notifier rp-2002 instruction manual

6
@) NOTI FI E by Honeywell - - - - Agent Release Panel RP·2002 RP·2002E RP·2002C ...••.• ....., Instruction Manual Document 53039 D1 2/28/2011 Rev: ';;.,1 " , ;,cft•.~•• <,

description

notifier rp-2002 instruction manual

Transcript of notifier rp-2002 instruction manual

Page 1: notifier rp-2002 instruction manual

@) NOTI FI E R®by Honeywell

--

-- Agent Release Panel

RP·2002RP·2002ERP·2002C

...••.•

.....,

Instruction ManualDocument 53039 D 12/28/2011 Rev:';;.,1 " ,;,cft•.~ ••

<,

Page 2: notifier rp-2002 instruction manual

Fire Alarm System LimitationsWhile a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!An automatic fire alarm system-typically made up ofsmoke detectors, heat detectors, manual pull stations, audiblewarning devices, and a fire alarm control panel with remotenotification capability-can provide early warning of a develop-ing fire. Such a system, however, does not assure protectionagainst property damage or loss of life resulting from a fire.

The Manufacturer recommends that smoke and/or heat detec-tors be located throughout a protected premise following therecommendations of the current edition of the National FireProtection Association Standard 72 (NFPA 72), manufacturer'srecommendations, State and local codes, and the recommen-dations contained in the Guides for Proper Use of SystemSmoke Detectors, which are made available at no charge to allinstalling dealers. These documents can be found at http://

.www.systemsensor.com/html/applicat.html. A study by theFederal Emergency Management Agency (an agency of theUnited States government) indicated that smoke detectorsmay not go off in as many as 35% of all fires. While fire alarmsystems are designed to provide early warning against fire,they do not guarantee warning or protection against fire. A firealarm system may not provide timely or adequate warning, orsimply may not function, for a variety of reasons:

Smoke detectors may not sense fire where smoke cannotreach the detectors such as in chimneys, in or behind walls, onroofs, or on the other side of closed doors. Smoke detectorsalso may not sense a fire on another level or floor of a buildinq.A second-floor detector, for example, may not sense a first-floor or basement fire.

Particles of combustion or "smoke" from a developing firemay not reach the sensing chambers of smoke detectorsbecause:

• Barriers such as closed or partially closed doors, walls, orchimneys may inhibit particle or smoke flow.

• Smoke particles may become "cold," stratify, and not reachthe ceiling or upper walls where detectors are located.

• Smoke particles may be blown away from detectors by airoutlets.

• Smoke particles may be drawn into air returns beforereaching the detector.

The amount of "smoke" present may be insufficient to alarmsmoke detectors. Smoke detectors are designed to alarm atvarious levels of smoke density. If such density levels are notcreated by a developing fire at the location of detectors, thedetectors will not go into alarm.

Smoke detectors, even when working properly, have sensinglimitations. Detectors that have photoelectronic sensingchambers tend to detect smoldering fires better than flamingfires, which have little visible smoke. Detectors that have ion-izing-type sensing chambers tend to detect fast-flaming firesbetter than smoldering fires. Because fires develop in differentways and are often unpredictable in their growth, neither typeof detector is necessarily best and a given type of detectormay not provide adequate warning of a fire.

Smoke detectors cannot be expected to provide adequatewarning of fires caused by arson, children playing withmatches (especially in bedrooms), smoking in bed, and violentexplosions (caused by escaping gas, improper storage offlammable materials, etc.).

2

Heat detectors do not sense particles of combustion andalarm only when heat on their sensors increases at a predeter-mined rate or reaches a predetermined level. Rate-of-riseheat detectors may be subject to reduced sensitivity over time.For this reason, the rate-of-rise feature of each detectorshould be tested at least once per year by a qualified fire pro-tection specialist. Heat detectors are designed to protectproperty, not life.

IMPORTANTI Smoke detectors must be installed in thesame room as the control panel and in rooms used by the sys-tem for the connection of alarm transmission wiring, communi-cations, signaling, and/or power. If detectors are not solocated, a developing fire may damage the alarm system, crip-pling its ability to report a fire.

Audible warning devices such as bells may not alert peopleif these devices are located on the other side of closed orpartly open doors or are located on another floor of a building.Any warning device may fail to alert people with a disability orthose who have recently consumed drugs, alcohol or medica-tion. Please note that:

• Strobes can, under certain circumstances, cause seizuresin people with conditions such as epilepsy.

• Studies have shown that certain people, even when theyhear a fire alarm signal, do not respond or comprehend themeaning of the signal. It is the property owner's responsi-bility to conduct fire drills and other training exercise tomake people aware of fire alarm signals and instruct themon the proper reaction to alarm signals.

• In rare instances, the sounding of a warning device cancause temporary or permanent hearing loss.

A fire alarm system will not operate without any electricalpower. If AC power fails, the system will operate from standbybatteries only for a specified time and only if the batteries havebeen properly maintained and replaced regularly.

