JUNCTION BOX, MAXIMUM HEIGHTABOVE CEILING 2'-0".
COUPLING
PROVIDE A "KELLEM GRIP",SIZE AS REQUIRED.
DROP CORD TO BE TYPE "SO".
SIZE AS REQUIRED.
5'-0" A
BOVE
FLOO
R
CORD AND MALE CONNECTORSUPPLIED WITH EQUIPMENT
(EQUIPMENT LEAD WIRES).
CONDUIT (SIZE AS REQUIRED)SHALL BE RIGIDLY SUPPORTEDFROM STRUCTURAL STEEL TOPREVENT BOTH LATERAL ANDVERTICAL MOVEMENT.
COOLER or CEILING PANEL.
PROVIDE OPENING LARGEENOUGH FOR COUPLING,THEN SILICONE CAULK AFTERINSTALLATION.
DATE:
SCALE: NONEDRAWN:ELECTRIC DROP CORD DETAIL
MASTER SPECIFICATION DETAILESD-16
{\C4;10/9/13}
COUPLING
5'-0" A
BOVE
FLOO
R
COOLER or CEILING PANEL.
PROVIDE TWIST-LOCK NEMA CONNECTORS WITH WEATHERPROOF RATED BOOTS, AS REQUIRED FOR EQUIPMENT SERVED WITH DIFFERENT ELECTRICAL REQUIREMENTS.
TO BE FED FROM A BREAKER CAPABLE OF SIMULTANEOUSLY DISCONNECTING ALL USED POLES.
PROVIDE "SO" CORD AND APPROPRIATE NEMA TWIST-LOCK MALE CONNECTOR
PRSINGLE DUPLEX OPTION
NOTE:CORD DROP SHALL BE FIELDCOORDINATED TO OPERATE1 TO 3 CIRCUITS. PROVIDEHANDLE TIES AS NECESSARYFOR SIMULTANEOUSBREAKER DISCONNECT.REFER TO CHART BELOW
1 CIRCUIT, 1 TO 2 DEVICES:NEMA L5-30, 3 WIRE SO, (1) DUPLEX.
1 CIRCUIT 3-4 DEVICES:NEMA L5-30, 3 WIRE SO, (2) DUPLEX.
2 CIRCUIT, 1 TO 2 DEVICES:NEMA L14-30, 4 WIRE SO, (1) DUPLEXWITH TABS CUT.
2 CIRCUIT 3-4 DEVICES:NEMA L14-30, 4 WIRE SO, (2) DUPLEX,EACH TO ONE CIRCUIT.
3 CIRCUIT 3-4 DEVICES:NEMA L21-30, 5 WIRE SO, (2) DUPLEX,(1) WITH TABS CUT.
PROVIDE OPENING LARGE ENOUGH FOR COUPLING, THEN SILICONE CAULK AFTER INSTALLATION.
CONDUIT (SIZE AS REQUIRED) SHALL BE RIGIDLY SUPPORTED FROM STRUCTURAL STEEL TO PREVENT BOTH LATERAL AND VERTICAL MOVEMENT.
DROP CORD TO BE TYPE "SO". SIZE AS REQUIRED.
PROVIDE A "KELLEM GRIP", SIZE AS REQUIRED.
JUNCTION BOX, MAXIMUM HEIGHT ABOVE CEILING 2'-0".
DATE:
SCALE: NONEDRAWN:ELECTRIC DROP CORD DETAIL FOR MULTIPLE OUTLETS
ESD-16A
{\C4;10/9/13}
ORIGINAL ISSUE DATE 10/9/13
MINIMUM LENGTH ARMOREDCABLE (AC), PAINTED TO
MATCH STRUCTURE.CABLESUPPORT, SEE
TWO POINT CABLESUSPENSION.SEE
NOTENo. 1
SEE
NOTE
No. 1MINIMUM LENGTH
ARMORED CABLE (AC)PAINTED TO MATCHSTRUCTURE.
THREADED ROD SUPPORT, ADJUSTABLE
CABLE LOCK.
EXTEND CABLE UPBETWEEN JOIST FLANGES ANDLOOP OVER TOP CHORDFLANGE AND SECURE WITH
CABLE LOCK, AS INDICATED.EXTEND THREADED ROD UP
BETWEEN JOIST FLANGES AND
SECURELY ATTACHED TO TOPCHORD OF JOIST WITH NUT AND
LOCK WASHER, AS INDICATED.
Notice:HIGH BAY TYPE OF FIXTURE IS
INDICATED IN THIS ILLUSTRATION.
Notice:INDIVIDUAL or CONTINUOUS ROW of FIXTURES
ARE INDICATED IN THIS ILLUSTRATION.
Threaded Rod Cable
SEE NOTE No.
SEE NOTE No. 6.
3.
& 2.NOTE No.
