NFPA 70E Approach to Considering DC Hazards - efcog.org Working Group/_Worker... · HOYDAR- BUCK,...
Transcript of NFPA 70E Approach to Considering DC Hazards - efcog.org Working Group/_Worker... · HOYDAR- BUCK,...
HOYDAR-
BUCK, INC.
2013 NFPA Conference and Expo
Chicago, IL
NFPA 70E® Approach to Considering DC Hazards
Bobby Gray Consultant
HBI
Steve McCluer Sr. Manager /External Codes & Standards
Schneider Electric
HOYDAR-
BUCK, INC.
David Dini was Assigned New Chair of NFPA 70E The New Chair Assigned Various Task Teams Including: DC Hazards Task Team
NFPA 70E® Approach to Considering DC Hazards
BACKGROUND
2012 NFPA 70E®
HOYDAR-
BUCK, INC.
1. Review Complete 2009 Standard 2. Identify Inadequacies 3. Generate Proposals for 2012
NFPA 70E® Approach to Considering DC Hazards
BACKGROUND
2012 DC Hazards Task Team’s Charter
HOYDAR-
BUCK, INC.
- Academia - Power and Manufacturing Industries - Research and Development - IEEE Stationary Battery Working Group
NFPA 70E® Approach to Considering DC Hazards
BACKGROUND
2012 DC Hazards Task Team Invited Industry Experts
HOYDAR-
BUCK, INC.
Shock Hazard
“Chapters 1 and 2 apply to electrical equipment that operates at frequencies normally supplied for consumer use.” --2009 NFPA 70E® Handbook
NFPA 70E® Approach to Considering DC Hazards
BACKGROUND
2012 DC Hazards Task Team Results of 2009 NFPA 70E® Review
HOYDAR-
BUCK, INC.
The Generic Threshold for Electrical Hazard Is 50 volts Shock Approach Tables are Based on Phase-To-Phase Voltage
NFPA 70E® Approach to Considering DC Hazards
BACKGROUND
2012 DC Hazards Task Team Results of 2009 NFPA 70E® Review
Shock Hazard
HOYDAR-
BUCK, INC.
1. IEC 60479, Effects of Current Passing Through the Body - referenced in NFPA 70E-2012®, 340.4
2. Published Research Papers by Dalziel, Geddes, Knickerbocker, LB Gordon, etc. 3. NIOSH Data
NFPA 70E® Approach to Considering DC Hazards
BACKGROUND
2012 DC Hazards Task Team Shock Hazard Research Papers
HOYDAR-
BUCK, INC.
“The current and voltage thresholds for physiological effects are at least twice the values for dc as compared to ac.“ --IEC 60479
See also: NFPA 70E-2012 Handbook
NFPA 70E® Approach to Considering DC Hazards
BACKGROUND
2012 DC Hazards Task Team Shock Hazard Research
HOYDAR-
BUCK, INC.
1. “DC arc models and incident energy calculations,” Ammerman, R.F.; Gammon, T.; Sen, P.K.; Nelson, J.P.; Petroleum and Chemical Industry Conference, 2009, Record of Conference Papers,14–16 September 2009. 2. “Arc Flash Calculations for Exposures to DC Systems,” Doan, D.R., IEEE IAS Electrical Safety Workshop, 2007, Record of Conference Papers, March 2007. 3. DC Arc Hazard Assessment Phase II Copyright Material Kinectrics Inc. Report No. K-012623-RA-0002-R00.
NFPA 70E® Approach to Considering DC Hazards
BACKGROUND
2012 DC Hazards Task Team Arc Flash Research
HOYDAR-
BUCK, INC.
1. DC Shock Approach Table 130.4(C)(b) 2. DC Arc Flash Hazard Risk Category Table 130.7(C)(15)(b) 3. DC Incident Energy Calculation Method Annex D, Paragraph D.8.1
NFPA 70E® Approach to Considering DC Hazards
BACKGROUND
2012 DC Hazards Task Team 2012 Proposals
HOYDAR-
BUCK, INC.
