NEW FANS SCHEDULE - Toronto · 2020-02-21 · kennels ground floor (cats holding rm. #120) carnes...
Transcript of NEW FANS SCHEDULE - Toronto · 2020-02-21 · kennels ground floor (cats holding rm. #120) carnes...
TAG
NEW FANS SCHEDULE
LOCATION MAKE & MODEL NO.
AIR FLOW
(L/S)
E.S.P.
(Pa.)
WATTS V / PH/ HZ
SOUND
EF-1
EF-2
EF-3
EF-4
EF-5
EF-6
KENNELS GROUND FLOOR
(CATS HOLDING RM. #120)
CARNES
VIBK12M1A1CL20S
410 1365 250 115/1/60
410 50115/1/60
410 50115/1/60
190 50115/1/60
190 50115/1/60
40 50
115/1/60
EF-7
120 50 115/1/60
EF-8
135 50 115/1/60
EF-9
160 50 115/1/60
EF-10
175 50 115/1/60
EF-11
150 50 115/1/60
EF-12
160 50 115/1/60
EF-13
120 50 115/1/60
EF-14
30 50 115/1/60
EF-15 ADMINISTATION OFFICE AREA
LAV RM. #108
60 50 115/1/60
CARNES
VCDD015CA
EF-16
180 50 115/1/60
-
EF-17
525 50 115/1/60
EF-18
120 50 115/1/60
EF-19 KENNELS BASEMENT
ROOM #B7
385 50
115/1/60
EF-20
410 50
115/1/60
EF-21
110 50
115/1/60
EF-22
30 50
115/1/60
-
EF-23
120 50
115/1/60
-
EF-24
120 50
115/1/60
300x200
300x200
~ ~
~
~
~~
~ ~
300x150-100
~ ~
~
~~
~ ~
~
~~
SHEET METAL DUCT - 300mm WIDE x 200mm HIGH
SHEET METAL RISER UP - SUPPLY
SHEET METAL RISER UP - RETURN AND EXHAUST
SHEET METAL RISER DOWN - SUPPLY
SQUARE ELBOW WITH AIR TURNING VANES
DUCT RISES
FUSIBLE LINK FIRE DAMPER WITH
ACCESS DOOR IN DUCT
SIDE-WALL GRILLE
EXHAUST / RETURN / TRANSFER AIR GRILLE
CEILING SUPPLY AIR DIFFUSER
FOR GRILLES AND DIFFUSERS:
"300x150" DENOTES SIZE
"100" DENOTES AIR QUANTITY IN L/S
BRANCH TAKE-OFF WITH ADJUSTABLE
SPLITTER DAMPER IN SUPPLY DUCT
SHORT BRANCH SUPPLY DUCT TAKE-OFF
WITH TURNING VANES
OPEN ENDED DUCT WITH BALANCING
DAMPER AND BELLMOUTH INLET
FLEXIBLE CONNECTION
INTERNAL ACOUSTICALLY LINED DUCT
FLEXIBLE DUCT
MANUAL BALANCING DAMPER
BD
MECHANICAL SYMBOLS
AD
ACCESS DOOR
FLEXIBLE DUCT CONNECTION C/W BD
ON BRANCH TAKE-OFF
SHEET METAL RISER DOWN -
RETURN AND EXHAUST
EXISTING TO BE DEMOLISHED
~ ~
NEW WORK
~ ~
EXISTING TO REMAIN
~ ~
MECHANICAL DRAWING LIST
DRAWING NUMBER DRAWING TITLE
M-1 SYMBOL LIST, DRAWING LIST, SCHEDULES AND DETAILS - MECHANICAL
M-2 ADMINISTRATION OFFICE AREA - GROUND FLOOR - HVAC DEMOLITION LAYOUT
M-3
M-4
M
MOTORIZED DAMPER
IN-LINE EXHAUST FAN C/W FILTER BOX
CABINET TYPE EXHAUST FAN
ABBREVIATIONS
SYMBOL DESCRIPTION
AC
AIR CONDITIONING UNIT (INDOOR)
A.F.F ABOVE FINISHED FLOOR
BD MANUAL BALANCING DAMPER
C/W COMPLETE WITH
CTE CONNECT TO EXISTING
DN DOWN
E/A EXHAUST AIR
OED OPEN ENDED DUCT C/W BD
FLD FUSIBLE LINK DAMPER
MD MOTORIZED DAMPER
O/A OUTDOOR AIR
RG REFRIGERANT GAS
S/A SUPPLY AIR
GC GENERAL CONTRACTOR
ELECTRICAL POWER
ALL IN-LINE FANS SHALL BE SUPPLIED WITH LOOSE FILTER BOX (C/W PULL OUT DISPOSABLE TYPE FILTERS) WITH BOTTOM ACCESS, BACK DRAFT DAMPER, SPRING TYPE VIBRATION ISOLATORS C/W
ADAPTERS AND SCREWS ETC FOR FIELD ASSEMBLY. DISCONNECT SWITCH SHALL BE FACTORY INSTALLED ON THE FAN HOUSING. MOTOR ORIENTATION SHALL MATCH EXISTING. T.S.P IS INCLUSIVE
OF DUCTWORK E.S.P, STATIC PRESSURE ACROSS FILTER AND BACK DRAFT DAMPER. WEIGHT INCLUDES FILTER BOX.
WIRING BY ELECTRICAL CONTRACTOR.
EF-13, 23 & 24 SHALL BE SUPPLIED WITH LOOSE CONTINUOUS SPEED CONTROLLER, LOOSE CEILING GRILLE AND SPRING TYPE VIBRATION ISOLATORS C/W ADAPTERS AND SCREWS ETC FOR FIELD
ASSEMBLY. BACK DRAFT DAMPER AND DISCONNECT SWITCH SHALL BE FACTORY INSTALLED ON THE FAN HOUSING. T.S.P IS INCLUSIVE OF DUCTWORK E.S.P AND BACK DRAFT DAMPER. WIRING BY
ELECTRICAL CONTRACTOR.
SF-A AND SF-B: SHALL BE SUPPLIED WITH LOOSE COMBINATION FAN AND LIGHT SWITCH. FANS SHALL BE SUSPENDED FROM EXISTING CEILING STRUCTURE AT 4500mm A.F.F. WIRING BY ELECTRICAL
CONTRACTOR.
4. MOTORS FOR IN-LINE FANS SHALL BE INSTALLED EITHER ABOVE OR ON THE SIDE OF THE EXHAUST FAN HOUSING AND NOT BELOW THE FAN.
5. EF-8 DOES NOT REQUIRE FILTER AND SHALL BE PROVIDED WITH ANTI-RUST COATING.
6. MECHANICAL CONTRACTOR SHALL SUPPLY CONTROLLERS, MOTOR STARTERS AND WEATHER-PROOF COVERS AND HAND-OVER TO ELECTRICAL CONTRACTOR FOR INSTALLATION AND WIRING.
7. SWITCH FOR EF-6, 14, 15 AND 22 SHALL BE PROVIDED AND WIRED BY ELECTRICAL CONTRACTOR.
1. DRAWINGS SHALL BE USED FOR REFERENCE ONLY TO PROVIDE A GENERAL OUTLINE OF THE SCOPE
OF WORK. THE DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE SPECIFICATIONS AND ALL
OTHER DRAWINGS AND DOCUMENTS ISSUED AS PART OF THIS PROJECT.
2. PRIOR TO SUBMISSION OF BID, COMMENCEMENT OF WORK, ORDERING OF EQUIPMENT AND/OR
FABRICATION OF MATERIALS, THE CONTRACTOR SHALL VISIT THE SITE TO VERIFY EXISTING
CONDITIONS. THIS SHALL BE DONE IN ORDER TO CONFIRM THAT EQUIPMENT AND SERVICES CAN BE
INSTALLED AS SHOWN ON DRAWINGS. IT IS THE CONTRACTORS RESPONSIBILITY TO NOTIFY THE
CONSULTANT OF ANY DISCREPANCIES, OMISSIONS OR INTERFERENCES PRIOR TO COMMENCEMENT
OF WORK. PROVIDE INTERFERENCE DRAWINGS. INCLUDE FOR ALL COSTS RELATED TO COORDINATION
OF OTHER TRADES' WORK.
5. PRIOR TO COMMENCING INSTALLATION OF NEW EQUIPMENT, CLEAN ALL EXISTING SUPPLY AIR,
RETURN AIR AND EXHAUST AIR DUCTWORK AND ASSOCIATED GRILLES. REPLACE EXISTING DAMAGED
OR DISTURBED DUCT INSULATION TO MATCH EXISTING. PRIOR TO CLEANING PROVIDE CLEANING
SCHEDULE AND PROCEDURE TO OWNER AND CONSULTANT FOR REVIEW. ISOLATE DUCTWORK IN THE
AREA THAT IS BEING CLEANED SUCH THAT ADJACENT AREAS ARE NOT AFFECTED.
6. PROVIDE NEW DUCT INSULATION UPTO 3 METERS FROM EXTERIOR OUTLET IF EXISTING INSULATION IS
MISSING. REPAIR DAMAGED / TORN EXISTING INSULATION.
7. ENSURE THAT ALL EQUIPMENT REQUIRING MAINTENANCE IS ACCESSIBLE. REPORT ANY
OBSTRUCTIONS TO THE CONSULTANT.
8. DUCTWORK AND EQUIPMENT SHALL BE INDEPENDENTLY SUPPORTED WITH PROPER SUPPORTS AND
VIBRATION ISOLATORS SECURED TO THE EXISTING BUILDING STRUCTURE. CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL DUCT MODIFICATIONS TO CONNECT THE NEW EXHAUST FANS TO THE EXISTING
DUCTWORK INCLUDING NEW FLEXIBLE CONNECTIONS AT THE INLET AND OUTLET OF EACH FAN.
9. FOR CLARITY, NOT ALL EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. HAS BEEN SHOWN ON THE
DRAWINGS. THE EXISTING EQUIPMENT AND DUCTWORK ARE SHOWN FOR REFERENCE ONLY. EXACT
LOCATIONS, SIZES AND DIMENSIONS SHALL BE DETERMINED ON SITE.
10. FIRESTOP PENETRATIONS THROUGH FIRE RATED ASSEMBLY. FIRESTOPPING ASSEMBLY SHALL BE ULC
LISTED AND SUITABLE FOR THE SPECIFIC APPLICATION.
11. CONTRACTOR SHALL PROVIDE NEW FIRE-RATED ACCESS DOORS FOR ALL EXHAUST FANS LOCATED
ABOVE GYPSUM BOARD CEILING. SIZE AND LOCATION OF THE ACCESS DOORS SHALL BE SUITABLE TO
ACCESS FAN COMPONENTS INCLUDING FAN WHEEL, MOTOR, CONTROLS, UNIT MOUNTED DISCONNECT
SWITCH AND FILTER HOUSING, ETC. CONTRACTOR SHALL BE RESPONSIBLE FOR MAKING GOOD
GYPSUM BOARD CEILINGS WHERE DAMAGE OR OVERCUTTING OCCURS.
12. ELEVATOR CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DEMOLITION AND NEW WORK RELATED TO
THE HYDRAULIC PUMP, MOTOR, ELEVATOR SYSTEM POWER PIPING, ELEVATOR SYSTEM CONTROL
WIRING, WIRING WITHIN ELEVATOR CAB, ETC.
13. ELEVATOR RELATED WORK CAN BE SCHEDULED ANY TIME ON WEEK DAYS, WEEKENDS AND HOLIDAYS.
14. WORK IN ADMINISTRATION BUILDING OFFICES AND FOYER SHALL BE SCHEDULED BETWEEN THE
HOURS OF 6:30 PM TO 6:30 AM ON WEEKDAYS AND ANYTIME ON WEEKENDS AND HOLIDAYS.
15. WORK IN ALL OTHER AREAS SHALL BE SCHEDULED BETWEEN THE HOURS OF 7 AM TO 6 PM ON
WEEKDAYS.
BDD BACKDRAFT DAMPER
CLG CEILING
GYP GYPSUM BOARD CEILING
AD ACCESS DOOR
GENERAL NOTES
T ROOM THERMOSTAT
FD
FD
EF
12
"EF" DENOTES EXHAUST FAN
"12" DENOTES EQUIPMENT NUMBER 12
EF EXHAUST FAN
~~
SOLID DUCT CONNECTION C/W BD
ON BRANCH TAKE-OFF
~
~ ~
DUCT TRANSITION
~ ~
BD
DOOR UNDER CUT
~~
INSULATED DUCT
~~
~
AND FLEX. CONNECTORS
C/W FLEX. CONNECTOR
KENNELS
LINK ADMINISTRATION
HEALTH CARE
AMPHITHEATRE
MECH.
AIR WELL
PROGRESS AVENUE
CENTRE
SITE PLAN
T/A TRANSFER AIR
FLOOR DRAIN
AREA FLOOR DRAIN
FUNNEL FLOOR DRAIN
KENNELS - BASEMENT FLOOR - HVAC DEMOLITION LAYOUT
KENNELS - GROUND FLOOR - HVAC DEMOLITION LAYOUT
HEALTH CARE CENTRE - GROUND FLOOR - HVAC DEMOLITION LAYOUT AND NEW WORK LAYOUTM-5
M-6 ADMINISTRATION OFFICE AREA - GROUND FLOOR - HVAC NEW WORK LAYOUT
M-7
M-8
KENNELS - BASEMENT FLOOR - HVAC NEW WORK LAYOUT
KENNELS - GROUND FLOOR - HVAC NEW WORK LAYOUT
NOT TO SCALE
NOTES:
TYPE
IN-LINE
IN-LINE
IN-LINE
IN-LINE
IN-LINE
IN-LINE
IN-LINE
IN-LINE
IN-LINE
IN-LINE
IN-LINE
IN-LINE
CABINET
CABINET
CABINET
IN-LINE
IN-LINE
IN-LINE
IN-LINE
IN-LINE
IN-LINE
CABINET
CABINET
CARNES
VIBK12M1A1CL20S
250
CARNES
VIBK12M1A1CL20S
250
KENNELS GROUND FLOOR
(STRAY DOGS RM. #121)
KENNELS GROUND FLOOR
(DOGS ADOPTION RM. #122)
FAN SPEED
(RPM)
50
1365
1365
102710
ADMINISTATION OFFICE AREA
LAV RM. #102
CARNES
VCDK008CS11
351500
HEALTH CARE CENTRE
LAV RM #137
CARNES
VCDK008CS11
351500
CABINET
ADMINISTATION OFFICE AREA
LUNCH RM. #106
CARNES
VCDD030CA
207905
HEALTH CARE CENTRE
TREATMENT RM #140
CARNES
VCDD030CA
207905
HEALTH CARE CENTRE
WARD RM #141
207905
KENNELS GROUND FLOOR
(MENS LAV / LOCKERS
RM. # 130 AND 131)
CARNES
VIBK08L1A1CL20S 1901747
CARNES
VIBK08L1A1CL20S 1901747
CARNES
VIBK08L1A1CL20S
941266
KENNELS GROUND FLOOR
(JANITOR RM # 128)
KENNELS GROUND FLOOR
(WOMENS LAV / LOCKERS
RM. # 132 AND 133)
KENNELS GROUND FLOOR
(FOOD PREP RM. # 125)
CARNES
VIBK08K4A1CL20S
1251639
KENNELS GROUND FLOOR
(DISHWASHER RM. # 124)
CARNES
VIBK08K4A1CL20S
1251655
175
175
50
175
175
175
175
175
175
50
50
50
175
175
175
175
175
175
50
50
75
175
175
175
T.S.P.
(Pa.)
KENNELS GROUND FLOOR
(CAT ISOLATION RM. # 118)
CARNES
VIBK08L1A1CL20S
1901691
KENNELS GROUND FLOOR
(STRAY CATS RM. # 117)
CARNES
VIBK08L1A1CL20S1901719
KENNELS GROUND FLOOR
(KITTENS / EXOTICS / TREATMENT
RM. # 114, 115 AND 116)
CARNES
VIBK08L1A1CL20S
1901673
WEIGHT
(KG)LWA SONES
ADMINISTATION OFFICE AREA
CAT BUBBLE RM. #111
CARNES
VIBK06K5A1CL20S
1901691
KENNELS BASEMENT
(CAT QUARANTINE / NURSERY
RM. # B13 AND B14)
CARNES
VIBK08L1A1CL20S
1901727
CARNES
VIBK15M1A1CL20S
2501016
KENNELS BASEMENT
(DOG ISOLATION AND QUARANTINE
RM. # B10 AND B11)
KENNELS BASEMENT
(ISOLATION AND CAT TREATMENT
RM. # B8 AND B9)
CARNES
VIBK15M1A1CL20S
1251639
~~
REFRIGERANT PIPING
~ PIPE TURNING DOWN
PIPE TURNING UP~
RS
~~
REFRIGERANT PIPING
RL
~~
CONDENSATE PIPING
CD
T
PROGRAMMABLE ROOM TEMPERATURE
SENSOR AND CONTROLLER
RL REFRIGERANT LIQUID
R/A RETURN AIR
ABV ABOVE
ACU
AIR COOLED CONDENSING UNIT (OUTDOOR)
N.T.S NOT TO SCALE
SCHEDULE OF SPLIT AIR CONDITIONING SYSTEM
MANUFACTURER REFRIGERANT
INDOOR UNIT OUTDOOR UNIT
TAG MODEL LOCATION
AREA
SERVED
FLOW (L/S)
(H/M/L)
COOLING
WEIGHT
(KG)
TAG MODEL LOCATION
OPERATING
RANGE
(°C)
EER /
SEER
ELECTRICAL
WEIGHT
(KG)
EAT (°C) LAT (°C)
CAPACITY
(KW)
V/PH/Hz MCA MOCP
DB WB DB WB
MITSUBISHI
ELECTRIC
R-410A AC-1 PKA-A12HA7
ELEVATOR
EQUIPMENT
ROOM (B6)
ELEVATOR
EQUIPMENT
ROOM (B6)
150/174/200 26.6 18.3 12.7 12.2 3.5 13 ACU-1
PUY-
A12NKA7-BS
GARAGE (B1)
-28.9 TO 46 12 / 20.8 208/1/60 11 28 41
NOTES:
1. ALTERNATE MANUFACTURERS MUST MEET ALL DESIGN CONDITIONS AND CAPACITIES FOR INDOOR AND OUTDOOR UNITS.
2. SYSTEM TO BE AHRI 1230-2010 CERTIFIED.
3. INDOOR UNIT AND OUTDOOR UNIT SHALL BE WALL MOUNTED (AT 2100 MM A.F.F).
4. SOUND PRESSURE LEVELS SHALL NOT EXCEED 43 dB(A) FOR INDOOR UNIT AND 44 dB(A FOR OUTDOOR UNIT.
5. POWER SHALL BE SUPPLIED ONLY TO THE OUTDOOR UNIT. INDOOR UNIT SHALL BE POWERED VIA OUTDOOR UNIT.
6. INDOOR UNIT SHALL BE C/W LOW VOLTAGE TRANSFORMER TO SERVE PROGRAMMABLE ROOM TEMPERATURE SENSOR AND CONTROLLER SUPPLIED WITH SYSTEM.
