More PV and Wind Power with Smart Meter Based Voltage Control

12
More PV and Wind Power with Smart Meter Based Voltage Control OLOF SAMUELSSON, IEA, LUND UNIVERSITY

Transcript of More PV and Wind Power with Smart Meter Based Voltage Control

Page 1: More PV and Wind Power with Smart Meter Based Voltage Control

More PV and Wind Power with Smart Meter Based Voltage ControlOLOF SAMUELSSON, IEA, LUND UNIVERSITY

Page 2: More PV and Wind Power with Smart Meter Based Voltage Control

Overvoltage from DG

• Low X/R in distribution active power affects voltage• DNO allows DG to raise LV voltage 5%• Case study with Kraftringen with three different LV feeders:

– With symmetric three-phase output, villa-roof-sized PV OK everywhere except in remote rural areas

– With unsymmetric output from DG, network capacity is limited with a factor up to 8 (eight)

• Only symmetric DG output considered in the following

Lund University/Industrial Electrical Engineering and Automation 2

Page 3: More PV and Wind Power with Smart Meter Based Voltage Control

Voltage Control Challenge

• Stay within upper and lower limits when– DG raises voltage– Load reduces voltage– Transformer tap changer raises or reduces all voltages

• How low is the lowest voltage?

Lund University/Industrial Electrical Engineering and Automation 3

Voltage reduction at maximum load

Page 4: More PV and Wind Power with Smart Meter Based Voltage Control

Smart Meter-Based Tap Changer Control

• Use voltage reading from smart customer meter– Standards define voltage limits at consumer

• If less than maximum load, substation voltage can be reduced• More room for DG until lower voltage limit is reached

Lund University/Industrial Electrical Engineering and Automation 4

Voltage reduction at actual load

Page 5: More PV and Wind Power with Smart Meter Based Voltage Control

Local Control of DG unit

• If necessary adjust voltage locally– Draw reactive power – remember loss increase– Curtail (reduce) active power

Lund University/Industrial Electrical Engineering and Automation 5

Page 6: More PV and Wind Power with Smart Meter Based Voltage Control

Case Study 1 – Simulated MV and LV

• Network data from E.ON– 40 MVA 130/20 kV infeed to 9x20 kV feeders – 1 load,

1 generation, 7 mixed– Residential and some rural LV network

• MV: 38 MW wind power and 16 MW PV, LV: 1 MW PV

Lund University/Industrial Electrical Engineering and Automation 6

Page 7: More PV and Wind Power with Smart Meter Based Voltage Control

Simulation Results

Lund University/Industrial Electrical Engineering and Automation 7

Traditional Local DG control Combined control

Page 8: More PV and Wind Power with Smart Meter Based Voltage Control

Case Study 2 – Field Test

• E.ON network– 12 MVA 50/10 kV infeed to 9x10 kV feeders– 0.8 MW WTG on 32 km feeder with 1.1 MW load

Lund University/Industrial Electrical Engineering and Automation 8

Page 9: More PV and Wind Power with Smart Meter Based Voltage Control

Field Test Results

0

5

10

15

20

25

30

Lund University/Industrial Electrical Engineering and Automation 9

% Curtailed wind power

Trad Central Combined

Page 10: More PV and Wind Power with Smart Meter Based Voltage Control

Field Test Meters

• Meters transmit values every 10 s via GPRS or GSM• Lowest voltage captured with two meters 89 % of time

Lund University/Industrial Electrical Engineering and Automation 10

Page 11: More PV and Wind Power with Smart Meter Based Voltage Control

Conclusions

• Smart Meters a resource for voltage control– Few key points need monitoring– Asynchronous update of data every 10 s works

• Control scheme can be simultaneously applied to MV and LV– No network data needed– Traditional tap changing controller is used

• DG projects need expected curtailment– Matching between load and generation central– Probability replaces worst case

• More details in Ingmar Leisse, PhD thesis 2013Lund University/Industrial Electrical Engineering and Automation 11

Page 12: More PV and Wind Power with Smart Meter Based Voltage Control