Advanced Metering and Communication
• ConstantCalibration™ArchitectureProvidesHighlyStableReadings,astheMeterSelf-calibratesEvery10Seconds
• CriticalMeteringNeedsareMetby0.06%AccuracyinEnergyMetrology
• ColorTouchscreenProgrammableDisplayEnhancestheMeter'sFunctionality
• 6AvailableCommunicationPorts,IncludingDualEthernetPorts
• EthernetPortsOfferSecure,ConfigurablePortServicesControl
• SupportedCOMProtocolsIncludeModbus,DNP3.0,IEC61850,GOOSEMessaging,andSNMP
Superior Recording and Power Quality Analysis
• ClassAIEC61000-4-30PowerQualityMeasurement
• ClassAIEC61000-4-15FlickerMeasurement
• ClassAIEC61000-4-7HarmonicsMeasurement
• SupportsCustomizedEN50160PowerQualityReporting
• Offersupto4GBofMemoryforStorage
• Offers50MHzTransientCaptureSpeed
• ThePerfectMeterforCo-generationandIndependentPowerProviders
• SupportsSubstationAutomation,GridMonitoring,andDistributionSubstationReliabilityMeasurements
Nexus® 1500+ Next Generation Power Quality Meter for Critical Energy Circuits
Introduction
TheNexus®1500+meterisdesignedtobeaprimaryandtestablerevenuemeterthatadditionallyprovidesadvancedpowerqualityanalysisfunctions.Itrecordseveryaspectofelectricalpower,includingpowerqualityandtransients,andgivesyouaccesstothisinformationbothinrealtimeandthroughreportsonthequalityoftheelectricalcircuitincompliancewiththeIEC61000-4-30ClassAandEN50160internationalstandards.Inthisway,theNexus®1500+meterprovidesyouwithacomprehensivepictureofyourcircuits’powerusageandreliability.
TheNexus®1500+meter’scapabilitiesinsurethatessentialdataiscapturedandstored,sothatcriticalinformationaboutimportantelectricalcircuitsisnotlost.Designedwithsuperiorprocessingpowerthatletsitmeasureenergyusageprecisely,largeamountsofmemoryforrecordingevents,andadvancedpowerqualityreportingcompliance,theNexus®1500+meteristheclearchoiceforyourapplicationswherecriticalmeteringisanabsolutenecessity,beitforpowerutility,industrial,orothercriticalmeteringusage.
Highly Accurate Energy Metrology
TheNexus®1500+meterincorporatesoneofthemostadvancedmetrologiesavailableformeasuringenergy.ProvidinghighlyaccuratemeasurementsexceedingtheANSIC12.20(0.2Class)standardandtheIEC62053-22(0.2SClass)standard,the1500+providesanEnergyClassaccuracyof0.06%,withtypicalshippingaccuraciesof0.02%.Additionally,themeterhasahighlyaccuratefrontpaneltestpulsethatletsyoutestononepulseatlowpulseweight,whichyoucanusetoquicklydetermineaccuracy.Themeteralsofeaturesanewprecisionrealtimeclockthatoffersaccuracyof3.5ppm,orlessthan10secondsper
monthdrift.
New Constant Calibration™ Architecture Increases the Stability of Measurement Accuracy
TheNexus®1500+meterimprovesonexistingNexus®architecturebyprovidingoneofthebestauto-calibrationmethodsavailable.EarlierNexus®modelsreliedonAccuMeasure™technologythatauto-calibratedthemeterevery12hoursor5degreetemperaturechange.ConstantCalibration™architectureimprovessignificantlyonthis,byprovidingconsiderablyfaster,ongoingauto-calibration.
WithConstantCalibration™architecture,themeterutilizesaseparatecalibrationchanneltocalibratetheincomingsignalinrealtimeevery10seconds,therebyinsuringthatthemeterexperiencesminimaldriftinaccuracyovertimeandtemperature.Withthisauto-calibratingcircuit,rightoutoftheboxtheNexus®1500+meterwillstabilizeitsreadingswithin10seconds.Thismeansyounolongerhavetowaitforthemetertostabilizeintemperaturetoachieveoptimalaccuracy.WithConstantCalibration™architecture,themeterwillholditsaccuracythroughoutitsoperationrange.Oncethemeteristested,itwillmaintaintheprecise
accuracyeveniftheoperatingconditionsarelessthanideal.
