Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8...

134
www.schneider-electric.com Modicon M171 Performance Logic Controller Hardware Guide 09/2015 EIO0000002030.02

Transcript of Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8...

Page 1: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

www.schneider-electric.com

Modicon M171 Performance Logic Controller

Hardware Guide

09/2015

EIO

0000

0020

30.0

2

Page 2: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

The information provided in this documentation contains general descriptions and/or technical characte-ristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.

No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Schneider Electric.

All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.

When devices are used for applications with technical safety requirements, the relevant instructions must be followed.

Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.

Failure to observe this information can result in injury or equipment damage.

Ā© 2015 Schneider Electric. All rights reserved.

2 EIO0000002030 09/2015

Page 3: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and
Page 4: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

4 EIO0000002030 09/2015

TABLE OF CONTENTS

CHAPTER 1. Introduction ...................................................................... 121.1. General description of Modicon M171 Performance ...................... 12

1.1.1. Modicon M171 Performance offer .................................................................12

CHAPTER 2. Mechanical installation ................................................... 152.1. Before Starting ............................................................................... 152.2. Disconnecting Power ..................................................................... 152.3. Programming Considerations ......................................................... 162.4. Operating Environment .................................................................. 162.5. Installation Considerations ............................................................. 162.6.ā€‚ TM171PDM27ā€‚/ā€‚TM171PBM27Rā€‚/ā€‚TM171EPRā€‚installation ..... 182.7.ā€‚ Assemblingā€‚theā€‚TM171Aā€‚Communicationā€‚Modules ............... 202.8.ā€‚ Assemblingā€‚theā€‚M171ā€‚Performanceā€‚Flushā€‚orā€‚TM171DGRPā€‚ .......... 21

2.8.1.ā€‚ Panelā€‚mounting .............................................................................................21

2.8.2.ā€‚ Accessoriesā€‚forā€‚Wallā€‚mounting ......................................................................22

CHAPTER 3. Electrical connections ..................................................... 233.1. Wiring Best Practices ..................................................................... 23

3.1.1.ā€‚ Wiringā€‚Guidelines ..........................................................................................23

3.1.2.ā€‚ Rulesā€‚forā€‚Removableā€‚Screwā€‚Terminalā€‚Block..................................................24

3.1.3.ā€‚ Protectingā€‚Outputsā€‚fromā€‚Inductiveā€‚Loadā€‚Damage .........................................25

3.1.4. Special handling considerations ....................................................................27

3.1.5.ā€‚ Analogā€‚Inputs-Probes ....................................................................................27

3.1.6. Serial connections .........................................................................................27

3.2. Wiring diagrams ............................................................................. 303.2.1. Modicon M171P wiring diagram ....................................................................30

3.2.2.ā€‚ Modiconā€‚M171EP14Rā€‚wiringā€‚diagram ...........................................................32

3.2.3.ā€‚ Examplesā€‚ofā€‚analogā€‚inputā€‚connectionā€‚(M171ā€‚Performanceā€‚only) ..................33

3.2.4.ā€‚ M171ā€‚Performanceā€‚/ā€‚M171ā€‚Displayā€‚Graphicā€‚connection ...............................37

3.2.5.ā€‚ M171ā€‚Performanceā€‚Flushā€‚TM171PFE03ā€‚andā€‚TM171PFE03HRā€‚connection .38

3.3.ā€‚ M171ā€‚Performanceā€‚protocolā€‚connectivity ....................................... 403.3.1.ā€‚ Example:ā€‚CANā€‚(Field)ā€‚networkā€‚connection ....................................................40

Page 5: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

5EIO0000002030 09/2015

3.3.2.ā€‚ Example:ā€‚CANā€‚connectionā€‚(Network) ............................................................41

3.3.3.ā€‚ Example:ā€‚RS485ā€‚connectionā€‚(Field) ..............................................................42

3.3.4.ā€‚ Example:ā€‚RS485ā€‚connectionā€‚withā€‚theā€‚Modiconā€‚M171Oā€‚network ...................43

3.4.ā€‚ M171ā€‚Performanceā€‚Flushā€‚protocolā€‚connectivity ............................. 443.4.1.ā€‚ Example:ā€‚RS485ā€‚connectionā€‚(Field) ..............................................................44

3.4.2. Example: CAN connection ............................................................................44

3.4.3.ā€‚ Example:ā€‚RS485ā€‚connectionā€‚withā€‚theā€‚Modiconā€‚M171Oā€‚network ...................45

3.4.4.ā€‚ Example:ā€‚CANā€‚networkā€‚connection ...............................................................46

3.5.ā€‚ TM171Aā€‚Communicationā€‚Modules ........................................ 473.5.1.ā€‚ Communicationā€‚Modulesā€‚compatibleā€‚withā€‚M171ā€‚andā€‚M172 ..........................47

3.5.2.ā€‚ Communicationā€‚Modulesā€‚exclusivelyā€‚compatibleā€‚withā€‚M171 .........................48

3.5.3.ā€‚ TM171ARS232 ..............................................................................................51

3.5.4.ā€‚ TM171AETHā€‚/ā€‚TM171AETHRS485 ...............................................................53

3.5.5.ā€‚ Example:ā€‚BACnetā€‚/ā€‚IP ....................................................................................54

3.5.6. TM171AMB....................................................................................................57

3.5.7.ā€‚ TM171ARS485ā€‚/ā€‚TM171AETHRS485 ...........................................................58

3.5.8. TM171ACAN .................................................................................................59

3.5.9. TM171APBUS ...............................................................................................60

3.5.10.ā€‚ TM171ALON................................................................................................61

3.6.ā€‚ Ethernetā€‚connectionā€‚(forā€‚M171ā€‚Performanceā€‚Flush) ...................... 62

CHAPTER 4. Technical data .................................................................. 644.1. General specifications .................................................................... 644.2.ā€‚ I/Oā€‚features .................................................................................... 66

4.2.1.ā€‚ M171ā€‚Performanceā€‚I/Oā€‚features ....................................................................66

4.2.2.ā€‚ M171EP14Rā€‚Performanceā€‚I/Oā€‚features .........................................................68

4.2.3.ā€‚ M171ā€‚Performanceā€‚Flushā€‚I/Oā€‚features ..........................................................69

4.3.ā€‚ Display ........................................................................................... 704.3.1.ā€‚ M171ā€‚Performanceā€‚Displayā€‚Graphicā€‚/ā€‚M171ā€‚Performanceā€‚Flushā€‚display ......70

4.4. Serials ............................................................................................ 704.4.1.ā€‚ TM171Aā€‚Communicationā€‚Module .........................................................71

4.5.ā€‚ Powerā€‚supply .................................................................................. 724.6. Mechanical dimensions .................................................................. 72

Page 6: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

6 EIO0000002030 09/2015

CHAPTER 5. M171 Performance User Interface .................................. 745.1.ā€‚ Keysā€‚andā€‚LEDs .............................................................................. 745.2. First power on ................................................................................ 755.3.ā€‚ Menu .............................................................................................. 75

5.3.1.ā€‚ Systemā€‚Menu ................................................................................................75

5.3.2.ā€‚ BIOSā€‚Configuration .......................................................................................76

5.3.3.ā€‚ BIOSā€‚I/Oā€‚Values ............................................................................................76

5.3.4.ā€‚ BIOSā€‚RTCā€‚Values ..........................................................................................77

5.3.5.ā€‚ USB-Hostā€‚Handling .......................................................................................77

CHAPTER 6. M171 Performance Display Graphic user interface ...... 826.1.ā€‚ Keysā€‚andā€‚LEDs .............................................................................. 826.2. First power on ................................................................................ 836.3.ā€‚ DIAGNOSTICSā€‚menu .................................................................... 84

6.3.1. BIOS parameters ...........................................................................................84

6.3.2.ā€‚ HMIā€‚Management ..........................................................................................84

6.4.ā€‚ Remoteā€‚interface ............................................................................ 846.4.1.ā€‚ Language ......................................................................................................84

6.4.2. ...............................................................................................................84

6.4.3.ā€‚ HMIā€‚Management ..........................................................................................85

CHAPTER 7. M171 Performance Flush user interface ........................ 867.1.ā€‚ Keysā€‚andā€‚LEDs .............................................................................. 867.2. First power on ................................................................................ 877.3.ā€‚ DIAGNOSTICā€‚menu ....................................................................... 88

7.3.1. BIOS parameters ...........................................................................................88

7.3.2.ā€‚ HMIā€‚management ..........................................................................................88

7.3.3.ā€‚ Probeā€‚values .................................................................................................88

7.3.4. Date and time ................................................................................................89

7.4.ā€‚ Remoteā€‚interface ............................................................................ 907.4.1.ā€‚ Language ......................................................................................................90

7.4.2. ...............................................................................................................90

7.4.3.ā€‚ HMIā€‚sel ..........................................................................................................90

7.4.4. COM Setting ..................................................................................................91

7.4.5.ā€‚ HMIā€‚Management ..........................................................................................91

Page 7: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

7EIO0000002030 09/2015

CHAPTER 8. Physical I/O and ports configuration ............................. 928.1.ā€‚ Analogā€‚inputs .................................................................................. 93

8.1.1.ā€‚ Analogā€‚inputsā€‚configurationā€‚forā€‚M171ā€‚Performance ......................................93

8.1.2.ā€‚ Analogā€‚inputsā€‚configurationā€‚forā€‚M171EP14R .................................................94

8.1.3.ā€‚ Analogā€‚inputsā€‚configurationā€‚forā€‚M171ā€‚Performanceā€‚Flush .............................96

8.2.ā€‚ Analogā€‚outputsā€‚configurationā€‚forā€‚M171ā€‚Performance ..................... 978.3.ā€‚ Digitalā€‚inputsā€‚configurationā€‚forā€‚M171ā€‚Performance ........................ 978.4.ā€‚ Digitalā€‚outputsā€‚configurationā€‚forā€‚M171ā€‚Performance ...................... 978.5.ā€‚ Portsā€‚configurationā€‚forā€‚M171ā€‚Performanceā€‚usingā€‚DipSwitch .......... 98

8.5.1.ā€‚ TM171PDM27ā€‚DipSwitch ............................................................................99

8.5.2.ā€‚ TM171PBM27Rā€‚DipSwitch ...........................................................................100

8.5.3.ā€‚ TM171EP27Rā€‚expansionā€‚DipSwitch ............................................................104

8.5.4.ā€‚ TM171EP14Rā€‚expansionā€‚DipSwitch ............................................................106

CHAPTER 9. Parameters ...................................................................... 1079.1. M171 Performance parameter table ............................................. 107

9.1.1.ā€‚ TM171PDM27ā€‚/ā€‚TM171PBM27Rā€‚/ā€‚TM171EP27Rā€‚parameters ...................108

9.1.2.ā€‚ M171EP14Rā€‚parameters .............................................................................. 119

9.1.3.ā€‚ M171ā€‚Performanceā€‚Flushā€‚parameters ..........................................................123

CHAPTER 10. Programming of the TM171EP14R ................................ 132

Page 8: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

8 EIO0000002030 09/2015

Important InformationReadā€‚theseā€‚instructionsā€‚carefully,ā€‚andā€‚lookā€‚atā€‚theā€‚equipmentā€‚toā€‚becomeā€‚familiarā€‚withā€‚theā€‚deviceā€‚beforeā€‚tryingā€‚toā€‚install,ā€‚operate,ā€‚service,ā€‚orā€‚maintainā€‚it.ā€‚Theā€‚followingā€‚specialā€‚messagesā€‚mayā€‚appearā€‚throughoutā€‚thisā€‚documentationā€‚orā€‚onā€‚theā€‚equipmentā€‚toā€‚informā€‚ofā€‚potentialā€‚hazardsā€‚orā€‚toā€‚callā€‚attentionā€‚toā€‚informationā€‚thatā€‚clarifiesā€‚orā€‚simplifiesā€‚aā€‚procedure.

Theā€‚additionā€‚ofā€‚thisā€‚symbolā€‚toā€‚aā€‚Dangerā€‚safetyā€‚labelā€‚indicatesā€‚thatā€‚anā€‚electricalā€‚hazardā€‚exists,ā€‚whichā€‚willā€‚resultā€‚inā€‚personalā€‚injuryā€‚ifā€‚theā€‚instructionsā€‚areā€‚notā€‚followed.

Thisā€‚isā€‚theā€‚safetyā€‚alertā€‚symbol.ā€‚Itā€‚isā€‚usedā€‚toā€‚alertā€‚youā€‚toā€‚potentialā€‚personalā€‚injuryā€‚hazards.Obeyā€‚allā€‚safetyā€‚messagesā€‚thatā€‚followā€‚thisā€‚symbolā€‚toā€‚avoidā€‚possibleā€‚injuryā€‚orā€‚death.

DANGERDANGER indicatesā€‚aā€‚hazardousā€‚situationā€‚which,ā€‚ifā€‚notā€‚avoided, will result inā€‚deathā€‚orā€‚seriousā€‚injury.

WARNINGWARNINGā€‚indicatesā€‚aā€‚hazardousā€‚situationā€‚which,ā€‚ifā€‚notā€‚avoided,ā€‚could result inā€‚deathā€‚orā€‚seriousā€‚injury.

CAUTIONCAUTIONā€‚indicatesā€‚aā€‚hazardousā€‚situationā€‚which,ā€‚ifā€‚notā€‚avoided,ā€‚could result in minorā€‚orā€‚moderateā€‚injury.

NOTICENOTICEā€‚isā€‚usedā€‚toā€‚addressā€‚practicesā€‚notā€‚relatedā€‚toā€‚physicalā€‚injury.

PLEASE NOTEElectricalā€‚equipmentā€‚shouldā€‚beā€‚installed,ā€‚operated,ā€‚serviced,ā€‚andā€‚maintainedā€‚onlyā€‚byā€‚qualifiedā€‚personnel.Noā€‚responsibilityā€‚isā€‚assumedā€‚byā€‚Schneiderā€‚Electricā€‚forā€‚anyā€‚consequencesā€‚arisingā€‚outā€‚ofā€‚theā€‚useā€‚ofā€‚thisā€‚material.Aā€‚qualifiedā€‚personā€‚isā€‚oneā€‚whoā€‚hasā€‚skillsā€‚andā€‚knowledgeā€‚relatedā€‚toā€‚theā€‚constructionā€‚andā€‚operationā€‚ofā€‚electricalā€‚equipmentā€‚andā€‚itsā€‚installation,ā€‚andā€‚hasā€‚receivedā€‚safetyā€‚trainingā€‚toā€‚recognizeā€‚andā€‚avoidā€‚theā€‚hazardsā€‚involved.

SAFETY INFORMATION

Page 9: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

9EIO0000002030 09/2015

Permitted useThisā€‚productā€‚isā€‚usedā€‚toā€‚controlā€‚HVAC-relatedā€‚andā€‚pumpingā€‚applications.

Forā€‚safetyā€‚reasons,ā€‚theā€‚deviceā€‚mustā€‚beā€‚installedā€‚andā€‚usedā€‚inā€‚accordanceā€‚withā€‚theā€‚instructionsā€‚provided.ā€‚Inā€‚particular,ā€‚partsā€‚carryingā€‚dangerousā€‚voltagesā€‚mustā€‚notā€‚beā€‚accessibleā€‚underā€‚normalā€‚conditions.

Theā€‚deviceā€‚mustā€‚beā€‚adequatelyā€‚protectedā€‚fromā€‚waterā€‚andā€‚dustā€‚withā€‚regardā€‚toā€‚theā€‚application,ā€‚andā€‚mustā€‚onlyā€‚beā€‚accessibleā€‚usingā€‚toolsā€‚(withā€‚theā€‚exceptionā€‚ofā€‚theā€‚frontā€‚panel).

Theā€‚deviceā€‚isā€‚alsoā€‚suitableā€‚forā€‚useā€‚inā€‚householdā€‚andā€‚commercialā€‚refrigerationā€‚appliancesā€‚and/orā€‚similarā€‚equipmentā€‚andā€‚hasā€‚beenā€‚testedā€‚forā€‚safetyā€‚aspectsā€‚inā€‚accordanceā€‚withā€‚theā€‚harmonizedā€‚Europeanā€‚referenceā€‚standards.

Prohibited useAnyā€‚useā€‚otherā€‚thanā€‚thatā€‚expressedā€‚aboveā€‚underā€‚Permittedā€‚useā€‚isā€‚strictlyā€‚prohibited.

Theā€‚relayā€‚contactsā€‚suppliedā€‚areā€‚ofā€‚anā€‚electromechanicalā€‚typeā€‚andā€‚subjectā€‚toā€‚wear.ā€‚Functionalā€‚safetyā€‚protectionā€‚devices,ā€‚spe-cifiedā€‚inā€‚internationalā€‚orā€‚localā€‚standards,ā€‚mustā€‚beā€‚installedā€‚externallyā€‚toā€‚thisā€‚device.

Liability and residual risksSchneiderā€‚Electricā€‚liabilityā€‚isā€‚limitedā€‚toā€‚theā€‚properā€‚andā€‚professionalā€‚useā€‚ofā€‚thisā€‚productā€‚underā€‚theā€‚guidelinesā€‚containedā€‚inā€‚theā€‚presentā€‚andā€‚otherā€‚supportingā€‚documents,ā€‚andā€‚doesā€‚notā€‚extendā€‚toā€‚damagesā€‚causedā€‚byā€‚(butā€‚notā€‚limitedā€‚to):

ā€¢ Unspecifiedā€‚installation/useā€‚and,ā€‚inā€‚particular,ā€‚inā€‚contraventionā€‚ofā€‚theā€‚safetyā€‚requirementsā€‚ofā€‚establishedā€‚legislationā€‚orā€‚specifiedā€‚inā€‚thisā€‚document;

ā€¢ Useā€‚ onā€‚ equipmentā€‚ whichā€‚ doesā€‚ notā€‚ provideā€‚ adequateā€‚ protectionā€‚ againstā€‚ electrocution,ā€‚ waterā€‚ andā€‚ dustā€‚ inā€‚ theā€‚ actualā€‚installationā€‚conditions;

ā€¢ Useā€‚onā€‚equipmentā€‚inā€‚whichā€‚dangerousā€‚componentsā€‚canā€‚beā€‚accessedā€‚withoutā€‚theā€‚useā€‚ofā€‚specificā€‚tools;ā€¢ Installation/useā€‚onā€‚equipmentā€‚whichā€‚doesā€‚notā€‚complyā€‚withā€‚establishedā€‚legislationā€‚andā€‚standards.

Disposal

Theā€‚applianceā€‚(orā€‚theā€‚product)ā€‚mustā€‚beā€‚disposedā€‚ofā€‚separatelyā€‚inā€‚complianceā€‚withā€‚theā€‚localā€‚standardsā€‚inā€‚forceā€‚onā€‚waste disposal.

Page 10: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

10 EIO0000002030 09/2015

Product Related Information

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

ā€¢ Disconnectā€‚allā€‚powerā€‚fromā€‚allā€‚equipmentā€‚includingā€‚connectedā€‚devicesā€‚priorā€‚toā€‚removingā€‚anyā€‚coversā€‚orā€‚doors,ā€‚ orā€‚installingā€‚orā€‚removingā€‚anyā€‚accessories,ā€‚hardware,ā€‚cables,ā€‚orā€‚wires.

ā€¢ Alwaysā€‚useā€‚aā€‚properlyā€‚ratedā€‚voltageā€‚sensingā€‚deviceā€‚toā€‚confirmā€‚theā€‚powerā€‚isā€‚removed.ā€¢ Replaceā€‚andā€‚secureā€‚allā€‚covers,ā€‚accessories,ā€‚hardware,ā€‚cables,ā€‚andā€‚wiresā€‚andā€‚confirmā€‚thatā€‚aā€‚properā€‚groundā€‚

connectionā€‚existsā€‚beforeā€‚applyingā€‚powerā€‚toā€‚theā€‚unit.ā€¢ Useā€‚onlyā€‚theā€‚specifiedā€‚voltageā€‚whenā€‚operatingā€‚thisā€‚equipmentā€‚andā€‚anyā€‚associatedā€‚products.

Failure to follow these instructions will result in death or serious injury.

Thisā€‚equipmentā€‚hasā€‚beenā€‚designedā€‚toā€‚operateā€‚outsideā€‚ofā€‚anyā€‚hazardousā€‚location.Onlyā€‚installā€‚thisā€‚equipmentā€‚inā€‚zonesā€‚knownā€‚toā€‚beā€‚freeā€‚ofā€‚hazardousā€‚atmosphere.

DANGERPOTENTIAL FOR EXPLOSIONInstallā€‚andā€‚useā€‚thisā€‚equipmentā€‚inā€‚non-hazardousā€‚locationsā€‚only.Failure to follow these instructions will result in death or serious injury.

WARNINGLOSS OF CONTROL

ā€¢ Theā€‚designerā€‚ofā€‚anyā€‚controlā€‚schemeā€‚mustā€‚considerā€‚theā€‚potentialā€‚failureā€‚modesā€‚ofā€‚controlā€‚pathsā€‚and,ā€‚forā€‚certainā€‚criticalā€‚controlā€‚functions,ā€‚provideā€‚aā€‚meansā€‚toā€‚achieveā€‚aā€‚safeā€‚stateā€‚duringā€‚andā€‚afterā€‚aā€‚pathā€‚failure.ā€‚Examplesā€‚ofā€‚criticalā€‚controlā€‚functionsā€‚areā€‚emergencyā€‚stopā€‚andā€‚overtravelā€‚stop,ā€‚powerā€‚outageā€‚andā€‚restart.

ā€¢ Separateā€‚orā€‚redundantā€‚controlā€‚pathsā€‚mustā€‚beā€‚providedā€‚forā€‚criticalā€‚controlā€‚functions.ā€¢ Systemā€‚controlā€‚pathsā€‚mayā€‚includeā€‚communicationā€‚links.ā€‚Considerationā€‚mustā€‚beā€‚givenā€‚toā€‚theā€‚implicationsā€‚ofā€‚unantici-

patedā€‚transmissionā€‚delaysā€‚orā€‚failuresā€‚ofā€‚theā€‚link.ā€¢ Observeā€‚allā€‚accidentā€‚preventionā€‚regulationsā€‚andā€‚localā€‚safetyā€‚guidelines.(1)

ā€¢ Eachā€‚implementationā€‚ofā€‚thisā€‚equipmentā€‚mustā€‚beā€‚individuallyā€‚andā€‚thoroughlyā€‚testedā€‚forā€‚properā€‚operationā€‚beforeā€‚beingā€‚placed into service.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

(1)ā€‚Forā€‚additionalā€‚information,ā€‚referā€‚toā€‚NEMAā€‚ICSā€‚1.1ā€‚(latestā€‚edition),ā€‚ā€œSafetyā€‚Guidelinesā€‚forā€‚theā€‚Application,ā€‚Installation,ā€‚andā€‚Maintenanceā€‚ofā€‚Solidā€‚Stateā€‚Controlā€ā€‚andā€‚toā€‚NEMAā€‚ICSā€‚7.1ā€‚(latestā€‚edition),ā€‚ā€œSafetyā€‚Standardsā€‚forā€‚Constructionā€‚andā€‚Guideā€‚forā€‚Selection,ā€‚Installationā€‚andā€‚Operationā€‚ofā€‚Adjustable-Speedā€‚Driveā€‚Systemsā€ā€‚orā€‚theirā€‚equivalentā€‚governingā€‚yourā€‚particularā€‚location.

