTDOWN

EMT CONDUIT RUN ON

ROOF OR IN ATTIC

VENT / ROOF

OBSTRUCTION (TYP)

ARRAY 2:

QTY:5

TILT:16°

AZIMUTH: 280°

ROOF PLAN : SCALE: 3/32"=1'-0

ROOF ACCESS POINT

AC DISCONNECT

PRODUCTION METER

MAIN SERVICE PANEL

INVERTER

(E)GARAGE

OWNER / ADDRESS

*

*

Lynwood CA 90262

PHONE:*

OCCUPANCY R3 /

TYPE 5 STRU.

APN#: *

CONTRACTOR

Home Owner Builder

*

Lynwood CA 90262

PHONE:*

STATE TYPE : -

STATE LICENSE# : -

EXPIRATION DATE : -

DATE: 01/10/18

REVISION :

© C

op

yrig

ht 2017-S

olar P

V P

erm

it

SYSTEM SIZE

2.990 KW-AC

3.190 KW-DC

REVISION :

PAGE INFORMATION

STAMP/ SIGNATURE :

MODULES :

(11) SILEVO TRIEX U290

DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General

Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.

INVERTER(S) :

(1) ABB PVI-3.0-OUTD-US

TITLE:

SITE PLAN / ROOF PLAN

PV-02

Page 3: NSAMPLE - Solar PV Permitsolarpvpermit.com/Sample/SPVPSample.pdf · if a discrepancy in quantity or size of conduit, wire, ... single family residential in rancho santa margarita,

2x6 RAFTERS @ 16" O.C.

(TYP)

ARRAY 1:

QTY:6

TILT:16°

AZIMUTH: 100°

4'-0"

Max.

ZEP SOLAR

COMP MOUNT

3'-0" 15'-7" 8'-6"

4'-9"

6'-11"

VENT / ROOF

OBSTRUCTION (TYP)

3'-0"

3'-0"

8'-8"

15'-7"

1'-5"

ARRAY 2:

QTY:5

TILT:16°

AZIMUTH: 280°

SCALE: 3/16"=1'-0

2x6 RAFTERS @

16" ON CENTER

5/16"x4-1/2 SS LAG

BOLT @4' O.C. MAX.

W/ 3" EMBEDMENT

OVER EXISTING

SHT'G.

PV MODULES

16°

2x6 RAFTERS @

16" ON CENTER

PV MODULES

COMP. SHINGLE ROOF

COMP. SHINGLE

ZEP SOLAR

COMP MOUNT

ZEPSOLAR

INTERLOCK PLATE

SYSTEM WIGHT

MODULE WIGHT 41.8 lbs

MODULE AREA 18.02 sq/ft

#OF MODULES 11

TOTAL WIGHT 459.8lbs

TOTAL AREA 198.2 sq/ft

LOADING / sqft 2.31 lbs

LOADING (PSF) 27.04 lbs

OWNER / ADDRESS

*

*

Lynwood CA 90262

PHONE:*

OCCUPANCY R3 /

TYPE 5 STRU.

APN#: *

CONTRACTOR

Home Owner Builder

*

Lynwood CA 90262

PHONE:*

STATE TYPE : -

STATE LICENSE# : -

EXPIRATION DATE : -

DATE: 01/10/18

REVISION :

© C

op

yrig

ht 2017-S

olar P

V P

erm

it

SYSTEM SIZE

2.990 KW-AC

3.190 KW-DC

REVISION :

PAGE INFORMATION

STAMP/ SIGNATURE :

MODULES :

(11) SILEVO TRIEX U290

DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General

Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.

INVERTER(S) :

(1) ABB PVI-3.0-OUTD-US

TITLE:

RAFTER SIDE VIEW

ATTACHMENT DETAIL

PV-03

Page 4: NSAMPLE - Solar PV Permitsolarpvpermit.com/Sample/SPVPSample.pdf · if a discrepancy in quantity or size of conduit, wire, ... single family residential in rancho santa margarita,

G

N

L2

L1

M

L2

L1

G

N

M

(N)INVERTER - ABB PVI- 3.0 -OUTD -US

96% CEC EFFICIENCY

3000 Wac CONTINUOUS

MAX OUTPUT CURRENT 14.5Aac

MAX INPUT CURRENT 12.5Adc

ACD

(N)30A AC DISCONNECT

SQUARE-D 2POLE- BLADE TYPE

240V NON-FUSIBLE,NEMA 3R

(N)PRODUCTION METER

(E)GROUNDING

ELECTRODE SYSTEM

L1N L2

(E) BI-DIRECTIONAL

UTILITY METER

1-PHASE, 240 V

TO UTILITY GRID

120/240V

SINGLE PHASE

(E)200A 120/240V

MAIN SERVICE PANEL

(E)200A MCB

200A

(N)20 A, 240 V, 2-P

PV BREAKER

INSTALLED PER

NEC 705.12(D)(7)