SCHEDULE OF GRILLES
TYPE SIZE
E.H.PRICE
STEEL CONSTRUCTION, 20 MM BLADE SPACING,
SURFACE MOUNT, BLADES PARALLEL TO LONG
DIMENSION, COUNTER SUNK SCREW HOLES.
M-9 DETAILS AND SCHEMATIC - MECHANICAL
45 68 8.2
45 68 8.2
45 68 8.2
ESP EXTERNAL STATIC PRESSURE
45 69 8.3
45 69 8.3
35 63 6.0
35 67 7.4
35 67 7.5
35 68 7.8
35 68 8.1
35 67 7.7
35 68 7.8
10 56 3.1
5 52 2.4
7 50 2.0
35 68 8.2
50 65 7.0
35 67 7.4
CARNES
VIBK10M1A1CL20S
250145245 69 8.4
CARNES
VIBK12L1A1CL20S
190145245 68 8.2
CARNES
VIBK08K4A1CL20S
1251629 35 67 7.3
5 52 2.4
9 56 3.1
9 56 3.1
CARNES
VCDD030CA
SF-A - -115/1/60
SF-B
CEILING
ADMINISTRATION OFFICE AREA
FOYER #103
BIG ASS FAN
"HAIKU" - L SERIES
0.7 AMPS400-10 - -
- -115/1/60
CEILING
ADMINISTRATION OFFICE AREA
FOYER #103
0.7 AMPS400-10 - -
KENNELS BASEMENT
ROOM #B1
KENNELS BASEMENT
ROOM #B1
1.
2.
3.
BIG ASS FAN
"HAIKU" - L SERIES
CEILING DESTRATIFICATION
CIRCULATION FAN WITH LIGHT
MOTOR STARTER
TOGGLE
TYPE
KEYED
TYPE
NOT REQUIRED
NOT REQUIRED
NOT REQUIRED
NOT REQUIRED
NOT REQUIRED
NOT REQUIRED
WEATHERPROOF
COVER
YES YES
YES YES
YES YES
YES
YES
YES YES
YES YES
YES YES
YES YES
YES YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
SYMBOL LIST, DRAWING
LIST, SCHEDULES AND
DETAILS - MECHANICAL
M-1
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALL
APPLICABLE CODES AND REQUIREMENTS OF
AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT
SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST
ASSUME FULL RESPONSIBILITY AND BEAR COSTS
FOR ANY CORRECTIONS OR DAMAGES RESULTING
FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS
PROVIDED BY AND IS THE PROPERTY OF THE
WSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPT
RESPONSIBILITY FOR ALL DIMENSIONS AND
CONDITIONS ON SITE AND SHALL NOTIFY THE
APPROPRIATE CONSULTANT OF ANY VARIATIONS
FROM THE SUPPLIED INFORMATION.
Project
Name:
CONSULTANT
19/12/2014 10:27:13 AM
821 PROGRESS AVENUE
SCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
600 Cochrane Drive, 5th Floor
Markham, ON L3R 5K3
t. 905-475-7270 f. 905-475-5994
www.wsp.com
FIRE ALARM UPGRADE,
EXHAUST FANS REPLACEMENT
AND ELEVATOR MODERNIZATION
G.V T.N
AS NOTED
TORONTO
ANIMAL SERVICES
EAST DISTRICT
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
400x400
300x300
250X150
400x400
300x300
T
T
EF
12
EF
15
4
0
0
x
3
5
0
300x300
AC
3
EF
14
1
5
0
Ø
39 L/S
T
T
4
0
0
x
4
0
0
40
0Ø
RTU
5
T
40
0Ø
500Ø
EF
A
C
D
B
E
F
1
A
23456789
CAT BUBBLE
111
LINK
112
VESTIBULE
102
RECEPTION
FOYER
103
LUNCH ROOM
106
CORRIDOR
110
MANAGER
105
LECTURE ROOM
104
OFFICE
103
LAV
108
LAV
102
VESTIBULE
101
CAT ADOPTION
600x600 ACCESS DOOR FOR
ENTRANCE TO ATTIC
LOCATED ABOVE CEILING
AD
AD
200x200 CEILING
ACCESS DOOR
MANAGER
OFFICE
EXISTING FLOOR MOUNTED
S/A REGISTER
(TYPICAL)
42 L/S 42 L/S
39 L/S
EXISTING CEILING R/A GRILLES
(1200x600-755 L/S)
62 L/S
62 L/S
62 L/S 62 L/S 62 L/S 62 L/S
EXISTING CEILING MOUNTED
S/A REGISTER (TYPICAL)
151 L/S
151 L/S
151 L/S
151 L/S
151 L/S
100 L/S
100 L/S
100 L/S
(TO AC-3)
DUCTWORK ROUTED
IN ATTIC (TYPICAL)
250x250
DRAWING NOTES:
1
2 MECHANICALLY CLEAN AND VACUUM EXISTING E/A DUCTWORK.
3 REPLACE EXISTING DAMAGED OR DISTURBED DUCT INSULATION TO
MATCH EXISTING.
4 VACUUM CLEAN EXISTING INDOOR CEILING E/A GRILLE.
5 VACUUM CLEAN EXISTING OUTDOOR SOFFIT T/A GRILLE.
1
2
32
4
5
56 L/S
56 L/S
56 L/S
69 L/S69 L/S69 L/S
76 L/S76 L/S
T
(FRONT
OFFICE +
CAT BUBBLE)
75 L/S
75 L/S
EXISTING FLOOR MOUNTED
S/A REGISTER
(TYPICAL)
900x900-755 L/S
30 L/S
23
5
1
5
23
120 L/S
EF
13
60 L/S
5
S/A AND R/A DUCT UP TO
RTU ON ROOF
EXISTING DUCT MOUNTED S/A REGISTER
750x150-157 L/S
(TYPICAL OF 6)
200x200-47 L/S
70 L/S
1
GRADE MOUNTED AIR COOLED
CONDENSING UNIT SERVING AC-3
FO
R C
ON
TIN
UA
TIO
N R
EF
ER
T
O D
RA
WIN
G M
-3
2 3
REMOVE EXISTING EXHAUST FAN AND SECTION OF DUCTWORK AS SHOWN
C/W ASSOCIATED SPRING ISOLATORS. DIVISION 26 SHALL BE RESPONSIBLE
FOR DISCONNECTION OF POWER AND REMOVAL OF OBSOLETE ANCILLARY
DEVICES SUCH AS WALL MOUNTED SWITCHES.
1
6 MECHANICALLY CLEAN AND VACUUM EXISTING S/A DUCTWORK.
7
6
6
6
EXISTING UNDER-SLAB
S/A DUCT
(TYPICAL)
(TYPICAL)
(TYPICAL)
(TYPICAL)
6
(TYPICAL)
8 VACUUM CLEAN EXISTING R/A GRILLE.
MECHANICALLY CLEAN AND VACUUM EXISTING R/A DUCTWORK.
7
9
(TYPICAL)
8
9
(TYPICAL)
6
(TYPICAL)
EXISTING UNDER-SLAB
S/A DUCT
(TYPICAL)
EXISTING UNDER-SLAB
S/A DUCT
(TYPICAL)
9 VACUUM CLEAN EXISTING S/A GRILLE.
8
7
ADMINISTRATION OFFICE
AREA - GROUND FLOOR -
HVAC DEMOLITION LAYOUT
M-2
1
M-2
SCALE: 1:50
ADMINISTRATION OFFICE AREA - GROUND FLOOR - HVAC DEMOLITION LAYOUT
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALL
APPLICABLE CODES AND REQUIREMENTS OF
AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT
SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST
ASSUME FULL RESPONSIBILITY AND BEAR COSTS
FOR ANY CORRECTIONS OR DAMAGES RESULTING
FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS
PROVIDED BY AND IS THE PROPERTY OF THE
WSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPT
RESPONSIBILITY FOR ALL DIMENSIONS AND
CONDITIONS ON SITE AND SHALL NOTIFY THE
APPROPRIATE CONSULTANT OF ANY VARIATIONS
FROM THE SUPPLIED INFORMATION.
Project
Name:
CONSULTANT
19/12/2014 10:27:13 AM
821 PROGRESS AVENUE
SCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
600 Cochrane Drive, 5th Floor
Markham, ON L3R 5K3
t. 905-475-7270 f. 905-475-5994
www.wsp.com
FIRE ALARM UPGRADE,
EXHAUST FANS REPLACEMENT
AND ELEVATOR MODERNIZATION
G.V T.N
AS NOTED
TORONTO
ANIMAL SERVICES
EAST DISTRICT
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
AHU
1
80
0x6
50
95
0x3
50
500x300
350x300 200x100
25
0x2
50
35
0x2
00
EF
19
EF
18
35
0x2
50
EF
17
30
0x2
50
25
0x1
50
35
0x2
50
EF
16
25
0x2
50
250x150
EF
21
M
EF
20
M
900x350
J L
11
10
9
KHGExDxDCyCx
LITTER STORAGE
B-2
GARAGE
B1
FREEZER
B3
FOOD STORAGE
B4
STORAGE
B6
ELEV. EQPT.
B8
CREMATORIUM
B7
DOG QUARANTINE
B11
RECORDS
B12
DOG ISOLATION
B10
CORRIDOR
B-17
NURSERY
B14
CAT QUARANTINE
B13
OPEN AREA FOR
MECHANICAL UNITS
TREATMENT
ROOM #2
B9
AD
AD
AD
GENERAL
ISOLATION
B8
AD
AD
OVER HEAD DOOR
OVER HEAD DOOR
RO
LL
-U
P S
HU
TT
ER
D
OO
R
RO
LL
-U
P S
HU
TT
ER
D
OO
R
ADAD
ELECTRICAL /
FIRE ALARM
ROOM
B15
ELEVATOR
STAIR
No.1
AC
1
AC
2
FOR CONTINUATION REFER TO DRAWING M-2
EXISTING 350x350 S/A DUCTS
TO ADMIN BUILDING
EXISTING 400x400 R/A DUCTS UP
C/W FD AT SLAB
EXISTING DUCT MOUNTED
D/X COOLING COILS
500EXISTING O/A
INTAKE LOUVER
EXISTING AIR COOLED
CONDENSING UNITS
SERVING AC-1 AND AC-2
EXISTING 350x900 S/A DUCT UP
C/W FD AT SLAB
300x300-225 L/S
200x200-80 L/S
300x300-245 L/S
200x200-90 L/S
200x200-80 L/S
30
0x3
00
T/A GRILLE
DN TO 300mm AFF
300x250-250 L/S
300x250-275 L/S
FD
FD
FD FD
1
1
2
2
23
23
2
2
2
2
2
2
4
4
150x150-55 L/S
23 23
200x200-60 L/S 200x200-60 L/S
FD
400x300-385 L/S
1
1
2
2
2
350x500-410 L/S
44
4
4
4
5
5
5
350x250
350x250
EXISTING WALL MOUNTED
AIR COOLED CONDENSING
UNIT SERVING FREEZER
REMOVE EXISTING 300x200 T/A GRILLE
LOCATED ABOVE DOOR
300x600 O/A
INTAKE
LOUVER
300x600 O/A
INTAKE
LOUVER
1
4
2
23
300x150-110 L/S
1
2
5
4
2
EXISTING MAKE-UP AIR UNIT
EXISTING MOTORIZED DAMPER
INTERLOCKED WITH EF-20
EXISTING MOTORIZED DAMPER
INTERLOCKED WITH EF-20
200x200-90 L/S
DRAWING NOTES:
1
2 MECHANICALLY CLEAN AND VACUUM EXISTING E/A DUCTWORK.
3 REPLACE EXISTING DAMAGED OR DISTURBED DUCT INSULATION TO
MATCH EXISTING.
4 VACUUM CLEAN EXISTING INDOOR CEILING E/A GRILLE.
5 VACUUM CLEAN EXISTING OUTDOOR SOFFIT T/A GRILLE.
REMOVE EXISTING EXHAUST FAN AND SECTION OF DUCTWORK AS SHOWN
C/W ASSOCIATED SPRING ISOLATORS. DIVISION 26 SHALL BE RESPONSIBLE
FOR DISCONNECTION OF POWER AND REMOVAL OF OBSOLETE ANCILLARY
DEVICES SUCH AS WALL MOUNTED SWITCHES.
6 MECHANICALLY CLEAN AND VACUUM EXISTING S/A DUCTWORK.
6
(TYPICAL)
6
(TYPICAL)
6
(TYPICAL)
5
(TYPICAL)
6
(TYPICAL)
7 MECHANICALLY CLEAN AND VACUUM EXISTING R/A DUCTWORK.
6
7
(TYPICAL)
KENNELS - BASEMENT FLOOR
- HVAC DEMOLITION LAYOUT
M-3
1
M-3
SCALE: 1:50
KENNELS - BASEMENT FLOOR - HVAC DEMOLITION LAYOUT
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALL
APPLICABLE CODES AND REQUIREMENTS OF
AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT
SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST
ASSUME FULL RESPONSIBILITY AND BEAR COSTS
FOR ANY CORRECTIONS OR DAMAGES RESULTING
FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS
PROVIDED BY AND IS THE PROPERTY OF THE
WSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPT
RESPONSIBILITY FOR ALL DIMENSIONS AND
CONDITIONS ON SITE AND SHALL NOTIFY THE
APPROPRIATE CONSULTANT OF ANY VARIATIONS
FROM THE SUPPLIED INFORMATION.
Project
Name:
CONSULTANT
19/12/2014 10:27:13 AM
821 PROGRESS AVENUE
SCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
600 Cochrane Drive, 5th Floor
Markham, ON L3R 5K3
t. 905-475-7270 f. 905-475-5994
www.wsp.com
FIRE ALARM UPGRADE,
EXHAUST FANS REPLACEMENT
AND ELEVATOR MODERNIZATION
G.V T.N
AS NOTED
TORONTO
ANIMAL SERVICES
EAST DISTRICT
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
90
0x3
50
EF
11
550x350
200x200
200x200
200x200
200x200
2
0
0
x
1
5
0
15
0x1
50
EF
1
350x250
30
0x2
50
30
0x2
50
30
0x2
50
450x350 450x300
20
0x2
00
300x300
200x200
200x200
250x200
EF
4
EF
6
EF
7
EF
8
EF
9
250x200
EF
10
200x200
J L
11
10
9
KHGExDxDCyCx
FOOD PREP.
125
CORRIDOR
123
DISH WASHER
124
CATS ISOLATION
118
STRAY CATS
117
EXOTICS
115
TREATMENT ROOM
116
KITTENS
114
CORRIDOR
113
CATS HOLDING
120
STRAY DOGS
121
DOGS ADOPTION
122
CORRIDOR
129
LOCKERS
133
WOMEN
132
MEN
130
LOCKERS
131
JANITOR
128
STAIR
No.1
ELEVATOR
CREMATORIUM FLUE
CHIMNEY
AD
600x600 ACCESS DOOR
FOR SOUTH ATTIC
ENTRANCE LOCATED
ABOVE CEILING
AD
600x600 ACCESS DOOR
FOR NORTH ATTIC
ENTRANCE LOCATED
ABOVE CEILING
AD
600x600 ACCESS DOOR
FOR WEST ATTIC
ENTRANCE LOCATED
ABOVE CEILING
STORAGE
126
450x450 ACCESS DOOR
FOR WEST ATTIC
ENTRANCE LOCATED
ABOVE CEILING
AD
MECHANICAL AIR WELL
AD
1200x600-755 L/S
400x400 R/A DUCTS DN
350x900 S/A
FROM BELOW
5
1
2
2 3
450x450-410 L/S 4
EF
2
350x250
5
1
2
2 3
450x450-410 L/S 4
EF
3
350x250
5
1
2
2 3
450x450-410 L/S 4
200x200-95 L/S
200x200-95 L/S
4 4
5
2
1
250x250-170 L/S
250x250-170 L/S
250x200
EF
5
200x200-95 L/S
4 4
5
2
1
200x200-95 L/S
32
4
5
32
150x150-40 L/S
2
350x350-365 L/S350x350-365 L/S350x350-365 L/S
200x200-125 L/S
200x200-140 L/S
250x250-155 L/S
150x150-45 L/S
150x150-45 L/S
5
32
2 4
2
1
1
4
32
5
GRADE MOUNTED AIR COOLED
CONDENSING UNITS SERVING
AHU-1 D/X COOLING COILS
4
2
2
5
3
250x200
1
1
4
2
2
3
5
150x150
(TYPICAL)
4
4
4
2
2
2
3
1
250x250-120 L/S
250x250-135 L/S
200x200
200x200150x150
300x300-160 L/S
300x300-175 L/S
150x150-50 L/S
(TYPICAL)
FOR CONTINUATION
REFER TO DRAWING M-2
200x200-105 L/S
32
DRAWING NOTES:
1
2 MECHANICALLY CLEAN AND VACUUM EXISTING E/A DUCTWORK.
3 REPLACE EXISTING DAMAGED OR DISTURBED DUCT INSULATION TO
MATCH EXISTING.