WARNINGUNINTENDED EQUIPMENT OPERATION

ā€¢ Onlyā€‚useā€‚softwareā€‚approvedā€‚byā€‚Schneiderā€‚Electricā€‚forā€‚useā€‚withā€‚thisā€‚equipment.ā€¢ Updateā€‚yourā€‚applicationā€‚programā€‚everyā€‚timeā€‚youā€‚changeā€‚theā€‚physicalā€‚hardwareā€‚configuration.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Page 11: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

11EIO0000002030 09/2015

Document ScopeThisā€‚documentā€‚describesā€‚theā€‚Modicon M171 performance logic controllers and accessories includingā€‚installationā€‚andā€‚wiringā€‚information.ā€‚Useā€‚thisā€‚documentā€‚to:ā€¢ Installā€‚andā€‚operateā€‚yourā€‚Modicon M171 Performance logic controller.ā€¢ Connect the Modicon M171 Performance logic controllerā€‚ toā€‚ aā€‚ programmingā€‚ deviceā€‚ equippedā€‚ withā€‚

SoMachine HVAC software.ā€¢ Interface the Modicon M171 Performance logic controllerā€‚withā€‚ I/Oā€‚expansionā€‚modules,ā€‚HMIā€‚ andā€‚otherā€‚

devices.ā€¢ Familiarizeā€‚yourselfā€‚withā€‚theā€‚Modicon M171 Performance logic controllerā€‚features.NOTE:ā€‚Readā€‚andā€‚understandā€‚thisā€‚documentā€‚andā€‚theā€‚relatedā€‚documentsā€‚beforeā€‚installing,ā€‚operating,ā€‚orā€‚maintain-ingā€‚yourā€‚controller.

Validity NoteThisā€‚documentā€‚isā€‚validā€‚forā€‚SoMachine HVAC (v.2.0 or greater).Theā€‚technicalā€‚characteristicsā€‚ofā€‚theā€‚devicesā€‚describedā€‚inā€‚thisā€‚manualā€‚alsoā€‚appearā€‚online. Theā€‚characteristicsā€‚thatā€‚areā€‚presentedā€‚inā€‚thisā€‚manualā€‚shouldā€‚beā€‚theā€‚sameā€‚asā€‚thoseā€‚characteristicsā€‚thatā€‚appearā€‚online.ā€‚Inā€‚lineā€‚withā€‚ourā€‚policyā€‚ofā€‚constantā€‚improvement,ā€‚weā€‚mayā€‚reviseā€‚contentā€‚overā€‚timeā€‚toā€‚improveā€‚clarityā€‚andā€‚accuracy.ā€‚Ifā€‚youā€‚seeā€‚aā€‚differenceā€‚betweenā€‚theā€‚manualā€‚andā€‚onlineā€‚information,ā€‚useā€‚theā€‚onlineā€‚informationā€‚asā€‚yourā€‚reference.

Related Documents

Title of Documentation Reference Document Code

Modiconā€‚M172ā€‚Performanceā€‚Logicā€‚Controller,ā€‚Hardwareā€‚Userā€‚Guide EIO0000002015ā€‚(ENG)EIO0000002017ā€‚(GER)

Modiconā€‚M171ā€‚Optimizedā€‚Logicā€‚Controller,ā€‚Hardwareā€‚Userā€‚Guide EIO0000002032ā€‚(ENG)EIO0000002033ā€‚(GER)

Modiconā€‚M171ā€‚Electronicā€‚Expansionā€‚Valveā€‚Drivers,ā€‚Userā€‚Guide EIO0000002034ā€‚(ENG)EIO0000002037ā€‚(GER)

SoMachineā€‚HVACā€‚Software,ā€‚Programmingā€‚Guide EIO0000002036ā€‚(ENG)

SoMachineā€‚HVACā€‚HVAC&Rā€‚Functionā€‚Library,ā€‚Userā€‚Guide EIO0000002057ā€‚(ENG)

TM172ā€‚Performanceā€‚28/42ā€‚IOā€‚Instructionā€‚Sheet NH87740

TM171ā€‚Performanceā€‚27ā€‚IOā€‚Instructionā€‚Sheet EAV96004

TM171ā€‚Performanceā€‚Flushā€‚3ā€‚IOā€‚Instructionā€‚Sheet EAV96006

TM171ā€‚Performanceā€‚Communicationā€‚Instructionā€‚Sheet EAV960007

TM171ā€‚Performanceā€‚Displayā€‚Instructionā€‚Sheet EAV96014

Youā€‚canā€‚downloadā€‚theseā€‚technicalā€‚publicationsā€‚andā€‚otherā€‚technicalā€‚informationā€‚fromā€‚ourā€‚websiteā€‚at:www.schneider-electric.com

ABOUT THE BOOK

Page 12: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

12 EIO0000002030 09/2015

1.1. General description of Modicon M171 PerformanceThe Modicon M171P is a Schneider Electricā€‚ rangeā€‚ofā€‚ programmableā€‚ controller,ā€‚ suitableā€‚ forā€‚managingā€‚ aā€‚wideā€‚ rangeā€‚ofā€‚HVAC/Rā€‚andā€‚manyā€‚otherā€‚applications,ā€‚fromā€‚theā€‚simplestā€‚toā€‚theā€‚mostā€‚complex.

Inā€‚ thisā€‚manual,ā€‚ theā€‚photosā€‚andā€‚drawingsā€‚areā€‚ intendedā€‚toā€‚showā€‚theā€‚Modicon M171 Performance programmable controller (andā€‚otherā€‚Modiconā€‚devices)ā€‚andā€‚areā€‚forā€‚illustrativeā€‚purposesā€‚only.ā€‚Theā€‚relativeā€‚sizesā€‚andā€‚proportionsā€‚mayā€‚notā€‚beā€‚indicativeā€‚ofā€‚actualā€‚dimensionsā€‚norā€‚toā€‚scale.ā€‚Inā€‚addition,ā€‚anyā€‚wiringā€‚diagramsā€‚orā€‚electricalā€‚schematicsā€‚areā€‚toā€‚beā€‚consideredā€‚asā€‚simplifiedā€‚renditions and not literal representations thereof.

1.1.1. Modicon M171 Performance offerThe Modicon M171P offer is made of:ā€¢ M171 Performance

ā€¢ M171 Performance Display Graphic

ā€¢ M171 Performance Flush

References DescriptionTM171PDM27R M171ā€‚Performanceā€‚Displayā€‚27ā€‚I/Os,ā€‚ModbusTM171PDM27S M171ā€‚Performanceā€‚Displayā€‚27ā€‚I/Osā€‚Modbus,ā€‚2ā€‚SSRTM171PBM27R M171ā€‚Performanceā€‚Blindā€‚27ā€‚I/Os,ā€‚ModbusTM171EP27R M171ā€‚Performanceā€‚expansionā€‚27ā€‚I/OsTM171EP14R M171ā€‚Performanceā€‚expansionā€‚14ā€‚I/OsTM171DGRP M171ā€‚Performanceā€‚Displayā€‚GraphicTM171PFE03 M171ā€‚Performanceā€‚Flushā€‚3ā€‚I/Os,ā€‚MBā€‚&ā€‚BACnetā€‚TM171PFE03 M171ā€‚Performanceā€‚Flushā€‚3ā€‚I/Os,ā€‚MBā€‚&ā€‚BACnetā€‚

TM171PFE03HR M171ā€‚Performanceā€‚Flushā€‚3ā€‚I/Osā€‚RH,ā€‚MBā€‚&ā€‚BACnetā€‚

CHAPTER 1 Introduction

Page 13: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

13EIO0000002030 09/2015

M171USB

miniUSB

M171 Performance Flush

M171 Performance

M171USB

miniUSB

M171 Display Graphic

Fig. 1. Modicon M171P

M171 Performanceā€‚ deliversā€‚ performanceā€‚ inā€‚ termsā€‚ofā€‚memory,ā€‚ connectivityā€‚ andā€‚ userā€‚ interfaceā€‚ asā€‚wellā€‚ asā€‚ straightforwardā€‚programming,ā€‚maintenanceā€‚andā€‚servicing.ā€‚

Theā€‚referencesā€‚areā€‚availableā€‚asā€‚8DINā€‚rail-mountedā€‚versions,ā€‚whichā€‚savesā€‚timeā€‚inā€‚termsā€‚ofā€‚wiring.ā€‚Theā€‚8DINā€‚formatā€‚providesā€‚extraā€‚flexibilityā€‚andā€‚easyā€‚installation.

Aā€‚wideā€‚ rangeā€‚ofā€‚2DINā€‚ railā€‚mountedā€‚Communicationā€‚Modulesā€‚allowā€‚ integrationā€‚withā€‚ industrialā€‚ systems,ā€‚BMSā€‚andā€‚Ethernetā€‚networks.Lastly,ā€‚ratiometricā€‚pressureā€‚sensorsā€‚andā€‚displaysā€‚canā€‚alsoā€‚beā€‚connectedā€‚withā€‚noā€‚needā€‚forā€‚furtherā€‚serialā€‚interfaces.

M171 Performance Flush canā€‚beā€‚usedā€‚asā€‚aā€‚systemā€‚controller,ā€‚withā€‚gatewayā€‚functions;ā€‚usedā€‚inā€‚combinationā€‚withā€‚theā€‚M171 Performance and the Modicon M171Oā€‚orā€‚third-partyā€‚controllers,ā€‚itā€‚deliversā€‚performanceā€‚inā€‚termsā€‚ofā€‚memory,ā€‚connectivityā€‚andā€‚userā€‚interfaceā€‚asā€‚wellā€‚asā€‚straightforwardā€‚programming,ā€‚maintenanceā€‚andā€‚servicing.

M171 Performance Flush isā€‚designedā€‚forā€‚panelā€‚mounting,ā€‚andā€‚canā€‚alsoā€‚beā€‚wall-mountedā€‚usingā€‚aā€‚specialā€‚backplate,ā€‚availableā€‚asā€‚anā€‚accessory.

M171 Performance Flush canā€‚beā€‚usedā€‚to:ā€¢ manageā€‚aā€‚localā€‚menuā€‚createdā€‚withā€‚theā€‚TM171SW (SoMachineHVAC)ā€‚Userā€‚Interface;

ā€¢ manageā€‚upā€‚toā€‚10ā€‚remoteā€‚menus,ā€‚createdā€‚withā€‚theā€‚TM171SW (SoMachineHVAC)ā€‚Userā€‚Interfaceā€‚andā€‚uploadedā€‚fromā€‚theā€‚respective M171 Performanceā€‚devicesā€‚connectedā€‚toā€‚theā€‚network;

ā€¢ shareā€‚networkā€‚variablesā€‚(binding).

Page 14: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

14 EIO0000002030 09/2015

In association with the Modicon M171Pā€‚hardware,ā€‚thereā€‚isā€‚alsoā€‚theā€‚TM171SW (SoMachineHVAC)ā€‚developmentā€‚toolā€‚toā€‚pro-gramā€‚andā€‚customizeā€‚newā€‚programsā€‚forā€‚manyā€‚HVAC-ā€‚andā€‚pumping-relatedā€‚applications.

Theā€‚useā€‚ofā€‚severalā€‚differentā€‚programmingā€‚languagesā€‚inā€‚accordanceā€‚withā€‚IEC61131-3ā€‚regulationsā€‚makesā€‚itā€‚possibleā€‚toā€‚deve-lopā€‚newā€‚algorithmsā€‚orā€‚programs,ā€‚whichā€‚canā€‚thenā€‚beā€‚uploadedā€‚toā€‚theā€‚Modicon M171Pā€‚modulesā€‚viaā€‚PCā€‚orā€‚(onlyā€‚forā€‚DINā€‚railā€‚mountedā€‚Performanceā€‚controllers)ā€‚USBā€‚memoryā€‚key.

Web functionalities

The Modicon M171 Performance alsoā€‚featuresā€‚webā€‚functionalities,ā€‚offeringā€‚makersā€‚ofā€‚machineryā€‚andā€‚systemsā€‚integratorsā€‚remoteā€‚access.ā€‚Havingā€‚aā€‚web-basedā€‚connectionā€‚inā€‚machinesā€‚reducesā€‚supportā€‚andā€‚maintenanceā€‚byā€‚minimizingā€‚call-outā€‚char-ges.ā€‚Endā€‚usersā€‚alsoā€‚benefit,ā€‚asā€‚theyā€‚canā€‚monitorā€‚theirā€‚ownā€‚systemsā€‚bothā€‚locallyā€‚andā€‚fromā€‚distance,ā€‚usingā€‚theā€‚graphicsā€‚interfaceā€‚ofā€‚anyā€‚browser.

Mainā€‚webā€‚functionalitiesā€¢ Web-basedā€‚access.

ā€¢ Remoteā€‚readingā€‚andā€‚support.

ā€¢ Localā€‚andā€‚remoteā€‚systemā€‚control,ā€‚includingā€‚alarmsā€‚management.

ā€¢ Preventive and predictive maintenance.

ā€¢ Email alarm alerts.

Careā€‚mustā€‚beā€‚takenā€‚andā€‚provisionsā€‚madeā€‚forā€‚useā€‚ofā€‚thisā€‚productā€‚asā€‚aā€‚controlā€‚deviceā€‚toā€‚avoidā€‚inadvertentā€‚consequencesā€‚ofā€‚commandedā€‚machineā€‚operation,ā€‚controllerā€‚stateā€‚changes,ā€‚orā€‚alterationā€‚ofā€‚dataā€‚memoryā€‚orā€‚machineā€‚operatingā€‚parameters.

WARNINGUNINTENDED EQUIPMENT OPERATION

ā€¢ Configureā€‚andā€‚installā€‚theā€‚mechanismā€‚thatā€‚enablesā€‚theā€‚remoteā€‚HMIā€‚localā€‚toā€‚theā€‚machine,ā€‚soā€‚thatā€‚localā€‚controlā€‚overā€‚theā€‚machine can be maintained regardless of the remote commands sent to the application.

ā€¢ Youā€‚mustā€‚haveā€‚aā€‚completeā€‚understandingā€‚ofā€‚theā€‚applicationā€‚andā€‚theā€‚machineā€‚beforeā€‚attemptingā€‚toā€‚controlā€‚theā€‚applica-tionā€‚remotely.

ā€¢ Takeā€‚theā€‚precautionsā€‚necessaryā€‚toā€‚assureā€‚thatā€‚youā€‚areā€‚operatingā€‚remotelyā€‚onā€‚theā€‚intendedā€‚machineā€‚byā€‚havingā€‚clear,ā€‚identifyingā€‚documentationā€‚withinā€‚theā€‚applicationā€‚andā€‚itsā€‚remoteā€‚connection.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Page 15: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

15EIO0000002030 09/2015

2.1. Before StartingReadā€‚andā€‚understandā€‚thisā€‚chapterā€‚beforeā€‚beginningā€‚theā€‚installationā€‚ofā€‚yourā€‚system.ā€‚Theā€‚useā€‚andā€‚applicationā€‚ofā€‚theā€‚informa-tionā€‚containedā€‚hereinā€‚requireā€‚expertiseā€‚inā€‚theā€‚designā€‚andā€‚programmingā€‚ofā€‚automatedā€‚controlā€‚systems.ā€‚Onlyā€‚you,ā€‚theā€‚user,ā€‚machineā€‚builderā€‚orā€‚integrator,ā€‚canā€‚beā€‚awareā€‚ofā€‚allā€‚theā€‚conditionsā€‚andā€‚factorsā€‚presentā€‚duringā€‚installationā€‚andā€‚setup,ā€‚operation,ā€‚andā€‚maintenanceā€‚ofā€‚theā€‚machineā€‚orā€‚process,ā€‚andā€‚canā€‚thereforeā€‚determineā€‚theā€‚automationā€‚andā€‚associatedā€‚equipmentā€‚andā€‚theā€‚relatedā€‚safetiesā€‚andā€‚interlocksā€‚whichā€‚canā€‚beā€‚effectivelyā€‚andā€‚properlyā€‚used.ā€‚Whenā€‚selectingā€‚automationā€‚andā€‚controlā€‚equip-ment,ā€‚andā€‚anyā€‚otherā€‚relatedā€‚equipmentā€‚orā€‚software,ā€‚forā€‚aā€‚particularā€‚application,ā€‚youā€‚mustā€‚alsoā€‚considerā€‚anyā€‚applicableā€‚local,ā€‚regionalā€‚orā€‚nationalā€‚standardsā€‚and/orā€‚regulations.ā€‚Payā€‚particularā€‚attentionā€‚inā€‚conformingā€‚toā€‚anyā€‚safetyā€‚information,ā€‚differentā€‚electricalā€‚requirements,ā€‚andā€‚normativeā€‚standardsā€‚thatā€‚wouldā€‚applyā€‚toā€‚yourā€‚machineā€‚orā€‚processā€‚inā€‚theā€‚useā€‚ofā€‚thisā€‚equipment.

WARNINGREGULATORY INCOMPATIBILITYBeā€‚sureā€‚thatā€‚allā€‚equipmentā€‚appliedā€‚andā€‚systemsā€‚designedā€‚complyā€‚withā€‚allā€‚applicableā€‚local,ā€‚regionalā€‚andā€‚nationalā€‚regula-tions and standards.Failure to follow these instructions can result in death, serious injury, or equipment damage.

2.2. Disconnecting PowerAllā€‚optionsā€‚andā€‚modulesā€‚shouldā€‚beā€‚assembledā€‚andā€‚installedā€‚beforeā€‚installingā€‚theā€‚controlā€‚systemā€‚onā€‚aā€‚mountingā€‚rail,ā€‚intoā€‚aā€‚panelā€‚doorā€‚orā€‚ontoā€‚aā€‚mountingā€‚surface.ā€‚Removeā€‚theā€‚controlā€‚systemā€‚fromā€‚itsā€‚mountingā€‚rail,ā€‚mountingā€‚plateā€‚orā€‚panelā€‚beforeā€‚disassemblingā€‚theā€‚equipment.

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

ā€¢ Disconnectā€‚allā€‚powerā€‚fromā€‚allā€‚equipmentā€‚includingā€‚connectedā€‚devicesā€‚priorā€‚toā€‚removingā€‚anyā€‚coversā€‚orā€‚doors,ā€‚ orā€‚installingā€‚orā€‚removingā€‚anyā€‚accessories,ā€‚hardware,ā€‚cables,ā€‚orā€‚wires.

ā€¢ Alwaysā€‚useā€‚aā€‚properlyā€‚ratedā€‚voltageā€‚sensingā€‚deviceā€‚toā€‚confirmā€‚theā€‚powerā€‚isā€‚removed.ā€¢ Replaceā€‚andā€‚secureā€‚allā€‚covers,ā€‚accessories,ā€‚hardware,ā€‚cables,ā€‚andā€‚wiresā€‚andā€‚confirmā€‚thatā€‚aā€‚properā€‚groundā€‚

connectionā€‚existsā€‚beforeā€‚applyingā€‚powerā€‚toā€‚theā€‚unit.ā€¢ Useā€‚onlyā€‚theā€‚specifiedā€‚voltageā€‚whenā€‚operatingā€‚thisā€‚equipmentā€‚andā€‚anyā€‚associatedā€‚products.

Failure to follow these instructions will result in death or serious injury.

CHAPTER 2 Mechanical installation

Page 16: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

16 EIO0000002030 09/2015

2.3. Programming ConsiderationsTheā€‚productsā€‚describedā€‚inā€‚thisā€‚manualā€‚haveā€‚beenā€‚designedā€‚andā€‚testedā€‚usingā€‚Schneiderā€‚Electricā€‚programming,ā€‚configurationā€‚andā€‚maintenanceā€‚softwareā€‚products.ā€‚

WARNINGUNINTENDED EQUIPMENT OPERATION

ā€¢ Onlyā€‚useā€‚softwareā€‚approvedā€‚byā€‚Schneiderā€‚Electricā€‚forā€‚useā€‚withā€‚thisā€‚equipment.ā€¢ Updateā€‚yourā€‚applicationā€‚programā€‚everyā€‚timeā€‚youā€‚changeā€‚theā€‚physicalā€‚hardwareā€‚configuration.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

2.4. Operating EnvironmentThisā€‚equipmentā€‚hasā€‚beenā€‚designedā€‚toā€‚operateā€‚outsideā€‚ofā€‚anyā€‚hazardousā€‚location.ā€‚Onlyā€‚installā€‚thisā€‚equipmentā€‚inā€‚zonesā€‚knownā€‚toā€‚beā€‚freeā€‚ofā€‚aā€‚hazardousā€‚atmosphere.

DANGERPOTENTIAL FOR EXPLOSIONInstallā€‚andā€‚useā€‚thisā€‚equipmentā€‚inā€‚non-hazardousā€‚locationsā€‚only.Failure to follow these instructions will result in death or serious injury.

WARNINGUNINTENDED EQUIPMENT OPERATIONInstallā€‚andā€‚operateā€‚thisā€‚equipmentā€‚accordingā€‚toā€‚theā€‚conditionsā€‚describedā€‚inā€‚theā€‚Generalā€‚Specifications.Failure to follow these instructions can result in death, serious injury, or equipment damage.

2.5. Installation Considerations

WARNINGUNINTENDED EQUIPMENT OPERATION

ā€¢ Useā€‚appropriateā€‚safetyā€‚interlocksā€‚whereā€‚personnelā€‚and/orā€‚equipmentā€‚hazardsā€‚exist.ā€¢ Installā€‚andā€‚operateā€‚thisā€‚equipmentā€‚inā€‚anā€‚enclosureā€‚appropriatelyā€‚ratedā€‚forā€‚itsā€‚intendedā€‚environment.ā€¢ Powerā€‚lineā€‚andā€‚outputā€‚circuitsā€‚mustā€‚beā€‚wiredā€‚andā€‚fusedā€‚inā€‚complianceā€‚withā€‚localā€‚andā€‚nationalā€‚regulatoryā€‚requirementsā€‚

forā€‚theā€‚ratedā€‚currentā€‚andā€‚voltageā€‚ofā€‚theā€‚particularā€‚equipment.ā€¢ Doā€‚notā€‚useā€‚thisā€‚equipmentā€‚inā€‚safety-criticalā€‚machineā€‚functions.ā€¢ Doā€‚notā€‚disassemble,ā€‚repair,ā€‚orā€‚modifyā€‚thisā€‚equipment.ā€¢ Doā€‚notā€‚connectā€‚anyā€‚wiringā€‚toā€‚reserved,ā€‚unusedā€‚connections,ā€‚orā€‚toā€‚connectionsā€‚designatedā€‚asā€‚Noā€‚Connectionā€‚(N.C.).ā€¢ Doā€‚notā€‚mountā€‚devicesā€‚inā€‚extremelyā€‚dampā€‚and/orā€‚dirt-ladenā€‚areas.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTE:ā€‚JDYX2ā€‚orā€‚JDYX8ā€‚fuseā€‚typesā€‚areā€‚UL-recognizedā€‚andā€‚CSAā€‚approved.

Forā€‚mechanicalā€‚dimensions,ā€‚seeā€‚4.6. Mechanical dimensions on page 72.

The Modicon M171Pā€‚logicā€‚controllersā€‚areā€‚intendedā€‚forā€‚DINā€‚railā€‚mounting,ā€‚panelā€‚mountingā€‚orā€‚wallā€‚mounting.

