Module 1 CX MV Switch Gear

78
1 Module One 06/12/22 SUBSTATION COMMISSIONING COURSE MODULE ONE MEDIUM VOLTAGE SWITCHGEAR ASSEMBLIES

Transcript of Module 1 CX MV Switch Gear

Page 1: Module 1 CX MV Switch Gear

1Module One04/11/23

SUBSTATION COMMISSIONING COURSE

MODULE ONE

MEDIUM VOLTAGESWITCHGEARASSEMBLIES

Page 2: Module 1 CX MV Switch Gear

2Module One04/11/23

INTRODUCTION

• The electrical commissioning and acceptance testing of electric power systems is essential for the energization of any electrical system for the first time.

Page 3: Module 1 CX MV Switch Gear

3Module One04/11/23

INTRODUCTION

Module One• Introduce the applicable switchgear

standards used in North America• Describe the construction aspects of

switchgear assemblies• Indentify NETA testing requirements• Perform acceptance testing

Page 4: Module 1 CX MV Switch Gear

4Module One04/11/23

INTRODUCTION

Skills from module one:• Know the major and basic parts of

switchgear assemblies• Use NETA switchgear testing section• Perform acceptance testing

procedures

Page 5: Module 1 CX MV Switch Gear

5Module One04/11/23

SWITCHGEAR STANDARDS

CANADIAN STANDARDS

• CSA Canadian Standards Association

• EEMAC Electrical Equipment Manufacturers Association of Canada

Page 6: Module 1 CX MV Switch Gear

6Module One04/11/23

SWITCHGEAR STANDARDS

NORTH AMERICAN STANDARDS

• ANSI American National Standards Institute

• IEEE Institute of Electrical and Electronics Engineers

• NEMA National Electrical Manufacturers Association

Page 7: Module 1 CX MV Switch Gear

7Module One04/11/23

SWITCHGEAR STANDARDS

INTERNATIONAL STANDARDS

• IEC International Electrotechnical Commission

Page 8: Module 1 CX MV Switch Gear

8Module One04/11/23

SWITCHGEAR STANDARDS

Page 9: Module 1 CX MV Switch Gear

9Module One04/11/23

SWITCHGEAR STANDARDS

Canadian Standard:• CSA standard

– CSA Standard C22.2 No. 31 – 2010

– Switchgear Assemblies

– Ninth edition

• Devices included:– switches;– interrupting devices;– air circuit breakers;– power circuit breakers;

and– control, metering,

protective, and regulating equipment with associated interconnections and supporting structures.