SEE NOTE No. 6.
4.& 2.
Note:
1.
2.
3.
4.
FIXTURE SUPPORT AND POWER CONNECTION FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR AS REQUIRED BY GOVERNING CODES. MOUNT FIXTURES BY THREADED RODS OR CABLES.
HANG INDIVIDUALLY MOUNTED FIXTURES BY ONE POINT AT EACH END (MINIMUM) PER MANUFACTURER'S INSTRUCTIONS. ATTACHMENTS MUST BE SUPPORTED AT INTERVALS OF EVERY 6'-0", COMPLYING WITH NEC 330.30.
1/8" MINIMUM DIAMETER THREADED ROD SUPPORT (NUMBER AS NEEDED TO SUPPORT FIXTURE RUN), SECURELY ATTACH BOTH ENDS OF ROD TO FIXTURE AND TOP OF JOIST AS REQUIRED.
FOR STORE REMODEL USE FIXTURE MOUNTING SUPPORT TO MATCH EXISTING. FIXTURES TO BE LEVEL AND ALIGN WITH SURROUNDING FIXTURES. THREADED ROD MAY BE USED AT LOCATIONS WHERE FIXTURES NEED TO BE PREVENTED FROM SWAYING.ATTACHMENTS CAN BE MADE TO EITHER TOP CHORD OF JOIST OR UNISTRUT CHANNEL SPANNING JOIST, ATTACHMENT OF FIXTURES TO ROOF METAL DECKING WILL NOT BE PERMITTED.
5.
6.
ATTACH CABLE TO FIXTURE END WITH FIXTURE MOUNTING WIRE HOOKS.
ROUTE ROD AROUND JOIST WEB AS REQUIRED.
TYPICAL OUTLET BOX AND CONDUIT LOCATION.
1/16" MINIMUM DIAMETER STANDARD STEEL WIRE ROPE OR STAINLESS STEEL AIRCRAFT CABLE (NUMBER & SIZE AS NEEDED TO SUPPORT FIXTURES). SECURELY ATTACH CABLE TO JOIST AND FIXTURE.
SECURE USING ADJUSTABLE CABLE LOCK.
TYPICAL OUTLET BOX AND CONDUIT LOCATION.
DATE:
SCALE: NONEDRAWN:FIXTURE MOUNTING DETAIL
MASTER SPECIFICATION DETAILESD-51
{\C4;12/13/11}
Notes:
US1 -- WATTSTOPPER PASSIVE INFRARED OCCUPANCY SENSOR MODEL PW-200.
LightingLoadMens
Black
Red
Green
Violet
Blue
LightingLoadWomens
CommonExhaustFan
NeutralGround
Black
BlueLightingLoadFamily
Blue
GND GND GND
OCCUPANCY
SENSOR - US1
CKT1
CKT2
CKT1
CKT2
CKT1
CKT2
LOAD1
LOAD2
LightingLoadMens
Black
Red
Green
Violet
Blue
LightingLoadWomens
Blue
NeutralGround
Black
Blue
GND GND GND
CKT1
CKT2
CKT1
CKT2
CKT1
CKT2
LOAD1
LOAD2
LOAD1
LOAD2
LOAD1
LOAD2
*120V FAN
LOAD1
LOAD2
LOAD1
LOAD2
CommonExhaustFan
LightingLoadFamily
REFER TO LIGHTING PLAN REFERENCE DRAWINGS FOR LIGHT FIXTURE AND
1.
2.
OCCUPANCY
SENSOR - US1
OCCUPANCY
SENSOR - US1
OCCUPANCY
SENSOR - US1
OCCUPANCY
SENSOR - US1
OCCUPANCY
SENSOR - US1
OCCUPANCY SENSOR REQUIREMENTS.
DATE:
SCALE: NONEDRAWN:RESTROOM LIGHTING AND EXHAUST FAN CONTROLESD-25
{\C4;3/23/11}
{\C4;JFQ}
MASTER SPECIFICATION DETAIL
Mo
tio
n S
en
so
rM
otion S
ensor
No Motion
Sensor
No Motion
Sensor
Motion S
ensor
Motion S
ensor These sensors
only control themiddle cases.Motion SensorMotion S
ensor
No Motion
Sensor
No Motion
Sensor
Typical-A
Typical-B
Based on:Watt Stopper Motion Sensor Model No. FS-705.
each motion sensor control 2 cases maximum. When an
odd number of cases are in a row one motion sensor will control only one case. See Typical - B.
Motion sensors shall only be used on cases in an aisle. No motion sensors are to be placed on end caps, dairy doors, nutrition cases, etc.Motion sensors shall be mounted to one side or the other of the case joint.
Watt Stopper motion sensor kit Kit includes (1)power supply, (1) motion sensor, (1) 10' shielded cable, (1) connector and (1) splitter.
