Network Solutionswww.mcscontrols.com
Rev. 2015-03-04
Presentation OverviewPresentation Overview
Network Hardware Types
Network Protocols
Network Adapters
MCS-Magnum Communication
MicroMag Communication
Example Network Configurations
Network Hardware TypesNetwork Hardware Types
Four network hardware types that are used in MCS products:
RS485
RS232
Ethernet
LonWorks (twisted pair)
RS485 HardwareRS485 Hardware One twisted pair (two conductors) Shielded wire – wrapped foil with drain wire Minimum AWG 20 Max baud rate: 115,000 bit/s Multidrop – point to point
Max 30 MCS Controllers wired together
Total Network cable length < 4000’ (1219m)Can be lengthened with a repeater
RS232 HardwareRS232 Hardware
One to one Three conductor 9 or 25 pin connecter Max total cable length < 50’
(15m) Can be lengthened with a
repeater
Ethernet HardwareEthernet Hardware Star topography 4 twisted pairs (8 conductors) CAT5E Max baud rate: 10 Mbit/s Max cable length < 328’ (100m)
Can be lengthened with a switch
LonWorks HardwareLonWorks Hardware One twisted pair (two conductors) Shielded
wire Free topography Minimum AWG 20 Total Network cable length < 3280’
(1000m) Can be lengthened with a repeater
Network ProtocolsNetwork Protocols Network protocols are formatting rules
that specify how data is sent and received between devices.
Protocols are necessary for devices to interact with each other
Protocols MCS controllers support: Bacnet Modbus LonTalk Johnson N2 MCS
Network ProtocolsNetwork Protocols The MCS Controllers support the
following network protocols:
Over Ethernet
Over RS485
Over LonWorks
MCS Network AdaptorsMCS Network Adaptors
MCS uses five different optional network adapters: Hardware Adapters
MCS-485-Gateway (RS232 - RS485)
MCS-Ethernet (Ethernet - RS232)
MCS-USB-RS232 (USB - RS232)
Hardware & Protocol Adapters MCS-BMS-Gateway (Bacnet MSTP, LonTalk, Johnson N2)
MCS-Bacnet-Router2 (Bacnet IP)
MCS-485-GatewayMCS-485-Gateway
Converts between RS485 and RS232
Used with the MicroMag for a connection to: PC (MCS-Connect) MCS-Touch (MCS-
Connect) MCS-Ethernet
Can be powered from MCS Controller
Only hardware conversion, does not change protocol
MCS-EthernetMCS-Ethernet
Converts between Ethernet and RS232
Used with the MicroMag for Ethernet connection to: Internet
Comes with 120V wall outlet power adapter
Only hardware conversion, does not change protocol
MCS-USB-RS232MCS-USB-RS232 Converts between
USB and RS232 Used for PC (MCS-Connect)
communication Powered through USB port Only hardware conversion, does not
change protocol
MCS-BMS-GatewayMCS-BMS-Gateway Converts Bacnet MSTP (RS485) to:
LonTalk (LonWorks) Johnson N2 (RS485)
Converts Bacnet IP (Ethernet) to: LonTalk (LonWorks) Johnson N2 (RS485) Bacnet MSTP (RS485)
Only supports one MCS-Magnum or MicroMag Can be powered from MCS Controller
MCS-Magnum EthernetBacnet IP
RS485Bacnet MSTP
MCS-BMS-Gateway
MCS-BMS-Gateway
RS485•Johnson N2•Bacnet MSTP
LonWorks•LonTalk
MicroMag
Or
RS485•Johnson N2
LonWorks•LonTalk
Or
MCS-Bacnet-Router2MCS-Bacnet-Router2
Converts Bacnet MSTP (RS485) to Bacnet IP (Ethernet)
Supports up to 30 MicroMag
Can be powered from MicroMag
MicroMag RS485Bacnet MSTP MCS-Bacnet-Router2
Ethernet•Bacnet IP
MCS-Pocket Router-2MCS-Pocket Router-2 The MCS-POCKET ROUTER-2 is the perfect travel
companion for anyone who needs fast, easy wireless internet access on the go. Designed with a portable form factor that easily fits into a pocket, a laptop case, or the palm of your hand
Easy SetupMCS-POCKET ROUTER-2 ships with a different default SSID and encryption enabled by default. Check the bottom of the Pocket Router-2 for the security key used by your router, or change it to one of your own choosing.
110# power cordUSB cable to MCS-POCKET ROUTER-2
Kit Components
The MCS-POCKET ROUTER-2, 2.4GHz wireless technology allows 11n data transfer rates of up to 150Mbps while still remaining compatible with older 11b/g devices.
Powered by USB for extreme portabilityThe MCS-POCKET ROUTER-2 can be USB-powered to ensure convenient internet access anywhere
Advanced Security FeaturesTo provide the highest data security possible, the MCS-POCKET ROUTER-2 supports WEP, WPA, and WPA2 encryption. It also comes equipped with firewall features like NAT (Network Address Translation), VPN pass-through, and SPI (Stateful Packet Inspection) to prevent attacks from the internet.
MCS-WIRELESS-3GMCS-WIRELESS-3G Broadband Router with Integrated Verizon 3G Modem
(Only for use in USA)
The MCS-WIRELESS-3G is a powerful tool that is especially useful in locations where there is no readily available internet connection. Combined with the data plan, the MCS-WIRELESS-3G may be used to wirelessly connect to the MCS-MAGNUM wherever a cellular signal is found.
NOTE: The MCS-WIRELESS-3G can be used to communicate with multiple MSC Controllers. Email: [email protected] for more information.
The MCS-WIRELESS-3G is built for your network. It’s a highly-featured, compact router designed for critical industrial applications that require 24x7 connectivity.