Page 17: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

17EIO0000002030 09/2015

Careā€‚ mustā€‚ beā€‚ takenā€‚ toā€‚ avoidā€‚ damageā€‚ fromā€‚ electrostaticā€‚ sourcesā€‚ whenā€‚ handlingā€‚ thisā€‚ equipment.ā€‚ Inā€‚ particularā€‚ exposedā€‚ connectorsā€‚and,ā€‚inā€‚someā€‚cases,ā€‚exposedā€‚printedā€‚circuitā€‚boardsā€‚areā€‚vulnerableā€‚toā€‚electrostaticā€‚discharge.

WARNINGUNINTENDED EQUIPMENT OPERATION DUE TO ELECTROSTATIC DISCHARGE DAMAGE

ā€¢ Keepā€‚equipmentā€‚inā€‚theā€‚protectiveā€‚conductiveā€‚packagingā€‚untilā€‚youā€‚areā€‚readyā€‚toā€‚installā€‚theā€‚equipment.ā€‚ā€¢ Onlyā€‚installā€‚equipmentā€‚inā€‚approvedā€‚enclosuresā€‚andā€‚/ā€‚orā€‚locationsā€‚thatā€‚preventā€‚casualā€‚accessā€‚andā€‚provideā€‚electrostaticā€‚

dischargeā€‚protectionā€‚asā€‚definedā€‚byā€‚IECā€‚1000-4-2.ā€‚ā€¢ Useā€‚aā€‚conductiveā€‚wristā€‚strapā€‚orā€‚equivalentā€‚fieldā€‚forceā€‚protectiveā€‚deviceā€‚attachedā€‚toā€‚anā€‚earthā€‚groundā€‚whenā€‚handlingā€‚

sensitiveā€‚equipment.ā€‚ā€¢ Alwaysā€‚dischargeā€‚yourselfā€‚byā€‚touchingā€‚aā€‚groundedā€‚surfaceā€‚orā€‚approvedā€‚antistaticā€‚matā€‚beforeā€‚handlingā€‚theā€‚equipment.ā€‚

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Page 18: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

18 EIO0000002030 09/2015

2.6. TM171PDM27 / TM171PBM27R / TM171EPR installationTheā€‚equipmentā€‚isā€‚intendedā€‚forā€‚8DINā€‚railā€‚mountingā€‚(referā€‚toā€‚Fig. 2 on page 18 and Fig. 3 on page 19).Forā€‚DINā€‚railā€‚installation,ā€‚followā€‚theā€‚stepsā€‚describedā€‚below:1. Moveā€‚theā€‚twoā€‚clip-onā€‚locksā€‚toā€‚theirā€‚standbyā€‚positionā€‚(useā€‚aā€‚screwdriverā€‚toā€‚pressā€‚againstā€‚theā€‚relativeā€‚compartments).

2. Install the device on the DIN rail.

3. Pressā€‚onā€‚theā€‚clip-onā€‚locksā€‚toā€‚putā€‚themā€‚intoā€‚theā€‚lockedā€‚position.

4. Onceā€‚assembledā€‚onā€‚theā€‚DINā€‚rail,ā€‚theā€‚clip-onā€‚locksā€‚mustā€‚beā€‚turnedā€‚downwards.

1

mmin.

3

4

2

AM1DE200IEC/EN60715

AM1DP200 AM1ED200

10.04

35 1.38

5,5

0.22

10.04

80.30

35 1.38 35 1.38

150.59

150.59

70.28

1,50.06

1,50.06 37 1.

46

mmin.

Fig. 2. Mounting

Page 19: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

19EIO0000002030 09/2015

Fig. 3. Detailsā€‚ofā€‚clip-onā€‚locks

The M171 Performance logic controllerā€‚hasā€‚beenā€‚designedā€‚asā€‚anā€‚IP20ā€‚productā€‚andā€‚mustā€‚beā€‚installedā€‚inā€‚anā€‚enclosure.ā€‚Clearancesā€‚mustā€‚beā€‚respectedā€‚whenā€‚installingā€‚theā€‚product.Thereā€‚areā€‚3ā€‚typesā€‚ofā€‚clearancesā€‚between:ā€¢ The M171Pā€‚andā€‚allā€‚sidesā€‚ofā€‚theā€‚cabinetā€‚(includingā€‚theā€‚panelā€‚door).ā€¢ The M171Pā€‚terminalā€‚blocksā€‚andā€‚theā€‚wiringā€‚ducts.ā€‚Thisā€‚distanceā€‚reducesā€‚electromagneticā€‚

interferenceā€‚betweenā€‚theā€‚controllerā€‚andā€‚theā€‚wiringā€‚ducts.ā€¢ The M171P and other heat generating devices installed in the same cabinet.

WARNINGUNINTENDED EQUIPMENT OPERATION

ā€¢ Placeā€‚devicesā€‚dissipatingā€‚theā€‚mostā€‚heatā€‚atā€‚theā€‚topā€‚ofā€‚theā€‚cabinetā€‚andā€‚ensureā€‚adequateā€‚ventilation.ā€¢ Avoidā€‚placingā€‚thisā€‚equipmentā€‚nextā€‚toā€‚orā€‚aboveā€‚devicesā€‚thatā€‚mightā€‚causeā€‚overheating.ā€¢ Installā€‚theā€‚equipmentā€‚inā€‚aā€‚locationā€‚providingā€‚theā€‚minimumā€‚clearancesā€‚fromā€‚allā€‚adjacentā€‚structuresā€‚andā€‚equipmentā€‚asā€‚

directedā€‚inā€‚thisā€‚document.ā€¢ Installā€‚allā€‚equipmentā€‚inā€‚accordanceā€‚withā€‚theā€‚specificationsā€‚inā€‚theā€‚relatedā€‚documentation.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

20 0.79

20 0.79

803.15

401.57

401.57

20 0.79

20 0.79 mm

in.

Fig. 4. Clearances

Page 20: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

20 EIO0000002030 09/2015

2.7. Assembling the TM171A Communication ModulesCommunicationā€‚ Modulesā€‚ areā€‚ 2DINā€‚ modulesā€‚ thatā€‚ connectā€‚ toā€‚ anā€‚ M171 Performance TM171PDM27 /ā€‚ TM171PBM27R controllerā€‚(referā€‚toā€‚Fig. 5 on page 20 and Fig. 6 on page 20).To assemble TM171A to TM171PDM27 /ā€‚TM171PBM27R,ā€‚followā€‚theā€‚stepsā€‚describedā€‚below:ā€‚1. Removeā€‚ theā€‚doorā€‚ (ifā€‚present)ā€‚onā€‚ theā€‚ leftā€‚sideā€‚ofā€‚ theā€‚TM171PDM27 /ā€‚TM171PBM27R controllerā€‚byā€‚usingā€‚ fingersā€‚orā€‚aā€‚

screw-driver.

2. Anchor TM171A to the TM171PDM27 /ā€‚TM171PBM27R controller.

ā€¢ viaā€‚theā€‚plug-inā€‚connector,ā€‚behindā€‚theā€‚removableā€‚door.

ā€¢ withā€‚theā€‚fixingā€‚screwsā€‚toā€‚whichā€‚theā€‚Communicationā€‚Moduleā€‚isā€‚anchoredā€‚to.

USB

miniUSB

HOW TO ASSEMBLE HOW TO REMOVE

TM171Apppp

USB

miniUSB

USB

miniUSB

11 22

USB

miniUSB

TM171PpM27p / TM171PBM27p

Click!

Fig. 5. Assemblingā€‚theā€‚TM171Aā€‚Communicationā€‚Modules

Followā€‚theā€‚instructionsā€‚belowā€‚toā€‚installā€‚itā€‚onā€‚DINā€‚rail:1. Moveā€‚theā€‚clip-onā€‚locksā€‚(twoā€‚forā€‚TM171PDM27 /ā€‚TM171PBM27R,ā€‚oneā€‚forā€‚TM171A)ā€‚toā€‚itsā€‚standbyā€‚positionā€‚(useā€‚

aā€‚screwdriver).

2. Install TM171PDM27 /ā€‚TM171PBM27R + TM171A on the DIN rail.

3. Pressā€‚theā€‚clip-onā€‚locksā€‚whichā€‚willā€‚goā€‚toā€‚theā€‚closingā€‚position.

4. Onceā€‚theā€‚"BASEā€ā€‚isā€‚mountedā€‚onā€‚theā€‚DINā€‚rail,ā€‚theā€‚clip-onā€‚locksā€‚mustā€‚beā€‚turnedā€‚downwards.

TM171ATM171PD / TM171PB

Fig. 6. Detailsā€‚ofā€‚clip-onā€‚locks

Page 21: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

21EIO0000002030 09/2015

2.8. Assembling the M171 Performance Flush or TM171DGRP

2.8.1. Panel mountingTheā€‚equipmentā€‚isā€‚intendedā€‚forā€‚panelā€‚mountingā€‚(referā€‚toā€‚Fig. 7 on page 21).

Theā€‚followingā€‚figuresā€‚showā€‚M171 Performance Flushā€‚mounting;ā€‚sameā€‚stepsā€‚areā€‚requiredā€‚forā€‚M171 Performance Display Graphicā€‚(TM171DGRP)ā€‚mounting.

Forā€‚panelā€‚mounting,ā€‚followā€‚theā€‚stepsā€‚describedā€‚below:1. Cutā€‚fromā€‚theā€‚panelā€‚aā€‚138ā€‚xā€‚68ā€‚mmā€‚rectangularā€‚opening.

2. Drill,ā€‚atā€‚theā€‚specifiedā€‚spacing,ā€‚4ā€‚holesā€‚inā€‚theā€‚panelā€‚thatā€‚theā€‚controllerā€‚isā€‚toā€‚beā€‚mountedā€‚onā€‚orā€‚twoā€‚holes,ā€‚ofā€‚diameterā€‚2.7ā€‚mm.

3. Insertā€‚theā€‚device,ā€‚fixingā€‚itā€‚withā€‚theā€‚screws.ā€‚

4. Press the front of the M171 Performance Flush to close.

4xƘ2.74xƘ0.11

2xƘ2.72xƘ0.11

4

3

21

Or

Panel cut out

68/2.68

90/3.54138/5.43150/5.91

6xƘ2.76xƘ0.11

84/3.31

Click!

mm / in.

Fig. 7. Assemblingā€‚theā€‚M171ā€‚Performanceā€‚Displayā€‚Graphicā€‚(TM171DGRP)ā€‚orā€‚M171ā€‚Performanceā€‚Flushā€‚display

Page 22: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

22 EIO0000002030 09/2015

2.8.2. Accessories for Wall mountingTheā€‚equipmentā€‚isā€‚alsoā€‚intendedā€‚forā€‚wallā€‚mountingā€‚(referā€‚toā€‚Fig. 8 on page 22).Contact the Schneider Electricā€‚Salesā€‚Departmentā€‚forā€‚wall-mountingā€‚accessories.ā€‚

1. Drillā€‚4ā€‚holesā€‚ofā€‚diameterā€‚4.2ā€‚mmā€‚inā€‚theā€‚wallā€‚atā€‚theā€‚specifiedā€‚spacingā€‚toā€‚fixā€‚theā€‚backplate.ā€‚

2. Useā€‚theā€‚twoā€‚sideā€‚slots,ā€‚oneā€‚atā€‚theā€‚bottomā€‚andā€‚oneā€‚atā€‚theā€‚top,ā€‚underā€‚theā€‚pre-formattedā€‚removableā€‚doors,ā€‚preventingā€‚theā€‚opening of holes in the wall.

3. Insertā€‚theā€‚backplate,ā€‚fixingā€‚itā€‚withā€‚theā€‚screws.ā€‚

4. Insertā€‚theā€‚device,ā€‚fixingā€‚itā€‚withā€‚theā€‚screws.ā€‚

5. Press the front of the M171 Performance Flush to close.

4xƘ4.24xƘ0.17

5

3

2

1

4

28,5

1,12

592.32

4xƘ4.26xƘ0.17

Ethernet

592.32

1.50.0

59

833.27

903.54

1606.30

1455.70

mmin

27 1.06

57 2.2490 3.5480 3.15

R

Fig. 8. Accessoriesā€‚forā€‚Wallā€‚mounting

Reference DescriptionTM171ABKPB Whiteā€‚backplateā€‚kitā€‚forā€‚wallā€‚mounting

TM171ABKPG Blackā€‚backplateā€‚kitā€‚forā€‚wallā€‚mounting

4ā€‚backplatesā€‚perā€‚package.

Page 23: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

23EIO0000002030 09/2015

3.1. Wiring Best PracticesTheā€‚ followingā€‚ informationā€‚ describesā€‚ theā€‚wiringā€‚ guidelinesā€‚ andā€‚ associatedā€‚ bestā€‚ practicesā€‚ toā€‚ beā€‚ respectedā€‚whenā€‚ usingā€‚ theā€‚ M171 Performance Logic Controller.

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

ā€¢ Disconnectā€‚allā€‚powerā€‚fromā€‚allā€‚equipmentā€‚includingā€‚connectedā€‚devicesā€‚priorā€‚toā€‚removingā€‚anyā€‚coversā€‚orā€‚doors,ā€‚ orā€‚installingā€‚orā€‚removingā€‚anyā€‚accessories,ā€‚hardware,ā€‚cables,ā€‚orā€‚wires.

ā€¢ Alwaysā€‚useā€‚aā€‚properlyā€‚ratedā€‚voltageā€‚sensingā€‚deviceā€‚toā€‚confirmā€‚theā€‚powerā€‚isā€‚removed.ā€¢ Replaceā€‚andā€‚secureā€‚allā€‚covers,ā€‚accessories,ā€‚hardware,ā€‚cables,ā€‚andā€‚wiresā€‚andā€‚confirmā€‚thatā€‚aā€‚properā€‚groundā€‚

connectionā€‚existsā€‚beforeā€‚applyingā€‚powerā€‚toā€‚theā€‚unit.ā€¢ Useā€‚onlyā€‚theā€‚specifiedā€‚voltageā€‚whenā€‚operatingā€‚thisā€‚equipmentā€‚andā€‚anyā€‚associatedā€‚products.

Failure to follow these instructions will result in death or serious injury.

WARNINGLOSS OF CONTROL

ā€¢ Theā€‚designerā€‚ofā€‚anyā€‚controlā€‚schemeā€‚mustā€‚considerā€‚theā€‚potentialā€‚failureā€‚modesā€‚ofā€‚controlā€‚pathsā€‚and,ā€‚forā€‚certainā€‚criticalā€‚controlā€‚functions,ā€‚provideā€‚aā€‚meansā€‚toā€‚achieveā€‚aā€‚safeā€‚stateā€‚duringā€‚andā€‚afterā€‚aā€‚pathā€‚failure.ā€‚Examplesā€‚ofā€‚criticalā€‚controlā€‚functionsā€‚areā€‚emergencyā€‚stopā€‚andā€‚overtravelā€‚stop,ā€‚powerā€‚outageā€‚andā€‚restart.

ā€¢ Separateā€‚orā€‚redundantā€‚controlā€‚pathsā€‚mustā€‚beā€‚providedā€‚forā€‚criticalā€‚controlā€‚functions.ā€¢ Systemā€‚controlā€‚pathsā€‚mayā€‚includeā€‚communicationā€‚links.ā€‚Considerationā€‚mustā€‚beā€‚givenā€‚toā€‚theā€‚implicationsā€‚ofā€‚unantici-

patedā€‚transmissionā€‚delaysā€‚orā€‚failuresā€‚ofā€‚theā€‚link.ā€¢ Observeā€‚allā€‚accidentā€‚preventionā€‚regulationsā€‚andā€‚localā€‚safetyā€‚guidelines.(1)

ā€¢ Eachā€‚implementationā€‚ofā€‚thisā€‚equipmentā€‚mustā€‚beā€‚individuallyā€‚andā€‚thoroughlyā€‚testedā€‚forā€‚properā€‚operationā€‚beforeā€‚beingā€‚placed into service.

Failure to follow these instructions can result in death, serious injury, or equipment damage.(1)ā€‚Forā€‚additionalā€‚information,ā€‚referā€‚toā€‚NEMAā€‚ICSā€‚1.1ā€‚(latestā€‚edition),ā€‚ā€œSafetyā€‚Guidelinesā€‚forā€‚theā€‚Application,ā€‚Installation,ā€‚andā€‚Maintenanceā€‚ofā€‚Solidā€‚Stateā€‚Controlā€ā€‚andā€‚toā€‚NEMAā€‚ICSā€‚7.1ā€‚(latestā€‚edition),ā€‚ā€œSafetyā€‚Standardsā€‚forā€‚Constructionā€‚andā€‚Guideā€‚forā€‚Selection,ā€‚Installationā€‚andā€‚Operationā€‚ofā€‚Adjustable-Speedā€‚Driveā€‚Systemsā€ā€‚orā€‚theirā€‚equivalentā€‚governingā€‚yourā€‚particularā€‚location.

3.1.1. Wiring Guidelines

Theā€‚followingā€‚rulesā€‚mustā€‚beā€‚appliedā€‚whenā€‚wiringā€‚aā€‚M171 Performance logic controllers:

ā€¢ I/Oā€‚andā€‚communicationā€‚wiringā€‚mustā€‚beā€‚keptā€‚separateā€‚fromā€‚theā€‚powerā€‚wiring.ā€‚Routeā€‚theseā€‚twoā€‚typesā€‚ofā€‚wiringā€‚inā€‚separateā€‚cableā€‚ducting.

ā€¢ Verifyā€‚thatā€‚theā€‚operatingā€‚conditionsā€‚andā€‚environmentā€‚areā€‚withinā€‚theā€‚specificationā€‚values.

ā€¢ Useā€‚properā€‚wireā€‚sizesā€‚toā€‚meetā€‚voltageā€‚andā€‚currentā€‚requirements.

ā€¢ Useā€‚copperā€‚conductorsā€‚(required).

ā€¢ Useā€‚twistedā€‚pair,ā€‚shieldedā€‚cablesā€‚forā€‚analog,ā€‚and/orā€‚fastā€‚I/O.

ā€¢ Useā€‚twistedā€‚pair,ā€‚shieldedā€‚cablesā€‚forā€‚networks,ā€‚andā€‚fieldbus.

CHAPTER 3 Electrical connections

Page 24: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

24 EIO0000002030 09/2015

Useā€‚shielded,ā€‚properlyā€‚groundedā€‚cablesā€‚forā€‚allā€‚analogā€‚andā€‚high-speedā€‚inputsā€‚orā€‚outputsā€‚andā€‚communicationā€‚connections.ā€‚Ifā€‚youā€‚doā€‚notā€‚useā€‚shieldedā€‚cableā€‚forā€‚theseā€‚connections,ā€‚electromagneticā€‚interferenceā€‚canā€‚causeā€‚signalā€‚degradation.ā€‚Degradedā€‚signalsā€‚canā€‚causeā€‚theā€‚controllerā€‚orā€‚attachedā€‚modulesā€‚andā€‚equipmentā€‚toā€‚performā€‚inā€‚anā€‚unintendedā€‚manner.

WARNINGUNINTENDED EQUIPMENT OPERATION

ā€¢ Useā€‚shieldedā€‚cablesā€‚forā€‚allā€‚fastā€‚I/O,ā€‚analogā€‚I/Oā€‚andā€‚communicationā€‚signals.ā€¢ Groundā€‚cableā€‚shieldsā€‚forā€‚allā€‚analogā€‚I/O,ā€‚fastā€‚I/Oā€‚andā€‚communicationā€‚signalsā€‚atā€‚aā€‚singleā€‚pointā€‚(1).ā€¢ Routeā€‚communicationā€‚andā€‚I/Oā€‚cablesā€‚separatelyā€‚fromā€‚powerā€‚cables.ā€¢ Makeā€‚connectionsā€‚asā€‚shortā€‚asā€‚possibleā€‚andā€‚doā€‚notā€‚windā€‚themā€‚aroundā€‚electricallyā€‚connectedā€‚parts.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

(1)ā€‚Multipointā€‚groundingā€‚ isā€‚permissibleā€‚ ifā€‚connectionsā€‚areā€‚madeā€‚toā€‚anā€‚equipotentialā€‚groundā€‚planeā€‚dimensionedā€‚toā€‚helpā€‚avoidā€‚cableā€‚shieldā€‚damageā€‚inā€‚theā€‚eventā€‚ofā€‚powerā€‚systemā€‚short-circuitā€‚currents.

NOTE:ā€‚Surfaceā€‚ temperaturesā€‚mayā€‚exceedā€‚60ā€‚ Ā°C.ā€‚Routeā€‚primaryā€‚wiringā€‚ (wiresā€‚connectedā€‚ toā€‚powerā€‚mains)ā€‚separatelyā€‚andā€‚apartā€‚fromā€‚secondaryā€‚wiringā€‚(extraā€‚lowā€‚voltageā€‚wiringā€‚comingā€‚fromā€‚interveningā€‚powerā€‚sources).ā€‚Ifā€‚thatā€‚isā€‚notā€‚possible,ā€‚doubleā€‚insulationā€‚isā€‚requiredā€‚suchā€‚asā€‚conduitā€‚orā€‚cableā€‚gains.

3.1.2. Rules for Removable Screw Terminal BlockTheā€‚followingā€‚tableā€‚presentsā€‚theā€‚cableā€‚typesā€‚andā€‚wireā€‚sizesā€‚forā€‚a 5.08 or 5.00 pitchā€‚removableā€‚screwā€‚terminalā€‚block:

Ƙ 3,5 mm (0.14 in.)

mm2

AWG0.2ā€¦2.524ā€¦14

0.2ā€¦2.524ā€¦14

0.25ā€¦2.522...14

2 x 0.25ā€¦12 x 22ā€¦18

2 x 0.2ā€¦1.52 x 24ā€¦16

2 x 0.2ā€¦12 x 24ā€¦18

2 x 0.5...1.52 x 20...16

mmin.

70.28

C0.5...0.64.42...5.31

Nā€¢mlb-in

0.25ā€¦2.522...14

Fig. 9. Pitchā€‚5.08ā€‚mmā€‚(0.20ā€‚in.)ā€‚orā€‚5.00ā€‚mmā€‚(0.197ā€‚in.)ā€‚ā€‚

Theā€‚followingā€‚tableā€‚presentsā€‚theā€‚cableā€‚typesā€‚andā€‚wireā€‚sizesā€‚forā€‚a 3.81 or 3.50 pitchā€‚removableā€‚screwā€‚terminalā€‚block:

Ƙ 3,5 mm (0.14 in.)

mm2

AWG0.2ā€¦2.524ā€¦14

0.2ā€¦2.524ā€¦14

0.25ā€¦2.522...14

2 x 0.25ā€¦12 x 22ā€¦18

2 x 0.2ā€¦1.52 x 24ā€¦16

2 x 0.2ā€¦12 x 24ā€¦18

2 x 0.5...1.52 x 20...16

mmin.

70.28

C0.5...0.64.42...5.31

Nā€¢mlb-in

0.25ā€¦2.522...14

Fig. 10. Pitchā€‚3.81ā€‚mmā€‚(0.15ā€‚in.)ā€‚orā€‚3.50ā€‚mmā€‚(0.14ā€‚in.)

