architectural drawing indexcover set
plans set
elevations set
sections set
details set
interior elevation set
schedules
A1.0A1.1A1.2A1.3
A2.1
A3.1A3.2A3.3
A4.1A4.2A4.3
A5.1
A7.1A7.2
COVER + INDEX
SITE & SLAB PLANGROUND & FIRST FLOOR PLANSECOND FLOOR & ROOF PLANREFLECTED CEILING PLANS
ELEVATIONS
SECTIONS A & BSECTION CSECTIONS D & E
DETAILSDETAILSDETAILS
INTERIORS - BATHROOM
DOOR & WINDOW SCHEDULEDOOR & WINDOW SCHEDULE
NE W OFF ICE BUIL D ING307 D UR HA M ST REET
4643file:
BUIL D ING C O NS E NT ISSUE14 Nov 2013date:
N E W O F F I C E B U I L D I N G3 0 7 D U R H A M S T R E E T
SITE & SLAB PLAN15/03/2013
4643
TH
A1.0
PR
ELI
MIN
AR
Y P
RIN
T | 1
4/11
/13
| 3:4
5 P
M
14.04 m2
N1 3
C
A
22,695 BOUNDARY3,990
12,0
80 B
OUND
ARY
40,510 BOUNDARY
12,3
70 B
OUND
ARY
3,600 2,500 2,500 2,850
5,0
00
3,100 21,400 2,160 13,850
3,0
50
8,7
90
75
15
01
,80
0
6.73 m2
3 12
staff coveredcycle stand(5no. min)
visitorcycle stand(2no. min)
SCALE: 1:100proposed site plan
EXISTING MAGNOLIA TREE TO REMAIN,LOCATION TO BE CONFIRMED ONSITE
exis
ting
vehi
cle
cros
sing
EX. SEWER DRAIN
PRECAST CONCRETE COLUMN
FINAL LOCATION DETERMINEDBY DRAINAGE ENGINEER
du
rh
am
st
re
et
BUILDING SET OFF 75mm ATCLOSEST POINT
120/120/120 FFR WALLS TO BOTHNORTH & SOUTH BOUNDARIES
EXPOSED AGGREGATE PATH
EXPOSED AGGREGATE TO FALLSUP TO ENTRANCE DOORTHRESHOLD
H5 TREATED 200x200 TIMBERKERB AS TREE SURROUND
GALVANISED 3.5m LONG x 400mmHIGH BOUNDARY RAIL FROM 100mmPFC FOR PAINT FINISH
EXPOSEDAGGREGATE PATH
FALLSUMP
FALLFALL
FALL
FALL
ASPHALT TO CARPARKFALLS TO SUMP
FALL
FALL
g a r d e n b e d
ga
rd
en
be
d
BFPHT
BUC
rail 1 rail 2 rail 3
rail
4ra
il 5
CL
FALL
DP1
DP2
DP4
2
B
SITE AREA: 490.28 m2
252.64 m2
1.58 m2
ne w building
LIFT SUMP
BUILDING TO BE PARALLELAND OFF-SET 75mm FROMTHE SOUTH BOUNDARY
EDGE OF EXPOSED AGGREGATEPAVING 150mm OFF BOUNDARY
CRITICAL SET-OUT NOTE
DC
DC
DP3
EXPOSED AGGREGATE 50mm MESHREINFORCED PAVING
ASPHALTIC CONCRETE (HOTMIX)DRIVE AS SPECIFIED WITH 100x35H5 TREATED TIMBER EDGE ORCONCRETE KERB
site/ locat ion key
NEW BUILDING FOOTPRINT
EXISTING SITE LEVELS, AS PERSURVEYORS DOCUMENTATION
PROPOSED SLAB LEVEL, FINISHED HEIGHT
PROPOSED SITE LEVEL, FINISHED HEIGHT
1. REFER STRUCTURAL ENGINEER FORGEOTECH REPORT
2. REFER ENGINEERS DOCUMENTATION FORSITE SURVEY
3. TREES SHOWN SHALL REMAIN AND BEPROTECTED AS NECESSARY
4. STOCKPILE TOPSOIL AS DIRECTED ON SITE
5. REFER LANDSCAPE ARCHITECT FORPLANTING, SOFT LANDSCAPING ANDANCILLARY PAVING
6. REFER DRAINAGE/HYRAULIC ENGINEERSDOCUMENTS FOR ALL STORMWATER ANDSEWER DRAINAGE
7. REFER SITEWORK SPECIFICATION
site/ locat ion plan notes
SITE FENCE
BFP BACK FLOW PREVENTER, REFERHYDRAULIC/DRAINAGE ENGINEERDOCUMENTATION
BUC BUBBLE-UP CHAMBER, REFERHYDRAULIC/DRAINAGE ENGINEERDOCUMENTATION
HT HOSE TAP, REFER HYDRAULIC/DRAINAGEENGINEER DOCUMENTATION
0.00
0.00 FFL
0.00
property address: 307 DURHAM STREET,CHRISTCHURCH
legal description: LOT 1, DP 9537
property area: 491m²
site inf or mat ion
RAIL 1, RAIL 2, RAIL 3, RAIL 4, RAIL 5 (5 OFF)
3,500 200
60
01
50
40
0
40
0
400 700
100mm ZINC SPRAYED PFC RAILAND LEGS
MITRE AND WELD RAIL AND LEGS
400x700x600 CONCRETEFOOTING
APPROX. (C.O.S.)
400x400x600 CONCRETEFOOTING
NO.
HARDWARE
FINISH
CONSTRUCTION
NOTES
LOCATION SITE CARPARK
LATCH & LOCKSET, LEVER HANDLE, DOOR CLOSER,RAVEN THRESHOLD BAR FOR LEVEL THRESHOLD
RAILS 1-3 INSTALLED WITH TOES FACING CARPARK,RAILS 4-5 INSTALLED WITH TOES FACING STREET
ZINC SPRAYED
100mm PFC RAIL AND LEGS SET IN CONCRETE FOOTINGCHECK LEVELS ON SITE PRIOR TOFABRICATION
-- SCALE 1:50
b o u n d a r y r ail de t a i l
bo unda r y rail s c hedule
SL1:100,1:50@A21:200@A4
A 13/11/13 BUILDING CONSENT ISSUE
A
N E W O F F I C E B U I L D I N G3 0 7 D U R H A M S T R E E T
GROUND & FIRST FLOORPLAN
15/03/2013
4643
TH
A1.1
PR
ELI
MIN
AR
Y P
RIN
T | 1
4/11
/13
| 3:4
5 P
M
GFA: 252 m2
N1 3
C
A
1234567
22,695 BOUNDARY3,990
12,0
80 B
OUND
ARY
40,510 BOUNDARY
12,3
70 B
OUND
ARY
2,400 3,600 2,500 2,500 2,8503,100 4,475 4,900 3,400 900 600 4,900 4,385
3,2
50
5,9
60
2,6
30
20
04
51
,11
09
01
,39
09
0
20
04
52
,59
09
08
,67
04
52
00
140 25 5,280 90 1,950 90 1,55045
200 1,775200
25 1,850 90 3,500 90 4,050 90 355 1,960
90 9,580 45 400
90 3,500 90
20
01
,60
02
,00
07
,04
08
00
20
0
30045
25 8,960 45300
45 11,435 45 400 1,960
20
02
,07
52
00
50
56
,25
02
,41
02
00
11
,84
0
3,100 21,400 2,160 13,850
3,0
50
8,7
90
75
1,5
00
3,5
00
1,800
FFL 15,560
AA3.1
AA3.1
CA3.2
CA3.2
EM CT
CT
V
V
W0.1
D0.
6
D0.
7
D0.5
D0.
2
W0.
3 W
0.2
D0.
3
D0.4
810
810
710
gr ound f loort enanc yent r ance
upper f loorst enanc yent r ance
SMOKE CURTAIN TO LIFT DOORS(TYPICAL)
650
STORE (UNDER STAIR)
exis
ting
vehi
cle
cros
sing
350 Ø PRECAST CONC COLUMN
800 x 400 PRECAST BUTTRESS
2000 x 400 PRECAST PANEL
CONC
BEA
M O
VER
SUNS
HADE
LOUV
RES
OVER
du
rh
am
st
re
et
SCALE: 1:100proposed gr ound f loor plan
BUILDING SET OFF 75mm ATCLOSEST POINT
lif t
t enancy 1
store(under )
120/120/120 FFR WALLS TO BOTHNORTH & SOUTH BOUNDARIES
1.8
m H
IGH
TIM
BER
FENC
E
810
910
910
650
FRR DOOR
LINE OF STRUCTURE OVERSHS POST
SHS POST
2400 x 400 SHEARWALL
SHS POST
SUMP
g a r d e n b e d
ga
rd
en
be
d
BFPHT
BUC
rail 1 rail 2 rail 3
rail
4ra
il 5
CL
CONCRETE FILLED STRUCTURAL 200SHS POST WITH INTUMESCENT PAINTFIRE PROTECTION TO ACHIEVE120min FIRE RATING
CONCRETE FILLED STRUCTURAL 100SHS POST WITH INTUMESCENT PAINTFIRE PROTECTION TO ACHIEVE120min FIRE RATING
FRR WINDOW DP1
DP2
DP4
2
B
5A4.1
6A4.1
1A4.1
2A4.1
4A4.1
8A4.3
10A4.3
2A4.3
1A4.3
6A4.3
7A4.3
BA3.1
BA3.1
DA3.3
DA3.3
EA3.3
EA3.3
SITE AREA: 490 m2
D0.
1
LIFT SUMP
TEA
SINK
BUILDING TO BE PARALLELAND OFF-SET 75mm FROMTHE SOUTH BOUNDARY
w clobby
ac cw c
w cent r ylobby
CRITICAL SET-OUT NOTE
DC
DC
similar
REFER INTERIOR ELEVATIONSSHEET A5.1 FOR WC ANDKITCHENETTE DETAILS
DP3
0 1 2 3 4 5
1 3
C
A
171819
20 21 22 23 24 25 26 27 28 29
3031323334
AA3.1
AA3.1
CA3.2
CA3.2
140 5,305 90 1,950 90 1,55045
200 1,775200
25 5,735 90 6,160 90
4,475 4,900 4,900 4,900 4,385 90
20
04
52
,69
09
0
20
04
59
50
90
1,6
50
90
20
02
,07
52
00
95 70 9,005 300 13,885 90
4,2
60
4,9
50
2,6
30
4,475 4,880 20 3,400 900 580 20 4,880 20 4,385 90
20
08
00
9,8
40
80
02
00
11
,84
0
45
2,4
00
20
0
20
02
,07
52
00
50
56
,26
02
,40
02
00
11
,84
0
400 1,960
20
04
52
,59
09
0
3,100 21,400 2,160
75
3,0
50
8,7
90
17
5
FFL 18,860
CT
CT
V
V CT
W1.
8
D1.
4
D1.
5
D1.3
W1.
6 W
1.5
W1.
7
W1.
1 W
1.2
W1.
3
W1.4
D1.1
810
710
810
r a isedplat f orm
810LINE OF STRUCTURE OVER
EXTERNAL METAL CLAD SILL
800 x 400 PRECAST BUTTRESS
BEAM
OVE
R
SUNS
HADE
LOUV
RES
OVER
lif t
t enancy 2
SCALE: 1:100proposed f irst f loor plan
810
FRR DOOR SMOKE DOOR
SHS POST
SHS POSTSHS POST
2400 x 400 SHEARWALL
800 x 400PRECASTBUTTRESS
CL
DOUBLE INSOL SOLARIS FINS
CONCRETE FILLED STRUCTURAL 200SHS POST WITH 2x19mm FYRELINEWALL LININGS AS FIRE PROTECTIONTO ACHIEVE 120min FIRE RATING
CONCRETE FILLED STRUCTURAL100 SHS POST WITHINTUMESCENT PAINT FIREPROTECTION TO ACHIEVE120min FIRE RATING CONCRETE FILLED STRUCTURAL 200
SHS POST WITH INTUMESCENT PAINTFIRE PROTECTION TO ACHIEVE120min FIRE RATING
FRR WINDOW DP1
DP2
DP4
2
B
BA3.1
BA3.1
DA3.3
DA3.3
EA3.3
EA3.3
8A4.3
10A4.3
2A4.3
1A4.3
1A4.3
9A4.2
GFA: 279 m2
w clobby
ac cw c
w c
TEA
SINK
lobby
171819 16
similar
REFER INTERIOR ELEVATIONSSHEET A5.1 FOR WC ANDKITCHENETTE DETAILS
DP3
V
EM
CT
f loor plan key
FIRE RATED WALL, REFER FIREENGINEERS REPORT.FIRE RATED CONSTRUCTION TO EXTEND TOSOFFIT OR UNDERSIDE OF ROOFCLADDING, NOTCH AROUND ROOFFRAMING AND SEAL ALL AROUND WITHINTUMESCENT SEALANT
STRUCTURAL PRECAST CONCRETE PANEL,REFER STRUCTURAL ENGINEERSDOCUMENTATION
45x70 H3.2 TIMBER STRAPPING
90x45 H3.2 TREATED MSG8 TIMBERFRAMED WALL
140x45 H3.2 TREATED MSG8 TIMBERFRAMED WALL
OVERHEAD EAVE LINE
SELECTED VINYL FLOOR FINISH
SELECTED ENTRANCE MAT FLOOR FINISH
SELECTED CARPET TILE FLOOR FINISH
DOOR REFERENCE BY NUMBER, REFERDRAWING SERIES A7, WHERE;DG. - GROUND FLOOR DOORD1. - FIRST FLOOR DOORD2. - SECOND FLOOR DOOR
DG.#
D1.#
D2.#
JOINERY UNIT REFERENCE BY NUMBER,REFER DRAWING SERIES A6
J#
WINDOW REFERENCE BY NUMBER, REFERDRAWING SERIES A7, WHERE;DG. - GROUND FLOOR WINDOWD1. - FIRST FLOOR WINDOWD2. - SECOND FLOOR WINDOW
WG.#
W1.#
W2.#
OVERFLOW SCUPPER OUTLETSOFS
f loor f inishes key1. FLOOR FINISHES ONLY WHERE INDICATED
SL
1:100@A21:200@A4
A
A 13/11/13 BUILDING CONSENT ISSUE
N E W O F F I C E B U I L D I N G3 0 7 D U R H A M S T R E E T
SECOND FLOOR & ROOFPLAN
15/03/2013
4643
TH
A1.2
PR
ELI
MIN
AR
Y P
RIN
T | 1
4/11
/13
| 3:4
5 P
M
GFA: 280 m2
REFER INTERIOR ELEVATIONSSHEET A5.1 FOR WC ANDKITCHENETTE DETAILS
1 3
C
A
24 25 26 27 28 29
303132333435363738
AA3.1
AA3.1
CA3.2
CA3.2
20
04
52
,69
09
0
20
04
59
50
90
1,6
50
90
20
02
,07
52
00
1,600 140 3,910 90 1,950 90 1,30590 200
200 1,775200
25 11,525 140320
90
4,455 20 4,880 20 4,880 20 4,880 20 4,385 90
20
03
,05
05
,96
02
,43
02
00
20
08
00
9,8
40
80
02
00
2,6
35
14
0
20
04
52
,59
01
40
4,475 4,880 20 3,400 900 580 20 4,880 20 4,385
1,670 3,980 5,800 5,950 5,800 360
20
02
,07
52
00
9,1
65
20
0
11
,84
0
4,455 20 4,880 20 4,880 20 4,880 20 4,385
75
3,0
50
8,7
90
17
5
11
,84
0
21,400 2,160
FFL 22,160
CT
CT
V
V CT
W2.4
D2.