NOTES:
1.
2.
3.
4.
Refer to Kroger Installation Specifications for Watt Stopper Motion Sensor for additional installation information.5.
The Fixture Electrical Installer shall install to
Owner Supplied Items: ePRO number K-0011767.
GLASS DOOR CASE MOTION SENSOREISD-1
{\C4;3/13/12}
FRONT ELEVATION
NOTES:1. DASHED LINES INDICATE HIDDEN CONDUIT IN SHELF BACK AND BASE.
JUNCTION BOX LOCATED IN STRUCTURAL STEEL
RIGID STEEL, IMC CONDUIT FOR ELECTRICAL. PAINT CONDUIT TO MATCH COLUMNS. LOCATE CONDUIT IN THE CENTER OF SHELVING RUN OR IN LINE WITH BUILDING COLUMNS IF POSSIBLE. DO NOT LOCATE VERTICAL CONDUIT AT END OF SHELF LINE.CONDUIT SECURED TO TOP OF SHELVING UNIT.
STEEL CONDUIT, RUN BETWEEN BACK TO BACK SHELVING UNITS OR WITHIN THE VERTICAL BACK OF THE UNIT.
EMT CONDUITJUNCTION BOX LOCATED WITHIN BASE OF SHELVING UNIT DUPLEX OUTLET OR JUNCTION BOX FOR ELECTRIC CONNECTION
SHELVING ELECTRIC FROM OVERHEADEISD-2
{\C4;7/23/12}
MASTER SPECIFICATION DETAIL
MASTER SPECIFICATION DETAIL
MASTER SPECIFICATION DETAIL
WALL PANEL.
INSULATED
PREFABRICATED
DOOR
FREEZERCOOLER/
STROBE
HORN
120 VAC
AC POWER
DOOR SWITCH
REMOTE ALARM DRY CONTACTS
ALARM DELAYSELECT
PIN JUMPER
SO
LEN
OID
3A, N
/C
FAN
S30
A, N
/C
NO
TU
SE
D
DAC-55
SEE NOTE #6
N O T E S :
1. PIN JUMPER SET TO 'INSTANT'.
2. DIP 1 & 2 DOWN.
DIP 3 UP FOR REF. PRE DELAY.DIP 4 UP FOR INSTANT EMS ALARM/LOG.
3. DIP 1 UP. DIPS 2-10 DOWN. 5 MIN. DELAY.
4. ADJUSTED TO THE MIDDLE WHICH IS A 60SECOND DELAY FOR SHUTTING OFF FANSAND REF..
DAC-55 POWER & SOLENOID1/2" CONDUIT FOR 120 VAC
SEE NOTE #4
SEE NOTE #3
SEE NOTE #2
MC-1-M
SEE NOTE #1
DAC-55 DOOR MONITOR
MAGNETIC CONTACTS
5. SOLENOID AND FAN CONNECTIONS CONTROLLEDON FREEZERS AND MEAT COOLERS ONLY.
FOR EMS WIRE1/2" CONDUIT
TO RESPECTIVE REFRIGERATIONCONTROLLER
AND FAN WIRING
6. MC-1-M 20" MAX. LENGTH ARMORED CABLEINCLUDED WITH UNIT.
WALK-IN DOOR MONITOREISD-4
{\C4;12/26/13}
ORIGINAL ISSUE DATE 12/18/13MASTER SPECIFICATION DETAIL
1.
2.
3.
4.
Notes:
5.
6.
7.
8.
FOLLOW INSTRUCTIONS FROM CHECKSTAND MANUFACTURER SUPPLIED WITH POWER POLES FOR ASSEMBLY & INITIAL INSTALLATION.POWER POLE WEIGHT IS SUPPORTED BY CHECKSTAND. CUT TOP OF POWER POLE AS NECESSARY AND ATTACH TO BUILDING STRUCTURE.WHEN TOP OF POWER POLE MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH A METAL SUPPORT, SUCH AS UNISTRUT CHANNEL, ACROSS NEAREST JOISTS.SECURELY ATTACH POWER POLE TO EXISTING STRUCTURE OR NEW METAL SUPPORT. DO NOT DRILL THRU, RUN BOLTS THRU, OR SCREW INTO POLE, PREVENT SHARP EDGES WHICH COULD DAMAGE COMMUNICATION CABLES.
3/8" x 5" INSIDE LENGTH x 4" INSIDE WIDTH SQUARE U-BOLT, TO CONNECT TO SLOTTED METAL SUPPORT (UNISTRUT) CHANNEL, WITHOUT DRILLING, IF POWER POLE IS CENTERED ON A SLOT IN METAL SUPPORT (UNISTRUT) CHANNEL. DO NOT OVER TIGHTEN U-BOLT NUTS, LEAVE LOOSE ENOUGH TO PERMIT VERTICAL MOVEMENT OF ROOF STRUCTURE. SIMILAR UNISTRUT HARDWARE MAY BE USED IN LIEU OF U-BOLTS, TO SECURELY ATTACH POWER POLES.HEIGHTS INDICATED RESULT IN POSITIONING BRACKETS TO PARTIALLY COVER SOME ACCESS HOLES.