Page 25: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

25EIO0000002030 09/2015

DANGERLOOSE WIRING CAUSES ELECTRIC SHOCKTightenā€‚connectionsā€‚inā€‚conformanceā€‚withā€‚theā€‚torqueā€‚specifications.Failure to follow these instructions will result in death or serious injury.

DANGERFIRE HAZARDā€¢ Useā€‚onlyā€‚theā€‚correctā€‚wireā€‚sizesā€‚forā€‚theā€‚currentā€‚capacityā€‚ofā€‚theā€‚I/Oā€‚channelsā€‚andā€‚powerā€‚supplies.ā€¢ Forā€‚2ā€‚Aā€‚-ā€‚relayā€‚outputā€‚wiring,ā€‚useā€‚conductorsā€‚withā€‚aā€‚crossā€‚sectionā€‚atā€‚leastā€‚equalā€‚toā€‚0.5ā€‚mm2ā€‚(AWGā€‚20)ā€‚andā€‚aā€‚temperatureā€‚

ratingā€‚atā€‚leastā€‚equalā€‚toā€‚80ā€‚Ā°Cā€‚(176ā€‚Ā°F).ā€¢ Forā€‚3ā€‚Aā€‚-ā€‚relayā€‚outputā€‚wiring,ā€‚useā€‚conductorsā€‚withā€‚aā€‚crossā€‚sectionā€‚atā€‚leastā€‚equalā€‚toā€‚1.5ā€‚mm2ā€‚(AWGā€‚16)ā€‚andā€‚aā€‚temperatureā€‚

ratingā€‚atā€‚leastā€‚equalā€‚toā€‚80ā€‚Ā°Cā€‚(176ā€‚Ā°F).ā€¢ Forā€‚commonā€‚conductorsā€‚ofā€‚8ā€‚Aā€‚-ā€‚relayā€‚outputā€‚wiring,ā€‚orā€‚greaterā€‚thanā€‚3ā€‚Aā€‚-ā€‚relayā€‚outputā€‚wiring,ā€‚useā€‚conductorsā€‚withā€‚aā€‚

cross section at least equalā€‚toā€‚2.0ā€‚mm2ā€‚(AWGā€‚12)ā€‚andā€‚aā€‚temperatureā€‚ratingā€‚atā€‚leastā€‚equalā€‚toā€‚80ā€‚Ā°Cā€‚(176ā€‚Ā°F).Failure to follow these instructions will result in death or serious injury.

3.1.3. Protecting Outputs from Inductive Load Damage

Ifā€‚ yourā€‚ controllerā€‚ orā€‚moduleā€‚ containsā€‚ relayā€‚outputs,ā€‚ theseā€‚ typesā€‚ofā€‚ outputsā€‚ canā€‚ supportā€‚ upā€‚ toā€‚ 250ā€‚Vacā€‚ (240ā€‚Vacā€‚ ifā€‚SSR).ā€‚Inductiveā€‚damageā€‚toā€‚theseā€‚typesā€‚ofā€‚outputsā€‚canā€‚resultā€‚inā€‚weldedā€‚contactsā€‚andā€‚lossā€‚ofā€‚control.ā€‚Eachā€‚inductiveā€‚loadā€‚mustā€‚includeā€‚aā€‚protectionā€‚deviceā€‚suchā€‚asā€‚aā€‚peakā€‚limiter,ā€‚RCā€‚circuitā€‚orā€‚flybackā€‚diode.ā€‚Capacitiveā€‚loadsā€‚areā€‚notā€‚supportedā€‚byā€‚theseā€‚relays.

WARNINGRELAY OUTPUTS WELDED CLOSED

ā€¢ Alwaysā€‚protectā€‚relayā€‚outputsā€‚fromā€‚inductiveā€‚alternatingā€‚currentā€‚loadā€‚damageā€‚usingā€‚anā€‚appropriateā€‚externalā€‚protectiveā€‚circuitā€‚orā€‚device.

ā€¢ Doā€‚notā€‚connectā€‚relayā€‚outputsā€‚toā€‚capacitiveā€‚loads.Failure to follow these instructions can result in death, serious injury, or equipment damage.

Dependingā€‚onā€‚theā€‚load,ā€‚aā€‚protectionā€‚circuitā€‚mayā€‚beā€‚neededā€‚forā€‚theā€‚outputsā€‚onā€‚theā€‚controllersā€‚andā€‚certainā€‚modules.ā€‚Inductiveā€‚loadsā€‚usingā€‚DCā€‚voltagesā€‚mayā€‚createā€‚voltageā€‚reflectionsā€‚resultingā€‚inā€‚overshootā€‚thatā€‚willā€‚damageā€‚orā€‚shortenā€‚theā€‚lifeā€‚ofā€‚outputā€‚devices.

CAUTIONOUTPUT CIRCUIT DAMAGE DUE TO INDUCTIVE LOADSUseā€‚anā€‚appropriateā€‚externalā€‚protectiveā€‚circuitā€‚orā€‚deviceā€‚toā€‚reduceā€‚theā€‚riskā€‚ofā€‚inductiveā€‚directā€‚currentā€‚loadā€‚damageFailure to follow these instructions can result in injury or equipment damage.

Chooseā€‚aā€‚protectionā€‚circuitā€‚fromā€‚theā€‚followingā€‚diagramsā€‚accordingā€‚toā€‚theā€‚powerā€‚supplyā€‚used.ā€‚Connectā€‚theā€‚protectionā€‚circuitā€‚toā€‚theā€‚outsideā€‚ofā€‚theā€‚controllerā€‚orā€‚relayā€‚outputā€‚module.ā€‚

Page 26: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

26 EIO0000002030 09/2015

Protective circuit A:ā€‚thisā€‚protectionā€‚circuitā€‚canā€‚beā€‚usedā€‚forā€‚bothā€‚ACā€‚andā€‚DCā€‚loadā€‚powerā€‚circuits.ā€‚

Output Q

COM

R C

or

Inductive load

~

Fig. 11. Protectiveā€‚circuitā€‚A

Cā€‚Valueā€‚fromā€‚0.1ā€‚toā€‚1ā€‚Ī¼FRā€‚Resistorā€‚ofā€‚approximatelyā€‚theā€‚sameā€‚resistanceā€‚valueā€‚asā€‚theā€‚load

Protective circuit B:ā€‚thisā€‚protectionā€‚circuitā€‚canā€‚beā€‚usedā€‚forā€‚DCā€‚loadā€‚powerā€‚circuits.

Output Q

COM

Inductive load

Fig. 12. Protectiveā€‚circuitā€‚B

Use a diode with the following ratings:ā€¢ Reverseā€‚withstandā€‚voltage:ā€‚powerā€‚voltageā€‚ofā€‚theā€‚loadā€‚circuitā€‚xā€‚10.ā€¢ Forwardā€‚current:ā€‚moreā€‚thanā€‚theā€‚loadā€‚current.

Protective circuit C:ā€‚thisā€‚protectionā€‚circuitā€‚canā€‚beā€‚usedā€‚forā€‚bothā€‚ACā€‚andā€‚DCā€‚loadā€‚powerā€‚circuits.

Output Q

COM

Inductive load

or~

U

Varistor

Fig. 13. Protectiveā€‚circuitā€‚C

Inā€‚applicationsā€‚whereā€‚theā€‚inductiveā€‚loadā€‚isā€‚switchedā€‚onā€‚andā€‚offā€‚frequentlyā€‚and/orā€‚rapidly,ā€‚ensureā€‚thatā€‚theā€‚continuousā€‚energyā€‚ratingā€‚(J)ā€‚ofā€‚theā€‚varistorā€‚exceedsā€‚theā€‚peakā€‚loadā€‚energyā€‚byā€‚20ā€‚%ā€‚orā€‚more.

NOTE: Place protection devices as close to the load as possible.

Page 27: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

27EIO0000002030 09/2015

3.1.4. Special handling considerationsCareā€‚ mustā€‚ beā€‚ takenā€‚ toā€‚ avoidā€‚ damageā€‚ fromā€‚ electrostaticā€‚ sourcesā€‚ whenā€‚ handlingā€‚ thisā€‚ equipment.ā€‚ Inā€‚ particularā€‚ exposedā€‚ connectorsā€‚and,ā€‚inā€‚someā€‚cases,ā€‚exposedā€‚printedā€‚circuitā€‚boardsā€‚areā€‚vulnerableā€‚toā€‚electrostaticā€‚discharge.

WARNINGUNINTENDED EQUIPMENT OPERATION DUE TO ELECTROSTATIC DISCHARGE DAMAGE

ā€¢ Keepā€‚equipmentā€‚inā€‚theā€‚protectiveā€‚conductiveā€‚packagingā€‚untilā€‚youā€‚areā€‚readyā€‚toā€‚installā€‚theā€‚equipment.ā€‚ā€¢ Onlyā€‚installā€‚equipmentā€‚inā€‚approvedā€‚enclosuresā€‚andā€‚/ā€‚orā€‚locationsā€‚thatā€‚preventā€‚unauthorizedā€‚accessā€‚andā€‚provideā€‚elec-

trostaticā€‚dischargeā€‚protectionā€‚asā€‚definedā€‚byā€‚IECā€‚1000-4-2.ā€‚ā€¢ Useā€‚aā€‚conductiveā€‚wristā€‚strapā€‚orā€‚equivalentā€‚fieldā€‚forceā€‚protectiveā€‚deviceā€‚attachedā€‚toā€‚anā€‚earthā€‚groundā€‚whenā€‚handlingā€‚

sensitiveā€‚equipment.ā€‚ā€¢ Alwaysā€‚dischargeā€‚yourselfā€‚byā€‚touchingā€‚aā€‚groundedā€‚surfaceā€‚orā€‚approvedā€‚antistaticā€‚matā€‚beforeā€‚handlingā€‚theā€‚equipment.ā€‚

Failure to follow these instructions can result in death, serious injury, or equipment damage.

3.1.5. Analog Inputs-ProbesTemperatureā€‚probesā€‚haveā€‚noā€‚connectionā€‚polarityā€‚andā€‚canā€‚beā€‚extendedā€‚usingā€‚aā€‚normalā€‚bipolarā€‚cable.ā€‚

WARNINGUNINTENDED EQUIPMENT OPERATION DUE TO CONNECTION

ā€¢ Applyā€‚powerā€‚toā€‚allā€‚externallyā€‚poweredā€‚devicesā€‚afterā€‚applyingā€‚powerā€‚toā€‚theā€‚M171ā€‚Performanceā€‚logicā€‚controllers.ā€¢ Signalā€‚leadsā€‚(probes,ā€‚digitalā€‚inputs,ā€‚communicationā€‚andā€‚theā€‚electronicā€‚supply)ā€‚mustā€‚beā€‚routedā€‚separatelyā€‚fromā€‚powerā€‚

cables.Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTICEINOPERABLE EQUIPMENTVerifyā€‚allā€‚wiringā€‚connectionsā€‚beforeā€‚applyingā€‚power.Failure to follow these instructions can result in equipment damage.

NOTE: ā€‚Theā€‚extensionā€‚ofā€‚theā€‚probesā€‚influencesā€‚theā€‚electromagneticā€‚compatibilityā€‚(EMC)ā€‚ofā€‚theā€‚equipment.

NOTE: Connectionā€‚polarityā€‚mustā€‚beā€‚correctlyā€‚respectedā€‚forā€‚probesā€‚whichā€‚needā€‚aā€‚specificā€‚polarity.

3.1.6. Serial connectionsThe reference has on-board serial

M171 Performance CAN,ā€‚RS485,ā€‚USBM171 Performance Flush CAN,ā€‚RS485,ā€‚ETHERNET

Payā€‚specialā€‚attentionā€‚whenā€‚connectingā€‚serialā€‚lines.ā€‚Miswiringā€‚mayā€‚leadā€‚toā€‚inoperableā€‚equipment.

NOTICEINOPERABLE EQUIPMENTā€¢ Doā€‚notā€‚connectā€‚equipmentā€‚thatā€‚communicateā€‚usingā€‚RS485ā€‚serialā€‚toā€‚CANā€‚terminals.ā€¢ Doā€‚notā€‚connectā€‚CANā€‚equipmentā€‚toā€‚RS485ā€‚terminals.Failure to follow these instructions can result in equipment damage.

Communicationā€‚ Modulesā€‚ TM171Aā€‚ ā€‚ provideā€‚ additionalā€‚ serialā€‚ portsā€‚ forā€‚ integrationā€‚ withā€‚ industrialā€‚ systems,ā€‚ BMSā€‚ andā€‚Ethernet. Controllerā€‚ serialsā€‚ areā€‚ definedā€‚ asā€‚ ā€œon-boardā€ā€‚ (OB)ā€‚ whereasā€‚ serialsā€‚ onā€‚ TM171Aā€‚ areā€‚ referredā€‚ toā€‚ asā€‚ Communicationā€‚Modulesā€‚(PI,ā€‚standsā€‚forā€‚"Plugā€‚In").

Page 28: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

28 EIO0000002030 09/2015

CAN Expansion Bus

ā€¢ Use a shielded and "twisted pair" cable with two 0.5 mm2ā€‚sectionā€‚conductorsā€‚(AWGā€‚22),ā€‚plusā€‚braidā€‚suchā€‚asā€‚Beldenā€‚cableā€‚referenceā€‚3105Aā€‚(characteristicā€‚impedanceā€‚120ā€‚Ī©)ā€‚withā€‚PVCā€‚sleeve,ā€‚nominalā€‚capacityā€‚betweenā€‚conductorsā€‚36ā€‚pF/m,ā€‚nomi-nalā€‚capacityā€‚betweenā€‚conductorā€‚andā€‚shieldingā€‚68ā€‚pF/m.

ā€¢ Alwaysā€‚followā€‚regulationsā€‚applicableā€‚toā€‚theā€‚routingā€‚andā€‚connectionā€‚ofā€‚cables.ā€‚Makeā€‚certainā€‚thatā€‚dataā€‚transmissionā€‚circuitsā€‚areā€‚properlyā€‚separatedā€‚fromā€‚powerā€‚lines.

ā€¢ Forā€‚connectionsā€‚overā€‚longerā€‚distances,ā€‚itā€‚isā€‚betterā€‚toā€‚endā€‚theā€‚lineā€‚withā€‚resistorsā€‚onā€‚bothā€‚ends,ā€‚insertingā€‚theā€‚twoā€‚R TERM jumpersā€‚(availableā€‚onā€‚theā€‚terminalā€‚stripā€‚nextā€‚toā€‚theā€‚CANā€‚Expansionā€‚Busā€‚asā€‚theā€‚defaultā€‚configuration).

ā€¢ Theā€‚maximumā€‚distanceā€‚dependsā€‚onā€‚theā€‚baudā€‚settingā€‚(seeā€‚theā€‚followingā€‚table).

kb/s (kbaud) On-board CAN (m) - M171 Performance CAN Communication Module (m)

50 1000 1000125 500 500250 200 250500 30 60

ā€¢ CANā€‚Expansionā€‚Busā€‚isā€‚usedā€‚toā€‚communicateā€‚withā€‚M171 Performance Display Graphicā€‚(TM171DGRP)ā€‚terminalā€‚andā€‚M171 Performance Expansion terminal.

RS 485

ā€¢ Use a shielded and "twisted pair" cable with two 0.5 mm2ā€‚sectionā€‚conductorsā€‚(AWGā€‚22),ā€‚plusā€‚braidā€‚suchā€‚asā€‚Beldenā€‚cableā€‚referenceā€‚3105Aā€‚(characteristicā€‚impedanceā€‚120ā€‚Ī©)ā€‚withā€‚PVCā€‚sleeve,ā€‚nominalā€‚capacityā€‚betweenā€‚conductorsā€‚36ā€‚pF/m,ā€‚nomi-nalā€‚capacityā€‚betweenā€‚conductorā€‚andā€‚shieldingā€‚68ā€‚pF/m.ā€‚Alternativelyā€‚useā€‚aā€‚shieldedā€‚andā€‚"twisted pair" cable with two 0.5 mm2ā€‚sectionā€‚conductorsā€‚(AWGā€‚20),ā€‚plusā€‚braidā€‚suchā€‚asā€‚Beldenā€‚cableā€‚referenceā€‚8762ā€‚withā€‚PVCā€‚sleeve,ā€‚nominalā€‚capacityā€‚betweenā€‚conductorsā€‚89ā€‚pF/m,ā€‚nominalā€‚capacityā€‚betweenā€‚conductorā€‚andā€‚shieldingā€‚161ā€‚pF/m.ā€‚Seeā€‚ENā€‚50174ā€‚standardā€‚onā€‚ITā€‚cablingā€‚forā€‚indicationsā€‚onā€‚howā€‚cablesā€‚shouldā€‚beā€‚routed.ā€‚

ā€¢ Alwaysā€‚followā€‚regulationsā€‚applicableā€‚toā€‚theā€‚routingā€‚andā€‚connectionā€‚ofā€‚cables.ā€‚Makeā€‚certainā€‚thatā€‚dataā€‚transmissionā€‚circuitsā€‚areā€‚properlyā€‚separatedā€‚fromā€‚powerā€‚lines.ā€‚

ā€¢ RSā€‚485ā€‚networkā€‚upā€‚toā€‚1200ā€‚mā€‚inā€‚lengthā€‚withā€‚aā€‚maximumā€‚ofā€‚32(1)ā€‚devicesā€‚canā€‚beā€‚connectedā€‚directlyā€‚toā€‚theā€‚controller.ā€‚ (1) Example of M171 Performance Modbusā€‚Slaveā€‚withā€‚singleā€‚Masterā€‚supervisor.ā€‚ ā€‚ Thisā€‚lengthā€‚canā€‚beā€‚extendedā€‚andā€‚theā€‚numberā€‚ofā€‚devicesā€‚forā€‚eachā€‚channelā€‚increasedā€‚usingā€‚appropriateā€‚repeaterā€‚ā€‚ā€‚ modules.ā€¢ Singleā€‚terminalā€‚stripā€‚withā€‚3ā€‚conductors:ā€‚useā€‚allā€‚3ā€‚conductorsā€‚(ā€œ+ā€,ā€‚ā€œ-ā€œā€‚forā€‚theā€‚signalā€‚andā€‚ā€œGNDā€ā€‚forā€‚theā€‚braid).

ā€¢ Attachā€‚theā€‚120ā€‚Ī©ā€‚1/4ā€‚Wā€‚resistorsā€‚betweenā€‚theā€‚"+"ā€‚andā€‚"-"ā€‚terminalsā€‚ofā€‚theā€‚interfaceā€‚andā€‚theā€‚lastā€‚controllerā€‚inā€‚eachā€‚branchā€‚ofā€‚theā€‚network.

ā€¢ Maximumā€‚settableā€‚speedā€‚115200ā€‚baud.

ā€¢ RSā€‚485ā€‚physicalā€‚layerā€‚canā€‚beā€‚usedā€‚forā€‚Modbusā€‚SL,ā€‚asā€‚wellā€‚asā€‚forā€‚BACnetā€‚MS/TPā€‚communication.ā€‚ Concurrentā€‚communicationā€‚ofā€‚differentā€‚protocolsā€‚onā€‚theā€‚sameā€‚serialā€‚portā€‚isā€‚NOT allowed.

Payā€‚specialā€‚attentionā€‚whenā€‚connectingā€‚serialā€‚lines.ā€‚Miswiringā€‚mayā€‚leadā€‚toā€‚inoperableā€‚equipment.

NOTICEINOPERABLE EQUIPMENTDoā€‚notā€‚communicateā€‚throughā€‚Modbusā€‚SLā€‚andā€‚BACnetā€‚MS/TPā€‚simultaneouslyā€‚onā€‚theā€‚sameā€‚line.ā€‚ Failure to follow these instructions can result in equipment damage.

Page 29: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

29EIO0000002030 09/2015

Ethernet

Theā€‚Ethernetā€‚connectionā€‚ofā€‚theā€‚Communicationā€‚Moduleā€‚TM171AETH / TM171AETHRS485 allows the M171 Performance logicā€‚controllerā€‚toā€‚communicateā€‚onā€‚anā€‚Ethernetā€‚networkā€‚usingā€‚TCP/IPā€‚protocol,ā€‚whereasā€‚M171 Performance Flush,ā€‚withā€‚itsā€‚embeddedā€‚Ethernet,ā€‚doesā€‚NOTā€‚requireā€‚anā€‚Ethernetā€‚Communicationā€‚Module.ā€‚

The connection allows:ā€¢ connectionā€‚ofā€‚differentā€‚controllersā€‚and/orā€‚applicationsā€‚exchangingā€‚variablesā€‚and/orā€‚parametersā€‚(network).

ā€¢ connectionā€‚ofā€‚aā€‚supervisionā€‚systemā€‚usingā€‚Modbusā€‚TCP/IPā€‚protocol.

ā€¢ connectionā€‚ofā€‚anā€‚IECā€‚61131-3ā€‚TM171SW (SoMachineHVAC)ā€‚developmentā€‚system.

ā€¢ connectionā€‚onā€‚deviceā€‚onā€‚aā€‚BACnet/TCPā€‚network,ā€‚withā€‚B-AACā€‚profile

Concurrentā€‚communicationā€‚onā€‚differentā€‚protocolsā€‚usingā€‚theā€‚sameā€‚Ethernetā€‚portā€‚isā€‚allowed.

Theā€‚Ethernetā€‚connectorā€‚shieldā€‚isā€‚internallyā€‚connectedā€‚toā€‚theā€‚earthā€‚ofā€‚theā€‚equipmentā€‚andā€‚thereforeā€‚toā€‚theā€‚referenceā€‚ofā€‚theā€‚inputā€‚andā€‚outputā€‚channels.

USBThereā€‚areā€‚2ā€‚USBā€‚connectorsā€‚placedā€‚onā€‚theā€‚upper-leftā€‚sideā€‚ofā€‚theā€‚M171 Performance controllerā€‚(inā€‚theā€‚frontā€‚view)ā€‚(seeā€‚Fig. 14 on page 29).ā€¢ USB Typeā€‚Aā€‚isā€‚aā€‚connectorā€‚forā€‚USBā€‚memoryā€‚key.ā€¢ USBā€‚Typeā€‚mini-Bā€‚isā€‚usedā€‚forā€‚programmingā€‚purposes.ā€‚

Theā€‚componentsā€‚requiredā€‚forā€‚M171 Performanceā€‚USBā€‚mini-Bā€‚are: TCSXCNAMUM3P or BMXXCAUSBH018.

USB PURPOSE NOTE

Type A (HOST)

Usedā€‚ toā€‚ connectā€‚ aā€‚ USBā€‚ memoryā€‚ keyā€‚ whenā€‚ downlo-adingā€‚ theā€‚ application.ā€‚ Thisā€‚ shouldā€‚ beā€‚ doneā€‚ fromā€‚ theā€‚controllerā€‚ keypadā€‚ (TM171PDM27ā€‚ references)ā€‚ orā€‚ fromā€‚the M171 Performance Display Graphicā€‚ (TM171DGRP)ā€‚ā€‚(TM171PBM27Rā€‚reference).

Seeā€‚ "USB-Hostā€‚ Handling"ā€‚ onā€‚ 5.3.3. BIOS I/O Values on page 76 for information on how to manageā€‚filesā€‚onā€‚USBā€‚memoryā€‚key.

