Mystery Solved: Five Surprises Discovered With Megahertz ...

30
© 2019 SEL and AEP Mystery Solved: Five Surprises Discovered With Megahertz Sampling and Traveling-Wave Data Analysis E. O. Schweitzer, III, V. Skendzic, A. Guzmán, M. V. Mynam, and J. L. Eternod Schweitzer Engineering Laboratories, Inc. Yanfeng Gong American Electric Power

Transcript of Mystery Solved: Five Surprises Discovered With Megahertz ...

Page 1: Mystery Solved: Five Surprises Discovered With Megahertz ...

© 2019 SEL and AEP

Mystery Solved: Five Surprises Discovered With Megahertz Sampling and Traveling-Wave Data Analysis

E. O. Schweitzer, III, V. Skendzic, A. Guzmán, M. V. Mynam, and J. L. Eternod

Schweitzer Engineering Laboratories, Inc.

Yanfeng GongAmerican Electric Power

Page 2: Mystery Solved: Five Surprises Discovered With Megahertz ...

• Detection of surges produced by lightning• LOCATION of lightning-induced surges• Breaker restriking and waves launched• HV transients• HV transients we located

MHz Sampling, 18-Bit Resolution, Absolute TimeMillisecond Protection, 100 ft Fault Locating, Greater Visibility

Page 3: Mystery Solved: Five Surprises Discovered With Megahertz ...

Clarke Components Work for Traveling WavesSymmetrical Components Don’t

α β 0

Can’t use symmetrical components because I1 and I2depend on the “a” operator…which only works with phasors

Page 4: Mystery Solved: Five Surprises Discovered With Megahertz ...

One Event Reveals Precursor Lightning Surges, BG Fault, and Breaker Restrike

Volta

ge (k

V)

0

100

200

–200

–100

Cur

rent

(A)

0

4000

–4000

8000

500–50 Time (ms)

Ib

Page 5: Mystery Solved: Five Surprises Discovered With Megahertz ...

Iα and I0 Components Dominate Ground Fault

0

8000

–4000

Cur

rent

(A)

0

–4000

8000

500–50 Time (ms)

Cur

rent

(A)

4000

4000Ib

IαI0

Page 6: Mystery Solved: Five Surprises Discovered With Megahertz ...

Differentiator-Smoother Accentuates Transientsand Attenuates System Frequency

t

di/dt

tat

i

i(t)is(t)

di/dt

Current Arrival Timei(t) is(t)

tadi/dt

d/dtSmoother

(LPF)Differentiator Time-of-

Peak Estimator

Interpolate to50 ns accuracy

Page 7: Mystery Solved: Five Surprises Discovered With Megahertz ...

0

500–50 Time (ms)

Cur

rent

(A)

Differentiator-Smoother Accentuates Transientsand Attenuates System Frequency

4000

–4000

0400

–400

0400

–400

Ib

I0

Page 8: Mystery Solved: Five Surprises Discovered With Megahertz ...

Rescaling I0 Reveals Prefault Transients18-bit resolution provides excellent dynamic range

500–50 Time (ms)

Cur

rent

(A)

Ib0

4000

–4000

0400

–400

0

20

–10–20

10

I0

Page 9: Mystery Solved: Five Surprises Discovered With Megahertz ...

Cur

rent

(A)

0

40

0

–40

–4

Similar Transients in All Three Phases: I0BPA Verifies Lightning Was Nearby

I0

80

–80

–8

–12

4

–36 –34Time (µs)–35

Page 10: Mystery Solved: Five Surprises Discovered With Megahertz ...

Cur

rent

(A)

0

400

0

–400

–400

800

–800

–800

400

Lightning Triggers BG Fault at T = 0Reflections From the Fault and Remote Terminal

0 Time (µs)100 200 300 400 500

Reflection from fault

Reflection from remote terminal

Page 11: Mystery Solved: Five Surprises Discovered With Megahertz ...

TW Fault Locator Reported Fault 65.5 km

From GoshenBPA Verified Location

0

Tim

e (µ

s)

200

400

600

800

1000

1200

1400

Page 12: Mystery Solved: Five Surprises Discovered With Megahertz ...

Cur

rent

(A)

0

100

0 Time (ms)

Breaker Restrike Delays Fault Clearing ½ CycleVo

ltage

(kV)

200

–100

–200

20 40 60

0

40002000

6000

–2000

Ib

Page 13: Mystery Solved: Five Surprises Discovered With Megahertz ...

40 45 50 55Time (ms)–4000

–2000

0

2000

4000

Cur

rent

(A)

47.2 47.4 47.6 47.8 48 48.2 48.4 48.6Time (ms)

–2000

–1500

–1000

–500

0

Breaker Restrike Delays Fault Clearing ½ Cycle

Restrike Reflectionfrom fault

Reflection from remote end

Page 14: Mystery Solved: Five Surprises Discovered With Megahertz ...

Restrike Launches WaveWhich Bounces Off Fault

and the Remote End Tim

e (μ

s)

–200

0

200

400

600

800

10000 50 100

Distance From Local Terminal (km)

RestrikeFault

Restrike reflected from fault

Restrike reflected from remote end

Page 15: Mystery Solved: Five Surprises Discovered With Megahertz ...