1. Determine Polarity Difference of Potential 2. Determine Nearest Approach Boundary To Be Crossed Based on Table 130.4(C)(b) Approach Boundaries to Energized Electrical Conductors or Circuit Parts for
Shock protection, Direct-Current Voltage Systems
3. Apply Proper Shock Protection Techniques
NFPA 70E® Approach to Considering DC Hazards
DC ELECTRICAL HAZARD ANALYSIS
Shock Hazard Analysis 130.4(A)
HOYDAR-
BUCK, INC.
NFPA 70E® Approach to Considering DC Hazards
DC ELECTRICAL HAZARD ANALYSIS
TABLE 130.4(C)(b) Approach Boundaries to Energized Electrical Conductors or Circuit Parts for dc Shock Protection (1) (2) (3) (4) (5)
Nominal Potential Difference Limited Approach Boundary Restricted Approach Boundary; Includes
Inadvertent Movement Adder
Prohibited Approach Boundary Exposed Movable
Conductorb Exposed Fixed Circuit
Part
<100 V Not specified Not specified Not specified Not specified
100 V–300 V 3.0 m (10 ft 0 in.) 1.0 m (3 ft 6 in.) Avoid contact Avoid contact
301 V–1 kV 3.0 m (10 ft 0 in.) 1.0 m (3 ft 6 in.) 0.3 m (1 ft 0 in.) 25 mm (0 ft 1 in.)
1.1 kV–5 kV 3.0 m (10 ft 0 in.) 1.5 m (5 ft 0 in.) 0.5 m (1 ft 5 in.) 0.1 m (0 ft 4 in.)
5 kV–15 kV 3.0 m (10 ft 0 in.) 1.5 m (5 ft 0 in.) 0.7 m (2 ft 2 in.) 0.2 m (0 ft 7 in.)
15.1 kV–45 kV 3.0 m (10 ft 0 in.) 2.5 m (8 ft 0 in.) 0.8 m (2 ft 9 in.) 0.4 m (1 ft 5 in.)
45.1 kV– 75 kV 3.0 m (10 ft 0 in.) 2.5 m (8 ft 0 in.) 1.0 m (3 ft 2 in.) 0.7 m (2 ft 1 in.)
75.1 kV–150 kV 3.3 m (10 ft 8 in.) 3.0 m (10 ft 0 in.) 1.2 m (4 ft 0 in.) 1.0 m (3 ft 2 in.)
150.1 kV–250 kV 3.6 m (11 ft 8 in.) 3.6 m (11 ft 8 in.) 1.6 m (5 ft 3 in.) 1.5 m (5 ft 0 in.)
250.1 kV–500 kV 6.0 m (20 ft 0 in.) 6.0 m (20 ft 0 in.) 3.5 m (11 ft 6 in.) 3.3 m (10 ft 10 in.)
500.1 kV–800 kV 8.0 m (26 ft 0 in.) 8.0 m (26 ft 0 in.) 5.0 m (16 ft 5 in.) 5.0 m (16 ft 5 in.)
A All dimensions are distance from exposed energized electrical conductors or circuit parts to worker. B This terms describes a condition in which the distance between the conductor and a person is not under the control of the person. The term is normally applied to overhead line conductors supported by poles.
HOYDAR-
BUCK, INC.
- Be Qualified 130.4(D) or - Be Continuously Escorted 130.4(D)(2) and - Work Under EEWP 130.2(B)(1) and - Use Insulated Tools and Equipment 130.7(D)(1)
NFPA 70E® Approach to Considering DC Hazards
DC ELECTRICAL HAZARD ANALYSIS
To Cross a Limited Approach Boundary you must:
HOYDAR-
BUCK, INC.
- Be Qualified 130.4(D)(2) and - Be Insulated from Energized Parts 130.4(C)(1)
or - Guard Energized Parts 130.4(C)(2)
NFPA 70E® Approach to Considering DC Hazards
DC ELECTRICAL HAZARD ANALYSIS
To Cross a Restricted Approach Boundary you must:
HOYDAR-
BUCK, INC.
