1. APPLICATION FORM
2. DECI.AMTION FORM
3. COPY OF THE LATEST BILL ON WHOSE NAME THE NET METERING
SOLAR POWER PROJECT PROPOSED TO BE INSTALLED
4. SINGLE LINE DIAGMM PROPdSED FOR NET METERING
FORM.I
NET METERING APPLICATION FORM
TO DATED:
Executive Engineer cum Nodal Officer,Electy. Op Divn. No. 2, New Power House,tndustrial Area Ph-I (opp. Transport Area' Sector-26)'
. UT Chandigarh-I / We herewith apply for a Solar Energy Net Metering with bi-directional
metering connection at the service connection for the solar Power Project of which
details are given below:
Sr. No; Details Required Details FurnishedI. Name of Applicant
2, Address of applicant
J. Service connection number
If there is Electricity Connection in
the name of the applicant, PleaseDrovide details
\ Is it for an individual premises or fora Grouo/ Sociew
o. Land Line Numbe(s)
7. Mobile Phone Number
8. Email Contact if available
9. Solar Plant Capacity kwp
10. Solar Inverter make & type
11. Solar Power Project invefter has
automatic isolation protection (Y/N)?
tz. Has a Solar Generation Meter been
installed (Y/N)?
13. Expected date of commissioning ofSolar Power Project
74. Concerned Safety requirementfulfilled (Yes/No)
15. Details of other service connectionin the name of Prosumer within UTchandioarh
16. Accelerated Depreciation claimed(Yes/No)
t7. Subsidy availed (Yes / No)
DECLAMTION
I do herebv declare that the information furnished above is true to my knowledge and
belief.
Signature with Name:
Position if on behalf of a Group or a Society
Address:
FORM-II
Declaration
I hereby declare that the information furnished in form-I (application form) is
true to the best of my knowledge and behalf. If found false at any stage, CED has the
right to reiec(/cancel the application and forfeit the application fees. Further, I hereby
agree ivith the specifications, terms and -,conditions stipulated in the regulation
applicable/notified by JERC as amended from time to time. I also confirm that I am
aware of the conditions stipulated in the CEA regulations on Technical Standards for
conneQivity of the Distributed Generation Resources) Regulations 2013 or any other
related r€gulations or as amended thereof and confirms that t will abide by the same. I
hereby conflrm that I have also read the Terms and Conditions for.Gross Metering for
Rooftop/ Ground Mounted Solar power plant (Form-6) and I will be abide by the same.
Place: Signature3
Date: Name:Address:-
FORM - 3..- Net-meterino Applacation Acknowl€doement
Rec€ived an application for a solar energy Net metering connection from,(To be filled by the appticant)
. Name:
Service Connection number:
Solar Plant Capaciw
Your application for setting up of solar grid interactive roof_top /small SpV powerplant under policy on Net metering in accordance solar power - Grid connected. Ground Mounted and Solar Rooftop and Metering Regulations - 2014 notinbd byHonble Joint Electricity Regulatory commission has been submitted arono withregistratjon fee amounung to Rs /_(in words also).
(To be filled in office),
The details of payment are as below:
Mode of payment:- D.D./Cash
Demand Draft No./8.A.16 No.:-
Date:
Name af Bank in case of O.O.-.
Amount:
ApplicaUon Registration no.:
. Signature :
Name of Authorized person of the Nodal Office:
FORM-4
Format for so|ar Net MeterineJ"Tlilfl'rtT8?'J'gi"*"
A. Service Connection Details:
Bill Group:1. Name of the Consumer:
2. Address:
3. Telephone No/Mobile No:
4. Email address:
5. Service connection number:
6. Tariff Category :
7. Sanctioned Load in kW (A):
8. Existing service connection metera) Single / three phase:b) Capacity in amPerec) Direct reading or current-transformer operated:
9, Landmark/Identiflcation
B. Distribution Transformer Details:
1. Name/Make of the distribution transformer (DTR):
2. Location of DTR:
3. Name of the HT feeder:
4. DTR capacity in KVA (B):
5. Voltage ratio of the DTR:
6. Solar PV Connection already connected to this DTR:
7. Solar PV capacity already connected to this DTR in KW (C):
8. Proposed Solar PV capacity in KW (D);
9. Total Solar PV capacity including the proposed new capacity(E=C+D):
Note; The proposed solar Pv capacity/ addition is technically feasible if1' The totat solar PV capacity (E) in kW is not more than 30o/o of the DTR
capacity in KVA (B) [E <= B x 30olo] and2. The proposea ioiai Pv capacity in kw (D) does not exceed the
sanctloned load of the service connection in kW (A) [D <= A]'3. In case of Net solar on single phase, the connectivity should be at the
heaviest load phase for maximum benefit and minimum currentimbalance,
In view of above the Proposed solar PV capacity/addition is technically
feasible/not feasible (strike out which is not applicable)
DATED:SIGNATURE OF THE SUBDMSIONAL OFFICER (withstamP)Electy'OP' S/DIVN. NO.
