Molded Case Circuit Breakers 12-109 800 – 2500 Amperes€¦ · Molded Case Circuit Breakers 12...

4
CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog 12-109 January 2001 Molded Case Circuit Breakers 12 800 – 2500 Amperes R-Frame Vol. 1, Ref. No. [0575] 100% Rated Digitrip RMS 810 Circuit Breakers The NEC allows the breaker to be rated at 100% of its frame size in an assembly, provided that 90°C wire is applied at 75°C ampacity. Order as individual components: Breaker Frame (which includes Trip Unit) and Rating Plug. Table 12-170. 100% Rated Digitrip RMS 810 Circuit Breakers 12 1 See Table 12-171 below for prices. 2 Includes B2016RDL rear connectors. Note: Instruction Leaflet/FRED Number 29C107 for Breaker; Number 29C888 for Digitrip 810 Trip Unit; DS29170R for Dimensions/FRED 2917016 Table 12-171. 100% Rated Digitrip RMS 810 Circuit Breakers Prices Maximum Continuous Ampere Rating @ 40°C Circuit Breaker Frame Only Digitrip Rating Plug Only L – Adjustable Long Delay Pickup (I r ) with Adjustable Long Delay Time S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I 2 t or Flat Response) I – Adjustable Instantaneous Pickup G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time Delay (I 2 t or Flat Response) Rated Current (I n ) Fixed Rating Plug LI LS LSI LIG LSG LSIG Catalog Number Catalog Number 3-Pole Standard Interrupting Capacity 600V AC Rated 65 kAIC @ 480V AC 1600 CRD316T81W CRD316T83W CRD316T82W CRD316T84W CRD316T85W CRD316T86W 800 1000 1200 1600 RP6R16A080 RP6R16A100 RP6R16A120 RP6R16A160 2000 CRD320T81W CRD320T83W CRD320T82W CRD320T84W CRD320T85W CRD320T86W 1000 1200 1600 2000 RP6R20A100 RP6R20A120 RP6R20A160 RP6R20A200 3-Pole High Interrupting Capacity 600V AC Rated 100 kAIC @ 480V AC 1600 CRDC316T81W CRDC316T83W CRDC316T82W CRDC316T84W CRDC316T85W CRDC316T86W 800 1000 1200 1600 RP6R16A080 RP6R16A100 RP6R16A120 RP6R16A160 2000 CRDC320T81W CRDC320T83W CRDC320T82W CRDC320T84W CRDC320T85W CRDC320T86W 1000 1200 1600 2000 RP6R20A100 RP6R20A120 RP6R20A160 RP6R20A200 Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ CRDC316T81W CRDC316T82W CRDC316T83W CRDC316T84W CRDC316T85W 25,590. 27,460. 25,970. 28,080. 28,450. CRDC320T85W CRDC320T86W CRD316T81W CRD316T82W CRD316T83W 30,030. 31,150. 23,620. 25,480. 23,990. CRD320T83W CRD320T84W CRD320T85W CRD320T86W RP6R16A080 25,420. 27,530. 27,900. 29,390. 112. RP6R20A160 RP6R20A200 112. 112. CRDC316T86W CRDC320T81W CRDC320T82W CRDC320T83W CRDC320T84W 29,940. 27,180. 27,550. 28,670. 29,660. CRD316T84W CRD316T85W CRD316T86W CRD320T81W CRD320T82W 26,100. 26,470. 27,970. 25,040. 26,910. RP6R16A100 RP6R16A120 RP6R16A160 RP6R20A100 RP6R20A120 112. 112. 112. 112. 112. Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CB-2

Transcript of Molded Case Circuit Breakers 12-109 800 – 2500 Amperes€¦ · Molded Case Circuit Breakers 12...

CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

12-109January 2001

Molded Case Circuit Breakers

12

800 – 2500 AmperesR-Frame

Vol. 1, Ref. No. [0575]

100% Rated Digitrip RMS 810 Circuit BreakersThe NEC allows the breaker to be rated at 100% of its frame size in an assembly, provided that 90°C wire is applied at 75°C ampacity. Order as individual components: Breaker Frame (which includes Trip Unit) and Rating Plug.