METAL SUPPORT (UNISTRUT), SQUARE U-BOLT AND ATTACHMENT HARDWARE, MC CABLE SUPPLIED AND INSTALLED BY CONTRACTOR. ALL OTHER COMPONENTS SUPPLIED BY OWNER.LANE LIGHT IS SUPPLIED WITH 10'-0" LONG CORD AND STANDARD GROUNDED PLUG. CONTRACTOR TO RUN LANE LIGHTCORD THROUGH PREDRILLED HOLE IN POWER POLE AND OUT BOTTOM OF POWER POLE TO FACTORY INSTALLEDRECEPTACLE IN CHECKSTAND BASE DESIGNATED FOR LANE LIGHT, RECEPTACLE IS CONTROLLED BY FACTORY INSTALLEDSWITCH LOCATED ON CHECKSTAND.BEFORE TIGHTENING HARDWARE ON LANE LIGHT, ADJUST TO PARTIALLY CONCEAL HOLE. INSTALL SHELVES AND MONITORBRACKET AT PREDRILLED LOCATIONS. CONTRACTOR TO RUN POWER CORD THROUGH PREDRILLED HOLES IN POWER
12. {\C256;ONE COMPARTMENT POWER POLES, LANE LIGHTS, BRACKETS AND STANDS COME FROM CHECKSTAND MANUFACTURER SUPPLIED BY OWNER INSTALLED BY CONTRACTOR.}13. {\C256;ALL HIGH VOLTAGE CONDUCTORS MUST BE WRAPPED WITH STEEL JACKETING (MC CABLE).}
{\Le-PRO NUMBERS:}Power Pole #K-0001345
Cube for Lane Light #K-0037228Express Topper #K-0037230
Light Arm Bracket With Lamp #K-0015235
ADA Topper #K-0015366 (Deactivated)
Family Friendly Topper (Fred Meyer Only) #K-0045002
Express Lane Topper (Fred Meyer Only) #K-0045000
NOTE #3
Elevation
Plan
Top
Front Right Side
POWERPOLE
POWERPOLE
POWER POLE
POWERPOLE &
Lc
METAL
SLOT INSUPPORT
Detail 'A'
JOISTS
NOTE #5
NOTENo. 5
NOTENo. 5
PRINTER PLATFORMS SUPPLIED WITH POWER POLE.STORE FLOOR
SEE NOTE No. 8
POWER POLE
LANE LIGHT & BRACKET MOUNTED TOWARD SALES AREA.
METAL SUPPORT (UNISTRUT), OPENING FACING POWER POLE.
POWER POLE LOCATION POINT. REFER TO CHECKSTAND INSTALLATION INSTRUCTIIONS.
(UNISTRUT)CHANNEL
1
JOIST GIRDER SEE DETAIL "A"METAL SUPPORT (UNISTRUT).
MONITOR BRACKET SUPPLIED WITH POWER POLE.
2'-2"3'-8"
11 1
/2"
7'-6
" A.F
.F.
Lc
1'-1 1/2"
CHECKSTAND, MODELS & ACCESSORIES VARY
ELEVATION B
Elevation B
CHECKSTAND
TELEPHONE
P.O.S.COMPONENT STAND
FIRST SECT
ION OF POW
ER POLES T
O BE {\C10;5
'-9"}
CHECKOUT POWER POLE AND LANE LIGHT INSTALLATIONESD-62
{\C4;6/5/15}
ORIGINAL ISSUE DATE 12/19/07
1.
2.
3.
4.
Notes:
NOTE #3
Plan
Top
Front Right Side
POWERPOLE
POWER
POLE
POWER POLE
POWERPOLE &
Lc
METAL
SLOT IN
5.
SUPPORT
Detail 'A'
JOISTS
NOTE #5
6.
7.
NOTENo. 5
NOTENo. 5
PRINTER PLATFORMS SUPPLIED WITH POWER POLE.STORE FLOOR
SEE NOTE No. 8
8.
POWER POLE
FOLLOW INSTRUCTIONS FROM CHECKSTAND MANUFACTURER SUPPLIED WITH POWER POLES FOR ASSEMBLY & INITIAL INSTALLATION.POWER POLE WEIGHT IS SUPPORTED BY CHECKSTAND. CUT TOP OF POWER POLE AS NECESSARY AND ATTACH TO BUILDING STRUCTURE.WHEN TOP OF POWER POLE MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH A METAL SUPPORT, SUCH AS UNISTRUT CHANNEL, ACROSS NEAREST JOISTS.SECURELY ATTACH POWER POLE TO EXISTING STRUCTURE OR NEW METAL SUPPORT. DO NOT DRILL THRU, RUN BOLTS THRU, OR SCREW INTO POLE, PREVENT SHARP EDGES WHICH COULD DAMAGE COMMUNICATION CABLES.