FORM _5
' Format for Feasibility intimation Letter to Consumer
FTom DATED:
Executive Engineer cum Nodal Officer
Elecw. OD Divn, No. 2, New Power House,
Industrial Area Ph-I (Opp. Transport Area, Sector-26)
UT Chandiga'rh .
To
Memo. No. Dated:
Dear Sir/Madam,
Subject: SolarNet/Gross-Metering:Technical Feasibilityintimation
Ref : Your application No
The aDplication for solar net/Gross metering of your proposed grid-connected
PV system of KW proposed at Service connection
number-is technically feasible.
You are requested to proceed with the installation of the solar PV system and
inform us as soon as the system is ready for inspection, This Technical Feasibility
Intimation is valid for a period of 180 days (For Ground mounted projects the Solar
Power developer can take time up to 365 days) from the date of intimation of the
technical feasibiliw. we need to receive your installation readiness communication
within above cited period. You may intimate your readiness to this office by letter, in
person or by email at solarpvced(oqmail.com to Executive Engineer cum Nodal Officer,
Electy. Op. Divn. No. 2, UT Chandigarh. The Solar Power developer failing to meet
these deadlines will have to seek fresh approval as per the regulations. The test report
of the installation shall be submitted to this office within stipulated period.
Executive Engineer cum Nodal officerElecty. Op, Divn, No' 2UT Chandigarh
FORM-6
. TERMS AND CONDITION FOR NET METERING FOR ROOFTOP/GROUND
MOUNTED SOLAR POWER PLANT
1. The Nodal ooint of contact for solar Net metering shall be the Executive Engineer
ElectriciW Operation Division No. 2, UT Chandigarh (Nodal Officer).
-fhe consute, can download the checklist including solar net metering rooftop
application (Form-1) and declaration form (Form-2) from the website
www.chdeng'ineering.gov.in and submit the application to the Nodal office and
tfrJjppiication fee of as.S0r per KW along with the declaration form and other
requisite documents as per the Checklist' The acknowledgement of the
application (Form-3) received with registration no. shall be provided by Nodal
Offlce.
The nodal omce shall complete the feasibility analysis of the Distribution
Transformer capaciry within 15 working days from the date of receipt of
completed Application Form and shall ensure that the solar net metering
application are processed expeditiously so that the solar energy targets set by
the Hon'ble JEdC are meticulously realized. The format for seeking the feasibility
is attached as Form-4.
3.
4. On receipt of the Feasibility Report from the concerned Sub Divisional Offlcer,
the Nodal officer shall accord solar net metering approvals on non-
discriminatory & first come first served basis until the grid connected Solar Power
installed capacity reaches 30% of the closest upstream Distribution Transformer
rated capacity based on the verification by the Sub Divisional Officer (Operation)
concerned. The format for Feasibility Intimation /Approval is attached as Form-5
5. The prioriry for such applications shall be maintained at Sub Divisional office
(OP) and at the Nodal Office Level for which a separate register shall be
maintained by them.