Equipment used in the system may not be technically com-patible with the control panel. It is essential to use only equip-ment listed for service with your control panel.

Telephone lines needed to transmit alarm signals from apremise to a central monitoring station may be out of serviceor temporarily disabled. For added protection against tele-phone line failure, backup radio transmission systems are rec-ommended.

The most common cause of fire alarm malfunction is inade-quate maintenance. To keep the entire fire alarm system inexcellent working order, ongoing maintenance is required perthe manufacturer's recommendations, and UL and NFPA stan-dards. At a minimum, the requirements of NFPA 72 shall befollowed. Environments with large amounts of dust, dirt orhigh air velocity require more frequent maintenance. A main-tenance agreement should be arranged through the local man-ufacturer's representative. Maintenance should be scheduledmonthly or as required by National and/or local fire codes andshould be performed by authorized professional fire alarminstallers only. Adequate written records of all inspectionsshould be kept.

Limit-C 1-2-2007

RP-2002 Series Manual- PIN 53039:01 2/28/2011

Page 3: notifier rp-2002 instruction manual

~

Installation Precautions

"

Adherence to the following will aid in problem-free installation with long-term reliability:

•••••••

WARNING - Several different sources of power can beconnected to the fire alarm control panel. Disconnect allsources of power before servicing. Control unit and associ-ated equipment may be damaged by removing and/or insert-ing cards, modules, or interconnecting cables while the unit isenergized. Do not attempt to install, service, or operate thisunit until manuals are read and understood.

CAUTION - System Re-acceptance Test after SoftwareChanges: To ensure proper system operation, this productmust be tested in accordance with NFPA 72 after any pro-gramming operation or change in site-specific software. Re-acceptance testing is required after any change, addition ordeletion of system components, or after any modification,repair or adjustment to system hardware or wiring. All compo-nents, circuits, system operations, or software functions knownto be affected by a change must be 100% tested. In addition,to ensure that other operations are not inadvertently affected,at least 10% of initiating devices that are not directly affectedby the change, up to a maximum of 50 devices, must also betested and proper system operation verified.

This system meets NFPA requirements for operation at 0-49°C/32-1200 F and at a relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F). However, the usefullife of the system's standby batteries and the electronic com-ponents may be adversely affected by extreme temperatureranges and humidity. Therefore, it is recommended that thissystem and its peripherals be installed in an environment witha normal room temperature of 15-27° C/60-800 F.

Verify that wire sizes are adequate for all initiating and indi-cating device loops. Most devices cannot tolerate more than a10% I.R. drop from the specified device voltage.-

Like all solid state electronic devices, this system mayoperate erratically or can be damaged when subjected to light-ning induced transients. Although no system is completelyimmune from lightning transients and interference, propergrounding will reduce susceptibility. Overhead or outside aerialwiring is not recommended, due to an increased susceptibilityto nearby lightning strikes. Consult with the Technical Ser-vices Department if any problems are anticipated or encoun-tered.

Disconnect AC power and batteries prior to removing orinserting circuit boards. Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing,reaming, or punching of the enclosure. When possible, makeall cable entries from the sides or rear. Before making modifi-cations, verify that they will not interfere with battery, trans-former, or printed circuit board location.

Do not tighten screw terminals more than 9 in-Ibs. Over-tightening may damage threads, resulting in reduced terminalcontact pressure and difficulty with screw terminal removal.

This system contains static-sensitive components.Always ground yourself with a proper wrist strap before han-dling any circuits so that static charges are removed from thebody. Use static suppressive packaging to protect electronicassemblies removed from the unit.

Follow the instructions in the installation, operating, and pro-gramming manuals. These instructions must be followed toavoid damage to the control panel and associated equipment.FACP operation and reliability depend upon proper installation.

Precau-01-9-2005

- WARNING: This equipment generates, uses, and canradiate radio frequency energy and if not installed andused in accordance with the instruction manual maycause interference to radio communications. It has beentested and found to comply with the limits for class Acomputing devices pursuant to Subpart B of Part 15 ofFCC Rules, which is designed to provide reasonableprotection against such interference when devices areoperated in a commercial environment. Operation of thisequipment in a residential area is likely to cause interfer-ence, in which case the user will be required to correctthe interference at his or her own expense.

FCC Warning

---Canadian Requirements

This digital apparatus does not exceed the Class A limitsfor radiation noise emissions from digital apparatus setout in the Radio Interference Regulations of the Cana-dian Department of Communications.

Le present appareil numerique n'emet pas de bruits radi-oelectriques depassant les limites applicables aux appa-reils numeriques de la classe A prescrites dans leReglement sur le brouillage radioelectrique edicte par leministere des Communications du Canada.

NOTIFIER® is a registered trademark of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.

©2011 by Honeywelllnternationallnc. All rights reserved. Unauthorized use of this document is strictly prohibited.