3/8" x 5" INSIDE LENGTH x 4" INSIDE WIDTH SQUARE U-BOLT, TO CONNECT TO SLOTTED METAL SUPPORT (UNISTRUT) CHANNEL, WITHOUT DRILLING, IF POWER POLE IS CENTERED ON A SLOT IN METAL SUPPORT (UNISTRUT) CHANNEL. DO NOT OVER TIGHTEN U-BOLT NUTS, LEAVE LOOSE ENOUGH TO PERMIT VERTICAL MOVEMENT OF ROOF STRUCTURE. SIMILAR UNISTRUT HARDWARE MAY BE USED IN LIEU OF U-BOLTS, TO SECURELY ATTACH POWER POLES.HEIGHTS INDICATED RESULT IN POSITIONING BRACKETS TO PARTIALLY COVER SOME ACCESS HOLES.
METAL SUPPORT (UNISTRUT), SQUARE U-BOLT AND ATTACHMENT HARDWARE, MC CABLE SUPPLIED AND INSTALLED BY CONTRACTOR. ALL OTHER COMPONENTS SUPPLIED BY OWNER.LANE LIGHT IS SUPPLIED WITH 10'-0" LONG CORD AND STANDARD GROUNDED PLUG. CONTRACTOR TO RUN LANE LIGHTCORD THROUGH PREDRILLED HOLE IN POWER POLE AND OUT BOTTOM OF POWER POLE TO FACTORY INSTALLEDRECEPTACLE IN CHECKSTAND BASE DESIGNATED FOR LANE LIGHT, RECEPTACLE IS CONTROLLED BY FACTORY INSTALLEDSWITCH LOCATED ON CHECKSTAND.BEFORE TIGHTENING HARDWARE ON LANE LIGHT, ADJUST TO PARTIALLY CONCEAL HOLE. INSTALL SHELVES AND MONITORBRACKET AT PREDRILLED LOCATIONS. CONTRACTOR TO RUN POWER CORD THROUGH PREDRILLED HOLES IN POWER
12. {\C256;ONE COMPARTMENT POWER POLES, LANE LIGHTS, BRACKETS AND STANDS COME FROM CHECKSTAND MANUFACTURER SUPPLIED BY OWNER INSTALLED BY CONTRACTOR.}13. {\C256;ALL HIGH VOLTAGE CONDUCTORS MUST BE WRAPPED WITH STEEL JACKETING (MC CABLE).}
LANE LIGHT & BRACKET MOUNTED TOWARD SALES AREA.
METAL SUPPORT (UNISTRUT), OPENING FACING POWER POLE.
POWER POLE LOCATION POINT. REFER TO CHECKSTAND INSTALLATION INSTRUCTIIONS.
{\Le-PRO NUMBERS:}Power Pole #K-0001345
Cube for Lane Light #K-0037228Express Topper #K-0037230
Light Arm Bracket With Lamp #K-0015235
ADA Topper #K-0015366 (Deactivated)
Family Friendly Topper (Fred Meyer Only) #K-0045002Express Lane Topper (Fred Meyer Only) #K-0045000
(UNISTRUT)CHANNEL
JOIST GIRDER SEE DETAIL "A"METAL SUPPORT (UNISTRUT).
MONITOR BRACKET SUPPLIED WITH POWER POLE.
CHECKSTAND, MODELS & ACCESSORIES VARY
2'-2"3'-8"
7'-6
" A
.F.F
.
L
c 11 1
/2"1'-1 1/2"
Elevation
7
Elevation B
CHECKSTAND
TELEPHONE
P.O.S.COMPONENT STAND
ELEV. B
FIRST SECT
ION OF POW
ER POLES T
O BE {\C10;5
'-9"}
CAROUSEL CHECKOUT POWER POLE AND LANE LIGHT INSTALLATIONESD-62B
{\C4;6/5/15}
ORIGINAL ISSUE DATE 11/21/14
1.
2.
3.
4.
Notes:
5.
6.
7.
8.
FOLLOW INSTRUCTIONS FROM CHECKSTAND MANUFACTURER SUPPLIED WITH POWER POLES FOR ASSEMBLY & INITIAL INSTALLATION.POWER POLE WEIGHT IS SUPPORTED BY CHECKSTAND. CUT TOP OF POWER POLE AS NECESSARY AND ATTACH TO BUILDING STRUCTURE.WHEN TOP OF POWER POLE MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH A METAL SUPPORT, SUCH AS UNISTRUT CHANNEL, ACROSS NEAREST JOISTS.SECURELY ATTACH POWER POLE TO EXISTING STRUCTURE OR NEW METAL SUPPORT. DO NOT DRILL THRU, RUN BOLTS THRU, OR SCREW INTO POLE, TO PREVENT SHARP EDGES WHICH COULD DAMAGE COMMUNICATION CABLES.