6. The solar project shall not exceed the service connection capacity / sanctioned
Ioad. If a consumer proposes to install a solar project with the capacity that
exceeds the service connection sanctioned load, a service connection
enhancement aDDlication shall be submitted by the consumer before submission
of the solar net metering application. Service connection. enhancement
applications shall be processed as per the existing standard procedures'
7. If the application for solar net metering is found feasible, the approval shall be
granted'to the Consumer for grid connectivity of the Solar Project' This approval
ihall contain the minimum permissible capacity of the Solar Project' The
consumer shall install a Solar Project (within permitted Capacity limits)
8. Solar Power Developer will set up the plant in 180 days (For Ground mounted
prolecE the Solar Power developer can take time up to 365 days) f(om the date
of [he Technical Feasibiliry Intimation letter. In case of delay the consumer shall
have to get further extension from the Distribution Licensee. such extension will
be grantld for a maximum period of 2 (two) months only and the approval
gran-ted will lapse automaticaily if the projact is not setup even in the extended
2-months period. However, hei stre wiil be eligible to apply in the next financial
year but his / her application will be kept at the bottom of the list of applicants
ind he/ she will be permitted to set-up the plant only if all the applicants above
him/ her are selected and there is still capacity available for allotment'
9. When the Consumer has installed the Solar Project, he shall intimate his
readiness by post/by e-mail ( [email protected] ) or in person to the Nodal
Officer along with Single Line Diagram. The Nodal Officer shall acknowledge the
readiness intimation immediately' Readiness intimation shall be followed by
safew insDection and commissioning of Solar Net metering to be carried out as
per rules and reg ulations.
10.Safety inspection for grid connected Solar Project should be obtained from the
appropriate authoritiei (Electrical Inspectorate of Chandigarh Administration)'
the safew inspections shall be carried out by the inspection authority within 10
(Ten) working days from the date of readiness intimation by the Consumer'
iafety certific;tes shall be issued within 5 (five) working days from the date of
safety inspection or rectification of defects, if any. The nodal officer may
fdcilitate that the safety inspection of Solar Project by the Electrical Inspectorate
takes place as per the above mentioned time schedule through close co-
ordination with the Electrical lnspectorate.
11, l4andatory safety precautions/features which have to be taken into
consideration as part of the grid connected solar Project installations are:-
a) The Solar Power Output feeder from the location of the installation / premises
shall have all time access by the Distribution Licensee, for isolation in case of
repair on Power distribution system. The solar plant shall comply with the
reievant standards specified by the MNRE / Bureau of Indian Standards (BIS)
and CEA. The responsibility of operation and maintenance of the Solar Photo
Voltaic (SPV) Generator including all accessories and apparatus lies with the
consumer.
b) The design and installation of the rooftop SPV should be equipped with
approprialely rated protective devices to sense any abnormality in the system
and carry out automatic isolation of the SPV from the grid The inverters used
should meet the necessary quality requirements and should be certified for
their quality by appropriate authority; the protection logics should be tested
before commissioning of the plant.
c) The automatic isolation or islanding protection of SPV should be ensured for,
no grid supply and low or over vbltage conditions and within the required
resp;nse time. Adequate rated fuses and fast acting circuit breakers on input
and output side of the inverters and disconnect/isolating switches to isolate
DC and AC system for maintenance shall be provided' The consumer should
Drovide for all internal safety and protective mechanism for earthing, surge'
DC ground fault, transients etc,
d) To prevent bqck feeding and possible accidents when maintenance works are
cariied out by Distribution Licensee personnel, Double polen-riple pole with
neuhal isolating disconnect switches which can be locked by Distribution
Licensee personnel should be provided. Responsibility of handling /maintaining such disconnect switches will be the responsibility of the Owner
ofthepremisesinWhoseterritorythisswitchisinsta||ed.Thisdisconnectingswitch is in addition to automatic sensing and isolating device on grid supply
failure,anda|soisinadditiontoanyotherinterna|disconnectswitchesprovided or needed to be provided keeping in view the safety of hYmln:. &
any animals. In the eveni of LT/HT supply failure from the end of the
Distribution Licensee, the consumer has to ensure that there will not be any
Solar Power being fed to the LT/HT grid of Distribution Licensee' The
consumer is solely responsible for any accident to human beings / animals
whatsoever (fatai /non{atal /departmental /non-departmental) that may
occur due to back feeding from the SPV plant when the grid supply is off'
DistributionLicenseereservestherighttodisconnecttheinsta||ationatanytime in the event of damage to its grid, meter, etc. or to prevent accident or
damage.
