SINTEF is Norwegian member of European Organisation for Technical Approvals, EOTA, and European Union of Agrément, UEAtc Reference: Appr. 3D30774 Contr. 3B0452 Subject: Wet room board Head Office: SINTEF Building and Infrastructure P.O.Box 124 Blindern – NO 0314 Oslo Tel. + 47 22 96 55 55 – Fax + 47 22 69 94 38 e-mail: [email protected] www.sintef.no/byggforsk Trondheim: SINTEF Building and Infrastructure 7465 Trondheim Tel. +47 73 59 30 00/33 90 – Fax +47 73 59 33 50/80 © Copyright SINTEF Byggforsk 1. Holder of the approval Litex AS Postboks 1073 3203 Sandefjord Norway Tel.: + 47 33 48 99 70 Fax: + 47 33 48 11 30 www.litex.no 2. Manufacturer Litex AS, Sandefjord, Norway 3. Product description Litex Membrane Board is a wet room board consisting of a core of extruded polystyrene (XPS), coated on both sides with an aluminium layer, a reinforcement mesh and a top layer of waterbased epoxy, see Fig. 1. The surface is light grey, while the core material is light blue. Supplementary products to Litex Membrane Board include: - Litex Jointing Strip, rubberised (NBR rubber) - Litex Jointing Strip, fibre - Litex Pipe Collar, rubberised (NBR rubber) - Litex Collar Internal and External Corner, rubberised (NBR rubber) - Litex Jointing Strip, self-adhesive (aluminium) - Litex Mounting Discs and Mounting Screws - Litex Floor drain collar Table 1 shows board dimensions and weight. The boards have straight edges. Table 1 Standard dimensions and weights for Litex Membrane Board Standard thickness mm Weight kg/m² Standard dimension mm x mm 13 1,3 20 1,6 30 1,8 50 2,5 75 3,3 2440 x 600 Fig. 1 Construction of Litex Membrane Board. The boards are symmetrical. The boards have the following measurement tolerances: thickness: ± 2 mm length: ± 5 mm width: ± 2 mm 4. Fields of application Litex Membrane Board can be used as a vapourtight and watertight layer on walls and floors in bathrooms and washrooms in houses, hotels and in rooms with equivalent conditions. The application as a watertight layer requires the use of reinforcement Strip over joints, fasteners and connections between floor and wall. Cl. 7 give additional requirements for use. The boards may be installed directly on a wall framework or other substrate such as brickwork or concrete, including walls below ground level. The boards shall always be covered by ceramic tiles or equivalent non combustible lining, such as 8 mm thick wall rendering. SINTEF Certification No. 20006 Issued t: 16.12.2010 Revised: 03.05.2013 Valid until: 01.10.2016 Page: 1 of 5 SINTEF Building and Infrastructure confirms that Litex Membrane Board meets the provisions regarding product documentation given in Norwegian building regulations, with properties, fields of application and conditions as stated in this document

Transcript of NBI Teknisk Godkjenning - Godkj.dokument NORSK · (NBR rubber) - Litex Jointing Strip,...

Page 1: NBI Teknisk Godkjenning - Godkj.dokument NORSK · (NBR rubber) - Litex Jointing Strip, self-adhesive (aluminium) - Litex Mounting Discs and Mounting Screws - Litex Floor drain collar

SINTEF is Norwegian member of European Organisation for Technical Approvals, EOTA, and European Union of Agrément, UEAtc

Reference: Appr. 3D30774 Contr. 3B0452 Subject: Wet room board

Head Office:SINTEF Building and InfrastructureP.O.Box 124 Blindern – NO 0314 OsloTel. + 47 22 96 55 55 – Fax + 47 22 69 94 38

e-mail: [email protected]/byggforsk

Trondheim:SINTEF Building and Infrastructure7465 TrondheimTel. +47 73 59 30 00/33 90 – Fax +47 73 59 33 50/80

© Copyright SINTEF Byggforsk

1. Holder of the approvalLitex ASPostboks 10733203 SandefjordNorwayTel.: + 47 33 48 99 70 Fax: + 47 33 48 11 30www.litex.no

2. ManufacturerLitex AS, Sandefjord, Norway

3. Product descriptionLitex Membrane Board is a wet room board consisting of a core of extruded polystyrene (XPS), coated on both sides with an aluminium layer, a reinforcement mesh and a top layer of waterbased epoxy, see Fig. 1. The surface is light grey, while the core material is light blue.

