Transcript of Notifier Net 2013

  • Honeywell Life SafetyPDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    NFN Network Description Peer-to-peer network Minimum hardware requirement for NFN

    2 nodes connected via wire or fiber Supports 103 Nodes with a maximum capacity

    of 324,360 points. It will support up to 54 nodes when it is set

    up to circulate digital audio messages from a DVC node.

    Each node requires a unique address and it communicates with other nodes via a network interface board.

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    AFP-200 / AFP-300 / AFP-400

    AM2020, AFP-1010 NFS-3030 NFS-640 Network Control

    Annunciator (NCA) Network Control Station

    (NCS 2.0 to 4.x)

    DVC/DVC-EM NCA-2 NFS2-3030 NFS2-640 NFS-320 Network Control Station

    (NCS 5.0 to 5.9) ONYXWorks

    8th Edition Nodes 9th Edition Nodes

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Network Interface Boards The physical interface which connects nodes

    forming a network: NAM-232W, NAM-232F

    AFP-200/300/400

    SIB-NET with MIB-W, MIB-F, MIB-WF NCM-W, NCM-F

    NFS2-3030, NFS-3030, NFS2-640, NFS-640, NFS-320, NCA-2, NCA, DVC

    NCS-NCW, NCS-NCF NFN-GW-PC-W, NFN-GW-PC-F RPT-W, RPT-F, RPT-WF

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Network Communications Module(NCM)

    Connects to the NUP (Notifier Universal Protocol) port on Onyx Fire Alarm Panels, NCA, NCA-2 and DVC.

    Each NCM on the network MUST be running the same version.

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    NCM-W

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Channel A & B connections

    Network connection Ports (NUP)

    Diagnostic LEDs

    Not Used

    NCM-F

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    NCS-NCW

    NFN-GW-PC-W

    NCS-NCF

    NFN-GW-PC-F

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Repeaters (RPT) Repeaters (RPT) regenerate data signals

    between network nodes, extending communication distances. RPT-W two twisted pair wire ports RPT-F two fiber optic cable ports RPT-WF one twisted pair wire port and one fiber

    optic cable port.

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Threshold Selection for Port A and

    Port B

    Ground fault detection feed-through

    24V

    RPT-W RPT-F

    RPT-WF

    Threshold Selection for

    Port A

    Port A and Port B

    Port A

    Port B

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Network Configurations NFN is capable of communicating using

    two types of wiring styles, style 4 and 7. Style 4

    A single open, wire-to-wire short, wire-to-wire short and open, wire-to-wire short and ground, or open and ground results in fragmentation of the network

    Style 7 A single open, wire-to-wire short, wire-to-wire short

    and open, wire-to-wire short and ground, or open and ground will not result in fragmentation of the network.

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Point-To-Point Configuration Wiring a Noti-Fire-Net in Style 7 point-to-point.

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Point-To-Point Configuration A point-to-point wiring configuration is defined as a twisted-pair

    segment with ONLY two nodes/repeaters attached to it. Terminating resistors are required at the beginning and the end of

    every segment and are built into each MIB/RPT/NAM232. Termination is done with slide switches on the NCM/NCS-

    NCW/NFN-GW-PC-W.Terminate Terminate Terminate

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Bus Configuration A bus wiring configuration is defined as a twisted pair

    network with more than two nodes. Termination is only required on the FIRST and LAST

    node of the bus. Remove termination on the middle nodes of the bus.

    TERMINATE

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Combination Network

    Admin Building

    Science Building

    Cafeteria

    Gymnasium

    BUS

    Point-to-Point

    Point-to-Point24V

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    ABB A

    Polarity does not matter on network wiring.

    EE

    Wire Connections

    MUST USE

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Wire Connections

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Wire ConnectionsWRONG

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Fiber Connections

    Rx B Tx B Rx A Tx A Rx B Tx B Rx A Tx A

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Mixing Wire and Fiber

    NCM-W RPT-WF NCM-F24V

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Network Wiring Requirements When designing the wiring layout of a

    NOTI-FIRE-NET system, the following limitations must be considered:

    1. The length of each individual twisted pair or fiber optic network communication circuit segment is limited.

    2. The system path length is limited.

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Network Wiring Requirements

    B A B A

    Network Node or repeaterNetwork

    Node

    B A

    Network Node or repeater

    B A

    Network Node

    Point-to-point segments 1, 2, and 3.