4 VACUUM CLEAN EXISTING INDOOR CEILING E/A GRILLE.
5 VACUUM CLEAN EXISTING OUTDOOR SOFFIT T/A GRILLE.
REMOVE EXISTING EXHAUST FAN AND SECTION OF DUCTWORK AS SHOWN
C/W ASSOCIATED SPRING ISOLATORS. DIVISION 26 SHALL BE RESPONSIBLE
FOR DISCONNECTION OF POWER AND REMOVAL OF OBSOLETE ANCILLARY
DEVICES SUCH AS WALL MOUNTED SWITCHES.
6 MECHANICALLY CLEAN AND VACUUM EXISTING S/A DUCTWORK.
6
(TYPICAL)
6
(TYPICAL)
7 VACUUM CLEAN EXISTING S/A DIFFUSER.
7
(TYPICAL)
7
(TYPICAL)
KENNELS - GROUND FLOOR
- HVAC DEMOLITION LAYOUT
M-4
1
M-4
SCALE: 1:50
KENNELS - GROUND FLOOR - HVAC DEMOLITION LAYOUT
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALL
APPLICABLE CODES AND REQUIREMENTS OF
AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT
SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST
ASSUME FULL RESPONSIBILITY AND BEAR COSTS
FOR ANY CORRECTIONS OR DAMAGES RESULTING
FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS
PROVIDED BY AND IS THE PROPERTY OF THE
WSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPT
RESPONSIBILITY FOR ALL DIMENSIONS AND
CONDITIONS ON SITE AND SHALL NOTIFY THE
APPROPRIATE CONSULTANT OF ANY VARIATIONS
FROM THE SUPPLIED INFORMATION.
Project
Name:
CONSULTANT
19/12/2014 10:27:13 AM
821 PROGRESS AVENUE
SCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
600 Cochrane Drive, 5th Floor
Markham, ON L3R 5K3
t. 905-475-7270 f. 905-475-5994
www.wsp.com
FIRE ALARM UPGRADE,
EXHAUST FANS REPLACEMENT
AND ELEVATOR MODERNIZATION
G.V T.N
AS NOTED
TORONTO
ANIMAL SERVICES
EAST DISTRICT
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
EXAM
136
RECEPTION
134
EXAM
135
WARD
141
VEST.
143
ELECTRICAL
PANEL
TREATMENT
140
SURGERY
139
LAV.
137
D/W.
RUN
142
750x750
ACCESS DOOR
AC
4
3
5
0
x
3
0
0
1
7
5
Ø
150Ø
2
2
5
Ø
1
5
0
Ø
3
5
0
x
2
0
0
EF
23
200Ø
175Ø
2
2
5
Ø
EF
22
T
(TO A/C-4)
GRADE MOUNTED AIR COOLED
CONDENSING UNITS SERVING AC-4
600x600-565 L/S
1
EF
24
2
3
4
200x200-65 L/S
400x200-125 L/S
200x200-70 L/S
1
4
2
3
150x150-35 L/S
200x200-55 L/S
400x200-135 L/S
120 L/S
1
2
3
4
200x200-120 L/S
200x200-120 L/S
150x150-30 L/S
250x150-80 L/S
30 L/S
120 L/S
DRAWING NOTES:
1
2 MECHANICALLY CLEAN AND VACUUM EXISTING E/A DUCTWORK.
3 REPLACE EXISTING DAMAGED OR DISTURBED DUCT INSULATION TO
MATCH EXISTING.
4VACUUM CLEAN EXISTING OUTDOOR SOFFIT T/A GRILLE.
REMOVE EXISTING EXHAUST FAN AND SECTION OF DUCTWORK AS SHOWN
C/W ASSOCIATED SPRING ISOLATORS. DIVISION 26 SHALL BE RESPONSIBLE
FOR DISCONNECTION OF POWER AND REMOVAL OF OBSOLETE ANCILLARY
DEVICES SUCH AS WALL MOUNTED SWITCHES.
5 MECHANICALLY CLEAN AND VACUUM EXISTING S/A DUCTWORK.
5
(TYPICAL)
6 MECHANICALLY CLEAN AND VACUUM EXISTING R/A DUCTWORK.
6
7VACUUM CLEAN EXISTING S/A DIFFUSER.
7
(TYPICAL)
8VACUUM CLEAN EXISTING R/A GRILLE.
8
EF
23
EF
22
EF
24
EXAM
136
RECEPTION
134
EXAM
135
WARD
141
VEST.
143
ELECTRICAL
PANEL
TREATMENT
140
SURGERY
139
LAV.
137
D/W.
RUN
142
750x750
ACCESS DOOR
AC
4
3
5
0
x
3
0
0
1
7
5
Ø
150Ø
2
2
5
Ø
1
5
0
Ø
3
5
0
x
2
0
0
200Ø
175Ø
2
2
5
Ø
T
(TO A/C-4)
GRADE MOUNTED AIR COOLED
CONDENSING UNITS SERVING AC-4
600x600-565 L/S
200x200-65 L/S
400x200-125 L/S
200x200-70 L/S
150x150-35 L/S
200x200-55 L/S
400x200-135 L/S
200x200-120 L/S
200x200-120 L/S
150x150-30 L/S
250x150-80 L/S
DRAWING NOTES:
1 PROVIDE NEW EXHAUST FAN C/W EXHAUST GRILLE. VIBRATION SPRING ISOLATORS (SUPPLIED LOOSE BY THE FAN SUPPLIER)
SHALL BE SUPPORTED FROM EXISTING HANGER RODS. REFER TO DETAIL 2 ON DRAWING M-9. MAKE-GOOD DISRUPTED OR
DAMAGED CEILING. DIVISION 26 SHALL PROVIDE WIRING TO DISCONNECT SWITCH (FACTORY MOUNTED ON FAN HOUSING)
AND MANUAL (MOTOR) STARTER (SUPPLIED BY DIVISION 23).
2 REPLACE EXISTING DAMAGED OR DISTURBED DUCT INSULATION TO MATCH EXISTING. PROVIDE NEW DUCT INSULATION UP TO
3 METERS FROM EXTERIOR OUTLET IF EXISTING INSULATION IS MISSING.
2
1
2
1
2
3
1
3
3
30 L/S
120 L/S
120 L/S
HEALTH CARE CENTRE
- GROUND FLOOR - HVAC
DEMOLITION LAYOUT AND
NEW WORK LAYOUT
M-5
1
M-5
SCALE: 1:50
HEALTH CARE CENTRE - GROUND FLOOR - HVAC DEMOLITION LAYOUT
2
M-5
SCALE: 1:50
HEALTH CARE CENTER - GROUND FLOOR - HVAC NEW WORK LAYOUT
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALL
APPLICABLE CODES AND REQUIREMENTS OF
AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT
SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST
ASSUME FULL RESPONSIBILITY AND BEAR COSTS
FOR ANY CORRECTIONS OR DAMAGES RESULTING
FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS
PROVIDED BY AND IS THE PROPERTY OF THE
WSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPT
RESPONSIBILITY FOR ALL DIMENSIONS AND
CONDITIONS ON SITE AND SHALL NOTIFY THE
APPROPRIATE CONSULTANT OF ANY VARIATIONS
FROM THE SUPPLIED INFORMATION.
Project
Name:
CONSULTANT
19/12/2014 10:27:13 AM
821 PROGRESS AVENUE
SCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
600 Cochrane Drive, 5th Floor
Markham, ON L3R 5K3
t. 905-475-7270 f. 905-475-5994
www.wsp.com
FIRE ALARM UPGRADE,
EXHAUST FANS REPLACEMENT
AND ELEVATOR MODERNIZATION
G.V T.N
AS NOTED
TORONTO
ANIMAL SERVICES
EAST DISTRICT
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
400x400
300x300
250X150
400x400
300x300
T
T
4
0
0
x
3
5
0
300x300
AC
3
1
5
0
Ø
39 L/S
T
T
4
0
0
x
4
0
0
40
0Ø
RTU
5
T
40
0Ø
500Ø
EF
A
C
D
B
E
F
1
A
23456789
CAT BUBBLE
111
LINK
112
VESTIBULE
102
RECEPTION
FOYER
103
LUNCH ROOM
106
CORRIDOR
110
MANAGER
105
LECTURE ROOM
104
OFFICE
103
LAV
108
LAV
102
VESTIBULE
101
CAT ADOPTION
600x600 ACCESS DOOR FOR
ENTRANCE TO ATTIC
LOCATED ABOVE CEILING
AD
AD
200x200 CEILING
ACCESS DOOR
MANAGER
OFFICE
EXISTING FLOOR MOUNTED
S/A REGISTER
(TYPICAL)
42 L/S 42 L/S
39 L/S
EXISTING CEILING R/A GRILLES
(1200x600-755 L/S)
62 L/S
62 L/S
62 L/S 62 L/S 62 L/S 62 L/S
EXISTING CEILING MOUNTED
S/A REGISTER (TYPICAL)
151 L/S
151 L/S
151 L/S
151 L/S
151 L/S
100 L/S
100 L/S
100 L/S
(TO AC-3)
DUCTWORK ROUTED
IN ATTIC (TYPICAL)
250x250
56 L/S
56 L/S
56 L/S
69 L/S69 L/S69 L/S
76 L/S76 L/S
T
(FRONT
OFFICE +
CAT BUBBLE)
75 L/S
75 L/S
EXISTING FLOOR MOUNTED
S/A REGISTER
(TYPICAL)
900x900-755 L/S
S/A AND R/A DUCT UP TO
RTU ON ROOF
EXISTING DUCT MOUNTED S/A REGISTER
750x150-157 L/S
(TYPICAL OF 6)
200x200-47 L/S
70 L/S
GRADE MOUNTED AIR COOLED
CONDENSING UNIT SERVING AC-3
FO
R C
ON
TIN
UA
TIO
N R
EF
ER
T
O D
RA
WIN
G M
-3
EXISTING UNDER-SLAB
S/A DUCT
(TYPICAL)
EXISTING UNDER-SLAB
S/A DUCT
(TYPICAL)
EXISTING UNDER-SLAB
S/A DUCT
(TYPICAL)
DRAWING NOTES:
1 PROVIDE NEW EXHAUST FAN. FILTER BOX, BDD AND VIBRATION ISOLATORS SHALL BE SUPPLIED LOOSE BY THE EXHAUST FAN
SUPPLIER. FILTER BOX AND BDD SHALL BE CONNECTED TO THE EXHAUST FAN HOUSING BY CONTRACTOR ON SITE.
VIBRATION ISOLATORS SHALL BE SUPPORTED FROM EXISTING HANGER RODS. PROVIDE NEW ACCESS DOOR. (SIZE AND
LOCATION OF THE ACCESS DOORS SHALL BE SUITABLE TO ACCESS FAN COMPONENTS INCLUDING FAN WHEEL, MOTOR,
CONTROLS, DISCONNECT SWITCH AND FILTER HOUSING, ETC). REFER TO DETAIL 1 ON DRAWING M-9. MAKE-GOOD DISRUPTED
OR DAMAGED CEILING. DIVISION 26 SHALL PROVIDE WIRING TO THE DISCONNECT SWITCH (FACTORY MOUNTED ON FAN
HOUSING) AND MANUAL (MOTOR) STARTER (SUPPLIED BY DIVISION 23).
2
3 REPAIR TORN OR DAMAGED EXISTING DUCT INSULATION. PROVIDE NEW DUCT INSULATION UPTO MAXIMUM 3 METERS FROM
THE EXTERIOR OUTLET IF EXISTING DUCT IS NOT INSULATED.
120 L/S
PROVIDE NEW EXHAUST FAN C/W EXHAUST GRILLE. VIBRATION SPRING ISOLATORS (SUPPLIED LOOSE BY THE FAN SUPPLIER)
SHALL BE SUPPORTED FROM EXISTING HANGER RODS. REFER TO DETAIL 2 ON DRAWING M-9. MAKE-GOOD DISRUPTED OR
DAMAGED CEILING. DIVISION 26 SHALL PROVIDE WIRING TO DISCONNECT SWITCH (FACTORY MOUNTED ON FAN HOUSING)
AND MANUAL (MOTOR) STARTER (SUPPLIED BY DIVISION 23).
2
30 L/S
60 L/S
EF
15
EF
14
EF
13
2
1
EF
12
33
3
3
(BALANCE EXISTING
E/A GRILLE TO 160 L/S)
4 PROVIDE NEW DESTRATIFICATION CIRCULATION SUPPLY FAN SUSPENDED FROM EXISTING CEILING STRUCTURE, MOUNTED AT
4500 MM A.F.F. FAN SHALL BE PROVIDED WITH DOWN ROD, SAFETY CHAIN, POWER CORD AND 120 VOLT FAN SPEED AND LIGHT
CONTROLLER AND ALL OTHER REQUIRED MOUNTING AND SECURING HARDWARE. WIRING TO THE CONTROLLER SHALL BE
PROVIDED BY DIVISION 26.
2
SF
A
SF
B
4
4
PROVIDE TYPE "A" 300x300 T/A GRILLE IN CEILING C/W 300x300 OPEN ENDED DUCT WITH ELBOW
C/W INTERNAL ACOUSTIC LINING.
5
5
ADMINISTRATION OFFICE
AREA - GROUND FLOOR -
HVAC NEW WORK LAYOUT
M-6
1
M-6
SCALE: 1:50
ADMINISTRATION OFFICE AREA - GROUND FLOOR - NEW WORK LAYOUT
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALL
APPLICABLE CODES AND REQUIREMENTS OF
AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT
SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST
ASSUME FULL RESPONSIBILITY AND BEAR COSTS
FOR ANY CORRECTIONS OR DAMAGES RESULTING
FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS
PROVIDED BY AND IS THE PROPERTY OF THE
WSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPT
RESPONSIBILITY FOR ALL DIMENSIONS AND
CONDITIONS ON SITE AND SHALL NOTIFY THE
APPROPRIATE CONSULTANT OF ANY VARIATIONS
FROM THE SUPPLIED INFORMATION.
Project
Name:
CONSULTANT
19/12/2014 10:27:13 AM
821 PROGRESS AVENUE
SCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
600 Cochrane Drive, 5th Floor
Markham, ON L3R 5K3
t. 905-475-7270 f. 905-475-5994
www.wsp.com
FIRE ALARM UPGRADE,
EXHAUST FANS REPLACEMENT
AND ELEVATOR MODERNIZATION
G.V T.N
AS NOTED
TORONTO
ANIMAL SERVICES
EAST DISTRICT
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
AHU
1
80
0x6
50
95
0x3
50
500x300
350x300 200x100
25
0x2
50
35
0x2
00
35
0x2
50
30
0x2
50
25
0x1
50
35
0x2
50
25
0x2
50
250x150
M
M
900x350
J L
11
10
9
KHGExDxDCyCx
LITTER STORAGE
B-2
GARAGE
B1
FREEZER
B3
FOOD STORAGE
B4
STORAGE
B6
ELEV. EQPT.
B8
CREMATORIUM
B7
DOG QUARANTINE
B11
RECORDS
B12
DOG ISOLATION
B10
CORRIDOR
B-17
NURSERY
B14
CAT QUARANTINE
B13
OPEN AREA FOR
MECHANICAL UNITS
TREATMENT
ROOM #2
B9
AD
AD
AD
GENERAL
ISOLATION
B8
AD
AD
OVER HEAD DOOR
OVER HEAD DOOR
RO
LL
-U
P S
HU
TT
ER
D
OO
R
RO
LL
-U
P S
HU
TT
ER
D
OO
R
ADAD
ELECTRICAL /
FIRE ALARM
ROOM
B15
ELEVATOR
STAIR
No.1
AC
1
AC
2
FOR CONTINUATION REFER TO DRAWING M-2
EXISTING 350x350 S/A DUCTS
TO ADMIN BUILDING
EXISTING 400x400 R/A DUCTS UP
C/W FD AT SLAB
EXISTING DUCT MOUNTED
D/X COOLING COILS
500EXISTING O/A
INTAKE LOUVER
EXISTING AIR COOLED
CONDENSING UNITS
SERVING AC-1 AND AC-2
EXISTING 350x900 S/A DUCT UP
C/W FD AT SLAB
300x300-225 L/S
200x200-80 L/S
300x300-245 L/S
200x200-90 L/S
200x200-80 L/S
30
0x3
00
T/A GRILLE
DN TO 300mm AFF
300x250-250 L/S
300x250-275 L/S
FD
FD
FD FD
150x150-55 L/S
200x200-60 L/S 200x200-60 L/S
FD
400x300-385 L/S
350x500-410 L/S
350x250
350x250
EXISTING WALL MOUNTED
AIR COOLED CONDENSING
UNIT SERVING FREEZER
300x600 O/A
INTAKE
LOUVER
300x600 O/A
INTAKE
LOUVER
300x150-110 L/S
EXISTING MAKE-UP AIR UNIT
EXISTING MOTORIZED DAMPER
INTERLOCKED WITH EF-20
EXISTING MOTORIZED DAMPER
INTERLOCKED WITH EF-20
200x200-90 L/S
DRAWING NOTES:
1 PROVIDE NEW EXHAUST FAN. FILTER BOX, BDD AND VIBRATION ISOLATORS SHALL BE SUPPLIED LOOSE BY
THE EXHAUST FAN SUPPLIER. FILTER BOX AND BDD SHALL BE CONNECTED TO THE EXHAUST FAN HOUSING
BY CONTRACTOR ON SITE. VIBRATION ISOLATORS SHALL BE SUPPORTED FROM EXISTING HANGER RODS.
PROVIDE NEW ACCESS DOOR. (SIZE AND LOCATION OF THE ACCESS DOORS SHALL BE SUITABLE TO ACCESS
FAN COMPONENTS INCLUDING FAN WHEEL, MOTOR, CONTROLS, DISCONNECT SWITCH AND FILTER HOUSING,
ETC). REFER TO DETAIL 1 ON DRAWING M-9. MAKE-GOOD DISRUPTED OR DAMAGED CEILING. DIVISION 26
SHALL PROVIDE WIRING TO THE DISCONNECT SWITCH (FACTORY MOUNTED ON FAN HOUSING) AND MANUAL
(MOTOR) STARTER (SUPPLIED BY DIVISION 23).