Table 12-170. 100% Rated Digitrip RMS 810 Circuit Breakers 12

1 See Table 12-171 below for prices.2 Includes B2016RDL rear connectors.Note: Instruction Leaflet/FRED Number 29C107 for Breaker; Number 29C888 for Digitrip 810 Trip Unit; DS29170R for Dimensions/FRED 2917016

Table 12-171. 100% Rated Digitrip RMS 810 Circuit Breakers Prices

MaximumContinuousAmpereRating@ 40°C

Circuit Breaker Frame Only Digitrip Rating Plug Only

L – Adjustable Long Delay Pickup (Ir) with Adjustable Long Delay TimeS – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response)I – Adjustable Instantaneous Pickup G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time Delay (I2t or Flat Response)

Rated Current(In)

Fixed Rating Plug

LI LS LSI LIG LSG LSIG

Catalog Number Catalog Number

3-Pole Standard Interrupting Capacity 600V AC Rated 65 kAIC @ 480V AC1600 CRD316T81W CRD316T83W CRD316T82W CRD316T84W CRD316T85W CRD316T86W 800

100012001600

RP6R16A080RP6R16A100RP6R16A120RP6R16A160

2000 CRD320T81W CRD320T83W CRD320T82W CRD320T84W CRD320T85W CRD320T86W 1000120016002000

RP6R20A100RP6R20A120RP6R20A160RP6R20A200

3-Pole High Interrupting Capacity 600V AC Rated 100 kAIC @ 480V AC1600 CRDC316T81W CRDC316T83W CRDC316T82W CRDC316T84W CRDC316T85W CRDC316T86W 800

100012001600

RP6R16A080RP6R16A100RP6R16A120RP6R16A160

2000 CRDC320T81W CRDC320T83W CRDC320T82W CRDC320T84W CRDC320T85W CRDC320T86W 1000120016002000

RP6R20A100RP6R20A120RP6R20A160RP6R20A200

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

CRDC316T81WCRDC316T82WCRDC316T83WCRDC316T84WCRDC316T85W

25,590.27,460.25,970.28,080.28,450.

CRDC320T85WCRDC320T86WCRD316T81WCRD316T82WCRD316T83W

30,030.31,150.23,620.25,480.23,990.

CRD320T83WCRD320T84WCRD320T85WCRD320T86WRP6R16A080

25,420.27,530.27,900.29,390.

112.

RP6R20A160RP6R20A200———

112.112.

———

CRDC316T86WCRDC320T81WCRDC320T82WCRDC320T83WCRDC320T84W

29,940.27,180.27,550.28,670.29,660.

CRD316T84WCRD316T85WCRD316T86WCRD320T81WCRD320T82W

26,100.26,470.27,970.25,040.26,910.

RP6R16A100RP6R16A120RP6R16A160RP6R20A100RP6R20A120

112.112.112.112.112.

—————

—————

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CB-2

TAB1204.fm Page 109 Wednesday, October 25, 2000 9:31 PM

CAT.200.01.T.E For more information contact Cutler-Hammer at:

www.ch.cutler-hammer.com/catalog

12-97

January 2001

Molded Case Circuit Breakers

12

800 – 2500 Amperes

R-Frame

Vol. 1, Ref. No. [0563]

Contents

Description Page

Product Description

. . . . . . . .

12-97

Technical Dataand Specifications

. . . . . . . .

12-97

Dimensions/Weights

. . . . . . .

12-99

Product Selection

. . . . . . . . . .

12-99

R-Frame

Typical R-Frame Circuit Breaker

Product Description

R-Frame Circuit Breakers are avail-able as frame (which includes trip unit), rating plug and terminals.

All R-Frame circuit breakers are suitable for reverse feed use.

Technical Data and Specifications

Table 12-148. UL489/CSA Interrupting Capacity Ratings

1

1

Utilization Category A circuit breakers.

2

100% Rated breakers.

Note:

See

Page 12-98

for Trip Unit Specifications.

Table 12-149. IEC 947-2 Interrupting Capacity Ratings

3

3

Utilization Category A circuit breakers.

