Location and Design Data

North Vancouver: “high earthquake, wind and rain”

Climatic Design Data (Per BCBC 2012)• Ground Snow Load: Ss=3 KPa, Sr=0.3 KPa Plus snow built up

where applicable• Hourly Wind Pressure: 0.35kPa (1/10) and 0.45kPa (1/50)

Structural Plan

Lateral load resisting system: SCL core + CLT moment frame (“Strong column-weak beam” balloon-frame)

Gravity resisting system: CLT roof / floors SCL core + CLT moment frame + post-beam frame

Seismic force modification factors: Rd = 2.0 and R0 = 1.5

Connection: HBV wood concrete or HSK hold downs

Structural Scheme

Wind Induced Response

Structural integrity (building structure check and component & cladding check) under ultimate wind loads (1/50, ULS)

Serviceability under service wind loads (1/10) with serviceability criteria (inter-story drift limit = 1/500, SLS)

Building motions and occupant comfort (cross-wind acceleration aw and along-wind acceleration aD)

6

Wind Design Parameters

Pressure CoefficientCp=0.8 for windward wallsCp=0.5 for leeward walls

Internal Pressure CoefficientCpi=-0.45~0.3 Category 2

Exposure B(rough exposure, urban and suburban areas)Ce=0.5(h/12.7)0.5

Cg Gust effect factor calculated by Dynamic procedure

Wind Induced Response

Estimated fundamental frequency 0.25Hz < fn < 1Hz; therefore, Dynamic Procedure is required to calculate gust effect factor.

P=IwqCeCgCp and Pi=IwqCeCgiCpi

Calculations of Ce , Cg , Cp and Cpi follow “NBCC Structural Commentary I Wind Load and Effects”.

Sufficient lateral stiffness is needed to satisfy the drift limit criteria.

8

Beam188 elements (glulam, steel beams and columns);

Shell181 elements (floor diaphragms and shear walls);

Pinned connections;

Combin39 nonlinear springs (for hold-downs, shear connections panel-panel contacts, under development…)

Numerical Models

9

10

Fig. I-16 Full and partial wind loads for building structure(NBCC 2010 Structural Commentary)

11

Level q (kPa)Cp(windward)

Cp(leeward)

Ce(static method) Cg(static) fi (kN)

2 0.45 0.8 -0.5 0.64 2 863 0.45 0.8 -0.5 0.70 2 944 0.45 0.8 -0.5 0.75 2 1015 0.45 0.8 -0.5 0.79 2 1066 0.45 0.8 -0.5 0.83 2 1117 0.45 0.8 -0.5 0.86 2 1168 0.45 0.8 -0.5 0.89 2 1209 0.45 0.8 -0.5 0.92 2 124

10 0.45 0.8 -0.5 0.95 2 12811 0.45 0.8 -0.5 0.97 2 13112 0.45 0.8 -0.5 1.00 2 13413 0.45 0.8 -0.5 1.02 2 13714 0.45 0.8 -0.5 1.04 2 14015 0.45 0.8 -0.5 1.06 2 14316 0.45 0.8 -0.5 1.08 2 14517 0.45 0.8 -0.5 1.10 2 14818 0.45 0.8 -0.5 1.12 2 15019 0.45 0.8 -0.5 1.13 2 15320 0.45 0.8 -0.5 1.15 2 155

Wind Load (ULS)

12

Roof drift 89 mm (1/640)

Max. Inter-story drift4.8 mm (1/625)

Building Deformations(ULS, Case A)

13

Stresses in LSL Shear Walls (ULS)

14

Bending Stresses in Steel Link Beams

15

Bending Stresses in Glulam Beams & Columns

16

Lowest Natural Frequency = 0.467 Hz for Dynamic Procedure

Calculation of gust effect factor Cg

Calculation of aw and aD related to building vibrations under serviceability limit state