4
D2.
5
W2.
1 W
2.2
W2.
3
D2.3 W
2.6
W2.
5
D2.
1
D2.2
810
810
710
810
CANTILEVER POST AND GLASSBALUSTRADE WITH SQUARE TOPHANDRAIL AS SPECIFIED.
140 FRAMING
EXTERNAL COLORSTEEL ONPLY SILL
36
0 U
B PO
RTAL
NOTE - EXTENT OF PANELREDUCED BY 90mm TOALLOW FRAMING TO EXTEND
36
0 U
B PO
RTAL
36
0 U
B PO
RTAL
36
0 U
B PO
RTAL
20
0 U
B +
25
0 P
FC B
EAM
380 PFC BEAM
380 PFC BEAM
140 FRAMING
lif t
t enancy 3
SCALE: 1:100proposed second f loor plan
ba
lco
nyLIQUID APPLIED MEMBRANETO BALCONY AT 2º PITCH.
CONTINUOUS VERTICAL SAWCUTAT FLASHING JUNCTION WITHPRECAST CONCRETE PANEL
CONC NIB UPSTAND ATDOOR THRESHOLD
SKYL
IGHT
OVER
SKYL
IGHT
OVER
810
SHS POST
SHS POST
SHS POST
SHS POSTFRR DOOR
SUNS
HADE
LOUV
RES
OVER
SHS POST
CONCRETE FILLED STRUCTURAL100 SHS POST WITHINTUMESCENT PAINT FIREPROTECTION TO ACHIEVE120min FIRE RATING
DOUBLE INSOL SOLARIS FINS
FRR WINDOW DP1
DP2
DP4
2
B
BA3.1
BA3.1
DA3.3
DA3.3
EA3.3
EA3.3
8A4.3
10A4.3
2A4.3
5A4.3
1A4.2
2A4.3
9A4.1
9A4.2
8A4.1
3A4.2
8A4.1
lobbyw clobby
ac cw c
w c
SKYL
IGHT
OVER
38
similar
similar
DP3
0 1 2 3 4 5
1 3
C
A
AA3.1
AA3.1
CA3.2
CA3.2
DP1
60
0
1,600 140 1,070 90 18,500 2,160
20
01
1,4
40
20
0
3,100 21,400 2,160
75
3,0
50
8,7
90
17
5
OFS
OFS OFS
OFS
DP2
DP4
BUTYL ON TREATED PLY ONFRAMING AT 400 CRS
1:60 FALL
1:60 FALL 1:60 FALL
BUTYL ON TREATED PLY ONFRAMING AT 400 CRS
15
DEG
15
DEG
15
DEG
15
DEG
0.55 COLORSTEEL PROFILED METAL ROOF
COLORSTEEL PARAPETCAPPING
BUTYL ROOF ONTREATED PLY ONFRAMING @ 400 CRS
2 D
EG2
DEG
OVERFLOW SCUPPER, TYPICAL ASSPECIFIED
COLORSTEEL CAPPING TO TIMBERFRAMED PARAPET WALL
GUTTER HIGH POINT
1:30 FALL1:60 FALL
RAKING END TO SIDEPRECAST WALL
RAKING END TO SIDEPRECAST WALL
1:60 FALL
SCALE: 1:100proposed roof plan
BALCONYBELOW
SK
Y5
SK
Y3
SK
Y4
SK
Y2
SK
Y1
SPOU
TING
SUNSHADE LOUVRESBELOW
BUTYL ROOF ONTREATED PLY ONFRAMING @ 400 CRS
FORM SUMP SET DOWN AS E2 AS1
DOMED RAINWATER OUTLET, TYPICAL ASSPECIFIED
FORM SUMP SET DOWN AS E2 AS1
1:30 FALL
RIDGE
BARG
EPA
RAPE
TPA
RAPE
TBA
RGE
BARG
EBA
RGE
PARA
PET
PARA
PET
PARAPET PARAPET
PARAPET PARAPET
SUPPLYFAN
2
B
BA3.1
BA3.1
DA3.3
DA3.3
EA3.3
EA3.3
DP3
4A4.2
7A4.2
7A4.1
4/5A4.2
2A4.2
7A4.1
DP5
15 DEGPASSIVE VENTILATOR
1200 x 600 DOUBLE GLAZEDLOW PITCHED FIXED SKYLIGHTS (x8)ON TIMBER KERBS WITH FOLDEDCOLORSTEEL APRON FLASHINGSAND CRICKET DIVERTERS TO TOP EDGE.
800 x 600 DOUBLE GLAZEDLOW PITCHED FIXED SKYLIGHTS (x2)ON TIMBER KERBS WITH FOLDEDCOLORSTEEL APRON FLASHINGSAND CRICKET DIVERTERS TO TOP.
EXTRACTFAN
roof 1
roof 2
roof
3
similar
V
EM
CT
f loor plan key
FIRE RATED WALL, REFER FIREENGINEERS REPORT.FIRE RATED CONSTRUCTION TO EXTEND TOSOFFIT OR UNDERSIDE OF ROOFCLADDING, NOTCH AROUND ROOFFRAMING AND SEAL ALL AROUND WITHINTUMESCENT SEALANT
STRUCTURAL PRECAST CONCRETE PANEL,REFER STRUCTURAL ENGINEERSDOCUMENTATION
45x70 H3.2 TIMBER STRAPPING
90x45 H3.2 TREATED MSG8 TIMBERFRAMED WALL
140x45 H3.2 TREATED MSG8 TIMBERFRAMED WALL
OVERHEAD EAVE LINE
SELECTED VINYL FLOOR FINISH
SELECTED ENTRANCE MAT FLOOR FINISH
SELECTED CARPET TILE FLOOR FINISH
DOOR REFERENCE BY NUMBER, REFERDRAWING SERIES A7, WHERE;DG. - GROUND FLOOR DOORD1. - FIRST FLOOR DOORD2. - SECOND FLOOR DOOR
DG.#
D1.#
D2.#
JOINERY UNIT REFERENCE BY NUMBER,REFER DRAWING SERIES A6
J#
WINDOW REFERENCE BY NUMBER, REFERDRAWING SERIES A7, WHERE;DG. - GROUND FLOOR WINDOWD1. - FIRST FLOOR WINDOWD2. - SECOND FLOOR WINDOW
WG.#
W1.#
W2.#
OVERFLOW SCUPPER OUTLETSOFS
f loor f inishes key1. FLOOR FINISHES ONLY WHERE INDICATED
roof plan key
ref no. size material (mm)
DP 1 80 POWDER COATED GALVANISED STEEL CHSWHERE EXPOSED AT GROUND FLOOR
80 uPVC WHERE CONCEALEDDP 2 80 POWDER COATED GALVANISED STEEL CHS
WHERE EXPOSED AT GROUND FLOOR 80 uPVC WHERE CONCEALEDDP 3 80 uPVCDP 4 80 uPVCDP 5 65 COLORSTEEL
0.55 COLORSTEEL ENDURA V-RIBROOFING WITH MATCHING FLASHINGS ASSPECIFIED
SKY# SKYLIGHT REFERENCE BY NUMBER,REFER SPECIFICATION
BUTYL ON TREATED PLY ON FRAMING AT400mm CRS
do w np ip e s c hedule
SL
1:100@A21:200@A4
A
A 13/11/13 BUILDING CONSENT ISSUE
N E W O F F I C E B U I L D I N G3 0 7 D U R H A M S T R E E T
REFLECTED CEILINGPLANS
15/03/2013
4643
TH
A1.3
PR
ELI
MIN
AR
Y P
RIN
T | 1
4/11
/13
| 3:4
5 P
M
1 33,100 21,400 2,160
75
194.17 m2
3.22 m2
1.82 m2
3.94 m2
4.65 m2
3.75 m2 6.22 m2
4.29 m2
SUN SHADINGLOUVRES OVER
2420 2420
2420
2700
RAKING
HF
SCALE: 1:100proposed gr ound f loor plan
BUILDING SET OFF 75mm ATCLOSEST POINT
lif t
t enancy 1
store(under )
120/120/120 FFR WALLS TO BOTHNORTH & SOUTH BOUNDARIES
2700
VOID OVER
SLOPINGWITH STAIRABOVE
2700
GIB1
GIB1
GIB1GIB1
GIB1
TILE GRID
VOID OVER
6mm HARDIFLEX ON TIMBERSOFFIT FRAMING
CUT OUT FOR RECESSED LIGHTFITTING - REFER TO ELECTRICALENGINEERS DOCUMENTATION.
RAW CONCTO UNDERSIDE OF STAIR
1no. LAYER 13mm GIB FYRELINE TO EACHSIDE OF 60/60/60 FRR TIMBER FRAMEDFIRE WALL, AS PER GBTL 60 GIB SYSTEM
2no. LAYERS 19mm GIB FYRELINE ONESIDE OF 120/120/120 FRR TIMBERFRAMED FIRE WALL, AS PER GBTL 120GIB SYSTEM
1no. LAYER 13mm STANDARD GIB OVER70x70 TREATED TIMBER STRAPING ONPRECAST CONCRETE PANEL
1no. LAYER 13mm GIB AQUALINE TOWASH HAND BASIN WALL ONLY
1no. LAYER 13mm GIB AQUALINE TOKITCHEN SINK WALL ONLY
2no. LAYERS 19mm GIB FYRELINE OVER45x70 TREATED TIMBER STRAPING ONPRECAST CONCRETE PANEL
CL
NOTE 8
RJC
RJC
RJC
RJWRJC
RJC
RJC
RJW
FIRE RATED STRUCTURAL STEEL POSTSLINED IN 2no. LAYERS 19mm GIBFYRELINE WALL LINING INSTALLED TOCOMPLY WITH GIB FIRE RATEDPROTECTION OF STEEL COLUMN WITHSTEEL CLIP AND CHANNEL SYSTEM -TYPICAL
DP1
DP2
DP4
r cp
2
BUILDING TO BE PARALLELAND OFF-SET 75mm FROMTHE SOUTH BOUNDARY
w clobby
ac cw c
w cent r ylobby
CRITICAL SET-OUT NOTE
DP3
1 33,100 21,400 2,160
3.22 m2
1.82 m2
3.94 m2
2.69 m2
4.64 m2
RAKING
HF
SUN SHADINGLOUVRES OVER
lif t
t enancy 2
SCALE: 1:100proposed f irst f loor plan
2420 2420
2420
GIB1
GIB1
GIB1 VOID OVER
2700TILE GRID
1no. LAYER 13mm GIB AQUALINE TOWASH HAND BASIN WALL ONLY
1no. LAYER 13mm GIB AQUALINE TOKITCHEN SINK WALL ONLY
CL
RJC
RJC
RJC
RJW
NOTE 8
RJW
1no. LAYER 13mm STANDARD GIB OVER70x70 TREATED TIMBER STRAPING ONPRECAST CONCRETE PANEL
DP1
DP2
DP4
r cp
2
222.54 m2
w clobby
ac cw c
w c
6mm HARDIFLEX SOFFIT LINING
lobby
1no. LAYER 13mm GIB FYRELINE TO EACHSIDE OF 60/60/60 FRR TIMBER FRAMEDFIRE WALL, AS PER GBTL 60 GIB SYSTEM
2no. LAYERS 19mm GIB FYRELINE ONESIDE OF 120/120/120 FRR TIMBERFRAMED FIRE WALL, AS PER GBTL 120GIB SYSTEM
1no. LAYER 19mm GIB FYRELINE OVER45x70 TREATED TIMBER STRAPING ONPRECAST CONCRETE PANEL
FIRE RATED STRUCTURAL STEEL POSTSLINED IN 2no. LAYERS 19mm GIBFYRELINE WALL LINING INSTALLED TOCOMPLY WITH GIB FIRE RATEDPROTECTION OF STEEL COLUMN WITHSTEEL CLIP AND CHANNEL SYSTEM -TYPICAL
DP3
1 321,400 2,160
EQEQ
EQ
478 2,400 1,200 1,200
3.22 m2
1.82 m2
3.94 m2
193.23 m2
14.70 m2
14.35 m2
RAKI
NGRA
KING
2420
HF
2420
24202420 lif t
t enancy 3
SCALE: 1:100proposed second f loor plan
ba
lco
ny
2420 2420
2420
GIB1
GIB1
GIB1
RAKI
NGPLYWOOD3900
GIB1
PLY1
GIB MOVEMENT JOINTSTYPICALLY ALIGN WITHPORTAL FRAMES OVER.
