NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016....

54
Address: 225 Commonwealth Street, Surry Hills, NSW 2010 Tel: (02) 8014 7720 Email: [email protected] NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE REPORT FOR DA LODGEMENT 5 ELVA STREET, STRATHFIELD NSW 2135 Class 3 Boarding House and Basement Carpark Prepared for: Bechara Chan and Associates Pty Ltd Project No.: 17/0558 Date: 27/11/2017 Status: Issue 1.0 (for DA lodgement) Report No.: 17/0558/R1.0/AJ

Transcript of NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016....

Page 1: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Address: 225 Commonwealth Street, Surry Hills, NSW 2010 Tel: (02) 8014 7720

Email: [email protected]

NATIONAL CONSTRUCTION CODE (NCC)

2016 COMPLIANCE REPORT

FOR DA LODGEMENT

5 ELVA STREET, STRATHFIELD NSW 2135

Class 3 Boarding House and Basement Carpark

Prepared for: Bechara Chan and Associates Pty Ltd

Project No.: 17/0558

Date: 27/11/2017

Status: Issue 1.0 (for DA lodgement)

Report No.: 17/0558/R1.0/AJ

Page 2: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 2 of 54

Table of Contents

1.0.  DOCUMENT HISTORY AND DRAWING SCHEDULE............................................... 3 

1.1.  DOCUMENT HISTORY ..................................................................................................... 3 

1.2.  DRAWING SCHEDULE .................................................................................................... 3 

2.0.  INTRODUCTION ......................................................................................................... 4 

2.1.  LOCATION AND DESCRIPTION ......................................................................................... 4 

2.2.  REPORT PURPOSE ........................................................................................................ 4 

2.3.  BASIS OF REPORT ......................................................................................................... 5 

2.4.  REFERENCED DOCUMENTS ........................................................................................... 5 

2.5.  LIMITATIONS AND EXCLUSIONS ...................................................................................... 5 

2.6.  LEGISLATIVE FRAMEWORK ............................................................................................. 6 

2.7.  TERMINOLOGY .............................................................................................................. 7 

BUILDING DESCRIPTION – PROPOSED DEVELOPMENT ................................................ 9 

2.8.  BUILDING CODE OF AUSTRALIA DESCRIPTION ................................................................ 9 

2.9.  RISE IN STOREYS (RIS) (CLAUSE C1.2) ......................................................................... 9 

2.10.  BUILDING CLASSIFICATIONS (CLAUSE A3.2) ........................................................... 10 

2.11.  EFFECTIVE HEIGHT (CLAUSE A1.1) ....................................................................... 10 

2.12.  TYPE OF CONSTRUCTION (TABLE C1.1) ................................................................. 10 

2.13.  FLOOR AREA AND VOLUME LIMITATIONS (TABLE C2.2) ........................................... 11 

2.14.  FIRE PROTECTION AND STRUCTURAL CAPACITY (CLAUSE 143) ................................ 11 

2.15.  FIRE BRIGADE REFERRAL (CLAUSE 144) ................................................................ 11 

3.0.  FIRE SAFETY SCHEDULES .................................................................................... 12 

3.1.  PROPOSED FIRE SAFETY SCHEDULE ........................................................................... 12 

3.2.  CERTIFICATION OF ESSENTIAL FIRE SAFETY MEASURES ............................................... 14 

4.0.  CONCLUSION .......................................................................................................... 15 

APPENDIX A – FIRE RESISTANCE LEVELS ..................................................................... 16 

APPENDIX B: BCA REQUIREMENTS - CLAUSE BY CLAUSE ASSESSMENT ............... 17 

4.1.  TABLE 4.1 – BCA 2016 CLAUSE BY CLAUSE ASSESSMENT ........................................... 18 

Page 3: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 3 of 54

1.0. DOCUMENT HISTORY AND DRAWING SCHEDULE 1.1. Document History Date Issue Status Prepared by Reviewed by

27.11.17 Issue 1.0 For DA lodgement Adam Johannesen Orlando Da Silva

(BPB 0081)

1.2. Drawing Schedule

Drawing By Drawing No. Drawing Title Date Issue

Bechara Chan and Associates Pty Ltd

DA.01 Site and roof plan;

Demolition plan.

June 2017 A

Bechara Chan and Associates Pty Ltd

DA.02 Basement plan;

Ground floor plan.

June 2017 A

Bechara Chan and Associates Pty Ltd

DA.03 First floor plan;

Second floor plan.

June 2017 A

Bechara Chan and Associates Pty Ltd

DA.04 Driveway section June 2017 A

Bechara Chan and Associates Pty Ltd

DA.05 East; West; South; North elevations;

Section AA and Section BB.

June 2017 A

Bechara Chan and Associates Pty Ltd

DA.06 Section AA-1;

Existing footprint;

Proposed footprint.

June 2017 A

Page 4: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 4 of 54

2.0. INTRODUCTION 2.1. Location and Description

The building the subject of this report is located at 5 Elva Street, Strathfield. Vehicular and principal pedestrian access is from Elva Street to the East. The proposed development is located on a corner lot with Ardittos Lane bounding the South of the building.

The proposed development relates to the demolition of the existing structure on the lot and erection of a three storey Boarding House incorporating 1 level of basement car parking, 3 above ground boarding house levels containing bedrooms (sole occupancy units), including an internal and outdoor common area on ground floor, and associated landscaping.

2.2. Report Purpose

This report has been prepared by Building Certificates Australia Pty Ltd and provides a BCA compliance review of the proposed works (not including demolition) at 5 Elva Street, Strathfield. The assessment has been undertaken against the Deemed-to-Satisfy provisions of the National Construction Code, otherwise known as the Building Code of Australia (BCA) relating to Parts C, D, E and F only. The BCA edition in force when this report was prepared is 2016.

Page 5: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 5 of 54

This review is provided in order to assist Council consider whether the proposal, as lodged, is indicatively capable of complying with the BCA and without significant modification to those plans for which approval is sought. This review does not include a detailed assessment against the ‘Adaptable Housing’ Code provisions (AS4299-1995).

2.3. Basis of Report This report is based upon:

A desktop review of the documentation submitted for assessment (refer to drawing schedule section 1.2); and

The Deemed-to-Satisfy provisions of Parts C, D, E and F of the National

Construction Code Series (volume 1) 2016.

2.4. Referenced Documents The following documentation was relied upon when preparing this report:

The performance and deemed-to-satisfy provisions of the National Construction

Code 2016 (BCA) incorporating the NSW Appendices where applicable.

Guide to the National Construction Code Volume 1.

Disability (Access to Premises — Buildings) Standards 2010.

Environmental Planning & Assessment Act 1979.

Environmental Planning & Assessment Regulation 2000. 2.5. Limitations and Exclusions

The limitations and exclusions of this report are as follows: This report is based on a review of the referenced documents.

No assessment has been undertaken with respect to the Disability Discrimination

Act 1992 (DDA). Separate advice from an appropriately qualified access consultant should be obtained by the client to be satisfied that their obligations under the DDA have been addressed.

Please note that whilst the BCA specifies a minimum standard of compliance with AS1428.1 and Part D3 of the BCA for access and facilities for people with disabilities, compliance with such requirements may not necessarily preclude the possibility of a future complaint made under the Disability Discrimination Act 1992 (DDA). The DDA is a complaint based legislation and is presently not identified by the State Building Codes and Regulations. In this regard the client should be satisfied that their obligations under the DDA have been addressed.

This Report does not address issues in relation to the following:

Page 6: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 6 of 54

a) The structural adequacy of the building including the Fire Resistance Levels (FRL’s) of any existing building elements (unless specifically referred to).

b) The design, maintenance or operation of any existing electrical, mechanical, hydraulic or fire protection services.

c) Environmental Planning and Assessment Act and Regulations. d) Local Government Act and Regulations. e) Occupational Health and Safety Act and Regulations. f) WorkCover Authority requirements. g) Requirements of other Regulatory Authorities including, but not limited to,

Telstra, Sydney Water, Electricity Supply Authority, RTA, Council and the like. h) Disability Discrimination Act. i) Construction Safety Act. j) Any previous conditions of Development Consent issued by the relevant Local

Council. k) The ‘Adaptable Housing’ Code (AS4299-1995)

Building Certificates Australia Pty Ltd cannot guarantee acceptance of this report by the Local Council, NSW Fire Brigades or other approval authorities.

Without written permission from Building Certificates Australia Pty Ltd, no part of this document may be reproduced in any form or by any means. This report is based solely on client instructions, and therefore should not be used by any third party without prior knowledge of such instructions.

2.6. Legislative Framework

Section 79C of the Environmental Planning and Assessment Act provides the matters of consideration that the consent authority must take into account in the determination of a development application. Once development consent is granted, and pursuant to Clause 145 of the Environmental Planning and Assessment Regulations 2000, a certifying authority must not issue a construction certificate for building work unless: (a1) the plans and specifications for the building include such matters as each

relevant BASIX certificate requires, and (a) the design and construction of the building (as depicted in the plans and

specifications and as described in any other information furnished to the certifying authority under clause 140) are not inconsistent with the development consent, and

(b) the proposed building (not being a temporary building) will comply with the

relevant requirements of the Building Code of Australia (as in force at the time the application for the construction certificate was made).