Page 10: Module 1 CX MV Switch Gear

10Module One04/11/23

SWITCHGEAR STANDARDS

Canadian Standard:• CSA standard

– CSA Standard C22.2 No. 31 – 2010

– Switchgear Assemblies

– Ninth edition

• Standard covers:– Covers construction

and design features– Nominal voltage of

46Kv or less– Components within the

assemblies must comply with CEC requirements

Page 11: Module 1 CX MV Switch Gear

11Module One04/11/23

SWITCHGEAR STANDARDS

CEC Approved Labels

• CSA• UL-C• Special Inspection

sticker

• CSA label– CSA sticker or CSA

logo on the nameplate– CSA designation

obtained by application, inspection and testing

Page 12: Module 1 CX MV Switch Gear

12Module One04/11/23

SWITCHGEAR STANDARDS

CEC Approved Labels

• CSA• UL-C• Special Inspection

sticker

• UL-C label– Equipment made in

USA– Tested by

Underwriters Laboratories to CSA standards

Page 13: Module 1 CX MV Switch Gear

13Module One04/11/23

SWITCHGEAR STANDARDS

CEC Approved Labels

• CSA• UL-C• Special Inspection

sticker

• Special Inspection Sticker– Requires special

inspection by the electrical inspector

– Requires document review

– Sticker affixed, dated and signed by the electrical inspector

Page 14: Module 1 CX MV Switch Gear

14Module One04/11/23

SWITCHGEAR STANDARDS

US Standards• IEEE C37.20.1 • IEEE C37.20.2 • IEEE C37.20.3• IEEE C37.20.4

• IEEE C37.20.1– Standard for Metal-

Enclosed Low-Voltage Power Circuit Breaker Switchgear

Page 15: Module 1 CX MV Switch Gear

15Module One04/11/23

SWITCHGEAR STANDARDS

US Standards• IEEE C37.20.1 • IEEE C37.20.2 • IEEE C37.20.3• IEEE C37.20.4

• IEEE C37.20.2– Standard for Metal-

Clad Switchgear

Page 16: Module 1 CX MV Switch Gear

16Module One04/11/23

SWITCHGEAR STANDARDS

US Standards• IEEE C37.20.1 • IEEE C37.20.2 • IEEE C37.20.3• IEEE C37.20.4

• IEEE C37.20.3– Standard for Metal-

Enclosed Interrupter Switchgear

Page 17: Module 1 CX MV Switch Gear

17Module One04/11/23

SWITCHGEAR STANDARDS

US Standards• IEEE C37.20.1 • IEEE C37.20.2 • IEEE C37.20.3• IEEE C37.20.4

• IEEE C37.20.4– Standard for Indoor

AC Switches (1kV – 38 kV) for Use in Metal Enclosed Switchgear

Page 18: Module 1 CX MV Switch Gear

18Module One04/11/23

SWITCHGEAR STANDARDS

IEC Standards• IEC Standard

62271-200

• IEC 62271-200– AC metal-enclosed

switchgear and controlgear for rated voltage above 1kV and up to and including 52kV

Note:

Comparable to the ANSI / IEEE Standard C37.20.2.

Page 19: Module 1 CX MV Switch Gear

19Module One04/11/23

SWITCHGEAR

What is Medium Voltage ?• ANSI/IEEE 1585-2002: (1 - 35 kV)• IEEE Std 1623-2004: (1 -35 kV • NECA/NEMA 600-2003: (.6 – 69 kV)• Littlefuse: (2.4 -38 Kv)

• Siemens: (1 – 38 kV) 600 volts to 69,000

Note: No true definition

Page 20: Module 1 CX MV Switch Gear

20Module One04/11/23

SWITCHGEAR

What is a MV Switchgear ?• Compartmentalized assemblies of

switching and interrupting devices • Operating from 1000V to 38 kV • Supplied from an insulated main bus

structure, along with control,

metering, protective and regulating equipment with associated

interconnections and supporting structure.

Page 21: Module 1 CX MV Switch Gear

21Module One04/11/23

SWITCHGEAR

Major Parts• Control devices• Switching and

Interrupting devices• Metering devices• Protective devices• Regulating devices• Interconnections• Supporting structure

Control Devices• Local controls

– Trip/close controls– Trip/close HMI

• Remote controls– Trip/close Interface -

Interpose– Trip/close RTU

Page 22: Module 1 CX MV Switch Gear

22Module One04/11/23

SWITCHGEAR

Major Parts• Control devices• Switching and

Interrupting devices• Metering devices• Protective devices• Regulating devices• Interconnections• Supporting structure

Switching & Interrupting devices

• Circuit breakers– Vacuum– SF6– Air-magnetic

• Switches– Load break– Isolation

Page 23: Module 1 CX MV Switch Gear

23Module One04/11/23

SWITCHGEAR

Major Parts• Control devices• Switching and

Interrupting devices• Metering devices• Protective devices• Regulating devices• Interconnections• Supporting structure

Metering Devices• CT’s and VT’s (PT’s)• Switchboard Instruments

– Volts, amps, watts, vars, PF, Hz

• Transducers• Revenue Metering

Page 24: Module 1 CX MV Switch Gear

24Module One04/11/23

SWITCHGEAR

Major Parts• Control devices• Switching and

Interrupting devices• Metering devices• Protective devices• Regulating devices• Interconnections• Supporting structure

Protective Devices• Discrete Protective Relays• Digital Relays• Overload relays

Page 25: Module 1 CX MV Switch Gear

25Module One04/11/23

SWITCHGEAR

Major Parts• Control devices• Switching and

Interrupting devices• Metering devices• Protective devices• Regulating devices• Interconnections• Supporting structure

Regulating Devices• Temperature controller• Voltage regulator function

Page 26: Module 1 CX MV Switch Gear

26Module One04/11/23

SWITCHGEAR

Major Parts• Control devices• Switching and

Interrupting devices• Metering devices• Protective devices• Regulating devices• Interconnections• Supporting structure

Interconnections• Bus-bar assemblies

Page 27: Module 1 CX MV Switch Gear

27Module One04/11/23

SWITCHGEAR

Major Parts• Control devices• Switching and

Interrupting devices• Metering devices• Protective devices• Regulating devices• Interconnections• Supporting structure