Type mini-B

(DEVICE)

Used to connect M171 Performanceā€‚ toā€‚ aā€‚ PCā€‚ viaā€‚mini-Bā€‚USBā€‚ cableā€‚ forā€‚ debugging,ā€‚ commissioning,ā€‚ downloading,ā€‚uploadingā€‚ withā€‚ TM171SW (SoMachineHVAC v2.0 or greater).ā€‚The operations can be done from PC or another device.

Compatible with the following operating systems:ā€¢ Windowsā€‚Vistaā€‚Businessā€‚x86ā€‚+ā€‚x64ā€‚(Serviceā€‚

Packā€‚2)ā€‚ā€¢ Windowsā€‚7ā€‚x86ā€‚+ā€‚x64ā€‚(Serviceā€‚Packā€‚1)ā€‚ā€¢ Windowsā€‚8ā€‚/ā€‚8.1ā€‚x86ā€‚+ā€‚x64ā€‚ā€¢ Windowsā€‚Serverā€‚2008,ā€‚SP2,ā€‚andā€‚R2ā€‚ā€¢ Windowsā€‚Serverā€‚2012ā€‚andā€‚R2ā€‚

Theā€‚driverā€‚isā€‚suppliedā€‚withā€‚theā€‚TM171SW (SoMachineHVAC v2.0 or greater) software.

Type A

Type mini-B

M171USB

miniUSB

Fig. 14. M171ā€‚Performance:ā€‚typeā€‚Aā€‚USBā€‚andā€‚typeā€‚mini-Bā€‚USB

Page 30: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

30 EIO0000002030 09/2015

3.2. Wiring diagramsMiswiringā€‚irreversiblyā€‚damagesā€‚theā€‚Modicon M171P.

NOTICEINOPERABLE EQUIPMENTVerifyā€‚allā€‚wiringā€‚connectionsā€‚beforeā€‚applyingā€‚power.Failure to follow these instructions can result in equipment damage.

3.2.1. Modicon M171P wiring diagram

DI 1DIGITAL INPUT RS485 CAN

DI2 DI3 DI4 C1-4 DI5 DI6 DI7 DI8 C5-8 GS - + GS H L POWER OUT

AI1ANALOG INPUT

GAO1 GAO2 GAO3 GAO4 GAO5

GFDI

AI2 AI3 AI4 AI5 AI6 12Vout 5Vout

+12V+5V

GG

POWER

POWER INDIGITAL OUTPUTS

DIGITAL INPUTS

ANALOG INPUTS

[Ext. Keyboard TM171DGRP]24 Va/c48 Vc

-

+ +

-24 Va/c48 Vc

24 Va/c48 Vc

RS485 CAN

4 DIP SWITCH

DO3 DO4 C34 DO5 DO6 DO7 C567C2 DO2 DO2C1 DO1 DO1

Conn

ecto

r

TM171A

ANALOG OUTPUTS

FAST DIGITAL INPUT

AO1 AO2 AO3 AO4 AO5

+

+ +

+

R TERM

R TERM

TM171PDM27

USB

miniUSB

12A max

TM171PBM27R/TM171EPR

10 DIP SWITCH 6 DIP SWITCH

1234ON

12345678910

ON ON

123456

Fig. 15. Modicon M171P wiring diagram

Page 31: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

31EIO0000002030 09/2015

Connector Labels Related To M171 Performance

LABEL DESCRIPTION NOTES

DIP SWITCH

4 DIP SWITCH 4-positionā€‚selectorsā€‚(Dipā€‚Switches) Dipā€‚Switchesā€‚defaultā€‚OFF

6 DIP SWITCH 6-positionā€‚selectorsā€‚(Dipā€‚Switches) Dipā€‚Switchesā€‚defaultā€‚OFFā€‚TM171PBM27Rā€‚/TM171EP27R reference

Dip Switches located behind the panel10 DIP SWITCH 10-positionā€‚selectorsā€‚(Dipā€‚Switches)

POWERSUPPLY

POWER IN +24ā€‚Vac/dcā€‚orā€‚+48ā€‚Vdcā€‚powerā€‚supply -

POWER OUT +24ā€‚Vac/dcā€‚orā€‚+48ā€‚Vdcā€‚powerā€‚supply

POWER [Ext. Keyboard M171 Performance Display Graphic

(TM171DGRP)]outputā€‚forā€‚display

ANALOGOUTPUTS

AO1ā€¦AO5 Analogā€‚outputsā€‚1...5 See CHAPTER 4 Technical data on page 64ā€‚forā€‚furtherā€‚detailsG 0ā€‚Vā€‚signalā€‚ground

DIGITALOUTPUTS

C1 DO1 DO1 SPDTā€‚Relayā€‚1 DO1ā€‚isā€‚theā€‚normallyā€‚openā€‚side,ā€‚DO1 is the normallyā€‚closedā€‚sideā€‚

C2 DO2 DO2 SPDTā€‚Relayā€‚2 DO2ā€‚isā€‚theā€‚normallyā€‚openā€‚side,ā€‚DO2 is the normallyā€‚closedā€‚sideā€‚

DO3 DO4 Relayā€‚outputā€‚3-4alsoā€‚availableā€‚asā€‚SSRā€‚outputs

-C34 Commonā€‚forā€‚digitalā€‚outputsā€‚3-4DO5 DO6 DO7 Relayā€‚outputā€‚5-6-7

C567 Commonā€‚forā€‚digitalā€‚outputsā€‚5-6-7 12 A max

CAN GS H L Isolated CAN serialGSā€‚groundā€‚serialā€‚isolatedā€‚fromā€‚G R TERM termination resistors for CAN

RS485 GS - + Isolatedā€‚RS485ā€‚serialGSā€‚groundā€‚serialā€‚isolatedā€‚fromā€‚G Applyā€‚120ā€‚Ī©ā€‚terminationā€‚resistors

DIGITALINPUTS

DI1...DI4 Digitalā€‚inputsā€‚1...4

-C1-4 Commonā€‚forā€‚digitalā€‚inputsā€‚1...4

DI5...DI8 Digitalā€‚inputsā€‚5...8C5-8 Commonā€‚forā€‚digitalā€‚inputsā€‚5...8

FAST D.I.FDI Fastā€‚digitalā€‚input

Pulse/frequencyā€‚counterā€‚upā€‚toā€‚1ā€‚kHzG 0ā€‚Vā€‚signalā€‚ground

ANALOG INPUTS

AI1...AI6 Analogā€‚inputs

-G 0ā€‚Vā€‚signalā€‚ground

SENSOR POWER SUPPLY

12Vout 12Vā€‚outputā€‚forā€‚analogā€‚inputs

5Vout 5Vā€‚outputā€‚forā€‚ratiometricā€‚analogā€‚inputs

Page 32: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

32 EIO0000002030 09/2015

3.2.2. Modicon M171EP14R wiring diagram

TM171EP14R

+ G AO2 DI4AO1AI4AI3AI2AI1c

+5Vc

+24VDI3

Power Supplyz 24V

4 DIP SWITCH

DI2DI1G DI_Commonā€”

Power Outc 5V: 20 mA

c 24V: 50 mA

6 27 345 1HGS L

CAN

ON

1234

DO1DO2DO3DO4N

MA

X. 1

0A

Fig. 16. Modiconā€‚M171EP14Rā€‚wiringā€‚diagram

Connector Labels Related To M171EP14R

LABEL DESCRIPTION NOTES

DIP SWITCH 4 DIP SWITCH 4-positionā€‚selectorsā€‚(Dipā€‚Switches) Dipā€‚Switchesā€‚defaultā€‚OFF

POWERSUPPLY + / - +24ā€‚Vac/dcā€‚powerā€‚supply -

ANALOGOUTPUTS

AO1, AO2 Analogā€‚outputsā€‚1ā€‚andā€‚2See CHAPTER 4 Technical data on page

64ā€‚forā€‚furtherā€‚detailsG 0ā€‚Vā€‚signalā€‚ground

+24V Powerā€‚Outā€‚+24ā€‚Vdcā€‚output+5V Powerā€‚Outā€‚+5ā€‚Vdcā€‚output

DIGITALOUTPUTS

1-2-3 SPDTā€‚Relayā€‚outputDO1

1ā€‚isā€‚theā€‚normallyā€‚openā€‚side,ā€‚ā€‚3ā€‚isā€‚theā€‚normallyā€‚closedā€‚sideā€‚

4-5-6 SPSTā€‚Relayā€‚outputā€‚2-3-4DO2 DO3 DO4 -

7 Commonā€‚forā€‚relayā€‚outputsā€‚2-3-4N 10 A max

CAN GS H L Isolated CAN serialGSā€‚groundā€‚serialā€‚isolatedā€‚fromā€‚G

Dip Switches 3-4 termination resistors for CAN

DIGITALINPUTS

DI1...DI4 Digitalā€‚inputsā€‚1...4-DI_Common Commonā€‚forā€‚digitalā€‚inputsā€‚1...4

ANALOG INPUTS

AI1...AI4 Analogā€‚inputs-G 0ā€‚Vā€‚signalā€‚ground

Page 33: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

33EIO0000002030 09/2015

3.2.3. Examples of analog input connection (M171 Performance only)

Example: NTC/PT1000 probe connectionā€¢ Analogā€‚inputsā€‚AI1ā€¦AI6ā€‚areā€‚availableā€‚forā€‚NTCā€¢ Analogā€‚inputsā€‚AI3ā€¦AI6ā€‚areā€‚availableā€‚forā€‚NTC/PT1000

AI1ANALOG INPUT

AI2 AI3 AI4 AI5 AI6G G

NTC

PT1000

Fig. 17. NTC/PT1000ā€‚probeā€‚connection

Example: 0-10 V transducer connectionAnalogā€‚Inputsā€‚AI3ā€¦AI6ā€‚areā€‚availableā€‚forā€‚0-10ā€‚Vā€‚transducerā€‚connection

ANALOG INPUTAI3 AI4 AI5 AI6 12VoutGG

0-10V Transducer

V SUPPLY

Fig. 18. 0-10ā€‚Vā€‚transducerā€‚connection

Example: Digital Input Connection (through analog input terminal)

AI1ANALOG INPUT

configured as Digital Inputs

AI2 AI3 AI4 AI5 AI6G G

Fig. 19. Analogā€‚Inputsā€‚configuredā€‚asā€‚Digitalā€‚Inputs

Page 34: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

34 EIO0000002030 09/2015

Example: 4...20 mA pressure transducer connection

Analogā€‚Inputsā€‚AI3ā€¦AI6ā€‚areā€‚availableā€‚asā€‚4...20ā€‚mAā€‚pressureā€‚transducerā€‚connection.

Inā€‚theā€‚caseā€‚ofā€‚aā€‚genericā€‚3-wireā€‚transducer,ā€‚connectā€‚theā€‚ā€‚0ā€‚Vā€‚referenceā€‚wireā€‚(groundā€‚ifā€‚soā€‚indicatedā€‚byā€‚theā€‚transducerā€‚manu-facturer)ā€‚toā€‚terminalā€‚GNDā€‚andā€‚theā€‚transducerā€‚powerā€‚supplyā€‚toā€‚12 Vdc screw terminal.

NOTICEINOPERABLE EQUIPMENTVerifyā€‚allā€‚wiringā€‚connectionsā€‚beforeā€‚applyingā€‚power.Failure to follow these instructions can result in equipment damage.

ANALOG INPUTAI3 AI4 AI5 AI6 12VoutGG

Two-wire 4...20mA Transducer

Supply

SIG

SIG

Supply

Transducer Power Supply

Three-wire 4...20mA Transducer

G

SIG

SIG

G

G

G

M171 Performance Three-wire 4...20 mA transducer Two-wire 4...20 mA transducerG G -

AI3 AI4 AI5 AI6 SIG SIG

12Vout Transducerā€‚Powerā€‚Supply SupplyFig. 20. 4...20ā€‚mAā€‚pressureā€‚transducerā€‚connection

Page 35: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

35EIO0000002030 09/2015

Example: ratiometric transducer connection

Analogā€‚Inputsā€‚AI3ā€¦AI6ā€‚areā€‚availableā€‚asā€‚ratiometricā€‚transducerā€‚connection

ANALOG INPUTAI3 AI4 AI5 AI6 5VoutGG

R 0/5V Transducer

SIGSIG

SIGSIG

+5 Vdc

+5 Vdc

GND

GND

GND

GND

GND

M171 Performance R 0/5V transducerG GND

AI3 AI4 AI5 AI6 SIG+5 Vout +5ā€‚Vdc

Fig. 21. Ratiometricā€‚transducerā€‚connection

Example: fan module connectionā€¢ 5ā€‚availableā€‚analogā€‚outputs:ā€‚AO1ā€¦AO5ā€¢ Exampleā€‚diagramā€‚withā€‚4ā€‚...20mAā€‚orā€‚0-10Vā€‚fanā€‚module

GAO1 GAO2 GAO3 GAO4 GAO5

ANALOG OUTPUTS

AO1 AO2 AO3 AO4 AO5

FANMODULE

FANMODULE

FANMODULE

FANMODULE

FANMODULE

Fig. 22. Fanā€‚moduleā€‚connection

Page 36: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

36 EIO0000002030 09/2015

Example: Open Collector connectionā€¢ 2ā€‚Openā€‚Collectorā€‚outputsā€‚availableā€‚asā€‚Openā€‚Collectorā€‚connection:ā€‚AO4/AO5ā€¢ Exampleā€‚withā€‚anā€‚externalā€‚relay

GAO4 GAO5

12Vout

+12V

ANALOG OUTPUTSOpen Collector

AO4 AO5

Fig. 23. Open Collector connection

Page 37: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

37EIO0000002030 09/2015

3.2.4. M171 Performance / M171 Display Graphic connection

CAN

24 Va/c48 Vc

CAN

GS H L POWER

RTERM

TM171DGRP

CANGS H L POWER

OUT

POWER

CAN

R TERM

R TERMRS485GS - +

RS485

M171 PerformanceTM171PDM27 / TM171PBM27R

CAN: max distance depending on baud rate

POW

ER :

max

dis

tanc

e

10m

Fig. 24. M171ā€‚Performanceā€‚/ā€‚M171ā€‚Performanceā€‚Displayā€‚Graphicā€‚(TM171DGRP)ā€‚terminalā€‚connection

NOTE: Whenā€‚supplyingā€‚powerā€‚fromā€‚theā€‚M171 Performance logic controllers,ā€‚makeā€‚theā€‚powerā€‚connectionā€‚cableā€‚asā€‚shortā€‚as possible.

NOTICEINOPERABLE EQUIPMENTDo not connect a power cable longer than 10m.Failure to follow these instructions can result in equipment damage.

LABEL DESCRIPTION NOTES

POWER POWER IN +24ā€‚Vac/dcā€‚orā€‚+48ā€‚Vdcā€‚powerā€‚supplyMaximumā€‚cableā€‚lengthā€‚10m

from TM171PM27ā€‚orā€‚separateā€‚powerā€‚supply

CAN GS H L Isolated CAN serialGSā€‚groundā€‚serialā€‚insulatedā€‚fromā€‚G

Rā€‚TERMā€‚terminationā€‚resistorsā€‚forā€‚CANMaximumā€‚cableā€‚length

See 3.1.6. Serial connections on page 27

Page 38: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

38 EIO0000002030 09/2015

3.2.5. M171 Performance Flush TM171PFE03 and TM171PFE03HR connection

RS485 CAN+ - GS

24 Va/c48 Vc

RS485 CAN

GS H L POWEREthernet

RemoteProbes

AI2 AI3 G

example ofTransducer

AI3 G+12V External Power Supply

AI2 G

Digital input

AI2 G

NTC

RTERM

TM171PFE03AI1NTC Sensor Built-in

CANGS H L POWER

OUT

POWER

CAN

R TERM

R TERMRS485GS - +

RS485

AI1AI2 AI3

Remote Probes

Built-in Probe

CAN: max distance depending on baud rate

POW

ER :

max

dis

tanc

e

10m

M171 PerformanceTM171PDM27 / TM171PBM27R

Fig. 25. TM171PFE03 connection

RS485 CAN+ - GS

24 Va/c48 Vc

RS485 CAN

GS H L POWEREthernet

RemoteProbes

AI2 AI3 G

AI2 G

Digital input

AI2 G

NTC

RTERM

TM171PFE03HRAI4RH Sensor Built-in

AI1NTC Sensor Built-in

CANGS H L POWER

OUT

POWER

CAN

R TER

MR

TERM

RS485GS - +

RS485

AI1AI2

AI4

Remote Probe

Built-in Probes

CAN: max distance depending on baud rate

POW

ER :

max

dis

tanc

e

10m

M171 PerformanceTM171PDM27 / TM171PBM27R

Fig. 26. TM171PFE03HRā€‚connection

Page 39: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

39EIO0000002030 09/2015

NOTE: Whenā€‚supplyingā€‚powerā€‚fromā€‚theā€‚M171 Performance logic controllers,ā€‚makeā€‚theā€‚powerā€‚connectionā€‚cableā€‚asā€‚shortā€‚as possible.

NOTICEINOPERABLE EQUIPMENTDo not connect a power cable longer than 10m.Failure to follow these instructions can result in equipment damage.

Label Description Notes

POWER +24ā€‚Vac/dcā€‚orā€‚+48ā€‚Vdcā€‚powerā€‚supply

Pinā€‚POWERā€‚Voutā€‚onā€‚TM171PDM27 /ā€‚TM171PBM27R

Max. distance 10m M171 Performance Flushā€‚/TM171PDM27 /ā€‚TM171PBM27R

CANGS H L

Isolated CAN serialGSā€‚groundā€‚serialā€‚isolatedā€‚fromā€‚G Rā€‚TERMā€‚terminationā€‚resistorsā€‚forā€‚CAN

RS485GS - +

Isolatedā€‚RS485ā€‚serialGSā€‚groundā€‚serialā€‚isolatedā€‚fromā€‚G Applyā€‚120ā€‚Ī©ā€‚terminalā€‚resistors

Ethernet ETHERNETā€‚serial -Built-in AI1 NTC Sensor On-boardā€‚NTCā€‚sensor -

AI2 Remote Probes G

NTC,ā€‚D.I.ā€‚ā€‚remoteGroundā€‚GND Probeā€‚notā€‚included

AI3 Remote ProbesG

4...20ā€‚mAā€‚/ā€‚0-10ā€‚Vā€‚-+/ā€‚0-5ā€‚VGroundā€‚GND

TM171PFE03Probeā€‚notā€‚included

12ā€‚Vā€‚Externalā€‚powerā€‚supplyBuilt-in AI4 RH Sensor On-boardā€‚RH%ā€‚sensor TM171PFE03HR

Page 40: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

40 EIO0000002030 09/2015

3.3. M171 Performance protocol connectivity

3.3.1. Example: CAN (Field) network connectionAā€‚CANā€‚(Field)ā€‚networkā€‚connectionā€‚canā€‚beā€‚constitutedā€‚by:

ā€¢ Max 1 M171 Performance TM171PDM27ā€‚functioningā€‚asā€‚MASTERā€¢ Max 12 M171 Performance TM171EPRā€‚functioningā€‚asā€‚SLAVES

NOTE: No more than two M171 Performance Display Graphicā€‚(TM171DGRP)ā€‚canā€‚beā€‚addedā€‚toā€‚theā€‚networkā€‚connectedā€‚toā€‚M171 Performance TM171PDM27

The M171 Performance Display Graphicā€‚(TM171DGRP)ā€‚isā€‚suppliedā€‚byā€‚TM171PDM27ā€‚viaā€‚theā€‚POWERā€‚OUTā€‚output.

M171

TM171PDM27p

USB

miniUSB

CAN GSCAN HCAN L

CAN GSCAN HCAN L

CAN GS

CAN GS

CAN HCAN L

CAN GSCAN HCAN L

Power

TM171EP27RPower OUT

USB

miniUSB

USB

miniUSB

12

1

TM171EP27R

Power

Power

y 10 m

USB

miniUSB

TM171EP27RMax 12

2

MASTER

Slave

Slave

Slaves

TM171DGRP

GS H L

POWERCAN

CAN GSCAN HCAN L

Power IN

TM171DGRP

GS H L

POWERCAN

CAN HCAN L

Power IN

y 10 m

z 24 V48 V

Fig. 27. CANā€‚(Field)ā€‚networkā€‚connectionā€‚usingā€‚M171ā€‚Performance

Page 41: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

41EIO0000002030 09/2015

3.3.2. Example: CAN connection (Network)Aā€‚CANā€‚connectionā€‚(Network)ā€‚canā€‚beā€‚constitutedā€‚by:

ā€¢ 1 M171 Performance TM171PDM27ā€¢ 1 M171 Performance Display Graphicā€‚(TM171DGRP)ā€‚connectedā€‚inā€‚CANā€‚toā€‚M171 Performance TM171PDM27 or

alternatively,ā€‚toā€‚TM171PBM27R.

NOTE: Max 10 M171 Performance TM171PBM27Rā€‚connectedā€‚inā€‚CANā€‚(binding).

The M171 Performance Display Graphicā€‚(TM171DGRP)ā€‚isā€‚suppliedā€‚byā€‚TM171PDM27ā€‚viaā€‚theā€‚POWERā€‚OUTā€‚output.

CAN GSCAN HCAN L

TM171PBM27p

M171

TM171PDM27p

USB

miniUSB

CAN GSCAN HCAN L

z 24 V48 V

Power OUT

BINDING M171USB

miniUSB

TM171PBM27p

M171USB

miniUSB

1 2 10

Max 10

TM171DGRP

GS H L

POWERCAN

CAN GSCAN HCAN LPower IN

Powery 10 m

Fig. 28. CANā€‚connectionā€‚(Network)ā€‚usingā€‚M171ā€‚Performance

Page 42: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

42 EIO0000002030 09/2015

3.3.3. Example: RS485 connection (Field)Aā€‚RS485ā€‚connectionā€‚(Field)ā€‚canā€‚beā€‚constitutedā€‚by:

Description Notes1 M171 Performance TM171PDM27 TM171PDM27ā€‚isā€‚inā€‚Modbusā€‚RTUā€‚Masterā€‚mode

Max 127 M171 Performance TM171EP27R expansion modulesā€‚connectedā€‚inā€‚RS485 TM171EP27Rā€‚areā€‚inā€‚Modbusā€‚RTUā€‚Slaveā€‚mode

1 M171 Performance Display Graphicā€‚(TM171DGRP)ā€‚ connected in CAN to M171 Performance TM171PDM27 -

The M171 Performance Display Graphicā€‚(TM171DGRP)ā€‚isā€‚suppliedā€‚byā€‚TM171PDM27ā€‚viaā€‚theā€‚POWERā€‚OUTā€‚output.

Power IN

1 127

Max 127

485GS485 ā€“485 +

485GS485 ā€“485 +

M171

TM171PDM27p

USB

miniUSB

CAN GSCAN HCAN L

TM171EP27R

z 24 V48 V

Power OUT

M171USB

miniUSB

TM171EP27R

M171USB

miniUSB

TM171DGRP

GS H L

POWERCAN

CAN GSCAN HCAN L

Powery 10 m

Fig. 29. RS485ā€‚connectionā€‚(Field)ā€‚usingā€‚M171ā€‚Performance

Page 43: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

43EIO0000002030 09/2015

3.3.4. Example: RS485 connection with the Modicon M171O networkAā€‚RS485ā€‚connectionā€‚withā€‚theā€‚Modicon M171Oā€‚networkā€‚canā€‚beā€‚constitutedā€‚by:

Description NotesM171 Performance TM171PDM27 TM171PDM27ā€‚isā€‚inā€‚Modbusā€‚RTUā€‚Masterā€‚mode

Max 127 M171 Performance TM171PDM27 / TM171PBM27R or Modicon M171O (TM171OMR / TM171ODM22S)

(Modbus Slave) or Schneider Electricā€‚and/orā€‚third-partyā€‚devi-cesā€‚equippedā€‚withā€‚RS485ā€‚serialā€‚

Allā€‚devicesā€‚equippedā€‚withā€‚RS485ā€‚areā€‚inā€‚Modbusā€‚RTUā€‚Slave mode

(includingā€‚theā€‚M171 Performanceā€‚logicā€‚controllers)See also the Modicon M171Oā€‚manualā€‚forā€‚furtherā€‚

details.