3/8" x 5" INSIDE LENGTH x 4" INSIDE WIDTH SQUARE U-BOLT, TO CONNECT TO SLOTTED METAL SUPPORT (UNISTRUT) CHANNEL, WITHOUT DRILLING, IF POWER POLE IS CENTERED ON A SLOT IN METAL SUPPORT (UNISTRUT) CHANNEL. DO NOT OVER TIGHTEN U-BOLT NUTS, LEAVE LOOSE ENOUGH TO PERMIT VERTICAL MOVEMENT OF ROOF STRUCTURE. SIMILAR UNISTRUT HARDWARE MAY BE USED IN LIEU OF U-BOLTS, TO SECURELY ATTACH POWER POLES.HEIGHTS INDICATED RESULT IN POSITIONING BRACKETS TO PARTIALLY COVER SOME ACCESS HOLES.
METAL SUPPORT (UNISTRUT), SQUARE U-BOLT AND ATTACHMENT HARDWARE, MC CABLE SUPPLIED AND INSTALLED BY CONTRACTOR. ALL OTHER COMPONENTS SUPPLIED BY OWNER.LANE LIGHT IS SUPPLIED WITH 10'-0" LONG CORD AND STANDARD GROUNDED PLUG. CONTRACTOR TO RUN LANE LIGHTCORD THROUGH PREDRILLED HOLE IN POWER POLE AND OUT BOTTOM OF POWER POLE TO FACTORY INSTALLEDRECEPTACLE IN CHECKSTAND BASE DESIGNATED FOR LANE LIGHT, RECEPTACLE IS CONTROLLED BY FACTORY INSTALLEDSWITCH LOCATED ON CHECKSTAND.BEFORE TIGHTENING HARDWARE ON LANE LIGHT, ADJUST TO PARTIALLY CONCEAL HOLE. INSTALL SHELVES AND MONITORBRACKET AT PREDRILLED LOCATIONS. CONTRACTOR TO RUN POWER CORD THROUGH PREDRILLED HOLES IN POWER
12. {\C256;ONE COMPARTMENT POWER POLES, LANE LIGHTS, BRACKETS AND STANDS COME FROM CHECKSTAND MANUFACTURER SUPPLIED BY OWNER INSTALLED BY CONTRACTOR.}13. {\C256;ALL HIGH VOLTAGE CONDUCTORS MUST BE WRAPPED WITH STEEL JACKETING (MC CABLE).}
{\Le-PRO NUMBERS:}
Cube for Lane Light #K-0037228Express Topper #K-0037230
Light Arm Bracket With Lamp #K-0015235
ADA Topper #K-0015366 (Deactivated)
Family Friendly Topper (Fred Meyer Only) #K-0045002
Express Lane Topper (Fred Meyer Only) #K-0045000
NOTE #3
Elevation
Plan
Top
Front Right Side
POWERPOLE
POWERPOLE
POWER POLE
POWERPOLE &
Lc
METAL
SLOT INSUPPORT
Detail 'A'
JOISTS
NOTE #5
NOTENo. 5
NOTENo. 5
STORE FLOOR
METAL SUPPORT (UNISTRUT), OPENING FACING POWER POLE.
POWER POLE LOCATION POINT. REFER TO CHECKSTAND INSTALLATION INSTRUCTIIONS.
(UNISTRUT)CHANNEL
JOIST GIRDERSEE DETAIL "A"METAL SUPPORT (UNISTRUT).
CHECKSTAND, MODELS & ACCESSORIES VARY7'-6
" A.F
.F.
2'-10"
3'-0
"10
1/2
"
5"
Lc
FIR
ST
SE
CT
ION
OF
PO
WE
R P
OLE
ST
O B
E A
FU
LL
8'-0
" S
EC
TIO
N.
PRINTER PLATFORMS SUPPLIED WITH POWER POLE.MONITOR BRACKET SUPPLIED WITH POWER POLE.
SEE NOTE No. 8
LANE LIGHT & BRACKET ONLY IF CHECKSTAND USED AT FRONT. MOUNT TOWARD SALES AREA.POWER POLE
IMAGES SHOWN ARE FOR METRO CHECKOUT - LEFT HAND. RIGHT HAND CHECKOUT MIRROR IMAGE.