GIB2
PERFORATED VENEERED BLONDEDDECORTECH FIRE SAFE PLY
2320
RJC
RJW
RJC
RJC
RJC
RJC
RJCRJW
RJC
SUN LOUVREOVER
RJCRJW RJC RJC RJCRJW
RJC
RJWRJC
NOTE 8
RJC CONTINUES AROUNDCOLUMNS, TYPICAL
HF
RJW
1no. LAYER 13mmSTANDARD GIB OVER70x70 TREATED TIMBERSTRAPING ON PRECASTCONCRETE PANEL
RAKI
NGRA
KING
SKY
LIG
HT
SKY
LIG
HT
SKY
LIG
HT
APPROX 140mm WIDEGIB LINED BULKHEAD ATCHANGE IN CEILINGS
DP1
DP2
DP4
r cp
2
lobbyw clobby
ac cw c
w c
6mm HARDIFLEX SOFFIT LINING
2no. LAYERS 19mm GIBFYRELINE ONE SIDE OF120/120/120 FRRTIMBER FRAMED FIREWALL, AS PER GBTL 120GIB SYSTEM
1no. LAYER 19mm GIBFYRELINE OVER 45x70TREATED TIMBERSTRAPING ON PRECASTCONCRETE PANEL
1no. LAYER 13mm GIB FYRELINE TO EACHSIDE OF 60/60/60 FRR TIMBER FRAMEDFIRE WALL, AS PER GBTL 60 GIB SYSTEM
DP3
ceiling plan key1200x600 SELECTED CEILING TILE &GRID SYSTEM
FAIRFACED CONCRETE - PAINT FINISH
FIRE RATED WALL, REFER FIREENGINEERS REPORT.FIRE RATED CONSTRUCTION TO EXTEND TOSOFFIT OR UNDERSIDE OF ROOFCLADDING, NOTCH AROUND ROOFFRAMING AND SEAL ALL AROUND WITHINTUMESCENT SEALANT
CEILING HEIGHT TO UNDERSIDE OFFRAMING2720
6mm HARDIFLEX SOFFIT LINING WITHNEGATIVE JOINTSHF
ACCESS PANELAP
EXTRACT GRILLE, REFER MECHANICALENGINEERS DOCUMENTATION
13mm STANDARD GIB PLASTERBOARDCEILING ON RONDO SUSPENSIONSYSTEM.WHERE;GIB1 - INDICATES LEVEL CEILINGGIB2 - INDICATES RAKING CEILING
12mm DECORTECH FIRESAFE PLYWOODCEILING - BLONDED FINISH
GIB 1
GIB 2
RESILIENT SHADOWLINE JOINT IN CEILINGAT JUNCTION WITH WALLS
RJC
RESILIENT VERTICAL CONTROL JOINTWHERE GIB SUBSTRATE CHANGES FROMTIMBER FRAMING TO CONCRETE
RJW
SUPPLY GRILLE, REFER MECHANICALENGINEERS DOCUMENTATION
CEILINGS INTERNAL CEILING LININGS SHALL BE ASFOLLOWS:
1. STAIR ENCLOSURE AND LOBBIESGENERALLY – 13mm STANDARD GIB FORPAINT FINISH ON RONDO SUSPENSIONSYSTEM EXCEPT TO SECOND FLOOR –REFER BELOW.
2. SECOND FLOOR ENCLOSURE AND LOBBY –SELECTED VENEERED 12mm DECORTECHFIRESAFE PLY ON RONDO SUSPENSIONSYSTEM.
3. TOILETS/ACCESSIBLE TOILETSTHROUGHOUT –13mm STANDARD GIBSEMI-GLOSS ENAMEL PAINT FINISH.
4. SECOND FLOOR RAKING AND FLAT CEILING– 13mm GIB ON RONDO SUSPENSIONSYSTEM. ALLOW FOR GIB MOVEMENTJOINTS AS SHOWN. ALLOW FOR SHADOWLINE BEAD AT JUNCTION OF WALLS ANDCEILING THROUGHOUT SECOND FLOOR.
5. UNDER STAIR CUPBOARD – 13mmSTANDARD GIB ON STEEL BATTENS.
6. TENANCY AREAS – 600 x 1200 MIDRANGE MINERAL FIBRE CEILING TILE INDONN TWO WAY EXPOSED SUSPENDEDGRID. ALLOW FOR SEISMIC BRACING TOSTRUCTURAL ENGINEERSREQUIREMENTS.
7. ALLOW FOR 6 no. RONDO PANTHERCEILING HATCHES IN LOCATIONS TO SUITHYDRAULIC/MECHANICAL ENGINEERSREQUIREMENT.
8. 19x19mm PAINTED TIMBER BEAD ATWALL/CEILING JUNCTION THROUGHOUTWC AND WC LOBBY AREAS TYPICAL
ceiling plan notes
RESILIENT VERTICAL CONTROL JOINTWHERE GIB SUBSTRATE CHANGES FROMTIMBER FRAMING TO CONCRETE
INTERNAL LININGS INTERNAL WALL LININGS SHALLBE AS FOLLOWS:
1. GENERALLY EXCEPT WHERE INDICATEDOTHERWISE – 13mm STANDARD GIB.
2. FIRE RATED INTERNAL PARTITIONS
BETWEEN STAIR LOBBY AREAS ANDTENANCIES – 13mm GIB FYRELINE EACHSIDE.
3. INTERNAL LININGS OF FIRE RATEDEXTERNAL TIMBER FRAMED WALL – 2no.LAYERS 19mm GIB FYRELINE.
4. TOILETS/ACCESSIBLE TOILETS
THROUGHOUT – 13mm GIB AQUALINE TOWHB WALL, 13mm STANDARD GIBELSEWHERE ALL FOR SEMI GLOSSENAMEL PAINT FINISH.
5. GIB EXPOSED TO VIEW SHALL BE LEVEL 4FOR SATIN PAINT FINISH. GIB EXTENDINGABOVE CEILING LEVEL AS PART OF FIRERATED PARTITION TO SECOND FLOORSTAIR LOBBY SHALL BE LEVEL 3 FINISH.
6. ALLOW FOR RAKING PLANTED STAIRSTRINGER CUT TO STAIR PROFILE TOOUTSIDE OF ALL STAIR FLIGHTS.
7. ALLOW FOR 60 x 12mm PAINTED TIMBERSKIRTING THROUGHOUT.
8. ALLOW FOR 3 no. RONDO PANTHER WALLACCESS HATCHES IN LOCATIONS TO SUITHYDRAULIC ENGINEER.
internal l inings
SL
1:100@A21:200@A4
A
A 13/11/13 BUILDING CONSENT ISSUE
N E W O F F I C E B U I L D I N G3 0 7 D U R H A M S T R E E T
ELEVATIONS15/03/2013
4643
TH
A2.1
PR
ELI
MIN
AR
Y P
RIN
T | 1
4/11
/13
| 3:4
5 P
M
3 2 1
BUILDING ENVELOPE RISK MATRIXNorth Elevation
Risk Factor Risk Severity Risk ScoreWind zone (per NZS 3604) Medium risk 0Number of storeys Very high risk 4Roof/wall intersection design Very high risk 5Eaves width Very high risk 5Envelope complexity Low risk 0Deck design Low risk 0Total Risk Score: 14
1,2
50
2,4
00
3,6
50
1,1
25
80
01
,60
0
20 580 900
2,895 1,560
57°
W2.4
W0.1
W1.4
WES
T BO
UNDA
RY
RECESSION PLANE
t od u r h a m s t
COLORSTEEL ENDURA V-RIBROOFING WITH MATCHINGFLASHINGS AS SPECIFIED
FAIRFACED PRECASTCONCRETE WALL WITH CLEARIMPREGNATING SEALERSYSTEM AS SPECIFIED
CLEAR ANTI-GRAFFITISYSTEM UP TO 2.4m, ASSPECIFIED
FIXED AND OPENING ROOFLIGHTS, AS SPECIFIED
120min FIRE RATEDWINDOWS, AS SPECIFIED
LINE OF EXISTING BUILDING OUTLINE SHOWN DASHED
nor th e levat ionSCALE: 1:100
ZINC SPRAYED 100 PFCBOUNDARY RAILS, ASDETAILS AND SPECIFIED
A B C
BUILDING ENVELOPE RISK MATRIXWest Elevation
Risk Factor Risk Severity Risk ScoreWind zone (per NZS 3604) Medium risk 0Number of storeys Very high risk 4Roof/wall intersection design Very high risk 5Eaves width Very high risk 5Envelope complexity Low risk 0Deck design Low risk 0Total Risk Score: 14
3,3
00
3,3
00
3,6
50
50
1,0
75
11
,37
5
D0.1
W2.1
D0.2
W2.2 W2.3
W1.1 W1.2 W1.3
east e levat ionSCALE: 1:100
SOUT
H BO
UNDA
RY
NORT
H BO
UNDA
RY
VERTICAL COLORSTEEL STANDINGSEAM CLADDING
O/FO/F
DP1DP2
COLORSTEEL CAPPINGCONTINUES IN FRONTOF GABLE
POWDERCOATED FACINGAT STRUCTURAL POSTLOCATIONS TYPICALLY
ground floor0
first floor3300
second floor6600
PROPRIETARYOVERFLOWSCUPPER,AS SPECIFIEDTYPICAL
COLORSTEEL CLADWINDOW SILLS
PLASTER SYSTEMMOVEMENT JOINTS TO BECONFIRMED ON SITE WITHARCHITECT
SELECTED PLASTERFINISH
DOUBLE INSOL SOLARISFINS ON PROPRIETARYALUMINIUM BRACKETS
SPANDREL PANELS TO BE SELECTEDCOLOUR TEMPACLAD TO OUTER PANE
ACID WASHED PRECASTWALLS AND COLUMN
1 2 3
BUILDING ENVELOPE RISK MATRIXSouth Elevation
Risk Factor Risk Severity Risk ScoreWind zone (per NZS 3604) Medium risk 0Number of storeys Very high risk 4Roof/wall intersection design Very high risk 5Eaves width Very high risk 5Envelope complexity Low risk 0Deck design Low risk 0Total Risk Score: 14
57°
WES
T BO
UNDA
RYRECESSIO
N PLANE
COLORSTEEL ENDURA V-RIBROOFING WITH MATCHINGFLASHINGS AS SPECIFIED
FAIRFACED PRECASTCONCRETE WALL WITH CLEARIMPREGNATING SEALERSYSTEM AS SPECIFIED
CLEAR ANTI-GRAFFITISYSTEM UP TO 2.4m, ASSPECIFIED
LINE OF EXISTING BUILDING OUTLINE SHOWN DASHED
t od u r h a m s t
FIXED AND OPENING ROOFLIGHTS, AS SPECIFIED
south e levat ionSCALE: 1:100
C B A
BUILDING ENVELOPE RISK MATRIXWest Elevation
Risk Factor Risk Severity Risk ScoreWind zone (per NZS 3604) Medium risk 0Number of storeys Very high risk 4Roof/wall intersection design Very high risk 5Eaves width Very high risk 5Envelope complexity Low risk 0Deck design Very high risk 6Total Risk Score: 20
W2.6 D2.1
W0.3 D0.3
W1.6 W1.5
W0.2
W1.7
W2.5
CLEAR ANTI-GRAFFITISYSTEM UP TO 2.4m, ASSPECIFIED
ground floor0
first floor3,300
second floor6,600
PROPRIETARYOVERFLOW SCUPPER,AS SPECIFIEDTYPICAL
30
01
,10
0
west e levat ionSCALE: 1:100
NORT
H BO
UNDA
RY
SOUT
H BO
UNDA
RY
VERTICAL COLORSTEEL STANDINGSEAM CLADDING
SUNSHADE LOUVRES
SUNSHADE LOUVRES
PRECASTCONCRETE WALLS
LIFT OVER-RUN
O/FO/F
METAL & GLASS BALUSTRADE
COLORSTEELPARAPET CAPPING
POWDERCOATED FACINGAT STRUCTURAL POSTLOCATIONS TYPICALLY
SUNSHADE LOUVRES
HTground floor0
first floor3300
second floor6600
EWL
EWL
balustrade elevationSCALE: 1:100
elevat ions key
HT HOSE TAP, REFER HYDRAULIC ENGINEERDOCUMENTATION
0.55 COLORSTEEL ENDURA V-RIBROOFING WITH MATCHING FLASHINGSAS SPECIFIED
FAIRFACED PRECAST CONCRETE WALLWITH CLEAR IMPREGNATING SEALERSYSTEM AS SPECIFIED
ETERPAN TWO WAY FIRE WALL SYSTEMWITH 120/120/120 FIRE RATING, BUILTUP WITH 9mm ETERPAN , 20mm CAVITY,OVER 9mm ETERPAN RAB, 2no. LAYERS60mm ETERCORE INSULATION AND 2no.19mm GIB FYRELINE PLASTERBOARD
CLEAR ANTI-GRAFFITI SYSTEM UP TO2.4m, AS SPECIFIED
SELECTED PLASTER FINISH OVER FIBRECEMENT BACKING SHEETS ON 20mmCAVITY OVER 90x45 TIMBER FRAMING.
EWL EXTERNAL WEATHER LOUVRE, REFERMECHANICAL ENGINEER DOCUMENTATIONLOCATION TO BE CONFIRMED ON SITE WITHARCHITECT
SELECTED 'TEMPACLAD' COLOUREDGLASS TO OUTER PANE
FIXED SASH WINDOW WITH HEADFLASHING & SILL
OPENING SASH WINDOW WITH HEADFLASHING & SILL
AREA OF '3M DUSTED CRYSTAL' ORAPPROVED COLOURED FILM
D#.# DOOR/WINDOW REFERENCE BY FLOORLEVEL AND NUMBER, REFER DOOR ANDWINDOW SCHEDULEW#.#
SL
1:100@A21:200@A4
A
A 13/11/13 BUILDING CONSENT ISSUE
N E W O F F I C E B U I L D I N G3 0 7 D U R H A M S T R E E T
SECTIONS A & B15/03/2013
4643
TH
A3.1
PR
ELI
MIN
AR
Y P
RIN
T | 1
4/11
/13
| 3:4
5 P
M
A B C
2,4
00
- CE
ILIN
G S
PRIN
G P
OINT
3,6
50
- TO
P OF
PAR
APET
1,1
25
APE
X
2,8
00
- PO
RTAL
SPR
ING
POI
NT8
50
3,6
50
3,6
50
200 2,650 400
3,050 8,790
15,560 FFL
18,860 FFL
22,160 FFL
15º
SCALE: 1:50Sect ion A
SOUT
H BO
UNDA
RY
NORT
H BO
UNDA
RY
t enancy 1
tenancy 2
tenancy 3
ROOF PITCH
store(understair s)
100mm THICK CONCRETETOPPING SLAB ON 200mmTHICK HOLLOWCORE
100mm THICK CONCRETETOPPING SLAB ON 200mmTHICK HOLLOWCORE
METAL ROOFING ON 90x45 TIMBERSTRAPPING ON 300/15 DHS PURLINSON CLEATS TO 360 UB PORTAL FRAMES
GIB SHEET CEILING ON SUSPENDEDRAILS, RAKING WITH ROOF PITCH.
GIB WALL LININGS OVER45mm THICK STRAPPINGWITH 40mm EPS INSULATIONTO 200mm THICK PRECASTCONCRETE WALL PANELS.