Page 7: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 7 of 54

Compliance with the National Construction Code The BCA is a performance based document whereby compliance can be achieved by satisfying the deemed to satisfy requirements or by formulating an alternative solution to address the relevant performance requirements. As indicated above, the requirements of the Environmental Planning and Assessment Regulations 2000 requires all new building works to comply with the relevant requirements of the BCA (as in force at the time the application for the construction certificate was made). This means that the plans and documentation submitted with the construction certificate (CC) application must demonstrate full compliance with the relevant provisions of the Building Code of Australia. Disability (Access to Premises — Buildings) Standards 2010 Disability (Access to Premises — Buildings) Standards 2010 is applicable to this development as a certificate under Part 4A of the EP&A Act 1979 will be sought. At the time an application is made to the consent authority for a construction certificate, full disclosure as to who the applicant for the construction certificate is must form part of said application. Should the applicant be a tenant in a multi-tenanted building, a concession will be applied and the ‘affected part’ upgrade with the Premises Standard will not apply. If however the applicant is the building owner, the affected part upgrade will apply. It is noted that his standard does not however apply to this building as it is a new build.

2.7. Terminology

National Construction Code (NCC) / Building Code of Australia (BCA) - Document published on behalf of the Australian Building Codes Board. The BCA is a uniform set of technical provisions for the design and construction of buildings and other structures throughout Australia and is adopted in NSW under the provisions of the Environmental Planning & Assessment Act & Regulation.

Fire Resistance Level (FRL) - means the grading periods in minutes tested in accordance with AS 1530.4-2005 for the following criteria -

(a) structural adequacy; and (b) integrity; and (c) insulation, and expressed in that order. Fire Source Feature (FSF) - the far boundary of a road adjoining the allotment; or

a side or rear boundary of the allotment; or an external wall of another building on the allotment which is not a Class 10 building.

Open space - means a space on the allotment, or a roof or other part of the building suitably protected from fire, open to the sky and connected directly with a public road.

Page 8: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 8 of 54

Performance Requirements of the BCA - A Building Solution will comply with the BCA if it satisfies the Performance Requirements. A Performance requirement states the level of performance that a Building Solution must achieve. Compliance with the Performance Requirements can only be achieved by- (a) complying with the Deemed-to-Satisfy Provisions; or (b) formulating an Alternative Solution which-

(i) complies with the Performance Requirements; or (ii) is shown to be at least equivalent to the Deemed-to-Satisfy Provisions; or

(c) a combination of (a) and (b).

Sole occupancy unit - means a room or other part of a building for occupation by one or joint owner, lessee, tenant, or other occupier to the exclusion of any other owner, lessee, tenant, or other occupier.

Page 9: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 9 of 54

BUILDING DESCRIPTION – PROPOSED DEVELOPMENT

2.8. Building Code of Australia Description For the purposes of the National Construction Code Volume 1, otherwise known as the Building Code of Australia (BCA) 2016 the proposed development is described in the following sections.

2.9. Rise in Storeys (RIS) (Clause C1.2)

The overall building has a rise in storeys of three (3). There are four (4) storeys contained within the building.

Page 10: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 10 of 54

2.10. Building Classifications (Clause A3.2)

The building has been classified in accordance with the table below.

BUILDING LEVELS PROPOSED CLASSIFICATION

Basement Level

Ground floor – Level 2

Class 7a (car park)

Class 3 (boarding house)

2.11. Effective Height (Clause A1.1)

The effective height of the building is 6 metres. Highest RL taken = 16.885 Lowest RL taken = 10.885

2.12. Type of Construction (Table C1.1)

The building is required to be of Type ‘A’ Construction.

Page 11: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 11 of 54

2.13. Floor Area and Volume Limitations (Table C2.2)

The proposed building is Type A construction. The Class 3 portions of the building are not subject to any floor area and volume limitations of C2.2 of the BCA. Table 3 of Specification C1.1 and C3.11 of the BCA regulate compartmentation and separation provisions applicable to Class 3 buildings or building portions. The class 7a basement car park sits well below the required threshold for its classification.

2.14. Fire protection and structural capacity (Clause 143)

If your development incorporates a Change of Use, Category 1 fire safety measures must be considered and implemented in to the design as applicable. EP1.3: A fire hydrant system (required) EP1.4: An automatic fire suppression system EP1.6: Suitable facilities must be provided to the degree necessary in a

building to co-ordinate fire brigade intervention (required) EP2.1: Sleeping Accommodation, occupants must be provided with automatic

warning EP2.2: Conditions in any evacuation route must be maintained for the period

of time occupants take to evacuate (required) EP3.2: One or more passenger lifts fitted as emergency lifts to serve each floor

served by the lifts in a building must be installed to facilitate the activities of the fire brigade and other emergency services personnel (required)

This is a new build and therefore the change of use provisions under clause 143 do not apply.

2.15. Fire Brigade referral (Clause 144)

A referral to Fire and Rescue NSW under Clause 144 will not be required as a result of the proposed works as the building does not have a fire compartment greater than 2000m² and the building’s overall floor area is not greater than 6000m².

Page 12: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 12 of 54

3.0. FIRE SAFETY SCHEDULES 3.1. Proposed Fire Safety Schedule

As a result of the works proposed under this development application, the DRAFT fire safety schedule for the site will be as follows. The final fire safety schedule is to be prepared for issue of the Construction Certificate.

Essential Fire and Other Safety Measures

Standard of Performance Proposed

Access panels, doors and hoppers to fire resisting shaft

BCA Clause C3.13 TBA

Prior to the issue of the construction certificate confirmation must be provided to the certifying authority confirming if the services shaft will be in a fire resisting shaft or capped off between levels with floor penetrations appropriately protected.

Automatic fire detection & alarm system (Class 3 areas ground floor to level 2 including SOU levels and common rooms. Not extending to the basement car park).

E2.2; Specification E2.2a (Clause 4 smoke detection system; clause 6 BOWS); AS1670.1-2015 (not less than 100dB(A) to be provided at the door of an SOU); AS1670.3 (system monitoring).

Emergency lighting E4.2, E4.4; and AS/NZS 2293.1-2005

Exit signs

E4.5, E4.6, E4.8; and

AS/NZS 2293.1-2005

Fire dampers (smoke control system for the car park)

AS/NZS 1668.1-1998; AS 1682.1-1990

TBA

Prior to the issue of the construction certificate confirmation must be provided to the certifying authority confirming if the car park ventilation system will operate in a manner that may unduly contribute to the spread of smoke from one fire

compartment to another fire compartment. The concept design at this stage does not provide full mechanical details yet it is anticipated that the car park ventilation system will penetrate the roof of the car park and discharge directly to open space

without passing through another fire compartment.

Fire doors

C3.8 (Openings in Fire Isolated Exits) C3.10 (Opening in Fire Isolated Lift Shafts) C3.11 (bounding construction); and

AS1905.1 - 2005

Fire hydrant systems BCA Clause E1.3 & AS 2419.1-2005

Fire seals (protecting openings in fire resisting components of the building)

C3.15; and

Specification C3.15

Lightweight construction BCA C1.8; and Specification C1.8

Mechanical air handling systems -(Mechanical ventilation to carpark)

AS1668.2-2012 (clause 5.5.3) Note: 5.5.3 Override / manual control switch at the designated building entry point (e.g.: at the fire indicator panel) to enable attending emergency services personnel the ability to cease the operation of fans that are not

Page 13: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 13 of 54

required to shut down on initiation of fire mode in the car park.

NOTE: Signage should be located at the car park entry indicating the location of the control

switch.

Portable fire extinguishers

BCA E1.6, AS 2444 – 2001

Smoke dampers (car park ventilation) BCA E2.2; AS1670.1 (cl. 7.5)

TBA

Prior to the issue of the construction certificate confirmation must be provided to the certifying authority confirming if the car park ventilation system will operate in a manner that may unduly contribute to the spread of smoke from one fire

compartment to another fire compartment. The concept design at this stage does not provide full mechanical details yet it is anticipated that the car park ventilation system will penetrate the roof of the car park and discharge directly to open space

without passing through another fire compartment.

Wall wetting drencher systems (Eastern fire isolated exit glazed wall facing east east)

BCA Clause C3.4 and AS 2118.2-1995

Hydrant coverage – Hydrant coverage is required as the building’s floor area is proposed to be greater than 500m². Whether the hydrant coverage will be provided from the street or by an internal hydrant system with pressure delivered by a hydrant booster assembly remains to be seen. Prior to the issue of a construction certificate a suitably qualified and practicing hydraulic engineer must confirm any existing street hydrant is located such that the required hose reel reach will be achieved as well as the required pressure and flow rates. The assessment is to include an enquiry to the regulatory authority Sydney Water to determine if the existing pressure and flow rates are adequate to serve the entire building. It is noted that the proposed DA drawings accommodate internal hydrants and a hydrant booster assembly; and the above draft fire safety schedule includes internal hydrants however in the event street coverage is achieved the booster assembly and internal hydrant points will be deleted from the plans and hydrants may be deleted from the building’s fire safety schedule.

Page 14: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 14 of 54

3.2. Certification of Essential Fire Safety Measures

Pursuant to Section 169 of the Environmental Planning and Assessment Regulations 2000, it will be necessary for the owner of the building, on completion of work to furnish a Final Fire Safety Certificate with regard to each essential fire safety measure identified in the proposed Fire Safety Schedule listed above. The final fire safety certificate must state that each essential fire safety measure specified in the fire safety schedule for the building to which the certificate relates: (a) has been assessed by a properly qualified Fire Safety Practitioner, and (b) was found, when it was assessed, to be capable of performing to at least the

standard required by the current fire safety schedule for the building for which the certificate is issued.

