Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC where art meets engineering NFPA 101 and NFPA 99, 2012 Editions Code Update

Transcript of NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... ·...

Page 1: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC

where art meets engineering

NFPA 101 and NFPA 99, 2012 EditionsCode Update

Page 2: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC

where art meets engineering

NFPA 101 and NFPA 99

Page 3: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

Agenda

• Review Changes to NFPA 101

• Review Changes to NFPA 99

• CMS Waiver Process

• Questions

Page 4: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes

• 2000 edition, CMS adopted March 2003

• 2003 edition, TDSHS adopted into rules

• 2006 edition

• 2009 edition

• 2012 edition, CMS indicates will adopt this

edition, approved categorical waivers based

on this edition

• 2015 edition

Page 5: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Chapter 3 Definitions

• Normally Unoccupied Building Service

Equipment Support Area (2012) 3.3.21.6

• Building Rehabilitation (2006)

– New definitions to support new Ch. 43.

• Fire Glazing (2012)

• Fire-Retardant-Treated Wood (2006) 3.3.107

– Specific definition* Note all code references are 2012 Edition NFPA 101

Page 6: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Chapter 3 Definitions

• Ambulatory HC (2003) 3.3.188.1

– More specific definition of incapacity

• Health Care Occupancy (2009) 3.3.188.7

– Added term inpatient basis

• Multiple Occupancy (2003) 3.3.188.11

– Mixed or separated* Note all code references are 2012 Edition NFPA 101

Page 7: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Chapter 3 Definitions

• Non-Patient-Care Suite (2012) 3.3.272.2

– Suite not for patients, new definition, concept in

2009

• Patient Care Suite (2006) 3.3.272.5

• Patient Care Non-sleeping Suite (2006) 3.3.272.3

– e.g. PACU, treatment

• Patient Care Sleeping Suite (2006) 3.3.272.4

• Stories in Height (2009) 3.3.267* Note all code references are 2012 Edition NFPA 101

Page 8: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Chapter 6 Occupancy

• Multiple Occupancy

– Mixed Occupancy

– Separated Occupancy

• Section 6.1.14.1.2

– Separated occupancies cannot share egress

– If shared, then a mixed occupancy* Note all code references are 2012 Edition NFPA 101

Page 9: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Exit Enclosures

• Structures supporting stairs within wall

– Section 7.1.3.2.1(6)

– Must be protected with same fire resistance

– Added in 2009

• Existing mechanical room openings to stairs -Categorical Waiver

– Section 7.1.3.2.1 (9)

– No storage, no fuel-fired equipment, must be sprinklered

– Changed in 2003* Note all code references are 2012 Edition NFPA 101

Page 10: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Exit Enclosures

• Electrical conduit serving stairs

– Section 7.1.3.2.1 (10)

– Allows communication, PA, security systems in

stairs

– Added in 2009

• Membrane penetrations of exit enclosures

– Section 7.1.3.2.1 (12)

– Added in 2012* Note all code references are 2012 Edition NFPA 101

Page 11: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Doors

• Horizontal Sliding Doors

– Section 7.2.1.4.1(4)(c)

– Allowed for < 10 occupants

– Added in 2006

• Electrically controlled egress doors

– Section 7.2.1.5.6

– Hardware on the door to release door

– Added in 2009* Note all code references are 2012 Edition NFPA 101

Page 12: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes - Locking

• Access Controlled Locks– Section 7.2.1.6.2(5)

– Manual alarms do not have to release locks

– Section 7.2.1.6.2(7)

– Provided with emergency lighting

• Elevator Lobbies– Section 7.2.1.6.3

– List of 14 items including alarm, communication

– Not allowed in new high-rise

– Added 2009* Note all code references are 2012 Edition NFPA 101

Page 13: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Stairs

• Minimum width increase

– Section 7.2.2.2.1.2

– 56 in. minimum when total occupants ≥ 2000

– Added 2006

• Stair Identification

– Section 7.2.2.5.4

– Applies to 3 or more stories for new

– Signage with floor information and level of discharge

– Revised 2006* Note all code references are 2012 Edition NFPA 101

Page 14: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Stairs

• Exit Stair Path Markings

– Section 7.2.2.5.5

– Photoluminescent markings. Not currently

required by any section

– Added in 2009* Note all code references are 2012 Edition NFPA 101

Page 15: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Occupant Load

• Storage in other than storage/mercantile

– Table 7.3.1.2

– Changed from probable load to 500 sf/person

– Changed in 2006* Note all code references are 2012 Edition NFPA 101

Page 16: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Number of Exits

• Electrical Spaces > 600 V

– Section 7.4.2

– Comply with NFPA 70

– Added in 2009* Note all code references are 2012 Edition NFPA 101

Page 17: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Egress Illumination

• Motion Sensor Activated Lighting

– Section 7.8.1.2.2(5)

– New requirement to be activated by fire alarm

– Added 2012

• Lighting in New Stairs

– Section 7.8.1.3.1

– Minimum light 108 lux (10 ft-candle)

– 10 times previous requirement

– Revised 2003* Note all code references are 2012 Edition NFPA 101

Page 18: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Emergency Lighting

• Function testing

– Section 7.9.3.1.1

– This option requires 3 week to 5 week range,

rather than monthly* Note all code references are 2012 Edition NFPA 101

Page 19: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes

• Normally Unoccupied Building Service

Equipment Support Areas

– Section 7.13

– For areas greater than 45,000 sf (non AS) and

greater than 90,000 sf (AS)

• Minimum clear path width 28 in.

