2016 All Star Training, Inc. 1 NEC 2017 Code Changes Chapter 3 - Wiring Methods and Materials Changes from the 2014 code are highlighted in yellow. ARTICLE 300 - General Requirements for Wiring Methods and Materials Part I. General Requirements 300.1 Scope. (A) All Wiring Installations. This article covers general requirements for wiring methods and materials for all wiring installations unless modified by other articles in Chapter 3. (B) Integral Parts of Equipment. The provisions of this article are not intended to apply to the conductors that form an integral part of equipment, such as motors, controllers, motor control centers, or factory-assembled control equipment or listed utilization equipment. (C) Metric Designators and Trade Sizes. Metric designators and trade sizes for conduit, tubing, and associated fittings and accessories shall be as designated in Table 300.1(C).

Transcript of NEC 2017 Code Changes Chapter 3 - Wiring Methods … 2017 Code Changes Chapter 3 - Wiring Methods...

2016AllStarTraining,Inc.

1

NEC 2017 Code Changes Chapter 3 - Wiring Methods and Materials

Changes from the 2014 code are highlighted in yellow. ARTICLE 300 - General Requirements for Wiring Methods and Materials PartI.GeneralRequirements

300.1Scope.

(A)AllWiringInstallations.Thisarticlecoversgeneralrequirementsforwiringmethodsand

materialsforallwiringinstallationsunlessmodifiedbyotherarticlesinChapter3.

(B)IntegralPartsofEquipment.Theprovisionsofthisarticlearenotintendedtoapplytothe

conductorsthatforman

integralpartofequipment,

suchasmotors,controllers,

motorcontrolcenters,or

factory-assembledcontrol

equipmentorlisted

utilizationequipment.

(C)MetricDesignatorsand

TradeSizes.Metric

designatorsandtradesizes

forconduit,tubing,andassociatedfittingsandaccessoriesshallbeasdesignatedinTable

300.1(C).

2016AllStarTraining,Inc.

2

300.2Limitations.

(A)Voltage.WiringmethodsspecifiedinChapter3shallbeusedfor1000volts,nominal,orless

wherenotspecificallylimitedinsomesectionofChapter3.Theyshallbepermittedforover

1000volts,nominal,wherespecificallypermittedelsewhereinthisCode.

(B)Temperature.Temperaturelimitationofconductorsshallbeinaccordancewith

310.15(A)(3).

300.3Conductors.

(A)SingleConductors.SingleconductorsspecifiedinTable310.104(A)shallonlybeinstalled

wherepartofarecognizedwiringmethodofChapter3.

Exception:Individualconductorsshallbepermittedwhereinstalledasseparateoverhead

conductorsinaccordancewith225.6.

(B)ConductorsoftheSameCircuit.Allconductorsofthesamecircuitand,whereused,the

groundedconductorandallequipmentgroundingconductorsandbondingconductors

shallbecontainedwithinthesameraceway,auxiliarygutter,cabletray,cablebusassembly,

trench,cable,orcord,unlessotherwisepermittedinaccordancewith300.3(B)(1)through

(B)(4).

(1)ParalleledInstallations.Conductorsshallbepermittedtoberuninparallelin

accordancewiththeprovisionsof310.10(H).Therequirementtorunallcircuit

conductorswithinthesameraceway,auxiliarygutter,cabletray,trench,cable,orcord

shallapplyseparatelytoeachportionoftheparalleledinstallation,andtheequipment

2016AllStarTraining,Inc.

3

groundingconductorsshallcomplywiththeprovisionsof250.122.Parallelrunsincable

trayshallcomplywiththeprovisionsof392.20(C).

Exception:Conductorsinstalledinnonmetallicracewaysrunundergroundshallbepermittedto

bearrangedasisolatedphase,neutral,andgroundedconductorinstallations.Theraceways

shallbeinstalledincloseproximity,andtheisolatedphase,neutral,andgrounded

conductorsshallcomplywiththeprovisionsof300.20(B).

(2)GroundingandBondingConductors.Equipmentgroundingconductorsshallbe

permittedtobeinstalledoutsidearacewayorcableassemblywhereinaccordancewith

theprovisionsof250.130(C)forcertainexistinginstallationsorinaccordancewith

250.134(B),ExceptionNo.2,fordccircuits.Equipmentbondingconductorsshallbe

permittedtobeinstalledontheoutsideofracewaysinaccordancewith250.102(E).