2 REPAIR TORN OR DAMAGED EXISTING DUCT INSULATION. PROVIDE NEW DUCT INSULATION UPTO
MAXIMUM 3 METERS FROM THE EXTERIOR OUTLET IF EXISTING DUCT IS NOT INSULATED.
AC-1
(WALL MOUNTED)
CD
FD
T
ACU-1
(WALL MOUNTED)
EF
18
EF
17
EF
16
EF
21
EF
20
EF
19
11
1
1
1
2
2
2
2
4
5
6
7
8 9
3
12mm CONDENSATE PIPE C/W INSULATION, ROUTED ALONG THE WALL AND DROP OVER
FUNNEL FLOOR DRAIN.
5
REPLACE EXISTING OPEN DRAIN WITH NEW FUNNEL FLOOR DRAIN.4
PROVIDE TYPE "A" 300x200 T/A GRILLES AT WALL OPENING ABOVE DOOR.6
PROVIDE TRANSFER AIR DUCT C/W FIRE DAMPER.7
PROGRAMMABLE TEMPERATURE SENSOR AND CONTROLLER SERVING SPLIT AC SYSTEM.8
REFRIGERANT PIPING C/W INSULATION ROUTED ALONG THE WALL.9
REFER TO DETAIL 3 ON DRAWING M-9.
10
3
10
REFER TO DETAIL 4 ON DRAWING M-9.
PROPOSED LOCATION
OF HYDRAULIC
EQUIPMENT
11 REFER TO DETAIL 5 ON DRAWING M-9.
11
11
11
KENNELS - BASEMENT FLOOR
- HVAC NEW WORK LAYOUT
M-7
1
M-7
SCALE: 1:50
KENNELS - BASEMENT FLOOR - HVAC NEW WORK LAYOUT
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALL
APPLICABLE CODES AND REQUIREMENTS OF
AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT
SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST
ASSUME FULL RESPONSIBILITY AND BEAR COSTS
FOR ANY CORRECTIONS OR DAMAGES RESULTING
FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS
PROVIDED BY AND IS THE PROPERTY OF THE
WSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPT
RESPONSIBILITY FOR ALL DIMENSIONS AND
CONDITIONS ON SITE AND SHALL NOTIFY THE
APPROPRIATE CONSULTANT OF ANY VARIATIONS
FROM THE SUPPLIED INFORMATION.
Project
Name:
CONSULTANT
19/12/2014 10:27:13 AM
821 PROGRESS AVENUE
SCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
600 Cochrane Drive, 5th Floor
Markham, ON L3R 5K3
t. 905-475-7270 f. 905-475-5994
www.wsp.com
FIRE ALARM UPGRADE,
EXHAUST FANS REPLACEMENT
AND ELEVATOR MODERNIZATION
G.V T.N
AS NOTED
TORONTO
ANIMAL SERVICES
EAST DISTRICT
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
J L
11
10
9
KHGExDxDCyCx
FOOD PREP.
125
CORRIDOR
123
DISH WASHER
124
CATS ISOLATION
118
STRAY CATS
117
EXOTICS
115
TREATMENT ROOM
116
KITTENS
114
CORRIDOR
113
CATS HOLDING
120
STRAY DOGS
121
DOGS ADOPTION
122
CORRIDOR
129
LOCKERS
133
WOMEN
132
MEN
130
LOCKERS
131
JANITOR
128
STAIR
No.1
ELEVATOR
CREMATORIUM FLUE
CHIMNEY
AD
600x600 ACCESS DOOR
FOR SOUTH ATTIC
ENTRANCE LOCATED
ABOVE CEILING
AD
600x600 ACCESS DOOR
FOR NORTH ATTIC
ENTRANCE LOCATED
ABOVE CEILING
AD
600x600 ACCESS DOOR
FOR WEST ATTIC
ENTRANCE LOCATED
ABOVE CEILING
STORAGE
126
450x450 ACCESS DOOR
FOR WEST ATTIC
ENTRANCE LOCATED
ABOVE CEILING
AD
MECHANICAL AIR WELL
AD
90
0x3
50
550x350
200x200
200x200
200x200
200x200
2
0
0
x
1
5
0
15
0x1
50
350x250
30
0x2
50
30
0x2
50
30
0x2
50
450x350 450x300
20
0x2
00
300x300
200x200
200x200
250x200
250x200
200x200
J L
11
10
9
KHGExDxDCyCx
FOOD PREP.
125
CORRIDOR
123
DISH WASHER
124
CATS ISOLATION
118
STRAY CATS
117
EXOTICS
115
TREATMENT ROOM
116
KITTENS
114
CORRIDOR
113
CATS HOLDING
120
STRAY DOGS
121
DOGS ADOPTION
122
CORRIDOR
129
LOCKERS
133
WOMEN
132
MEN
130
LOCKERS
131
JANITOR
128
STAIR
No.1
ELEVATOR
CREMATORIUM FLUE
CHIMNEY
AD
600x600 ACCESS DOOR
FOR SOUTH ATTIC
ENTRANCE LOCATED
ABOVE CEILING
AD
600x600 ACCESS DOOR
FOR NORTH ATTIC
ENTRANCE LOCATED
ABOVE CEILING
AD
600x600 ACCESS DOOR
FOR WEST ATTIC
ENTRANCE LOCATED
ABOVE CEILING
STORAGE
126
450x450 ACCESS DOOR
FOR WEST ATTIC
ENTRANCE LOCATED
ABOVE CEILING
AD
MECHANICAL AIR WELL
AD
1200x600-755 L/S
400x400 R/A DUCTS DN
350x900 S/A
FROM BELOW
450x450-410 L/S
350x250
450x450-410 L/S
350x250
450x450-410 L/S
200x200-95 L/S
200x200-95 L/S
250x250-170 L/S
250x250-170 L/S
250x200
200x200-95 L/S
200x200-95 L/S
150x150-40 L/S
350x350-365 L/S350x350-365 L/S350x350-365 L/S
200x200-125 L/S
200x200-140 L/S
250x250-155 L/S
150x150-45 L/S
150x150-45 L/S
GRADE MOUNTED AIR COOLED
CONDENSING UNITS SERVING
AHU-1 D/X COOLING COILS
250x200
150x150
(TYPICAL)
250x250-120 L/S
250x250-135 L/S
200x200
200x200150x150
300x300-160 L/S
300x300-175 L/S
150x150-50 L/S
(TYPICAL)
FOR CONTINUATION
REFER TO DRAWING M-2
200x200-105 L/S
EF
7
22
EF
8
EF
9
2
2
2
EF
5
EF
6
2
EF
4
EF
1
EF
2
EF
3
2
2
2
2
EF
10
EF
11
2
1
1
1
111
1
1
11
1
DRAWING NOTES:
1 PROVIDE NEW EXHAUST FAN. FILTER BOX, BDD AND VIBRATION ISOLATORS SHALL BE SUPPLIED
LOOSE BY THE EXHAUST FAN SUPPLIER. FILTER BOX AND BDD SHALL BE CONNECTED TO THE
EXHAUST FAN HOUSING BY CONTRACTOR ON SITE. VIBRATION ISOLATORS SHALL BE SUPPORTED
FROM EXISTING HANGER RODS. PROVIDE NEW ACCESS DOOR. (SIZE AND LOCATION OF THE
ACCESS DOORS SHALL BE SUITABLE TO ACCESS FAN COMPONENTS INCLUDING FAN WHEEL,
MOTOR, CONTROLS, DISCONNECT SWITCH AND FILTER HOUSING, ETC). REFER TO DETAIL 1 ON
DRAWING M-9. MAKE-GOOD DISRUPTED OR DAMAGED CEILING. DIVISION 26 SHALL PROVIDE
WIRING TO THE DISCONNECT SWITCH (FACTORY MOUNTED ON FAN HOUSING) AND MANUAL
(MOTOR) STARTER (SUPPLIED BY DIVISION 23).
2 REPAIR TORN OR DAMAGED EXISTING DUCT INSULATION. PROVIDE NEW DUCT INSULATION UPTO
MAXIMUM 3 METERS FROM THE EXTERIOR OUTLET IF EXISTING DUCT IS NOT INSULATED.
KENNELS - GROUND FLOOR
- HVAC NEW WORK LAYOUT
M-8
1
M-7
SCALE: 1:50
KENNELS - GROUND FLOOR - HVAC NEW WORK LAYOUT
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALL
APPLICABLE CODES AND REQUIREMENTS OF
AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT
SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST
ASSUME FULL RESPONSIBILITY AND BEAR COSTS
FOR ANY CORRECTIONS OR DAMAGES RESULTING
FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS
PROVIDED BY AND IS THE PROPERTY OF THE
WSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPT
RESPONSIBILITY FOR ALL DIMENSIONS AND
CONDITIONS ON SITE AND SHALL NOTIFY THE
APPROPRIATE CONSULTANT OF ANY VARIATIONS
FROM THE SUPPLIED INFORMATION.
Project
Name:
CONSULTANT
19/12/2014 10:27:13 AM
821 PROGRESS AVENUE
SCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
600 Cochrane Drive, 5th Floor
Markham, ON L3R 5K3
t. 905-475-7270 f. 905-475-5994
www.wsp.com
FIRE ALARM UPGRADE,
EXHAUST FANS REPLACEMENT
AND ELEVATOR MODERNIZATION
G.V T.N
AS NOTED
TORONTO
ANIMAL SERVICES
EAST DISTRICT
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
CEILING
NOTES:
1. FILTER BOX AND BDD ARE SUPPLIED LOOSE WITH EXHAUST FAN, THEY SHALL BE FIELD ASSEMBLED.
2. ENSURE THAT ALL ACCESS REQUIREMENT ARE PROVIDED - COORDINATE FINAL LOCATION WITH NEW AND
EXISTING SERVICES AND EXISTING STRUCTURE.
3. EXISTING DUCT AND GRILLES TO BE CLEANED PRIOR TO INSTALLATION OF NEW EQUIPMENT.
4. REPLACE EXISTING DAMAGED OR DISTURBED INSULATION.
5. PROVIDE NEW INSULATION UPTO MAXIMUM 3 METERS FROM EXTERIOR WALL IF EXISTING INSULATION IS MISSING.
6. MAKE-GOOD DISRUPTED OR DAMAGED CEILING.
EXTERIOR WALL
EXISTING GRILLE
IN SOFFIT
EXISTING GRILLE
IN CEILING
EXISTING SUPPORT HANGER SUSPENDED FROM
EXISTING STRUCTURE (TYPICAL)
NEW VIBRATION ISOLATOR
SUPPLIED LOOSE WITH FAN
(TYPICAL)
NEW FLEX CONNECTOR
EXISTING INSULATED DUCT
NEW FILTER BOX (BOTTOM ACCESS)
SUPPLIED LOOSE WITH FAN
NEW EXHAUST FAN
CTE
EF
CTE
FLOOR
NEW FLEX CONNECTOR
CEILING
NOTES:
1. ENSURE THAT ALL ACCESS REQUIREMENT ARE PROVIDED - COORDINATE FINAL LOCATION WITH NEW
AND EXISTING SERVICES AND EXISTING STRUCTURE.
2. EXISTING DUCT AND GRILLES TO BE CLEANED PRIOR TO INSTALLATION OF NEW EQUIPMENT.
3. REPLACE EXISTING DAMAGED OR DISTURBED INSULATION.
4. PROVIDE NEW INSULATION UPTO 3 METERS FROM EXTERIOR WALL IF EXISTING INSULATION IS MISSING.
5. MAKE-GOOD DISRUPTED OR DAMAGED CEILING.
EXTERIOR WALL
EXISTING GRILLE
IN SOFFIT
NEW CEILING GRILLE
SUPPLIED WITH EF
EXISTING SUPPORT HANGER SUSPENDED
FROM EXISTING STRUCTURE
(TYPICAL)
NEW VIBRATION ISOLATOR
SUPPLIED WITH FAN
(TYPICAL)
NEW FLEX CONNECTOR
EXISTING INSULATED DUCT
NEW EXHAUST FAN
C/W BUILT-IN BDD
CTE
EF
FLOOR
PROVIDE NEW SUPPORT BRACING
FOR EF AS REQUIRED
NEW BDD
DUCT INSULATION
FUSIBLE LINK
DUCT
FLOOR
EXISTING WALL
"C" CHANNEL SUPPORT FRAMING
ACU-1 C/W ISOLATION PADS
GARAGE
(MOUNTED 2100 MM A.F.F)
FIRE DAMPER
FRAME
1-1/2"x1-1/2"x12 GA.
ANGLE SECURE TO
SLEEVE
14 GA. STEEL SLEEVE
SECURE TO FIRE
DAMPER FRAME
EXISTING WALL
REFRIGERANT PIPE SIZE
P1
SYMBOL DESCRIPTION
LOW VOLTAGE CONTROL WIRE
POWER WIRE
POWER SIGNAL WIRE
ACU-1
T
TB1
TB1
TB4
FUSE
28~16-2 AWG(S)
SYMBOL LIQUID PIPE (MM) GAS PIPE (MM)
6 (1/4") 12 (1/2")
P1
1. PROGRAMMABLE CONTROLLER (T) WITH BUILT-IN
TEMPERATURE SENSOR SHALL ACTIVATE THE SYSTEM
WHEN THE ROOM TEMPERATURE EXCEEDS 25°C
(ADJUSTABLE). INDOOR UNIT (AC-1) SHALL BE INITIATED
AT MEDIUM SPEED AND SHALL SWITCH TO HIGH SPEED
IF SPACE TEMPERATURE CANNOT BE SATISFIED AFTER
A PERIOD OF 30 MINUTES (ADJUSTABLE).
2. CONTROLLER SHALL DEACTIVATE THE SYSTEM WHEN
THE ROOM TEMPERATURE DROPS BELOW 23°C
(ADJUSTABLE).
(OUTDOOR UNIT)
208V/1 PH/60Hz
POWER SUPPLY
(REFRIGERANT
PIPING SET)
GP1
TB7
E
1. AC-1, ACU-1 AND PROGRAMMABLE CONTROLLER SHALL
BE PROVIDED BY UNIT SUPPLIER.
2. APPROPRIATE CIRCUIT PROTECTION DEVICE IN
ACCORDANCE WITH LOCAL GOVERNMENT REGULATIONS
ARE MANDATORY REQUIRED SUCH AS GFI (INVERTER
TYPE) AND WB ETC.
3. AMOUNT OF PRE-CHARGE AND THE FORMULA OF
CALCULATION SHALL BE AS PER MANUFACTURER'S
RECOMMENDATION.
4. 1.25MM² (16 AWG) : 1.25MM² (16 AWG) OR MORE.
5. GROUNDING REQUIRED BETWEEN ACU-1 AND AC-1.
ELECTRICAL WIRING LEGEND
PROGRAMMABLE ROOM
TEMPERATURE SENSOR
AND CONTROLLER
GENERAL NOTES
SEQUENCE OF OPERATION
AC-1
(INDOOR UNIT)
NEW ACCESS DOOR
1
M-9
TYPICAL IN-LINE EXHAUST FAN INSTALLATION DETAIL
N.T.S.
2
M-9
TYPICAL CABINET EXHAUST FAN INSTALLATION DETAIL
N.T.S.
3
M-9
HORIZONTAL AIR FLOW FIRE DAMPER DETAIL
N.T.S.
4
M-9
MOUNTING DETAIL OF ACU-1
N.T.S.
5
M-9
SPLIT SYSTEM AIR CONDITIONING SYSTEM SCHEMATIC
N.T.S.
DETAILS AND SCHEMATIC
-MECHANICAL
M-9
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALL
APPLICABLE CODES AND REQUIREMENTS OF
AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT
SPECIFICALLY MARKED "FOR CONSTRUCTION" MUST
ASSUME FULL RESPONSIBILITY AND BEAR COSTS
FOR ANY CORRECTIONS OR DAMAGES RESULTING
FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS
PROVIDED BY AND IS THE PROPERTY OF THE
WSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPT
RESPONSIBILITY FOR ALL DIMENSIONS AND
CONDITIONS ON SITE AND SHALL NOTIFY THE
APPROPRIATE CONSULTANT OF ANY VARIATIONS
FROM THE SUPPLIED INFORMATION.
Project
Name:
CONSULTANT
19/12/2014 10:27:13 AM
821 PROGRESS AVENUE
SCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
600 Cochrane Drive, 5th Floor
Markham, ON L3R 5K3
t. 905-475-7270 f. 905-475-5994
www.wsp.com
FIRE ALARM UPGRADE,
EXHAUST FANS REPLACEMENT
AND ELEVATOR MODERNIZATION
G.V T.N
AS NOTED
TORONTO
ANIMAL SERVICES
EAST DISTRICT
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
ELECTRICAL DRAWING LISTDRAWING No. DRAWING TITLE SCALE
E-1 N.T.S.
E-2 1:50ADMINISTRATION OFFICE AREA - GROUND FLOOR - DEMOLITION LAYOUT - ELECTRICAL
E-3
KEY PLAN, SYMBOL LIST AND DRAWING LIST - ELECTRICAL
KENNELS
LINK 112 ADMINISTRATION
HEALTH CARE
AMPHITHEATRE
MECH.AIR WELL
CATBUBBLE
111
CATADOPTION
KENNELS - BASEMENT FLOOR - DEMOLITION LAYOUT - ELECTRICAL 1:50
NOTE:THE SITE PLAN IS PREPARED BASED ON OLDDRAWINGS, AND MAY NOT BE ACCURATE.SHOULD BE USED AS REFERENCE ONLY.
1
1
E-1 SCALE: N.T.S.SITE PLAN
E-4 1:50KENNELS - GROUND FLOOR - HVAC DEMOLITION LAYOUT- ELECTRICAL
E-5 HEALTH CARE CENTRE - GROUND FLOOR - DEMOLITION LAYOUT AND NEW WORK LAYOUT 1:50
E-6 1:50ADMINISTRATION OFFICE AREA - GROUND FLOOR - NEW WORK LAYOUT - ELECTRICAL
E-7 KENNELS - BASEMENT FLOOR - NEW WORK LAYOUT - ELECTRICAL 1:50
E-8 KENNELS - GROUND FLOOR - NEW WORK LAYOUT - ELECTRICAL 1:50
E-9 RISER DIAGRAM AND SCHEMATICS - ELECTRICAL N.T.S.