Every year, the owner(s) will need to submit an Annual Fire Safety Statement to the Local Council and the NSW Fire Brigades, which confirms that all essential fire safety measures have been tested and maintained and perform to the original design and installation standard. A copy of the Annual Fire Safety Statement must also be displayed in a prominent areas of the buildings (i.e. the main entrance foyers).

Page 15: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 15 of 54

4.0. CONCLUSION

Although demonstrating full compliance with the BCA at DA assessment stage is not a prescribed head of consideration under Section 79C of the Environmental Planning & Assessment Act 1979, Council has an obligation to consider whether the proposal, as lodged, is indicatively capable of complying with the BCA and without significant modification to those plans for which approval is sought. In this regard, the concept design submitted to council for approval exhibits three specific departures from the deemed to satisfy provisions of the BCA that are to be addressed by way of fire engineering to achieve the relevant BCA performance requirements. The DtS departures are:

1. D1.7(b)(ii) Travel via fire-isolated exits (the discharge area is not open for at least 2/3 of its perimeter).

2. D1.7(c) Travel via fire-isolated exits (the path of travel from the discharge point to open space necessitates an occupant to pass by openings in the building’s external wall that are unprotected).

3. E1.3 Fire Hydrants (the location of the fire hydrant booster assembly does not comply with AS2419.1; and the proposed shield wall does not strictly comply with the minimum dimensions in AS2419.1).

To address these DtS departures, a qualified C10 accredited fire engineer is required to prepare a report in accordance with Part A0.7 of the BCA to ensure the relevant performance requirement/s have been met. The justification of these DtS departures by means of performance solutions will satisfy the requirements of the BCA, thus the design will comply.

At the time a construction certificate is lodged with the certifying authority it is expected that the construction certificate plans will be advanced in order to illustrate more detailed compliance with the BCA, as an example those DtS provisions within our clause by clause assessment referred to as having ‘compliance readily achievable’ (CRA) and other relevant services. It is our opinion that the advanced construction drawings that are lodged in order to satisfy the requirements of the BCA (in force at the time the construction certificate application is lodged) will not demand the need for any significant design changes that in turn would necessitate the submission of an application under Section 96 of the Environmental Planning and Assessment Act 1979. Finally, we draw Council’s attention to the requirements of clause 145 of the Environmental Planning & Assessment Regulation 2000, and suggest that detailed & specific BCA compliance matters shall be addressed to the satisfaction of the appointed Certifying Authority prior to the issue of the Construction Certificate and therefore achieving the necessary BCA compliance.

PREPARED BY: Adam Johannesen Senior Building Regulations Consultant Building Certificates Australia Pty Ltd

REVIEWED BY: Orlando Da Silva Director Building Certificates Australia Pty Ltd A1 Accredited Certifier & PCA – BPB 0081

Page 16: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 16 of 54

\ APPENDIX A – FIRE RESISTANCE LEVELS

Note: Under Spec C1.1, there are many individual additional requirements and concessions which need to be assessed and read in conjunction with this Specification. Your engineer is to confirm compliance with all required Fire Rated Elements. General Requirements:

- Exposure to Fire-source features - Fire Protection for a supporting of another part - Lintels - Attachments not to impair fire-resistance - General concessions

Fire-resistance of building elements: In a building required to be of Type ‘A’ construction (a) each building element listed in Table 3 and any beam or column incorporated in it, must have an FRL not less than that listed in the Table for the particular Class of building concerned; and (b) external walls, common walls and the flooring and floor framing of lift pits must be non-combustible; and (c) any internal wall required to have an FRL with respect to integrity and insulation must extend to;

(i) the underside of the floor next above; or (ii) the underside of a roof complying with Table 3; or (iii) if under Clause 3.5 the roof is not required to comply with Table 3, the underside of the non-combustible roof covering and, except for roof battens with dimensions of 75 mm x 50 mm or less or sarking-type material, must not be crossed by timber or other combustible building elements; or (iv) a ceiling that is immediately below the roof and has a resistance to the incipient spread of fire to the roof space between the ceiling and the roof of not less than 60 minutes; and

(d) a loadbearing internal wall and a loadbearing fire wall (including those that are part of a loadbearing shaft) must be of concrete or masonry; and (e) a non-loadbearing

(i) internal wall required to be fire-resisting; and (ii) lift, ventilating, pipe, garbage, or similar shaft that is not for the discharge of hot products of combustion, must be of non-combustible construction; and

(f) the FRLs specified in Table 3 for an external column apply also to those parts of an internal column that face and are within 1.5 m of a window and are exposed through that window to a fire-source feature.

Page 17: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 17 of 54

APPENDIX B: BCA REQUIREMENTS - CLAUSE BY CLAUSE ASSESSMENT

Noting that the current level of documentation is for assessment purposes related to the development application stage, an indicative compliance assessment of the referenced documents identified in section 1.2 of this report has been undertaken against the Deemed-to-Satisfy Provisions of the National Building Code of Australia 2016 (BCA). In Table 4.1 below is a summary of the Deemed-to-Satisfy Provisions of the BCA. All Deemed-to-Satisfy clauses that are applicable to the subject building have been referred to below, including a comment adjacent to each clause of the proposal’s ability to satisfy each respective clause.

The abbreviations outlined below have been used in the following tables:

N/A The Deemed-to-Satisfy clause does not apply to the subject Building.

Complies The relevant provisions of the Deemed-to-Satisfy clause have been

demonstrated by the proposed design and existing building features.

CRA ‘Compliance Readily Achievable’. It is considered that the level of detail included in the CC documentation will not determine strict compliance with the individual BCA clause requirements. Further certification well be required prior to the issue of the Construction Certificate.

FI Further information is necessary to determine the compliance potential

of the building design.

PS Performance Solution with respect to this Deemed-to-Satisfy Provision is possible to satisfy the relevant BCA Performance Requirements.

DNC Does Not Comply.

DTS Deemed-To-Satisfy provisions as defined by the National Building

Code of Australia 2016.

Page 18: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 18 of 54

4.1. Table 4.1 – BCA 2016 Clause by Clause Assessment

Clause Description Status Comments

SECTION C – FIRE RESISTANCE

Part C1 – Fire Resistance and Stability

C1.1 Type of construction required

CRA The building is to be constructed of Type ‘A’ fire resisting construction in accordance with Specification C1.1 of the BCA and the external cladding / façade must be non-combustible unless it complies with specification C1.1 - 2.4 ‘Attachments not to impair fire-resistance’. Prior to the issue of a construction certificate a schedule is to be submitted to the certifying authority detailing the FRL’s of the proposed wall systems and external cladding systems. Note: Non-combustible roof allowance – Specification C1.1 – 3.5 ‘Roof concession’ applies to this proposed class 3 building to allow the roof to be non-combustible in lieu of complying with Table 3 of spec. C1.1. Note: Class 3 concession – Specification C1.1 – 3.10 Concession for class 3 buildings permits the building to be constructed of timber framing throughout; non-combustible material throughout; or a combination of both, provided insulation in cavity walls is non-combustible and the building is fitted with an automatic smoke alarm system complying with Specification E2.2a. Despite this it does not appear as though the building will apply this concession.

C1.2 Calculation of rise in storeys

Noted The building has an overall rise in storeys of three (3).

Rise in storeys = 3 The basement car park is completely underground and is not included in the calculation of the rise in storeys.

Page 19: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 19 of 54

Clause Description Status Comments

C1.3 Buildings of multiple

classification Noted Top storey is class 3. This is not a mixed use building yet

the basement car park is being treated as class 7a.

C1.4 Mixed types of Construction

N / A

C1.5 Two storey Class 2,3 or 9c buildings

N / A

C1.6 Class 4 parts of buildings N / A

C1.7 Open spectator stands and indoor sports stadiums

N / A

C1.8 Lightweight construction CRA Lightweight construction used in a wall system must comply with Specification C1.8. For any wall or ceiling system that is to be upgraded as part of this proposal, construction drawings must indicate the FRL to be achieved; OR be supported by detailed specification regarding the wall system and the nominated FRL. It is not considered necessary to provide this information at the DA stage.

C1.9 - - No provisions

C1.10 Fire hazard properties CRA The fire hazard properties of all floor linings and floor coverings, wall linings and ceiling linings must comply with Specification C1.10. Prior to the issue of a Construction Certificate design certification, relevant testing data, product manufacturer specification is to be provided to the consent authority to verify compliance with this clause as well as to confirm that the lining has been used in a manner consistent with the testing data scenario.

C1.11 Performance of external walls in fire

N / A

Page 20: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 20 of 54

Clause Description Status Comments

C1.12 Non-combustible materials

Noted The following materials, though combustible or containing combustible fibres, may be used wherever a non-combustible material is required:

(a) Plasterboard. (b) Perforated gypsum lath with a normal paper finish. (c) Fibrous-plaster sheet. (d) Fibre-reinforced cement sheeting. (e) Pre-finished metal sheeting having a combustible surface finish not exceeding 1 mm thickness and where the Spread-of-Flame Index of the product is not greater than 0. (f) Bonded laminated materials where— (i) each laminate is non-combustible; and

(ii) each adhesive layer does not exceed 1 mm in thickness; and (iii) the total thickness of the adhesive layers does not exceed 2 mm; and

(iv) the Spread-of-Flame Index and the Smoke-Developed Index of the laminated material as a whole does not exceed 0 and 3 respectively.