- + - + - +

- + - + - +

STRING 1 :

(6)SILEVO TRIEX U290

Voc =68.9V, Vmp = 56.2V

Isc = 5.59A, Imp = 5.19A

RSD

G

1

1

2

INVERTER

ABB PVI-

3.0-OUTD-US

3 3 3

STRING 2 :

(5)SILEVO TRIEX U290

Voc =68.9V, Vmp = 56.2V

Isc = 5.59A, Imp = 5.19A

(N)ABB RAPID SHUTDOWN

UL LISTED, NEMA 4X

MOUNTED ON ROOF

BUS RATING CALCULATION PER 705.12(D)(7)

MAIN PANEL BUS = 200A

MAIN BREAKER = 200A

MAIN BUS X 120% =240A - MAIN BREAKER =

40A AVAILABLE FOR SOLAR

SOLAR BREAKER = 20A OK

NOTES:

-SOLID BARE E.G.C. (FREE-AIR) MOUNTED UNDER ARRAY

-PER NEC 250.120(C): WHERE CONDUCTORS & GROUND WIRE ARE RUN EXPOSED ON ROOF FROM ARRAY TO J-BOX,

CONDUCTORS & BARE GROUND WIRE SHALL BE CONCEALED INSTALL IN CONDUIT

-PER NEC ARTICLE 690.35 INVERTER GROUND FAULT PROTECTION PROVIDED

-ALL GROUNDS AND NEUTRALS BONDED TO EXISTING GROUNDING CONDUCTOR W/ IRREVERSIBLE CRIP CONNECTOR.

-BACKFED BREAKERS MUST BE LOCATED @ OPPOSITE END OF BUS BAR FROM MAIN BREAKER OR MAIN LUG ON GRID SIDE.

WHEN A BACKFED BREAKER IS THE METHOD OF UNTILITY INTERCONNECTION, BREAKER SHALL NOT READ 'LINE OR LOAD'.

-PER CEC 250.64(C): CONDUCTOR SPLICES ONLY ALLOWED WITH COMPRESSION CONNECTORS OR EXOTHERMIC WELDING

-ALL GROUNDS AND NEUTRALS BONDED TO EXISTING GROUNDING CONDUCTOR W/ IRREVERSIBLE CRIP CONNECTOR.

-VERIFY (E) UFER GROUND NEAR MSP. IF (E) UFER IS NOT ACCESSIBLE OR VERIFIABLE, INSTALL A NEW 5/8"Ø X 8' LONG

GROUNDING ROD AND BOND SOLAR SYSTEM EQUIPMENT GROUNDING ACCORDINGLY.

-PRODUCTION METER ADJACENT TO MAIN ELECTRICAL PANEL 10" TO 72" CENTER TO CENTER OF METERS 48" TO 75" ABOVE GRADE LEVEL

OWNER / ADDRESS

*

*

Lynwood CA 90262

PHONE:*

OCCUPANCY R3 /

TYPE 5 STRU.

APN#: *

CONTRACTOR

Home Owner Builder

*

Lynwood CA 90262

PHONE:*

STATE TYPE : -

STATE LICENSE# : -

EXPIRATION DATE : -

DATE: 01/10/18

REVISION :

© C

op

yrig

ht 2017-S

olar P

V P

erm

it

SYSTEM SIZE

2.990 KW-AC

3.190 KW-DC

REVISION :

PAGE INFORMATION

STAMP/ SIGNATURE :

MODULES :

(11) SILEVO TRIEX U290

DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General

Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.