CircuitBreaker Type

Number of Poles

Interrupting Capacity (Symmetrical Amperes) (kA)

Volts AC (50/60 Hz)

240 277 480 600

RD 3, 4 125 — 65 50

CRD

2

3, 4 125 — 65 50

RDC 3, 4 200 — 100 65

CRDC

2

3, 4 200 — 100 65

CircuitBreakerType

Number ofPoles

Interrupting Capacity (Symmetrical Amperes) (kA)

Volts AC (50/60 Hz)

240 415 690

RDIcuIcs

3, 4135100

7050

2513

RDCIcuIcs

3, 4200100

10050

3518

TAB1204.fm Page 97 Wednesday, October 25, 2000 9:31 PM

12-98

For more information contact Cutler-Hammer at:

www.ch.cutler-hammer.com/catalog

CAT.200.01.T.E

January 2001

Molded Case Circuit Breakers

12

800 – 2500 Amperes

R-Frame

Vol. 1, Ref. No. [0564]

R-Frame Digitrip Specifications

Table 12-150. Specifications

1

Adjust by rating plug.

2

Except 2500 ampere frame is 200 – 600%.

3

Varies by frame.

4

LS/LSG only.

5

Not to exceed 1200 amperes.

6

By OPTIMizer/BIM.

7

Optional. Add suffix “R” to Catalog Number.BIM = Breaker Interface Module

(A) = GF AlarmIs = Sensor RatingIn = Rating PlugIr = Long Delay Pickup Setting x In

Trip Unit Type Digitrip RMS 310

Digitrip RMS 510

Digitrip RMS 610

Digitrip RMS 810

Digitrip RMS 910

Digitrip OPTIM 1050

RMS Sensing Yes Yes Yes Yes Yes Yes

Breaker Type

Frame R R R R R RAmpere Range 800A-2500A 800A – 2500A 800A – 2500A 800A – 2500A 800A – 2500A 800A – 2500AInterrupting Rating @ 480V 65, 100 (kA) 65, 100 (kA) 65, 100 (kA) 65, 100 (kA) 65, 100 (kA) 65, 100 (kA)

Protection

Ordering Options LS, LSG LSI, LSIG LI, LS, LSI, LIG,LSG, LSIG

LI, LS, LSI, LIG,LSG, LSIG

LI, LS, LSI, LIG,LSG, LSIG

LI, LS, LSI, LIG,LSG, LSIG

LSI(A), LISG

Fixed Rated Plug (In) Yes Yes Yes Yes Yes Yes YesOvertemperature Trip Yes Yes Yes Yes Yes Yes Yes

Long Delay Protection (L)

Adjustable Rating Plug (In) Yes Yes No No No No NoLong Delay Pickup 0.5 – 1.0 (In)

1

0.5 – 1.0 (In)

1

0.5 – 1.0 x (In) 0.5 – 1.0 x (In) 0.5 – 1.0 x (In) 0.5 – 1.0 x (In) 0.4 – 1.0 x (In)Long Delay Time I

2

t 12 Seconds 12 Seconds 2 – 24 Seconds 2 – 24 Seconds 2 – 24 Seconds 2 – 24 Seconds 2 – 24 SecondsLong Delay Time I

4

t No No No No No No 1 – 5 SecondsLong Delay Thermal Memory Yes Yes Yes Yes Yes Yes YesHigh Load Alarm No No No 0.85 x Ir 0.85 x Ir 0.85 x Ir 0.5-1.0 x Ir

Short Delay Protection (S)

Short Delay Pickup 200 – 800% x (In)

2

200 – 800% x (In)

2

200 – 600% S1&S2 x (Ir)

200 – 600% S1&S2 x (Ir)

200 – 600% S1&S2 x (Ir)

200 – 600% S1&S2 x (Ir)

150-800% x (Ir)

23

Short Delay Time I

2

t 100 mS No 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mSShort Delay Time Flat No Inst – 300 mS 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mSShort Delay Time ZoneSelective Interlocking

No No Yes Yes Yes Yes Yes

Instantaneous Protection (I)