C1.13 Fire-Protective Timber Noted Fire-protected timber in a Class 2, 3 or 5 building may be used wherever an element is required to be non-combustible, provided—

(a) the building is— (i) a separate building; or (ii) a part of a building—

(A) which only occupies part of a storey, and is separated from the remaining part by a fire wall; or (B) which is located above or below a part not containing fire-protected timber and the floor between the adjoining parts is provided with an FRL not less than that prescribed for a fire wall for the lower storey; and

(b) the building has an effective height of not more than 25 m; and (c) the building has a sprinkler system throughout complying with Specification E1.5; and (d) any insulation installed in the cavity of the timber building element required to have an FRL is non-combustible; and (e) cavity barriers are provided in accordance with Specification C1.13.

Part C2 – Compartmentation and Separation

C2.1 Application of Part Noted Clauses C2.2, C2.3 and C2.4 do not apply to a sprinkler protected carpark, open deck carpark or open spectator stand.

C2.2 General floor area limitations

Complies The basement is considered a class 7a car park and is therefore subject to the floor area limitations of this clause. The car park complies with the maximum threshold for Type A construction (refer to section 2.13 of this report).

Page 21: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 21 of 54

Clause Description Status Comments Class 3 portion: The floor area and volume limitations are not applicable to the subject Class 3 building.

C2.3 Large isolated buildings N / A

C2.4 Requirements for open spaces and vehicular access

N / A

C2.5 Class 9a and 9c buildings

N / A

C2.6 Vertical separation of Openings in external walls

CRA Window openings in the first and second floor along the southern façade yet that are facing east, have complying vertical spandrel protection by way of not less than 900mm vertical separation with a minimum of 300mm below and 600mm above the top of the slab. This spandrel must have an FRL not less than 60/60/60. Full design specification and drawings showing the extent of the spandrel and the proposed FRL must be submitted to the certifying authority prior to the issue of a construction certificate. In addition to the complying vertical spandrel protection, the windows also have a horizontal projection of not less than 1100mm separating them from the window openings below however the horizontal slab projection does not extend either side of the window by at least 450mm. This is inconsequential as the vertical spandrel protection already complies.

First and second floor – southern elevation (yet window openings face east)

C2.7 Separation by fire walls N / A

C2.8 Separation of classifications in the

Complies Each part of a building must be classified separately. Despite this, BCA clause A3.3 allows parts that have different purposes to be considered part of the predominant use as

Page 22: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 22 of 54

Clause Description Status Comments same storey long as the minor use is not more than 10% of the total floor

area of that storey. The following ancillary spaces are found in the basement level:

- Plant room: this requires that it inherits the same classification as the major classification. In this regard the plant room is therefore considered to be part of the class 7a car park and this clause does not apply to it.

- Bin room / accessible toilet / storage: these areas are less than 10% of the storey floor area and therefore the basement classification being 7a applies to the entire storey.

Upper levels (Ground floor, level 1 & level 2):

- All upper levels are considered class 3.

C2.9 Separation of classifications in different storeys

CRA The car park must be separated from the remainder of the building above with construction complying with an FRL of not less than that prescribed in Specification C1.1 for the classification of the lower storey. Prior to the issue of the construction certificate the design team must confirm where the delineation of the car park is and provide the certifying authority with a schedule of the FRL’s for the separating slab.

Page 23: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 23 of 54

Clause Description Status Comments

C2.10 Separation of lift shafts CRA The proposed lift is to be enclosed by a shaft that complies

with the FRL’s outline in specification C1.1 – 3 (Table 3).

C2.11 Stairways and lifts in one

shaft N/A

C2.12 Separation of equipment N/A Where protection is required it must be as follows: (A) an FRL as required by Specification C1.1, but not less than 120/120/120; and (B) any doorway protected with a self-closing fire door having an FRL of not less than –/120/30.

C2.13 Electricity supply system N/A

C2.14 Public corridors in Class 2 and 3 buildings

N/A No public corridors exceeding 40m in length. (Public corridors must be divided at intervals of not more than 40m by smoke-proof walls complying with Clause 2 of Specification C2.5).

Part C3 – Protection of Openings

C3.1 Application of Part Noted Concessions and definition for certain types of openings.

C3.2 Protection of openings in external walls

Complies

Openings in external walls that require an FRL and that are within 3m of a side or rear boundary shall be protected in accordance with Clause C3.4 of the BCA. (Note: Openings from the far boundary of a road only require protection when within 6m of that far boundary). The

C3.3 Separation of external walls and associated openings in different fire compartments

N/A

Page 24: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 24 of 54

Clause Description Status Comments

C3.4 Acceptable method of protection

CRA The eastern fire isolated exit incorporates glazed sections in its eastern and southern external walls. Eastern glazing – BCA clause C3.8 (b) requires that any part of a fire isolated exit that is exposed to an opening in an external wall of the same building (other than the fire isolated stairway itself) must be protected in accordance with C3.4. Level 1 and level 2 both have an opening within its external wall that is within 6m of the eastern fire isolated stairway glazing:

Level 1

Level 2 Southern glazing – BCA clause C3.2 requires that an opening in an external wall that requires an FRL and is within 6 metres of a far boundary of a road must be protected in accordance with C3.4. The eastern fire isolated stairway that incorporates glazing in its external southern facing wall does not need to be protected as the fire source feature is more than 6 metres away.

Page 25: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 25 of 54

Clause Description Status Comments

No protection required – Southern facing glazed external wall in the eastern fire isolated exit.

C3.5 Doorways in fire walls N / A

C3.6 Sliding fire doors N / A

C3.7 Protection of doorways in horizontal exits

N / A

C3.8 Openings in fire isolated exits

CRA

BCA clause C3.8 (b) requires that any part of a fire isolated exit that is exposed to an opening in an external wall of the same building (other than the fire isolated stairway itself) must be protected in accordance with C3.4. Refer to C3.4 in this table for further details.

C3.9 Service penetrations in fire isolated exits

CRA

Fire-isolated exits must not be penetrated by any services other than for a building of this classification and size - electrical wiring permitted by D2.7(e) to be installed within the exit; or water supply pipes for fire services.

C3.10 Openings in fire isolated lift shafts

CRA

Doorways — If a lift shaft is required to be fire-isolated, an entrance doorway to that shaft must be protected by –/60/– fire doors that—

(i) comply with AS 1735.11; and (ii) are set to remain closed except when discharging or receiving passengers, goods or vehicles.

Lift indicator panels — A lift call panel, indicator panel or other panel in the wall of a fire-isolated lift shaft must be backed by construction having an FRL of not less than –

/60/60 if it exceeds 35 000 mm2 in area.

C3.11 Bounding construction: Noted The proposed DA plans do not incorporate doorways that require protection in accordance with this clause. The SOU’s

Page 26: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 26 of 54

Clause Description Status Comments Class 3 buildings open up onto walkways that have the choice of two exits thus

allowing the doorways to not require protection.

C3.12 Openings in floors for services

CRA Services passing through floors are to be placed within fire resisting shafts or protected in accordance with Clause C3.15 and specification C3.15.

C3.13 Openings in shafts CRA In a building of Type A construction, an opening in a wall providing access to a ventilating, pipe, garbage or other service shaft must be protected by a self-closing –/60/30 fire door or hopper; or an access panel having an FRL of not less than –/60/30. Prior to the issue of a construction certificate compliance details for all services are to be submitted to the certifying authority for assessment.

C3.14 - - No provisions

C3.15 Openings for service installation

CRA Methods and materials used are to be identical to tested prototypes and in accordance with AS4072.1 and AS1530.4, and having achieved the required FRL or resistance to the incipient spread of fire or other specified method.

C3.16 Construction Joints CRA Construction joints are to be installed in accordance with a tested prototype in accordance with AS1530.4.

C3.17 Columns protected with lightweight construction

Noted Columns must be protected in accordance with the identical tested prototype.

SECTION D – ACCESS AND EGRESS

Part D1 – Provision for Escape

Clause Description Status Comments

D1.1 Application of Part Noted The Deemed to Satisfy provisions of this part do not apply to the internal parts of a sole occupancy unit in a Class 3 building.

D1.2 Number of exits required Complies

D1.3 When fire isolated exits are required

Complies The eastern stairway is required to be fire isolated.

The following stairs are not required to be fire isolated:

- Western stairway that connects 2 storeys (level 2 and level 1) yet passes by the third storey (ground floor) and is proposed to be separated from, the extra storey by construction having—

Page 27: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 27 of 54

Clause Description Status Comments (A) an FRL of –/60/60, if non-loadbearing; and (B) an FRL of 90/90/90, if loadbearing; and (C) no opening that could permit the passage of fire or

smoke.

- Basement egress stairs do not connect more than 2 storeys and discharge directly to open space on ground floor.

D1.4 Exit travel distances Complies

D1.5 Distances between alternative exits

Complies

D1.6 Dimensions of exits and paths of travel to exits

CRA Handrails and their dimensions are not currently shown on the plans. All stairs that are used for egress purposes alone require a single handrail that should not encroach on the required 1 metre egress width. Where stairs are also used for everyday purposes these must have double handrails and again these must not encroach on the required 1 metre egress path. The stairway widths appear to be wide enough to accommodate said handrails however confirmation of design prior to the issue of the construction certificate will be required. The doorways that are paths of travel to an exit must have a clear opening width not less than 750mm. Prior to the issue of a construction certificate, full details of the double handrails are to be provided illustrating that the 1 metre width is maintained. A door schedule is also required confirming all door widths.