ELECTRICAL SYMBOL LISTDESCRIPTIONSYMBOL
EXISTING ITEM TO REMAIN AS INSTALLED.
EXISTING ITEM TO BE DELETED. REMOVE ALL EXISTING WIRING, CONDUIT, ETC. BACK TO ITS SOURCE.MAINTAIN CIRCUIT CONTINUITY DOWNSTREAM.
EXISTING ITEM TO RELOCATED. EXTEND EXISTING WIRING IN CONDUIT TO NEW LOCATION AND CONNECTCOMPLETE.
EXISTING ITEM IN ITS RELOCATED POSITION.
EXISTING ITEM TO BE REPLACED BY A NEW FIXTURE OR DEVICE AND RECONNECTED TO EXISTING ORNEW CIRCUIT WHERE SHOWN.
EXISTING ITEM TO DISCONNECTED, REMOVED, CLEANED, RE-INSTALLED IN SAME LOCATION ANDRECONNECTED TO EXISTING CIRCUIT.
EXISTING ITEM IN ITS RE-INSTALLED POSITION.
GENERAL ELECTRICAL
SYMBOL DESCRIPTION
RECESSED OR SURFACE MOUNTED FIRE ALARM CONTROL PANEL.
FACP
RECESSED OR SURFACE MOUNTED FIRE ALARM ANNUNCIATOR PANEL.FAA
FIRE ALARM BELL, MOUNTED APPROXIMATELY 12" (300mm) BELOW FINISHED CEILING.UNLESS OTHERWISE NOTED.
MOTOR
DUPLEX U-GROUND 15A, 125 VOLT, 2 POLE, 3 WIRE GROUNDING RECEPTACLE MOUNTED 12" (300 mm)ABOVE FINISHED LEVEL, UNLESS OTHERWISE NOTED.
SINGLE SURFACE MOUNTED PANELBOARD,"PP" DENOTES POWER PANEL,"LP" DENOTES LIGHTING AND POWER PANEL
LINE VOLTAGE CONTROL CONNECTION BETWEEN SWITCH AND FIXTURE THERMOSTAT AND HEATER, ETC.
ONE, TWO, THREE AND FOUR GANG LINE VOLTAGE TOGGLE SWITCH MOUNTED 4'-0" (1.2m) ABOVEFINISHED FLOOR LEVEL. UNLESS OTHERWISE NOTED.
SIMILAR TO ABOVE, BUT GROUND FAULT INTERRUPTER TYPE DUPLEX RECEPTACLE.
AUTOMATIC HEAT DETECTOR 15°F (8.3°C) RATE OF RISE AND FIXED TEMPERATURE TYPE 135°F (57°C)RATED AT 2500 FT ² (232m² ) COVERAGE, CEILING MOUNTED TYPE.
FACP
FAA
FORCE FLOW HEATER
PRODUCTS OF COMBUSTION DETECTOR PHOTO ELECTRIC CEILING MOUNTED TYPE.
TELEPHONE OUTLET, FLUSH MOUNTED 4'-0" (1200mm) ABOVE FINISHED FLOOR LEVEL TO CENTER LINE.
GENERAL NOTES
208V, 1PH CONNECTION TO EQUIPMENT
DEMOLITION SYMBOLS
DW
EXP
DRYWALL CEILING
EXPOSED CEILING
"3" WHERE SHOWN, DENOTES 3-WAY SWITCH3
"K" WHERE SHOWN, DENOTES KEY SWITCHK
"SC" WHERE SHOWN, DENOTES SPEED CONTROL SWITCHSC
AREA OFWORK
AREA OFWORK
ISOLATOR.
CG "CG" WHERE SHOWN, DENOTES CLEAR GUARD.
FIRE ALARM HORN, MOUNTED APPROXIMATELY 12" (300mm) BELOW FINISHED CEILING.UNLESS OTHERWISE NOTED.
COMBINATION FIRE ALARM HORN AND STROBE LIGHT, MOUNTED APPROXIMATELY 12" (300mm)BELOW FINISHED CEILING. UNLESS OTHERWISE NOTED.
WALL MOUNTED FIRE ALARM SYSTEM STROBE LIGHT.
E-10 FIRE ALARM ZONING PLANS - ELECTRICAL 1:200
AUTOMATIC HEAT DETECTOR 15°F (8.3°C) RATE OF RISE AND FIXED TEMPERATURE TYPE 135°F (57°C)RATED AT 2500 FT ² (232m² ) COVERAGE, WALL MOUNTED TYPE.
1. DRAWINGS SHALL BE USED FOR REFERENCE ONLY TO PROVIDEA GENERAL OUTLINE OF THE SCOPE OF WORK. THE DRAWINGSSHALL BE READ IN CONJUNCTION WITH THE SPECIFICATIONSAND ALL OTHER DRAWINGS AND DOCUMENTS ISSUED AS PARTOF THIS PROJECT.
2. PRIOR TO SUBMISSION OF BID, COMMENCEMENT OF WORK,ORDERING OF EQUIPMENT AND/OR FABRICATION OF MATERIALS,THE CONTRACTOR SHALL VISIT THE SITE TO VERIFY EXISTINGCONDITIONS. THIS SHALL BE DONE IN ORDER TO CONFIRM THATEQUIPMENT AND SERVICES CAN BE INSTALLED AS SHOWN ONDRAWINGS. IT IS THE CONTRACTORS RESPONSIBILITY TO NOTIFYTHE CONSULTANT OF ANY DISCREPANCIES, OMISSIONS ORINTERFERENCES PRIOR TO COMMENCEMENT OF WORK. PROVIDEINTERFERENCE DRAWINGS. INCLUDE FOR ALL COSTS RELATEDTO COORDINATION OF OTHER TRADES' WORK.
3. ENSURE THAT ALL EQUIPMENT REQUIRING MAINTENANCE ISACCESSIBLE. REPORT ANY OBSTRUCTIONS TO THE CONSULTANT.
4. FOR CLARITY, NOT ALL EXISTING EQUIPMENT. HAS BEEN SHOWNON THE DRAWINGS. THE EXISTING EQUIPMENT, AND SERVICESARE SHOWN FOR REFERENCE ONLY. EXACT LOCATIONS, SIZESAND DIMENSIONS SHALL BE DETERMINED ON SITE.
5. FIRESTOP PIPE PENETRATIONS THROUGH FIRE RATEDASSEMBLY. FIRESTOPPING ASSEMBLY SHALL BE ULC LISTEDAND SUITABLE FOR THE SPECIFIC APPLICATION.
6. ACCESS DOORS ARE NOT SHOWN ON THE DRAWING; IT WILL BETHE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE ACCESSDOORS ARE PROVIDED FOR EQUIPMENT THAT REQUIRESACCESS.
7. EQUIPMENT SHALL BE INDEPENDENTLY SUPPORTED WITHPROPER SUPPORTS SECURED TO THE BUILDING STRUCTURE .
8. ELEVATOR CONTRACTOR SHALL BE RESPONSIBLE FOR ALLDEMOLITION AND NEW WORK RELATED TO THE HYDRAULIC PUMPAND MOTOR, ELEVATOR SYSTEM POWER PIPING, ELEVATORSYSTEM CONTROL WIRING, WIRING WITHIN ELEVATOR CAB TOEXHAUST FAN, ETC.
9. ELEVATOR CONTRACTOR TO ACCOMMODATE AUTO RECALLOPTION AS PER ELEVATOR SPECIFICATIONS.
10. EXISTING EXHAUST FANS ARE TO BE REPLACED COMPLETE WITHWIRE, BREAKERS, SWITCHES , ETCETERA AS IDENTIFIED.
11. REPLACE EXISTING FIRE ALARM SYSTEM COMPLETE WITH MAINPANEL, ANNUNCIATOR, FIRE ALARM DEVICES, AUXILIARYDETECTION AND SIGNALLING.
12. ALL WORK MUST BE COORDINATED WITH THE CITY.
13. WORK MUST NOT DISRUPT THE OPERATION OF THE FACILITY.
14. ELEVATOR RELATED WORK CAN BE SCHEDULED ANY TIME ONWEEK DAYS, WEEKENDS AND HOLIDAYS.
15. WORK IN ALL OTHER AREAS SHALL BE SCHEDULED BETWEENTHE HOURS OF 7 AM TO 6 PM ON WEEKDAYS.
16. WORK IN ADMINISTRATION BUILDING OFFICES AND FOYER SHALLBE SCHEDULED BETWEEN THE HOURS OF 6:30 PM TO 6:30 AM ONWEEKDAYS AND ANYTIME ON WEEKENDS AND HOLIDAYS.
17. PROVIDE SURFACE RACEWAYS FOR CONCRETE BLOCK WALLS, IFEXISTING CONCEALED CONDUIT CAN NOT REUSED FOR NEWWORK. AND FOR DRY WALL AREAS, PROVIDE CONDUIT FOR NEWWORK (CONDUITS TO BE CONCEALED BEHIND DRYWALL).
PRODUCTS OF COMBUSTION DETECTOR, DUCT TYPE WITH SAMPLING TUBES.D
C
P
WP "WP" WHERE SHOWN, WEATHERPROOF.
WT "WT" WHERE SHOWN, WATERPROOF.
DIMMER SWITCH. "LV" WHERE SHOWN, DENOTES LOW VOLTAGE SWITCH."OS", DENOTES OCCUPANCY SENSOR
GENERAL NOTES FOR FIRE ALARM INSTALLATION - BASE PRICE
1. REMOVE COMPLETE EXISTING FIRE ALARM SYSTEM INCLUDING BUT NOT LIMITED TO PANELS, DEVICES, WIRING ANDCONDUIT.
2. INSTALL NEW FIRE ALARM SYSTEM COMPLETE WITH ALL DEVICES, ACCESSORIES, WIRING, ETCETERA. TEST ANDCOMMISSION THE NEW FIRE ALARM SYSTEM COMPLETE WITH TERMINATING TO REMOTE MONITORING.
3. PROVIDE FIRE WATCH FOR WHOLE PERIOD OF FIRE ALARM SYSTEM REPLACEMENT WORK, UNTIL THE NEW FIREALARM SYSTEM IS TESTED, COMMISSIONED AND CONNECTED TO REMOTE MONITORING.
GENERAL NOTES FOR FIRE ALARM INSTALLATION - ALTERNATE PRICE
1. THE EXISTING FIRE ALARM SYSTEM MUST REMAIN FULLY OPERATIONAL UNTIL THE NEW FIRE ALARM SYSTEM ISCOMPLETELY INSTALLED, VERIFIED AND FULLY OPERATIONAL. AFTER THE NEW SYSTEM IS FULLY OPERATIONAL,REMOVE ALL REDUNDANT - BUT NOT LIMITED TO: PANELS, DEVICES, WIRING AND CONDUIT THAT IS ASSOCIATED WITHTHE ORIGINAL SYSTEM. NO REDUNDANT MATERIALS SHALL BE ABANDONED IN PLACE. ALL MAIN COMPONENTS FROMTHE FIRE ALARM SYSTEM ARE TO BE TURNED OVER TO THE YRDSB ONCE DECOMMISSIONED.
2. FOR WORKING HOURS, REFER TO GENERAL NOTE IN E-1.
3. ELECTRICAL CONTRACTOR SHALL POST A SIGN AT THE MAIN ENTRANCE, ADVISING THAT A FIRE ALARM SYSTEMUPGRADE IS OCCURRING AND THAT TWO (2) SYSTEM(S) MAY BE INSTALLED SIMULTANEOUSLY.
4. FIRE WATCHES:a) THE EXISTING SYSTEM MUST STAY OPERATIONAL UNTIL THE NEW SYSTEM IS OPERATIONAL. THE
CONTRACTOR IS RESPONSIBLE TO ENSURE THE EXISTING SYSTEM IS NOT IN "TROUBLE" OR OFF-LINE WITHMONITORING FOR MORE THAN 30 MINUTES. IF THIS OCCURS A FIRE WATCH SHALL BE ARRANGED.
b) IF FIRE WATCHES ARE REQUIRED, THE CONTRACTOR WILL BE RESPONSIBLE TO WORK WITH THE OWNERSTAFF TO OBTAIN AND SIGN THE REQUIRED FIRE WATCH DOCUMENTATION. THE CONTRACTOR WILL BEREQUIRED TO PERFORM THE REQUIRED DUTIES OF THE FIRE WATCH.
KEY PLAN, SYMBOL LISTAND DRAWING LIST -ELECTRICAL
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY: I.Z.
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED: -
No. Date Description
REVIEWED BY: S.S.
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALLAPPLICABLE CODES AND REQUIREMENTS OFAUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOTSPECIFICALLY MARKED "FOR CONSTRUCTION" MUSTASSUME FULL RESPONSIBILITY AND BEAR COSTSFOR ANY CORRECTIONS OR DAMAGES RESULTINGFROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE ISPROVIDED BY AND IS THE PROPERTY OF THEWSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPTRESPONSIBILITY FOR ALL DIMENSIONS ANDCONDITIONS ON SITE AND SHALL NOTIFY THEAPPROPRIATE CONSULTANT OF ANY VARIATIONSFROM THE SUPPLIED INFORMATION.
ProjectName:
CONSULTANT
19/12/2014 10:27:13 AM
TORONTOANIMAL SERVICES
EAST DISTRICT
821 PROGRESS AVENUESCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
FIRE ALARM UPGRADE,EXHAUST FANS REPLACEMENTAND ELEVATOR MODERNIZATION
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
N.T.S.
E-1
C
D
B
E
F
1
A
23456789
CAT BUBBLE111
LINK112
VESTIBULE102
RECEPTION
FOYER103
LUNCH ROOM106
CORRIDOR110
MANAGER105
LECTURE ROOM104
OFFICE103
LAV108
LAV102
VESTIBULE101
CAT ADOPTION
600x600 ACCESS DOOR FORENTRANCE TO ATTICLOCATED ABOVE CEILING
AD
AD200x200 CEILINGACCESS DOOR
MANAGEROFFICE
E
NEW PANEL A
PANEL A1E
PANEL A
E
PANEL E
EF
A
SC
K
E
E
EF-13
EF-14
EF-15
EF-12
EF-A
D
D
DD
D
D
D
D
D
D
D
D
D
DD
DD
D
D
D
D
D
D
D
D
DFIRE ALARMSYSTEM REMOTEANNUNCIATOR
FAA
D
D
CONNECTION TOTHIS EXISTINGEXHAUST FAN TOREMAIN.
REFER TO NOTES ,1 2
REFER TO NOTES ,1 2
REFER TO NOTES ,1 2
REFER TO NOTE 2
FIRE ALARM TROUBLE
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY: I.Z.
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED: -
No. Date Description
REVIEWED BY: S.S.
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALLAPPLICABLE CODES AND REQUIREMENTS OFAUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOTSPECIFICALLY MARKED "FOR CONSTRUCTION" MUSTASSUME FULL RESPONSIBILITY AND BEAR COSTSFOR ANY CORRECTIONS OR DAMAGES RESULTINGFROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE ISPROVIDED BY AND IS THE PROPERTY OF THEWSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPTRESPONSIBILITY FOR ALL DIMENSIONS ANDCONDITIONS ON SITE AND SHALL NOTIFY THEAPPROPRIATE CONSULTANT OF ANY VARIATIONSFROM THE SUPPLIED INFORMATION.
ProjectName:
CONSULTANT
19/12/2014 10:27:13 AM
TORONTOANIMAL SERVICES
EAST DISTRICT
821 PROGRESS AVENUESCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
FIRE ALARM UPGRADE,EXHAUST FANS REPLACEMENTAND ELEVATOR MODERNIZATION
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
1:50
ADMINISTRATION OFFICEAREA - GROUND FLOOR -DEMOLITION LAYOUT
E-2
1
E-2 SCALE: 1:50ADMINISTRATION OFFICE AREA - GROUND FLOOR - DEMOLITION LAYOUT
NOTES:EXHAUST FANS EF-13, EF-14 AND EF-15 ARE ALL FED FROM SAME BREAKER (15A-1P, POS'N 37) OF PANEL A1, AS WELL LIGHTING WITHIN 'LAV-102','LAV-108 AND 'LUNCHROOM-106' '. BE RESPONSIBLE TO DISCONNECT ALL THREE EXHAUST FANS AND LIGHTING WITHIN 'LAV-102' AND 'LAV-108'FROM THIS CIRCUIT. LIGHTING WITHIN 'LUNCHROOM-106' SHALL REMAIN CONNECTED TO THIS CIRCUIT. MODIFY EXISTING BRANCH CIRCUIT ASREQUIRED.
REMOVE AND DISPOSE OF ALL WIRING AND CONDUITS FOR EXISTING EXHAUST FANS EF-12, EF-13, EF-14 AND EF-15 BACK TO SOURCE, INCLUDINGREMOVAL OF EXISTING BREAKERS.