• Clear height egress path 6 ft. 8 in.

• Two exits

• Exit signage and lighting* Note all code references are 2012 Edition NFPA 101

Page 20: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Fire Protection

• Fire protection rated glazing marking/label– Section 8.3.3.12

– Requires specific labeling on every glass piece

– Required for wired glass

– Added 2003

• Inspection of Dampers – Categorical Waiver– Section 8.5.5.4.2

– Allows 1 and 6 year interval for dampers (NFPA 80/105)

– Added 2009* Note all code references are 2012 Edition NFPA 101

Page 21: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes - Generators

• Updated Reference to NFPA 110 – Categorical

Waiver

– Section 9.1.3.1

– 2010:110 allows reduction in annual testing times

• Monitored by fire alarm

– Section 9.1.3.2

– Controllers monitored for running, fault, and switch

in non-auto position

– Added 2009* Note all code references are 2012 Edition NFPA 101

Page 22: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Fire Alarm

• Smoke detectors at equipment

– Section 9.6.1.8.1

– Required at FA control unit, NAC power supplies,

transmitting equipment* Note all code references are 2012 Edition NFPA 101

Page 23: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Suppression ITM

• Updated reference document NFPA 25 - 2011

• Categorical Waiver

– Section 9.5

– Reduce to monthly electric fire pump test

– Reduce to semi-annual flow alarm tests* Note all code references are 2012 Edition NFPA 101

Page 24: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Interior Finish

• Existing finish > 1/28 in. – CMS Clarification

– Section 10.2.1.3

– Allows for existing finishes without documentation

– Added 2012

• Bulletin boards, posters, paper

– Section 10.2.5.3

– Allows 20% of wall covering

– Increase from 10% general incidental finish

– Added 2006* Note all code references are 2012 Edition NFPA 101

Page 25: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – High Rise

• Standby Power

– Section 11.8.2.5.4

– Added jockey pump and air compressors for dry

and preaction sprinkler systems to be connected

– Revised 2012* Note all code references are 2012 Edition NFPA 101

Page 26: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Health Care General

• Contiguous Facilities

– Section 18/19.1.3.4.2

– Allows inpatients capable of self preservation to use contiguous facilities

– Added 2012

• Construction Type

– Section 18.1.3.5

– Minimum type is based on entire building height, not just highest HC floor

– Revised 2012* Note all code references are 2012 Edition NFPA 101

Page 27: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – HC Locking

• Security needs locking arrangement – Categorical Waiver– Section 18/19.1.1.1.7

– Section 18/19.2.2.2.5.2

– Allows for locking for security needs where previously only for clinical needs

– List of requirements including complete SD, staff unlocking, FA disabling the locks, power fail safe

– Added 2009

• Delayed Egress– Section 18/19.2.2.2.4(2)

– Removed one lock in a path of egress limitation

– Revised 2009* Note all code references are 2012 Edition NFPA 101

Page 28: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Corridor Width 18/19.2.3.4

• Wall mounted projections – Clarification– 6 in. or less above 38 in.

– Noncontinuous

– Added 2006/Revised 2012

• Wheeled Equipment – Categorical Waiver– Must maintain 5 ft.

– Fire plan to relocate

– Limited to:• Equipment/carts in use

• Emergency equipment not in use

• Lift and transport

– Added 2012* Note all code references are 2012 Edition NFPA 101

Page 29: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Corridor Width 18/19.2.3.4

• Fixed furniture – Categorical Waiver– Min. 8 ft corridor

– Permanently affixed

– 6 ft. clear

– One side only

– Area less than 50 sq ft

– Separated by 10 ft

– Direct supervision or Corridor SD

– Does not block equipment

– Added 2012* Note all code references are 2012 Edition NFPA 101

Page 30: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Exit

• Travel Distance

– Section 18.2.5.3

– Added a common path of travel limitation of

100 ft to an exit access door* Note all code references are 2012 Edition NFPA 101

Page 31: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Suites 18/19.2.5.7

• Construction

– Must meet the requirements of corridor

construction

• Exit Access – Categorical Waiver

– One directly to a corridor

– If two required, can be through another suite

– If two required, can be directly to a stair/exit* Note all code references are 2012 Edition NFPA 101

Page 32: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Suites 18/19.2.5.7

• Travel Distance

– Patient care

• Exit access – 100 ft

• Exit – 200 ft

• No more intervening room limitation

– Non Patient Care

• Based on primary use

• E.g. pharmacy would be 200 ft to exit* Note all code references are 2012 Edition NFPA 101