D1.7 Travel via fire-isolated exits

PS The eastern fire isolated exit does not strictly comply with 2 provisions of D1.7 relating to the discharge from the exit. D1.7(b)(ii): The eastern fire isolated stairway discharges to a space on ground floor within the confines of the building that is used only for pedestrian movement; provides an unimpeded path of travel not further than 20 metres to the road; however is not open for at least 2/3 of its perimeter. The image below

Page 28: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 28 of 54

Clause Description Status Comments

D1.7(c): The discharge point of the eastern fire isolated stairway necessitates occupants to pass by within 6m of an opening in the external wall of the building that is unprotected (building entry doors and services cupboard).

Prior to the issue of the construction certificate, the two above mentioned departures from the DtS provisions of the BCA must be justified by a qualified C10 accredited fire engineer. The fire engineer is to confirm compliance with the relevant performance requirements and prepare the report in accordance with Part A0.7 of the BCA.

D1.8 External stairways in lieu of fire-isolated exits

N/A

D1.9 Travel by Non-fire-isolated Stairways or ramps

Complies All levels including the basement have a minimum of two exits available to occupants at all times. The eastern exit stairway is fire isolated however the western stairway is assessed as a non-fire isolated stairway because it connects 2 storeys (level 2 and level 1) yet passes by the third storey (ground floor) and is proposed to be separated from, the extra storey by construction having—

(A) an FRL of –/60/60, if non-loadbearing; and (B) an FRL of 90/90/90, if loadbearing; and (C) no opening that could permit the passage of fire or

smoke.

Page 29: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 29 of 54

Clause Description Status Comments

D1.10 Discharge from exits CRA If a required exit leads to an open space, the path of travel to

the road must have an unobstructed width throughout of not less than—

(i) the minimum width of the required exit; or

(ii) 1m,

Whichever is the greater

Fully dimension drawings are to be submitted to the certifying authority prior to the issue of the construction certificate.

If an exit discharges to open space that is at a different level than the public road to which it is connected, the path of travel to the road must be by—

A ramp or other incline having a gradient not steeper than 1:8 at any part, or not steeper than 1:14 if required by the Deemed-to-Satisfy Provisions of Part D3. The hatched pathway to the road is assessed as a pathway for egress purposes only. Full design documentation illustrating the levels, gradient, egress path dimensions are to be provided to the certifying authority prior to the issue of the construction certificate.

D1.11 Horizontal exits N/A

D1.12 Non-required stairs, ramps or escalators

N/A

D1.13 Number of persons Noted

Page 30: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 30 of 54

Clause Description Status Comments accommodated

D1.14 Measurement of distance Noted

D1.15 Method of measurement Noted

D1.16 Plant rooms and lift machine rooms: Concession

N/A The plantroom is located in the basement and access to it is grade.

D1.17 Access to lift pits N/A

Part D2 – Construction of Exits

D2.1 Application of Part Noted Except for—

(b) D2.13, D2.14(a), D2.16, D2.17(d), D2.17(e), D2.18 and D2.24, the Deemed-to-Satisfy Provisions of this Part do not apply to the internal parts of a sole-occupancy unit in a Class 2 building or Class 4 part of a building.

D2.2 Fire isolated stairs or ramps

CRA A stairway or ramp (including any landings) that is required to be within a fire-resisting shaft must be constructed—

(a) of non-combustible materials; and

(b) so that if there is local failure it will not cause structural damage to, or impair the fire-resistance of, the shaft.

D2.3 Non-fire-isolated stairways and ramps

CRA In a building having a rise in storeys of more than 2, required stairs and ramps (including landings and any supporting building elements) which are not required to be within a fire-resisting shaft, must be constructed according to D2.2, or only of—

(a) reinforced or prestressed concrete; or (b) steel in no part less than 6 mm thick; or (c) timber that—

(i) has a finished thickness of not less than 44 mm; and

(ii) has an average density of not less than 800 kg/m3

at a moisture content of 12%; and (iii) has not been joined by means of glue unless it has been laminated and glued with resorcinol formaldehyde or resorcinol phenol formaldehyde glue.

The design team has indicated that the two egress stairs serving the basement car park; and the western exit stairway is to be constructed of reinforced concrete.

D2.4 Separation of rising and descending stair flights

N/A

D2.5 Open access ramps and balconies

N/A

D2.6 Smoke lobbies N/A

D2.7 Installations in exits and paths of travel

CRA Electrical boards or other services or equipment are to be located wholly within and enclosed by non-combustible construction or have a fire-protective covering with the doorway suitably sealed against smoke spreading from the enclosure.

Page 31: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 31 of 54

Clause Description Status Comments

D2.8 Enclosure of space under stairs and ramps

N/A

D2.9 Width of stairways Noted A required stairway or ramp that exceeds 2 m in width is counted as having a width of only 2 m unless it is divided by a handrail or barrier continuous between landings and each division has a width of not more than 2 m. There are no stairs that are greater than 2 metres in width.

D2.10 Pedestrian ramps CRA There are no pedestrian ramps serving as required exits other than the rear pathway to Ardittos Lane. This pathway must have a gradient not steeper than 1:8 and the surface of the path is to have a slip-resistance classification not less than that listed in Table D2.14 when tested in accordance with AS 4586.

Prior to the issue of a construction certificate full details illustrating compliance are to be provided to the Certifying Authority.

D2.11 Fire-isolated passageways

N/A The

D2.12 Roof as open space CRA The exit path leading to Elva Street is located above the basement. This pathway must be provided with an FRL of not less than 120/120/120. Prior to the construction certificate being issued, full design details (structural drawings; and building FRL specification) is to be provided to the certifying authority for assessment.

Page 32: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 32 of 54

Clause Description Status Comments

Pathway to Elva Street.

Basement level.

D2.13 Goings and risers CRA For the public stairs – Risers are required to be between 115-190mm and goings between 250-355. Relationship – ALL Goings and Risers are to satisfy the equation of 2R+G=700(max) and 550(min). Construction tolerances – Goings and risers are to be consistent throughout in one flight other than where the allowable construction tolerances are not exceeded – i.e. the variation is as follows: Adjacent risers, or between adjacent goings, is no greater than 5 mm; and the largest and smallest riser within a flight, or the largest and smallest going within a flight, does not exceed 10 mm.

Page 33: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 33 of 54

Clause Description Status Comments

Gaps – Any gap between risers must not permit a 125mm sphere to pass through it. Slip Resistance – All tread surfaces and nosing strips are to achieve a slip resistance classification not less than that listed in Table D2.14 when tested in accordance with AS4586.

D2.14 Landings CRA

Landings must comply with the requirements of Clause D2.14 of the BCA. Landings must be not less than 750mm long and have a non-slip finish throughout or an adequate non-skid strip near the edge of the landing where it leads to a flight below.

D2.15 Thresholds CRA

A threshold of a doorway must not incorporate a step or ramp at any point closer to the doorway than the width of the door leaf unless: - the door sill is not more than 190 mm above the finished

surface of the ground, balcony, or the like, to which the doorway opens.

The rear doorway to the communal area is proposed to have a threshold ramp to comply with AS1428.1-2009 (10.5): Threshold ramps at doorways on a continuous path of travel shall have—

(a) a maximum rise of 35 mm; (b) a maximum length of 280 mm; (c) a maximum gradient of 1:8; and (d) be located within 20 mm of the door leaf which it

serves,

D2.16 Barriers to prevent falls CRA Compliance with Table D2.16a is required for all barriers that

are designed to prevent falls of greater than 1 metre from a surface below.

Page 34: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 34 of 54

Clause Description Status Comments Where a barrier is a single or series of glazed panels, compliance with AS1288 and AS1170 is required. For barriers that prevent falls greater than 4 metres from the surface below, the barrier is to be designed in order to ensure there are no climbable elements between 150mm-760mm from the finished floor level. Where fire isolated staircases are also to be used for everyday access and exit purposes and not only for emergency purposes the concession in Table D2.16a is no longer afforded to the stairway. Prior to the issue of a construction certificate full barrier details illustrating compliance is to be provided to the Certifying Authority.

D2.17 Handrails CRA For ALL staircases handrails are to be provided to at least one side of stair flights and located not less than 865mm above the nosings of stair treads and the floor surfaces of landings. The handrail extension is required (300mm) and is to finish in accordance with the handrail provisions in AS1428.1-2009. Where stairs are also used for general access (i.e. for a purpose other than an emergency) the stairway is to have double handrails in accordance with AS1428.1-2009. These handrails are not allowed to encroach into the required 1 metre stairway width. Prior to the issue of the construction certificate full specifications are to be provided to the certifying authority that include handrail extension details.

D2.18 Fixed platforms walkways, stairways and ladders

N/A Fixed platforms, walkways, stairways, ladders, landings, handrails, balustrades and any tread or riser in a plant room, lift motor room or the like is to comply with AS1657.