(3)NonferrousWiringMethods.Conductorsinwiringmethodswithanonmetallicor

othernonmagneticsheath,whererunindifferentraceways,auxiliarygutters,cable

trays,trenches,cables,orcords,shallcomplywiththeprovisionsof300.20(B).

Conductorsinsingle-conductorTypeMIcablewithanonmagneticsheathshallcomply

withtheprovisionsof332.31.Conductorsofsingle-conductorTypeMCcablewitha

nonmagneticsheathshallcomplywiththeprovisionsof330.31,330.116,and300.20(B).

(4)Column-WidthPanelboardEnclosures.Whereanauxiliarygutterrunsbetweena

column-widthpanelboardandapullbox,andthepullboxincludesneutralterminations,

theneutralconductorsofcircuitssuppliedfromthepanelboardshallbepermittedto

originateinthepullbox.

2016AllStarTraining,Inc.

4

(C)ConductorsofDifferentSystems.

(1)1000Volts,Nominal,orLess.Conductorsofacanddccircuits,rated1000volts,

nominal,orless,shallbepermittedtooccupythesameequipmentwiringenclosure,

cable,orraceway.Allconductorsshallhaveaninsulationratingequaltoatleastthe

maximumcircuitvoltageappliedtoanyconductorwithintheenclosure,cable,or

raceway.Secondarywiringtoelectric-dischargelampsof1000voltsorless,ifinsulated

forthesecondaryvoltageinvolved,shallbepermittedtooccupythesameluminaire,

sign,oroutlinelightingenclosureasthebranch-circuitconductors.

InformationalNoteNo.1:See725.136(A)forClass2andClass3circuitconductors.

InformationalNoteNo.2:See690.4(B)forphotovoltaicsourceandoutputcircuits.

(2)Over1000Volts,Nominal.Conductorsofcircuitsratedover1000volts,nominal,

shallnotoccupythesameequipmentwiringenclosure,cable,orracewaywith

conductorsofcircuitsrated1000volts,nominal,orlessunlessotherwisepermittedin

300.3(C)(2)(a)through300.3(C)(2)(d).

(a)Primaryleadsofelectric-dischargelampballastsinsulatedfortheprimaryvoltageof

theballast,wherecontainedwithintheindividualwiringenclosure,shallbepermitted

tooccupythesameluminaire,sign,oroutlinelightingenclosureasthebranch-circuit

conductors.

(b)Excitation,control,relay,andammeterconductorsusedinconnectionwithany

individualmotororstartershallbepermittedtooccupythesameenclosureasthe

motor-circuitconductors.

2016AllStarTraining,Inc.

5

(c)Inmotors,transformers,switchgear,switchboards,controlassemblies,andsimilar

equipment,conductorsofdifferentvoltageratingsshallbepermitted.

(d)Inmanholes,iftheconductorsofeachsystemarepermanentlyandeffectively

separatedfromtheconductorsoftheothersystemsandsecurelyfastenedtoracks,

insulators,orotherapprovedsupports,conductorsofdifferentvoltageratingsshallbe

permitted.

Conductorshavingnonshieldedinsulationandoperatingatdifferentvoltagelevelsshallnot

occupythesameenclosure,cable,orraceway.

300.4ProtectionAgainstPhysicalDamage.Wheresubjecttophysicaldamage,conductors,

raceways,andcablesshallbeprotected.

InformationalNote:Minordamagetoaraceway,cablearmor,orcableinsulationdoesnot

necessarilyviolatetheintegrityofeitherthecontainedconductorsortheconductors’

insulation.

(A)CablesandRacewaysThroughWoodMembers.

(1)BoredHoles.Inbothexposedandconcealedlocations,whereacable-orraceway-

typewiringmethodisinstalledthroughboredholesinjoists,rafters,orwoodmembers,

holesshallbeboredsothattheedgeoftheholeisnotlessthan32mm(11∕4in.)from

thenearestedgeofthewoodmember.Wherethisdistancecannotbemaintained,the

cableorracewayshallbeprotectedfrompenetrationbyscrewsornailsbyasteel

plate(s)orbushing(s),atleast1.6mm(1∕16in.)thick,andofappropriatelengthand

widthinstalledtocovertheareaofthewiring.