Typical Meter Accuracy Charts
Typical0.02%AccuracyoverFullRange
Notethattypicalaccuracyis0.02%;however,themeterspecificationshouldbe
consultedforaccuracydetails.
MeterMaintainsAccuracyoverChangingTemperature
Typical Accuracy over Current Range Drift over Temperature
2
Advanced Revenue Meter for Primary Loads
TheNexus®1500+unitisaprimaryrevenuemeterdesignedtobeusedforanyimportantapplications.Inadditiontohighlyaccurateenergymeasurement,themeterfeatures:
• Full4quadrantmetering
• Energyloadprofiling:logvirtuallyunlimitedhistoricaltrending
• TimeofUseperpetualcalendarthatsupportsmultipletariffs
• TransformerandLineLosscompensation:forbothironandcopperandtotalsubstationlosses
• CTandPTcompensation:correctforerrorsincurrentandvoltagetransformers
• Coincidentalreadings:e.g.,PForVARsattimeofPeakDemand,toidentifynumberofcapacitorsneeded,peakinefficiencies,etc.
• Loadaggregation/universalmetering:pulseinputscanbeusedtoaggregateoraccumulatedifferentloads;utilityproductssuchasgasandwatercanalsobeaccumulated
System Events Logging
Theunitprovidesextensiveusageinformationfordetectionofunauthorizedaccess.Theunitrecords:
• Resets
• Programmingchanges
• Passwordaccesschanges
• Timechanges
• Powerup/down
• ChangeofFirmware
Test Mode and Energy Presets
TheNexus®1500+meteroffersaTestModefortestingmeteraccuracy.TestModeallowsthemetertobetestedforwatt-hourandVAR-houraccuracywithoutaffectingthestoredreadings.UsingTestMode,userscanverifythemeter’sreadingsoverthelifespanofaninstalledmeterwithouthavingtoresetenergyordisturbtheloadprofilinganddemandrecording.
TheEnergyPresetfeatureallowsausertoprogramtheenergyaccumu-latorvaluesuponexitingTestMode.Thisletstheusercompensateforaccumulationsmissedduringtestingtime,oreasilyswapanewmeterforameterbeingreplaced.
Perpetual Time of Use for Complex Metering
TheNexus®1500+meterusesaperpetualTimeofUse(TOU)calendarthatonlyneedstobesetuponce.TheTOUimplementationallowstheusertosetupmultipletariffstomeetanycontractualobligations.ItalsoallowstheusertocustomizeanyenergyparameterforTOU.The16availableTOUregisterscanbeconfigurednotonlyforTOUbuilt-inenergyreadings,butalsoforanystoreddatafrompulsesorRTUMasterreadingsthatmightneedTOUfunctionality.
3
Class A Power Quality Recorder
EIG’sNexus®1500+meterisoneoftheindustry’spremierfaultandvoltagedisturbancerecorders.Thisinstrumentcapturesandstoresacomprehensivepictureofthehistoryofvoltagereliabilityandpowerqualityevents,fordetailedandextensiveforensicengineeringanalysis.TheNexus®1500+meteroffersamultitudeofpowerqualityfunctionalitythathelpstheuseridentifypowerqualityproblems,includingharmonics,sags,swellsandtransients.Powerqualityfeaturesinclude:
IEC 61000-4-30 Class A Power Quality Meter:
TheNexus®1500+meterisacomprehensiveClassApowerqualityrecorder.DesignedspecificallytomeettherigorousIEC61000-4-30ClassAstandard,itmeasuresandanalyzespowerqualityprecisely.AllreportingisavailableviatheEN50160reportingformat,whichprovidesaweeklyreportofpowerqualityindicessystem-wide.Additionally,thereportcanbefullycustomizedtomeettherequiredapplicationorjurisdictionalneeds.