1
2
J L
11
10
9
KHGExDxDCyCx
LITTER STORAGEB-2
GARAGEB1
FREEZERB3
FOOD STORAGEB4
STORAGEB6
ELEV. EQPT.B8
CREMATORIUMB7
DOG QUARANTINEB11
RECORDSB12
DOG ISOLATIONB10
CORRIDORB-17
NURSERYB14
CAT QUARANTINEB13
OPEN AREA FORMECHANICAL UNITS
TREATMENTROOM #2
B9
AD
AD
AD
GENERALISOLATION
B8
AD AD
OVER HEAD DOOR
OVER HEAD DOOR
RO
LL-U
P S
HU
TT
ER
DO
OR
RO
LL-U
P S
HU
TT
ER
DO
OR
ADAD
ELECTRICAL /FIRE ALARM
ROOMB15
ELEVATOR
STAIRNo.1
PANEL KB
E
HYDROMETERCABINET
M
E
EPANEL KC
FACP
D
E
MAINSWITCHBOARD PP1
E
D
D
D
D
D D
D
D
D
D
D
D D
D
D D
D
D
DD
D
D
D
DD
DD
D
D
D
D
D
D
D
D
D
K
D
D
D
D
EF-16
EF-17
EF-18 EF-19
EF-21
EF-20
ELEVATOR CONTROLLERHYDRAULIC PUMP, ETC.TO BE DEMOLISHED BYELEVATOR CONTRACTOR.REFER TO NOTE 1
ERREFERTO NOTE 3
E EXISTING SWITCHFOR PIT LIGHT
E
DELEVATOR CARLIGHT DISCONNECT
D D
SPAREELEVATOR CONTROLDISCONNECT
E
E
REFERTO NOTE 2
REFERTO NOTE 4
REFER TO NOTE 5
REFERTO NOTE 6
REFER TO NOTE 7
REFER TO NOTE 8
REFER TO NOTE 5
REFER TO NOTE 5
REFER TO NOTE 5
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY: I.Z.
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED: -
No. Date Description
REVIEWED BY: S.S.
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALLAPPLICABLE CODES AND REQUIREMENTS OFAUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOTSPECIFICALLY MARKED "FOR CONSTRUCTION" MUSTASSUME FULL RESPONSIBILITY AND BEAR COSTSFOR ANY CORRECTIONS OR DAMAGES RESULTINGFROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE ISPROVIDED BY AND IS THE PROPERTY OF THEWSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPTRESPONSIBILITY FOR ALL DIMENSIONS ANDCONDITIONS ON SITE AND SHALL NOTIFY THEAPPROPRIATE CONSULTANT OF ANY VARIATIONSFROM THE SUPPLIED INFORMATION.
ProjectName:
CONSULTANT
19/12/2014 10:27:13 AM
TORONTOANIMAL SERVICES
EAST DISTRICT
821 PROGRESS AVENUESCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
FIRE ALARM UPGRADE,EXHAUST FANS REPLACEMENTAND ELEVATOR MODERNIZATION
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
1:50
KENNELS- BASEMENT FLOOR- DEMOLITION LAYOUT
E-3
1
E-3 SCALE: 1:50KENNELS - BASEMENT FLOOR - DEMOLITION LAYOUT
ELECTRICAL DEMOLITION NOTES:DISCONNECT AND REMOVE ALL POWER CONNECTIONS FROM ELEVATOR CONTROLLERS, DISCONNECTS, RECEPTACLES TO SOURCE COMPLETE WITH ALL WIRING ACCESSORIES.
DISCONNECT AND REMOVE ALL WIRING RELEVANT TO EXISTING ELEVATOR CIRCUIT COMPLETE WITH WIRING ACCESSORIES BACK TO SOURCES. (MAIN SWITCHBOARD AND PANEL "KB"). RETAIN UNUSED BREAKER IN PANEL "KB" AS SPARE.
REPLACE EXISTING RECEPTACLE IN ELEVATOR PIT WITH NEW GFI TYPE DUPLEX RECEPTACLE.
DISCONNECT AND REMOVE ALL WIRING AND CONDUIT FOR EXISTING LIGHT FIXTURE BACK TO SOURCE.
REMOVE AND DISPOSE OF ALL WIRING AND CONDUITS FOR EXISTING EXHAUST FAN BACK TO SOURCE, INCLUDING REMOVAL OF EXISTING BREAKER.
INVESTIGATE AND TRACE EQUIPMENT BEING CONTROLLED BY TWO (2) EXISTING RELAYS WITHIN FIRE ALARM SYSTEM (PANEL). DISCONNECT EXISTING WIRING AND RECONNECT TO NEW FIRE ALARM SYSTEM (PANEL). PROVIDE NECESSARY ACCESSORIESFOR THIS RECONNECTION TO NEW FIRE ALARM CONTROL PANEL.
EXISTING DUAL GANG SWITCH IS TO BE REPLACED WITH A NEW ONE. RETAIN EXISTING ELECTRICAL BOX AND CONDUIT INFRASTRUCTURE AND RECONNECT EXISTING LIGHTING LOAD. NEW EXHAUST FAN STARTER TO BE INSTALLED SEPRATELY, IF SAMECANNOT BE INSTALLED IN ELECTRICAL BOX. PROVIDE BLANK COVER AS NECESSARY.
EXHAUST FAN EF-20 AND 'CARBON DETECTOR' ARE FED FROM SAME CIRCUIT (CCT#60) OF PANEL KB. BE RESPONSIBLE TO DISCONNECT EXHAUST FAN EF-20 FROM THIS CIRCUIT. 'CARBON DETECTOR' SHALL REMAIN CONNECTED TO THIS CIRCUIT BUTWITH A NEW 15A-1P BREAKER (CONTRACTOR TO CONFIRM WITH 'CARBON DETECTOR' MANUFACTURER, PRIOR TO CONSTRUCTION WORK, THAT 15A-1P BREAKER IS RECOMMENDED).
1
2
3
4
5
6
7
8
J L
11
10
9
KHGExDxDCyCx
FOOD PREP.125
CORRIDOR123
DISH WASHER124
CATS ISOLATION118
STRAY CATS117
EXOTICS115
TREATMENT ROOM116
KITTENS114
CORRIDOR113
CATS HOLDING120
STRAY DOGS121
DOGS ADOPTION122
CORRIDOR129
LOCKERS133
WOMEN132
MEN130 LOCKERS
131
JANITOR128
STAIRNo.1
ELEVATOR
CREMATORIUM FLUECHIMNEY
AD600x600 ACCESS DOORFOR SOUTH ATTICENTRANCE LOCATEDABOVE CEILING
AD
600x600 ACCESS DOORFOR NORTH ATTICENTRANCE LOCATEDABOVE CEILING
AD
600x600 ACCESS DOORFOR WEST ATTICENTRANCE LOCATEDABOVE CEILING
STORAGE126
450x450 ACCESS DOORFOR WEST ATTICENTRANCE LOCATEDABOVE CEILING
AD
MECHANICAL AIR WELL
AD
PANEL KA
E
D
D
D
D
D
D DD
D
DD D D
D
D
D
D D D
D
D
D
DD
D
D
D
D
DK
K D
D
D
DK
DK
DD
DK
D
DK
DKD
D
DK
D
DK
DK
DK
D D
EF-1 EF-2 EF-3
EF-4
EF-5
EF-6EF-7EF-8
EF-9
EF-10
EF-11
REFER TO NOTE 2
REFER TO NOTE
REFER TO NOTE 2
2
REFER TO NOTE 2
REFER TO NOTE 2
REFER TO NOTE 2 REFER TO NOTE 2
REFER TO NOTE 2
REFER TO NOTE 2REFER TO NOTE 2
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY: I.Z.
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED: -
No. Date Description
REVIEWED BY: S.S.
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALLAPPLICABLE CODES AND REQUIREMENTS OFAUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOTSPECIFICALLY MARKED "FOR CONSTRUCTION" MUSTASSUME FULL RESPONSIBILITY AND BEAR COSTSFOR ANY CORRECTIONS OR DAMAGES RESULTINGFROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE ISPROVIDED BY AND IS THE PROPERTY OF THEWSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPTRESPONSIBILITY FOR ALL DIMENSIONS ANDCONDITIONS ON SITE AND SHALL NOTIFY THEAPPROPRIATE CONSULTANT OF ANY VARIATIONSFROM THE SUPPLIED INFORMATION.
ProjectName:
CONSULTANT
19/12/2014 10:27:13 AM
TORONTOANIMAL SERVICES
EAST DISTRICT
821 PROGRESS AVENUESCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
FIRE ALARM UPGRADE,EXHAUST FANS REPLACEMENTAND ELEVATOR MODERNIZATION
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
1:50
KENNELS- GROUND FLOOR- DEMOLITION LAYOUT
E-4
1
E-4 SCALE: 1:50KENNELS - GROUND FLOOR - DEMOLITION LAYOUT
NOTES:FIRE ALARM DEVICE / DETECTOR(S) IN ATTIC IS NOT SHOWN. CONTRACTOR TO IDENTIFY SAME AND DEMOLISH ALL FIRE ALARM DEVICES.
REMOVE AND DISPOSE OF ALL WIRING AND CONDUITS FOR EXISTING EXHAUST FAN BACK TO SOURCE, INCLUDING REMOVAL OF EXISTING BREAKER.
1
2
EXAM136
RECEPTION134
EXAM135
WARD141
VEST.143
ELECTRICALPANEL
TREATMENT140
SURGERY139
LAV.137
D/W.
RUN142
750x750ACCESS DOOR
D
D
D
E
D
DE
EPANEL H
D
D
D
E
E
D
D
D
D
D
D D
D
SC
D
SCD
EF-24
EF-23
EF-22
REFER TO NOTE 2
REFER TO NOTE 2
REFER TO NOTE 3
EXAM136
RECEPTION134
EXAM135
WARD141
VEST.143
ELECTRICALPANEL
TREATMENT140
SURGERY139
LAV.137
D/W.
RUN142
750x750ACCESS DOOR
EF-24
EF-23
EF-22
EPANEL H
REFER TO NOTE ,(TYPICAL)
3 4
H-45
H-47
H-46
REFER TO NOTE ,(TYPICAL)
3 4
REFER TO NOTE(TYPICAL)
2
REFER TO NOTE 1
WT
WT
WT
WT
WP
REFER TO NOTE 6
REFER TO NOTE 1REFER TO NOTE 1
APPROXIMATE LOCATIONOF STARTER & SPEEDCONTROLLER (TYPICAL)
HEALTH CARE CENTRE -GROUND FLOOR -DEMOLITION LAYOUT ANDNEW WORK LAYOUT
E-5
1
E-5 SCALE: 1:50HEALTH CARE CENTRE - GROUND FLOOR - DEMOLITION LAYOUT 2
E-5 SCALE: 1:50HEALTH CARE CENTER - GROUND FLOOR - NEW WORK LAYOUT
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY: I.Z.
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED: -
No. Date Description
REVIEWED BY: S.S.
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALLAPPLICABLE CODES AND REQUIREMENTS OFAUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOTSPECIFICALLY MARKED "FOR CONSTRUCTION" MUSTASSUME FULL RESPONSIBILITY AND BEAR COSTSFOR ANY CORRECTIONS OR DAMAGES RESULTINGFROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE ISPROVIDED BY AND IS THE PROPERTY OF THEWSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPTRESPONSIBILITY FOR ALL DIMENSIONS ANDCONDITIONS ON SITE AND SHALL NOTIFY THEAPPROPRIATE CONSULTANT OF ANY VARIATIONSFROM THE SUPPLIED INFORMATION.
ProjectName:
CONSULTANT
19/12/2014 10:27:13 AM
TORONTOANIMAL SERVICES
EAST DISTRICT
821 PROGRESS AVENUESCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
FIRE ALARM UPGRADE,EXHAUST FANS REPLACEMENTAND ELEVATOR MODERNIZATION
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
1:50
NOTES:1
NOTES:INCLUDE COST FOR SUPPLY AND INSTALLATION OF TWO (2) HEAT DETECTORS FOR ATTIC SPACE. EXACT LOCATION OF HEAT DETECTORS AT ATTIC SPACE TO BE CONFIRMED DURING CONTRACTION.
REUSE EXISTING FIRE ALARM SYSTEM WIRING CONDUIT / DUCT PRESENTLY CONNECTING EXISTING FIRE ALARM CONTROL PANEL WIRING, FOR NEW WIRING TO NEW FIRE ALARM CONTROL PANEL.
PROVIDE NEW BREAKERS IN PANEL H, AND CONNECT NEW EXHAUST FANS AS MENTIONED BELOW COMPLETE WITH WIRE AND ACCESSORIES AS BELOW EF-23 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-24 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC
PROVIDE NEW 15A-1P BREAKER IN PANEL H, AND CONNECT NEW EXHAUST FAN EF-22 AND LIGHT IN WASHROOM 'LAV 137' c/w 12#12+12G AWG IN 21mmC.
CONTRACTOR TO VERIFY THAT ADDITION OF NEW EQUIPMENT WOULD NOT RESULT IN BLOWN UPSTREAM FUSE AND / OR TRIPPED UPSTREAM BREAKER, BY MEASURING LOAD OF RESPECTIVE PANEL (S)PRIOR TO COMMENCEMENT OF WORK. ALSO REFER TO APPENDIX-B OF SPECIFICATION FOR ADDITIONAL INFORMATION.
PROVIDE CONNECTION TO NEW EXHAUST FAN AS INDICATED, INCLUDING ALL REQUIRED LINE AND LOAD CONNECTIONS BETWEEN STARTER, SPEED CONTROLLER AND EXHAUST FAN. BE RESPOSIBLE TOINSTALL STARTER AND SPEED CONTROLLER IN LOCATION SHOWN ON PLANS. COORDINATE WITH MECHANICAL CONTRACTOR ON SITE.
ELECTRICAL CONTRACTOR TO PROVIDE TOGGLE SWITCH (ES) FOR ALL EXHAUST FAN (S) THAT DOES NOT REQUIRE STARTER. MECHANICAL CONTRACTOR TO PROVIDE STARTER. REFER TO MECHANICALDRAWING M-1 FOR 'NEW FANS SCHEDULE' AND ADDITIONAL INFORMATION.
BREAKER RATINGS MENTIONED ABOVE ARE BASED ON OESC GUIDE ONLY. EXACT BREAKER SIZES ARE TO BE PROVIDED AS PER MANUFACTURER'S RECOMMENDATION, WHICH MIGHT BE DIFFERENTTHAN ABOVE.
1
2
3
4
5
FIRE ALARM DEVICE / DETECTOR(S) IN ATTIC IS NOT SHOWN. CONTRACTOR TO IDENTIFY SAME AND DEMOLISH ALL FIRE ALARM DEVICES.
REMOVE AND DISPOSE OF ALL WIRING AND CONDUITS FOR EXISTING EXHAUST FAN BACK TO SOURCE, INCLUDING REMOVAL OF EXISTING BREAKER.
IT SEEMS THAT EXHAUST FAN EF-22, LIGHTS IN 'LAV-137' AND 'SURGERY-139' ARE ALL FED FROM ONE CIRCUIT AT PANEL H. BE RESPONSIBLE TO DISCONNECT EF-22 ANDLIGHT IN 'LAV-137' FROM THIS CIRCUIT BACK TO SOURCE. LIGHTING WITHIN 'SURGERY-139' SHALL REMAIN CONNECTED TO THIS CIRCUIT. MODIFY EXISTING BRANCH CIRCUITAS REQUIRED. REFER TO 'APPENDIX-B' IN SPECIFICATION FOR ADDITIONAL INFORMATION.
2
3
6
7
8
C
D
B
E
F
1
A
23456789
CAT BUBBLE111
LINK112
VESTIBULE102
RECEPTION
FOYER103
LUNCH ROOM106
CORRIDOR110
MANAGER105
LECTURE ROOM104
OFFICE103
LAV108
LAV102
VESTIBULE101
CAT ADOPTION
600x600 ACCESS DOOR FORENTRANCE TO ATTICLOCATED ABOVE CEILING
AD
AD200x200 CEILINGACCESS DOOR
MANAGEROFFICE
E
NEW PANEL A
PANEL A1E
PANEL A
E
PANEL B E
K
E
E
EF-13
EF-14
EF-15
EF-12
EF-A
A-40
FIRE ALARM TROUBLE
FIRE ALARM SYSTEM REMOTEANNUNCIATOR
FAA
REFER TO NOTE(TYPICAL)
3
REFER TO NOTE AND(TYPICAL)
2 3
A-18
A-42
NEW PANEL A-31
REFER TO NOTE 4
PASSIVE GRAPHIC DISPLAY
REFER TONOTE 6
ALTERNATIVELOCATION OF NEWFIRE ALARM PANEL.REFER TONOTE 6
SC
SF-BSF-A A-16
REFER TONOTE 7
REFER TONOTE 7
WT
WTWP
WT
WTWT
WP
WP
WP
REFER TONOTE 7
LVOS
L1
L1
L2
REFER TONOTE 9
REFER TONOTE 8LV
OS
REFER TONOTE 12
REFER TONOTE 13
REFER TO NOTE 1
1REFER TONOTE 1
REFER TO NOTE 1
APPROXIMATE LOCATIONSTARTER AND SPEEDCONTROLLER. (TYPICAL)
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY: I.Z.
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED: -
No. Date Description
REVIEWED BY: S.S.
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALLAPPLICABLE CODES AND REQUIREMENTS OFAUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOTSPECIFICALLY MARKED "FOR CONSTRUCTION" MUSTASSUME FULL RESPONSIBILITY AND BEAR COSTSFOR ANY CORRECTIONS OR DAMAGES RESULTINGFROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE ISPROVIDED BY AND IS THE PROPERTY OF THEWSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPTRESPONSIBILITY FOR ALL DIMENSIONS ANDCONDITIONS ON SITE AND SHALL NOTIFY THEAPPROPRIATE CONSULTANT OF ANY VARIATIONSFROM THE SUPPLIED INFORMATION.
ProjectName:
CONSULTANT
19/12/2014 10:27:13 AM
TORONTOANIMAL SERVICES
EAST DISTRICT
821 PROGRESS AVENUESCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
FIRE ALARM UPGRADE,EXHAUST FANS REPLACEMENTAND ELEVATOR MODERNIZATION
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
1:50
ADMINISTRATION OFFICEAREA - GROUND FLOOR -NEW WORK LAYOUT
E-6
1
E-6 SCALE: 1:50ADMINISTRATION OFFICE AREA - GROUND FLOOR - NEW WORK LAYOUT
NOTES:INCLUDE COST FOR SUPPLY AND INSTALLATION OF THREE (3) HEAT DETECTORS FOR ATTIC SPACE. EXACT LOCATION OF HEAT DETECTORS AT ATTIC SPACE TO BE CONFIRMED DURING CONTRACTION.