D2.19 Doorways and doors Complies

D2.20 Swinging doors Complies

D2.21 Operation of latch CRA Does not apply to the internal parts of the SOU’s. This means that compliance is required on the outside of the SOU door. A door in a required exit, forming part of a required exit or in the path of travel to a required exit must be readily openable without a key from the side that faces a person seeking egress, by—

(i) a single hand downward action on a single device which is located between 900 mm and 1.1 m from the floor and if serving an area required to be accessible by Part D3—

Page 35: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 35 of 54

Clause Description Status Comments A) be such that the hand of a person who

cannot grip will not slip from the handle during the operation of the latch; and

B) have a clearance between the handle and the back plate or door face at the centre grip section of the handle of not less than 35 mm and not more than 45 mm; or

(ii) a single hand pushing action on a single device which is located between 900 mm and 1.2 m from the floor.

Doors are allowed to be locked for security purposes on the side facing a person seeking egress but only in certain circumstances – e.g.: where a failsafe device is also provided and connected to the building’s alarm system. Or where the locked doorway serves a room that has a concession applied to it under this clause. Prior to the issue of the construction certificate a door schedule is to be provided to the certifying authority confirming all door hardware and security requirements.

D2.22 Re-entry fire-isolated exits

N/A

D2.23 Signs on doors CRA Prior to the issue of the construction certificate a door schedule is to be provided to the certifying authority confirming all lettering that is to be installed. The fire isolated stairway (eastern stairway) requires the following signage on all self-closing doorways associated with it – i.e.: that provide direct access to it (on the side facing a person entering the stairway); and that discharge from it (on both sides of the doorway):

“FIRE SAFETY DOOR DO NOT OBSTRUCT DO NOT KEEP OPEN”

Voluntary signage such as “FIRE SAFETY DOOR—DO NOT OBSTRUCT” may be installed on the doorways that serve the non-fire isolated staircases (western stairway and basement stairs).

Page 36: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 36 of 54

Clause Description Status Comments

D2.24 Protection of openable windows

CRA Design detail of the barriers and manufacturer’s specification of the locking mechanisms to restrict windows is to be submitted to the certifying authority for assessment prior to the issue of a construction certificate. (a) A window opening must be provided with protection, if the floor below the window is 2 m or more above the surface beneath in—

(i) a bedroom in a Class 2 or 3 building or Class 4 part of a building; or (ii) a Class 9b early childhood centre.

(b) Where the lowest level of the window opening is less than 1.7 m above the floor, a window opening covered by (a) must comply with the following:

(i) The openable portion of the window must be protected with—

(A) a device capable of restricting the window opening; or (B) a screen with secure fittings.

(ii) A device or screen required by (i) must— (A) not permit a 125 mm sphere to pass through the window opening or screen; and (B) resist an outward horizontal action of 250 N against the— (aa) window restrained by a device; or (bb) screen protecting the opening; and (C) have a child resistant release mechanism if the screen or device is able to be removed, unlocked or overridden.

(c) A barrier with a height not less than 865 mm above the floor is required to an openable window—

(i) in addition to window protection, when a child resistant release mechanism is required by (b)(ii)(C); and (ii) where the floor below the window is 4 m or more above the surface beneath if the window is not covered by (a).

(d) A barrier covered by (c) except for (e) must not— (i) permit a 125 mm sphere to pass through it; and (ii) have any horizontal or near horizontal elements between 150 mm and 760 mm above the floor that facilitate climbing.

(e) A barrier required by (c) to an openable window in— (i) fire-isolated stairways, fire-isolated ramps and other areas used primarily for emergency purposes, excluding external stairways and external ramps; and (ii) Class 7 (other than carparks) and Class 8 buildings and parts of buildings containing those classes;

must not permit a 300mm sphere to pass through it.

Page 37: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 37 of 54

Clause Description Status Comments

D2.25 Timber stairways: Concession

CRA This does not apply to the internal parts of the SOU’s.

The basement staircase is to be constructed of reinforced concrete and therefore complies.

(a) Notwithstanding D2.2(a), timber treads, risers, landings and associated supporting framework which—

(i) has a finished thickness of not less than 44 mm; and (ii) has an average density of not less than 800 kg/m

3

at a moisture content of 12%, may be used within a required fire-isolated stairway or fire-isolated passageway constructed from fire-protected timber in accordance with C1.13 subject to— (iii) the building being protected throughout by a sprinkler system complying with Specification E1.5 which extends to within the fire-isolated enclosure; and

(iv) fire protection being provided to the underside of stair flights and landings located immediately above a landing level which—

(A) is at or near the level of egress; or (B) provides direct access to a carpark.

(b) Fire protection required by (a) must be not less than one layer of 13 mm fire-protective grade plasterboard fixed in accordance with the system requirements for a fire-protective covering.

SECTION D3.3 – ACCESS FOR PEOPLE WITH DISABILITIES

D3.0 Deemed-to-Satisfy Provisions

Noted

D3.1 General Building Access Requirements

Complies

Access has been provided to ALL SOU’s. Access to the common areas for use by all residents has been provided (rear yard communal area; bin room; car park).

D3.2 Access to Buildings Complies

The principal pedestrian entry via Elva Street is provided with compliant accessible entry.

Page 38: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 38 of 54

Clause Description Status Comments N / A

Accessways from accessible car parking spaces – At least one accessible car space is required.

D3.3 Parts of Buildings to be accessible

CRA The pedestrian ramps are required to comply with AS1428.1-2009 (clause 10); and the basement stairways are required to comply with AS1428.1-2009 (clause 11). Every passenger lift must comply with E3.6. Final details to be provided at the construction certificate stage detailing compliance with AS1428.1-2009 ‘Design for access and mobility’. Slip resistance details for compliance with Table D2.14 and AS4586 is also required to be submitted for assessment.

Page 39: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 39 of 54

Clause Description Status Comments

Page 40: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 40 of 54

Clause Description Status Comments

Page 41: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 41 of 54

Clause Description Status Comments

D3.4 Exemptions Noted The following areas are not required to be accessible: (a) An area where access would be inappropriate because of the particular purpose for which the area is used, (b) An area that would pose a health or safety risk for people with a disability, (c) Any path of travel providing access only to an area exempted by (a) or (b)

D3.5 Accessible Car parking N / A

Class 3 residential buildings must comply with table D3.5. Note: Accessible car parking is to comply with AS/NZS 2890.6. Confirmation the clearance above the accessible car space and entry into the basement garage from Elva Street complies with this standard.

D3.6 Signage CRA Prior to the issue of the construction certificate all signage details are to be provided to the certifying authority confirming the location of the signage, the text and that the braille portion of the signage complies with specification D3.6. In this regard the following braille signage incorporating the international symbol of access as appropriate, in accordance with AS 1428.1 to identify each–

sanitary facility, except a sanitary facility within a sole-occupancy unit in a Class 3 building; and

identify each door required by E4.5 to be provided with an exit sign and state—

o "Exit"; and o "Level" ; and either (aa) the floor level

number; or (bb) a floor level descriptor; or

o a combination of (aa) and (bb)

o signage in accordance with AS 1428.1

must be provided for accessible unisex sanitary facilities to identify if the facility is suitable for left or right handed use.

D3.7 Hearing Augmentation N / A

D3.8 Tactile Ground Surface indicators

CRA Where required, TGSI’s must comply with the requirements of AS1428.4-2009. Coverage is required at the top and

Page 42: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 42 of 54

Clause Description Status Comments bottom of each stairway serving the basement; and are also required at the top and bottom of each required ramp. The construction drawings set will need to fully document the location and level of luminance contrast for the TGSI’s.

There are three (3) distinct types of TGSI, these each need to be assessed as to the most appropriate based on the surface it is to be applied and lighting conditions. AS1428.4.1 – 2009 clearly provides installation requirements.

30% contrast to surface 45% Contrast to Surface 60% Contrast to Surface

D3.9 Wheelchair Seating Spaces in Class 9b Assembly Buildings

N / A

D3.10 Swimming Pools N / A

D3.11 Ramps Complies The overall rise addressed by the pedestrian ramps does not exceed 3.6m. All landings appear to comply. Fully dimensioned and detailed drawings must be submitted to the certifying authority prior to the issue of the construction certificate.

D3.12 Glazing on an Accessway CRA On an accessway, where there is no chair rail, handrail or transom, all frameless or fully glazed doors, sidelights and any glazing capable of being mistaken for a doorway or opening, must be clearly marked in accordance with AS 1428.1.

SECTION E – SERVICES AND EQUIPMENT

Part E1 – Fire Fighting Equipment

Clause Description Status Comments

E1.1 - - No Provisions

E1.2 - - No Provisions

E1.3 Fire Hydrants CRA

Hydrant coverage is required to AS2419.1-2005 as the building’s floor area is proposed to be greater than 500m². Whether the hydrant coverage will be provided from the street or by an internal hydrant system with pressure delivered by a hydrant booster assembly remains to be seen. Prior to the issue of a construction certificate a suitably qualified and practicing hydraulic engineer must confirm any existing street hydrant is located such that the required hose reel reach will be achieved as well as the required pressure and flow rates. The assessment is to include an enquiry to the regulatory authority Sydney Water to determine if the existing pressure and flow rates are adequate to serve the entire building.