• IEC61000-4-30Reporting:ClassAReporting–supportsthemoststringentinternationalpowerqualitystandards;theNexus®1500+meteroffersfullreportingofpowerqualityconditionsusingtheIEC61000-4-30ClassAmethodology
• AutomaticgenerationofEN50160reportsandEN50160reportcustomizationtosupportdifferentjurisdictionalrequirements
IEC 61000-4-15 Class A Flicker Meter:
• FlickercompliantwiththeIEC61000-4-15ClassAstandard
• Operatesonboth220volt/50Hzand120volt/60Hzthroughoutstandardtestpoints
IEC 61000-4-7 Class A Harmonics and Interharmonics Analysis:
• Viewharmonicmagnitudestothe511thorderforeachvoltageandcurrentchannel
• Harmonicmagnitudesandphaseanglesinrealtimeareresolvedtothe127thorder
• Obtain%THD,TDD,andK-Factor
• Conductpowerqualityanalysisatthehighendoftheharmonicmagnitudespectrum
Phasor Analysis:
Themonitorreadsaphaseangleanalysisbetweenthevoltageandcurrentchannels,allowingyoutoanalyzeefficiencyandsystemintegrity.
High-speed Voltage Reliability Measurements:
TheNexus®1500+meterprovidesindustryleadingvoltagemeasurement.
• RealtimesinglecycleRMSmeasurements
• Customizablehigh-speedreadings–canbesetfrom2to20cyclesRMS
Easy-to-UnderstandReportsDisplayingPQCompliance
4
Set Limit Control:
TheNexus®1500+powermonitorprovidestheuserwithprogrammablesetpoints.Thisfeatureallowsausertoconfigurethemetertobeusedasacontroldeviceformanyapplications,suchas:
• Capacitorcontrol
• Loadshedding
• Automatictransferschemes
• Transformermonitoring&control
• Redundantprotection(notdesignedforprimaryover-currentprotection)
• Manyothercontrolfunctions
Alarm Notification:
• TheNexus®1500+meterletsyousetmultipleprogrammablelimitsforanymeasuredvalue,aswellasthosesetupinaBooleanlogictree,andlimitssetupintheIEC61850protocolimplementation.Userscanbenotifiedofalarmconditionsviaemail.
16 Bit Waveform and Fault Recorder:
• Recordupto1024samplespercycle;captureatransientatover800,000samplespercycleorat50MHzsamplingspeed
• Voltageandcurrentrecordingwithpreandpost-eventanalysis
• Faultrecordingoffers8timesfullscalecapturecapability
• 16bitA/Dconverterprovidesprecisewaveformresolution
• Bothhardwareandsoftwaretriggersareavailable
High-speed Status Input Triggers:
• Waveformsarerecordedattimeofstatuschange
• Inputchangeandwaveformrecordingaretime-stampedtoa100microsecondresolution
• Inputsandwaveformscanbedisplayedtogethertotimebreakersandrelays
Subcycle 50 MHz Transient Recorder (V3 Option):
Transientsoftencauseintermittent,expensiveperiodsofdowntime.Thesubcycletransientrecorderallowsyouto:
• Recordsubcycletransientsat50MHzresolution
• Monitorswitchingnoisefromcapacitors,statictransferswitches,SCRs,andotherdevicesthatnegativelyimpactpowerquality
Thisfeatureisessentialforcriticalapplicationssuchashospitals,wafer-fabsplants,datacentersandotherhighlypowerqualitysensitiveapplications.Independent ITIC/CBEMA Log Plotting:
• Quicklyviewtotalsurges,sags,andaveragedurationintheindependentITIC/CBEMAlog
• SEMIF47graphingforpowerqualitycomplianceinsemi-conductorindustry
Compatible Waveform Formats
UsingCommunicatorEXT™software,themeterwillprovideallwaveformdataviaCOMTRADEandPQDIFcompatibleformats.ThisallowsthewaveformPQandfaultrecordstobereadbymostthird-partywaveformanalysissoftwareprograms.
• COMTRADE(commonformatfortransientdataexchange)isdefinedbyIEEEStdC37.111
• PQDIF(powerqualitydatainterchangeformat)isdefinedbyIEEEStd1159.3-2003
RecordandAnalyzeWaveformFaultandTransientData
5
Multiport Communication
TheNexus®1500+meteroffersupto6simultaneouscommunicationportsandmultipleprotocolstomeetalmosteveryneed.