INVERTER(S) :

(1) ABB PVI-3.0-OUTD-US

TITLE:

ELECTRICAL DIAGRAM

PV-04

WIRE

TAG#

MAX AMPS X

NEC MULT=

DESIGN AMPS

BREAKER

SIZE AMPS

WIRE TYPE EGC / GRND.SIZE

WIRE RATING IN 90° X

TEMP DERATE X CONDUCTOR

DERATE = DERATE WIRE

TERMINAL

60°C

RATING

CONDUIT SIZE CONDUIT FILL

1 5.59 x 1.5625 =8.7A 20A

(2)

#10PV WIRE

(1)#6 THWN-2

COPPER EGC

40 x 0.65 x 1.0 =26.0 >=8.7 30> =8.7 OPEN AIR

2 5.59 x 1.5625 =8.7A 20A

(4)

#10THWN-2

(1)#8 THWN-2 EGC

40 x 0.65 x 0.8 =20.8 >=8.7 30> =8.7 3/4" EMT FILL: 0.1210, 23%

3 14.5 x 1.25 x =18.1A 20A

(3)

#10THWN-2

(1)#8 THWN-2 EGC

40 x 0.65 x 0.8 =20.8 >=18.1 30> =18.1 3/4" EMT FILL: 0.0999, 19%

Page 5: NSAMPLE - Solar PV Permitsolarpvpermit.com/Sample/SPVPSample.pdf · if a discrepancy in quantity or size of conduit, wire, ... single family residential in rancho santa margarita,

TITLE:

WARNING LABELS

PLACARD

PV-05

PLAQUE SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITH

POP-RIVETS OR SCREWS.

POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THEFOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN

WARNINGMIN.6"x6" PLACARD TO GO ON MAIN SERVICE PANEL

AC DISCONNECT

MSP

OWNER / ADDRESS

*

*

Lynwood CA 90262

PHONE:*

OCCUPANCY R3 /

TYPE 5 STRU.

APN#: *

CONTRACTOR

Home Owner Builder

*

Lynwood CA 90262

PHONE:*

STATE TYPE : -

STATE LICENSE# : -

EXPIRATION DATE : -

DATE: 01/10/18

REVISION :

© C

op

yrig

ht 2017-S

olar P

V P

erm

it

SYSTEM SIZE

2.990 KW-AC

3.190 KW-DC

REVISION :

PAGE INFORMATION

STAMP/ SIGNATURE :

MODULES :

(11) SILEVO TRIEX U290

DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General

Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.

INVERTER(S) :

(1) ABB PVI-3.0-OUTD-US

PHOTOVOLTAIC AC DISCONNECT

MAX OPERATION CURRENT 14.5 AMPS

MAX. OPERATION VOLTAGE 240 VOLTS

CAUTION

SOLAR ELECTRIC SYSTEM CONNECTED

CAUTION: AC SOLAR VOLTAGE

WARNING

POWER TO THIS BUILDING IS

ALSO SUPPLIED BY THE

PHOTOVOLTAIC SOLAR SYSTEM

DO NOT TOUCH TERMINALS

WARNING

INVERTER OUTPUT

CONNECTIONS(S),

DO NOT RELOCATE THIS

OVERCURRENT DEVICE

WARNING

ELECTRICAL SHOCK HAZZARD

THE DC CONDUCTORS OF THIS

PHOTOVOLTAIC SYSTEM ARE

UNGROUNDED AND MAYBE ENERGIZED

N

WARNING

PHOTOVOLTAIC POWER SOURCE

PLACED ON INTERIOR AND EXTERIOR AC CONDUIT,

RACEWAYS, ENCLOSURES, CABLE ASSEMBLIES, JUNCTION

BOXES, AND DISCONNECTS. MARKING SHALL BE PLACED ON

INTERIOR AND EXTERIOR AC CONDUIT, RACEWAYS,

ENCLOSURES AND CABLE ASSEMBLIES EVERY 10 FEET

(3048MM), WITHIN 1 FOOT OF TURNS OR BENDS AND WITHIN

1 FOOT ABOVE AND BELOW PENETRATIONS OF

ROOF/CEILING ASSEMBLIES, WALLS OR BARRIERS.

CFC 604.11.1& CRC R331.2

CAUTION: SOLAR CUICUIT

PLACED ON ALL AC CONDUITS RACEWAY EVERY 10 FEET

PLACE ON MAIN PANEL

PLACE ON MAIN ELECTRICAL PANEL 690.54

PLACE ON AC DISCONNECT

NEAR GROUND-FAULT INDICATORSTRING INVERTERS

ONLY (Art. 690.5 (C) CEC)

PLACE ON MAIN PANEL & SUB PANELPLACE ON MAIN PANEL

PERMANENT SIGNAGE NOTES:

1. NOT ALL PLACARDS SHOWN MAY BE REQUIRED BY LOCAL AHJ. CONTRACTOR TO VERIFY PLACARD

REQUIREMENTS WITH LOCAL AHJ BEFORE INSTALLATION.