1. Determine Arc Flash Boundary (Where is PPE Required?) 2. Determine Incident Energy At Working Distance (What Rating of PPE is Required?) 3. Choose Arc-Rated and Other PPE Based on Task
NFPA 70E® Approach to Considering DC Hazards
DC ELECTRICAL HAZARD ANALYSIS
Arc Flash Hazard Analysis 130.5
HOYDAR-
BUCK, INC.
NFPA 70E® Approach to Considering DC Hazards
DC ELECTRICAL HAZARD ANALYSIS
Arc Flash Hazard Analysis Two Methods to Select PPE [130.5(B)]:
1. Incident Energy Analysis [130.5(B)(1)]
a) Determine Actual Exposure
b) Use 130.7(C) or Table H.3(b)
2. Hazard Risk Category from Table 130.7(C)(15)(b)
& PPE from Table 130.7(C)(16) [130.5(B)(2)]
HOYDAR-
BUCK, INC.
NFPA 70E-2012 Table 130.4(C)(b) identifies 4 Conditions at 11 dc voltage ranges. [see next slide]
(It does not address Amperes, Watts, or fault potential)
NFPA 70E® Approach to Considering DC Hazards
HAZARD ANALYSIS FOR BATTERIES
Shock Approach Boundaries: Energized dc circuits or conductors
HOYDAR-
BUCK, INC.
NFPA 70E® Approach to Considering DC Hazards
HAZARD ANALYSIS FOR BATTERIES
From Table 130.4(C)(b)
HOYDAR-
BUCK, INC.
o NFPA 70E-2012 Table 130.7(C)(15)(b) is for all dc use, including storage batteries, dc switchboards, & other dc supply sources o Hazard risk categories (1 - 4) o Rubber insulating gloves & Insulated hand tools are required in all cases -
NFPA 70E® Approach to Considering DC Hazards
HAZARD ANALYSIS FOR BATTERIES
Hazard Risk Category Classes for dc Equipment
HOYDAR-
BUCK, INC.
NFPA 70E® Approach to Considering DC Hazards
HAZARD ANALYSIS FOR BATTERIES
Table 130.7(C)(15)(b) Potential Arc Flash Boundaries:
HOYDAR-
BUCK, INC.
NFPA 70E® Approach to Considering DC Hazards
HAZARD ANALYSIS FOR BATTERIES
Annex D.8 Calculated Arc Flash Boundary:
●70E picks up Doan’s method (based on Lee’s work); comments
that “testing completed for Bruce power has shown that the
calculation is conservatively high…”
●Recommends multiplying factor of 3 for “arc in a box”
configurations
●Applicable to systems up to 1000V DC
Schneider Electric 22
Maximum Power Transfer
● Max power is delivered to arc when Arc Voltage = ½ System Voltage
● In other words – impedance matching!
● Power delivered = ½ bolted fault MVA
VA
VS
ZA
IF
VSys
ZS
HOYDAR-
BUCK, INC.
NFPA 70E® Approach to Considering DC Hazards
HAZARD ANALYSIS FOR BATTERIES Table 130.7(C)(15)(b)
Table 130.7(C)(15)(b)
HOYDAR-
BUCK, INC.
NFPA 70E® Approach to Considering DC Hazards
HAZARD ANALYSIS FOR BATTERIES
Is there such a thing as dc “arc flash?”
• Maybe a spark?
• in most cases a battery cannot sustain an arc
• unlike a utility, which has ‘unlimited’ EMF
• a battery’s stored energy is rapidly depleted
• Literature search reveals shock hazards and
millisecond-long “sparks”
• but no “flash” and no “blast”
• The real hazards are ‘thermal’ and ‘shock’
HOYDAR-
BUCK, INC.
NFPA 70E® Approach to Considering DC Hazards
HAZARD ANALYSIS FOR BATTERIES
Needed: DC Test Data
●NFPA & IEEE are conducting a US $6 million collaborative
research project to characterize arc flash
The joint study includes:
● Heat & thermal effects
● Blast Pressure
● Sound
● Light intensity
● Initial report is for ac only; some dc modeling has been done
HOYDAR-
BUCK, INC.
