More PV and Wind Power with Smart Meter Based Voltage Control
Transcript of More PV and Wind Power with Smart Meter Based Voltage Control
More PV and Wind Power with Smart Meter Based Voltage ControlOLOF SAMUELSSON, IEA, LUND UNIVERSITY
Overvoltage from DG
• Low X/R in distribution active power affects voltage• DNO allows DG to raise LV voltage 5%• Case study with Kraftringen with three different LV feeders:
– With symmetric three-phase output, villa-roof-sized PV OK everywhere except in remote rural areas
– With unsymmetric output from DG, network capacity is limited with a factor up to 8 (eight)
• Only symmetric DG output considered in the following
Lund University/Industrial Electrical Engineering and Automation 2
Voltage Control Challenge
• Stay within upper and lower limits when– DG raises voltage– Load reduces voltage– Transformer tap changer raises or reduces all voltages
• How low is the lowest voltage?
Lund University/Industrial Electrical Engineering and Automation 3
Voltage reduction at maximum load
Smart Meter-Based Tap Changer Control
• Use voltage reading from smart customer meter– Standards define voltage limits at consumer
• If less than maximum load, substation voltage can be reduced• More room for DG until lower voltage limit is reached
Lund University/Industrial Electrical Engineering and Automation 4
Voltage reduction at actual load
Local Control of DG unit
• If necessary adjust voltage locally– Draw reactive power – remember loss increase– Curtail (reduce) active power
Lund University/Industrial Electrical Engineering and Automation 5
Case Study 1 – Simulated MV and LV
• Network data from E.ON– 40 MVA 130/20 kV infeed to 9x20 kV feeders – 1 load,
1 generation, 7 mixed– Residential and some rural LV network
• MV: 38 MW wind power and 16 MW PV, LV: 1 MW PV
Lund University/Industrial Electrical Engineering and Automation 6
Simulation Results
Lund University/Industrial Electrical Engineering and Automation 7
Traditional Local DG control Combined control
Case Study 2 – Field Test
• E.ON network– 12 MVA 50/10 kV infeed to 9x10 kV feeders– 0.8 MW WTG on 32 km feeder with 1.1 MW load
Lund University/Industrial Electrical Engineering and Automation 8
Field Test Results
0
5
10
15
20
25
30
Lund University/Industrial Electrical Engineering and Automation 9
% Curtailed wind power
Trad Central Combined
Field Test Meters
• Meters transmit values every 10 s via GPRS or GSM• Lowest voltage captured with two meters 89 % of time
Lund University/Industrial Electrical Engineering and Automation 10
Conclusions
• Smart Meters a resource for voltage control– Few key points need monitoring– Asynchronous update of data every 10 s works
• Control scheme can be simultaneously applied to MV and LV– No network data needed– Traditional tap changing controller is used
• DG projects need expected curtailment– Matching between load and generation central– Probability replaces worst case
• More details in Ingmar Leisse, PhD thesis 2013Lund University/Industrial Electrical Engineering and Automation 11