Page 33: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Suites 18/19.2.5.7

• Size

– Sleeping

• Increase to 7,500 sq ft

• Increase to 10,000 if direct supervision and complete

SD coverage

– Non-sleeping

• 10,000 sq ft

– Non-patient-care

• No limitation* Note all code references are 2012 Edition NFPA 101

Page 34: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Special Hazards

• Cooking Equipment – Categorical Waiver– Section 18.3.2.5

– Added 2012

• Alcohol-Based Hand-Rub Dispensers– Section 18.3.2.6

– Update of previous

• Direct Vent Gas and Solid Fuel Fireplaces –Categorical Waiver– Section 18.5.2.3

– Added 2012* Note all code references are 2012 Edition NFPA 101

Page 35: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Corridors

• Powered Doors– Section 18/19.3.6.3.7

– Do not have to latch if door can hold 5 lbf

– E.g. suite doors

– Added 2009

• Roller Latches– Section 18/19.3.6.9

– Still not allowed except in acute psych settings

– Must maintain hold at 5 lbf

– Added 2012* Note all code references are 2012 Edition NFPA 101

Page 36: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Smoke Compartments

• Mechanical Floors

– Section 18/19.3.7.2(5)

– No smoke barrier required

– 2 hr separation

– Added 2012

• Cross Corridor Single Leaf Door

– Section 18/19.3.7.7

– If not in required means of egress

– Added 2006* Note all code references are 2012 Edition NFPA 101

Page 37: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Operations

• Furnishings/Decorations – Categorical

Waiver

– Section 18/19.7.5

– Allows for curtains

– Combustible decorations

• up to 30% if AS

• Up to 50% in Patient Rooms with AS

– Revised 2012* Note all code references are 2012 Edition NFPA 101

Page 38: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Operations

• Recycle Containers – Categorical Waiver

– Section 18/19.7.5.7.2

– Maximum 96 gal

– FM Approved container

– > 96 gal in rated room

– Added 2012* Note all code references are 2012 Edition NFPA 101

Page 39: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 101 Changes – Existing High-Rise

• Retrofit Sprinkler

– Section 19.4.2

– 12 years to install upon adoption of LSC

– Added 2009* Note all code references are 2012 Edition NFPA 101

Page 40: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 99 – 2012 Changes

• Changed from Occupancy Based

Requirements to Risk-Based

• Eliminated Occupancy Chapters

• Risk to Patient Defined by Category

• New Chapters on IT, Communications

Systems, Plumbing, HVAC, Security

Management, and Features of Fire Protection

Page 41: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 99 – 2012 Changes

• Facility Governing Body to Designate:

– Patient Care Rooms

• Critical Care

• General Care

• Basic Care

• Support

– Anesthetizing Locations

– Wet Procedure Locations

Page 42: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 99 – 2012 Changes

• Med Gas Master Alarm – Categorical Waiver

– Section 5.1.9.2

– Two panels

– Can use computer system for one panel per

5.1.9.4

• Relative Humidity – Categorical Waiver

– Section 9.3.1.1

– ASHRAE 170 2008

Page 43: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

NFPA 99 – 2012 Changes

• Fire Protection Features Chapter 15

– Allows NFPA 30 and 45 to outline requirements

for labs and flammable storage

– Eliminates OR smoke removal

– Eliminates sprinklers in small closets 15.8.1.3

– Recognizes compact mobile storage

Page 44: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

CMS Waivers

• 6-year damper testing

– Memo 10-04-LSC

• Wall mounted projections

– Memo 10-18-LSC

• Exist Interior Finish Documentation < 1/28 in.

– Memo 11-07-LSC

• Wheeled Equipment/Fixed Furniture

– Memo 12-21-LSC

Page 45: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

CMS Waivers

• Kitchen Equipment

– Memo 12-21-LSC

• Fireplaces

– Memo 12-21-LSC

• Furnishings/Decorations

– Memo 12-21-LSC

• Relative Humidity

– Memo 13-25-LSC

Page 46: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

CMS Waivers

• Med Gas Master Alarms

– Memo 13-58-LSC

• Openings in Exit Enclosures

– Memo 13-58-LSC

• Emergency Generator Testing

– Memo 13-58-LSC

• Door Locking

– Memo 13-58-LSC

Page 47: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

CMS Waivers

• Suite Exiting

– Memo 13-58-LSC

• Suppression System Testing

– Memo 13-58-LSC

• Clean/Recycling Waste Containers

– Memo 13-58-LSC

Page 48: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

CMS Waivers - Documentation

• CMS

– Document which waivers using

– Present to Surveyor prior to start of survey

– ASHE recommends letter signed by CEO/Safety Committee

• Joint Commission

– Life Safety Issues documented in electronic BBI

– EC issues (e.g. generators, med gas alarms) documented in Safety Committee meeting minutes

– Notify Surveyor at start of Survey

Page 49: NFPA 101 and NFPA 99, 2012 Editions - HAAHEhaahe.org/images/meeting/010914/haahe_2014_01_09... · NFPA 101 and NFPA 99, 2012 Editions Code Update. Austin Dallas Denver Houston Kansas

Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC

where art meets engineering

Thank You!