CANā€‚networkā€‚ā€“ā€‚seeā€‚3.3.1. Example: CAN (Field) network con-nection on page 40.

The CAN connection can beā€¢ Field,ā€‚asā€‚illustrated

ā€¢ Network,ā€‚ifā€‚oneā€‚orā€‚moreā€‚M171 Performance TM171PDM27ā€‚/ā€‚TM171PBM27Rs are connected

1 M171 Performance Display Graphicā€‚(TM171DGRP)ā€‚con-nected in CAN to M171 Performance TM171PDM27 -

The M171 Performance Display Graphicā€‚(TM171DGRP)ā€‚isā€‚suppliedā€‚byā€‚TM171PDM27ā€‚viaā€‚theā€‚POWERā€‚OUTā€‚output.

TM171PDM27p

TM171DGRP

CAN Powery 10 m

127

Max 127M171

TM171PDM27

USB

miniUSB

1 2 3 4 5 6 7

F1

F3

F2

F4

F5

esc

set

TM171OD p22p

485GS485 ā€“485 +

485GS485 ā€“485 +

485GS485 ā€“485 +

485GS485 ā€“485 +

24 V48 V

TM171EP27R

M171USB

miniUSB

M171USB

miniUSB

TM171EP27R

M171USB

miniUSB

CAN GS

CANRS 485

CAN HCAN L

Power OUT

M171USB

miniUSB

1 2 3 4 5 6 7

F1

F3

F2

F4

F5

esc

set

TM171OD p22pTM171PBM27

12

Max 12

pp

z

TM171OFM22R

esc

set

M171

Fig. 30. RS485ā€‚connectionā€‚withā€‚theā€‚Modiconā€‚M171Oā€‚networkā€‚usingā€‚M171ā€‚Performance

Page 44: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

44 EIO0000002030 09/2015

3.4. M171 Performance Flush protocol connectivity

3.4.1. Example: RS485 connection (Field)Aā€‚RS485ā€‚connectionā€‚(Field)ā€‚canā€‚beā€‚constitutedā€‚by:

Description Notes

1 M171 Performance Flush M171 Performance Flushā€‚isā€‚inā€‚Modbusā€‚RTUā€‚Masterā€‚mode

Max 127 M171 Performance TM171EP27R expansionā€‚modulesā€‚connectedā€‚inā€‚RS485 TM171EP27Rā€‚areā€‚inā€‚Modbusā€‚RTUā€‚Slaveā€‚mode

EthernetAI2

AI1

NTC SensorBuilt-in

RH Sensor Built-in

AI3 GS H L

POWERGSG

RS485Analogue inputs CAN

+ ā€“

AI4

z 24 V48 V

Switch/Router

Ethernet

SlavesTM171EP27R TM171EP27R

M171USB

miniUSB

M171USB

miniUSB

MasterTM171PFE03 / TM171PFE03HR

485GS 485GS485 ā€“ 485 ā€“

485 + 485 +

1 127

Max 127

SoMachine HVAC softwareSupervisor

Power IN

Fig. 31. RS485ā€‚connectionā€‚(Field)ā€‚usingā€‚M171ā€‚Performanceā€‚Flush

3.4.2. Example: CAN connectionAā€‚CANā€‚connectionā€‚canā€‚beā€‚constitutedā€‚byā€‚1ā€‚M171 Performance Flush.

NOTE: Max 12 M171 Performance TM171EPR expansionā€‚modulesā€‚connectedā€‚inā€‚CAN.

Ethernet

AI2

AI1

NTC SensorBuilt-in

RH Sensor Built-in

AI3 GS H L

POWERGSG

RS485Analogue inputs CAN

+ ā€“

AI4

z 24 V48 V

TM171EP27R TM171EP27R

Max 12USB

miniUSB

USB

miniUSB

TM171PFE03/PFE03HR

CAN GSCAN HCAN L

Power IN

1 12

Fig. 32. CANā€‚connectionā€‚usingā€‚M171ā€‚Performanceā€‚Flush

Page 45: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

45EIO0000002030 09/2015

3.4.3. Example: RS485 connection with the Modicon M171O networkAā€‚RS485ā€‚connectionā€‚withā€‚theā€‚Modicon M171Oā€‚networkā€‚canā€‚beā€‚constitutedā€‚by:

Description Notes

1 M171 Performance Flush M171 Performance Flushā€‚isā€‚inā€‚Modbusā€‚RTUā€‚Masterā€‚mode

Max 127 M171 Performance TM171PDM27 /TM171PBM27R or Modicon M171O or Schneider Electricā€‚and/orā€‚third-partyā€‚

equipmentā€‚equippedā€‚withā€‚RS485ā€‚serial

Allā€‚devicesā€‚equippedā€‚withā€‚RS485ā€‚areā€‚inā€‚Modbusā€‚RTUā€‚Slaveā€‚modeā€‚(includingā€‚theā€‚M171 Performance logic controllers)See also the Modicon M171Oā€‚manualā€‚forā€‚furtherā€‚details.

CANā€‚network see 3.4.2. Example: CAN connection on page 44

Fig. 33. RS485ā€‚connectionā€‚withā€‚theā€‚Modiconā€‚M171Oā€‚networkā€‚usingā€‚M171ā€‚Performanceā€‚Flush

Page 46: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

46 EIO0000002030 09/2015

3.4.4. Example: CAN network connectionAā€‚CANā€‚networkā€‚connectionā€‚canā€‚beā€‚constitutedā€‚byā€‚1ā€‚M171 Performance Flush.

NOTE: Max 10 M171 Performance TM171PDM27 /ā€‚TM171PBM27R.

NOTE:ā€‚CANā€‚network:ā€‚seeā€‚3.4.2. Example: CAN connection on page 44

HMI menuM171 Performance Flushā€‚canā€‚beā€‚equippedā€‚withā€‚itsā€‚ownā€‚menuā€‚(namedā€‚Networkā€‚menu).In this case M171 Performance Flush logic controllerā€‚ isā€‚programmedā€‚withā€‚ theā€‚networkā€‚menu,ā€‚whichā€‚canā€‚readā€‚variablesā€‚present in the M171 Performance logic controller network.M171 Performance Flushā€‚logicā€‚controllerā€‚canā€‚operateā€‚fromā€‚theā€‚individualā€‚controllersā€‚andā€‚downloadā€‚upā€‚toā€‚10ā€‚remoteā€‚menusā€‚from the respective M171 Performance logic controllers.Inā€‚thisā€‚caseā€‚theā€‚remoteā€‚menuā€‚allowsā€‚'local'ā€‚navigationā€‚ofā€‚theā€‚individual M171 Performance logic controller.

Controller applicationTheā€‚variablesā€‚ofā€‚theā€‚variousā€‚controllersā€‚areā€‚sharedā€‚(boundā€‚together).An application present on M171 Performance Flushā€‚logicā€‚controllerā€‚canā€‚useā€‚variablesā€‚presentā€‚inā€‚theā€‚networkā€‚andā€‚shareā€‚itsā€‚own variables with other applications present on the respective M171 Performance logic controllers.

Ethernet

AI2

AI1

NTC SensorBuilt-in

RH Sensor Built-in

AI3 GS H L

POWERGSG

RS485Analogue inputs CAN

+ ā€“

AI4

TM171PFE03/PFE03HR

CAN GSCAN HCAN L

Power IN

CAN GSCAN HCAN L

CAN GSCAN HCAN L

Power OUT

z 24 V48 V

Powery 10 m

Binding

TM171PDM27p

M171USB

miniUSB

TM171PBM27p

M171USB

miniUSB

TM171PBM27p

Max 10

GSGH

1021

M171USB

miniUSB

M171USB

miniUSB

485 GS485 -485 +

485 GS

485 -

485 +

485 GS485 -

485 +

M171USB

miniUSB

Max 127

127

1

TM171EP27R

TM171EP27R

Fig. 34. CANā€‚networkā€‚connectionā€‚usingā€‚M171ā€‚Performanceā€‚Flush

Page 47: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

47EIO0000002030 09/2015

3.5. TM171A Communication ModulesCommunicationā€‚ Modulesā€‚ areā€‚ 2DINā€‚ modulesā€‚ thatā€‚ canā€‚ beā€‚ connectedā€‚ toā€‚ an M171 Performance controller or an M172 Performanceā€‚controllerā€‚(withā€‚restrictions,ā€‚referā€‚toā€‚theā€‚M172ā€‚Performanceā€‚controllerā€‚Hardwareā€‚Guide)ā€‚viaā€‚theā€‚Communicationā€‚Moduleā€‚connectorā€‚onā€‚theā€‚leftā€‚side,ā€‚behindā€‚theā€‚removableā€‚door.ā€‚Theā€‚Communicationā€‚Moduleā€‚isā€‚anchoredā€‚toā€‚theā€‚controllerā€‚withā€‚theā€‚twoā€‚fixingā€‚hooks.Itā€‚mountsā€‚toā€‚theā€‚DINā€‚railā€‚inā€‚theā€‚sameā€‚wayā€‚asā€‚theā€‚controller.

3.5.1. Communication Modules compatible with M171 and M172Interface for Communication Module

RS 232 TM171ARS232 5Aā€‚SPDTā€‚relayā€‚available

RS 485 TM171AMBTM171ARS485 RSā€‚485ā€‚inā€‚Daisyā€‚Chain(1)

CAN Expansion Bus TM171ACAN CANā€‚Expansionā€‚Busā€‚inā€‚Daisyā€‚Chain(1)LON TM171ALON LonWorksā€‚Communicationā€‚Module

(1)ā€‚Useā€‚aā€‚shieldedā€‚cable.ā€‚Seeā€‚3.1.6. Serial connections on page 27.

NOTE:ā€‚Theā€‚LonWorksā€‚communicationā€‚moduleā€‚supportsā€‚upā€‚toā€‚63ā€‚nodes.ā€‚Exceedingā€‚thisā€‚specificationā€‚mayā€‚resultā€‚inā€‚anā€‚electricalā€‚overloadā€‚conditionā€‚inā€‚theā€‚M171ALONā€‚Communicationā€‚Moduleā€‚andā€‚consequentlyā€‚inā€‚theā€‚controller.

WARNINGUNINTENDED EQUIPMENT OPERATIONDoā€‚notā€‚exceedā€‚theā€‚maximumā€‚ofā€‚63ā€‚nodesā€‚onā€‚theā€‚TM171ALONā€‚Communicationā€‚Module.Failure to follow these instructions can result in death, serious injury, or equipment damage.

Forā€‚moreā€‚informationā€‚onā€‚theā€‚LonWorksā€‚network,ā€‚visitā€‚www.echelon.com/technology/lonwork/

Page 48: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

48 EIO0000002030 09/2015

3.5.2. Communication Modules exclusively compatible with M171Interface for Communication Module

ETHERNETTM171AETH

TM171AETHRS485

Theā€‚MACADDRESSā€‚isā€‚suppliedā€‚inā€‚theā€‚box,Expressedā€‚asā€‚barcodeā€‚andā€‚12-digitā€‚alphanumericā€‚code.

Theā€‚Ethernetā€‚connectorā€‚shieldā€‚isā€‚connectedā€‚internallyā€‚toā€‚theā€‚equipmentā€‚ground,ā€‚andā€‚thereforeā€‚toā€‚theā€‚referenceā€‚ofā€‚theā€‚inputā€‚andā€‚outputā€‚channels

WebVisu:ā€‚WEBā€‚functionalitiesā€‚ofā€‚M171 Performance TM171PDM27 or TM171PBM27R + TM171AETH/ TM171AETHRS485ā€‚Communicationā€‚

Module

PROFIBUS TM171APBUS Profibus DP Slave-V0

Contactā€‚yourā€‚localā€‚Schneiderā€‚Electricā€‚representativeā€‚forā€‚moreā€‚informationā€‚ concerningā€‚theā€‚.GSDā€‚Profibusā€‚configurationā€‚file

Seeā€‚officialā€‚Profibusā€‚documentationā€‚forā€‚moreā€‚detailedā€‚information

Communicationā€‚Moduleā€‚TM171A are shown below:

TM171AETHTM171ACAN TM171ALONTM171APBUS

2 x RS485relay

RS232

TM171AETHRS485TM171ARS485TM171AMB TM171ARS232

2 x RS4852 x CAN

Fig. 35. TM171Aā€‚Communicationā€‚Modules

Page 49: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

49EIO0000002030 09/2015

CAN

1 2 3

R Term.(1)

CAN_

H

CAN_

GS

CAN

_L

CAN

1 2 3

CAN_

H

CAN_

GS

CAN

_L

TM171ACAN

TM171ARS232

TM171AMBTM171ARS485

TM171ALON

(1) CAN terminal resistance.

AB

Service red LEDLon status LED

Service button

FT_B

FT_A

To be connected externally to the protective earth

(1)

1 2 3 4

PE

LON

_GN

D

(1) PE

A

RT1 AND RT2 terminators

RT1 mounted

RT2 mounted

YESYESNO

NONO

YES

Termination resistance value

105 OhmNo termination

52.5 Ohm

RT1

RT2

B

1 4

A

B

A B

1 3 1 3

1 2 3

Com

mon

NO NC

A

Sub-DB9

12345

6789

RS 232NĀ° RS232123456789

DCD

DTRTXDRXD

GND

RICTSRTSDSR

BA

B

1 3

+

A

B

A

B

RS 485 RS 485

GS ā€“ + GS ā€“ +

GS

RS

485

ā€“

RS

485

+

GS

RS

485

ā€“

RS

485

+A B

RS 485 RS 485

GS GS

GS

RS

485

ā€“

RS

485

+

GS

RS

485

ā€“

RS

485

+

ā€“ + ā€“ +

A B-+-

+- +-

5 A 250 Vac

SPDT

Fig. 36. Communicationā€‚Modulesā€‚compatibleā€‚withā€‚M171/M172

Page 50: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

50 EIO0000002030 09/2015

12

45

67

83

1

8

RJ45

RS 485 RS 485

GS GS

GS

RS

485

ā€“

RS

485

+

GS

RS

485

ā€“

RS

485

+

ā€“ + ā€“ +

TM171AETHRS485 / TM171ARS485

TM171AETHRS485

Fig. 37. ETHERNET,ā€‚ETHERNET+RS485ā€‚Communicationā€‚Modules

Sub-DB9

12345

6789

ProfibusNĀ° Profibus1 Shield2 Output ground 24 V3 RXD-TXD +4 Repeater Control Signal TRS5 Ground 0 V6 5 V7 24 V8 RXD-TXD-9 Control Signal direction

TM171APBUS

Pin Required signals - pins 3-5-6-8

1 ShieldToā€‚beā€‚connectedā€‚externallyā€‚toā€‚theā€‚protectiveā€‚earthā€‚

2 24Vā€‚outputā€‚ground3 RXD-TXDā€‚+4 RTSā€‚repeaterā€‚controlā€‚signalā€‚direction5 Digitalā€‚ground6 5V7 24V8 RXD-TXDā€‚-9 Directionā€‚controlā€‚signalā€‚ground

Fig. 38. PROFIBUSā€‚Communicationā€‚Module

NOTE:ā€‚Inā€‚aā€‚networkā€‚withā€‚Profibusā€‚Communicationā€‚Modules,ā€‚theā€‚firstā€‚andā€‚lastā€‚elementā€‚inā€‚theā€‚networkā€‚mustā€‚terminateā€‚withā€‚Profibusā€‚resistors.

Page 51: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

51EIO0000002030 09/2015

3.5.3. TM171ARS232Theā€‚RS232ā€‚Communicationā€‚Moduleā€‚allowsā€‚M171/M172ā€‚DINā€‚ railā€‚mountedā€‚Performanceā€‚controllersā€‚ toā€‚communicateā€‚viaā€‚anā€‚RS232ā€‚serial.

Modbus RTU communication protocolThe connection allows:ā€¢ connectionā€‚toā€‚aā€‚supervisionā€‚systemā€‚usingā€‚theā€‚Modbusā€‚RTUā€‚protocol

ā€¢ connectionā€‚ofā€‚anā€‚IECā€‚61131-3ā€‚TM171SW (SoMachineHVAC)ā€‚developmentā€‚system

TM171EP27R

z 24 V48 V

CAN GSCAN HCAN L

Power OUT

TM171PDM27p

USB

miniUSB

RS232

TM171ARS232

M171USB

miniUSBSoMachine HVAC software

Supervisor

Fig. 39. Modbusā€‚RTUā€‚communicationā€‚protocolā€‚usingā€‚TM171ARS232

Page 52: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

52 EIO0000002030 09/2015

Modbus ASCII communication protocol send/receive AT commands for modem(1)

Thisā€‚protocolā€‚activatesā€‚whenā€‚thereā€‚isā€‚aā€‚modemā€‚connectedā€‚toā€‚theā€‚Communicationā€‚Module.The connection allows:ā€¢ connectionā€‚toā€‚aā€‚monitoringā€‚systemā€‚usingā€‚theā€‚Modbusā€‚ASCIIā€‚protocol;

ā€¢ connectionā€‚ofā€‚anā€‚IECā€‚61131-3ā€‚TM171SW (SoMachineHVAC)ā€‚developmentā€‚system;

ā€¢ send/receiveā€‚TXTā€‚messagesā€‚viaā€‚aā€‚modemā€‚connectedā€‚toā€‚theā€‚RS232(2) port.

NOTE:ā€‚Theā€‚Communicationā€‚Moduleā€‚hasā€‚aā€‚relayā€‚thatā€‚canā€‚beā€‚pilotedā€‚fromā€‚theā€‚controllerā€‚applicationā€‚toā€‚allowā€‚theā€‚modemā€‚toā€‚beā€‚activated/resetā€‚orā€‚asā€‚anā€‚additionalā€‚digitalā€‚output.(1)ā€‚Referā€‚toā€‚theā€‚Modem_IEC.pllā€‚softwareā€‚libraryā€‚inC:\<Programs>\Schneiderā€‚Electric\SoMachineHVAC\Catalog\FreeEvolution\PLC(2)ā€‚Referā€‚toā€‚theā€‚SMS_IEC.pllā€‚softwareā€‚libraryā€‚inC:\<Programs>\Schneiderā€‚Electric\SoMachineHVAC\Catalog\FreeEvolution\PLCSee TM171SW (SoMachineHVAC)ā€‚Manualā€‚forā€‚details.

NOTE: Referā€‚toā€‚theā€‚sectionā€‚onā€‚Parametersā€‚/ā€‚RS232ā€‚PASSIVEā€‚PLUG-INā€‚folderā€‚(seeā€‚CHAPTER 9 Parameters on page 107).Referā€‚toā€‚theā€‚sectionā€‚onā€‚Parametersā€‚/ā€‚MODEMā€‚folderā€‚(seeā€‚CHAPTER 9 Parameters on page 107).

TM171EP27R

z 24 V48 V

CAN GSCAN HCAN L

Power OUT

TM171PDM27p

USB

miniUSB

RS232

TM171ARS232

M171USB

miniUSB

SoMachine HVAC softwareSupervisor

Switch/Router

RESET

Switch/Router

Fig. 40. Modbusā€‚ASCIIā€‚communicationā€‚protocolā€‚usingā€‚TM171ARS232

Page 53: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

53EIO0000002030 09/2015

3.5.4. TM171AETH / TM171AETHRS485Theā€‚Ethernetā€‚Communicationā€‚Moduleā€‚enablesā€‚communicationā€‚ofā€‚theā€‚M171 Performance TM171PDM27 / TM171PBM27R onā€‚anā€‚Ethernetā€‚networkā€‚usingā€‚theā€‚Modbusā€‚TCPā€‚protocol.The connection allows:ā€¢ networkā€‚connectionā€‚ofā€‚differentā€‚controllersā€‚and/orā€‚applicationsā€‚exchangingā€‚variablesā€‚and/orā€‚parametersā€‚(network)

ā€¢ connectionā€‚toā€‚aā€‚supervisionā€‚systemā€‚usingā€‚theā€‚Modbusā€‚TCPā€‚protocol

ā€¢ connectionā€‚ofā€‚anā€‚IECā€‚61131-3 TM171SW (SoMachineHVAC)ā€‚developmentā€‚system

NOTE:Theā€‚MACā€‚ADDRESSā€‚(barcodeā€‚andā€‚12-digitā€‚alphanumericā€‚code)ā€‚isā€‚suppliedā€‚inā€‚theā€‚boxā€‚containingā€‚theā€‚Ethernetā€‚Communicationā€‚Module.Referā€‚toā€‚theā€‚sectionā€‚onā€‚Parametersā€‚/ā€‚ETHERNETā€‚PASSIVEā€‚PLUG-INā€‚folderā€‚(seeā€‚CHAPTER 9 Parameters on page 107).

NOTE: Theā€‚Ethernetā€‚connectorā€‚shieldā€‚isā€‚connectedā€‚internallyā€‚toā€‚theā€‚functionalā€‚ground,ā€‚andā€‚thereforeā€‚toā€‚theā€‚referenceā€‚ofā€‚theā€‚inputā€‚andā€‚outputā€‚channels.ā€‚Careā€‚mustā€‚beā€‚takenā€‚toā€‚theā€‚factā€‚thereā€‚mayā€‚beā€‚withinā€‚theā€‚Ethernetā€‚communicationsā€‚systemā€‚otherā€‚groundingā€‚points.ā€‚ Interconnectionā€‚ofā€‚multipleā€‚protectiveā€‚earthā€‚groundingā€‚pointsā€‚ inā€‚ theā€‚sameā€‚ installationā€‚ canā€‚causeā€‚currentā€‚loopsā€‚andā€‚voltageā€‚shiftsā€‚acrossā€‚conductiveā€‚partsā€‚ofā€‚theā€‚equipment.

WARNINGUNINTENDED EQUIPMENT OPERATIONDoā€‚notā€‚connectā€‚theā€‚connectorā€‚shieldā€‚toā€‚protectiveā€‚earthā€‚(PE)ā€‚orā€‚toā€‚functionalā€‚earthā€‚(FE)ā€‚ofā€‚yourā€‚installation.Failure to follow these instructions can result in death, serious injury, or equipment damage.

Ethernet Ethernet

TM171EP27R

z 24 V48 V

CAN GSCAN HCAN L

Power OUT

TM171PDM27p

USB

miniUSB

TM171PDM27p

CAN GSCAN HCAN L

TM171EP27R

z 24 V48 V

Power OUT

USB

miniUSB

Switch/RouterSwitch/Router

VPNVPN

Switch/Router

M171USB

miniUSB

M171USB

miniUSB

TM171AETHRS485

SoMachine HVAC softwareSupervisor

SoMachine HVAC softwareSupervisor

TM171AETH

TM171DGRP

GS H L

POWERCAN

CAN GSCAN HCAN LPower IN

Powery 10 m

Fig. 41. Modbusā€‚TCPā€‚protocolā€‚usingā€‚TM171AETH

Page 54: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

54 EIO0000002030 09/2015

VPNā€‚isā€‚notā€‚necessaryā€‚whenā€‚usingā€‚DynDNSā€‚connection.