60 Min FRR WALL TO STAIRS.LINE WITH 13mm GIB FYRELINETO BOTH SIDES. REFER TO FIREREPORT.
CANTILEVERED GLASS BALUSTRADETO STAIRS WITH SS DISC FIXINGS ANDHANDRAILS ON STAND OFF BRACKETS
FIRE RATED WALL CONTINUES UPTO UNDERSIDE OF ROOFING. REFERTO FIRE REPORT.
BUYTL LINED INTERNAL GUTTER SETTO FALLS, REFER TO ROOF PLAN ANDDETAILS.
600mm THICK CONCRETE FLOORSLAB. REFER TO STRUCTURALENGINEERS DOCUMENTATION.
FIRE RATED PLYWOOD CEILING LININGTO TOP OF STAIR WELL, REFER TOREFLECTED CEILING PLAN.
ground floor0
first floor3,300
second floor6,600
7A4.1
2,7
00
CEI
LING
60
02
,70
0 C
EILI
NG6
00
1,5
63
lobby
lobby
lobby
lif t over -run
FR SEALANT TO UNDERSIDESTAIR / GIB JUNCTION,REFER TO FIRE REPORT
3 4
3 5
3 6
3 7
3 8
3 3
3 2
31
3 0
2 9
19
18
17
16
15
14
13
12
11
10
9
STANDARD VALLEY GUTTER TO SMALLPITCHED ROOFING BEHIND LIFT SHAFT
BUTYNOL ROOFING @ 2º MIN PITCH ON17mm STRUCTURAL GRADE PLYWOODON 140x45mm MSG8 ROOF FRAMING@ 400mm CRS MAX BOTH WAYS. DRESSUP SIDES MIN 150mm TO FLASHING INTOSEALANT FILLED CONCRETE CHASE.
A B3,050
25
1,1
00
3,3
00
3,3
00
3,6
50
85
0
4,5
00
15
0
SCALE: 1:50Sect ion B
t enancy 2
tenancy 1
tenancy 3
LIFTING BEAM ZONE
SOUT
H BO
UNDA
RY
600mm THICK CONCRETE FLOORSLAB. REFER TO STRUCTURALENGINEERS DOCUMENTATION.
100mm THICK CONCRETETOPPING SLAB ON 200mmTHICK HOLLOWCORE. REFERTO STRUCTURAL ENG. DOCS.
GIB SHEET CEILING ON SUSP.RAIL SYSTEM, RAKING WITHROOF PITCH.
MIN
ground floor0
first floor3,300
second floor6,600
7A4.1
lif t shaf t
lif t pit
DOUBLE GLAZED LOW PITCHEDSKYLIGHTS ON TIMBER KERBSWITH FOLDED COLORSTEELAPRON FLASHINGS
similar
SF
1:50 @A21:100@A4
A
A 13/11/13 BUILDING CONSENT ISSUE
N E W O F F I C E B U I L D I N G3 0 7 D U R H A M S T R E E T
SECTION C15/03/2013
4643
TH
A3.2
PR
ELI
MIN
AR
Y P
RIN
T | 1
4/11
/13
| 3:4
5 P
M
METAL ROOFING ON 70x45 TIMBERPACKING ON 300/15 DHS PURLINSON CLEATS TO 360 UB PORTAL FRAMES
COLORSTEEL BARGE / RIDGE FLASHINGSCOLOURED TO MATCH ROOFING
COLORSTEEL PARAPET CAP FLASHINGCOLOURED TO MATCH WALL CLADDING
BUTYL ROOFING @ 2º MIN PITCH ON17mm STRUCTURAL GRADE PLYWOODON 100x45 MSG8 ROOF FRAMING@ 400mm CRS MAX BOTH WAYS.
BUTYNOL ROOFING @ 2º MIN PITCH ON17mm STRUCTURAL GRADE PLYWOODON 140x45mm MSG8 ROOF FRAMING@ 400mm CRS MAX BOTH WAYS.DRESSED DOWN OVER 50x50 ALUM.ANGLE TO FORM DRIP EDGE TO GUTTER.
ROOF PITCH 15º
9mm FIBRE CEMENT WALL CLADDINGOVER 20mm MIN CAVITY OVER 120minFRR WALL STRUCTURE. REFER TOELEVATION SHEET A2.1 FOR SETOUTOF EXPRESSED JOINTS.
LIQUID APPLIED MEMBRANE OVER CONCTO FALLS ON BALCONY. MINIMUM 150mmUPSTAND TO WALLS.
300mm THICK INSITU CONCRETESHEARWALL. REFER TO STRUCTURALENGINEERS DOCUMENTATION.
PROPRIETARY ALUMINIUM POST &HANDRAIL BALUSTRADE WITHGLAZING BETWEEN.
1 2 3
15,560 FFL15,610
18,860 FFL
22,160 FFL
2,3
00
1,1
00
3,3
00
3,3
00
3,6
50
85
0
2,1
00
HEA
DROO
M
90
0
90
0
25
01
,10
0
2,7
00
60
02
,70
06
00
2,4
20
15 65
21,400 2,160
2,7
00
60
02
,70
06
00
2,4
20
60
05
75
50
1,8
55
82
05
75
50
1,8
55
1,2
20
140 410
3,4
51
19
9
90
0
150 400
2,3
20
10
0
700 Max
600
15
0
57°
SCALE: 1:50Sect ion C
SITE
BOU
NDAR
Y - W
EST
LIFTING BEAM ZONE
RECESSION PLA
NE
100mm THICK CONCRETETOPPING SLAB ON 200mmTHICK HOLLOWCORE
100mm THICK CONCRETETOPPING SLAB ON 200mmTHICK HOLLOWCORE
GIB SHEET CEILING ON SUSPENDEDRAILS, RAKING WITH ROOF PITCH.
13mm GIB WALL LININGS OVER70mm THICK STRAPPINGTO 300mm THICK PRECASTCONCRETE SHEARWALL, TOALIGN WITH FIRE RATED WALL.
SUNSHADE LOUVRESOVER REAR WINDOWS.INSOL ZENITH MODULAR
t enancy 2
tenancy 1
tenancy 3
DOUBLE INSOL SOLARIS 300VERTICAL LOUVRE BLADES ONPROPRIETARY ALUMINIUMCLASP BRACKETS. POWDERCOATED FINISH.
COLORSTEEL CLAD WINDOW SILLSOVER PLYWOOD SUBSTRATE.
STAIR 1:- Accessible stair
Risers: 173.68 Max 180Treads: 310 Min 310Going: 285 Min 285Nosing: 25 Max 25Total Rise: 3300 Max rise 2500
Construction: Precast Concrete stair
STEEL STRUCTURE WITHIN WALLFRAMING TO SUPPORT STAIRS.REFER TO STRUCTURAL DRAWINGS.
SUNSHADE LOUVRES OVER REARWINDOWS. INSOL ZENITH MODULAR
TEA SINK
TEA SINK
TEA SINK
50mm SOFFIT BOARD XPSINSULATION TO UNDERSIDEOF FLOOR SYSTEM BELOWEXTERIOR BALCONY ASSPECIFIED.
50mm SOFFIT BOARDXPS INSULATION TOUNDERSIDE OF FLOORSLAB AS SPECIFIED.
13mm GIB FYRELINE WALL LININGSEACH SIDE TO MAINTAIN 60min FRR.
16mm GIB FYRELINETO RAKING CEILING
INTUMESCENT PAINTFOR 60Min FRR TOSTEEL POST AND BEAMBELOW STAIR LANDING.
MIN
EXPOSED AGGREGATE PAVINGREFER TO SITEWORKS PLAN
2x19mm GIB FYRELINEWALL LININGS OVER 140mmTIMBER FRAMING TO ACHIEVE120 Min FRR.
2x19mm GIB FYRELINELININGS AROUND TOPSTEEL MEMBERS CONT.UP TO UNDERSIDE OFBUYTL ROOF FRAMING
600mm THICK CONCRETE FLOORSLAB. REFER TO STRUCTURALENGINEERS DOCUMENTATION.
13mm GIB FYRELINE TOINSIDE FACE OF STORE
0.55 COLORSTEEL APRON FLASHINGLAPS UP UNDER 0.55 COLORSTEELFOLDED PARAPET CAPPING.
0.55 COLORSTEEL APRON FLASHINGUP MIN 110mm INTO SEALANT FILLEDCHASE IN CONC, 2 CRESTS MIN COVEROVER PROFILED ROOFING.
FIREPRO BJ201 (OSA) FLEXIBLEFIRE RESISTANT BARRIER TO WALLFRAMING BETWEEN FLOORS TOMAINTAIN 120min FRR.
4A4.1
3A4.1
8A4.1
8A4.2
8A4.2
9A4.2
8A4.2
9A4.2
2A4.2
3/6A4.2
4A4.2
5A4.2
7A4.1
90
0
90
0
1,1
00
2,7
00
2
,70
0
VARI
ES -
RAKI
NG
lobby ent r y
DOUBLE GLAZED LOW PITCHEDSKYLIGHTS ON TIMBER KERBSWITH FOLDED COLORSTEELAPRON FLASHINGS
FALL
balc ony
lobby
lobby
w clobby
w clobby
w clobby
w c
w c
w c
lif t shaf t
lif t pit
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
3 0
31
3 2
3 3
3 4
3 5
3 6
3 7
3 8
21
20
22
23
24
25
26
27
28
29
similar
similar
ground floor0
first floor3,300
second floor6,600
SL
1:50@A21:200@A4
A
A 13/11/13 BUILDING CONSENT ISSUE
N E W O F F I C E B U I L D I N G3 0 7 D U R H A M S T R E E T
SECTIONS D & E15/03/2013
4643
TH
A3.3
PR
ELI
MIN
AR
Y P
RIN
T | 1
4/11
/13
| 3:4
5 P
M
COLORSTEEL BARGE / RIDGE FLASHINGSCOLOURED TO MATCH ROOFING
COLORSTEEL PARAPET CAP FLASHINGTO SELECTED COLOUR REFER SCHEDULE.
9mm FIBRE CEMENT WALL CLADDINGOVER 20mm MIN CAVITY OVER 9mmFIBRE CEMENT RAB BOARD ON 140mmWALL STRUCTURE. REFER TOELEVATION SHEET A2.1 FOR SETOUTOF EXPRESSED JOINTS.
BUTYNOL ROOFING @ 2º MIN PITCH ON17mm STRUCTURAL GRADE PLYWOODON 100x45 MSG8 ROOF FRAMING@ 400mm CRS MAX BOTH WAYS.
LIQUID APPLIED MEMBRANE OVER CONCTO FALLS ON BALCONY. MINIMUM 150mmUPSTAND TO WALLS.
9mm FIBRE CEMENT WALL CLADDINGOVER 20mm MIN CAVITY OVER 9mmFIBRE CEMENT RAB BOARD ON 140mmWALL STRUCTURE. REFER TOELEVATION SHEET A2.1 FORSETOUT OF EXPRESSED JOINTS.
METAL FLASHING INTO CHASE INPRECAST WALL TO TERMINATEWATERPROOFING MEMBRANEMIN 150mm ABOVE BALCONY.
PROPRIETARY ALUMINIUM POST &HANDRAIL BALUSTRADE WITHGLAZING BETWEEN.
DOUBLE GLAZED ALUMINIUM WINDOWJOINERY, REFER TO DETAILS.
1
15,560 FFL
18,860 FFL
22,160 FFL
15,610
2,3
00
80
01
,30
01
,20
08
00
1,3
00
90
0
80
01
,45
01
70
50 2
50
1,1
00
15
2
57°
SCALE: 1:50Sect ion D
WES
T BOU
NDAR
Y
RECESSION PLA
NE
600mm THICK CONCRETE FLOORSLAB. REFER TO STRUCTURALENGINEERS DOCUMENTATION.
2x19mm GIB FYRELINE WALL LININGSOVER 140mm TIMBER FRAMING TOACHIEVE 120 Min FRR.
t enancy 2
tenancy 1
tenancy 3
100mm THICK CONCRETETOPPING SLAB ON 200mmTHICK HOLLOWCORE
CUSTOM DESIGNEDTIMBER ROOF TRUSSTO GABLE END. 45mmSTRAPPING TO INSIDEFACE AS SHOWN.
SUNSHADE LOUVRESOVER REAR WINDOWS.INSOL ZENITH MODULAR
125 PFC OR 100x50 RHSSUPPORT STEELWORK ABOVEAND BELOW WINDOWS, REFERTO STRUCTURAL ENG. DOCS.
MIN
EXPOSED AGGREGATE PAVINGREFER TO SITEWORKS PLAN
ground floor0
first floor3,300
second floor6,600
9A4.1
6A4.3
4A4.3
5A4.3
1/2A4.3
2A4.2
3/6A4.2
4A4.3
5A4.3
4A4.2
5A4.2
17
5
FALL
balc ony
s imilar
COLORSTEEL BARGE / RIDGE FLASHINGSCOLOURED TO MATCH ROOFING
COLORSTEEL PARAPET CAP FLASHINGCOLOURED TO MATCH WALL CLADDING
METAL ROOFING ON 90x45 TIMBERSTRAPPING ON 300/15 DHS PURLINSON CLEATS TO 360 UB PORTAL FRAMES
SELECTED PLASTER FINISH OVER FIBRECEMENT BACKING SHEETS ON 20mmCAVITY OVER 90x45 TIMBER FRAMING.
DOUBLE GLAZED ALUMINIUMWINDOW JOINERY, REFER TODETAILS. OPAQUE GLAZINGTO LOWER PANES.
2 3
ROOF PITCH 15º
90
01
,65
07
50
57
55
01
,85
5
15,560 FFL
18,860 FFL
22,160 FFL
80
01
,60
09
00
80
01
,60
0
2,7
00
60
02
,48
08
20
2,4
80
57
55
01
,85
51
,22
0
SCALE: 1:50Sect ion E
100mm THICK CONCRETETOPPING SLAB ON 200mmTHICK HOLLOWCORE
GIB SHEET CEILING ON SUSPENDEDRAILS, RAKING WITH ROOF PITCH.
COLORSTEEL CLAD WINDOW SILLSOVER 20mm PLYWOOD SUBSTRATEON 90x45 TIMBER FRAMING.
t enancy 2
tenancy 1
tenancy 3
750mm DEEP x 400 WIDE INSITUCONCRETE BEAM. REFER STRUCT.ENGINEERS DOCUMENTATION.