Supplementary products to Litex Membrane Board include: - Litex Jointing Strip, rubberised (NBR rubber)- Litex Jointing Strip, fibre- Litex Pipe Collar, rubberised (NBR rubber)- Litex Collar Internal and External Corner, rubberised

(NBR rubber)- Litex Jointing Strip, self-adhesive (aluminium)- Litex Mounting Discs and Mounting Screws- Litex Floor drain collar

Table 1 shows board dimensions and weight. The boards have straight edges.

Table 1 Standard dimensions and weights for Litex Membrane Board

Standard thickness mm

Weight kg/m²

Standard dimensionmm x mm

13 1,320 1,630 1,850 2,575 3,3

2440 x 600

Fig. 1Construction of Litex Membrane Board. The boards are symmetrical.

The boards have the following measurement tolerances: thickness: ± 2 mm length: ± 5 mm width: ± 2 mm

4. Fields of applicationLitex Membrane Board can be used as a vapourtight and watertight layer on walls and floors in bathrooms and washrooms in houses, hotels and in rooms with equivalent conditions. The application as a watertight layer requires the use of reinforcement Strip over joints, fasteners and connections between floor and wall. Cl. 7 give additional requirements for use.

The boards may be installed directly on a wall framework or other substrate such as brickwork or concrete, including walls below ground level. The boards shall always be covered by ceramic tiles or equivalent non combustiblelining, such as 8 mm thick wall rendering.

SINTEF Certification

No. 20006Issued t: 16.12.2010Revised: 03.05.2013Valid until: 01.10.2016Page: 1 of 5

SINTEF Building and Infrastructure confirms that

Litex Membrane Boardmeets the provisions regarding product documentation given in Norwegian building

regulations, with properties, fields of application and conditions as stated in this document

Page 2: NBI Teknisk Godkjenning - Godkj.dokument NORSK · (NBR rubber) - Litex Jointing Strip, self-adhesive (aluminium) - Litex Mounting Discs and Mounting Screws - Litex Floor drain collar

SINTEF Technical Approval - No. 20006 Page 2 av 5

5. PropertiesMaterial properties Table 2 shows the material properties of the core material, and Table 3 shows the properties of the Litex Membrane Board determined by type testing.

Table 2Material properties of the core material determined by type testing

Property Value Test method

Compressive strength 300 kN/m² EN 826Water absorption, immersion < 0,5 vol % EN 12087

Thermal conductivity, D 0,034 W/(mK) EN 13164

Table 3Material properties of Litex Membrane Board determined by type testing

Property Value Test method

Water vapour permeability equiv. air layer thickness, sd,

7800 m NS-EN-ISO 12572

Watertightness at 1.5 bar water pressure for 7 days Passed NS-EN 14891,

Annex A.7Watertightness at wall penetrations 1) Passed ETAG 022

Annex EWatertightness at wall penetrations Passed ETAG 022

Annex ACrack bridging properties:- tensile strenght- shear strenght

2 mm – Passed2 mm – Passed

ETAG 022, Annex B

Bending moment capacity:- 13 mm board- 20 mm board

57 Nmm/mm136 Nmm/mm

NS-EN 12089

Bending stiffness, EI:- 13 mm board- 20 mm board

85 kNmm2/mm216 kNmm2/mm

NS-EN 12089

Bond strength 2) 0,3 N/mm2 NS-EN 14891, Anneks A 6.2

Bond strength 2) after 21 days in water at 23 ºC 0,2 N/mm2 NS-EN 14891,

Annex A.6.3Bond strength 2) after 14 days in air at 70 ºC 0,3 N/mm2 NS-EN 14891,

Annex A 6.5Resistanse to soft body impact load 3)

3 x 120 Nm/1 x 240 Nm ETAG 003

1) Penetrations: Copper pipe Ø22 mm and wall box Ø46 mm2) Tile adhesive: Maxit Serpo Flislim 610 Multi3) 20 mm boards, fully tiled, installed on studs spaced

c/c 600 mm resist 120 Nm three times and 240 mm one time using ceramic tile “Prosjektflis” 20 x 20 cm, tile adhesive Hey`di Cemfix and grout Hey`di Fugemasse.20 mm board without tiles, installed on studs spaced c/c 300 mm resists 120 Nm three times.

Properties related to fireThe XPS core material is classified as Class F according to EN 13501-1. Reaction to fire for Litex Membrane Board without surface protection has not been determined, i.e. Class F according to EN 13501-1. Covered by ceramic tiles the surface complies with Class In1 according to NS 3919.

6. Environmental aspectsSubstances hazardous to health and environmentThe product contains no hazardous substances with priority in quantities that pose any risk for human health and environment. Chemicals with priority include CMR, PBT or vPvB substances.