2016AllStarTraining,Inc.

6

ExceptionNo.1:Steelplatesshallnotberequiredtoprotectrigidmetalconduit,intermediate

metalconduit,rigidnonmetallicconduit,orelectricalmetallictubing.

ExceptionNo.2:Alistedandmarkedsteelplatelessthan1.6mm(1∕16in.)thickthatprovides

equalorbetterprotectionagainstnailorscrewpenetrationshallbepermitted.

(2)NotchesinWood.Wherethereisnoobjectionbecauseofweakeningthebuilding

structure,inbothexposedandconcealedlocations,cablesorracewaysshallbe

permittedtobelaidinnotchesinwoodstuds,joists,rafters,orotherwoodmembers

wherethecableorracewayatthosepointsisprotectedagainstnailsorscrewsbya

steelplateatleast1.6mm(1∕16in.)thick,andofappropriatelengthandwidth,

installedtocovertheareaofthewiring.Thesteelplateshallbeinstalledbeforethe

buildingfinishisapplied.

ExceptionNo.1:Steelplatesshallnotberequiredtoprotectrigidmetalconduit,intermediate

metalconduit,rigidnonmetallicconduit,orelectricalmetallictubing.

ExceptionNo.2:Alistedandmarkedsteelplatelessthan1.6mm(1∕16in.)thickthatprovides

equalorbetterprotectionagainstnailorscrewpenetrationshallbepermitted.

(B)Nonmetallic-SheathedCablesandElectricalNonmetallicTubingThroughMetalFraming

Members.

(1)Nonmetallic-SheathedCable.Inbothexposedandconcealedlocationswhere

nonmetallic-sheathedcablespassthrougheitherfactory-orfield-punched,cut,or

drilledslotsorholesinmetalmembers,thecableshallbeprotectedbylistedbushings

2016AllStarTraining,Inc.

7

orlistedgrommetscoveringallmetaledgesthataresecurelyfastenedintheopening

priortoinstallationofthecable.

(2)Nonmetallic-SheathedCableandElectricalNonmetallicTubing.Wherenailsor

screwsarelikelytopenetratenonmetallic-sheathedcableorelectricalnonmetallic

tubing,asteelsleeve,steelplate,orsteelclipnotlessthan1.6mm(1∕16in.)in

thicknessshallbeusedtoprotectthecableortubing.

Exception:Alistedandmarkedsteelplatelessthan1.6mm(1∕16in.)thickthatprovidesequal

orbetterprotectionagainstnailorscrewpenetrationshallbepermitted.

(C)CablesThroughSpacesBehindPanelsDesignedtoAllowAccess.Cablesorraceway-type

wiringmethods,installedbehindpanelsdesignedtoallowaccess,shallbesupportedaccording

totheirapplicablearticles.

(D)CablesandRacewaysParalleltoFramingMembersandFurringStrips.Inbothexposedand

concealedlocations,whereacable-orraceway-typewiringmethodisinstalledparallelto

framingmembers,suchasjoists,rafters,orstuds,orisinstalledparalleltofurringstrips,the

cableorracewayshallbeinstalledandsupportedsothatthenearestoutsidesurfaceofthe

cableorracewayisnotlessthan32mm(11∕4in.)fromthenearestedgeoftheframing

memberorfurringstripswherenailsorscrewsarelikelytopenetrate.Wherethisdistance

cannotbemaintained,thecableorracewayshallbeprotectedfrompenetrationbynailsor

screwsbyasteelplate,sleeve,orequivalentatleast1.6mm(1∕16in.)thick.

2016AllStarTraining,Inc.

8

ExceptionNo.1:Steelplates,sleeves,ortheequivalentshallnotberequiredtoprotectrigid

metalconduit,intermediatemetalconduit,rigidnonmetallicconduit,orelectricalmetallic

tubing.

ExceptionNo.2:Forconcealedworkinfinishedbuildings,orfinishedpanelsforprefabricated

buildingswheresuchsupportingisimpracticable,itshallbepermissibletofishthecables

betweenaccesspoints.