Supporting structures• Designed for structural

integrity• Support weight on

equipment• Withstand forces of

operating equipment• Seismic options• Arc flash option

Page 28: Module 1 CX MV Switch Gear

28Module One04/11/23

SWITCHGEAR

5 Vertical Section Unit 3 Vertical Section Unit

Page 29: Module 1 CX MV Switch Gear

29Module One04/11/23

SWITCHGEAR

Characteristics:• Voltage category• Current rating• Mechanical aspects• Metal-clad Vs Metal-

enclosed

Voltage category• 5 kV• 15 kV• 27 kV• 38 kV

Page 30: Module 1 CX MV Switch Gear

30Module One04/11/23

SWITCHGEAR

Characteristics:• Voltage category• Current rating• Mechanical aspects• Metal-clad Vs Metal-

enclosed

Current Rating• 1200A, 2000A, 3000A• Fan cooled for above

3000A

Page 31: Module 1 CX MV Switch Gear

31Module One04/11/23

SWITCHGEAR

Characteristics:• Voltage category• Current rating• Mechanical aspects• Metal-clad Vs Metal-

enclosed

Mechanical Aspects• Removable / drawout

circuit breakers• Insulated Main Bus

section• In / out sections• Compartmentalized• Metal barriers for vertical

structures and compartments

Page 32: Module 1 CX MV Switch Gear

32Module One04/11/23

SWITCHGEAR

Metal Enclosed Vs Metalclad

Page 33: Module 1 CX MV Switch Gear

33Module One04/11/23

SWITCHGEARApplication

example

Page 34: Module 1 CX MV Switch Gear

34Module One04/11/23

SWITCHGEAR

Basic Parts• Vertical Structure• Compartments

Vertical Structure• Width: 26”, 36” or 42”• Height: 90 to 100”• Structures are bolted together

to form continuous assy.• Front are hinged doors• Rear are removable plate or

hinged (optional)

Page 35: Module 1 CX MV Switch Gear

35Module One04/11/23

SWITCHGEAR

Basic Parts• Vertical Structure• Compartments

Page 36: Module 1 CX MV Switch Gear

36Module One04/11/23

SWITCHGEAR

Basic Parts• Vertical Structure• Compartments

Page 37: Module 1 CX MV Switch Gear

37Module One04/11/23

SWITCHGEAR

Basic Parts• Vertical Structure• Compartments

Compartments• Circuit Breakers• Main Bus• Cable Connection / Line• Low Voltage / Control• PT / Auxiliary

Page 38: Module 1 CX MV Switch Gear

38Module One04/11/23

SWITCHGEAR

Basic Parts• Compartments

A - Circuit Breakers

B - Main Bus

C - Cable / Line

D - Low Voltage / Control

E - PT / Auxiliary

Page 39: Module 1 CX MV Switch Gear

39Module One04/11/23

SWITCHGEAR

Basic Parts• CB compartment

- Enclosure

Enclosure• Top, bottom, left / right, rear• Faceplate is the front when CB

is fully racked in– The current carrying parts

are compartmentalized– Provides pri and sec

connections points• Mechanical Interlocks• Testing in the test /disconnect

Page 40: Module 1 CX MV Switch Gear

40Module One04/11/23

SWITCHGEAR

Basic Parts• CB compartment

- Enclosure

Page 41: Module 1 CX MV Switch Gear

41Module One04/11/23

SWITCHGEAR

Basic Parts• CB compartment

- Primary Electrical Connections

Primary Electrical Connections• 6 primary connecting device

– 2 per phase, line and load side

– Pressured finger clusters– Mate with stationary bus

bar connecting stabs

Page 42: Module 1 CX MV Switch Gear

42Module One04/11/23

SWITCHGEAR

Basic Parts• CB compartment

- Primary Electrical Connections

Page 43: Module 1 CX MV Switch Gear

43Module One04/11/23

SWITCHGEAR

Basic Parts• CB compartment

- Primary Electrical Connections

Page 44: Module 1 CX MV Switch Gear

44Module One04/11/23

SWITCHGEAR

Basic Parts• CB compartment

- Secondary Electrical Connections

Secondary Elect. Connections• Male to female contact plugs• Complete circuits for controls• Auto Engaged in