PROVIDE NEW BREAKERS IN RESPECTIVE PANELS, AND CONNECT NEW EXHAUST FANS AS MENTIONED BELOW, COMPLETE WITH WIRE AND ACCESSORIES AS BELOW EF-12 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-13 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC
APPROXIMATE LOCATION OF STARTER.
PROVIDE NEW TOGGLE SWITCH FOR OPERATING EXHAUST FAN EF-15, AND LIGHT IN 'LAV 108' WASHROOM. FEED WITH A NEW 15A-1P BREAKER AND 2#12+12G ANG IN 21mmC.
CONTRACTOR TO VERIFY THAT ADDITION OF NEW EQUIPMENT WOULD NOT RESULT IN BLOWN UPSTREAM FUSE AND / OR TRIPPED UPSTREAM BREAKER, BY MEASURING LOAD OF RESPECTIVE PANEL (S) PRIOR TOCOMMENCEMENT OF WORK. ALSO REFER TO APPENDIX - B OF SPECIFICATION FOR ADDITIONAL INFORMATION.
PROVIDE SEPARATE PRICE FOR INSTALLING NEW FIRE ALARM PANEL IN VESTIBULE 101, INSTEAD OF ELECTRICAL/FIRE ALARM ROOM SHOWN ON DRAWING E-7. IF NEW FIRE ALARM PANEL IS LOCATED WITHIN VESTIBULE 101,REMOTE ANNUNICATOR WOULD NOT BE REQUIRED AND ALL FIRE ALARM DEVICE WIRING, FIRE ALARM MONITOR WIRING AND POWER WIRING ARE TO BE EXTENDED ACCORDINGLY. ALSO ACCOMMODATE WIRING PER NOTEON DRAWING E-7.
MECHANICAL CONTRACTOR TO SUPPLY AND INSTALL CEILING FANS 'SF-A', 'SF-B' AND SUPPLY ASSOCIATED WALL MOUNTED TYPE SWITCH. ELECTRICAL CONTRACTOR TO INSTALL THE SWITCH AND COMPLETE ELECTRICALCONNECTIONS TO 'SF-A', 'SF-B' CEILING FANS (THROUGH SWITCH) WITH ONE (1) NEW 15A-1P BREAKER AND 2#12+G AWG IN 21mmC, UP TO SOURCE PANEL.
PROVIDE CONNECTION TO NEW EXHAUST FAN AS INDICATED, INCLUDING ALL REQUIRED LINE AND LOAD CONNECTIONS BETWEEN STARTER, SPEED CONTROLLER AND EXHAUST FAN. BE RESPOSIBLE TO INSTALL STARTER ANDSPEED CONTROLLER IN LOCATION SHOWN ON PLANS. COORDINATE WITH MECHANICAL CONTRACTOR ON SITE.
1
2
3
4
5
6
16
7
8
PROVIDE NEW TOGGLE SWITCH FOR OPERATING EXHAUST FAN EF-14, AND LIGHT IN 'LAV 102' WASHROOM. FEED WITH A NEW 15A-1P BREAKER AND 2#12+12G ANG IN 21mmC.
ELECTRICAL CONTRACTOR TO PROVIDE TOGGLE SWITCH (ES) FOR ALL EXHAUST FAN (S) THAT DOES NOT REQUIRE STARTER. MECHANICAL CONTRACTOR TO PROVIDE STARTER. REFER TO MECHANICAL DRAWING M-1FOR 'NEW FANS SCHEDULE' AND ADDITIONAL INFORMATION.
BREAKER RATINGS MENTIONED ABOVE ARE BASED ON OESC GUIDE ONLY. EXACT BREAKER SIZES ARE TO BE PROVIDED AS PER MANUFACTURER'S RECOMMENDATION, WHICH MIGHT BE DIFFERENT.
CONTRACTOR TO FEED NEW LIGHT FIXTURES IN THE MANAGERS OFFICE FROM EXISTING PERIMETER LIGHT CIRCUIT IN SAME ROOM, AFTER VERIFYING THAT ADDITION OF NEW LIGHT FIXTURES WOULD NOT TRIPRELEVANT OVER CIRCUIT PROTECTION DEVICE.
CONTRACTOR TO FEED NEW LIGHT FIXTURES IN THE CORRIDOR FROM EXISTING LIGHT CIRCUIT IN SAME ROOM, AFTER VERIFYING THAT ADDITION OF NEW LIGHT FIXTURES WOULD NOT TRIP RELEVANT OVER CIRCUITPROTECTION DEVICE.
9
10
11
12
13
J L
11
10
9
KHGExDxDCyCx
LITTER STORAGEB-2
GARAGEB1
FREEZERB3
FOOD STORAGEB4
STORAGEB6
ELEV. EQPT.B8
CREMATORIUMB7
DOG QUARANTINEB11
RECORDSB12
DOG ISOLATIONB10
CORRIDORB-17
NURSERYB14
CAT QUARANTINEB13
OPEN AREA FORMECHANICAL UNITS
TREATMENTROOM #2
B9
AD
AD
AD
GENERALISOLATION
B8
AD AD
OVER HEAD DOOR
OVER HEAD DOOR
RO
LL-U
P S
HU
TT
ER
DO
OR
RO
LL-U
P S
HU
TT
ER
DO
OR
ADAD
ELECTRICAL /FIRE ALARM
ROOMB15
ELEVATOR
STAIRNo.1
E
HYDROMETERCABINET
M
E
E
FACP
E
EXISTING MAINSWITCHBOARD PP1
E
E EXISTING SWITCHFOR PIT LIGHT
E
ER
EXISTINGPANEL KB
AHU
1
EXISTING AIR COOLEDCONDENSING UNITSSERVING AC-1 AND AC-2
24
EXISTING MAKE-UP AIR UNIT
APPROXIMATE ROUTING OF POWER FEEDERS FORPANEL "KD", CONTROL AND ELEVATORDISCONNECT. REFER TO NOTE .
ACU-1(WALL MOUNTED)
PANEL"KD"
KD-1,3
DW
EXP
EXP
6
REFER TONOTE
10
REFERTO NOTE 3
EXISTINGPANEL KC
REFERTO NOTE 2
EXP
K
EF-16
EF-17
EF-18 EF-19
EF-21
EF-20
ELEVATOR CONTROLLERHYDRAULIC PUMP, ETC.TO BE INSTALLED BYELEVATOR CONTRACTOR.REFER TO NOTE 1
E
E
KD-7
ELEVATOR CONTROLSDISCONNECT(FUSED DISCONNECT).REFER TO NOTES , AND .
1
REFER TONOTES AND .3
AC-1 (WALLMOUNTED)REFER TONOTE
8
KD-7
10
6
REFER TONOTE 4
REFER TONOTE 9
ELEVATOR LIGHTAND FAN. REFERTO NOTE .7
9
INSULATION OF HYDRAULICPOWER UNIT BY ELEVATORCONTRACTOR.
KB-18 KB-56
KB-52
WP
KB-54
CG
KD-9
KB-60REFER TO NOTES ,(TYPICAL)
12 13
REFER TONOTE 11
REFER TONOTE 15
REFER TONOTE 16
WTWT
WT
WT
WT
WT
WPWP
WP
WP
REFER TO NOTE 17
APPROXIMATE LOCATIONOF STARTER. (TYPICAL)
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY: I.Z.
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED: -
No. Date Description
REVIEWED BY: S.S.
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALLAPPLICABLE CODES AND REQUIREMENTS OFAUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOTSPECIFICALLY MARKED "FOR CONSTRUCTION" MUSTASSUME FULL RESPONSIBILITY AND BEAR COSTSFOR ANY CORRECTIONS OR DAMAGES RESULTINGFROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE ISPROVIDED BY AND IS THE PROPERTY OF THEWSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPTRESPONSIBILITY FOR ALL DIMENSIONS ANDCONDITIONS ON SITE AND SHALL NOTIFY THEAPPROPRIATE CONSULTANT OF ANY VARIATIONSFROM THE SUPPLIED INFORMATION.
ProjectName:
CONSULTANT
19/12/2014 10:27:13 AM
TORONTOANIMAL SERVICES
EAST DISTRICT
821 PROGRESS AVENUESCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
FIRE ALARM UPGRADE,EXHAUST FANS REPLACEMENTAND ELEVATOR MODERNIZATION
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
1:50
KENNELS- BASEMENT FLOOR- NEW WORK LAYOUT
E-7
1
E-7 SCALE: 1:50KENNELS - BASEMENT FLOOR - NEW WORK LAYOUT
ELECTRICAL NEW WORK NOTES:CONTRACTOR TO ENSURE WORKING SPACE CLEARANCE IN ELEVATOR EQUIPMENT ROOM MEETS OESC AND TSSA REQUIREMENTS. COORDINATE WITH ELEVATOR CONTRACTOR.
REPLACE EXISTING RECEPTACLE IN ELEVATOR PIT WITH NEW GFI TYPE DUPLEX RECEPTACLE.
PROVIDE WIRE GUARDS FOR THE EXISTING LIGHT FIXTURES IN ELEVATOR PIT AND ELEVATOR EQUIPMENT ROOM.
PROVIDE NEW TELEPHONE LINE , COMPLETE WITH OUTLET. COORDINATE WITH BASE BUILDINGS TELECOM PROVIDER TO ACTIVATE THE PHONE LINE.
PROVIDE POWER TO SPLIT UNIT AIR CONDITIONING SYSTEM FROM PANEL "KD", COMPLETE WITH INTERCONNECTING WIRING BETWEEN RESPECTIVE OUTDOOR AND INDOOR UNITS. REFER TO SCHEMATIC ON M-7.
PROVIDE 30A-2P FUSED DISCONNECT COMPLETE WITH 1x15A FUSE FOR ELEVATOR CAB LIGHT AND FEED FROM PANEL "KD". DISCONNECT SHALL BE LOCKABLE IN OPEN POSITION.
NEW ELEVATOR CONTROLLER DISCONNECT LOCATED IN ELEVATOR EQUIPMENT ROOM SHOULD BE LOCKABLE IN OPEN POSITION AND HAVE AUXILIARY CONTACTS TO SENSE OPEN/CLOSED POSITION. COORDINATEWITH ELEVATOR CONTRACTOR FOR CONNECTION DETAILS.
ELEVATOR CONTRACTOR TO COMPLETE ALL POWER AND CONTROL WIRING FOR THE LOAD SIDE OF ELEVATOR CONTROLS DISCONNECT SWITCH.
CONNECT NEW GFI DUPLEX RECEPTACLE AND EXISTING LIGHT FIXTURE TO NEW PANEL "KD". LIGHT SWITCH SHOULD NOT BE CONNECTED TO THE LOAD SIDE TERMINAL OF THE GFI RECEPTACLE.
CONDUIT ROUTING IS SHOWN FOR REFERENCE ONLY. CONTRACTOR TO CONFIRM EXACT ROUTING ON SITE PRIOR TO ROUGH-IN. CONTRACTOR SHALL BE RESPONSIBLE FOR REINSTALLING DRYWALL CEILINGFINISHES WHERE PENETRATIONS ARE MADE TO FACILITATE ROUGHING OF ELECTRICAL CONDUITS. PAINT ENTIRE CEILING TO MATCH.
SMOKE DETECTOR TO BE CONNECTED TO RELAY AT ELEVATOR CONTROLLER TO ALLOW FOR CONNECTION FOR ELEVATOR RECALL FUNCTIONALITY.
1
2
3
4
5
6
7
8
9
10
PROVIDE NEW BREAKERS IN RESPECTIVE PANELS, AND CONNECT NEW EXHAUST FANS AS MENTIONED BELOW, COMPLETE WITH WIRE AND ACCESSORIES: EF-16 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-17 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-18 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-19 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-21 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC
RATING OF TOGGLE SWITCHES, WHEN STARTER NOT REQUIRED, SHOULD MATCH RESPECTIVE BREAKER AMPACITY.
CONTRACTOR TO VERIFY THAT ADDITION OF NEW EQUIPMENT WOULD NOT RESULT IN BLOWN UPSTREAM FUSE AND / OR TRIPPED UPSTREAM BREAKER, BY MEASURING LOAD OF RESPECTIVEPANEL (S) PRIOR TO COMMENCEMENT OF WORK. ALSO REFER TO APPENDIX-B OF SPECIFICATION FOR ADDITIONAL INFORMATION.
INSTALL DUCT DETECTOR WITH SUPPLY AIR DUCT FOR 'AHU-1'. DETECTOR SHALL BE INSTALLED UPSTREAM OF ANY DUCT BRANCH AND BE CONNECTED TO FIRE ALARM PANEL.
RECONNECT EXISTING EQUIPMENT WHICH WERE CONTROLLED BY THE OLD FIRE ALARM SYSTEM TO NEW FIRE ALARM CONTROL PANEL C/W ALL ACCESSORIES.REFER TO NOTE ON DRAWING E-3.
PROVIDE NEW DUAL GANG TOGGLE SWITCH. CONNECT EXHAUST FAN TO FIRST SWITCH OF THE DUAL GANG SWITCH AS PER NOTE ABOVE. CONNECT THE REMAINING LOAD / EQUIPMENT AT THERESPECTIVE ROOM TO THE SECOND SWITCH. ALSO REFER TO NOTE OF E-3 DRAWING.
ELECTRICAL CONTRACTOR TO PROVIDE TOGGLE SWITCH (ES) FOR ALL EXHAUST FAN (S) THAT DOES NOT REQUIRE STARTER. MECHANICAL CONTRACTOR TO PROVIDE STARTER. REFER TOMECHANICAL DRAWING M-1 FOR 'NEW FANS SCHEDULE' AND ADDITIONAL INFORMATION.
BREAKER RATINGS MENTIONED ABOVE ARE BASED ON OESC GUIDE ONLY. EXACT BREAKER SIZES ARE TO BE PROVIDED AS PER MANUFACTURER'S RECOMMENDATION, WHICH MIGHT BE DIFFERENTTHAN ABOVE.
12
13
14
15
167
1217
18
11 19
7
J L
11
10
9
KHGExDxDCyCx
FOOD PREP.125
CORRIDOR123
DISH WASHER124
CATS ISOLATION118
STRAY CATS117
EXOTICS115
TREATMENT ROOM116
KITTENS114
CORRIDOR113
CATS HOLDING120
STRAY DOGS121
DOGS ADOPTION122
CORRIDOR129
LOCKERS133
WOMEN132
MEN130 LOCKERS
131
JANITOR128
STAIRNo.1
ELEVATOR
CREMATORIUM FLUECHIMNEY
AD600x600 ACCESS DOORFOR SOUTH ATTICENTRANCE LOCATEDABOVE CEILING
AD
600x600 ACCESS DOORFOR NORTH ATTICENTRANCE LOCATEDABOVE CEILING
AD
600x600 ACCESS DOORFOR WEST ATTICENTRANCE LOCATEDABOVE CEILING
STORAGE126
450x450 ACCESS DOORFOR WEST ATTICENTRANCE LOCATEDABOVE CEILING
AD
MECHANICAL AIR WELL
AD
REFER TO NOTE
E
PANEL KA
E
K
K
K
KKK
K
K
K
K K
EF-1 EF-2 EF-3
EF-4
EF-5
EF-6KA-46KA-48
KA-55
KA-57
KA-59
EF-7EF-8
CG
FOR ELEVATOR RUN/STOP
1
KA-29
REFER TO NOTE AND(TYPICAL)
3 4
KA-20
KA-18
KA-12 KA-14 KA-16
EF-11
EF-10
EF-9 REFER TO NOTE(TYPICAL)
3
REFER TO NOTE(TYPICAL)
4
WT WT WTWT
WT
WT
WT
WT
WT
WPWP
WPWP
WP
WP
WP
WPWP
WP
WP
WT
WP
WP
WP
WP
WPREFER TO NOTE 2
REFER TO NOTE 2
REFER TO NOTE 2 REFER TO NOTE 2 REFER TO NOTE 2
REFER TO NOTE 2
REFER TO NOTE 2 REFER TO NOTE 2 REFER TO NOTE 2
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY: I.Z.
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED: -
No. Date Description
REVIEWED BY: S.S.
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALLAPPLICABLE CODES AND REQUIREMENTS OFAUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOTSPECIFICALLY MARKED "FOR CONSTRUCTION" MUSTASSUME FULL RESPONSIBILITY AND BEAR COSTSFOR ANY CORRECTIONS OR DAMAGES RESULTINGFROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE ISPROVIDED BY AND IS THE PROPERTY OF THEWSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPTRESPONSIBILITY FOR ALL DIMENSIONS ANDCONDITIONS ON SITE AND SHALL NOTIFY THEAPPROPRIATE CONSULTANT OF ANY VARIATIONSFROM THE SUPPLIED INFORMATION.
ProjectName:
CONSULTANT
19/12/2014 10:27:13 AM
TORONTOANIMAL SERVICES
EAST DISTRICT
821 PROGRESS AVENUESCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
FIRE ALARM UPGRADE,EXHAUST FANS REPLACEMENTAND ELEVATOR MODERNIZATION
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
1:50
KENNELS- GROUND FLOOR- NEW WORK LAYOUT
E-8
1
E-8 SCALE: 1:50KENNELS - GROUND FLOOR - NEW WORK LAYOUT
SMOKE DETECTOR TO BE CONNECTED TO RELAY AT ELEVATOR CONTROLLER TO ALLOW FOR CONNECTION FOR ELEVATOR RECALL FUNCTIONALITY.
INCLUDE COST FOR SUPPLY AND INSTALLATION OF NINE (9) HEAT DETECTORS FOR ATTIC SPACE. EXACT LOCATION OF HEAT DETECTORS AT ATTIC SPACE TO BE CONFIRMED DURINGCONSTRUCTION.
PROVIDE NEW BREAKERS IN RESPECTIVE PANELS, AND CONNECT NEW EXHAUST FANS AS MENTIONED BELOW, COMPLETE WITH WIRE AND ACCESSORIES AS BELOW EF-1 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-2 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-3 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-4 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-5 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC
RATING OF TOGGLE SWITCHES, WHEN STARTER NOT REQUIRED, SHOULD MATCH RESPECTIVE BREAKER AMPACITY.