    Each segment is connected to only two nodes/repeaters and can not exceed the limits of the wire used.

    1 2 3

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Limit on System Path Length

    B A

    B A

    B A

    NetworkNode

    End of Network End of Network

    B A

    Network Node or repeater

    Network

    Node

    Network Node or repeater

    B A B A

    Network Node or repeater

    Network Node or repeater

    14

    2

    3

    System Path Length = Sum of the length of Segments 1, 2, 3, and 4.

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    450,000

    400,000

    350,000

    300,000

    250,000

    200,000

    150,000

    100,000

    50,000

    00 50 100 150 200 250

    Total Number of Nodes/Repeaters

    Overall Distance(Feet)

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Limit for Fiber Optic Circuits The attenuation of cabling between two nodes/repeaters is limited

    by cable choice.

    Fiber optic circuits are point-to-point only, NO Star or Bussing is allowed.

    Use repeaters (RPT-F) to extend segments.

    Attenuation limits for multimode fiber: 62.5/125m cable = 8dB limit 50/125m cable = 4.2dB limit Use industry standard equipment using a test wavelength of

    850 nanometers to calculate dB loss.

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Calculating approximate dB loss1. Calculate loss due to cable look up the rated dB

    loss per foot from manufacturers specifications. Multiply this by the length of cable between 2 nodes/repeaters to determine loss due to cable. (Loss/ft x length in ft)

    2. Calculate loss due to connectors/splices Look up the dB loss for each connector and splice. Add all figures to determine loss due to connectors/splices.

    3. Calculate total loss Add the attenuation factors obtained in steps 1 & 2. This will provide an approximate attenuation total.

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Calculating approximate dB loss2. Calculate loss due to connectors/splices

    Look up the dB loss for each connector and splice.Connectors = 0.3 dB loss for most adhesive/polish connectors.

    0.75 dB loss for most prepolished/spliced connectors.

    Splices = Typically 0.3 dB loss for each splice

    1.Add all figures to determine loss due to connectors/splices.

    E.g. There are two prepolished connectors and one splice between the networked nodes

    (0.75 + 0.75 + 0.3) = 1.8 dB loss

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    Calculating approximate dB loss3. Calculate total loss

    Add the attenuation factors obtained in steps 1 & 2. This will provide an approximate attenuation total, which should be 8 dB or less for the standard NFN.

    Step 1 (.001 x 1800) = 1.8 dB lossStep 2 (0.75 + 0.75 + 0.3) = + 1.8 dB loss

    Step 3 Approximate total loss = 3.6 dB

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    HS-NCM Overview

    v Increased Node Count 200+ Node Addresses on HS-NCM even when using

    Digital Audio Current NCMs 103 Nodes, 54 Nodes w/Digital Audio

    v Single Channel Digital Audio over NFN Future releases will allow multiple channels of Digital

    Audio over NFNv HS-NCM can have two node addresses per modulev ONYX Series Compatible (8th and 9th Edition)v Flash Memory

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    HS-NCM Overview

    *NFN on IP based VDSL Network (Very High Data Rate Subscriber Line)*The HS-NCM is NOT compatible with the

    standard NCM Noti-Fire-Net Network.*Supports NUP Universal Protocol*Can be configured as a network repeater*Installs in same single module bay as NCM*Replacement for all IP based Gateways+BACNET GATEWAY+NWS+NFN-GW-EM

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    HS-NCM Hybrids

    HS-NCM-WSF HS-NCM-WMF

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    HS-NCM Applications

    NUP NUP

    USB USB

    NFN NFN

    HS-NCM2 Node

    Addresses

    HS-NCMHS-NCM

    Veri-Fire Tools

    100

    DVC,NCA-2,Gatewayor another FACP

    PDF created with pdfFactory Pro trial version www.pdffactory.com

  • Honeywell Life Safety

    ?

    Blah,Blah,Blah,

    Blah,Blah,Blah. What was he talkingabout ?

    Z z z z

    z z z z

    z zQuestions,