CONNECTED pos’n• Auto Dis-engaged is

DISCONNECTED pos’n• Manually engaged in TEST

pos’n

Page 45: Module 1 CX MV Switch Gear

45Module One04/11/23

SWITCHGEAR

Basic Parts• CB compartment

– Secondary Electrical Connections

Page 46: Module 1 CX MV Switch Gear

46Module One04/11/23

SWITCHGEAR

Basic Parts• CB compartment

– Secondary Electrical Connections

Page 47: Module 1 CX MV Switch Gear

47Module One04/11/23

SWITCHGEAR

Basic Parts• CB compartment

- Safety Interlocks

Safety Interlocks• Required by governing

standards• Incorporates mechanical and

electrical interlocks

Note:

DO NOT bypass or defeat the interlocks, they are necessary for the safe operation of the circuit breaker

Page 48: Module 1 CX MV Switch Gear

48Module One04/11/23

SWITCHGEAR

Basic Parts• CB compartment

- Extension

Rails

Extension Rails• Provide support• Allows equipment to be

withdrawn from the compartment

Page 49: Module 1 CX MV Switch Gear

49Module One04/11/23

SWITCHGEAR

Basic Parts• CB compartment

- Extension

Rails

Page 50: Module 1 CX MV Switch Gear

50Module One04/11/23

SWITCHGEAR

Basic Parts• Main Bus

Compartment

Main Bus Compartment• Houses the main bus• Buses are mounted on

insulators• Breakers connects to the main

bus via bus joints• Isolating barriers in each

vertical structure compartmentalize the main bus

Page 51: Module 1 CX MV Switch Gear

51Module One04/11/23

SWITCHGEAR

Basic Parts• Main Bus

Compartment1. Circuit Breaker

Compt2. Main Bus Compt3. Bus Bars4. CB to Bus Bar

Conn5. Primary Conn6. Cable Compt

Page 52: Module 1 CX MV Switch Gear

52Module One04/11/23

SWITCHGEAR

Basic Parts• Main Bus

Compartment

Page 53: Module 1 CX MV Switch Gear

53Module One04/11/23

SWITCHGEAR

Basic Parts• Main Bus

Compartment

Page 54: Module 1 CX MV Switch Gear

54Module One04/11/23

SWITCHGEAR

Basic Parts• Main Bus

Main Bus • Extends the length of the

assembly (typical)• Pass through insulated

opening on sides of structures• Bus are not one continuous

piece• Supported and braced• Vertical sections are

compartmentalized• Silver plate bus joints

Page 55: Module 1 CX MV Switch Gear

55Module One04/11/23

SWITCHGEAR

Basic Parts• Main Bus Ratings

Main Bus Ratings• 1200A, 2000A or 3000A• + 3000A using forced air

cooling (fans via thermostat)• Design for temperature rise

Page 56: Module 1 CX MV Switch Gear

56Module One04/11/23

SWITCHGEAR

Basic Parts• Line Compartment

Line Compartment• Rear most compartment• Bolted rear panel access• Rear doors are optional• Cable or bus duct entry area• Top or bottom entry• Also used for surge arresters

or control power transformers• Run length of vertical structure

Page 57: Module 1 CX MV Switch Gear

57Module One04/11/23

SWITCHGEAR

Basic Parts• Line

Compartment

Page 58: Module 1 CX MV Switch Gear

58Module One04/11/23

SWITCHGEAR

Basic Parts• Line

Compartment

Page 59: Module 1 CX MV Switch Gear

59Module One04/11/23

SWITCHGEAR

Basic Parts• Control

Compartment

Control Compartment• The space available between

the breaker faceplate and the front door.

