An Overview of the Scope and Purpose of NFPA 25
An Overview of the Scope and Purpose of NFPA 25
![Page 2: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/2.jpg)
Russ is the Chairman and CEO of Telgian, Inc. whose subsidiaries include Fire Materials Group and TVA Fire and Life Safety. He holds a degree from the University of Nevada, Las Vegas and a Level IV certification from NICET in Fire Sprinkler Layout. He is a licensed contractor in 40 states and has 25 years of experience in the design, installation, and testing of fire protection systems. Telgian provides a wide range of fire protection and life safety services including fire systems engineering and design, code consulting, loss control engineering, installation, and the inspection and testing. Russ has worked on projects throughout North America, Central and South America, the Far East, and Europe. He serves as a principal on the NFPA 25 technical committee and theNFPA 5000 (building code) correlating committee. Russ conducts seminars throughout North America for Authorities Having Jurisdiction, Contractors, and Engineers on a variety of subjects and is a member of AFSA, NFPA, NFSA, and SFPE.
![Page 3: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/3.jpg)
Russ Leavitt, S.E.T.
Telgian, Inc2615 S Industrial Park Ave.
Tempe, AZ 85282
PH: (480) 753-5444Email: [email protected]
Russ Leavitt, S.E.T.
Telgian, Inc2615 S Industrial Park Ave.
Tempe, AZ 85282
PH: (480) 753-5444Email: [email protected]
![Page 4: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/4.jpg)
NFPA 13AFirst published in 1940Last edition 1987No mandatory language
NFPA 25Technical committee appointed in 1990First edition 1992
NFPA 13AFirst published in 1940Last edition 1987No mandatory language
NFPA 25Technical committee appointed in 1990First edition 1992
![Page 5: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/5.jpg)
LET’S REVIEW WHYLET’S REVIEW WHY
![Page 6: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/6.jpg)
80% of System Failures can be attributed to a lack of
maintenance!
80% of System Failures can be attributed to a lack of
maintenance!
![Page 7: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/7.jpg)
![Page 8: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/8.jpg)
Leading causes of failures:System shut off (66%)Lack of other Maintenance (10%)Damaged Component (2%)
Leading causes of failures:System shut off (66%)Lack of other Maintenance (10%)Damaged Component (2%)
![Page 9: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/9.jpg)
NFPA 25 2008 EditionNFPA 25 2008 Edition
Two-thirds of all failures are because of a shut water control valve!
Think about it—We could eliminate 2/3 of failures by simply keeping control valves open!
Two-thirds of all failures are because of a shut water control valve!
Think about it—We could eliminate 2/3 of failures by simply keeping control valves open!
![Page 10: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/10.jpg)
NFPA 25 2008 EditionNFPA 25 2008 Edition
The Objective of NFPA 25 is to eliminate the failures that
are caused by the lack of maintenance.
The Objective of NFPA 25 is to eliminate the failures that
are caused by the lack of maintenance.
![Page 11: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/11.jpg)
NFPA 25 is widely adopted.
NFPA 25 is not widely enforced.
NFPA 25 is widely misinterpreted by both
contractors and jurisdictions.
NFPA 25 is widely adopted.
NFPA 25 is not widely enforced.
NFPA 25 is widely misinterpreted by both
contractors and jurisdictions.