ExceptionNo.3:Alistedandmarkedsteelplatelessthan1.6mm(1∕16in.)thickthatprovides

equalorbetterprotectionagainstnailorscrewpenetrationshallbepermitted.

(E)Cables,Raceways,orBoxesInstalledinorUnderRoofDecking.Acable,raceway,orbox,

installedinexposedorconcealedlocationsundermetal-corrugatedsheetroofdecking,shallbe

installedandsupportedsothereisnotlessthan38mm(11∕2in.)measuredfromthelowest

surfaceoftheroofdeckingtothetopofthecable,raceway,orbox.Acable,raceway,orbox

shallnotbeinstalledinconcealedlocationsinmetal-corrugated,sheetdecking–typeroof.

InformationalNote:Roofdeckingmaterialisoftenrepairedorreplacedaftertheinitial

racewayorcablingandroofinginstallationandmaybepenetratedbythescrewsorother

mechanicaldevicesdesignedtoprovide“holddown”strengthofthewaterproofmembraneor

roofinsulatingmaterial.

Exception:Rigidmetalconduitandintermediatemetalconduitshallnotberequiredtocomply

with300.4(E).

2016AllStarTraining,Inc.

9

(F)CablesandRacewaysInstalledinShallowGrooves.Cableorraceway-typewiringmethods

installedinagroove,tobecoveredbywallboard,siding,paneling,carpeting,orsimilar

finish,shallbeprotectedby1.6mm(1∕16in.)thicksteelplate,sleeve,orequivalentorbynot

lessthan32-mm(11∕4-in.)freespaceforthefulllengthofthegrooveinwhichthecableor

racewayisinstalled.

ExceptionNo.1:Steelplates,sleeves,ortheequivalentshallnotberequiredtoprotectrigid

metalconduit,intermediatemetalconduit,rigidnonmetallicconduit,orelectricalmetallic

tubing.

ExceptionNo.2:Alistedandmarkedsteelplatelessthan1.6mm(1∕16in.)thickthatprovides

equalorbetterprotectionagainstnailorscrewpenetrationshallbepermitted.

(G)InsulatedFittings.Whereracewayscontain4AWGorlargerinsulatedcircuitconductors,

andtheseconductorsenteracabinet,abox,anenclosure,oraraceway,theconductors

shallbeprotectedbyanidentifiedfittingprovidingasmoothlyroundedinsulatingsurface,

unlesstheconductorsareseparatedfromthefittingorracewaybyidentifiedinsulating

materialthatissecurelyfastenedinplace.

Exception:Wherethreadedhubsorbossesthatareanintegralpartofacabinet,box,enclosure,

orracewayprovideasmoothlyroundedorflaredentryforconductors.

2016AllStarTraining,Inc.

10

Conduitbushingsconstructedwhollyofinsulatingmaterialshallnotbeusedtosecureafitting

orraceway.Theinsulatingfittingorinsulatingmaterialshallhaveatemperatureratingnotless

thantheinsulationtemperatureratingoftheinstalledconductors.

(H)StructuralJoints.Alistedexpansion/deflectionfittingorotherapprovedmeansshallbe

usedwherearacewaycrossesastructuraljointintendedforexpansion,contractionor

deflection,usedinbuildings,bridges,parkinggarages,orotherstructures.

300.5UndergroundInstallations.

(A)MinimumCoverRequirements.Direct-buriedcable,conduit,orotherracewaysshallbe

installedtomeettheminimumcoverrequirementsofTable300.5.

(B)WetLocations.Theinteriorofenclosuresorracewaysinstalledundergroundshallbe

consideredtobeawetlocation.Insulatedconductorsandcablesinstalledintheseenclosures

orracewaysinundergroundinstallationsshallcomplywith310.10(C).

(C)UndergroundCablesandConductorsUnderBuildings.Undergroundcableandconductors

installedunderabuildingshallbeinaraceway.

ExceptionNo.1:TypeMIcableshallbepermittedunderabuildingwithoutinstallationina

racewaywhereembeddedinconcrete,fill,orothermasonryinaccordancewith332.10(6)orin

undergroundrunswheresuitablyprotectedagainstphysicaldamageandcorrosiveconditionsin

accordancewith332.10(10).