Power Pole Ceiling Metro Universal #K-0052766
1
EURO - METRO CHECKOUT POWER POLE AND LANE LIGHT INSTALLATIONESD-62C
{\C4;6/5/15}
ORIGINAL ISSUE DATE 6/5/15
MASTER SPECIFICATION DETAIL MASTER SPECIFICATION DETAIL
DATE:
SCALE: NONE
DRAW
N:DATE:
SCALE: NONEDRAWN:
DATE:
SCALE: NONE
DRAW
N:DATE:
SCALE: NONE
DRAW
N:DATE:
SCALE: NONEDRAWN:
DATE:
SCALE: NONEDRAWN:
TRACK INSTALLATION MONOPOINT INSTALLATION
NOTES:
ELECTRICAL POWER SUPPLY
AIRCRAFT CABLE. SEE NOTES No. 1 & No. 3.
ELECTRICAL POWER SUPPLY MONOPOINT CANOPY ADAPTER
THREADED ROD. SEE NOTES No. 1 & No. 4.
THREADED ROD COUPLING, IF NEEDED.
EXTEND CABLE OVER JOIST FLANGES AND SECURE WITH CABLE LOCK, AS INDICATED. EXTEND THREADED ROD UP BETWEEN JOIST FLANGES AND SECURELY ATTACH TO JOIST, CONNECTION SEE DETAIL 'B'
1.
2.
3.
4.
FIXTURE SUPPORT AND POWER CONNECTION FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR AS REQUIRED BY GOVERNING CODES.THIS DETAIL IS ASSOCIATED WITH THE INSTALLATION OF TR15, TR16, TR17, TR18 AND TR19 LED TRACK LIGHT FIXTURES. HANG ELECTRIFIED TRACK FOR MULTIPLE FIXTURES WITH AIRCRAFT CABLE AND THREADED ROD FOR MONOPOINT FIXTURE INSTALLATION. THREADED ROD SHOULD BE USED TO SUPPORT ELECTRIFIED TRACK AT LOCATIONS WHERE HVAC DIFFUSERS CAN CAUSE TRACK TO SWAY.
\A1;INSTALL ELECTRIFIED TRACK WITH MIN 1/16" DIAMETER STANDARD STEEL WIRE ROPE OR STAINLESS STEEL AIRCRAFT CABLE WITH CABLE LOCK CONNECTED TO 1/4" EYE BOLT THRU FACTORY DRILLED HOLES WITH LOCK NUT WITH NYLON INSERT ON BOTTOM AND STANDARD JAMB NUT ON TOP OF THE TRACK. 4' TRACK TO BE INSTALLED BY 2 POINTS OF ATTACHMENT, 8' BY 3 POINTS AND 12' BY 4 POINTS.
LIGHT TRACK LENGTH AND HEIGHT ABOVE FLOOR VARIES PER LOCATION. REFER TO LIGHTING PLAN FOR MOUNTING HEIGHT AND LOCATIONS.\A1;WHERE MOUNTING CABLE OR THREADED ROD MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH METAL SUPPORT BETWEEN STEEL USING STEEL CHANNEL 7/8" MIN, 1" x 1" ANGLE IRON OR 3/4" IMC OR RIGID CONDUIT.
6.
5.
\A1;MONOPOINT FIXTURE TO BE HUNG BY 1/4" THREADED ROD ATTACHED TO STEEL AND JUNCTION BOX, FOR LONGER DROPS INSTALL THREADED COUPLING AS HIGH AS POSSIBLE. ATTACH TO BOTTOM CHORD OF JOIST BY EXTENDING THREADED ROD BETWEEN JOIST FLANGES AND HOLE IN JUNCTION BOX BY ATTACHING WITH LOCK NUT WITH NYLON INSERT ON TOP AND STANDARD JAMB NUT & WASHER ON BOTTOM.
SEE DETAIL 'B' FOR TYPICAL THREADED ROD CONNECTION
NYLON INSERT LOCK NUT AND WASHERJAMB NUT AND WASHER
SEE DETAIL 'A' FOR TYPICAL EYE BOLT CONNECTION
JAMB NUT
DETAIL 'A' DETAIL 'B'
JUNCTION BOX, CONNECTION SEE DETAIL 'B'
DATE:
SCALE: NONEDRAWN:LED TRACK LIGHT & MONOPOINT DETAILESD-50
{\C4;11/5/13}
NOTES:1.
2.
FIXTURE SUPPORT AND POWER CONNECTION FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR AS REQUIRED BY GOVERNING CODES.
REFER TO LIGHTING PLAN FOR MOUNTING HEIGHT AND LOCATIONS.
\A1;WHERE THREADED ROD MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH METAL SUPPORT BETWEEN STEEL USING STEEL CHANNEL 7/8" MIN, 1" x 1" ANGLE IRON OR 3/4" IMC OR RIGID CONDUIT.4.
3.