• Used for mounting control devices, relays and metering

• Limited space availability• Items can be mounted on the

rear door panel or inserted in the door panel

Page 60: Module 1 CX MV Switch Gear

60Module One04/11/23

SWITCHGEAR

Basic Parts• Control

Compartment

Page 61: Module 1 CX MV Switch Gear

61Module One04/11/23

SWITCHGEAR

Basic Parts• Auxiliary

Compartment

Auxilliary Compartment• Located above or below a

breaker compartment (typical)• Can be an entire vertical

section• Often used for PT’s or CPT’s

Page 62: Module 1 CX MV Switch Gear

62Module One04/11/23

SWITCHGEAR

Basic Parts• Auxiliary

Compartment

Page 63: Module 1 CX MV Switch Gear

63Module One04/11/23

SWITCHGEAR

Basic Parts• Auxiliary

Compartment1. Drawout PT’s2. Drawout CPT’s3. Drawout Fuses4. Fixed CPT

Page 64: Module 1 CX MV Switch Gear

64Module One04/11/23

SWITCHGEAR

Installations• Indoor• Outdoor

Indoor• Classification based on

enclossure type– Nema 1, 1A, 2, 3R, 12

• Classification based of function– Arc resistant, seismic rated,

weatherproof, dust proof, drip proof, sprinkler proof

Page 65: Module 1 CX MV Switch Gear

65Module One04/11/23

SWITCHGEAR

Installations• Indoor• Outdoor

Page 66: Module 1 CX MV Switch Gear

66Module One04/11/23

SWITCHGEAR

Installations• Indoor• Outdoor

– Aisle-less– Sheltered Aisle– Common Aisle

Outdoor• Aisle-less switchgear

– Weatherproof, gasketed doors / rear panels / doors

– Heaters minimize condensation and moisture

– NEMA 3, 3R, 4 or 4X

Page 67: Module 1 CX MV Switch Gear

67Module One04/11/23

SWITCHGEAR

Installations• Outdoor

– Aisle-less– Sheltered

Aisle– Common Aisle

Page 68: Module 1 CX MV Switch Gear

68Module One04/11/23

SWITCHGEAR

Installations• Indoor• Outdoor

– Aisle-less– Sheltered Aisle– Common Aisle

Outdoor• Sheltered Aisle Switchgear

– Aisle is part of the enclosure and provided at the front

– Weatherproof gasketed door at both ends of the

– Nema 3R enclosure

– Heaters minimize condensation and moisture

Page 69: Module 1 CX MV Switch Gear

69Module One04/11/23

SWITCHGEAR

Installations• Outdoor

– Aisle-less– Sheltered

Aisle– Common Aisle

Page 70: Module 1 CX MV Switch Gear

70Module One04/11/23

SWITCHGEAR

Installations• Indoor• Outdoor

– Aisle-less– Sheltered Aisle– Common Aisle

Outdoor

Common Aisle Switchgear– As per Sheltered Aisle with

switchgear on both sides of the aisle

– Installed in 2 parts

Page 71: Module 1 CX MV Switch Gear

71Module One04/11/23

SWITCHGEAR

Installations• Outdoor

– Aisle-less– Sheltered

Aisle– Common Aisle

Page 72: Module 1 CX MV Switch Gear

72Module One04/11/23

SWITCHGEAR

Testing• Type of testing varies

upon what standards it was designed to– CSA, EEMAC– ANSI, IEEE, NEMA– IEC

Type of Tests• Design and proof test• Production test

Page 73: Module 1 CX MV Switch Gear

73Module One04/11/23

SWITCHGEAR STANDARDS

• Built and tested to a specific set of engineering standards

Page 74: Module 1 CX MV Switch Gear

74Module One04/11/23

SWITCHGEAR

Type of Testing• Design and Proof• Production

Design and Proof Testing• Short circuit testing • BIL testing • Dielectric testing • Continuous current testing • Mechanical life testing • Thermal testing • Environmental testing

Page 75: Module 1 CX MV Switch Gear

75Module One04/11/23

SWITCHGEAR

Type of Testing• Design and Proof• Production tests

– Circuit breaker– Assembled

equipment

Circuit Breaker Testing• Verification of nameplate

ratings • Control wiring check • Control wiring insulation test • Charging motor insulation test • Operation of switches, control

devices, latches and interlocks

Page 76: Module 1 CX MV Switch Gear

76Module One04/11/23

SWITCHGEAR

Type of Testing• Design and Proof• Production tests

– Circuit breaker– Assembled

equipment

Circuit Breaker Testing• Breaker operation at minimum,

maximum, and rated control voltages

• Vacuum interrupter operation and withstand tests

• Breaker contact resistance • Closing and opening timing

tests • Dielectric tests

Page 77: Module 1 CX MV Switch Gear

77Module One04/11/23

SWITCHGEAR

Type of Testing• Design and Proof• Production tests

– Circuit breaker– Assembled

equipment

Assembled Equipment Testing• Component nameplate

verification for compatible application

• Dielectric tests • Mechanical testing of all

operational parts and devices • Control wiring continuity

verification

Page 78: Module 1 CX MV Switch Gear

78Module One04/11/23

SWITCHGEAR

Type of Testing• Design and Proof• Production tests

– Circuit breaker– Assembled

equipment

Assembled Equipment Testing• Operation of all relays,

instruments, meters and other devices

• Control wiring insulation tests • Instrument transformer polarity

verification tests • Sequence of operation tests, if

applicable