2. ALL PLAQUES AND SIGNAGE REQUIRED BY THE LATEST EDITION OF THE CALIFORNIA ELECTRICAL CODE

AND THE SAN DIEGO AREA ELECTRICAL NEWSLETTER WILL BE INSTALLED AS REQUIRED.

3. ALTERNATE POWER SOURCE PLACARD SHALL BE METALLIC OR PLASTIC, ENGRAVED OR MACHINE

PRINTED LETTERS IN A CONTRASTING COLOR TO THE PLAQUE. THIS PLAQUE WILL BE ATTCHED BY POP

RIVETS OR SCREWS OR OTHER APPROVED METHOD.

4. DIRECTORY PLACARD MARKING CONTENT AND FORMAT: RED BACKGROUND, WHITE LETTERING,

MINIMUM 3/8" LETTER HIEGHT, ALL CAPITAL LETTERS, ARIAL OR SIMILAR FONT, NON BOLD, REFLECTIVE

WEATHER RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT.

541

6 CL

ARK

ST

.

"WARNING"

DUAL POWER SOURCES

SECOND SOURCE IS PHOTO-VOLTAIC SYSTEM

RATED AC OUTPUT CURRENT - 14.5 AMPS

AC NORMAL OPERATING VOLTAGE - 240 VOLTS

INVERTER 1 - 690.14(C0(2), 690.15, 690.53

PV SYSTEM DC DISCONNECT

RATED MAX POWER-POINT CURRENT 10.38 A

RATED MAX POWER-POINT VOLTAGE 384 V

MAXIMUM SYSTEM VOLTAGE 312 V

SHORT CIRCUIT CURRENT 8.94A

PV MODULES

Page 6: NSAMPLE - Solar PV Permitsolarpvpermit.com/Sample/SPVPSample.pdf · if a discrepancy in quantity or size of conduit, wire, ... single family residential in rancho santa margarita,

OWNER / ADDRESS

*

*

Lynwood CA 90262

PHONE:*

OCCUPANCY R3 /

TYPE 5 STRU.

APN#: *

CONTRACTOR

Home Owner Builder

*

Lynwood CA 90262

PHONE:*

STATE TYPE : -

STATE LICENSE# : -

EXPIRATION DATE : -

DATE: 01/10/18

REVISION :

© C

op

yrig

ht 2017-S

olar P

V P

erm

it

SYSTEM SIZE

2.990 KW-AC

3.190 KW-DC

REVISION :

PAGE INFORMATION

STAMP/ SIGNATURE :

MODULES :

(11) SILEVO TRIEX U290

DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General

Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.

INVERTER(S) :

(1) ABB PVI-3.0-OUTD-US

TITLE:

SPECS

PV-06

Page 7: NSAMPLE - Solar PV Permitsolarpvpermit.com/Sample/SPVPSample.pdf · if a discrepancy in quantity or size of conduit, wire, ... single family residential in rancho santa margarita,

OWNER / ADDRESS

*

*

Lynwood CA 90262

PHONE:*

OCCUPANCY R3 /

TYPE 5 STRU.

APN#: *

CONTRACTOR

Home Owner Builder

*

Lynwood CA 90262

PHONE:*

STATE TYPE : -

STATE LICENSE# : -

EXPIRATION DATE : -

DATE: 01/10/18

REVISION :

© C

op

yrig

ht 2017-S

olar P

V P

erm

it

SYSTEM SIZE

2.990 KW-AC

3.190 KW-DC

REVISION :

PAGE INFORMATION

STAMP/ SIGNATURE :

MODULES :

(11) SILEVO TRIEX U290

DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General

Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.

INVERTER(S) :

(1) ABB PVI-3.0-OUTD-US

TITLE:

SPECS

PV-07

Page 8: NSAMPLE - Solar PV Permitsolarpvpermit.com/Sample/SPVPSample.pdf · if a discrepancy in quantity or size of conduit, wire, ... single family residential in rancho santa margarita,

OWNER / ADDRESS

*

*

Lynwood CA 90262

PHONE:*

OCCUPANCY R3 /

TYPE 5 STRU.

APN#: *

CONTRACTOR

Home Owner Builder

*

Lynwood CA 90262

PHONE:*

STATE TYPE : -

STATE LICENSE# : -

EXPIRATION DATE : -

DATE: 01/10/18

REVISION :

© C

op

yrig

ht 2017-S

olar P

V P

erm

it

SYSTEM SIZE

2.990 KW-AC

3.190 KW-DC

REVISION :

PAGE INFORMATION

STAMP/ SIGNATURE :

MODULES :

(11) SILEVO TRIEX U290

DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General

Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.