6mm HARDIFLEX ON TIMBERSOFFIT FRAMING
FIREPRO BJ201 (OSA) FLEXIBLEFIRE RESISTANT BARRIER TO WALLFRAMING BETWEEN FLOORS TOMAINTAIN 120min FRR.
ground floor0
first floor3,300
second floor6,600
2A4.1
1A4.1
7A4.2
8A4.2
8A4.2
9A4.2
8A4.2
4A4.2
similar
SF
1:50@A21:200@A4
A
A 13/11/13 BUILDING CONSENT ISSUE
N E W O F F I C E B U I L D I N G3 0 7 D U R H A M S T R E E T
DETAILS15/03/2013
4643
TH
A4.1
PR
ELI
MIN
AR
Y P
RIN
T | 1
4/11
/13
| 3:4
5 P
M
2800 AFL
360
UB P
ORTA
L
LOW POINT
HIGH POINT
15
0
50
2400 AFL
LOW POINTSUMP
~24
0
50
15°
10°
C
SHEET INSULATION
ROOF PITCH
Min
Min
PARAPET SLOPE
0.55 BMT COLOURSTEEL V-RIB PROFILEROOFING OVER ROOFING UNDERLAY. FIXTHRU RIB CREST ONLY WITH 14G x 55mmSCREWS INTO MIN 70x45mm TIMBERBATTENS OVER 300 DHS STEEL PURLINS
R5.0 FIBREGLASS BATTS INSULATIONFITTED NEATLY BETWEEN DHS PURLINSON FOIL ON 50mm GALV WIRE MESHSCREW FIXED TO UNDERSIDE OF DHSPURLINS. ALLOW EXTRA FOR DAN BANDSTRAPPING AT MID SPAN OF EACH WIREMESH SHEET.
360 UB PORTAL FRAME. REFER TOSTRUCTURAL ENG. DOCUMENTATION.
13mm STANDARD GIB BOARD CEILINGSON RONDO STEEL SUSPENSION SYSTEMFIXED TO DHS PURLINS ABOVE, RAKINGWITH THE SLOPE OF THE PORTAL FRAMES.
GIB GOLDLINE PLATINUM TRIM TO CREATENEGATIVE DETAIL AT WALL JUNCTIONS.
380 PFC
100mm Ø PVC DOWNPIPE OFFSETTO PASS THROUGH CENTRE OF380 PFC BEAMS BELOW. CLAMPRING ROOF DRAIN WITH FLAT GRATEFITTED TO ROOF SUMP ABOVE.
Min
1.5mm BUTYL ROOFING OVER MIN 17mm CDSTRUCTURAL GRADE PLYWOOD SUBSTRATETO MIN 1:100 GUTTER FALLS WITH 20mmTREATED TRIANGULAR TIMBER FILLETS TOALL 90º UPSTANDS AS REQUIRED. SUPPORTFRAMING TO BE @400mm CRS MAX IN BOTHDIRECTIONS. DRESS UP 150mm MIN UNDERMETAL FLASHING INTO SEALANT FILLEDCONCRETE CHASE.
7A3.1 Scale: 1: 10
detail: internal gut ter - typical
200 200
25 75 100 70
15 40
10
15
0
75 200
275
15
0
50
12
52
00
50 15
40 15
25
50
12
51
00
10
0
50
20
10
0
12mm
30
0
10
15 40
25 75 100 70
200 200
20
mm
GAP
5
100mm APL VANTAGE FLUSHGLAZED ALUMINIUM WINDOWSUITE WITH DOUBLE GLAZING.POWDER COATED FINISH.
400mm THICK INSITU CONCBEAM OR WALL. REFER TOSTRUCT ENG. DRAWINGS.
DRIP EDGE CAST 15mm WIDE10mm DEEP REBATE INTOHEAD ONLY (NOT REQUIREDFOR JAMBS)
40mm FOAMULAR EPS WALLINSULATION NEATLY FITTEDBETWEEN 70x45mm MSG8THICK TIMBER STRAPPING.
13mm STD GIB BOARD WALLLININGS OVER STRAPPINGOVER DPC TO CONC WALLS
25mm THICK TIMBERREVEALS GROOVED FORLININGS
VANTAGE ALUM. REVEALADAPTER TO WINDOW SUITE.PC TO MATCH FRAMES.
100mm APL VANTAGE FLUSHGLAZED ALUMINIUM WINDOWSILL OVER SILL TRAY WITHDOUBLE GLAZING. POWDERCOATED FINISH.
VEHICLE GRADE ASPHALT TOFORECOURT AREA TO EDGESAS SHOWN ON CIVIL ENG.DRAWINGS.
100mm THICK EXPOSEDAGGREGATE CONCRETEPAVING STRIP TO FRONT OFGROUND FLOOR WINDOWS
SITE CONCRETE OVERFOUNDATIONS TO REQUIREDLEVELS.
REFER TO STRUCTUAL ENG.DRAWINGS FOR SLAB ANDFOUNDATION DETAILS
SELECTED DRAINAGE CHANNELAT DOOR THRESHOLD MIN150mm DEEP.
MIN GAP
100mm APL VANTAGE FLUSHGLAZED ALUMINIUM WINDOWMULLION TO MAGNUM 50 HINGEDDOOR FRAME. ALL WITH DOUBLEGLAZING.
100mm APL VANTAGE FLUSHGLAZED ALUMINIUM WINDOWMULLION TO MAGNUM 50 HINGEDDOOR FRAME. ALL WITH DOUBLEGLAZING.
DRIP EDGE CAST 15mm WIDE10mm DEEP REBATE INTOHEAD ONLY (NOT REQUIREDFOR JAMBS)
100mm APL VANTAGE FLUSHGLAZED ALUMINIUM WINDOWSUITE WITH DOOR ADAPTERFRAME TO MAGNUM 50.POWDER COATED FINISH.
40mm FOAMULAR EPS WALLINSULATION NEATLY FITTEDBETWEEN 70x45mm MSG8THICK TIMBER STRAPPING.
13mm STD GIB BOARD WALLLININGS OVER STRAPPINGOVER DPC TO CONC WALLS
25mm THICK TIMBERREVEALS GROOVED FORLININGS
VANTAGE ALUM. REVEALADAPTER TO WINDOW SUITE.PC TO MATCH FRAMES.
MAX
2
11
AP40
AP65
1A3.3
2A3.3
4A3.2
3A3.2
9A3.3
6A1.1
8A3.2
5A1.1
2
APL VANTAGE MAGNUM 50HINGED DOOR WITH DOUBLEGLAZING. POWDER COATFINISH
Scale: 1:5w indow detail: head / jamb to insitu conc
Scale: 1:5w indow detail: sill at s lab edge
Scale: 1:5door detail: entry thr eshold / door sill
Scale: 1:5door detail: door head
REFER TO STRUCTUAL ENG.DRAWINGS FOR SLAB ANDFOUNDATION DETAILS
HEAVY DUTY ANODISED ALUMRIBBED DOOR THRESHOLD,RAVEN RP19 OSA.
SELECTED ENTRANCE MAT ONFLC AS REQUIRED WITH SCREWFIXED 12x3mm ALUMINIUMANGLE TRIM; ANODISED FINISH
scale: 1:5w indow detail: head / jamb to insitu conc
LIQUID APPLIED BALCONYMEMBRANE OVER CONCRETESET TO 2º FALL TO EXTERIOR.
2x19mm GIB FYRELINE WALLLINING OVER TIMBER FRAMINGAS PART OF FIRE RATED WALL
DRIP EDGE TOUNDERSIDE OF CONC BEAM
SELECTED ALUMINIUM POST & RAILBALUSTRADE WITH GLASS PANELS.
Scale: 1:5w indow detail: south entry door jamb to precast
scale: 1:5w indow detail: head / jamb to insitu conc
LIQUID APPLIED BALCONYMEMBRANE OVER CONCRETESET TO 2º FALL TO EXTERIOR.
SELECTED ALUMINIUM POST & RAILBALUSTRADE WITH GLASS PANELS.
Scale: 1:5w indow detail: mullion to door jamb
400mm THICK INSITU CONCBEAM OR WALL. REFER TOSTRUCT ENG. DRAWINGS.
APL VANTAGE MAGNUM 50HINGED DOOR WITH DOUBLEGLAZING. POWDER COATFINISH
300mm THICK PRECASTCONCRETE SHEAR WALL.REFER TO STRUCTURALENG. DOCUMENTATION.
200mm THICK HOLLOWCORESTRUCTURAL FLOOR SYSTEM
200mm THICK HOLLOWCORESTRUCTURAL FLOOR SYSTEM
9.0mm FIBRE CEMENT WALL CLADDINGWITH EXPRESSED JOINTS ON XPRESSCLADCAVITY BATTEN SYSTEM OVER 9.0mmETERPAN FIBRE CEMENT SHEETS AS RABON 140x45 MSG8 TIMBER FRAMING.
CLADDING ADHESIVE FIXED OVERFOLDED GALV BACK FLASHINGINTO SEALANT FILLED CHASE ONXPRESSCLAD ZED RAIL (XZR)
SF
1:5 @A21:10@A4
A
A 13/11/13 BUILDING CONSENT ISSUE
N E W O F F I C E B U I L D I N G3 0 7 D U R H A M S T R E E T
DETAILS15/03/2013
4643
TH
A4.2
PR
ELI
MIN
AR
Y P
RIN
T | 1
4/11
/13
| 3:4
5 P
M
70
MIN
70
MIN
Min
15
0m
m U
PSTA
ND
Min
35
50
MIN
15
0
2 CRESTS MIN LAP
12
0
40
80
10
05
0
10
0 M
IN
70
MIN
7.5
50
140 320 90
140 35 90 195 90
10
0 M
IN
Min
15
0m
m U
PSTA
ND
7.5
20 100 20 320 90 20
GAP
5
25
35
75
11
0 M
IN T
OTAL
50
25
20
50 MIN
5°
5°
10°
MIN SLOPE
GAP
MIN SLOPE
UPST
AND
25mm THICK TIMBER REVEALSGROOVED FOR LININGS
100x50 RHS LINTEL VARIATIONDETAIL. REFER TO STRUCT.
150 PFC STEEL LOCATION WITHTIMBER PACKING TO SUIT. REFERTO STRUCT DOCUMENTATION.
25mm THICK TIMBER REVEALSGROOVED FOR LININGS
MIN
GAP
MIN
COV
ER
40mm COMMERCIAL VANTAGEALUMINIUM WINDOW SUITE WITHDOUBLE GLAZING.POWDER COATED FINISH.
WATER VAPOUR AIR SEALON PEF RODS TO PERIMETER
WALL WRAP DRESSED INTO ANDAROUND OPENING, APPLY FLEXIBLEFLASHING TAPE 100mm AT CORNERSAND TURN OUT 50mm MIN.
WALL WRAP DRESSED INTO ANDAROUND OPENING, APPLY FLEXIBLEFLASHING TAPE 100mm AT CORNERSAND TURN OUT 50mm MIN.
WATER VAPOUR AIR SEALON PEF RODS TO PERIMETER
DOUBLE INSOL SOLARIS 300 VERTICALLOUVRE BLADES. SELECTED POWDERCOAT FINISH. SUPPLIED AND INSTALLEDBY INSOL NZ (0800 34 6000).
INSOL PROPRIETARY CLASP BRACKETLOUVRE FIXING SYSTEM TO UNDERSIDEOF 75 x 50 UA.
MIN
SLOPE
3
2A3.2
3A3.2
5A3.3
7A3.3
1A1.2
8A3.3
4A3.3
6A3.3
9A3.3
scale: 1:5detail: west par apet / buty l roof ing
1.5mm BUTYL ROOFING OVER MIN 17mm CDSTRUCTURAL GRADE PLYWOOD SUBSTRATETO MIN 2º FALL WITH 20mm TREATEDTRIANGULAR TIMBER FILLETS TO ALL 90ºUPSTANDS AS REQUIRED. SUPPORTFRAMING TO BE @400mm CRS MAX IN BOTHDIRECTIONS.
9.0mm FIBRE CEMENT WALL CLADDINGWITH EXPRESSED JOINTS ON XPRESSCLADCAVITY BATTEN SYSTEM OVER 9mm ETERPANFIBRE CEMENT SHEETS ON BUILDINGWRAP ON 140x45 MSG8 TIMBER FRAMINGWITH 2 x 60mm ETERCORE INSULATION WITH16mm FYRELINE LININGS TO INSIDE FACE.
0.55 BMT FOLDED COLORSTEELCAPPING TO MIN 5º SLOPE. FIXINGTHRU SIDES ONLY. UNDERLAY TOPROVIDE SEPARATION OF CAPPINGAND TIMBER.
scale: 1:5detail: conc nib up stand / wall
200mm THICK HOLLOWCORESTRUCTURAL FLOOR SYSTEM
2x19mm GIB FYRELINE WALL LININGOVER 140x45 TIMBER FRAMINGTO ACHIEVE 120Min FRR WALLRATING, REFER TO SPECIFICATION.
scale: 1:5detail: s t anding seam / buty l roof ing
scale: 1:5w indow detail: head / jamb to insitu conc
scale: 1:5detail: par apet wall / precast junc t ion
HIGH POINT
LIQUID APPLIED TRAFFICABLEWATERPROOFING MEMBRANEOVER CONCRETE SET TO 2º FALLTO EXTERIOR BALCONY.
0.55 BMT FOLDED COLORSTEEL FLASHINGOVER 9mm PLYWOOD SUBSTRATE TO MIN5º SLOPE. UNDERLAY TO PROVIDESEPARATION OF FLASHING & TIMBER.
scale: 1:5w indow detail: head / jamb to insitu conc
scale: 1:5detail: bar ge / s t anding seam
VENTED VERMIN TRAY MIN 20mmFROM BOT. EDGE OF F.C. SHEET.
CLIP-ONFOOT TRAY TO BOTTOM EDGEOF FIBRE CEMENT SHEET.
SELECTED PLASTER FINISH OVER 9mmJH MONOTEK FIBRE CEMENT SHEET WALLCLADDING SYSTEM ON 20mm NOM WALLCAVITY BATTENS OVER WALL UNDERLAY.ALL AS OUTLINED WITHIN SPECIFICATION.
VERTICAL COLORSTEEL 'EUROLINE' STANDINGSEAM ON SELECTED BUILDING WRAP ON MIN15mm PLYWOOD SUBSTRATE OVER 20mmCAVITY BATTENS ON BUILDING WRAP. REFERTO MANUFACTURERS DOCUMENTATION.
VERTICAL COLORSTEEL 'EUROLINE' STANDINGSEAM ON SELECTED BUILDING WRAP ON MIN15mm PLYWOOD SUBSTRATE OVER 20mmCAVITY BATTENS ON BUILDING WRAP. REFERTO MANUFACTURERS DOCUMENTATION.