\A1;PENDANT TO BE HUNG BY 1/4" THREADED ROD ATTACHED TO STEEL AND JUNCTION BOX, FOR LONGER DROPS INSTALL THREADED COUPLING AS HIGH AS POSSIBLE. ATTACH TO BOTTOM CHORD OF JOIST BY EXTENDING THREADED ROD BETWEEN JOIST FLANGES AND HOLE IN JUNCTION BOX BY ATTACHING WITH LOCK NUT WITH NYLON INSERT ON TOP AND STANDARD JAMB NUT & WASHER ON BOTTOM.
NYLON INSERT LOCK NUT AND WASHERJAMB NUT AND WASHER
DETAIL 'B'
EXTEND THREADED ROD UP BETWEEN JOIST FLANGES AND SECURELY ATTACH TO JOIST, CONNECTION SEE DETAIL 'B'
SEE DETAIL 'B' FOR TYPICAL THREADED ROD CONNECTION THREADED ROD COUPLING, IF NEEDED.
THREADED ROD. SEE NOTE No. 2.
ELECTRICAL POWER SUPPLY
CANOPY PLATE
JUNCTION BOX
PENDANT LIGHT INSTALLATION
PENDANT. SEE NOTE No. 4.
6'-0" 6'-0" ADJUSTABLE CORD PROVIDED WITH FIXTURE
PENDANT LIGHT MOUNTING DETAILESD-50A
{\C4;12/5/13}
ORIGINAL ISSUE DATE 12/5/13
MASTER SPECIFICATION DETAIL
DATE:
SCALE: NONEDRAWN:
MASTER SPECIFICATION DETAIL
ISSUE DATE:
PROJECT NO.:
SHEET NUMBER:
NO. REVISIONS
K n o x v i l l e , T e n n e s s e e 37915phone: 865-546-9374 fax: 865-673-9028e - m a i l : [email protected]
111 E. J a c k s o n A v e n u e S u i t e "1 0 1 "
FURNISHED BY DOLLAR & EWERS ARCHITECTURE, INC.
C O P Y R I G H T
THEY ARE TO BE USED ONLY WITH RESPECT TO THIS PROJECTPROJECT AND ARE NOT TO BE USED WITH ANY OTHER
ARE AND SHALL REMAIN THE PROPERTY OF DEA, INC.
FOR EACH PARTY TO THE CONTRACT, SUCH DOCUMENTS ARETO BE RETURNED OR SUITABLY ACCOUNTED FOR TO DEA, INC.ON REQUEST AT THE COMPLETION OF THE WORK. SUBMISSIONDISTRIBUTION TO MEET OFFICIAL REGULATORY REQUIREMENTSOR FOR OTHER PURPOSES IN CONNECTION WITH THE PROJECTIS NOT TO BE CONSTRUED AS PUBLICATION IN DEROGATIONDEA'S COMMON LAW COPYRIGHT OR OTHER RESERVED RIGHTS.
PROJECT. WITH THE EXCEPTION OF ONE CONTRACT SET
C O P Y R I G H TALL DRAWINGS, SPECIFICATIONS AND COPIES THEREOF
A W
ith-in
-the-
Wal
ls R
emod
el fo
r:
KR
OG
ER S
TOR
E #U
-523
- D
ICK
SON
143
HEN
SLEE
DR
IVE,
DIC
KSO
N, T
ENN
ESSE
E 37
055
DECEMBER 16, 2020
220269 /20072
C
E E
1M
T o.N ETA FO
SMO
75 30 E
ET NNES
SE
C
R
SE
VR E D
ERE N R
AGRICULTUREXVIK
TREGI
SNG
II
ERE
E.NI N
O4
THIS DRAWING IS GENERALLY DIAGRAMMATIC AND,EXCEPT WHERE SPECIFICALLY DIMENSIONED ORDETAILED, INDICATES THE GENERAL ARRANGEMENTOF THE WORK. THE CONTRACTOR SHALL INSTALL HISWORK TO CONFORM AS NEARLY AS POSSIBLE TO THELOCATIONS AND ARRANGEMENTS SHOWN. COORDINATETHE WORK WITH ALL OTHER TRADES TO AVOID
THE EXPRESS WRITTEN AUTHORIZATION OF NORRIS &NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT
OF NORRIS & ASSOCIATES ENGINEERS INC. AND SHALLTHIS DRAWING AND IT'S CONTENTS ARE THE PROPERTY
ENGINEERS
865-584-3065FAX:
PHONE:
KNOXVILLE, TN5518 WALLWOOD ROAD
37912
865-584-3063
INC.
INTERFERENCES.
ASSOCIATES ENGINEERS INC.
ASSOCIATESNORRIS &
www.norrisengineers.com E1.3-2
ELEC
TRIC
AL
STA
ND
AR
D D
ETA
ILS
(ESD
'S)