INVERTER(S) :

(1) ABB PVI-3.0-OUTD-US

PV-08

TITLE:

SPECS

Page 9: NSAMPLE - Solar PV Permitsolarpvpermit.com/Sample/SPVPSample.pdf · if a discrepancy in quantity or size of conduit, wire, ... single family residential in rancho santa margarita,

OWNER / ADDRESS

*

*

Lynwood CA 90262

PHONE:*

OCCUPANCY R3 /

TYPE 5 STRU.

APN#: *

CONTRACTOR

Home Owner Builder

*

Lynwood CA 90262

PHONE:*

STATE TYPE : -

STATE LICENSE# : -

EXPIRATION DATE : -

DATE: 01/10/18

REVISION :

© C

op

yrig

ht 2017-S

olar P

V P

erm

it

SYSTEM SIZE

2.990 KW-AC

3.190 KW-DC

REVISION :

PAGE INFORMATION

STAMP/ SIGNATURE :

MODULES :

(11) SILEVO TRIEX U290

DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General

Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.

INVERTER(S) :

(1) ABB PVI-3.0-OUTD-US

PV-09

TITLE:

SPECS

Page 10: NSAMPLE - Solar PV Permitsolarpvpermit.com/Sample/SPVPSample.pdf · if a discrepancy in quantity or size of conduit, wire, ... single family residential in rancho santa margarita,

OWNER / ADDRESS

*

*

Lynwood CA 90262

PHONE:*

OCCUPANCY R3 /

TYPE 5 STRU.

APN#: *

CONTRACTOR

Home Owner Builder

*

Lynwood CA 90262

PHONE:*

STATE TYPE : -

STATE LICENSE# : -

EXPIRATION DATE : -

DATE: 01/10/18

REVISION :

© C

op

yrig

ht 2017-S

olar P

V P

erm

it

SYSTEM SIZE

2.990 KW-AC

3.190 KW-DC

REVISION :

PAGE INFORMATION

STAMP/ SIGNATURE :

MODULES :

(11) SILEVO TRIEX U290

DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General

Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.

INVERTER(S) :

(1) ABB PVI-3.0-OUTD-US

PV-10

TITLE:

SPECS

Page 11: NSAMPLE - Solar PV Permitsolarpvpermit.com/Sample/SPVPSample.pdf · if a discrepancy in quantity or size of conduit, wire, ... single family residential in rancho santa margarita,

OWNER / ADDRESS

*

*

Lynwood CA 90262

PHONE:*

OCCUPANCY R3 /

TYPE 5 STRU.

APN#: *

CONTRACTOR

Home Owner Builder

*

Lynwood CA 90262

PHONE:*

STATE TYPE : -

STATE LICENSE# : -

EXPIRATION DATE : -

DATE: 01/10/18

REVISION :

© C

op

yrig

ht 2017-S

olar P

V P

erm

it

SYSTEM SIZE

2.990 KW-AC

3.190 KW-DC

REVISION :

PAGE INFORMATION

STAMP/ SIGNATURE :

MODULES :

(11) SILEVO TRIEX U290

DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General

Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.

INVERTER(S) :

(1) ABB PVI-3.0-OUTD-US

PV-11

TITLE:

SPECS

Page 12: NSAMPLE - Solar PV Permitsolarpvpermit.com/Sample/SPVPSample.pdf · if a discrepancy in quantity or size of conduit, wire, ... single family residential in rancho santa margarita,

OWNER / ADDRESS

*

*

Lynwood CA 90262

PHONE:*

OCCUPANCY R3 /

TYPE 5 STRU.

APN#: *

CONTRACTOR

Home Owner Builder

*

Lynwood CA 90262

PHONE:*

STATE TYPE : -

STATE LICENSE# : -

EXPIRATION DATE : -

DATE: 01/10/18

REVISION :

© C

op

yrig

ht 2017-S

olar P

V P

erm

it

SYSTEM SIZE

2.990 KW-AC

3.190 KW-DC

REVISION :

PAGE INFORMATION

STAMP/ SIGNATURE :

MODULES :

(11) SILEVO TRIEX U290

DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing, of such error or omission. In the event that the Owner or General

Contractor falis to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them.

INVERTER(S) :

(1) ABB PVI-3.0-OUTD-US

PV-12

TITLE:

SPECS