Hardware Features:
• 2optionalRS485portsspeakingModbusand/orDNP3.0
• USBfrontpanelport
• ANSIopticalfrontpanelport
• 2separatelyaddressableEthernetports
• OptionalFiberorRJ45mediaononeEthernetport
Ethernet Communication Port Capabilities:
• 2Ethernetportsprovidemultiplesimultaneouscommunication
• EachporthasseparateMACaddressandIPaddress
• SupportsModbusTCP/IP,DNP3.0andIEC61850
• GOOSEmessagingprotocolsupportedforIEC61850
• Upto32ModbusTCP/IPsocketsperEthernetport
• Highlysecureportcontroltodisableunneededservicesandports
• EmailFunction-SMTPemailtoclientonalarm
• PreciseTimeSynchcronization-SNTPTimeSyncprotocol
• FileTransferProtocol-High-speedfiledatatransfer
Industry-Leading DNP 3.0 Level 2 Plus - Complies with DNP Level 1 and Level 2 Certification Requirements:
• Upto136measurements(64BinaryInputs,8BinaryCounters,64AnalogInputs)canbemappedtoDNPstaticpoints
• Upto16relaysand8resetscanbecontrolledthroughDNP
• Report-by-exceptionprocessing(DNPEvents)deadbandswithunsolicitedresponseforserialcommunication
• 250availableevents,infoureventtypes(BinaryInputChange,FrozenCounter,CounterChange,andAnalogChange)
SNMP Protocol:
• SNMPprotocolV1andV2csupported
• 40+measurementssupported
• Trapsforlimits,inputchange,andpowerquality
• ColdStarttrapandAuthenticationFailuresupported
• Perfectfordatacentersandothermanageddevicenetworks
8 Built-in Digital High-speed Status Inputs:
• Inputsautomaticallysensewhetherthecircuitisexternallywetted
• Ifexternallywetted,inputupto150VDCisaccepted
• Ifinternallywetted,themetersuppliesthenecessaryvoltageforthecontolapplication
VAUX Input:
• Neutraltogroundorauxvoltagereadings
• Synchronizingschemes,forexample,obtainingthefrequency,magnitude,andphaseangleonbothsidesofaswitchorbetweengeneratorandbusvoltage
Secure Communication
TheNexus®1500+meteroffers9levelsofpasswordsecuritytoprotectthemeterfromunauthorizeduse.Eachlevelcanbeconfiguredtoenablespecificcapabilities,sothataUtilitycancontrolaccesstofunctionsaccordingtothetypeofuser.Forexample,oneuserlevelisabletocreateandchangeTOUcalendars,whileadifferentuserlevelisabletoreadTOUdata,butnotchangeanything.
HighlyCapableCommunicationOptions6
Substation Automation
V-Switch™keylevelsV2andaboveofferanembeddedIEC61850ProtocolServerforseamlessintegrationwithsubstationautomationapplications.FeaturesoftheNexus®1500+meter’sIEC61850implementationinclude:
• TheIEC61850ProtocolServerallowsupto6simultaneousMMSclients.
• EitherEthernetportcanbeconfiguredforIEC61850(onlyoneportatatimecanrunIEC61850).
• GOOSEpublisher/subscriberfunctionalityissupported.
• Bufferedandunbufferedreportsaresupportedforthefollowingtriggers:generalmeterinterrogation,forexample,thereportisgeneratedinresponsetoaquery;meterintegrity,forexample,thereportisgeneratedaccordingtoaprogrammedinterval;anddatachange,forexample,thereportisgeneratedduetoachangeinthecontentsofadataset.
• Filetransferissupported.
• EmbeddedWebProtocolServersupportisavailableforIEC61850CIDfileuploading,IEC61850ProtocolServerstatusandfordisplayingincomingandoutgoingGOOSEmessages.
• MultipleLogicalNodes,whichmapflicker,harmonics,digitalinputs/outputs,limitstate,voltage,current,energyandotherdata,aresupported.
• WaveformcapturecanbetriggeredbystatusinputdatainsideGOOSEmessages.Theusercanprogramupto16statusinputsthatwilltriggerawaveformcapturewhentheinformationisreceivedviaaGOOSEmessage.Thestatusinputsincludedigitalinputs,limitstates,andanyotherstatusinputsupportedbythemeter.