e) The consumer shall abide by all the codes and regulations issued by the
Commission to the extent applicable and in force from time to time' The
consumer shall comply with JERC/Dishibution Licensee /CEA requirements
with resoect to safe, secure and reliable function of the SPV plant and the
grid. The power injected into the grid shall be of the required quality as per
limits specified in these regulations or any other standards prescribed by CEA
from time to time that are applicable at the time of Solar Project installation'
F) The consumer shall restrict the harmonic generation within the limit specifled
in the agreement or specified by the Central Electricity Authority as and when
such regulation is issued.
S) The Solar Power Generator (SPG) (individual homes/commercial, establishments and other entities deflned under eligibility criteria ) may
establish grid interactive solar power plant in the Rooftop or elevated surface
with the following options:i. Grid interactive Solar Svstem without battery.ii. Grid interactive Solar System with battery backup.
However, in both the options, features as per these regulations shall
be available so as to ensure islanding of the Solar system & prevent back
feeding to Grid system of the Distribution Licensee. The invefter standard
shall be such that it should not allow Solar Pv/battery power to extend toDistribution Licensee's grid on failure of Distribution Licensee's grid supply,
irrespective of the connectivity options. The required inverter standards forthree phase and single phase Solar PV are furnished in the regulations. The
inverter should be a sine wave invefter. Harmonic standards shall be as per
IEEE 519.
h) Solar Power systems will be allowed with in house auto synchronization /de-synchronization facility with distribution system of the licensee at generation
voltage level. They will utilize the same service line for excess power
injection into the Grid which is currently being used by the consumer for
drawl of power from utility's grid and will operate in synchronization with
Distribution licensee's system provided that such injection of power from the
Rooftop solar system shall not be more than the limit of the total
consumption from the licensee's supply by the consumer in a Settlement
Period. However, specific approval of the licensee will be required in case the
above said limit is required to go beyond the said limit, keeping in view the
Capacity available in the Transformer where the Solar Power is to be grid
fed, it will be decided by the Dishibution Licensee to see the overall average
cost of power purchase. It will be mandatory for the solar rooftop generator
to provide an appropriate protection system on their incoming side/
consumer premises with the feature of "Islanding the solar generator"/ so as
to achieve isolation of consumer power-system from utility power-system
during grid failure including protection from voltage / lightning surges.
Islanding protection will be installed by the Solar Power Generator and thedistribution licensee to ensure that it is effectively working including when
operating on Batteries, The Power Conditioning Unit of the solar plant shall
have features to filter out harmonics and other distortions before injecting
the energy into the system of the Distribution Agency. The harmonics &
invener standards are as specified in the requlations
12. A single bi-directional service connection meter shall be installed to measure
import and export (Kwh) separately. For existing service connections, the
uni-directional service connection meter shall be replaced with a bi-
directional service connection meter.
13. Solar Generation meter to measure gross solar Pv energygeneration is mandatory for consumers' Solar Generation meters shall
be located at Ground floor adjacent to the bidirectional meter.
14. Upon receiving the consumer's request for effecting Solar net metering along
with the copy of the Safety Certificate and the singed net metering
agreement, the Solar Project shall be connected to the grid by the respective
Sub Divisional Officer, Electy.(OP) within 10 (Ten) working days and the bF
directional service connection meter shall be sealed. The intimation of the
commissioning of solar power plant be sent to the Director/ Science and
Technology. UT Chandigarh and the Nodal Officer by SDO (Operation) within
5 days positively). The closing meter reading of the old service connection
meter and opening meter reading of the new bidirectional service connectlon
meter should be properly recorded'
15. Caution stiakers shall be used with the green back ground and the text
"Solar Power System'written in white lette-rs The size of these stickers shall
oe ro CU (widin) x 7 CM (height) with the text clearly printed in the centre
of the sticker. All SPV ownini iont'*"|.s should have a mandatory sign
board fitted near the exi*in6 meter reading terminal- stating that 'This
iervice is fitted with a LT grid donnected SPV plant'' The- Solar Power System
. ciution Stickers shall be fixed under the supervision of the Junior Engineer
in the following locations.