Effect on indoor environment The product is not regarded as emitting any particles, gases or radiation that have a perceptible impact on the indoor climate, or to have any significant impact on health.

Waste treatment/recycling Litex Membrane Board shall be sorted as residual waste on the building/demolition site. The product shall be delivered to an authorized waste treatment plant for energy recovery.

Wet liquid membranes are defineded as hazardous waste (according to the Norwegian regulations on waste treatment (Avfallsforskriften)). The product must be sorted as hazardous waste on the building site. The product must be delivered to an authorized waste treatment plant for hazardous waste.

Environmental declarationNo environmental declaration (EPD) has been worked out for Litex Membrane Board.

7. Special conditions for use and installationStorage and contitioneringThe boards shall be covered during storage and transport to avoid dust or dirt that may reduce the adhesive bond properties of the board surface. The boards must not be exposed to flames, other ignition sources or organic solvents. The product should be protected from UV radiation during long-term storage.

UnderlayThe underlay for installation of Litex Membrane Board shall fulfil the requirements for directional- and surface tolerance class PB as given in NS 3420 Part 1.

Påstrykningsmembranene Hey’di K10, F1 Membran, Norflis Våtromsmembran, Hey'di Smøremembran, Serpo 554 Smøremembran Flex, Optiform smøremembran og Alfix 1K Tætningsmasse

MembranesLiquid applied membranes Hey’di K10, F1 Membran, Norflis Våtromsmembran, Hey'di Smøremembran, Serpo 554 Smøremembran Flex, Optiform smøremembran and Alfix 1K Tætningsmasse can be used together with Litex accessories as waterproof sealing for joints, screws and pipe penetrations. Membranes shall be applied according to the manufacturers’ directions.

Joint sealing on wallIn the wet zone, all joints and screw fixings must be covered by Litex Jointing Strip, rubberised or fibre in combination with a liquid applied membrane. The liquid

Page 3: NBI Teknisk Godkjenning - Godkj.dokument NORSK · (NBR rubber) - Litex Jointing Strip, self-adhesive (aluminium) - Litex Mounting Discs and Mounting Screws - Litex Floor drain collar

SINTEF Technical Approval - No. 20006 Page 3 av 5

applied membrane shall cover the reinforcement Strip completely, see Fig. 2.

Alternatively Litex Jointing Strip, self-adhesive, can be used to cover joints and screw fixings without using a liquid applied membrane.

Joint sealing on floor and floor/wallLitex Jointing Strip, rubberised is used over board joints and screw fixings together with a liquid applied membrane as shown in fig. 2. The liquid applied membrane shall cover the reinforcement Strip completely.

At external and internal corners Litex Sleeves External and Internal Corner are applied to the Litex Membrane Board using liquid applied membrane. The sleeves are to be covered bya liquid applied membrane.

Sealing at pipe penetrationsin floor and wallLitex Pipe Collars are attached to the underlay using liquid applied membrane. The collar shall be completely covered with liquid applied membrane, see Fig 2.

Fig. 2Principle for sealing around pipe penetrations, over joints and screw fixings.

Water vapour control layerLitex Membrane Board meets the required water vapour resistance for external walls and walls against rooms with limited heating. Only sealing over joints, screw fixings and at penetrations is necessary. Any present plastic foil in external walls shall be removed before boards are installed.

Fig. 3Example of connection between tiled floor and wall.

Installation on frameworkBoards with a thickness of min. 20 mm may be installed directly on studs spaced max. c/c 300 mm. Thinner boards require a continous underlay of panels or boards.Extra noggings must be used for installation of heavy objects like washstands, cabinets etc.

The boards shall be fixed along the edges with screws and washers intended for installation of the board system. Recommended spacing between screws is max. 250 mm for 13 mm boards, 300 mm for 20 mm boards and 400 mm for 30 mm boards, plus at least one fixing point at every horizontal nogging.

For boards fixed to a continous underlay it is recommended to additionally use 3 screws with washers evenly spaced along the center of the board and one screw in the center of the board at the top and bottom sill. All screws shall be at least 20 mm longer than the board thickness.