CONTRACTOR TO VERIFY THAT ADDITION OF NEW EQUIPMENT WOULD NOT RESULT IN BLOWN UPSTREAM FUSE AND / OR TRIPPED UPSTREAM BREAKER, BY MEASURING LOAD OFRESPECTIVE PANEL (S) PRIOR TO COMMENCEMENT OF WORK. ALSO REFER TO APPENDIX-B OF SPECIFICATION FOR ADDITIONAL INFORMATION.
ELECTRICAL CONTRACTOR TO PROVIDE TOGGLE SWITCH (ES) FOR ALL EXHAUST FAN (S) THAT DOES NOT REQUIRE STARTER. MECHANICAL CONTRACTOR TO PROVIDE STARTER. REFER TOMECHANICAL DRAWING M-1 FOR 'NEW FANS SCHEDULE' AND ADDITIONAL INFORMATION.
BREAKER RATINGS MENTIONED ABOVE ARE BASED ON OESC GUIDE ONLY. EXACT BREAKER SIZES ARE TO BE PROVIDED AS PER MANUFACTURER'S RECOMMENDATION, WHICH MIGHT BEDIFFERENT THAN ABOVE.
ELECTRICAL NEW WORK NOTES:1
2
3 EF-6 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-7 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-8 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-9 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-10 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC EF-11 WITH 15A-1P BREAKER AND 2#12+12G AWG IN 21mmC
4
REFER TO NOTE 2
5
6
7
BA
SE
ME
NT
FL
OO
RG
RO
UN
D F
LO
OR
ALARM INITIATING ZONE
SPRINKLER FLOWZONE No.ZONE No.
FIRE ALARM REMARKSDESCRIPTIONAUXILIARYCONTACT
SUPERVISORY/TROUBLE ZONE No.
1 PULL STATIONS, HEAT DETECTORS, HORNS, STROBES
2
3
4
5
6
7
8
9
11
12
13
14
FACP
NOTES:
1. REFER TO FLOOR PLANS FOR QUANTITIES AND LOCATIONS OF DEVICES.
2. UNLESS OTHERWISE NOTED, ALL CONDUITS SHALL BE 19mm.
3. RISER DIAGRAM IS DIAGRAMMATIC ONLY AND IS INTENDED TO SHOW SCOPE OF WORK AND GENERAL FIRE ALARM DEVICE INSTALLATION. REFER TO ZONING PLANS AND ZONESCHEDULE FOR EXACT QUANTITY OF REQUIRED FIRE ALARM ZONES.'
4. SUPPLY AND INSTALL INTERFACE FOR EXISTING MONITORING PANEL.
5. PROVIDE FIRE WATCH THROUGHOUT CONSTRUCTION ACTIVITIES AS REQUIRED BY AUTHORITIES HAVING JURISDICTION.
6. NEW FIRE ALARM SYSTEM SHOULD BE SINGLE STAGE, MULTI-ZONE, ADDRESSSABLE AS MENTIONED IN SPECIFICATIONS.
CREMATORIUM
FIRE ALARM ZONING SCHEDULE
SOUTH STAIR
VESTIBULE 101
- - - ADMINISTRATION
- - - ADMINISTRATION ATTIC
- - - KENNELS BASEMENT FLOOR
- - ELEVATOR SHAFT
- -
- - CREMATORIUM
- - AHU
- - -
--
--
BA
SE
ME
NT
FL
OO
RG
RO
UN
D F
LO
OR
1200A-3P
1200A, 120/208V, 3Ø, 4W
MAIN SWITCHBOARD 'PP-1'(IN ELECTRICAL ROOM)
100A 3x100AF
1200A-3P
MAIN SWITCHBOARD 'PP-1'(IN ELECTRICAL ROOM)
100A 3x100AF
100A
SPARE
400A 3x300AF
100A 3x70AF
3x70AF
3x70AF
M
3x70AF
100A 3x70AF
100A 3x30AF
3x15AF
3x30AF
200A 3x175AF
200A
400A 3x300AF
'PANEL H' IN HEALTH CARE BUILDING
100A 3x70AF
'PANEL KC' IN ELECTRICAL ROOM.
3x70AF
UNIT HEATER #1 IN GARAGE
3x70AF
3x70AF
UNIT HEATER #2 IN GARAGE
100A 3x70AF
100A 3x30AF
3x15AF
FIRE ALARM PANEL TO BE DEMOLISHED
3x30AF
200A 3x175AF
200A 3x110AF
TO ELEVATOR CONTROLS DISCONNECT
100A3x100AF TIMEDELAY TYPE
200A 3x200AF
200A 3x200AF
200A
200A 3x200AF
200A 3x200AF
'PANEL A' IN ADMIN OFFICE AREA
200A 3x200AF
'PANEL A1' IN ADMIN OFFICE AREA
200A
'PANEL KB' IN ELECTRICAL ROOM
200A 3x200AF
'PANEL KA' IN KENNEL CORRIDOR
HYDROMETER
M
HYDROMETER
BIG OUTDOOR AC UNIT LOCATEDOUTSIDE, NEAR MECHANICAL WELL
SMALL OUTDOOR AC UNIT, LOCATEDBESIDE BIG OUTDOOR UNIT
NEW 'PANEL A' AT KITCHEN ROOMIN PET ADOPTION AREA
CONDENSING UNIT LOCATED INMECHANICAL WELL
AC UNIT #1, LOCATED IN MECHANICALAIR WELL
AIR MAKE UP UNIT IN MECHANICALAIR WELL
'PANEL H' IN HEALTH CARE BUILDING
'PANEL KC' IN ELECTRICAL ROOM.
UNIT HEATER #1 IN GARAGE
UNIT HEATER #2 IN GARAGE
'PANEL A1' IN ADMIN OFFICE AREA
'PANEL KB' IN ELECTRICAL ROOM
'PANEL KA' IN KENNEL CORRIDOR
BIG OUTDOOR AC UNIT LOCATEDOUTSIDE, NEAR MECHANICAL WELL
SMALL OUTDOOR AC UNIT, LOCATEDBESIDE BIG OUTDOOR UNIT
NEW 'PANEL A' AT KITCHEN ROOMIN PET ADOPTION AREA
CONDENSING UNIT LOCATED INMECHANICAL WELL
AC UNIT #1, LOCATED IN MECHANICALAIR WELL
AIR MAKE UP UNIT IN MECHANICALAIR WELL
ELECTRICAL SINGLE LINE DIAGRAM - DEMOLITION WORKNOT TO SCALE
1
E-9
DD
3x125AF TIMEDELAY TYPE
ELEVATOR CONTROLLERDISCONNECT(200A, 120/208V)
FIRE ALARM PANEL
NOT TO SCALE
3
E-9FIRE ALARM RISER DIAGRAM AND ZONE SCHEDULE
(GROUND FLOOR) (GROUND FLOOR)
4#1 + #6G - 53mmC
4#1 + #6G - 53mmC
NOTES:CONTRACTOR TO VERIFY ABOVE SINGLE LINEDIAGRAM DURING CONSTRUCTION AND UPDATE ASREQUIRED.
1
TO ELEVATOR CONTROLLER
TO ELEVATOR CONTROLLER
CONTROL WIRING
1200A, 120/208V, 3Ø, 4W
200A3x125AF TIMEDELAY TYPE
SPLIT SYSTEMWIRING DIAGRAMNOT TO SCALE
4
E-9
ELECTRICAL SINGLE LINE DIAGRAM - NEW WORKNOT TO SCALE
2
E-9
TO PANEL "KD" ADJACENT TOELEVATOR EQUIPMENT ROOM
TO BE DONE BY ELEVATOR CONTRACTOR.2
2
REFER TONOTE
'PANEL A' IN ADMINOFFICE AREA
2
REFER TONOTE
D
LOAD DESCRIPTION LOAD DESCRIPTIONBREAKERS
PHCCTNo.
CCTNo.
TOTALLOAD
FEEDER/CONDUIT
REC RECTOTALLOAD
FEEDER/CONDUIT
BREAKERS
L/B GFI15A2P
15A1P
OTHER15A1P
15A2P
OTHER GFI L/BAREA SERVED AREA SERVED
1 A 2
3 B 4
5 C 6
7 A 8
9 B 10
11 C 12
13 A 14
15 B 16
17 C 18
19 A 20
21 B 22
23 C 24
25 A 26
27 B 28
29 C 30
PANEL: "KD"SURFACE MOUNTED
PANEL MAINS (AMPS): 100A
MAIN BREAKER (Y/N - AMPS):YES, 100A-3P, NON-AUTO
CONNECTED LOADSLIGHTING RECEPTACLE MOTOR HEATING
xx kW xx kW xx kW -- kW
DOUBLE LUG (Y/N): NOVOLTAGE: 120/208V, 3Ø, 4W
PANEL LOCATION: ELEVATOR EQUIPMENT ROOM
PANEL FEEDER: REFER TOSINGLE LINE DIAGRAM
-SPLIT A/C UNIT ACU-1(REFER TO NOTE ) -
2#12 + #12G21mmC
X
ELEVATOR CAB - LIGHTS(REFER TO NOTE , ) - -
2#12+G21mmC
X1
1
ELEVATOR EQUIPMENT RMLIGHT AND REC
- -2#12+G21mmC
X
X
X
X
X
SPARE BREAKER
SPARE BREAKER
SPARE BREAKER
NOTES:CONTRACTOR TO PROVIDE BREAKER ACCORDING TO MANUFACTURERS' RECOMMENDATION COMPLETE WITHFEEDER. SIZE PROVIDED IS BASED ON STANDARD EQUIPMENT.
BREAKER SHOULD BE LOCKABLE IN OPEN POSITION.
1
2
I.C. = 25kA
PULL STATIONS, HEAT DETECTORS,SMOKE DETECTORS, HORNS, STROBES
EF-20 - -2#12+G21mmC
HEAT DETECTORS
-
-
-
- - SOUTH STAIR SMOKE DETECTORS
-
-
-
SMOKE DETECTOR
HEAT DETECTORS
ELEVATOR EQUIPMENT ROOM
HEAT DETECTOR, HORN, STROBES
DUCT DETECTORS (LOCATED IN ELECTRICAL ROOM)
KENNELS GROUND FLOOR PULL STATIONS, HEAT DETECTORS,SMOKE DETECTORS, HORNS, STROBES
10
-- - KENNELS ATTIC HEAT DETECTORS
PULL STATIONS, HEAT DETECTORS, HORNS, STROBESHEALTH CARE
HEALTH CARE ATTIC HEAT DETECTORS
ROOF
AT
TIC
AT
TIC
ROOF
ELEV. SHAFT
KENNELS GROUND FLOOR
KENNELS ATTIC
ELEV. EQUIPMENTROOM KENNEL BASEMENT
AHU
ADMINISTRATION ATTIC
ELECTRICAL ROOM
ADMINISTRATION
FAA
GR
OU
ND
FL
OO
R
ROOF
AT
TIC
HEALTH CARE ATTIC
HEALTH CARE
FROMHEALTHCAREBUILDING
--
--
-
-
-
-
SPARE
SPARE
FA TROUBLEINDICATORLIGHT
L1 120VEATON - METALUX14GR LEDCAT# 14GR-LD5-40-A125-UNV-L835-CD1-PAF
298mm W1219mm L143mm H
RECESSED, LENSED TROFFER. DIE FORMED, CODE GUAGE PRIME CRS HOUSING AND DIE FORMED FLAT STEEL DOOR. 0.125" THICKACRYLIC LENS WITH #12 PRISMATIC PATTERN. C/W DRYWALL FRAME FIT. RUST AND CORROSION RESISTANT PRE-TREATMENT AND WHITEPOWDER COAT PAINT FINISH PAINTED AFTER FABRICATION. ELECTRONIC 0-10V 10%-100% DIMMING DRIVER. CUL LISTED FOR DAMPLOCATION.
4045LM39W LED3500K
CRI 80+
120VELLIPTIPARSTYLE S132CAT# S132-L328-2xHSD-02-M-00-J-35-ZX
914mm W130mm H
130mm DEPTH
WALL MOUNTED ON CANTILEVER ARMS, LENSED, LINEAR WALL WASHER. EXTRUDED ALUMINUM HEAT SINK HOUSING. ASYMMETRIC OPTICPROVIDES EVEN WALL WASHING DISTRIBUTION. CLEAR PRISMATIC GLASS LENS WITH HOLOGRAPHIC DIFFUSER ENHANCES LATERAL BEAMDISTRIBUTION. CORROSION RESISTANT PRE-TREATMENT, ABRASION AND FADE RESISTANT WHITE POWDER COAT PAINT FINISH. C/W TWO457mm LONG CANTILEVER HANGER AND WALL PLATE SETS. ELECTRONIC 0-10V 10% TO 100% DIMMING DRIVER. CSA CERTIFIED.
57W LED3500K
CRI 85+
1782LM
LITHONIAPHILIPSCOLUMBIAPIONEER
EATONPEERLESS LIGHTINGPHILIPSVODE
SCHEDULE OF LUMINAIRES
WATTS &LAMPS
MOUNTING
R S W/B SUSDIMENSIONSTYPESPECIFIED MANUFACTURERAND CATALOGUE NUMBER VOLTSPRODUCT DESCRIPTION MANUFACTURERS
DELIVEREDLUMENS
ACCEPTABLE
L2
2
X
3#12 + #12G - 21mmC
RISER DIAGRAM ANDSCHEMATICS -ELECTRICAL
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY: I.Z.
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED: -
No. Date Description
REVIEWED BY: S.S.
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALLAPPLICABLE CODES AND REQUIREMENTS OFAUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOTSPECIFICALLY MARKED "FOR CONSTRUCTION" MUSTASSUME FULL RESPONSIBILITY AND BEAR COSTSFOR ANY CORRECTIONS OR DAMAGES RESULTINGFROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE ISPROVIDED BY AND IS THE PROPERTY OF THEWSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPTRESPONSIBILITY FOR ALL DIMENSIONS ANDCONDITIONS ON SITE AND SHALL NOTIFY THEAPPROPRIATE CONSULTANT OF ANY VARIATIONSFROM THE SUPPLIED INFORMATION.
ProjectName:
CONSULTANT
19/12/2014 10:27:13 AM
TORONTOANIMAL SERVICES
EAST DISTRICT
821 PROGRESS AVENUESCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
FIRE ALARM UPGRADE,EXHAUST FANS REPLACEMENTAND ELEVATOR MODERNIZATION
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
N.T.S.
E-9
CAT BUBBLE111
LINK112
VESTIBULE102
RECEPTION
FOYER103
LUNCH ROOM106
CORRIDOR110
MANAGER105
LECTURE ROOM104
OFFICE103
LAV108
LAV102
VESTIBULE101
CAT ADOPTION
600x600 ACCESS DOOR FORENTRANCE TO ATTICLOCATED ABOVE CEILING
AD
AD
MANAGEROFFICE
EXAM136
RECEPTION134
EXAM135
WARD141
VEST.143
ELECTRICALPANEL
TREATMENT140
SURGERY139
LAV.137
D/W.
RUN142
750x750ACCESS DOOR
FIRE ALARMZONE #1
FIRE ALARMZONE #4
FIRE ALARMZONE #10
FIRE ALARMZONE #7
FIRE ALARMZONE #8
CAT BUBBLE111
LINK112
VESTIBULE102
RECEPTION
FOYER103
LUNCH ROOM106
CORRIDOR110
MANAGER105
LECTURE ROOM104
OFFICE103
LAV108
LAV102
VESTIBULE101
CAT ADOPTION
600x600 ACCESS DOOR FORENTRANCE TO ATTICLOCATED ABOVE CEILING
AD
AD
MANAGEROFFICE
EXAM136
RECEPTION134
EXAM135
WARD141
VEST.143
ELECTRICALPANEL
TREATMENT140
SURGERY139
LAV.137
D/W.
RUN142
750x750ACCESS DOOR
FIRE ALARMZONE #2
FIRE ALARMZONE #9
FIRE ALARMZONE #11
FIRE ALARMZONE #5
FIRE ALARMZONE #6
FIRE ALARMZONE #3
FIRE ALARMZONE #7
FIRE ALARMZONE #8
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY: I.Z.
REVISIONS
No. Date Description
CLIENT
KEY PLAN
SEAL
CONSTRUCTION NORTH
ISSUED: -
No. Date Description
REVIEWED BY: S.S.
THIS DRAWING IS NOT TO BE SCALED.
CONSTRUCTION MUST CONFORM TO ALLAPPLICABLE CODES AND REQUIREMENTS OFAUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOTSPECIFICALLY MARKED "FOR CONSTRUCTION" MUSTASSUME FULL RESPONSIBILITY AND BEAR COSTSFOR ANY CORRECTIONS OR DAMAGES RESULTINGFROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE ISPROVIDED BY AND IS THE PROPERTY OF THEWSP.
THE CONTRACTOR SHALL VERIFY AND ACCEPTRESPONSIBILITY FOR ALL DIMENSIONS ANDCONDITIONS ON SITE AND SHALL NOTIFY THEAPPROPRIATE CONSULTANT OF ANY VARIATIONSFROM THE SUPPLIED INFORMATION.
ProjectName:
CONSULTANT
19/12/2014 10:27:13 AM
TORONTOANIMAL SERVICES
EAST DISTRICT
821 PROGRESS AVENUESCARBOROUGH, ONTARIO
OCTOBER 2017
WSP PROJECT NUMBER: 17M-01158-00
FIRE ALARM UPGRADE,EXHAUST FANS REPLACEMENTAND ELEVATOR MODERNIZATION
1. SEPT 22, 2017 ISSUED FOR OWNER'S REVIEW
2. NOV 17, 2017 ISSUED FOR PERMIT AND TENDER
1:100
FIRE ALARM ZONE PLANSELECTRICAL
E-10
1
E-10 SCALE: 1:200GROUND FLOOR - FIRE ALARM ZONING PLAN3
E-10 SCALE: 1:200ATTIC AREAS - FIRE ALARM ZONING PLAN
2
E-10 SCALE: 1:200BASEMENT FLOOR - FIRE ALARM ZONING PLAN