ExceptionNo.2:TypeMCcablelistedfordirectburialorconcreteencasementshallbe

permittedunderabuildingwithoutinstallationinaracewayinaccordancewith330.10(A)(5)

andinwetlocationsinaccordancewith330.10(A)(11).

2016AllStarTraining,Inc.

11

(D)ProtectionfromDamage.Direct-buriedconductorsandcablesshallbeprotectedfrom

damageinaccordancewith300.5(D)(1)through(D)(4).

(1)EmergingfromGrade.Direct-buriedconductorsandcablesemergingfromgrade

andspecifiedincolumns1and4ofTable300.5shallbeprotectedbyenclosuresor

racewaysextendingfromtheminimumcoverdistancebelowgraderequiredby300.5(A)

toapointatleast2.5m(8ft)abovefinishedgrade.Innocaseshalltheprotectionbe

requiredtoexceed450mm(18in.)belowfinishedgrade.

(2)ConductorsEnteringBuildings.Conductorsenteringabuildingshallbeprotectedto

thepointofentrance.

(3)ServiceConductors.Undergroundserviceconductorsthatarenotencasedin

concreteandthatareburied450mm(18in.)ormorebelowgradeshallhavetheir

locationidentifiedbyawarningribbonthatisplacedinthetrenchatleast300mm(12

in.)abovetheundergroundinstallation.

(4)EnclosureorRacewayDamage.Wheretheenclosureorracewayissubjectto

physicaldamage,theconductorsshallbeinstalledinelectricalmetallictubing,rigid

metalconduit,intermediatemetalconduit,RTRC-XW,Schedule80PVCconduit,or

equivalent.

(E)SplicesandTaps.Direct-buriedconductorsorcablesshallbepermittedtobesplicedor

tappedwithouttheuseofspliceboxes.Thesplicesortapsshallbemadeinaccordancewith

110.14(B).

(F)Backfill.Backfillthatcontainslargerocks,pavingmaterials,cinders,largeorsharplyangular

substances,orcorrosivematerialshallnotbeplacedinanexcavationwherematerialsmay

2016AllStarTraining,Inc.

12

damageraceways,cables,conductors,orothersubstructuresorpreventadequatecompaction

offillorcontributetocorrosionofraceways,cables,orothersubstructures.Wherenecessary

topreventphysicaldamagetotheraceway,cable,orconductor,protectionshallbeprovidedin

theformofgranularorselectedmaterial,suitablerunningboards,suitablesleeves,orother

approvedmeans.

(G)RacewaySeals.Conduitsorracewaysthroughwhichmoisturemaycontactlivepartsshall

besealedorpluggedateitherorbothends.Spareorunusedracewaysshallalsobesealed.

Sealantsshallbeidentifiedforusewiththecableinsulation,conductorinsulation,bare

conductor,shield,orothercomponents.

InformationalNote:Presenceofhazardousgasesorvaporsmayalsonecessitatesealingof

undergroundconduitsorracewaysenteringbuildings.

(H)Bushing.Abushing,orterminalfitting,withanintegralbushedopeningshallbeusedatthe

endofaconduitorotherracewaythatterminatesundergroundwheretheconductorsorcables

emergeasadirectburialwiringmethod.Asealincorporatingthephysicalprotection

characteristicsofabushingshallbepermittedtobeusedinlieuofabushing.

2016AllStarTraining,Inc.

13

(I)ConductorsoftheSameCircuit.Allconductorsofthesamecircuitand,whereused,the

groundedconductorandallequipmentgroundingconductorsshallbeinstalledinthesame

racewayorcableorshallbeinstalledincloseproximityinthesametrench.

2016AllStarTraining,Inc.

14

ExceptionNo.1:Conductorsshallbepermittedtobeinstalledinparallelinraceways,

multiconductorcables,ordirect-buriedsingleconductorcables.Eachracewayormulticonductor

cableshallcontainallconductorsofthesamecircuit,includingequipmentgrounding

conductors.Eachdirect-buriedsingleconductorcableshallbelocatedincloseproximityinthe

trenchtotheothersingleconductorcablesinthesameparallelsetofconductorsinthecircuit,

includingequipmentgroundingconductors.