XPRESSCLAD VENTED ZED RAIL FORFIXING BOTTOM OF F.C. CLADDING
9.0mm FIBRE CEMENT WALL CLADDINGWITH EXPRESSED JOINTS ON XPRESSCLADCAVITY BATTEN SYSTEM OVER 9.0mmETERPAN FIBRE CEMENT SHEETS AS RABON 140x45 MSG8 TIMBER FRAMING.
9.0mm FIBRE CEMENT WALL CLADDINGWITH EXPRESSED JOINTS ON XPRESSCLADCAVITY BATTEN SYSTEM OVER 9.0mmETERPAN FIBRE CEMENT SHEETS AS RABON 140x45 MSG8 TIMBER FRAMING.
BUTYL ROOFING MEMBRANE VERTICALLY UPSIDES ON 9mm TREATED PLYWOOD SUBSTRATEOR PRECAST CONCRETE PANELS WITH 20mmTREATED TRIANGULAR TIMBER FILLETS TO ALL90º UPSTANDS AS REQUIRED.
scale: 1:5detail: conc nib upstand / door sill
200mm THICK HOLLOWCORESTRUCTURAL FLOOR SYSTEM
LIQUID APPLIED BALCONYMEMBRANE OVER CONCRETESET TO 2º FALL TO EXTERIOR.
200mm THICK PRECASTCONC WALL PANELS
SELECTED ADHESIVE FIXEDTIMBER SKIRTING TRIM
19mm GIB FYRELINE WALL LININGON 19mm TIMBER PACKER ON DPCOVER CONC NIB UPSTAND TO LINEWITH 2x19mm FIRE RATED WALL.
WANZ SUPPORT BAR TO DOORFRAME, OSA.
COVED CORNER OVER BONDBREAKER
13mm STD GIB WALL LINING OVER140x45mm MSG8 TIMBER FRAMING
13mm STD GIB WALL LINING OVER140mm TIMBER FRAMING
150 PFC STEEL LOCATION WITHTIMBER PACKING TO SUIT. REFERTO STRUCT DOCUMENTATION.
DASHED LINES INDICATE 100 SHS POSTSWITHIN WALL FRAMING BEYOND.
scale: 1:5w indow detail: head / jamb to insitu conc
9.0mm FIBRE CEMENT CLADDING DOWNBACK FACE OF PARAPET, JUNCTION WITH16mm GIB FYRELINE WITH FIRE RATEDSEALANT.
LOW POINT
VENTED VERMIN TRAY MIN 20mm FROMBOTTOM OF CLADDING, FLASHING TAPEOVER TOP TO BUILDING WRAP.
COLORSTEEL FOLDED OVER FLASHING LAPSDOWN OVER BUTYL ROOFING MEMBRANEBELOW.
CLADDING ADHESIVE FIXED OVERFOLDED GALV BACK FLASHINGINTO SEALANT FILLED CHASE ONXPRESSCLAD ZED RAIL (XZR)
OUTLINE OF SADDLE FLASHING OVERSHOWN DASHED BELOW PARAPETCAP FLASHING.
SELECTED ADHESIVE FIXEDTIMBER SKIRTING TRIM
0.55 BMT FOLDED COLORSTEEL FLASHINGOVER ROOFING WITH MIN 2 CRESTS COVER,TURNED DOWN OVER STAND SEAM CLADDINGAS SHOWN
0.55 BMT V-RIB PROFILE COLORSTEELMETAL ROOFING OVER SELF-SUPPORTINGROOFING UNDERLAY. SCREW FIXED THRURIB CRESTS ONLY; ALLOW FOR THERMALMOVEMENT FIXING AS REQUIRED.
RESILIENT SHADOWLINE NEGATIVEAT CEILING TO WALL JUNCTIONS.
6.0mm FIBRE CEMENT SOFFITFOR PAINT FINISH
COLORSTEEL BACK FLASHINGDOWN OVER HEAD FLASHING
COLORSTEEL WINDOW HEADFLASHING
SELECTED PLASTER FINISH OVER 9mmJH MONOTEK FIBRE CEMENT SHEET WALLCLADDING SYSTEM ON 20mm NOM WALLCAVITY BATTENS OVER WALL UNDERLAY.ALL AS OUTLINED WITHIN SPECIFICATION.
0.55 BMT FOLDED COLORSTEEL FLASHINGOVER 9mm PLYWOOD SUBSTRATE TO 10ºSLOPE. UNDERLAY TO PROVIDE SEPARATIONOF FLASHING & TIMBER. FRONT EDGECONTINUES PAST 50mm AT SIDES.
POWDERCOATED CHANNEL TO FIX TOPOF LOUVRES INTO, FIXED THRU SOFFITINTO SOLID BLOCKING ABOVE.
DASHED LINES INDICATE LINE OF360UB PORTAL FRAME
13mm STD GIB WALL LINING OVER140x45mm MSG8 TIMBER FRAMING
100x50 RHS LINTEL VARIATIONDETAIL. REFER TO STRUCT.
2 LAYERS OF 60mm ETERCOREINSULATION WITHIN WALL FRAMING
140mm THICK WALL BATTS INSULATION.
LAP FLASHING TAPE DOWN OVERCAVITY CLOSER
VENTED VERMIN TRAY MIN 20mmFROM BOT. EDGE OF F.C. SHEET.
APL VANTAGE MAGNUM 50HINGED DOOR WITH DOUBLEGLAZING. POWDER COATFINISH
ALLPROOF 200x75 ROOF SCUPPERAS OVERFLOW THRU WALL CLADDING.
SILL FLASHING STOPENDED AT SIDESAND RETURNS AROUND CORNER AT FRONTEDGE INTO CAVITY.
SF
1:5 @A21:10@A4
A
A 13/11/13 BUILDING CONSENT ISSUE
N E W O F F I C E B U I L D I N G3 0 7 D U R H A M S T R E E T
DETAILS15/03/2013
4643
TH
A4.3
PR
ELI
MIN
AR
Y P
RIN
T | 1
4/11
/13
| 3:4
5 P
M
7.5
50
15
25
210
50
15 2
5
50
15
25
20
20
70 130
300 45
300
10
5
210
15
10
05
01
51
01
0
10
51
45
51
45
15
0
15
0
120/120/120 FIRE RATED WALL(NO UNPROTECTED OPENINGS),REFER FIRE ENGINEER
2no. LAYERS 19mm GIBFYRELINE. INSTALLED TO MEETGIB FIRE RATED WALL SYSTEMGBUW120
1
25mm GROOVED FOR LININGSREVEALS
FLASHING TAPE 100mmUPSTAND ON JAMBVANTAGE 40mm SERIES
ALUMINIUM FRAME WITHOPENING SASHES
DPC
SAW CUT 15mm DEEP x 6mmWIDE CHASE IN CONCRETE PANEL
CONTINUOUS BEAD OF FIRERATED ADHESIVE SEALANT
BACK FLASHING 70mm WIDE
XPRESSCLAD ZED RAIL
2no. LAYERS 19mm GIBFYRELINE. INSTALLED TO MEETGIB FIRE RATED WALL SYSTEMGBUW120POWDER COATED ALUMINIUM
FLASHING
25mm GROOVED FOR LININGSREVEALS
CONTINUOUS BEAD OF FIRERATED ADHESIVE SEALANT
SOLID BLOCKING TO SUIT FACADEPANEL AND BATTEN THICKNESSOVER
VANTAGE MAGNUM 50ALUMINIUM FRAME DOOR
1
9mm ETERPAN PANEL. EDGE TOBE SEALED BEFORE WINDOWINSTALLED
C
VANTAGE 40mm SERIESALUMINIUM FRAME
1
25mm GROOVED FOR LININGSREVEALS
1no. LAYER13mm STANDARD GIBWALL LINING ON TIMBERSTRAPPING ON PRECASTCONCRETE WALL
SELECTED 120 FIRE RATEDSTEEL GLAZING SYSTEM
FIRE RATED MASIC
CONTINUOUS FIRE RATED MASTIC
FIRE RATED MINERAL WOOL
9mm ETERPAN BASE PANEL ONFLAMESTOP 650 BUILDING WRAP
SOLID BLOCKING TO SUIT
1no. LAYER13mm STANDARD GIBWALL LINING ON TIMBERSTRAPPING ON PRECASTCONCRETE WALL (LIMITEDUNPROTECTED OPENINGS),REFER FIRE ENGINEER
25mm GROOVED FOR LININGSREVEALS
CONTINUOUS BEAD OF FIRERATED ADHESIVE SEALANT
ETERPAN 9mm
SAW CUT 15mm DEEP x 6mmWIDE CHASE IN CONCRETE PANEL
VANTAGE MAGNUM 50ALUMINIUM FRAME DOOR
C
25mm GROOVED FOR LININGSREVEALS
SELECTED 120 FIRE RATEDSTEEL GLAZING SYSTEM
CONTINUOUS FIRE RATEDMASTIC
FIRE RATED MINERAL WOOL
WATERPROOF LIQUIDMEMBRANE TO COMPLY WITHAS/NZS 4858
DRIP EDGE METAL ANGLECONTINUOUS FIRE RATEDMASTIC
120/120/120 FIRE RATEDPRECAST WALL (NOUNPROTECTED OPENINGS),REFER FIRE ENGINEER
40mm FOAMULAR EPS WALLINSULATION NEATLY FITTEDBETWEEN 70x45mm MSG8THICK TIMBER STRAPPING.
C
25mm GROOVED FOR LININGSREVEALS
SLOPED PRECASTCONCRETE SILL
CONTINUOUS FIRE RATEDMASTIC
FIRE RATED MINERAL WOOL
SILL MEMBRANE TO EXTENDUP JAMBS 40mm MIN. ANDAPPLIED CONTINUOUSLYACROSS FULL WIDTH OFOPENING
CONTINUOUS FIRE RATEDMASTIC
40mm FOAMULAR EPS WALLINSULATION NEATLY FITTEDBETWEEN 70x45mm MSG8THICK TIMBER STRAPPING.
DPC TO TIMBER STRAPPING
FIRE RATED CONTROL JOINT
2no. LAYERS 19mm GIBFYRELINE. INSTALLED TO MEETGIB FIRE RATED WALL SYSTEMGBUW120
FLASHING 70mm WIDE
1
25mm GROOVED FOR LININGSREVEALS
FLEXIBLE FLASHING TAPEVANTAGE 40mm SERIESALUMINIUM FRAME WITHOPENING SASHES
15x15 FOAM TAPE BY WINDOWINSTALLER
XPRESSCLAD HORIZONTALRUNNER
1
9mm ETERPAN BASE PANEL ONFLAMESTOP 650 BUILDINGWRAP. WRAP DRESSED INTOOPENING WITH FLEXIBLEFLASHING TAPE INSTALLED OVER
1
MIN
.TO
PAV
ED G
ROUN
D9mm ETERPAN BASE PANEL ONFLAMESTOP 650 BUILDING WRAP
9mm ETERPAN PANEL
INTERMEDIATE VERTICALRUNNERS @ 600 CRS MAX
XPRESSCLAD ZED RAIL
PANEL TAK ADHESIVESYSTEM WITH FOAM TAPE
MIN
.M
IN.
CONTINUOUS UNBROKEN LINE OFSEALANT BEHIND FLASHING &20mm STOP END
VANTAGE 40mm SERIESALUMINIUM FRAME WITHOPENING SASHES
MIN
.
9mm ETERPAN BASE PANEL ONFLAMESTOP 650 BUILDING WRAP
XPRESSCLAD ZED RAIL
PANEL TAK ADHESIVESYSTEM WITH FOAM TAPE
VENTILATED & DRAINEDCAVITY (20mm)
APPROVED AIRSEAL OVER PEFBACKING ROD
2no. LAYERS 19mm GIBFYRELINE. INSTALLED TO MEETGIB FIRE RATED WALL SYSTEMGBUW120
SUPPORT BLOCK BYWINDOW SUPPLIER
APPROVED AIRSEAL OVER PEFBACKING ROD
APPROVED AIRSEAL OVER PEFBACKING ROD
SLOPE PAVED AREA LEADINGUP TO DOOR ENTRY
EXPOSED AGGREGATE FIN.TO EXTERIOR PAVING
0.7mm POWDER COATEDALUMINIUM HEAD FLASHINGWITH 15deg FALL AND 10mmMIN. COVER TO WINDOWJOINERY
SELECTED 120 FIRE RATEDSTEEL GLAZING SYSTEM
EXPOSED AGGREGATE FIN.TO EXTERIOR PAVING
1A1.1
2A1.1
3A1.1
8A1.1
9A1.1
10A1.1
4A1.1
7A1.1
6A1.1
5A1.1
w indow detail: jamb to insitu conc
100 SHS CONCRETE FILLED POSTWITH INTUMESCENT PAINT TOEXTEND 100mm ABOVE ANDBELOW WINDOW SUPPORT STEEL,REFER STRUCTURAL & FIREENGINEER DOCUMENTATION
door detail: jamb to shs post
door detail: jamb to insitu conc
SCALE: 1:5FR R w indow detail: jamb to precast conc
SCALE: 1:5
SCALE: 1:5
SCALE: 1:5
SCALE: 1:5FR R w indow detail: head to precast conc
SCALE: 1:5FR R w indow detail: sill to precast conc
LINE OF PRECAST CONCRETEOVER
w indow detail: head to eterpan c laddingSCALE: 1:5
125 PFC BEAM WITHINTUMESCENT PAINT REFERSTRUCTURAL & FIRE ENGINEERDOCUMENTATION
100 SHS POST BEYONDINDICATED WITH DASHED LINE
door detail: f oundat ionSCALE: 1:5
f oundat ion detail: eterpan c laddingSCALE: 1:5
w indow detail: s ill/ jamb to eterpan c laddingSCALE: 1:5
100 SHS POST BEYONDINDICATED WITH DASHED LINE
125 PFC BEAM WITHINTUMESCENT PAINT REFERSTRUCTURAL & FIRE ENGINEERDOCUMENTATION
NOTE: SILL SUPPORT BAR TO SILLDETAIL UNDER WINDOW JOINERYWITH 5mm GAP TO WINDOWFLANGE AND PANEL
WANZ SUPPORT BAR TO DOORFRAME, OSA.