![Page 12: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/12.jpg)
The objective of this seminar to create a greater awareness regarding the scope and purpose of NFPA 25
The objective of this seminar to create a greater awareness regarding the scope and purpose of NFPA 25
![Page 13: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/13.jpg)
Let’s take a Look Let’s take a Look
![Page 14: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/14.jpg)
Chapter 1 – AdministrationChapter 2 – Referenced PublicationsChapter 3 – DefinitionsChapter 4 – General RequirementsChapter 5 – Sprinkler SystemsChapter 6 – Standpipe and Hose SystemsChapter 7 – Private Fire Service Mains
Chapter 1 – AdministrationChapter 2 – Referenced PublicationsChapter 3 – DefinitionsChapter 4 – General RequirementsChapter 5 – Sprinkler SystemsChapter 6 – Standpipe and Hose SystemsChapter 7 – Private Fire Service Mains
![Page 15: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/15.jpg)
Chapter 8 – Fire PumpsChapter 9 – Water Storage TanksChapter 10 – Water Spray Fixed SystemsChapter 11 – Foam-Water Sprinkler SystemsChapter 12 - Water Mist SystemsChapter 13 – Valves, Valve Components, TrimChapter 14 - Obstruction InvestigationChapter 15 - ImpairmentsAnnexes/Supplements
Chapter 8 – Fire PumpsChapter 9 – Water Storage TanksChapter 10 – Water Spray Fixed SystemsChapter 11 – Foam-Water Sprinkler SystemsChapter 12 - Water Mist SystemsChapter 13 – Valves, Valve Components, TrimChapter 14 - Obstruction InvestigationChapter 15 - ImpairmentsAnnexes/Supplements
![Page 16: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/16.jpg)
Minimum requirementsWater-based systemsCoordinate with NFPA 72Covers systems installed in accordance with generally accepted practicesNot intended to reveal installation flaws or code of compliance violationsDoes not apply to 13D systems
Minimum requirementsWater-based systemsCoordinate with NFPA 72Covers systems installed in accordance with generally accepted practicesNot intended to reveal installation flaws or code of compliance violationsDoes not apply to 13D systems
![Page 17: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/17.jpg)
Ensure reasonable degree of protection for life and propertyEnsure reasonable degree of
protection for life and property
![Page 18: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/18.jpg)
Chapter 2Chapter 2
![Page 19: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/19.jpg)
Chapter 3Chapter 3
![Page 20: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/20.jpg)
NFPA Official Definitions (3.2)“Approved”“AHJ”“Listed”“Shall”“Should”
NFPA Official Definitions (3.2)“Approved”“AHJ”“Listed”“Shall”“Should”
![Page 21: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/21.jpg)
Inspection (3.3.18)Testing (3.3.34)Maintenance (3.3.20)Qualified (3.3.28)
Inspection (3.3.18)Testing (3.3.34)Maintenance (3.3.20)Qualified (3.3.28)
![Page 22: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/22.jpg)
Chapter 4Chapter 4
![Page 23: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/23.jpg)
Owner shall provide ready access (4.1.1)Owner responsible for maintaining system (4.1.2)Tasks performed by competent personnel (4.1.2.2)Owner shall notify all parties as required before testing or shutting down system (4.1.3)
Owner shall provide ready access (4.1.1)Owner responsible for maintaining system (4.1.2)Tasks performed by competent personnel (4.1.2.2)Owner shall notify all parties as required before testing or shutting down system (4.1.3)
Owner shall make repairs promptly (4.1.4)All tasks to be performed by qualified personnel
(4.1.2.2 and 4.1.4.1)
Owner shall make repairs promptly (4.1.4)All tasks to be performed by qualified personnel
(4.1.2.2 and 4.1.4.1)
![Page 24: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/24.jpg)
Owner shall evaluate all changes to occupancy, use, or materials stored (4.1.5)Where changes occur, owner shall contract with qualified consultant and the AHJ to evaluate systems (4.1.6)Correct any deficiency found (4.1.6.1)
Owner shall evaluate all changes to occupancy, use, or materials stored (4.1.5)Where changes occur, owner shall contract with qualified consultant and the AHJ to evaluate systems (4.1.6)Correct any deficiency found (4.1.6.1)
Owner shall ensure responsible occupants know how to shut system down (4.1.7) Information signs (4.1.8) Note: This is a retroactive requirement!When system is returned to service following an impairment is shall be verified to be working properly (4.2.2)
Owner shall ensure responsible occupants know how to shut system down (4.1.7) Information signs (4.1.8) Note: This is a retroactive requirement!When system is returned to service following an impairment is shall be verified to be working properly (4.2.2)
![Page 25: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/25.jpg)
Made available to the AHJ upon request (4.4.1)Maintained by owner (4.4.3)Original records kept for life of building (4.4.4)Subsequent records kept for a period of one year after next scheduled task (4.4.5)
Made available to the AHJ upon request (4.4.1)Maintained by owner (4.4.3)Original records kept for life of building (4.4.4)Subsequent records kept for a period of one year after next scheduled task (4.4.5)
![Page 26: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/26.jpg)