Page 43: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 43 of 54

Clause Description Status Comments PS

It is noted that the proposed DA drawings accommodate internal hydrants and a hydrant booster assembly. Should the hydraulic engineer’s assessment result in the requirement to install the booster assembly and hydrant points, it is noted that the location of the booster assembly does not comply with the requirements of AS2419.1-2005 nor does the construction of the shield wall. These two code departures must be justified by a qualified C10 fire engineer, the report prepared in accordance with A0.7 of the BCA and submitted to the certifying authority prior to the issue of the construction certificate.

E1.4 Hose Reels CRA Class 3 building part – Fire hose reels are not required in the class 3 portions of the building – i.e.: the ground floor, level 1 and level 2. Class 7a car park – If internal hydrants are installed in the building (refer to BCA E1.3) then fire hose reels must be installed in the car park. If however there are no internal hydrants installed in the building then fire hose reels are only required in the car park if the car park level is deemed to be greater than 500m². Where hose reels are required they are to be installed to comply with AS2441-2005.

E1.5 Sprinklers N / A

E1.6 Portable fire extinguishers CRA Portable fire extinguishers are required to be provided in accordance with Table E1.6 of the BCA and AS 2444. Portable fire extinguishers provided in a Class 3 building must be an ABE type fire extinguisher; and be a minimum size of 2.5 kg; and distributed outside a sole-occupancy unit—

(A) to serve only the storey at which they are located; and (B) so that the travel distance from the entrance doorway of any sole-occupancy unit to the nearest fire extinguisher is not more than 10 m.

Page 44: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 44 of 54

Clause Description Status Comments

E1.7 - - No Provisions

E1.8 Fire control centres N/A

E1.9 Fire precautions during construction

CRA In a building under construction not less than one fire extinguisher to suit Class A, B and C fires and electrical fires must be provided at all times on each storey adjacent to each required exit or temporary stairway or exit.

E1.10 Provisions for special hazards

N/A

Part E2 – Smoke Hazard Management

E2.1 Application of Part Noted

E2.2 General requirements CRA Table E2.2a for a building less than 25m in effective height requires that the building is provided with an automatic

Page 45: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 45 of 54

Clause Description Status Comments smoke detection and alarm system complying with Specification E2.2a:

- A clause 4 system is required due to a class 3 part of the building being located more than 2 storeys above ground level

- The detection system is required to set off a building occupant warning system (BOWS) in accordance with clause 6.

Within Sole-Occupancy Units: A smoke detection system complying with AS1670.1-2015, installed to comply with specification E2.2a clause 3(c)(i) and 3(c)(ii). Within public corridors and other internal public spaces (not car park): A smoke detection system complying with AS1670.1-2015. Basement car park: For the purposes of interpreting Table E2.2a, the basement car park is not considered as part of the class 3 building, rather it is its own classification being a class 7a. In addition, there is no fire isolated staircase that connects the class 3 building with the class 7a car park. As a result, the smoke detection system does not need to extend to the basement car park. This clause must be read in conjunction with BCA clause F4.11 ‘car parks’ and AS1668.2 (clause 5.5.3), for the purposes of installing a manual control device that turns off the car park mechanical ventilation system. Building occupant warning system: A BOWS must be installed to sound throughout the entire building. The minimum sound pressure level required at SOU doors is not less than 100dB(A). System Monitoring: The smoke detection system must be connected to a fire alarm monitoring system connected to a fire station or fire station dispatch centre in accordance with AS 1670.3

E2.3 Provisions for special hazards

N/A

Part E3 – Lift Installations

E3.1 Lift Installations CRA An electric passenger lift installation and an electrohydraulic passenger lift installation must comply with Specification E3.1.

E3.2 Stretcher facility in lifts N/A

E3.3 Warning against use of lifts in fire

CRA A warning sign must—

a) be displayed where it can be readily seen—

i. near every call button for a passenger lift or group of lifts throughout a building; except

Page 46: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 46 of 54

Clause Description Status Comments ii. a small lift such as a dumb-waiter or the like

that is for the transport of goods only; and

b) comply with the details and dimensions of Figure E3.3 and consist of—

i. incised, inlaid or embossed letters on a metal, wood, plastic or similar plate securely and permanently attached to the wall; or

ii. letters incised or inlaid directly into the surface of the material forming the wall.

E3.4 Emergency lifts N/A

E3.5 Landings CRA Access and egress to and from lift well landings must comply with the Deemed-to-Satisfy Provisions of Section D.

E3.6 Facilities for people with disabilities

CRA The internal lift must have accessible features in accordance with Table E3.6b:

- The minimum internal landing dimension is 1100mm x 1400mm.

- Handrails; minimum clear door opening; lighting; and a passenger protection system to AS1735.12

- Audible and visual requirements – o Automatic audible information

within the lift car to identify the level each time the car stops;

o audible and visual indication at each lift landing to indicate the arrival of the lift car; and

o audible information and audible indication required by (a) and (b) is to be provided in a range of between 20–80 dB(A) at a maximum frequency of 1 500 Hz

- Emergency hands-free communication, including a button that alerts a call centre of a problem and a light to signal that the call has been received.

E3.7 Fire Services Control N/A

E3.8 Aged care buildings N/A

E3.9 Fire service recall control switch

N/A

Page 47: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 47 of 54

Clause Description Status Comments

E3.10 Lift car fire service drive control switch

N/A

Part E4 – Emergency Lighting, Exit Signs and Warning Systems

E4.1 - - No provisions

E4.2 Emergency lighting requirements

CRA Emergency lighting is to be provided throughout the building in accordance with Clause E4.2 of the BCA. Emergency lighting is to be provided in every passageway, hallway, corridor or the like, that is part of the path of travel to an exit. In every passageway, corridor, hallway, or the like, having a length of more than 6 m from the entrance doorway of any sole-occupancy unit in a class 3 building to the nearest doorway opening directly to a road or open space and in every required non fire-isolated stairway.

E4.3 Measurement of distance Noted

E4.4 Design and operation of emergency lighting

CRA Every required emergency lighting system must comply with AS 2293.1-2005 (test switch to be installed at each storey).

E4.5 Exit signs CRA Exit signs are to be provided in accordance with Clause E4.5 of the BCA. Exit signs must be clearly visible to person approaching the exit and must be installed on, above or adjacent to; 1. A door providing direct egress from a storey to a stairway, passageway or ramp serving as a required exit. 2. A door from an enclosed stairway, passageway or ramp at every level of discharge to a road or open space. 3. A door serving as or forming part of a required exit in a storey required to be provided with emergency lighting.

E4.6 Direction signs CRA Where an exit is not readily apparent then exit signs with directional arrows must be installed in appropriate positions in corridors, hallways, lobbies and the like indicating the direction to a required exit in accordance with Clause E4.6 of the BCA.

E4.7 Class 2, 3 and 4

buildings: Exemptions Noted E4.5 does not apply to an entrance door of a sole-occupancy

unit in a class 3 building.

E4.8 Design and operation of exit signs

Noted Exit signs are to operate in accordance with AS 2293.1 and be clearly visible at all times while the building is occupied.

Page 48: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 48 of 54

Clause Description Status Comments

E4.9 Sound systems and

intercom systems for emergency purposes

N/A

SECTION F – HEALTH AND AMENITY

Part F1 – Damp and Weatherproofing

Clause Description Status Comments

F1.1 Stormwater drainage CRA Stormwater drainage design shall be in accordance with AS/NZS 3500.3. Details and a design certificate will be required by a suitably qualified hydraulic engineer prior to the issue of a Construction Certificate.

F1.2 - - No provisions

F1.3 - - No provisions

F1.4 - - No provisions

F1.5 Roof coverings CRA Roof coverings are to comply with the relevant Australian Standards as per Clause F1.5. Details and design certification to be provided prior to the issue of a Construction Certificate.

F1.6 Sarking CRA Sarking type materials used for weatherproofing of roofs and walls must comply with AS/NZS 4200 Parts 1 and 2. Details and design certification to be provided prior to the issue of a Construction Certificate.

F1.7 Waterproofing of wet areas

CRA Shower enclosure surfaces, floor surfaces in bathrooms, shower rooms, slop hoppers, sink compartments, laundry and sanitary compartments is required to be waterproofed and/or Water Resistant in accordance with AS 3740. Details and design certification to be provided prior to the issue of a Construction Certificate.

F1.8 - - No provisions

F1.9 Damp-proofing CRA Details and design certification to be provided prior to the issue of a Construction Certificate.

F1.10 Damp-proofing of floors on the ground

CRA A vapour barrier in accordance with AS2870 is to be provided beneath the basement floor slab.

Page 49: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 49 of 54

Clause Description Status Comments Details and design certification to be provided prior to the issue of a Construction Certificate.

F1.11 Provisions of floor wastes CRA The floor of each bathroom / laundry is to be graded to permit drainage to a floor waste. The plans forming part of the Construction Certificate Application must detail compliance with the above.

F1.12 Sub-floor ventilation CRA The proposed design is showing a sub-floor space above the basement car park.

Subfloor spaces must—

(i) be provided with openings in external walls and internal subfloor walls in accordance with Table F1.12 for the climatic zones given in Figure F1.12; and (ii) have clearance between the ground surface and the underside of the lowest horizontal member in the subfloor in accordance with Table F1.12. In situations where openings in external walls and internal subfloor walls, are not able to be provided, additional measures must be provided to ensure that the overall level of ventilation of the subfloor space is maintained.

F1.13 Glazed assemblies CRA Windows, sliding doors with a frame, adjustable louvres, shopfronts and window walls with one piece framing in an external wall must comply with AS 2047 requirements for resistance to water penetration. Details and design certification to be provided prior to the issue of a Construction Certificate.