V-Switch™ Key Technology
TheNexus®1500+meterisequippedwithV-Switch™keyupgradetechnologythatletsyouupgrademeterfunctionalityevenafterinstallation.Thismeansyoucanpurchasewhatyouneednowandthenupgradewheneveryouneedtheadditionalfeatures.FollowingaretheavailableV-Switch™keys:
Feature V1 V2 V3
BasicMeasurements * * *
Memory 512MB 1GB 4GB
SamplingSpeed 512 1024 Upto800,000
50MHzTransients *
EN61000-4-30ClassA
* * *
IEC61850Server * *
IEC61850GOOSE * *
Unique GOOSE Cross Trigger:
• Fault-basedcrosstriggerofwaveformbasedonGOOSEmessage
• Providessystem-widedistributionfaultanalysisonanevent
• Timingbetterthan200microsecondsistypical
• Manydifferentcircuitscanbeviewedafteraneventoccured
IntelligentSubstationIEC61850DesignCrossTriggerFaultReadingsforSimultaneousStation-wideFaultAnalysis
7
The Meter of Choice for Critical Energy Measurement
DesignedforusebetweentwoutilitytiepointsorforcriticalSCADAdata
8
Internal I/O
Pulse Outputs:
485P:DualRS485/PulseOutputCard
• 4KYZpulses-SolidState
• Pulsewidth:5ms
• TwoRS485ports
Relay Outputs:
6RO1:6RelayOutputCard
• 5A,250VAC/30VDC
• FormC(Latching)
Digital Input Status:
16DI1:16StatusInputsCard
• Usedforalarmdetectorpulseaccumulation
• Upto150VDCwettedornon-wetted(24VDCinternallyprovided)
Note: TheNexus®1500+meterprovidesoneI/Oslotforthe485P(Slot1),andtwoI/Oslotsforthe6RO1and16DI1(Slots3and4).
External I/O
Analog Outputs:
• 1mAON4/1mAON8:4or8AnalogOutputs,0-1mA,self-powered,scalable,bidirectional
• 20mAON4/20mAON8:4or8AnalogOutputs,4-20mA,self-powered,scalable
• Wiring:CommonMode
• Accuracy:0.1%ofFullScale
• Calibration:Self-calibrating
• Scaling:Programmable
• Ordering:Upto4AnalogOutputmodules
Analog Inputs:
• 8AI1:8AnalogInputs,0±1mA
• 8AI2:8AnalogInputs,4-20mA
• 8AI3:8AnalogInputs,0±5VDC
• 8AI4:8AnalogInputs,0±20VDC
• Wiring:CommonMode
• Accuracy:0.25%ofFullScale
• Scaling:Programmable
• Ordering:Upto4AnalogInputmodules
Digital Dry Contact Relay Outputs:
• 4RO1:4RelayOutputs,5A,250VAC/30VDC,Form-CLatching
• Ordering:1moduleinadditiontointernalmodules
Digital Solid State Pulse Outputs:
• 4PO1:4SolidStatePulseOutputs,FormAorCKYZpulses
• MaximumPulseSpeed:20pulsespersecond
• Ordering:Upto4DigitalSolidStateOutputmodules
I/O Module Accessories (Required):
• PSIO:PowersupplyrequiredwhenusinganexternalI/Omodule.TheNexus®1500+meterdoesnothaveinternalpowerforexternalI/Omodules.
• MBIO:MountingbracketforexternalI/Omodules.MustbeorderedwithexternalI/Omodule.