Location of Lightning-Induced Surges

Page 16: Mystery Solved: Five Surprises Discovered With Megahertz ...

MHz Records Track Lightning Storm as It Moves Across CFE 400 kV System

Over 30 records triggered in 35 minutes with NO faults

R

MID

IBD CHM

TMD

223.8 km

33.6 km195.2 km 102 km

20 km

5.6 km

144 km

R

102 km

144 km

Page 17: Mystery Solved: Five Surprises Discovered With Megahertz ...

Each Record Shows Multiple Transients Both on Voltages and Currents

Cur

rent

(A)

0200

0 Time (ms)

Volta

ge (k

V)

400

–200–400

0

200100

–200

50 100

–100

300

Page 18: Mystery Solved: Five Surprises Discovered With Megahertz ...

I0 Dominance Suggests Lightning CFE Verifies Lightning Was NearbyC

urre

nt (A

)

0

200

0 Time (µs)

–200

0

80

40

–80

–40

200 400 600

All Recorded Transients Share Common Shape

I0

Page 19: Mystery Solved: Five Surprises Discovered With Megahertz ...

No fault,so only reflection

is from remote end

Double-Ended Fault Locating Detects

Location of Lightning Activity

–500

0

500

1000

1500

2000

MID

0 100 200Distance From MID (km)

TMD

Tim

e (μ

s)

Page 20: Mystery Solved: Five Surprises Discovered With Megahertz ...

Transients Move Across System Like a Storm!

21:50 22:00 22:10 22:20 22:30Local Time (hh:mm)

90

95

100

105

110

115

120

125

Dis

tanc

e Fr

om M

ID (k

m)

Page 21: Mystery Solved: Five Surprises Discovered With Megahertz ...

High-Voltage Transients

Page 22: Mystery Solved: Five Surprises Discovered With Megahertz ...

Sudden Onset of Transients but No Faults

R

MID

IBD CHM

TMD

223.8 km

33.6 km195.2 km 102 km

20 km

5.6 km

144 km

R

102 km

144 km

Page 23: Mystery Solved: Five Surprises Discovered With Megahertz ...

Transients on Voltages and Currents Confirm System Disturbance, not Secondary Wiring

Cur

rent

(A)

0200

0 Time (ms)

Volta

ge (k

V)

400

–200–400

0

800

400

–800100 150

–400

50

Page 24: Mystery Solved: Five Surprises Discovered With Megahertz ...

• Wave propagates from MID toward TMD

• Source is behind MID• Most likely at MID bus

Transients Originate Outside the Line Zone

Tim

e (μ

s)

–200

0

200

400

600

800

1000

1200

1400

1600

MID

0 100 200Distance From MID (km)

TMD

Source of transient unknown Investigation in progress

Page 25: Mystery Solved: Five Surprises Discovered With Megahertz ...

AEP Engineers Concerned About 765 kV TransientsOscillogram shows first of three records, in 15 minutes;

Second one was similarC

urre

nt (A

)

0

0 Time (ms)

Volta

ge (k

V)

0

2000

600

–2000

200 400–200

–2000

2000

Page 26: Mystery Solved: Five Surprises Discovered With Megahertz ...

First and Second Events Triggered by Disconnect Closing; Third by Breaker Closing

Reactor Breaker

Disconnect

R

39.7 kmLine Trap

16.3 km 187.4 km

Station 1

Station 2 Station 3

Station 4

Cur

rent

(A)

0

0Time (ms)

200–200

2000

1000

–2000

–1000Closing disconnecttriggered a flurry of transients.Breaker closing produced clean transients.

Page 27: Mystery Solved: Five Surprises Discovered With Megahertz ...

Here’s the Third Record…When Reactor Breaker Closed

Cur

rent

(A)

0

0 Time (ms)

Volta

ge (k

V)

0

2000

–2000

10–10

–2000

2000

1000

–1000

20

Page 28: Mystery Solved: Five Surprises Discovered With Megahertz ...

Transients From Each Event Show the Same Reflections Suggest All Events Occurred at the

Same Location

Cur

rent

(A)

–0.2 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6Time (ms)

–50

0

50

–50

0

50

Vol

tage

(kV

)

–0.2 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6Time (ms)

Reflection From Station 2

Reflection From Station 3

Page 29: Mystery Solved: Five Surprises Discovered With Megahertz ...

First and Second Events Triggered by Disconnect Closing; Third by Breaker Closing

Reactor Breaker

Disconnect

R

39.7 kmLine Trap

16.3 km 187.4 km

Station 1

Station 2 Station 3

Station 4

Cur

rent

(A)

0

0Time (ms)

200–200

2000

1000

–2000

–1000Closing disconnecttriggered a flurry of transients.Breaker closing produced clean transients.

Page 30: Mystery Solved: Five Surprises Discovered With Megahertz ...

• Lightning surges produce I0 only … no Iα or Iβ• We can locate lightning surges• Restriking launches waves in α and 0 modes• We can locate faults from the restrike waves• We can locate origin of high-voltage transients• Modes help us differentiate between lightning, faults,

restrikes, and incipient faults

MHz Sampling Reveals Details We Seldom See