Page 4: NBI Teknisk Godkjenning - Godkj.dokument NORSK · (NBR rubber) - Litex Jointing Strip, self-adhesive (aluminium) - Litex Mounting Discs and Mounting Screws - Litex Floor drain collar

SINTEF Technical Approval - No. 20006 Page 4 av 5

Installation on masonry or concreteFixing to masonry or concrete substrates can be done with tile adhesive, see Fig. 4. Boards with a minimum thickness 20 mm can be fastened with adhesive applied in 15 – 20 spots spread thoughout the board. Thinner boards shall be fastened with a contionous adhesive layer.All loose wallpaper, plaster, paint and dust must be removed before fixing the boards. Absorbing surfaces must be primed.

Installation on floorIn a distance 0,8 m from the gully the board shall be installed with a slope 1:50 towards the gully. The other parts of the floor should have a 1:100 slope tovards the gully. 13 mm or 20 mm boards can be installed on concrete floors or on a underlay with a stiffness and constructional details as described in Building Research Design Guide 522.861 and 541.805.In floors the boards shall always be covered with minimum 10 mm mortar/adhesive before tile installation. The liquid applied membrane used for joints shall be approved for this application.

Fig. 4Example of Litex Membran Board used on wall against the ground.

Sealing around the gullyLiquid applied membrane shall be used when applying Litex Drain Collar to the Litex Membrane Board, see Fig 5.

TilingLitex Membrane Board shall always be covered with tiles. The maximum water absorbtion rate for the tiles shall be 20 % for walls, 10 % for floors and 6 % when used with a low profile floor heating system.

8. Factory production controlLitex Membrane Board is subject to supervisory factory production control according to contract with SINTEF Building and Infrastructure concerning Technical Approval.

Fig. 5Principle for sealing at gully with Litex Gully Collar.

9. Basis for the approvalThis approval is primarely based on the properties verified in the following reports: SINTEF Building and Infrastructure. Prøving av

vanntettheten for Litex Membranplate i kombinasjon med butylbånd, ETAG 022. Part 3, Annex E. Report 3B054701 dated 30.5.2011.

SINTEF Building and Infrastructure. Prøving av Litex Membranplate iht. Annex A. Report 3D100301 dated 17.4.2010.

SINTEF Building and Infrastructure. Prøving av motstand mot bløte støt iht. ETAG 003. Report 3D101401 dated 18.5.2010.

SINTEF Building and Infrastructure. Prøving av bøyemomentkapasitet og bøyestivhet, 13 mm og 20 mm tykke plater. Report 3D0639B dated 9.9.2009.

SINTEF Building and Infrastructure. Prøving av bøyemomentkapasitet og bøyestivhet, 13 mm og 20 mm tykke plater. Report 3D0639B dated 9.9.2009.

SINTEF Building and Infrastructure. Prøving av vanntettheten for Litex membranplate iht. ETAG022, Annex E. Report 3D017314 dated 4.3.2009.

SINTEF Building and Infrastructure. Litex Membranplate. Prøving av vanntettheten ved 1,5 bar. Report 3D063901 C dated 24.4.2009.

SINTEF Building and Infrastructure. Prøving av skjøtoverbyggende evne. Report 3D0848 A dated 14.12.2009.

SINTEF Building and Infrastructure. Prøving av skjøtoverbyggende evne. Report 3D063901 A dated 5.3.2009.

Statens Byggeforskningsinstitut. Prøving av motstand mot bløte støt iht. ETAG 003. Med modifikasjoner som beskrevet i Anneks C og D i ETAG no. 003. Report nr. 722-165 dated 13.7.2009.

VTT Technical research center of Finland. Testing the water vapour properties of 12,5 mm thick Litex wet room board. Report VTT-S-01199-13 dated 13.4.2013.

VTT Certificate No. VTT-C-154207 dated 13.2.2009.

Page 5: NBI Teknisk Godkjenning - Godkj.dokument NORSK · (NBR rubber) - Litex Jointing Strip, self-adhesive (aluminium) - Litex Mounting Discs and Mounting Screws - Litex Floor drain collar

SINTEF Technical Approval - No. 20006 Page 5 av 5

SP Technical Research institute of Sweden. VOC emisions. Report FX216776 dated 6.9.2012.

10. MarkingThe product packaging shall be marked with the manufacturer’s name, product name and time of production. The marking may be fixed directly on the boards or on the packaging. The approval mark for Technical Approval TG 20006 may also be used.

Approval mark

11. LiabilityThe holder/manufacturer has sole product responsibility according to existing law. Claims resulting from the use of the product cannot be brought against SINTEF beyond the provisions of Norwegian Standard NS 8402

12. Technical managementProject manager for this approval is Thale Sofie Plesser,SINTEF Building and Infrastructure, dep. Energy and architecture, Oslo.

for SINTEF Building and Infrastructure

Tore H. ErichsenApproval Manager