ExceptionNo.2:Isolatedphase,polarity,groundedconductor,andequipmentgroundingand

bondingconductorinstallationsshallbepermittedinnonmetallicracewaysorcableswitha

nonmetalliccoveringornonmagneticsheathincloseproximitywhereconductorsareparalleled

aspermittedin310.10(H),andwheretheconditionsof300.20(B)aremet.

(J)EarthMovement.Wheredirect-buriedconductors,raceways,orcablesaresubjectto

movementbysettlementorfrost,direct-buriedconductors,raceways,orcablesshallbe

arrangedsoastopreventdamagetotheenclosedconductorsortoequipmentconnectedto

theraceways.

InformationalNote:Thissectionrecognizes“S”loopsinundergrounddirectburialcablesand

conductorstoracewaytransitions,expansionfittingsinracewayriserstofixedequipment,and,

generally,theprovisionofflexibleconnectionstoequipmentsubjecttosettlementorfrost

heaves.

2016AllStarTraining,Inc.

15

(K)DirectionalBoring.Cablesorracewaysinstalledusingdirectionalboringequipmentshallbe

approvedforthepurpose.

300.6ProtectionAgainstCorrosionandDeterioration.Raceways,cabletrays,cablebus,

auxiliarygutters,cablearmor,boxes,cablesheathing,cabinets,elbows,couplings,fittings,

supports,andsupporthardwareshallbeofmaterialssuitablefortheenvironmentinwhich

theyaretobeinstalled.

(A)FerrousMetalEquipment.Ferrousmetalraceways,cabletrays,cablebus,auxiliarygutters,

cablearmor,boxes,cablesheathing,cabinets,metalelbows,couplings,nipples,fittings,

supports,andsupporthardwareshallbesuitablyprotectedagainstcorrosioninsideandoutside

(exceptthreadsatjoints)byacoatingofapprovedcorrosion-resistantmaterial.Where

corrosionprotectionisnecessaryandtheconduitisthreadedinthefield,thethreadsshallbe

coatedwithanapprovedelectricallyconductive,corrosion-resistantcompound.

InformationalNote:Field-cutthreadsarethosethreadsthatarecutinconduit,elbows,or

nipplesanywhereotherthanatthefactorywheretheproductislisted.

Exception:Stainlesssteelshallnotberequiredtohaveprotectivecoatings.

(1)ProtectedfromCorrosionSolelybyEnamel.Whereprotectedfromcorrosionsolely

byenamel,ferrousmetalraceways,cabletrays,cablebus,auxiliarygutters,cablearmor,

boxes,cablesheathing,cabinets,metalelbows,couplings,nipples,fittings,supports,

andsupporthardwareshallnotbeusedoutdoorsorinwetlocationsasdescribedin

300.6(D).

2016AllStarTraining,Inc.

16

(2)OrganicCoatingsonBoxesorCabinets.Whereboxesorcabinetshaveanapproved

systemoforganiccoatingsandaremarked“Raintight,”“Rainproof,”or“OutdoorType,”

theyshallbepermittedoutdoors.

(3)InConcreteorinDirectContactwiththeEarth.Ferrousmetalraceways,cable

armor,boxes,cablesheathing,cabinets,elbows,couplings,nipples,fittings,supports,

andsupporthardwareshallbepermittedtobeinstalledinconcreteorindirectcontact

withtheearth,orinareassubjecttoseverecorrosiveinfluenceswheremadeof

materialapprovedforthecondition,orwhereprovidedwithcorrosionprotection

approvedforthecondition.

(B)AluminumMetalEquipment.Aluminumraceways,cabletrays,cablebus,auxiliarygutters,

cablearmor,boxes,cablesheathing,cabinets,elbows,couplings,nipples,fittings,supports,and

supporthardwareembeddedorencasedinconcreteorindirectcontactwiththeearthshallbe

providedwithsupplementarycorrosionprotection.

(C)NonmetallicEquipment.Nonmetallicraceways,cabletrays,cablebus,auxiliarygutters,

boxes,cableswithanonmetallicouterjacketandinternalmetalarmororjacket,cable

sheathing,cabinets,elbows,couplings,nipples,fittings,supports,andsupporthardwareshall

bemadeofmaterialapprovedfortheconditionandshallcomplywith(C)(1)and(C)(2)as

applicabletothespecificinstallation.