The router features a built-in high-speed Verizon 3G EVDO modem. Supplied with one year subscription to MCS Wireless Verizon Data Plan, 250MB per month.
You will receive everything you need to setup communication with an MCS Controller, one year Verizon 250MB per month data plan and a crossover Ethernet cable to link the MCS-WIRELESS-3G to the MCS Controller board.
MCS also offers an MCS-WIRELESS-ROUTER-No Modem, for users who like the idea of wireless connection but want to supply their own Broadband Modem and Data Plan.
MCS-Magnum CommunicationMCS-Magnum Communication
RS485 Port
Ethernet Port
The MCS-Magnum comes with two hardware communication ports:
MCS-Magnum CommunicationMCS-Magnum Communication The MCS-MAGNUM-DOOR-NEMA4 Keypad has been sealed in its own frame using a new Gasket
(BISCO HT-800 Medium Cellular Silicone). The RS485 port has been added to the back of the Keypad. Moving the communicating port to the back, adding the new gasket, provides the unit with a NEMA4 rating. Operating Temperature -4°F to +158°F (-20°C to +70°C)
RS485 port on the MCS-Magnum
Keypad showingNew design,adding RS-485 connection
New GasketProvides the unit with a NEMA4 rating
MCS-USB-RS485
PC(MCS-Connect)
MCS –USB-RS485MCS –USB-RS485 The MCS-USB-RS485 cable is a USB to RS485 levels
serial that provides a fast, simple way to connect to MCS controllers, such as the and the MCS-MICROMAG.
The MCS-USB-RS485 cable contains a small internal electronic circuit board, utilizing the FT232R, which is encapsulated into the USB connector end of the cable. Each cable supports the FTDIChip-ID™ and is equipped with a
unique USB serial number programmed into the FT232R.
MCS-MAGNUM
MCS-Magnum RS485MCS-Magnum RS485 Using the RS485, the MCS-Magnum can be
connected to the BMS (Modbus RTU or MCS 485)
RS485
...Building
Management System
The RS232 cannot be used with different protocols when the RS485 is used
Wiring Multiple MCS ControllersWiring Multiple MCS Controllers
...
Using the RS485, the network must be wired controller to controller
Star configurations not allowed Up to 30 controllers can be wired together
Correct Incorrect
MCS-Magnum EthernetMCS-Magnum Ethernet Using the Ethernet, the MCS-Magnum can
be connected to: BMS (Bacnet IP or Modbus IP) MCS-Touch (MCS-Connect) PC (MCS-Connect) Internet access through router (which allows connection
via MCS-Connect from anywhere)
Ethernet
Or
Or
Or
MicroMag CommunicationMicroMag Communication
Ethernet access can be added with the MCS-Ethernet
The MicroMag comes standard with two independent ports:
RS232 Port
RS485 Port
MCS-PC9-MM cable
The MicroMag RS232 serial port only supports MCS protocol. It can be used to connect to: MCS-Touch (MCS-Connect) PC (MCS-Connect)
The PC may require USB to RS232 adapter, MCS Part # (MCS-USB-RS232)
MicroMag RS232MicroMag RS232
Or
PC(MCS-Connect)
MCS-Touch
MCS-USB-RS232
MicroMag RS485MicroMag RS485 The MicroMag RS485 port can be used to connect:
MCS-Touch (MCS-Connect) BMS (Bacnet MSTP or Modbus RTU or MCS 485)
Or
Building Management
System
MCS-Touch
...RS485
MicroMag RS485MicroMag RS485 The MicroMag RS485 port can be used to connect:
MCS-Touch (MCS-Connect) BMS (Bacnet MSTP or Modbus RTU or MCS 485)
Internet Access using: MCS-485-GATEWAY and the MCS-Ethernet
MCS-485-GATEWAY MCS-ETHERNET
RS232 9pin 25pin
Ethernet
Internet Router
...RS485
Ethernet
MCS-Touch
Ethernet
Example Network #1Example Network #1Standalone MCS-Magnum
MCS-Touch
Ethernet
Building Management
System
MCS-Touch
Internet Router
Example Network #2Example Network #2Standalone MCS-Magnum MCS-Touch BMS (Johnson N2 or LonTalk or Bacnet MSTP) Internet Access
MCS-BMS-Gateway
RS485 or LonWorks
Ethernet
Rooftop/Chiller #1
Building Management
System
Internet Router
Example Network #3Example Network #3Multiple MCS-Magnum Enclosures
Internet Access BMS (Bacnet IP or Modbus IP)
Rooftop/Chiller #2
RS485
MCS-Touch
Building Management
System
Example Network #4Example Network #4Standalone MicroMag
MCS-Touch BMS (Modbus RTU or Bacnet MS/TP)
MCS-PC9-MM cableRS485
MCS-485-Gateway
RS485
MCS-Touch
Example Network #5Example Network #5Multiple MicroMags
BMS (Bacnet MSTP or Modbus RTU or MCS 485) MCS-Touch
Building Management
System
RS485
RS232
RS232
RS232
Advanced Example Network Advanced Example Network
MCS-Bacnet-Router2
Building Management
System
MCS-ETHERNET-SWITCH
MCS-Touch
Multiple MCS-Magnum & Multiple MicroMag
MCS-Touch BMS (Bacnet IP)
QUESTIONS ON NETWORK QUESTIONS ON NETWORK SOLUTIONSSOLUTIONS
For additional information please visit our website www.mcscontrols.com
Or call MCS at 239-694-0089
5580 Enterprise Pkwy.Fort Myers, FL 33905Office: 239-694-0089Fax: 239-694-0031 www.mcscontrols.com