IEEE StaBatt Committee Approach to Considering DC Hazards
HAZARD ANALYSIS FOR BATTERIES
● HAZARD and RISK are NOT THE SAME THING
● If there is no hazard, there is no risk
● If there is a hazard, the risk depends upon the
probability of an incident
● Risk can be minimized
● Personal Protective Equipment (PPE) must be
based upon the risk, not the hazard
HOYDAR-
BUCK, INC.
IEEE StaBatt Committee Approach to Considering DC Hazards
Concerns About Required PPE
●Gloves, clothing, and other PPE should:
● protect against both Electrical &Chemical hazards
● allow full freedom of movement & visibility for all
battery-related tasks
● be readily available
● Too much PPE can actually create a
hazardous situation
HOYDAR-
BUCK, INC.
IEEE StaBatt Committee Approach to Considering DC Hazards
HAZARD ANALYSIS FOR BATTERIES
●Methods of minimizing risk:
● use insulated tools
● segment battery sections
● insulate exposed dc bus
● prevent contact between + and –
● train, certify, refresh
● perform risk analysis for planned tasks prior to
doing the work
APC by Schneider Electric – BATTCON 2011/ McCluer – West
APC by Schneider Electric – BATTCON 2011/ McCluer – West
APC by Schneider Electric – BATTCON 2011/ McCluer – West
APC by Schneider Electric – BATTCON 2011/ McCluer – West
HOYDAR-
BUCK, INC.
NFPA 70E® Approach to Considering DC
Hazards
SIGNIFICANT CHANGES EXPECTED IN 2015 NFPA 70E
● Safe Shock Voltage Lowered back to 50vdc in
Table
● Reformatted Arc Flash Table
● Replaced Arcing Current with SSC Values in
Table
● Added Paragraph to Instruct How to Obtain
Arcing Current in Annex D
HOYDAR-
BUCK, INC.
NFPA 70E® Approach to Considering DC
Hazards
SIGNIFICANT CHANGES EXPECTED IN 2015 NFPA 70E
Lower Safe Shock Voltage to 50 Vdc in Table
Needed to reconcile with AC threshold in NFPA 70E
and NEC
LAB – 3’6” RAB – Avoid Contact
Justification to Cross Required at 50 Vdc
Qualified or Continuously Escorted
No PPE Requirements
Tools Not Required to be Insulated [130.7(D)(1)]
HOYDAR-
BUCK, INC.
NFPA 70E® Approach to Considering DC
Hazards
SIGNIFICANT CHANGES EXPECTED IN 2015 NFPA 70E
Two existing arc flash tables – 130.7(C)(15)(B)(a) & (b)
will be merged into one: 130.7(C)(15)(b)
First Table Screens Tasks With Arc Flash Hazard
Second Table Assigns HRC to Equipment
Some DC Tasks Added
HOYDAR-
BUCK, INC.
NFPA 70E® Approach to Considering DC
Hazards
SIGNIFICANT CHANGES EXPECTED IN 2015 NFPA 70E
Will replace Arcing Current with SSC values in arc
flash table
2012 Requires conversion from SSC to arcing
current to use table
Other changes include defining proper installation
and maintenance
HOYDAR-
BUCK, INC.
NFPA 70E® Approach to Considering DC
Hazards
SIGNIFICANT CHANGES EXPECTED IN 2015 NFPA 70E
Adds paragraph to instruct how to obtain arcing
current in Annex D
Method is based on IEEE 946
50% of DC short circuit value
Assume 25°C ambient
Maximum available SSC =10 times 1 Minute ampere rating
of the battery
Better: Contact battery manufacturer for specific battery
model short circuit values
HOYDAR-
BUCK, INC.
NFPA 70E® Approach to Considering DC
Hazards
CONCLUSION
●QUESTIONS?
●COMMENTS?
●THANK YOU!