(1)ExposedtoSunlight.Whereexposedtosunlight,thematerialsshallbelistedas

sunlightresistantorshallbeidentifiedassunlightresistant.

2016AllStarTraining,Inc.

17

(2)ChemicalExposure.Wheresubjecttoexposuretochemicalsolvents,vapors,

splashing,orimmersion,materialsorcoatingsshalleitherbeinherentlyresistantto

chemicalsbasedontheirlistingorbeidentifiedforthespecificchemicalreagent.

(D)IndoorWetLocations.Inportionsofdairyprocessingfacilities,laundries,canneries,and

otherindoorwetlocations,andinlocationswherewallsarefrequentlywashedorwhere

therearesurfacesofabsorbentmaterials,suchasdamppaperorwood,theentirewiring

system,whereinstalledexposed,includingallboxes,fittings,raceways,andcableused

therewith,shallbemountedsothatthereisatleasta6-mm(1∕4-in.)airspacebetweenitand

thewallorsupportingsurface.

Exception:Nonmetallicraceways,boxes,andfittingsshallbepermittedtobeinstalledwithout

theairspaceonaconcrete,masonry,tile,orsimilarsurface.

InformationalNote:Ingeneral,areaswhereacidsandalkalichemicalsarehandledandstored

maypresentsuchcorrosiveconditions,particularlywhenwetordamp.Severecorrosive

conditionsmayalsobepresentinportionsofmeatpackingplants,tanneries,gluehouses,and

somestables;ininstallationsimmediatelyadjacenttoaseashoreandswimmingpoolareas;in

areaswherechemicaldeicersareused;andinstoragecellarsorroomsforhides,casings,

fertilizer,salt,andbulkchemicals.

300.7RacewaysExposedtoDifferentTemperatures.

(A)Sealing.Whereportionsofaracewayorsleeveareknowntobesubjectedtodifferent

temperatures,andwherecondensationisknowntobeaproblem,asincoldstorageareasof

2016AllStarTraining,Inc.

18

buildingsorwherepassingfromtheinteriortotheexteriorofabuilding,theracewayorsleeve

shallbefilledwithanapprovedmaterialtopreventthecirculationofwarmairtoacolder

sectionoftheracewayorsleeve.Anexplosionproofsealshallnotberequiredforthispurpose.

(B)Expansion,Expansion-Deflection,andDeflectionFittings.Racewaysshallbeprovidedwith

expansion,expansiondeflection,ordeflectionfittingswherenecessarytocompensatefor

thermalexpansion,deflection,andcontraction.

InformationalNote:Table352.44andTable355.44providetheexpansioninformationfor

polyvinylchloride(PVC)andforreinforcedthermosettingresinconduit(RTRC),respectively.A

nominalnumberforsteelconduitcanbedeterminedbymultiplyingtheexpansionlengthin

Table352.44by0.20.Thecoefficientofexpansionforsteelelectricalmetallictubing,

intermediatemetalconduit,andrigidmetalconduitis1.170×10-5(0.0000117mmpermmof

conduitforeach°Cintemperaturechange)[0.650×10-5(0.0000065in.perinchofconduitfor

each°Fintemperaturechange)].Anominalnumberforaluminumconduitandaluminum

electricalmetallictubingcanbedeterminedbymultiplyingtheexpansionlengthinTable

352.44by0.40.Thecoefficientofexpansionforaluminumelectricalmetallictubingand

aluminumrigidmetalconduitis2.34×10-5(0.0000234mmpermmofconduitforeach°Cin

temperaturechange)[1.30×10-5(0.000013in.perinchofconduitforeach°Fintemperature

change)].

2016AllStarTraining,Inc.

19

300.8InstallationofConductorswithOtherSystems.Racewaysorcabletrayscontaining

electricalconductorsshallnotcontainanypipe,tube,orequalforsteam,water,air,gas,

drainage,oranyserviceotherthanelectrical.