Performance testing allowed if approved by the AHJ (4.6.1.1.1)If water supplies, including pumps are taken out of service during testing and maintenance impairment procedures must be followed unless under constant attendance by qualified personnel (4.6.3)Test results are compared to original test or most recent test results (4.6.4)
Performance testing allowed if approved by the AHJ (4.6.1.1.1)If water supplies, including pumps are taken out of service during testing and maintenance impairment procedures must be followed unless under constant attendance by qualified personnel (4.6.3)Test results are compared to original test or most recent test results (4.6.4)
![Page 27: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/27.jpg)
Chapter 5Chapter 5
![Page 28: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/28.jpg)
Table 5.1 Summary of Sprinkler System Inspection, Testing, and
Maintenance
Table 5.1 Summary of Sprinkler System Inspection, Testing, and
Maintenance
![Page 29: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/29.jpg)
Inspection of Sprinklers From the floor (5.2.1.1)Omit areas above ceilings (5.2.1.1.4)Condition of sprinklers (5.2.1.1.2)
PaintedCorroded or LoadedDamagedOrientation
Inspection of Sprinklers From the floor (5.2.1.1)Omit areas above ceilings (5.2.1.1.4)Condition of sprinklers (5.2.1.1.2)
PaintedCorroded or LoadedDamagedOrientation
![Page 30: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/30.jpg)
Inspection of Sprinklers Glass bulbs (5.2.1.1.3)Recalled Sprinklers (5.2.1.1.6)Obstructions limited to clearance below the sprinkler (5.2.1.2)
Inspection of Sprinklers Glass bulbs (5.2.1.1.3)Recalled Sprinklers (5.2.1.1.6)Obstructions limited to clearance below the sprinkler (5.2.1.2)
![Page 31: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/31.jpg)
Inspection of Pipe and FittingsFrom the floor (5.2.2)Omit areas above ceilings (5.2.2.3)Condition of pipe and fittings (5.2.2.1)
DamageLeakage and Corrosion
Inspection of Pipe and FittingsFrom the floor (5.2.2)Omit areas above ceilings (5.2.2.3)Condition of pipe and fittings (5.2.2.1)
DamageLeakage and Corrosion
![Page 32: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/32.jpg)
Inspection of Pipe and Fittings
External loads (5.2.2.2)
Inspection of Pipe and Fittings
External loads (5.2.2.2)
![Page 33: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/33.jpg)
Inspection of Hangers and Braces
From the floor (5.2.3)Omit areas above ceilings (5.2.3.3)Condition of hangers and braces (5.2.3.1)
DamagedLoose
Inspection of Hangers and Braces
From the floor (5.2.3)Omit areas above ceilings (5.2.3.3)Condition of hangers and braces (5.2.3.1)
DamagedLoose
![Page 34: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/34.jpg)
Inspection of other componentsSpare sprinklers (5.2.1.3)Gauges (5.2.4.)Buildings for freeze protection (5.2.5)Alarm Devices (5.2.6)Hydraulic Nameplate (5.2.7)
Inspection of other componentsSpare sprinklers (5.2.1.3)Gauges (5.2.4.)Buildings for freeze protection (5.2.5)Alarm Devices (5.2.6)Hydraulic Nameplate (5.2.7)
![Page 35: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/35.jpg)
![Page 36: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/36.jpg)
![Page 37: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/37.jpg)
![Page 38: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/38.jpg)
![Page 39: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/39.jpg)
![Page 40: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/40.jpg)
![Page 41: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/41.jpg)
Testing of componentsSprinklersGauges replaced or tested with calibrated gauge every 5 years (5.3.2)
Testing of componentsSprinklersGauges replaced or tested with calibrated gauge every 5 years (5.3.2)
![Page 42: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/42.jpg)
![Page 43: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/43.jpg)
MaintenanceReplacement sprinklers must have the required characteristics for the application (5.4.1)Only new sprinklers shall be used (5.4.1.2)Dry sprinkler replacement (5.4.1.4.2.1)
MaintenanceReplacement sprinklers must have the required characteristics for the application (5.4.1)Only new sprinklers shall be used (5.4.1.2)Dry sprinkler replacement (5.4.1.4.2.1)
![Page 44: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/44.jpg)
![Page 45: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/45.jpg)
![Page 46: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/46.jpg)
MaintenanceDry pipe systems shall be kept dry at all times (5.4.2)Compressors maintained in accordance with manufacturers instructions (5.4.2.3)
MaintenanceDry pipe systems shall be kept dry at all times (5.4.2)Compressors maintained in accordance with manufacturers instructions (5.4.2.3)
![Page 47: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/47.jpg)
![Page 48: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/48.jpg)
MaintenanceComponent Action Requirements
Table 5.5.1 Summary of Component Replacement Action RequirementsMain drain test required if upstream valves were operated (5.5.1.2)Design review not required
(5.5.1.3)
MaintenanceComponent Action Requirements
Table 5.5.1 Summary of Component Replacement Action RequirementsMain drain test required if upstream valves were operated (5.5.1.2)Design review not required
(5.5.1.3)
![Page 49: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/49.jpg)
All remaining system chapters are organized
in a similar format.