Part F2 – Sanitary and Other Facilities

F2.1 Facilities in residential buildings

Complies Each SOU is provided with a shower; closet pan; and wash basin. There is proposed to be no more than 10 employees in the building at any one time therefore a single unisex accessible sanitary compartment has been provided in the basement car park. The compartment must have Adequate means of disposal of sanitary towels must be provided in sanitary facilities for use by females.

F2.2 Calculation of number of occupants and fixtures

Noted

F2.3 Facilities in Class 3 to 9 buildings

CRA Where there is an accessible or adaptable apartment containing a sanitary facility (toilet) at least one must be accessible. The design proposes 4 adaptable units and therefore the sanitary compartment internal dimensions and wall construction must be capable of complying with the provisions of AS1428.1-2009 for an accessible unisex sanitary compartment. Design certification from an access consultant is to be provided confirming the building can comply with the Adaptable housing Code Provisions (AS4299-1995).

Page 50: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 50 of 54

Clause Description Status Comments In addition, an accessible unisex sanitary compartment is required where a male or female bank of toilets is provided for in a common area. The basement unisex accessible compartment addresses this requirement.

F2.4 Accessible sanitary Facilities

CRA Accessible or Adaptable Units required by Council’s relevant DCP and reflected in any Development Application Consent from Council may require full compliance with AS1428.1-2009. In this regard any accessible toilet and/or shower compartment or facility will need to comply with AS1428.1-2009. Full compliance with AS1428.1:2009 is to be indicated on the Construction Certificate Plans. Despite the requirement above, signage in accordance with AS1428.1-2009 and BCA clause D3.6 would not be required to denote the accessible sanitary compartment within an SOU proposed to be ‘adaptable’; nor will the adaptable car space be sign posted as being accessible.

F2.5 Construction of sanitary compartments

CRA Doors to fully enclosed toilets are to open outwards, slide or be readily removable from the outside of the sanitary compartment unless there is a clear space of at least 1.2m between the closet pan within the sanitary compartment and the nearest part of the doorway. Plans submitted with the Construction Certificate Application must ensure that compliance with the above has been achieved for all sanitary facilities including within SOU’s.

F2.6 Interpretation: Urinals and washbasins

Noted

F2.7 Warm water installations N / A Not Applicable in NSW

F2.8 Waste Management N / A

Part F3 – Room Sizes

F3.1 Height of rooms and CRA Ceiling heights must be not less than—

Page 51: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 51 of 54

Clause Description Status Comments other spaces (a) in a habitable room excluding a kitchen — 2.4 m; and

(b) in a kitchen — 2.1 m; and (c) in a corridor, passageway or the like — 2.1 m; and (d) in a bathroom, shower room, laundry, sanitary compartment, airlock, pantry, storeroom, garage, car parking area or the like — 2.1 m; and (e) in a room or space with a sloping ceiling or projections below the ceiling line within— (i) a habitable room— (A) in an attic — a height of not less than 2.2 m for at least two-thirds of the floor area of the room or space; and (B) in other rooms — a height of not less than 2.4 m over two-thirds of the floor area of the room or space; and (ii) a non-habitable room — a height of not less than 2.1 m for at least two-thirds of the floor area of the room or space, and when calculating the floor area of a room or space, any part that has a ceiling height of less than 1.5 m is not included; and (f) in a stairway — 2.0 m measured vertically above the nosing line.

Page 52: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 52 of 54

Clause Description Status Comments

Part F4 – Light and Ventilation

F4.1 Provisions of natural light

Noted Natural light must be provided to all bedrooms in a class 3 building.

F4.2 Methods and extent of natural light

Complies

F4.3 Natural light borrowed from adjoining room

CRA IF REQUIRED – Natural lighting to a room in a Class 3 building may come through a glazed panel or opening from an adjoining room (including an enclosed verandah).

F4.4 Artificial lighting CRA Artificial lighting must be provided in required stairways, passageways, ramps, sanitary compartments, bathrooms, laundries and other spaces used in common by occupants of the building complying with AS1680.0 in accordance with the requirements of Clause F4.4 of the BCA. Details and design certification to be provided by electrical consultant prior to the issue of a Construction Certificate.

F4.5 Ventilation of rooms Complies CRA

Ventilation shall be provided throughout the building by means of natural ventilation complying with Clause F4.6. Prior to the issue of a construction certificate, if ventilation will be provided by mechanical means then design details are to be provided to the certifying authority for assessment confirming compliance with AS1668.2 and AS3666.1 as required by Clause F4.5. Note: Condenser locations may require additional approvals through the consent authority (local council).

F4.6 Natural ventilation Complies

F4.7 Ventilation borrowed from adjoining room

N / A Not required as direct ventilation is being provided.

F4.8 Restriction on location of sanitary compartments

Noted Compliance with F4.9 is required.

F4.9 Airlocks CRA If restricted by F4.8 – Access to the toilet must be by an airlock, hallway or other room; or the sanitary compartment must be provided with mechanical exhaust ventilation.

F4.10 - - No provisions

F4.11 Carparks CRA The carpark is being provided with a mechanical ventilation system complying with AS1668.2. Note: AS1668.2 - 5.5.3 Override control To enable manual control by attending emergency services personnel, fans that are not required to shut down on initiation of fire mode in the car park shall be provided with a control switch at the designated building entry point. NOTE: Signage should be located at the car park entry indicating the location of the control switch.

Page 53: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 53 of 54

Clause Description Status Comments NOTE: As the building is to incorporate a fire indicator panel associated with the smoke detection system (AS1670.1-2015), the override switch for the car park mechanical ventilation system can be installed at the same location. Details and design certification to be provided by mechanical engineer prior to the issue of a Construction Certificate.

F4.12 Kitchen local exhaust N / A Commercial Kitchens only. Note: Despite the above, any range hood or ducting proposed must not contravene the building’s ability to suppress fire via construction methods. Adherence to C3.15 is required.

Part F5 – Sound Transmission and Insulation

F5.1 Application of part Applies Applicable to Class 3 buildings

F5.2 Determination of airborne sound insulation ratings

Noted Construction required to have an airborne sound insulation rating must have the value for weighted sound reduction index (Rw) or weighted sound reduction index with spectrum adaptation term (Rw + Ctr) determined in accordance with AS/NZS1276.1, or ISO717.1 using result from laboratory measurements, or comply with Specification F5.2 of the BCA.

F5.3 Determination of impact sound installation ratings

Noted A floor required to have an impact sound insulation rating must have the required value for weighted normalised impact sound pressure level with spectrum adaptation term (Ln,w+Cl) determined in accordance with AS/ISO 717.2 using results from laboratory measurements or comply with Specification F5.2 of the BCA. A wall that is required to have an impact sound insulation rating must be of discontinuous construction. Detailed design documentation and specification to be provided prior to the issue of a Construction Certificate.

F5.4 Sound insulation rating for floors

CRA Floors separating sole occupancy units or separating sole occupancy units from a plant room, lift shaft, public lobby or the like or parts of different classifications must have an Rw + Ctr of not less than 50 and an Ln,w + Cl of not more than 62. A design certificate and details of form of construction required to achieve such will be required from a qualified acoustic engineer prior to the issue of a Construction Certificate.

F5.5 Sound insulation rating of walls

CRA A wall separating sole occupancy units must have an Rw + Ctr not less than 50. A wall separating a sole occupancy from a lift shaft, public lobby or the like, or parts of different classifications must have an Rw + Ctr not less than 50. Compliance with F5.3(b) is required if the wall separates a bathroom, sanitary compartment, laundry or kitchen in one sole occupancy unit from a habitable room (excluding a

Page 54: NATIONAL CONSTRUCTION CODE (NCC) 2016 COMPLIANCE … · Construction Code Series (volume 1) 2016. 2.4. Referenced Documents The following documentation was relied upon when preparing

Page 54 of 54

Clause Description Status Comments kitchen) in another adjoining unit or a sole occupancy unit from a plant room or lift shaft. A door may be incorporated in a wall that separates a sole occupancy unit from a stairway, public corridor, public lobby or the like, provided the door assembly has an Rw not less than 30. Where a wall required to have sound insulation has a floor above, the wall must continue to the underside of the floor above or a ceiling that provides the sound insulation required for the wall. Where a wall required to have sound insulation has a roof above, the wall must continue to the underside of the roof above or a ceiling that provides the sound insulation required for the wall. A design certificate and details of form of construction required to achieve such will be required from a qualified acoustic engineer prior to the issue of a Construction Certificate.

F5.6 Sound insulation rating of services

CRA If a duct, soil, waste or water supply pipe, including a duct or pipe that is located in a wall or floor cavity, serves or passes through more than one sole-occupancy unit, the duct or pipe must be separated from the rooms of any sole-occupancy unit by construction with an Rw + Ctr (airborne) not less than— (i) 40 if the adjacent room is a habitable room (other than a kitchen); or (ii) 25 if the adjacent room is a kitchen or non-habitable room. If a storm water pipe passes through a sole-occupancy unit it must be separated in accordance with (i) and (ii) above. A design certificate and details will be required by a qualified acoustic engineer prior to the issue of a Construction Certificate.

F5.7 Isolation of pumps CRA A flexible coupling must be used at the point of connection between the service pipes in a building and any circulating or other pump.

END OF REPORT.