300.9RacewaysinWetLocationsAbovegrade.Whereracewaysareinstalledinwetlocations

abovegrade,theinterioroftheseracewaysshallbeconsideredtobeawetlocation.Insulated

conductorsandcablesinstalledinracewaysinwetlocationsabovegradeshallcomplywith

310.10(C).

300.10ElectricalContinuityofMetalRacewaysandEnclosures.Metalraceways,cablearmor,

andothermetalenclosuresforconductorsshallbemetallicallyjoinedtogetherintoa

continuouselectricalconductorandshallbeconnectedtoallboxes,fittings,andcabinetssoas

toprovideeffectiveelectricalcontinuity.UnlessspecificallypermittedelsewhereinthisCode,

racewaysandcableassembliesshallbemechanicallysecuredtoboxes,fittings,cabinets,and

otherenclosures.

ExceptionNo.1:Shortsectionsofracewaysusedtoprovidesupportorprotectionofcable

assembliesfromphysicaldamageshallnotberequiredtobemadeelectricallycontinuous.

ExceptionNo.2:Equipmentenclosurestobeisolated,aspermittedby250.96(B),shallnotbe

requiredtobemetallicallyjoinedtothemetalraceway.

300.11SecuringandSupporting.

(A)SecuredinPlace.Raceways,cableassemblies,boxes,cabinets,andfittingsshallbesecurely

fastenedinplace.

2016AllStarTraining,Inc.

20

(B)WiringSystemsInstalledAboveSuspendedCeilings.Supportwiresthatdonotprovide

securesupportshallnotbepermittedasthesolesupport.Supportwiresandassociated

fittingsthatprovidesecuresupportandthatareinstalledinadditiontotheceilinggridsupport

wiresshallbepermittedasthesolesupport.Whereindependentsupportwiresareused,

theyshallbesecuredatbothends.Cablesandracewaysshallnotbesupportedbyceilinggrids.

(1)Fire-RatedAssemblies.Wiringlocatedwithinthecavityofafire-ratedfloor–ceiling

orroof–ceilingassemblyshallnotbesecuredto,orsupportedby,theceilingassembly,

includingtheceilingsupportwires.Anindependentmeansofsecuresupportshallbe

providedandshallbepermittedtobeattachedtotheassembly.Whereindependent

supportwiresareused,theyshallbedistinguishablebycolor,tagging,orothereffective

meansfromthosethatarepartofthefire-rateddesign.

Exception:Theceilingsupportsystemshallbepermittedtosupportwiringandequipmentthat

havebeentestedaspartofthefire-ratedassembly.

InformationalNote:Onemethodofdeterminingfireratingistestinginaccordancewith

ANSI/ASTME119-2015,MethodforFireTestsofBuildingConstructionandMaterials.

(2)Non–Fire-RatedAssemblies.Wiringlocatedwithinthecavityofanon–fire-rated

floor–ceilingorroof–ceilingassemblyshallnotbesecuredto,orsupportedby,the

ceilingassembly,includingtheceilingsupportwires.Anindependentmeansofsecure

supportshallbeprovidedandshallbepermittedtobeattachedtotheassembly.Where

2016AllStarTraining,Inc.

21

independentsupportwiresareused,theyshallbedistinguishablebycolor,tagging,or

othereffectivemeans.

Exception:Theceilingsupportsystemshallbepermittedtosupportbranch-circuitwiringand

associatedequipmentwhereinstalledinaccordancewiththeceilingsystemmanufacturer’s

instructions.

(C)RacewaysUsedasMeansofSupport.Racewaysshallbeusedonlyasameansofsupport

forotherraceways,cables,ornonelectricalequipmentunderanyofthefollowingconditions:

(1)Wheretheracewayormeansofsupportisidentifiedasameansofsupport

(2)Wheretheracewaycontainspowersupplyconductorsforelectricallycontrolled

equipmentandisusedtosupportClass2circuitconductorsorcablesthataresolelyfor

thepurposeofconnectiontotheequipmentcontrolcircuits

(3)Wheretheracewayisusedtosupportboxesorconduitbodiesinaccordancewith

314.23ortosupportluminairesinaccordancewith410.36(E)

(D)CablesNotUsedasMeansofSupport.Cablewiringmethodsshallnotbeusedasameans

ofsupportforothercables,raceways,ornonelectricalequipment.