All remaining system chapters are organized
in a similar format.
![Page 50: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/50.jpg)
Chapter 13Chapter 13
![Page 51: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/51.jpg)
Table 13.1InspectionsTestingMaintenance
Table 13.1InspectionsTestingMaintenance
![Page 52: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/52.jpg)
General ProvisionsAll valves shall be protected from damage (13.2.3)Verify for adequate drainage beforeopening valve or drain (13.2.4)
General ProvisionsAll valves shall be protected from damage (13.2.3)Verify for adequate drainage beforeopening valve or drain (13.2.4)
![Page 53: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/53.jpg)
General ProvisionsMain drain test shall be conducted annually (13.2.5)Main drain test shall be conducted quarterly where sole water supply is through a backflow preventer or pressure reducing valve (13.2.5.1)10 percent reduction in residual requires investigation (13.2.5.2)
General ProvisionsMain drain test shall be conducted annually (13.2.5)Main drain test shall be conducted quarterly where sole water supply is through a backflow preventer or pressure reducing valve (13.2.5.1)10 percent reduction in residual requires investigation (13.2.5.2)
![Page 54: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/54.jpg)
CONTROLCONTROL VALVESVALVES
![Page 55: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/55.jpg)
Control ValvesSystems with more than one control valve shall have a sign on each valve referring to the existence and location of the other valves (13.3.1.1) Retroactive
Control ValvesSystems with more than one control valve shall have a sign on each valve referring to the existence and location of the other valves (13.3.1.1) Retroactive
![Page 56: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/56.jpg)
Control ValvesAll valves shall be inspected monthly if supervised or weekly if not (13.3.2.1 and 13.3.2.1.1)All valves must be operated annually (13.3.3.1)Valve supervisory switches shall be tested semi-annually (13.3.3.5.1)
Control ValvesAll valves shall be inspected monthly if supervised or weekly if not (13.3.2.1 and 13.3.2.1.1)All valves must be operated annually (13.3.3.1)Valve supervisory switches shall be tested semi-annually (13.3.3.5.1)
![Page 57: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/57.jpg)
![Page 58: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/58.jpg)
![Page 59: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/59.jpg)
Chapter 14Chapter 14
![Page 60: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/60.jpg)
InspectionInternal inspection at 5 year intervals by opening the end of one main and removing a sprinkler toward the end of one branch line (14.2.1)When uncorrected conditions exist (14.2.2) the system shall receive a four point inspection every 5 years (14.2.3.2)
InspectionInternal inspection at 5 year intervals by opening the end of one main and removing a sprinkler toward the end of one branch line (14.2.1)When uncorrected conditions exist (14.2.2) the system shall receive a four point inspection every 5 years (14.2.3.2)
![Page 61: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/61.jpg)
InspectionPipe passing into freezer or cold storage rooms shall be internally inspected annually (14.3)Alternative nondestructive examinations are permitted (14.2.1.1 and 14.3.1)
InspectionPipe passing into freezer or cold storage rooms shall be internally inspected annually (14.3)Alternative nondestructive examinations are permitted (14.2.1.1 and 14.3.1)
![Page 62: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/62.jpg)
Chapter 15Chapter 15
![Page 63: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/63.jpg)
Coordinator (15.2)Tagging (15.3)Preplanned Impairments (15.5)
Coordinator (15.2)Tagging (15.3)Preplanned Impairments (15.5)
![Page 64: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/64.jpg)
Emergency Impairments (15.6)Restoring the system to service (15.7)
Emergency Impairments (15.6)Restoring the system to service (15.7)
![Page 65: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/65.jpg)
![Page 66: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/66.jpg)
![Page 67: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/67.jpg)
![Page 68: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/68.jpg)
![Page 69: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/69.jpg)
![Page 70: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/70.jpg)
![Page 71: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/71.jpg)
![Page 72: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/72.jpg)
![Page 73: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/73.jpg)
![Page 74: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/74.jpg)
![Page 75: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/75.jpg)
![Page 76: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/76.jpg)
![Page 77: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/77.jpg)
![Page 78: Nfpa 25 Presentation](https://reader031.fdocuments.net/reader031/viewer/2022012315/543f433cafaf9fff098b4632/html5/thumbnails/78.jpg)
Questions and AnswersQuestions and Answers