(a) on or near to, the service connection meter of service with grid
connected Solar Project;
(b) On the Consumer maln switch, of a service connection with a grid
connected solar Project;
(c) On LT poles wlth grid connected Solar Project at helght of about 150
meter from the ground;
(d) On LT feeder pillars with grid connected Solar Project on the street -facing door of the feeder Pillar'
(e) On each of the LT take off poles of a Distribution Transformer to which
Solar Project are connected
(f) On substation end of HT feeder having Solar Project'
16.AListofServiceconnect|onsWithgridconnectedSolarProjectsha||beavailable at the Nodal Office
(a) The Nodal Offlcer shall verity periodically the. expected generation with
the Solar Generation Neter and also compare the inverter meter reading
with Solar Generation Meter reading to avoid malpractices'
(b) A record may be maintained at the Nodal Offlce of each SPV plant
iommissioning date and other details including whether the inverter is a slne
wave inverter and comply with Harmonic requirements as seen in the test
ceftificate.
(c) The SPV qonnection details of pole/pillar box/DT/SS feeder end wise may
be maintained at Sub Divisional level as this information are vltal'
17. CED personnel reserve the right to inspect the solar Project and grid
connection routinely in accordance with the provision of Electricity Act, 2003'
18. Meter Reading & Billing
(a) The service connection meter readings of solar service connections can
L" t tun along with the readings of otlier service connections as per the
itandard metei reading scheduli' The settlement period for final settlement
of net-metered un"rgv tnuii b.6 months (30th September and 31* March)'
(b) In case of a net import bill, the Consumer shall settle the same as per
exlsting norms and the applicable service connections tariff' If in any billing
;;l; ;""6t exported u"t!"ai"n"tgv imported, the surplus of export Kwh
oir"iitpoft'f*fi shall be carried ovei lo the next billing cycle for adjustment
.iii"if'tn. itport Kwh of that billing cycle' A meter card to recoro
separately the servlce connection 'import' fwn and export Kwh and the
iuiJingt'of the Solar Generation Meter and Solar Generation check meter
i*n"tJ "u.t applicable) with a facility to incorporate both the assessors ano
iontumers initials shall be provided by CED'
(c) For final settlement at the end of a Settlement Period a maximum of
i-rio"z" ton" hundred percent) of the impofted energy, will be credited as
""pott"i energy for the puriose of net-metering' Surplus energy expoded
to the Crid at the Solar Power Premises in excess of 100o/o (one hundredpercent) of imported energy may be adjusted in another electricity service
connection of the Prosumer within the State or Union Territory. Excess
energy exported to the grid (measured in kWh) may only be utilized to offsetthe consumption (measured in kwh) and may not be utilized for adjustmentof any other fees or charges levied by the Distribution Licensee. The
Distribution Licensee in addition to energy billing shall be eligible to raise
Invoices for any other charges as allowed by the Commission. Electricity
, Dufy, if applicable, shall be payable on the net energy imported from thegrid
d) The Net-metering injection is not eligible for REC (Renewable Energy
Certificate). The quantum of electricity purchased by the DistributionLicensee of the respective licensee area under the commission's jurisdiction
shall get covered towards the Solar RPOS for the Solar Power purchased
from any consumer who is either a Non-obligated or an obligated entitywhether covered under Solar Rooftop with Net Metering. The Ground
mounted Solar PV and Solar Thermal projects are also tovered. The self-consumption of the Solar Power Generated will also be counted towards theRPOS of the Distribution licensee, if the Solar Power Generator is meteredand such generation is ceftified by the nominated State Nodal Agency i.e.
Director/Science and Technology, UT Chandigarh.
19. Remaining Terms & Conditions shall be as per JERC regulation 2015'
NOTE:
THE PROCEDURE HAS BEEN PREPARED BASED OIV THE
REGULATIONS AS NOTIFIED 8Y THE HON'BLE COMMISSIOIV.ITOWEVE& IN CASE OF ANY INCOMISTEwCY BETWEEItI THEPROCEDT'RE AND THE REGI'LATIONS, THE MEANING CONTAINEDIN THE REGULATIONS SHALL PREUAIL