APL VANTAGE MAGNUM 50HINGED DOOR WITH DOUBLEGLAZING. POWDER COATFINISH
SF
1:5 @A21:10@A4
A
A 13/11/13 BUILDING CONSENT ISSUE
N E W O F F I C E B U I L D I N G3 0 7 D U R H A M S T R E E T
INTERIORS - BATHROOM15/03/2013
4643
TH
A5.1
PR
ELI
MIN
AR
Y P
RIN
T | 1
4/11
/13
| 3:4
5 P
M
3.14 m2
1.77 m2
90 1,450 500 90
90
1,1
75
47
59
0
90 1,950 90
90
1,6
50
90
46
070
07
50
90 225 750 975 90
160
40
07
60
1,0
00
1,0
00
500
30
0
1,0
00
45
47
54
75
90
45
95
09
0
1,0
00
1,0
00
450
90 1,950 90
90 1,950 90
EQEQ
10
65
02
03
70
45
09
75
10
10
35
06
70
1,8
05
10
07
60
10
30
90
05
00
90
01
00
2,4
00
350
600
10 1,790 650 360
1,800 1,010
10 1,170 620 650 360
1,6
50
65
01
00
77
59
0
2,8
35
1-
2-
3-
4-
SELECTED VINYLFLOORING
SCALE 1:25internal elevat ion1
•SCALE 1:25accessible wc plan - typical
SAFETY MIRROR WITH POLISHED EDGES
(400mm MIN)
(40
0m
m M
AX)
(MIN
. CLE
AR O
PENI
NG)
810 door leaf (MAX
)
50x10mm PAINTED TIMBER SKIRTING
SCALE 1:25internal elevat ion2
•
SELECTED SPLASHBACK
300mm HIGH STAINLESS STEELKICKPLATE TO CUBICLE SIDE OF DOORONLY
PRIVACY LATCH AND LOCKSET, REFERHARDWARE SCHEDULE
SELECTED GRAB RAIL ON CUBICLE SIDEOF DOOR
SIGNAGE TO EXTERNAL SIDE OF DOOR
s ignage
SCALE 1:25unisex wc plan - typical
660 door leaf
SCALE 1:25internal elevat ion3
•
SAFETY MIRROR WITHPOLISHED EDGES
(MAX
)
50x10mm PAINTED TIMBER SKIRTING
SELECTED SPLASHBACK
WC-1
TRH-1
WHB-1
WC-1
GR-1
WHB-1
TAP-1
WHB-2
TAP-1
WHB-1
TAP-1GR-2
GR-1
WC-2
WC-2
WHB-2
TRH-1
WC-1
WC-2
WHB-1
WHB-2
TAP-1
GR-1
TRH-1
GR-2
SD-1
SD-1
SD-1TAP-1
TAP-1
SCALE 1:25tea s ink - typical
SCALE 1:25internal elevat ion4
•
FF
FF
HWC
HWC
HWC
SNK
SNK
SNK
DW
DW
CUT
UTL
DW
FF
MW
MW
MW
adj
adj
adjadj
adj
adj
TAP
TAP
T-RAIL
BASKET
T-RAIL
BASKET
BIN
BIN
TRH-1
TRH-1
LINE OF WALL LINING SURROUND TO STEELPORTAL ON SECOND FLOOR ONLY
13mm STANDARD GIB PLASTERBOARDCEILING LINING WITH SELECTED SEMI-GLOSS ENAMEL PAINT FINISH
13mm STANDARD GIB PLASTERBOARDCEILING LINING WITH SELECTED SEMI-GLOSS ENAMEL PAINT FINISH
13mm STANDARD GIB PLASTERBOARDCEILING LINING WITH SELECTED SEMI-GLOSS ENAMEL PAINT FINISH
13mm GIB AQUALINE PLASTERBOARDCEILING LINING (TO WHB WALL ONLY) WITHSELECTED SEMI-GLOSS ENAMEL PAINTFINISH
SEAL PERIMETER OF WC TOSURROUNDING WALL AND FLOORSURFACE, USING A COMPATIBLE SILICONESEALANT
SEAL PERIMETER OF WHB TOSURROUNDING WALL SURFACE, USING ACOMPATIBLE SILICONE SEALANT
SEAL PERIMETER OF WHB TOSURROUNDING WALL SURFACE, USING ACOMPATIBLE SILICONE SEALANT
13mm GIB AQUALINE PLASTERBOARDCEILING LINING (TO WHB WALL ONLY) WITHSELECTED SEMI-GLOSS ENAMEL PAINTFINISH
13mm STANDARD GIB PLASTERBOARDWALL LINING (GENERALLY) WITHSELECTED SEMI-GLOSS ENAMEL PAINTFINISH
13mm STANDARD GIB PLASTERBOARDWALL LINING (GENERALLY) WITHSELECTED SEMI-GLOSS ENAMEL PAINTFINISH
broomcupboard
broomcupboard
19x19mm PAINTED TIMBER BEAD ATWALL AND CEILING JUNCTION JUNCTION
19x19mm PAINTED TIMBER BEAD ATWALL AND CEILING JUNCTION JUNCTION
2no. LAYERS 19mm GIB FYRELINEPLASTERBOARD WALL LINING INSTALLEDTO COMPLY WITH GIB FIRE RATEDPROTECTION OF STEEL COLUMN WITHSTEEL CLIP AND CHANNEL SYSTEM
10
04
70
15
01
40
10 3
03
50
40
0
bat hr oom f it t ings k ey
CAROMA 'OPAL' # 987073 WALL FACEDCLOSE-COUPLED TOILET SUITE
METHVEN 'ECHO CIRCA' WASH HANDBASIN MIXER
SELECTED 90 DEGREE GRAB RAIL -INSTALLED TO COMPLY WITH NZS 4121
BOBRICK B-2111 SOAP DISPENSER orSIMILAR APPROVED
SELECTED TOILET TISSUE DISPENSER -INSTALLED TO COMPLY WITH NZS 4121
CAROMA 'CARE 800' ACCESSIBLE WALLFACED CLOSE-COUPLED TOILET SUITE,INSTALLED TO COMPLY WITH NZS 4121
SELECTED GRAB RAIL -INSTALLED TOCOMPLY WITH NZS 4121
CAROMA 'FLORA 500' WALL BASIN WITHSHROUD
CAROMA 'FAUN 450' WALL BASIN WITHSHROUD
k it chenet t e f it t ings k ey
PRINCIPAL SUPPLIED, FISHER & PAYKELCOMPACT STAINLESS STEEL FRIDGE/FREEZER 248L, E249TRX
UNDERBENCH HOT WATER CYLINDER 45L,REFER MECHANICAL ENGINEER
'MERCER' AMPIO STAINLESS STEELRECTANGULAR BOWL SINK,455x305x170(D)mm
PRINCIPAL SUPPLIED, COMPACT 450mmWIDE DISHWASHER
PRINCIPAL SUPPLIED, MICROWAVE
'JAECO' 305mm CHROME TEA TOWEL RAILMOUNTED TO INSIDE OF DOOR PANEL,
'HAFELE' CHROME SOAP/CLEANERSBASKET MOUNTED TO INSIDE OF DOORPANEL
'HIDEAWAY' WASTE BIN PULL SYSTEM
SL
1:25@A21:50@A4
A
A 13/11/13 BUILDING CONSENT ISSUE
N E W O F F I C E B U I L D I N G3 0 7 D U R H A M S T R E E T
DOOR & WINDOWSCHEDULE
15/03/2013
4643
TH
A7.1
PR
ELI
MIN
AR
Y P
RIN
T | 1
4/11
/13
| 3:4
5 P
M
D0.1 (1 OFF) D0.2 (1 OFF) D0.3 (including W0.2, W0.3) (1 OFF)
W0.2 W0.3
D0.3
D2.1 (including W2.5, W2.6) (1 OFF)
W2.5 W2.6
D2.1
W1.1 (including W1.2, W1.3) (2 OFF)W2.1 (including W2.2, W2.3)
W1.1(W2.1)
W1.2(W2.2)
W1.3(W2.3)
910
1,555
120
12
02
20
2,5
50
1,0
00
910 EQ EQ EQ EQ
7,040
120
12
02
20
2,5
50
1,0
00
810
80
01
,30
0
7,390
120
12
02
20
2,1
00
1,0
00
50 450 450 EQ 450 EQ 450 EQ 450
80
01
,45
0
7,390
120
12
01
20
2,2
50
1,0
00
450 450 EQ 450 EQ 450 EQ 450
17
5
80
01
,60
0
9,750
2,4
00
450 450 EQ 450 EQ 450 EQ
450 450 450 450
450 810
90
01
,65
0
5A4.1
3A4.1
4A4.1
6A4.1
1A4.1
2A4.1
7A4.3
4A4.3
5A4.3
1A4.3
2A4.3
3A4.3
4A4.3
5A4.3
6A4.2
8A4.2
9A4.2
0.54 m2 0.54 m2 0.54 m2 0.54 m2 0.54 m2
1.66 m2
TOTAL OPENING AREA: 10.34 m2
DOOR NO.
NE
W D
OO
RS
EX
TE
RIO
R D
OO
RS
AL
UM
INIU
M
HARDWARE
GLAZING
FINISH
DOOR
FRAME
NOTES
LOCATION
REVEALS
ENTRY (EAST)
DOOR CLOSER
LATCH & LOCKSET, LEVER HANDLE, DOOR CLOSER,RAVEN THRESHOLD BAR FOR LEVEL THRESHOLD
VANTAGE MAGNUM 50 HINGED DOOR WITH SQUARE BEADGLAZED STILES. DOOR BOTTOM RAIL EXTENDER.
CLEAR LAMINATED DOUBLE GLAZED SAFETY GLASS TO COMPLYWITH NZS:4223
TENANCY 1 ENTRY (EAST)
SPANDREL PANELS TO BE SELECTED COLOUR TEMPACLAD (TC) TO OUTER PANE.ILLUMINATED EXIT SIGN OVER.3M FILM MANIFESTATION TO DOOR PANEL
TENANCY 1 / COURTYARD (WEST)
REVEALS
HARDWARE
GLAZING
FINISH
DOOR
FRAME
NOTES
LOCATION
DOOR NO.
EX
TE
RIO
R D
OO
RS
AL
UM
INIU
M
NE
W D
OO
RS
TENANCY 3 / BALCONY (WEST)
REVEALS
HARDWARE
GLAZING
FINISH
DOOR
FRAME
NOTES
LOCATION
WINDOW NO.
EX
TE
RIO
R W
IND
OW
SA
LU
MIN
IUM
NE
W W
IND
OW
S
TENANCY 2, TENANCY 3 (EAST)
-/120/120 FRR WALL - LIMITED UNPROTECTED OPENINGS
FIRE REPORT: THE MAXIMUM PERCENTAGE OF UNPROTECTED AREA FOR THE EXTERNAL WALL IS 30% OR 10m², WHICHEVER IS THE SMALLER.THE EXTERNAL WALLS INDICATED ON THE FIRE DRAWINGS SHALL BE FIRE RATED TO MEET THE ABOVE REQUIREMENTS.3M FILM MANIFESTATION TO DOOR PANEL
FIRE REPORT: THE MAXIMUM PERCENTAGE OF UNPROTECTED AREA FOR THE EXTERNAL WALL IS 30% OR 10m², WHICHEVER IS THE SMALLER.THE EXTERNAL WALLS INDICATED ON THE FIRE DRAWINGS SHALL BE FIRE RATED TO MEET THE ABOVE REQUIREMENTS.3M FILM MANIFESTATION TO DOOR PANEL
-/120/120 FRR WALL - LIMITED UNPROTECTED OPENINGS
ILLUMINATED EXIT SIGN OVER3M FILM MANIFESTATION TO DOOR PANEL
VANTAGE 100mm FLUSHGLAZE SUITE ALUMINIUM FRAME WITHSIDE HING OPENING WINDOWS AND MAGNUM 50 HINGED DOOR
LATCH & LOCKSET, LEVER HANDLE, DOOR CLOSER, RESTRICTOR STAYS TO OPENING SASHES,RAVEN THRESHOLD BAR FOR LEVEL THRESHOLD
DOOR CLOSER
CLEAR LAMINATED DOUBLE GLAZED SAFETY GLASS TO COMPLYWITH NZS:4223
VANTAGE MAGNUM 50 HINGED DOOR WITH SQUARE BEAD GLAZED STILES.DOOR BOTTOM RAIL EXTENDER.
25mm GROOVED FOR LININGS REVEALS
POWDER COATED ALUMINIUM FRAMES WITH PAINT FINISHREVEALS
VANTAGE 40mm SERIES ALUMINIUM FRAME WITH SIDE HUNGOPENING SASHES
VANTAGE 40mm SERIES ALUMINIUM FRAME WITH SIDE HUNGOPENING WINDOWS AND MAGMUM 50 HINGED DOOR
VANTAGE 100mm FLUSHGLAZE SUITE ALUMINIUM FRAME WITHMAGNUM 50 HINGED DOOR
25mm GROOVED FOR LININGS REVEALS
POWDER COATED ALUMINIUM FRAMES WITH PAINT FINISHREVEALS
LATCH & LOCKSET, LEVER HANDLE, DOOR CLOSER,RAVEN THRESHOLD BAR FOR LEVEL THRESHOLD
CLEAR LAMINATED DOUBLE GLAZED SAFETY GLASS TO COMPLYWITH NZS:4223
VANTAGE MAGNUM 50 HINGED DOOR WITH SQUARE BEAD GLAZED STILES.DOOR BOTTOM RAIL EXTENDER.
POWDER COATED ALUMINIUM FRAMES WITH PAINT FINISHREVEALS
DOOR CLOSER
DOOR CLOSER
25mm GROOVED FOR LININGS REVEALS
3M FILMMANIFESTATION(INDICATIVE ONLY)
3M FILMMANIFESTATION(INDICATIVE ONLY)
3M FILMMANIFESTATION(INDICATIVE ONLY)
3M FILMMANIFESTATION(INDICATIVE ONLY)
POWDER COATED ALUMINIUMFLASHING COVER TO STEEL POST,TO MATCH WINDOW JOINERYCOLOUR
POWDER COATED ALUMINIUMFLASHING COVER TO STEEL POST,TO MATCH WINDOW JOINERYCOLOUR
POWDER COATED ALUMINIUMFLASHING COVER TO STEEL POST,TO MATCH WINDOW JOINERYCOLOUR
POWDER COATED ALUMINIUMFLASHING COVER TO STEEL POST,TO MATCH WINDOW JOINERYCOLOUR
VANTAGE 40mm SERIES ALUMINIUM FRAME WITH SIDE HUNGOPENING WINDOWS AND MAGMUM 50 HINGED DOOR
LATCH & LOCKSET, LEVER HANDLE, DOOR CLOSER
CLEAR LAMINATED DOUBLE GLAZED SAFETY GLASS TO COMPLYWITH NZS:4223
VANTAGE MAGNUM 50 HINGED DOOR WITH SQUARE BEADGLAZED STILES
POWDER COATED ALUMINIUM FRAMES WITH PAINT FINISHREVEALS
25mm GROOVED FOR LININGS REVEALS
CLEAR LAMINATED DOUBLE GLAZED SAFETY GLASS TO COMPLYWITH NZS:4223
-
POWDER COATED ALUMINIUM FRAMES WITH PAINT FINISHREVEALS
25mm GROOVED FOR LININGS REVEALS
CONCRETE NIB UPSTAND
TC TC TC TC
d o o r n o t e sREFER TO FLOOR PLANS FOR DIRECTION OF DOORSWING.