Expandable Inputs and Outputs to Extend Measurements
ExpandableExternalI/OModules
9
TheNexus®1500+meterfeaturesanLCDcolordisplaywithtouchscreencapability.ThedisplayusesbrightTFTglasswithahightempera-tureandlonglifeLEDbacklight.LEDissuperiortoCCFLsolutionsduetobettertemperatureandhalf-lifespecifications.Screendisplaysinclude:
• Real-timeviewing(voltage,current,power,demand)
• Accumulatedenergyandtimeofusereadings
• Flickerreadings
• Alarms
• PhasorAnalysis
• Harmonicspectrumanalysisandwaveforms
• Realtimetrending
• Logstatus
• Configurationsettings
• Multi-languagesupport
• Digitalstatusinputs
VaVbVcVnVaux
N/U
CTs
CBA
CBA
Vc
Vb
Va
VaVbVcVnVaux
N/U
CTs
Vc
Vn
Va
PTs
NCBA
NCBA
NCBA
NCBA
VaVbVcVnVaux
CTs
N/U
Vn
Vc
Vb
Va
NCBA
NCBA
VaVbVcVnVaux
Vn
Vc
Vb
Va
PTs
CTs
N/U
Earth Ground
Earth Ground
Earth Ground
CTShortingBlock
Earth Ground
CTShortingBlock
Earth Ground
CTShortingBlock
*
Earth Ground
CTShortingBlock
*
Wiring Diagrams
4-WireWye,2.5Element,3CTsand2PTs
VividColorDisplay
4-WireWye,3Elementwith4CTsand3PTs*Note:OptionalCTforCurrentMeasurementOnly
3-Wire,2ElementDeltaDirectwith2CTs
4-WireWye,3Elementwith4CTsandnoPTs*Note:OptionalCTforCurrentMeasurementOnly
Vibrant LCD Touch Screen Display
10
Specifications
Voltage Input Range:
• (5-347)VAC,LinetoNeutral
• (10-600)VAC,LinetoLine
Voltage Input Withstand Capability:
• VoltageInputsisolatedto2500VAC
Current Input Range:
• ProgrammabletoanyCTratio
• Class2:Nominal1A,with2timesoverrange
• Class2:faultcurrentrecordingto+/-16Apeak
• Class20:Nominal5A,with4timesoverrange
• Class20:faultcurrentrecordingto+/-80Apeak
Current Input Withstand Capability (at 23°C):
• 100Afor10seconds
• 300Afor3seconds
• 500Afor1second
Burden:
• VoltageInputs:0.072VA/phasemaxat600volts,0.003VA/phasemaxat120volts
• CurrentInputs:0.008VAperphasemaxat20A
Isolation:
• Allinputstooutputsareisolatedto2500VAC
Temperature Rating:
• Operatingtemperature:(-20to+70)°C
• Storagetemperature:(-30to+80)°C
• Humidity:Upto95%RHnon-condensing
Sensing Method:
• Upto1024samplespercycle(programmable)
• 16BitA/Dresolution–multipleconverters
• ConstantCalibration™technology
• TrueRMS
• Transientat50millionsamplespersecond
Accuracy Rating:
• Energymeasurementaccuracyat0.06%
• FullaccuracyspecificationsavailableinNexus®1500+meterUserManual
• Timeclock:3.5ppmfor-40to+85°C-lessthan10secondsdriftpermonthoncrystalsync;2.0ppmTypicalfrom0-+40°C-lessthan6secondspermonthdrift
Update Time:
• 1Second-Revenueaccuratereadings
• 1Cycle-Fasterupdatedreadings
• Customizablehigh-speedreadings-from2to20cyclesRMS
Control Power Requirements:
• D2Option:(100–240)VAC@50/60Hzor(100-240)VDC
• 115ACOption:(100-240)VAC@50/60Hz
• DOption:(18-60)VDC(24-48VDCSystems)
• Burden:25VAMax
Frequency Range:
• 45Hz–69.9Hz
Communication:
• Programmableparityandstopbits
• Communicationprotocols:ModbusTCP/IP,ASCII/RTU;DNP3.0;IEC61850(V2andabove),SNMP
• ANSIopticalport
• USB1.1/2.0VirtualCOMport
• RJ45Ethernetport10/100BaseT
• Optional2ndEthernetport-RJ45orFiberOptic
• 2RS485ports(optional)
Shipping:
• Totalshippingweight:approx.6.5lbs(2.9kgs)
• Shippingcontainerdimensions:16"x15.5"x11.5"(40.64amx39.37cmx29.21cm)
Compliance:
• ANSIC12.20(0.2Class)andIEC62053-22(0.2SClass)Accuracy
• ANSIC12.1(CodeforElectricityMetering)
• ANSIC62.41(Burst)
• ANSI/IEEEC37.90.1–SurgeWithstand
• FCCPart15,SubpartB,ClassA
• IEC61000-4-2–ESD
• IEC61000-4-3–RadiatedImmunity
• IEC61000-4-4–FastTransient
• IEC61000-4-5–SurgeImmunity
• IEC61000-4-6-ConductedImmunity
• IEC61000-4-7–Harmonics
• IEC61000-4-15–FlickerMeter
• IEC61000-4-30–ClassA
• IEC62052-11-GeneralRequirements
• IEC/CISPR14-1-ContinuousEMDisturbance
• CEMarked
• ULandcULListed
External I/O Modules
• 1mAON4:4AnalogOutputs,0±1mA
• 1mAON8:8AnalogOutputs,0±1mA
• 20mAON4:4AnalogOutputs,4-20mA
• 20mAON8:8AnalogOutputs,4-20mA
• 8AI1:8AnalogInputs,0±1mA
• 8AI2:8AnalogInputs,4-20mA
• 8AI3:8AnalogInputs,0±5VDC
• 8AI4:8AnalogInputs,0±10VDC
• 4RO1:4RelayOutputs
• 4PO1:4SolidStatePulseOutputs
• PSIO:PowerSupplyforI/Omodules(mustbeorderedwithexternalI/Omodule)
• MBIO:I/Omountingbracket(mustbeorderedwithexternalI/Omodule)
Note:PleaseseeproductUserManualforcomprehensivespecifications.