RP-2002 Series Manual- PIN 53039:D1 2/2812011 3

Page 4: notifier rp-2002 instruction manual

Software DownloadsIn order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we makefrequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latestfeatures, we strongly recommend that you down load the most current version of software for each product prior tocommissioning any system. Contact Technical Support with any questions about software and the appropriate version fora specific application.

Documentation FeedbackYour feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions aboutour online Help or printed manuals, you can email us.

Please include the following information:

·Product name and version number (if applicable)·Printed manual or online Help·Topic Title (for online Help)·Page number (for printed manual)·Brief description of content you think should be improved or corrected·Your suggestion for how to correct/improve documentation

Send email messages to:

[email protected]

Please note this email address is for documentation feedback only. If you have any technical issues, please contactTechnical Services.

4 RP-2002 Series Manual- PIN 53039:Dl 212812011

Page 5: notifier rp-2002 instruction manual

Table of Contents

-Section 1: Product Description 13

1.1: Product Features 131.2: Specifications 141.3: Controls and Indicators 171.4: Components 181.5: Optional Modules and Accessories 18

Section 2: Installation 202.1: Backbox Mounting 202.2: Operating Power 232.3: Input Circuits 242.4: Output Circuits 27

2.4.1: Outputs/Notification AppliancelReleasing Circuits 272.4.2: Special Application DCPower Output Connections 282.4.3: Relays - Programmable 28

2.5: Power-limited Wiring Requirements 292.6: Installation of Optional Modules 30

2.6.1: N-CAC-5X Class A Converter Module 30Installation 30Wiring NACs and IDCs for Class A 31

2.6.2: 4XTM Municipal Box Transmitter Option Module 324XTM Transmitter Module Installation 32

2.6.3: ANN-SEC Option Card 332.7: ANN-BUS Devices 34

Guidelines 342.7.1: ANN-BUS Wiring 35

Calculating Wiring Distance for ANN-BUS Modules 35Powering ANN-BUS Devices from Auxiliary Power Supply 37

2.7.2: ANN-BUS Device Addressing 382.7.3: N-ANN-80 Remote LCD Annunciator.. 38

Specifications 38Installation 38Wiring N-ANN-80 to FACP 39Programming 40

2.7.4: N-ANN-S/PG Serial/Parallel Printer Interface Installation .40Specifications 41PRN-6 Printer Installation 41

2.7.5: N-ANN-I/O LED Driver Module 43N-ANN-I/O Board Layout 43Specifications 43N-ANN-I/O Connection to FACP 44N-ANN-I/O Module LED Wiring 44

2.7.6: N-ANN-LED Annunciator Module 45Specifications 45Mounting/Installation 45N-ANN-LED Board Layout and Connection to FACP .46

2.7.7: N-ANN-RL Y Relay Module 46Specifications 46Mounting/Installation 47N-ANN-RLY Board Layout and Connection to FACP .47

Section 3: Programming 483.1: User Programming 483.2: Initial Power-up 493.3: Programming Screens Description 49

,,:

-

.•...•

--

--

----

KP-2002 Series Manual- PIN 53039:D1 2/28/2011 5

Page 6: notifier rp-2002 instruction manual

Table of Contents

3.4: Programming and Passwords 503.5: Master Programming Level 51

3.5.1: FACP CONFIG (Application Templates) 523.5.2: Input Zones 533.5.3: Output Circuits 59

Enabled 60Type 60Silence , 62Auto Silence 63Silence Inhibited 63Coding 64

3.5.4: Cross Input Zones 663.5.5: On-Board Relays 683.5.6: System Setup 69

Abort Type 70Timers 70Banner 73Time-Date 74Trouble Reminder 76Charger Disable 76Canadian Option 76Secondary ANN-BUS Option 77

3.5.7: ANN-BUS 77ANN-BUS Enabled 77ANN-BUS Modules 77Auto-Configure 78ANN-S/PG Options 79ANN-I/O LED Zone Assignments 80ANN-80 Options 81ANN-RL Y Options 82

3.5.8: History 83View Events 83Erase History 83

3.5.9: Walktest 843.5.10: Clear Program 853.5.11: Password Change 85

3.6: Maintenance Programming Level 863.6.1: Input Zones - EnablelDisable 873.6.2: History 873.6.3: Walktest 883.6.4: Time-Date 89

Section 4: Operating Instructions 904.1: Panel Control Buttons 90

4.1.1: Acknowledge/Step 904.1.2: Alarm Silenced 904.1.3: Drill/Hold 2 Sec 904.1.4: Reset 90

4.2: Indicators 914.3: Normal Operation 924.4: Trouble Operation 924.5: Alarm Operation 934.6: Supervisory Operation 944.7: DisablelEnable Operation 954.8: Waterflow Circuits Operation 954.9: Detector Functions 954.10: Time Functions: Real-Time Clock 96

6 RP-2002 Series Manual- PIN 53039:D I 2/28/2011::.-