Protocol Field Network

Modbusā€‚TCP -Max 10 M171 Performance + 2 M171 Performance Display Graphic

(TM171DGRP)Maxā€‚Modbusā€‚Messagesā€‚=ā€‚128ā€‚/ā€‚numberā€‚ofā€‚M171 Performance connected

Ethernet Ethernet

TM171EP27R

z 24 V48 V

CAN GSCAN HCAN L

Power OUT

TM171PDM27p

USB

miniUSB

TM171PBM27p

CAN GSCAN HCAN L

TM171EP27R

z 24 V48 V

Power OUT

USB

miniUSB

Switch/Router

M171USB

miniUSB

USB

miniUSB

TM171AETH TM171AETH

Powery 10 m

TM171EP27R

z 24 V48 V

CAN GSCAN HCAN L

Power OUT

TM171PDM27p

USB

miniUSB

M171USB

miniUSB

TM171AETH

Max 10101 2

TM171DGRP

GS H L

POWERCAN

CAN GSCAN HCAN LPower IN

Fig. 42. Modbusā€‚TCPā€‚protocolā€‚usingā€‚TM171AETHā€‚-ā€‚limits

3.5.5. Example: BACnet / IP

Protocol Field NetworkBACnet IP - Max 4 M171 Performance

Ethernet Ethernet

TM171PBM27p

CAN GSCAN HCAN L

TM171EP27R

z 24 V48 V

Power OUT

USB

miniUSB

Switch/Router

USB

miniUSB

TM171AETH

Powery 10 m

TM171EP27R

z 24 V48 V

CAN GSCAN HCAN L

Power OUT

TM171PDM27p

USB

miniUSB

M171USB

miniUSB

TM171AETH

Max 441 2

TM171DGRP

GS H L

POWERCAN

CAN GSCAN HCAN LPower IN

BAcnet Supervisor

Fig. 43. BACnetā€‚IPā€‚protocolā€‚usingā€‚Ethernetā€‚portā€‚ofā€‚theā€‚M171ā€‚Performance

Page 55: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

55EIO0000002030 09/2015

WebVisu (WEB SERVER HTTP)WebVisu is an M171 Performance TM171PDM27, TM171PBM27R with the TM171AETH Communication Module.Theā€‚Ethernetā€‚Communicationā€‚Moduleā€‚alsoā€‚usesā€‚HTTPā€‚protocol,ā€‚ i.e.ā€‚allowingā€‚accessā€‚ toā€‚aā€‚Webā€‚Serverā€‚ containedā€‚ inā€‚M171 Performance.

TM171SW (SoMachineHVAC v2.0 or greater)ā€‚allowsā€‚theā€‚creationā€‚andā€‚managementā€‚ofā€‚webā€‚pagesā€‚ internallyā€‚ofā€‚WebVisu (WEB SERVER HTTP),ā€‚i.e.ā€‚aā€‚websiteā€‚inā€‚miniature.

WEBā€‚functionalitiesā€‚allowā€‚localā€‚andā€‚remoteā€‚accessā€‚byā€‚wayā€‚ofā€‚anā€‚ordinaryā€‚browser.ā€‚Thanksā€‚toā€‚theā€‚webā€‚connection,ā€‚theā€‚systemā€‚providesā€‚reading,ā€‚supportā€‚andā€‚diagnosticsā€‚services,ā€‚asā€‚wellā€‚asā€‚e-mailā€‚alarmā€‚alerts.

Mainā€‚webā€‚functionalities:ā€¢ Web-basedā€‚access.ā€¢ Remoteā€‚readingā€‚andā€‚support.ā€¢ Localā€‚andā€‚remoteā€‚systemā€‚control,ā€‚includingā€‚alarmsā€‚management.ā€¢ Preventive and predictive maintenance.ā€¢ Email alarm alerts.

Careā€‚mustā€‚beā€‚takenā€‚andā€‚provisionsā€‚madeā€‚forā€‚useā€‚ofā€‚thisā€‚productā€‚asā€‚aā€‚controlā€‚deviceā€‚toā€‚avoidā€‚inadvertentā€‚consequencesā€‚ofā€‚commandedā€‚machineā€‚operation,ā€‚controllerā€‚stateā€‚changes,ā€‚orā€‚alterationā€‚ofā€‚dataā€‚memoryā€‚orā€‚machineā€‚operatingā€‚parameters.

WARNINGUNINTENDED EQUIPMENT OPERATION

ā€¢ Configureā€‚andā€‚installā€‚theā€‚mechanismā€‚thatā€‚enablesā€‚theā€‚remoteā€‚HMIā€‚localā€‚toā€‚theā€‚machine,ā€‚soā€‚thatā€‚localā€‚controlā€‚overā€‚theā€‚machine can be maintained regardless of the remote commands sent to the application.

ā€¢ Youā€‚mustā€‚haveā€‚aā€‚completeā€‚understandingā€‚ofā€‚theā€‚applicationā€‚andā€‚theā€‚machineā€‚beforeā€‚attemptingā€‚toā€‚controlā€‚theā€‚applica-tionā€‚remotely.

ā€¢ Takeā€‚theā€‚precautionsā€‚necessaryā€‚toā€‚assureā€‚thatā€‚youā€‚areā€‚operatingā€‚remotelyā€‚onā€‚theā€‚intendedā€‚machineā€‚byā€‚havingā€‚clear,ā€‚identifyingā€‚documentationā€‚withinā€‚theā€‚applicationā€‚andā€‚itsā€‚remoteā€‚connection.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Referā€‚toā€‚theā€‚sectionā€‚onā€‚Parametersā€‚/ā€‚ETHERNETā€‚PASSIVEā€‚PLUG-INā€‚folderā€‚(seeā€‚CHAPTER 9 Parameters on page 107).

Ethernet

TM171PDM27p

z 24 V48 V

Switch/Router

M171USB

miniUSB

TM171AETH

WebBrowser

SoMachine HVAC softwareSupervisor

SoMachine HVAC softwareSupervisor

WebBrowser

Fig. 44. WebVisuā€‚(WEBā€‚SERVERā€‚HTTP)ā€‚usingā€‚M171ā€‚Performanceā€‚andā€‚TM171AETH

Page 56: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

56 EIO0000002030 09/2015

BRIDGETM171SW (SoMachineHVAC) allows monitoring of the Modicon M171Oā€‚orā€‚M171Pā€‚controllerā€‚orā€‚thirdā€‚partyā€‚devices,ā€‚typical-lyā€‚Modbus/RTUā€‚slaves,ā€‚whereā€‚WebVisuā€‚ (orā€‚M171 Performance with TM171AETHā€‚Communicationā€‚Module)ā€‚ isā€‚ theā€‚Masterā€‚Modbus/RTU.

In a TM171SW (SoMachineHVAC)ā€‚project,ā€‚moreā€‚exactly,ā€‚WebVisuā€‚isā€‚usedā€‚asā€‚aā€‚Modbus/TCPā€‚toā€‚Modbus/RTUā€‚protocolā€‚con-versionā€‚elementā€‚forā€‚Modbusā€‚0x03ā€‚andā€‚0x10ā€‚commands.

For example from TM171SW (SoMachineHVAC),ā€‚setā€‚theā€‚connectionā€‚withā€‚theā€‚Modicon M171Oā€‚asā€‚Modbus/TCP,ā€‚insertingā€‚the WebVisuā€‚IPā€‚addressā€‚andā€‚theā€‚Modbus/RTUā€‚addressā€‚ofā€‚theā€‚Modicon M171O slave.

TM171PDM27p

TM171OFM22R

TM171ODp22p

485GS485 ā€“485 +

z 24 V48 V

Max 127

M171USB

miniUSB

RS 485

TM171PBM27p

Slaves

M171USB

miniUSB

esc

set

M171

ā€“

+

1 2 3 4 5 6 7

F1

F3

F2

F4

F5

esc

set

M171

Ethernet

Switch/Router

SoMachine HVAC softwareSupervisor

WebBrowser

SoMachine HVAC softwareSupervisor

Ethernet

TM171DBM27p

M171USB

miniUSB

TM171AETH

+-

Fig. 45. BRIDGEā€‚usingā€‚TM171AETH

TFTP (Trivial File Transfer Protocol)

TFTPā€‚canā€‚alsoā€‚beā€‚enabledā€‚forā€‚fileā€‚transferā€‚betweenā€‚PCā€‚andā€‚controllerā€‚onā€‚anā€‚Ethernetā€‚network.

Page 57: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

57EIO0000002030 09/2015

3.5.6. TM171AMBTheā€‚RS485ā€‚Communicationā€‚Moduleā€‚allowsā€‚M171/M172ā€‚DINā€‚ railā€‚mountedā€‚Performanceā€‚controllersā€‚ toā€‚communicateā€‚viaā€‚anā€‚RS485ā€‚serialā€‚usingā€‚aā€‚Modbusā€‚RTUā€‚Master/Slaveā€‚communicationā€‚protocol,ā€‚inā€‚additionā€‚toā€‚theā€‚RS485ā€‚serial.The connection allows:ā€¢ connectionā€‚toā€‚aā€‚supervisionā€‚systemā€‚usingā€‚theā€‚Modbusā€‚RTUā€‚protocol

ā€¢ connectionā€‚ofā€‚anā€‚IECā€‚61131-3ā€‚TM171SW (SoMachineHVAC)ā€‚developmentā€‚system

ā€¢ connectionā€‚toā€‚peripheralā€‚Modbusā€‚devicesā€‚(forā€‚exampleā€‚TM171EPR)

Theā€‚twoā€‚CANā€‚serialsā€‚portsā€‚(integratedā€‚andā€‚communicationā€‚module)ā€‚offerā€‚theā€‚sameā€‚levelā€‚ofā€‚services.ā€‚ M171 Performanceā€‚managesā€‚onlyā€‚oneā€‚ofā€‚theā€‚twoā€‚asā€‚Modbusā€‚Master.ā€‚Bothā€‚canā€‚operateā€‚asā€‚aā€‚Modbusā€‚Slave.

485GS485 ā€“485 +

TM171AMB

ModbusSlave

RS485

ModbusMaster

TM171PDM27p

CAN GSCAN HCAN L

Powery 10 m

TM171EP27R

z 24 V48 V

Power OUT

USB

miniUSB

M171USB

miniUSB

SoMachine HVAC softwareSupervisor

TM171AETHRS485TM171ARS485

TM171DGRPGS H L

POWERCAN

CAN GSCAN HCAN LPower IN

Fig. 46. Modbusā€‚RTUā€‚protocolā€‚usingā€‚TM171AMB

Page 58: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

58 EIO0000002030 09/2015

3.5.7. TM171ARS485 / TM171AETHRS485The connection allows M171 Performance controllersā€‚toā€‚connectā€‚toā€‚aā€‚BACnetā€‚supervisionā€‚systemā€‚usingā€‚theā€‚BACnetā€‚MS/TPā€‚communicationā€‚protocol.

485GS485 ā€“485 +

BACnet MSTP

RS485

ModbusMaster

TM171PDM27p

CAN GSCAN HCAN L

Powery 10 m

TM171EP27R

z 24 V48 V

Power OUT

USB

miniUSB

M171USB

miniUSB

SoMachine HVAC softwareSupervisor

TM171AETHRS485TM171ARS485

TM171DGRPGS H L

POWERCAN

CAN GSCAN HCAN LPower IN

485GS485 ā€“485 +

BACnet Node BACnet Node

BACnet Node

Fig. 47. ā€‚BACnetā€‚MS/TPā€‚onā€‚RSā€‚485ā€‚networkā€‚usingā€‚TM171ARS485ā€‚/ā€‚TM171AETHRS485

Page 59: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

59EIO0000002030 09/2015

3.5.8. TM171ACANTheā€‚CANā€‚Communicationā€‚Moduleā€‚allowsā€‚M171/M172ā€‚DINā€‚railā€‚mountedā€‚Performanceā€‚controllersā€‚toā€‚communicateā€‚viaā€‚aā€‚CANā€‚serialā€‚usingā€‚aā€‚CANā€‚protocolā€‚inā€‚additionā€‚toā€‚theā€‚existingā€‚CANā€‚serial.It allows:ā€¢ connectionā€‚toā€‚aā€‚supervisionā€‚systemā€‚usingā€‚theā€‚CANā€‚protocol.

ā€¢ connectionā€‚ofā€‚anā€‚IECā€‚61131-3ā€‚TM171SW (SoMachineHVAC)ā€‚developmentā€‚system.

ā€¢ connection to TM171EPR expansions.

ā€¢ connection to M171 Performance Display Graphicā€‚(TM171DGRP)ā€‚devices.

Theā€‚twoā€‚CANā€‚serialsā€‚portsā€‚(integratedā€‚andā€‚communicationā€‚module)ā€‚offerā€‚theā€‚sameā€‚levelā€‚ofā€‚services.ā€‚ M171 Performanceā€‚managesā€‚onlyā€‚oneā€‚ofā€‚theā€‚twoā€‚toā€‚pilotā€‚expansions.

Referā€‚toā€‚theā€‚sectionā€‚onā€‚Parametersā€‚/ā€‚CANā€‚PASSIVEā€‚PLUG-INā€‚folderā€‚(seeā€‚CHAPTER 9 Parameters on page 107).

TM171DGRPGS H L

POWERCAN

TM171ACAN

CAN CAN

TM171EP27R

z 24 V48 V

CAN GSCAN HCAN L

Power OUT

TM171PDM27p

USB

miniUSB

TM171PBM27p

CAN GSCAN HCAN L

Powery 10 m

TM171ACAN TM171EP27R

z 24 V48 V

Power OUT

USB

miniUSB

USB

miniUSB

M171USB

miniUSB

SoMachine HVAC softwareSupervisor

CAN GSCAN HCAN LPower IN

Fig. 48. CANā€‚protocolā€‚usingā€‚TM171ACAN

Page 60: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

60 EIO0000002030 09/2015

3.5.9. TM171APBUSTheā€‚PROFIBUSā€‚Communicationā€‚Moduleā€‚allowsā€‚M171 Performance TM171PDM27 and TM171PBM27Rā€‚ toā€‚communicateā€‚viaā€‚aā€‚Profibusā€‚serialā€‚usingā€‚theā€‚Profibusā€‚DPā€‚Slaveā€‚V-0ā€‚communicationā€‚profile.Theā€‚connectionā€‚allowsā€‚interfaceā€‚withā€‚aā€‚supervisionā€‚systemā€‚orā€‚masterā€‚controllerā€‚usingā€‚theā€‚Profibusā€‚protocol.

TM171APBUS

Profibus DP Slave V-0

Master Profibus

Profibus DP Slave V-0

TM171EP27R

z 24 V48 V

CAN GSCAN HCAN L

Power OUT

TM171PDM27p

USB

miniUSB

TM171PBM27p

CAN HCAN L

TM171APBUS TM171EP27R

z 24 V48 V

Power OUT

USB

miniUSB

M171USB

miniUSB

M171USB

miniUSB

TM171DGRPGS H L

POWERCAN

CAN GS

CAN GS

CAN HCAN LPower IN

Powery 10 m

Fig. 49. Profibusā€‚protocolā€‚usingā€‚TM171APBUS

Page 61: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

61EIO0000002030 09/2015

3.5.10. TM171ALONTheā€‚LONā€‚Communicationā€‚Moduleā€‚allowsā€‚M171/M172ā€‚DINā€‚railā€‚mountedā€‚Performanceā€‚controllersā€‚toā€‚communicateā€‚viaā€‚aā€‚LONā€‚serialā€‚usingā€‚theā€‚LonWorkSā€‚(FFT-10)ā€‚communicationā€‚profile.Theā€‚connectionā€‚allowsā€‚interfaceā€‚withā€‚aā€‚supervisionā€‚systemā€‚orā€‚masterā€‚controllerā€‚usingā€‚theā€‚LONā€‚protocol.

TM171PDM27p

z 24 V48 V

M171USB

miniUSB

TM171ALON

LON Interface

TX RX SVC

RT1

RT2

TM171PDM27p

z 24 V48 V

M171USB

miniUSB

TM171ALON

RT1

RT2

Fig. 50. LONā€‚protocolā€‚usingā€‚TM171ALON

NOTE:ā€‚Theā€‚LonWorksā€‚communicationā€‚moduleā€‚supportsā€‚upā€‚toā€‚63ā€‚nodes.ā€‚Exceedingā€‚thisā€‚specificationā€‚mayā€‚resultā€‚inā€‚anā€‚electricalā€‚overloadā€‚conditionā€‚inā€‚theā€‚M171ALONā€‚Communicationā€‚Moduleā€‚andā€‚consequentlyā€‚inā€‚theā€‚controller.

WARNINGUNINTENDED EQUIPMENT OPERATIONDoā€‚notā€‚exceedā€‚theā€‚maximumā€‚ofā€‚63ā€‚nodesā€‚onā€‚theā€‚TM171ALONā€‚Communicationā€‚Module.Failure to follow these instructions can result in death, serious injury, or equipment damage.

Forā€‚moreā€‚informationā€‚onā€‚theā€‚LonWorksā€‚network,ā€‚visitā€‚www.echelon.com/technology/lonwork/

Page 62: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

62 EIO0000002030 09/2015

3.6. Ethernet connection (for M171 Performance Flush)The M171 Performance Flush productā€‚isā€‚alsoā€‚designatedā€‚forā€‚WebVisuTheā€‚Ethernetā€‚connectionā€‚alsoā€‚allowsā€‚communicationā€‚usingā€‚HTTPā€‚protocol,ā€‚ i.e.ā€‚accessā€‚toā€‚aā€‚Webā€‚Serverā€‚containedā€‚inā€‚M171 Performance.

TM171SW (SoMachineHVAC v2.0 or greater)ā€‚allowsā€‚theā€‚creationā€‚andā€‚managementā€‚ofā€‚webā€‚pagesā€‚ internallyā€‚ofā€‚WebVisu (WEB SERVER HTTP),ā€‚i.e.ā€‚aā€‚websiteā€‚inā€‚miniature.

WEBā€‚functionalitiesā€‚allowā€‚localā€‚andā€‚remoteā€‚accessā€‚byā€‚wayā€‚ofā€‚anā€‚ordinaryā€‚browser.ā€‚Thanksā€‚toā€‚theā€‚webā€‚connection,ā€‚theā€‚systemā€‚providesā€‚reading,ā€‚supportā€‚andā€‚diagnosticsā€‚services,ā€‚asā€‚wellā€‚asā€‚e-mailā€‚alarmā€‚alerts.

Mainā€‚webā€‚functionalities:ā€¢ Web-basedā€‚access.ā€¢ Remoteā€‚readingā€‚andā€‚support.ā€¢ Localā€‚andā€‚remoteā€‚systemā€‚control,ā€‚includingā€‚alarmsā€‚management.ā€¢ Preventive and predictive maintenance.ā€¢ Email alarm alerts.

Careā€‚mustā€‚beā€‚takenā€‚andā€‚provisionsā€‚madeā€‚forā€‚useā€‚ofā€‚thisā€‚productā€‚asā€‚aā€‚controlā€‚deviceā€‚toā€‚avoidā€‚inadvertentā€‚consequencesā€‚ofā€‚commandedā€‚machineā€‚operation,ā€‚controllerā€‚stateā€‚changes,ā€‚orā€‚alterationā€‚ofā€‚dataā€‚memoryā€‚orā€‚machineā€‚operatingā€‚parameters.

WARNINGUNINTENDED EQUIPMENT OPERATION

ā€¢ Configureā€‚andā€‚installā€‚theā€‚mechanismā€‚thatā€‚enablesā€‚theā€‚remoteā€‚HMIā€‚localā€‚toā€‚theā€‚machine,ā€‚soā€‚thatā€‚localā€‚controlā€‚overā€‚theā€‚machine can be maintained regardless of the remote commands sent to the application.

ā€¢ Youā€‚mustā€‚haveā€‚aā€‚completeā€‚understandingā€‚ofā€‚theā€‚applicationā€‚andā€‚theā€‚machineā€‚beforeā€‚attemptingā€‚toā€‚controlā€‚theā€‚applica-tionā€‚remotely.

ā€¢ Takeā€‚theā€‚precautionsā€‚necessaryā€‚toā€‚assureā€‚thatā€‚youā€‚areā€‚operatingā€‚remotelyā€‚onā€‚theā€‚intendedā€‚machineā€‚byā€‚havingā€‚clear,ā€‚identifyingā€‚documentationā€‚withinā€‚theā€‚applicationā€‚andā€‚itsā€‚remoteā€‚connection.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Referā€‚toā€‚theā€‚sectionā€‚onā€‚Parametersā€‚/ā€‚ETHERNETā€‚PASSIVEā€‚PLUG-INā€‚folderā€‚(seeā€‚CHAPTER 9 Parameters on page 107).

Ethernet

Switch/RouterWebBrowser

SoMachine HVAC softwareSupervisor

WebBrowser

SoMachine HVAC softwareSupervisor

Ethernet

AI2

AI1

NTC SensorBuilt-in

RH Sensor Built-in

AI3 GS H L

POWERGSG

RS485Analogue inputs CAN

+ ā€“

AI4

TM171PFE03 / TM171PFE03HR

z 24 V48 V

Power IN

Fig. 51. WebVisuā€‚usingā€‚M171ā€‚Performanceā€‚Flush

Page 63: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

63EIO0000002030 09/2015

BRIDGETM171SW (SoMachineHVAC)ā€‚allowsā€‚monitoringā€‚ofā€‚ theā€‚Modicon M171Oā€‚orā€‚M171Pā€‚controllerā€‚orā€‚ thirdā€‚partyā€‚devices,ā€‚ typi-callyā€‚ Modbus/RTUā€‚ slaves,ā€‚ whereā€‚ WebVisuā€‚ (orā€‚ M171 Performance Flushā€‚ logicā€‚ controllerā€‚ withā€‚ Communicationā€‚ Moduleā€‚TM171AETH)ā€‚isā€‚theā€‚Masterā€‚Modbus/RTU.In a TM171SW (SoMachineHVAC)ā€‚project,ā€‚moreā€‚exactly,ā€‚WebVisuā€‚isā€‚usedā€‚asā€‚aā€‚Modbus/TCPā€‚toā€‚Modbus/RTUā€‚protocolā€‚con-versionā€‚elementā€‚forā€‚Modbusā€‚0x03ā€‚andā€‚0x10ā€‚commands.For example from TM171SW (SoMachineHVAC),ā€‚setā€‚theā€‚connectionā€‚withā€‚theā€‚Modicon M171Oā€‚asā€‚Modbus/TCP,ā€‚insertingā€‚the WebVisuā€‚IPā€‚addressā€‚andā€‚theā€‚Modbus/RTUā€‚addressā€‚ofā€‚theā€‚Modicon M171O slave.