Wiring Diagrams
Front Side Back
Dimensional Drawings
4.44”[11.28cm
]
7.6”[19.30cm]
5.94” [15.09cm]
4.44” [11.28cm]
5.04”[12.80cm]
5.73”[14.55cm]
1.87”[4.75cm]
10.74”[27.28cm]
6.96” [17.68cm]
6.74” [17.12cm]
11
To order a Nexus® 1500+ meter:
• Fillouttheoptionsyouwantintheorderchartshownbelow:listaccessoriesseparately.
• SpecifyCommunicatorEXT™4.0software.
• EIGcanalsoprovidecurrentandpotentialtransformers.
• Emailorfaxorderinformationandquantitytotheemailaddressorfaxnumberlistedbelow,orcallthephonenumberlistedbelowtoplaceyourorder.
About Electro Industries: ElectroIndustries/GaugeTechisoneoftheoldestandlargestmanufacturersofmicroprocessor-baseddigitalpowermetersintheUnitedStates.EIG'ssuccessisattributabletoourwillingnesstosupportouruserswithon-stafftechnicalexpertise.Contactusandwewillassistyouinsolvingyourcomplexmeteringapplications.
Nexus® 1500+ web page:http://electroind.com/product-info/nexus-1500_plus-next-generation-power-quality-revenue-meter/
1800ShamesDrive,Westbury,NY115901-877-EIMETER(1-877-346-3837)
Tel:516-334-0870Fax:516-338-4741Email:[email protected]
Ordering InformationNexus®
Base MeterControl Power
Frequency Range
Current Class
Virtual Switch
Communication Expansion/Slot 1
I/O Slot 2
I/O Slot 3
I/O Slot 4
Option Numbers:
Example: Nexus 1500+ D2 60 20 V2 485P NTRJ 6RO1 6RO1
Nexus® 1500+ Meter
115AC (100-240)VAC@50/60Hz
60 60Hz
2020A
V1Standard
Nexus®1500+Meter512MBmemory/512s/c
XNoOption
XNoOption
XNoOption
XNoOption
D2Universal
(100-240)VAC@50/60Hz
or(100-240)VDC
50 50Hz
22A
V2V1+1GBmemory/
1024s/cIEC61850
485P2RS485and4PulseOutputs
NTRJSecondRJ45NetworkCard
6RO16RelayOutputs
6RO16RelayOutputs
D(18-60)VDC
V3V2+4GBmemory/
50MHzTransientRecording
NTFOSecondFiberNetworkCard(STterminated)
16DI116StatusInputs
16DI116StatusInputs
Accessory OptionsSoftware
COMEXT4P1Y CommunicatorEXT™4.0SoftwareforWindowsSingle-ComputerLicense(OneSite)
I/O Modules
1mAON4 1mAON8 20mAON4 20mAON8 8AI1 8AI2 8AI3 8AI4 4RO1 4PO1
4AnalogOutputs,0±1mA8AnalogOutputs,0±1mA4AnalogOutputs,4-20mA8AnalogOutputs,4-20mA8AnalogInputs,0±1mA8AnalogInputs,4-20mA8AnalogInputs,0±5VDC8AnalogInputs,0±10VDC4RelayOutputs4SolidStatePulseOutputs
*PSIO
*MBIO
PowerSupplyforExternalI/OModulesI/OMountingBracket
*MustbeorderedwithanexternalI/Omodule.
- - -- -- - -
- - -- -- - -
Electro Industries/GaugeTech™The Leader in Power Monitoring and Smart Grid Solutions™
E154718050918V.1.06