Instantaneous Pickup No 200 – 800% x (In)

200 – 600%M1&M2 x (In)

200 – 600%M1&M2 x (In)

200 – 600%M1&M2 x (In)

200 – 600%M1&M2 x (In)

200 – 800% x (In)

3

Discriminator No No Yes

4

Yes

4

Yes

4

Yes

4

YesInstantaneous Override Yes Yes Yes Yes Yes Yes Yes

Ground Fault Protection (G)

Ground Fault Alarm

5

No No No No No No 25 – 100% x (In)Ground Fault Pickup

5

Varies by Frame

Varies by Frame

25 – 100% x (Is) 25-100% x (Is) 25 – 100% x (Is) 25 – 100% x (Is) 25 – 100% x (In)

Ground Fault Delay I

2

T No No 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mSGround Fault Delay Flat Inst – 500 mS Inst – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mSGround Fault ZoneSelective Interlocking

No No Yes Yes Yes Yes Yes

Ground Fault Thermal Memory Yes Yes Yes Yes Yes Yes Yes

System Diagnostics

Status LEDs Yes Yes Yes Yes Yes Yes YesCause of Trip LEDs No No Yes Yes Yes Yes YesMagnitude of Trip Information No No No Yes Yes Yes YesRemote Signal Contacts Yes

7

Yes

7

No Yes Yes Yes Yes

System Monitoring

Digital Display No No No Yes Yes Yes Yes

6

Current No No No Yes Yes Yes YesVoltage No No No No No Yes NoPower and Energy No No No No Yes Yes YesPower Quality — Harmonics No No No No No Yes YesPower Factor No No No No Yes (Over

Cutler-Hammer PowerNet Only)

Yes Yes

Communications

Cutler-Hammer PowerNet No No No No Yes Yes Yes

Testing

Testing Method Test Set Integral Integral Integral Integral OPTIMizer, BIM, Cutler-Hammer PowerNet

TAB1204.fm Page 98 Wednesday, October 25, 2000 9:31 PM

CAT.200.01.T.E For more information contact Cutler-Hammer at:

www.ch.cutler-hammer.com/catalog

12-99

January 2001

Molded Case Circuit Breakers

12

800 – 2500 Amperes

R-Frame

Vol. 1, Ref. No. [0565]

Dimensions/Weights

Table 12-151. Dimensions in Inches (mm)

Table 12-152. Approximate Shipping Weight, Lbs. (kg)

Product Selection

This information is presented only as an aid to understanding Catalog Numbers. It is not to be used to build Catalog Numbers for circuit breakers or trip units.

Table 12-153. Circuit Breaker/Frame Catalog Numbering System

1

For complete list of available trip types refer to

Pages 12-100

12-113

.

Number of Poles

Width Height Depth

3 15.5 (394) 16 (406) 9.75 (248)

4 20 (508) 16 (406) 9.75 (248)

BreakerType

Complete Breaker

Number of Poles

3 4

1600A

RD, CRD, RDC, CRDC 102 (46.3) 135 (61.2)

2000A

RD, RDC 102 (46.3) 135 (61.2)

CRD, CRDC 130 (59.0) 175 (79.4)

2500A

RD, RDC 135 (61.2) 182 (82.6)

R D 3 1 6 T 3 2 W

Circuit Breaker/Frame Type

RDRDCCRDCRDC

Number of Poles

3 = 3 Poles4 = 4 Poles

Circuit Breaker/Frame Ampere Rating

16 = 1600A20 = 2000A25 = 2500A

Trip Type 1

T32 = Digitrip RMS 310 LSIT53 = Digitrip RMS 510 LST65 = Digitrip RMS 610 LSGT86 = Digitrip RMS 810 LSIGT96 = Digitrip RMS 910 LSIGT106 = Digitrip OPTIM 1050 LSIGT107 = Digitrip OPTIM 1050 LSIA

Suffix

W = Without TerminalsP = 100% Protected Neutral PoleR = Ground Fault Remote

(310 Only)K = Molded Case Switch

TAB1204.fm Page 99 Wednesday, October 25, 2000 9:31 PM