1.
4.
5. FIX ALL PROPRIETARY ELEMENTS IN ACCORDANCEWITH THE DOOR MANUFACTURERSREQUIREMENTS.
SHOP DRAWINGS AND INSTALLATION DETAILS ARETO BE PROVIDED AND APPROVED BY ARCHITECTPRIOR TO MANUFACTURE.
6.
3.
REFER TO SOPERS FOR DOOR HARDWARE TYPEAND FINISH.
REFER TO FLOOR PLANS FOR WALL TYPES ANDTHICKNESS
2.
CHECK ALL OPENINGS ON SITE FOR SIZE ANDSTANDARD OF EXECUTION PRIOR TOMANUFACTURE. INSTALLATION TOLERANCESSUBJECT TO EARTHQUAKE DESIGN.
FLASHING, GENERALLY, TO MATCH WINDOWFRAMES. ENSURE MATERIALS USED FOR HEAD,JAMB & SILL FLASHINGS ARE COMPATIBLE WITHTHE WINDOW FRAME MATERIALS, FIXINGS ANDCLADDING MATERIALS.
7.
GLAZING TO MEET 'HUMAN IMPACT SAFETYREQUIREMENTS - NZS 4223.3
8.
9. GLAZING MANIFESTATIONS TO COMPLY WITH NZS4223.3
10. ALL REQUIRED STIFFENERS SHALL BE INTERNALAND TO BE APPROVED BY ARCHITECT
11. ALL HANDLES, LEVERS AND RECESSED PULLSSHALL BE CENTERED @ 1.0m AFL
12. ALLOW FOR WALL/FLOOR MOUNTED DOOR STOPSTO ALL DOORS.
SL
1:50@A21:100@A4
A
A 13/11/13 BUILDING CONSENT ISSUE
N E W O F F I C E B U I L D I N G3 0 7 D U R H A M S T R E E T
DOOR & WINDOWSCHEDULE
15/03/2013
4643
TH
A7.2
PR
ELI
MIN
AR
Y P
RIN
T | 1
4/11
/13
| 3:4
5 P
M
W0.1, W1.4, W2.5 (3 OFF)
W1.5 W1.6 W1.7
W1.5 (including W1.6, W1.7) (1 OFF)
D0.4 (1 OFF)
D0.5, D1.3, D2.3 (3 OFF) D0.6, D1.4, D2.4 (3 OFF) D0.7, D1.5, D2.5 (3 OFF)
D1.1, D2.2 (2 OFF) D1.2 (1 OFF)
fixed
W1.8 (1 OFF)
fixed80
01
,60
0
900
2,4
00
80
01
,30
0
7,390
2,1
00
50 450 50 450 EQ 450 EQ 450 EQ 450 50
1,330 100 4,950 100 910
650 650
1,9
00
45
1,405
1,9
45
1,0
00
810
2,0
50
1,0
00
810
2,0
50
1,0
00
710
2,0
50
1,0
00
810
3203201701
,63
01
70
1,0
00
1,9
60
20
0
30
0
20
0
810
1,200
320320170
1,6
30
17
0
2,2
00
1,0
00
1,9
60
970
15
02
,05
0
EQ 400 EQ
1,4
00
40
0
9A4.3
10A4.3
8A4.3
TOTAL OPENING AREA:9.61 m2
0.52 m2 0.52 m2
REVEALS
HARDWARE
GLAZING
FINISH
DOOR
FRAME
NOTES
LOCATION
WINDOW NO.
EX
TE
RIO
R W
IND
OW
SF
IRE
RA
TE
D -
ST
EE
L
NE
W W
IND
OW
S
TENANCY 1, TENANCY 2, TENANCY 3
-/120/120 FRR
-/120/120 FRR WALL - LIMITED UNPROTECTED OPENINGS
HARDWARE
GLAZING
FINISH
DOOR
FRAME
NOTES
LOCATION
DOOR NO.
INT
ER
IOR
DO
OR
S
NE
W D
OO
RS
STORE
WC LOBBY ACCESSIBLE WC WC
REVEALS
HARDWARE
GLAZING
FINISH
DOOR
FRAME
NOTES
LOCATION
DOOR NO.
INT
ER
IOR
DO
OR
SF
IRE
RA
TE
D -
TIM
BE
R
NE
W D
OO
RS
DOOR CLOSER
TENANCY 2 LOBBY, TENANCY 3 LOBBY
-/60/30sm FRR
TENANCY 2 LOBBY
smoke control only
REVEALS
HARDWARE
GLAZING
FINISH
DOOR
FRAME
NOTES
LOCATION
WINDOW NO.
EX
TE
RIO
R W
IND
OW
SA
LU
MIN
IUM
NE
W W
IND
OW
S
50mm GALVANISED STEEL SECTION WINDOW FRAME
POWDER COATED STEEL FRAMES WITH PAINT FINISH REVEALS
25mm GROOVED FOR LININGS REVEALS
-
PACIFIC VP60-P HINGED DOORSET WITH SIDELIGHT
PYROBEL 16 GLAZING WITH ALUMINIUM ANGLE GLAZING BEAD
42mm SELECTED TIMBER FRAME WITH PROFILE 'B' GROOVED FORLININGS REVEAL AND 30x20mm PLANTED STOP
48mm THICK SOLID CORE TIMBER DOOR STILES WITH SELECTEDTIMBER VENEER
REFER FIRE REPORT
SELECTED TIMBER VENEER DOOR FOR CLEAR FINISH,SELECTED TIMBER REVEAL FOR CLEAR FINISH
TIMBER FRAME HINGED DOORSET WITH SIDELIGHT
TOUGHENED SAFETY GLASS WITH ALUMINIUM ANGLE GLAZINGBEAD
42mm TIMBER FRAME WITH PROFILE 'B' GROOVED FOR LININGSREVEAL AND 30x20mm PLANTED STOP
40mm THICK SGG CONTRAFLAM GLASS WITH GALVANISEDSTEEL GLAZING BEADS
LATCH, LEVER HANDLE PRIVACY LATCH, LEVER HANDLE PRIVACY LATCH, LEVER HANDLE
SELECTED TIMBER VENEER DOOR FOR CLEAR FINISH,SELECTED TIMBER REVEAL FOR CLEAR FINISH
REFER FIRE REPORT
PAINT FINISH
-
MILK WHITE LAMINATED OBSURE VISION PANEL WITH SATINSILVER ANODISED BEAD
- -
38mm THICK SOLID CORE DOOR FOR PAINT FINISH 38mm THICK SOLID CORE DOOR FOR PAINT FINISH 38mm THICK SOLID CORE DOOR FOR PAINT FINISH
PAINT FINISH DOOR AND FRAME
REFER FIRE REPORT
LATCH & LOCKSET, REBATE KITSET, LEVER HANDLE, FLUSH BOLT,DUST SOCKET, DOOR CLOSERS
CLEAR LAMINATED DOUBLE GLAZED SAFETY GLASS TO COMPLY WITH NZS:4223
-
POWDER COATED ALUMINIUM FRAMES WITH PAINT FINISH REVEALS
25mm GROOVED FOR LININGS REVEALS
POWDER COATED ALUMINIUMFLASHING COVER TO STEEL POST
TENANCY 2
VANTAGE 40mm SERIES ALUMINIUM FRAME WITH SIDE HUNG OPENING SASHES
-/60/30sm FRR
REFER FIRE REPORT
DOOR CLOSER
PACIFIC VP60-P HINGED DOORSET
42mm TIMBER FRAME WITH PROFILE 'B' GROOVED FOR LININGSREVEAL AND 30x20mm PLANTED STOP
48mm THICK SOLID CORE TIMBER DOOR STILES WITH SELECTEDTIMBER VENEER
50mm THICK SOLID CORE TIMBER DOOR LEAF FOR PAINT FINISH
MAX
HEI
GHT
SID
ELIG
HT
MAX
HEI
GHT
VIS
ION
PANE
LDOOR LEAF
HEIG
HT T
O M
ATCH
FIR
E DO
OR A
DJAC
ENT
SMOKE SEALS, DOOR CLOSER, SMOKE CONTROL SIGNAGE
HEIG
HT T
O M
ATCH
FIR
E DO
OR A
DJAC
ENT
DOOR LEAF
300mm HIGHSTAINLESS STEELKICKPLATE TO CUBICLESIDE OF DOOR ONLY
GRABRAIL TO CUBICLESIDE OF DOOR ONLY
INTUMESCENT SMOKE SEALS TO FRAME
HARDWOOD TIMBER ARCHTRAVEOVER 13mm PLASTERBOARDBETWEEN FRAMES
REVEALS
HARDWARE
GLAZING
FINISH
DOOR
FRAME
NOTES
LOCATION
WINDOW NO.
INT
ER
IOR
WIN
DO
WS
NE
W W
IND
OW
S
TENANCY 2 LOBBY
25mm GROOVED FOR LININGS REVEALS
-
VANTAGE 40mm SERIES ALUMINIUM FRAME
CLEAR LAMINATED SINGLE GLAZED SAFETYGLASS TO COMPLY WITH NZS:4223
POWDER COATED ALUMINIUM FRAMES WITHPAINT FINISH REVEALS
DOOR CLOSERS
CIRCULAR VISION PANELWITH ALUMINIUMGLAZING BEAD
PAINT FINISH DOOR AND FRAME PAINT FINISH DOOR AND FRAME
40x150mm PINUS CLEARS TO SUIT LININGS OVER 90FRAMED WALL
REVEALS 40mm GROOVED FOR LININGS REVEALS 40mm GROOVED FOR LININGS REVEALS 40mm GROOVED FOR LININGS REVEALS
40x150mm PINUS CLEARS TO SUIT LININGS OVER 90FRAMED WALL
40x150mm PINUS CLEARS TO SUIT LININGS OVER 90FRAMED WALL
DOOR CLOSER, CERTIFICATION LABELS, FIRE DOOR SIGNAGE INTUMESCENT SMOKE SEALS TO FRAME
DOOR UNDERCUT, REFERMECHANICAL
DOOR UNDERCUT, REFER MECHANICAL ENGINEERSDOCUMENTATION FOR VENTILATION REQUIREMENTS
d o o r n o t e sREFER TO FLOOR PLANS FOR DIRECTION OF DOORSWING.
1.
4.
5. FIX ALL PROPRIETARY ELEMENTS IN ACCORDANCEWITH THE DOOR MANUFACTURERSREQUIREMENTS.
SHOP DRAWINGS AND INSTALLATION DETAILS ARETO BE PROVIDED AND APPROVED BY ARCHITECTPRIOR TO MANUFACTURE.
6.
3.
REFER TO SOPERS FOR DOOR HARDWARE TYPEAND FINISH.
REFER TO FLOOR PLANS FOR WALL TYPES ANDTHICKNESS
2.
CHECK ALL OPENINGS ON SITE FOR SIZE ANDSTANDARD OF EXECUTION PRIOR TOMANUFACTURE. INSTALLATION TOLERANCESSUBJECT TO EARTHQUAKE DESIGN.
FLASHING, GENERALLY, TO MATCH WINDOWFRAMES. ENSURE MATERIALS USED FOR HEAD,JAMB & SILL FLASHINGS ARE COMPATIBLE WITHTHE WINDOW FRAME MATERIALS, FIXINGS ANDCLADDING MATERIALS.
7.
GLAZING TO MEET 'HUMAN IMPACT SAFETYREQUIREMENTS - NZS 4223.3
8.
9. GLAZING MANIFESTATIONS TO COMPLY WITH NZS4223.3
10. ALL REQUIRED STIFFENERS SHALL BE INTERNALAND TO BE APPROVED BY ARCHITECT
11. ALL HANDLES, LEVERS AND RECESSED PULLSSHALL BE CENTERED @ 1.0m AFL
12. ALLOW FOR WALL/FLOOR MOUNTED DOOR STOPSTO ALL DOORS.
f i r e d o o r n o t e sSINGLE FIRE DOORS SHALL BE -/60/30smCERTIFIED FIRE DOORS COMPLETE WITH;
CLEAR FIRE RATED GLAZING, WHERE VISION PANELSPECIFED, (NOT GEORGIAN WIRED) TO HAVE A-/60/- FRR AND HAVE A SIZE NO GREATER THAN0.065m2
1.
REBATED INTUMESCENT SMOKE SEALS TO THETWO VERTICAL EDGES AND TOP EDGE OF THEDOOR FRAME
2.
DOOR CLOSER3.
MORTICE LATCH. ANY LOCKING SYSTEM SHALLNOT STOP THE DOOR FROM CLOSING WHEN IN THEACTIVE POSITION
4.
CERTIFICATION LABELS5.
FIRE DOOR SIGNAGE ON BOTH SIDES OF THE DOORSTATING ‘FIRE DOOR. PLEASE KEEP CLOSED.’THESE SHALL BE SMALL GREEN STICKERS WITHWHITE LETTERING.
6.
EGRESS DOORS ARE SHALL HAVE 760mmMINIMUM CLEAR OPENING
7.
REFER 'TM CONSULTANTS' FIRE ENGINEER FORFIRE RATED DOOR AND WINDOW SYSTEMS
f i r e w i n d o w n o t e sNORTH WALL FIRE WINDOWS SHALL BE -/120/120CERTIFIED FIRE WINDOW SYSTEMS
1.
REFER 'TM CONSULTANTS' FIRE ENGINEER FORFIRE RATED DOOR AND WINDOW SYSTEMS
THESE WINDOWS SHALL NOT BE OPENABLE
THE PANEL JOIN SEALANT USED IN THESE WALLSSHALL BE CERTIFIED TO PROVIDE NO LESS THAN ATWO WAY 120 MINUTE FIRE RESISTANCE RATING.
SL
1:50@A21:100@A4
A
A 13/11/13 BUILDING CONSENT ISSUE