Ethernet

AI2

AI1

NTC SensorBuilt-in

RH Sensor Built-in

AI3 GS H L

POWERGSG

RS485Analogue inputs CAN

+ ā€“

AI4

MasterTM171PFE03 / TM171PFE03HR

TM171PDM27p

TM171OFM22RTM171ODp22p

485GS485 ā€“485 +

z 24 V48 V

Max 127

M171USB

miniUSB

RS 485

Power IN

TM171PBM27p

SlavesM171USB

miniUSB

esc

set

M171

ā€“+

ā€“

+

1 2 3 4 5 6 7

F1

F3

F2

F4

F5

esc

set

M171

Ethernet

Switch/Router

SoMachine HVAC softwareSupervisor

WebBrowser

SoMachine HVAC softwareSupervisor

BRIDGE

z 24 V

Fig. 52. WebVisuā€‚usingā€‚M171ā€‚Performanceā€‚Flush

TFTP (Trivial File Transfer Protocol)TFTPā€‚(Trivialā€‚Fileā€‚Transferā€‚Protocol)ā€‚canā€‚alsoā€‚beā€‚enabledā€‚forā€‚fileā€‚transferā€‚betweenā€‚PCā€‚andā€‚controllerā€‚onā€‚anā€‚Ethernetā€‚network.

Page 64: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

64 EIO0000002030 09/2015

All M171 Performance logic controllersā€‚ systemā€‚ componentsā€‚ meetā€‚ Europeanā€‚ Communityā€‚ (CE)ā€‚ requirementsā€‚ forā€‚ openā€‚equipment.ā€‚Youā€‚mustā€‚installā€‚themā€‚inā€‚anā€‚enclosureā€‚orā€‚otherā€‚locationā€‚designedā€‚forā€‚theā€‚specificā€‚environmentalā€‚conditionsā€‚andā€‚toā€‚minimizeā€‚theā€‚possibilityā€‚ofā€‚unintendedā€‚contactā€‚withā€‚hazardousā€‚voltages.ā€‚Useā€‚metalā€‚enclosuresā€‚toā€‚improveā€‚theā€‚electromagneticā€‚immunityā€‚ofā€‚yourā€‚M171 Performance logic controllersā€‚system.ā€‚Thisā€‚equipmentā€‚meetsā€‚CEā€‚requirementsā€‚asā€‚indicatedā€‚inā€‚theā€‚table below.

WARNINGUNINTENDED EQUIPMENT OPERATIONDoā€‚notā€‚exceedā€‚anyā€‚ofā€‚theā€‚ratedā€‚valuesā€‚specifiedā€‚withinā€‚thisā€‚chapter.Failure to follow these instructions can result in death, serious injury, or equipment damage.

Applyingā€‚ incorrectā€‚ currentā€‚ orā€‚ voltageā€‚ levelsā€‚ onā€‚ analogā€‚ inputsā€‚ andā€‚ outputsā€‚ couldā€‚ damageā€‚ theā€‚ electronicā€‚ circuitry.ā€‚ Further,ā€‚ connectingā€‚aā€‚currentā€‚inputā€‚deviceā€‚toā€‚anā€‚analogā€‚inputā€‚configureā€‚forā€‚voltage,ā€‚andā€‚vice-versa,ā€‚willā€‚likewiseā€‚damageā€‚theā€‚electronicā€‚circuitry.

NOTICEINOPERABLE EQUIPMENT

ā€¢ Doā€‚notā€‚applyā€‚voltagesā€‚aboveā€‚11ā€‚Vdcā€‚toā€‚theā€‚analogā€‚inputsā€‚ofā€‚theā€‚controllerā€‚orā€‚Input/Outputā€‚expansionā€‚moduleā€‚whenā€‚analogā€‚inputā€‚isā€‚configuredā€‚asā€‚0-10ā€‚Vā€‚input.

ā€¢ Doā€‚notā€‚applyā€‚currentā€‚aboveā€‚30ā€‚mAā€‚toā€‚theā€‚analogā€‚inputsā€‚ofā€‚theā€‚controllerā€‚orā€‚Input/Outputā€‚expansionā€‚moduleā€‚whenā€‚analogā€‚inputā€‚isā€‚configuredā€‚asā€‚0-20ā€‚mAā€‚orā€‚4-20ā€‚mAā€‚input.

ā€¢ Doā€‚notā€‚mismatchā€‚appliedā€‚signalā€‚withā€‚analogā€‚inputā€‚configuration.Failure to follow these instructions can result in equipment damage.

4.1. General specificationsStandard Min Max

Supplyā€‚voltage1 +24ā€‚Vac/dcā€‚Ā±20%ā€‚orā€‚+48ā€‚Vdcā€‚Ā±20%ā€‚ 21ā€‚V 60ā€‚VSupplyā€‚voltageā€‚TM171EP14R +24ā€‚Vac/dcā€‚Ā±10%ā€‚NOTā€‚ISOLATED 20ā€‚V 38ā€‚VSupplyā€‚frequency 50ā€‚Hzā€‚/ā€‚60ā€‚Hz --- ---

Power draw

22ā€‚VAā€‚/ā€‚18ā€‚Wā€‚(M171 Performance)16ā€‚VAā€‚/ā€‚7ā€‚Wā€‚maxā€‚(M171EP14R)

5ā€‚Wā€‚(M171 Performance Flush and M171 Display Graphic)

--- ---

Insulationā€‚class 2 --- ---Ambientā€‚operatingā€‚temperature 25ā€‚Ā°Cā€‚/ā€‚77ā€‚Ā°F -10ā€‚Ā°Cā€‚/ā€‚14ā€‚Ā°F +55Ā°C/ā€‚+131ā€‚Ā°FAmbientā€‚operatingā€‚temperatureā€‚ of M171 Performance Display Graphic (TM171DGRP)

25ā€‚Ā°Cā€‚/ā€‚77ā€‚Ā°F -5Ā°Cā€‚/ā€‚23ā€‚Ā°F +55Ā°C/ā€‚+131ā€‚Ā°F

Ambientā€‚operatingā€‚humidityā€‚(non-condensing) 30% 10% 90%Ambientā€‚storageā€‚temperature 25ā€‚Ā°Cā€‚/ā€‚77ā€‚Ā°F -20ā€‚Ā°Cā€‚/ā€‚-4ā€‚Ā°F +85Ā°Cā€‚/ā€‚+185ā€‚Ā°F

Ambientā€‚storageā€‚humidityā€‚(non-condensing) 30% 10% 90%

1 For M171 Performance Flush / M171 Performance Display Graphicā€‚ (TM171DGRP):ā€‚poweredā€‚byā€‚M171 Performance TM171PDM27 / TM171PBM27Rā€‚orā€‚directlyā€‚fromā€‚anā€‚independent,ā€‚properlyā€‚ratedā€‚powerā€‚supply.

CHAPTER 4 Technical data

Page 65: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

65EIO0000002030 09/2015

NOTE: Whenā€‚supplyingā€‚powerā€‚fromā€‚theā€‚M171 Performance logic controllers,ā€‚makeā€‚theā€‚powerā€‚connectionā€‚cableā€‚asā€‚shortā€‚as possible.

NOTICEINOPERABLE EQUIPMENTDo not connect a power cable longer than 10m.Failure to follow these instructions can result in equipment damage.

ClassificationTheā€‚productā€‚compliesā€‚withā€‚theā€‚followingā€‚harmonizedā€‚regulations: ENā€‚60730-2-6ā€‚/ā€‚ENā€‚60730-2-9ā€‚/ā€‚ENā€‚60730-1

Use Inā€‚termsā€‚ofā€‚construction,ā€‚asā€‚anā€‚independentlyā€‚mountedā€‚tem-perature-sensitiveā€‚automaticā€‚electronicā€‚controller

Mounting Panel,ā€‚wallā€‚orā€‚onā€‚DINā€‚Omegaā€‚barā€‚supportTypeā€‚ofā€‚action 1.Bā€‚ā€“ā€‚1.YPollutionā€‚class 2ā€‚(normal)Overā€‚voltageā€‚category IINominalā€‚pulseā€‚voltage 2500VDigitalā€‚outputs refer to the label on the deviceFireā€‚resistanceā€‚category DSoftwareā€‚classā€‚andā€‚structure ATypeā€‚ofā€‚disconnectionā€‚orā€‚suspensionā€‚forā€‚eachā€‚circuit Microswitch disconnectionPTIā€‚ofā€‚materialsā€‚usedā€‚forā€‚insulation PTIā€‚250VPeriodā€‚ofā€‚electricalā€‚stressā€‚onā€‚theā€‚insulatingā€‚parts Longā€‚period

Page 66: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

66 EIO0000002030 09/2015

4.2. I/O features

4.2.1. M171 Performance I/O featuresM171 Performanceā€‚featuresā€‚forā€‚inputsā€‚andā€‚outputs.

Type and Label No. DescriptionTM171PDM27RTM171PBM27RTM171EP27R

TM171PDM27S

Digitalā€‚inputā€‚DI1ā€¦DI8 8

8ā€‚opto-isolatedā€‚digitalā€‚inputsWorkingā€‚voltageā€‚+24ā€‚Vac/dcā€‚Ā±20%ā€‚orā€‚+48ā€‚Vdcā€‚Ā±20%

Power draw max. 5 mADigitalā€‚inputsā€‚canā€‚beā€‚usedā€‚asā€‚pulseā€‚counters.ā€‚Theā€‚

lengthā€‚ofā€‚theā€‚pulseā€‚(positiveā€‚orā€‚negative)ā€‚mustā€‚beā€‚gre-ater than 12 ms.

See CHAPTER 8 Physical I/O and ports configura-tion on page 92.

p p

Digitalā€‚inputFAST DI 1

1ā€‚no-voltageā€‚digitalā€‚inputā€‚ (Pulseā€‚countā€‚+ā€‚Readā€‚frequency)

Note:ā€‚measureā€‚aā€‚signalā€‚withā€‚aā€‚maximumā€‚frequencyā€‚ofā€‚1ā€‚kHz

See CHAPTER 8 Physical I/O and ports configura-tion on page 92.

p p

Relayā€‚digitalā€‚outputsHighā€‚voltageDO1, DO2

7

2ā€‚ā€‚xā€‚ā€‚8ā€‚Aā€‚250ā€‚Vacā€‚relays p -

Relayā€‚digitalā€‚outputsHighā€‚voltageDO3ā€¦DO7

5ā€‚ā€‚xā€‚ā€‚5ā€‚Aā€‚250ā€‚Vacā€‚relays p -

Relayā€‚digitalā€‚outputsHighā€‚voltageDO1, DO2

5

2ā€‚ā€‚xā€‚ā€‚8ā€‚Aā€‚250ā€‚Vacā€‚relays - p

Relayā€‚digitalā€‚outputsHighā€‚voltage

DO5, DO6, DO73ā€‚ā€‚xā€‚ā€‚5ā€‚Aā€‚250ā€‚Vacā€‚relays - p

SSRā€‚digitalā€‚outputsHighā€‚voltageDO3, DO4

2 2ā€‚ā€‚xā€‚1ā€‚Aā€‚250ā€‚Vacā€‚SSR - p

Analogā€‚outputsAO1ā€¦AO5 5

5ā€‚xā€‚0-10ā€‚Vā€‚/ā€‚4..20mAā€‚/ā€‚ON-OFFā€‚configurableā€‚outputs:ā€¢ 0..10V2%ā€‚fullā€‚scaleā€‚Min.loadā€‚500ā€‚Ī©;ā€‚1%ā€‚fullā€‚scaleā€‚withā€‚loadā€‚greaterā€‚thanā€‚5ā€‚kĪ©ā€¢ 4ā€¦20mA2%ā€‚fullā€‚scaleā€‚max.ā€‚400ā€‚Ī©ā€¢ ON-OFFMax.loadā€‚400ā€‚Ī©

Note:ā€‚AO4ā€‚andā€‚AO5ā€‚canā€‚beā€‚configuredā€‚asā€‚Openā€‚Collector. See CHAPTER 8 Physical I/O and ports configuration on page 92.

p p

Analogā€‚inputsAI1 AI2AI3 AI4AI5 AI6

6 See the following table p p

Page 67: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

67EIO0000002030 09/2015

NTCā€‚(NK103)10ā€‚kĪ©ā€‚atā€‚25ā€‚Ā°Cā€‚(77ā€‚Ā°F)BETAā€‚valueā€‚3435

DIā€‚(1)

NTC (103AT-2)

10ā€‚kĪ©ā€‚atā€‚25ā€‚Ā°Cā€‚(77ā€‚Ā°F)BETAā€‚valueā€‚3435

4-20ā€‚mA 0-10ā€‚V

AI1 p p p - -

AI2 p p p - -

AI3 p p p p p

AI4 p p p p p

AI5 p p p p p

AI6 p p p p p

Range -40ā€¦+150ā€‚Ā°Cā€‚(-40...+302ā€‚Ā°F) - -50...+110ā€‚Ā°C

(-58...+230ā€‚Ā°F) 0ā€¦1000 0ā€¦1000

Accuracy 0.5%ā€‚fullā€‚scale+ 1 digit - 0.5%ā€‚fullā€‚scale

+ 1 digit

1%ā€‚fullā€‚scale+

1 digit

1%ā€‚fullā€‚scale+

1 digitResolution 0.1Ā°C - 0.1ā€‚Ā°C 1 digit 1 digit

Input impedance 10ā€‚kĪ© 20ā€‚kĪ© 10ā€‚kĪ© 100ā€‚Ī© 21ā€‚kĪ©

(1)ā€‚DIā€‚Digitalā€‚Input:ā€‚voltageā€‚freeā€‚digitalā€‚input.

0-5ā€‚VRatiometric

(1)PT1000 hĪ©ā€‚(NTC) daĪ©

(PT1000)

AI1 - - - -

AI2 - - - -

AI3 p p p p

AI4 p p p p

AI5 p p p p

AI6 p p p p

Range 0ā€¦1000 -200...+800ā€‚Ā°C(-328...+1472ā€‚Ā°F) 0...150ā€‚kĪ©ā€‚ 0ā€¦30ā€‚kĪ©

Accuracy1%ā€‚fullā€‚scale

+ 1 digit

0.5%ā€‚fullā€‚scale+

1 digit

1%ā€‚fullā€‚scale+

1 digit

1%ā€‚fullā€‚scale+

1 digitResolution 1 digit 0.1ā€‚Ā°C 1ā€‚hĪ© 1ā€‚daĪ©

Input impedance 21ā€‚kĪ© 2ā€‚kĪ© 10ā€‚kĪ© 2ā€‚kĪ©

(1)ā€‚0-5ā€‚Vā€‚Ratiometric.ā€‚50ā€‚mAā€‚maximumā€‚currentā€‚atā€‚5ā€‚V

Also see 8.1.1. Analog inputs configuration for M171 Performance on page 93ā€‚ forā€‚ instructionsā€‚onā€‚offsetsā€‚andā€‚calibra-tions.

Page 68: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

68 EIO0000002030 09/2015

4.2.2. M171EP14R Performance I/O featuresM171EP14R Performanceā€‚featuresā€‚forā€‚inputsā€‚andā€‚outputs.

Type and Label No. Description TM171EP14R

Digitalā€‚inputā€‚DI1ā€¦DI4 4

4ā€‚digitalā€‚inputsā€‚NOTā€‚ISOLATEDWorkingā€‚voltageā€‚24ā€‚Vac/dcā€‚Ā±10%ā€‚(Vac:ā€‚maxā€‚38Vac)

Power draw max. 5mAp

Relayā€‚digitalā€‚outputsHighā€‚voltageDO1...DO4

41ā€‚ā€‚xā€‚ā€‚5Aā€‚250ā€‚Vacā€‚SPDTā€‚relay3ā€‚ā€‚xā€‚ā€‚3Aā€‚250ā€‚Vacā€‚SPSTā€‚relays

(commonā€‚maxā€‚10A)p

Analogā€‚outputsAO1ā€¦AO2 2 2ā€‚xā€‚0-10ā€‚Vā€‚outputs:

4%ā€‚fullā€‚scaleā€‚Min.loadā€‚5KĪ©;ā€‚2%ā€‚fullā€‚scaleā€‚withā€‚loadā€‚greaterā€‚thanā€‚5KĪ© p

Analogā€‚inputsAI1 AI2AI3 AI4

4 See the following table p

NTCā€‚(NK103)10ā€‚kĪ©ā€‚atā€‚25ā€‚Ā°Cā€‚(77ā€‚Ā°F)BETAā€‚valueā€‚3435

DIā€‚(1)NTCā€‚(103AT-2)

10ā€‚kĪ©ā€‚atā€‚25ā€‚Ā°Cā€‚(77ā€‚Ā°F)BETAā€‚valueā€‚3435

4-20ā€‚mA 0-10ā€‚V

AI1 p p p - -

AI2 p p p - -AI3 p p p p p

AI4 p p p p p

Range -40ā€¦+137ā€‚Ā°C(-40...+278.6ā€‚Ā°F) - -50Ā°...+110ā€‚Ā°C

(-58...230ā€‚Ā°F) 0ā€¦1000 0ā€¦1000

Accuracy 0.5%ā€‚fullā€‚scale+ 1 digit - 0.5%ā€‚fullā€‚scale

+ 1 digit

1%ā€‚fullā€‚scale+

1 digit

1%ā€‚fullā€‚scale+

1 digitResolution 0.1ā€‚Ā°C - 0.1ā€‚Ā°C 1 digit 1 digit

Input impedance 10ā€‚kĪ© 10ā€‚kĪ© 10ā€‚kĪ© <200ā€‚Ī© >10ā€‚kĪ©

(1)ā€‚DIā€‚Input:ā€‚voltageā€‚freeā€‚digitalā€‚input.

0-5ā€‚V(1) PT1000 hĪ©ā€‚(NTC) daĪ©

(PT1000)PTC

(KTY81)

AI1 - - - - p

AI2 - - - - p

AI3 p p p p p

AI4 p p p p p

Range 0ā€¦1000 -200..+295ā€‚Ā°C(-328...+563ā€‚Ā°F) 0..150ā€‚kĪ©ā€‚ 0ā€¦30ā€‚kĪ© -50Ā°Cā€‚..+150ā€‚Ā°C

(-58...+302ā€‚Ā°F)

Accuracy1%ā€‚fullā€‚scale

+ 1 digit

0.5%ā€‚fullā€‚scale+

1 digit

1%ā€‚fullā€‚scale+

1 digit

1%ā€‚fullā€‚scale+

1 digit

0.5%ā€‚fullā€‚scale+

1 digitResolution 1 digit 0.1ā€‚Ā°C 1ā€‚hĪ© 1ā€‚daĪ© 0.1ā€‚Ā°C

Input impedance >20ā€‚kĪ© 2ā€‚kĪ© 10ā€‚kĪ© 2ā€‚kĪ© 2ā€‚kĪ©

(1)ā€‚Ratiometric.ā€‚50ā€‚mAā€‚maximumā€‚currentā€‚atā€‚5ā€‚V

Also see 8.1.1. Analog inputs configuration for M171 Performance on page 93ā€‚ forā€‚ instructionsā€‚onā€‚offsetsā€‚andā€‚calibra-tions.

Page 69: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

69EIO0000002030 09/2015

4.2.3. M171 Performance Flush I/O featuresM171 Performance Flushā€‚featuresā€‚forā€‚inputs.

Type and Label

Analog inputs

Probe Description Resolution Accuracy Measurementrange Impedance

TM17

1PFE

03

TM17

1PFE

03H

R

AI1 On-board NTC 0.1ā€‚Ā°Cā€‚/ā€‚Ā°F 0.5%ā€‚fullā€‚scale + 1 digit - 10ā€‚kĪ© p p

AI2configurable

Remote

NOT included

NTC 103AT 0.1ā€‚Ā°Cā€‚/ā€‚Ā°F 0.5%ā€‚fullā€‚scale + 1 digit

-50ā€¦+110ā€‚Ā°C(-58...230ā€‚Ā°F) 10ā€‚kĪ©

p pNTC NK103 0.1ā€‚Ā°Cā€‚/ā€‚Ā°F 0.5%ā€‚fullā€‚scale + 1 digit

-40ā€¦+150ā€‚Ā°C(-40...302ā€‚Ā°F) 10ā€‚kĪ©

D.I.(1)ā€‚ - - - 20ā€‚kĪ©

AI3configurable

Remote

NOT included

4...20 mA 1 digit 1%ā€‚fullā€‚scale + 1 digit 0ā€¦1000 100ā€‚Ī© p -

0-5ā€‚Vā€‚(2)ā€‚ 1 digit 1%ā€‚fullā€‚scale + 1 digit 0ā€¦1000 21ā€‚kĪ© - -

0..10ā€‚V 1 digit 1%ā€‚fullā€‚scale + 1 digit 0ā€¦1000 21ā€‚kĪ© - -

AI4 On-board On-boardā€‚%RHā€‚input

0.01ā€‚%RH(0%=0pt,

100%ā€‚=ā€‚1000pt)

Ā±3%ā€‚[20...80%]ā€‚Ā±5%ā€‚ā€¦elsewhere 0-100ā€‚%RH - - p

(1)ā€‚D.I.ā€‚Digitalā€‚Inputā€‚voltage-free.(2)ā€‚50ā€‚mAā€‚maximumā€‚currentā€‚atā€‚5ā€‚V.ā€‚

Also see 8.1.2. Analog inputs configuration for M171EP14R on page 94ā€‚forā€‚instructionsā€‚onā€‚offsetsā€‚andā€‚calibrations.

Page 70: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

70 EIO0000002030 09/2015

4.3. DisplayM171 Performance TM171PDM27ā€‚references,ā€‚remoteā€‚displayā€‚andā€‚M171 Performance Flush:ā€¢ backlitā€‚withā€‚LEDs

ā€¢ 3ā€‚LEDsLEDsā€‚andā€‚backlightingā€‚canā€‚beā€‚controlledā€‚fromā€‚application.

4.3.1. M171 Performance Display Graphic / M171 Performance Flush displayDisplay Monochromaticā€‚LCDā€‚graphicā€‚displayā€‚128x64pxā€‚backlitā€‚withā€‚LEDs

Container Backplateā€‚ +ā€‚ frameā€‚ inā€‚ PC+ABSā€‚UL94ā€‚V-0ā€‚ plasticā€‚ resin,ā€‚ transparentā€‚ polycarbonateā€‚ frontā€‚cover,ā€‚polyesterā€‚membraneā€‚keypad

4.4. SerialsSerial Description Notes References

CAN CANā€‚Expansionā€‚Bus

maxā€‚50ā€‚mā€‚atā€‚500ā€‚kpbs;ā€‚200ā€‚mā€‚atā€‚125ā€‚kpbs.

TM171PTM171EPRM171 Performance Display Graphic (TM171DGRP)

Ifā€‚necessary,ā€‚apply aā€‚120ā€‚Ī©ā€‚termina-tion resistor to both the ends.

RS 485 2ā€‚xā€‚RSā€‚485ā€‚serial

If the controller is connected at the endā€‚ ofā€‚ theā€‚ RSā€‚ 485ā€‚ communicationā€‚line,ā€‚ applyā€‚ aā€‚ 120ā€‚ Ī©ā€‚ terminationā€‚ resi-storā€‚ betweenā€‚ lineā€‚ +ā€‚ andā€‚ lineā€‚ -ā€‚ ofā€‚ theā€‚RSā€‚485ā€‚

TM171PTM171EP27R

Onlyā€‚ oneā€‚ RSā€‚ 485ā€‚ serialā€‚ portā€‚ canā€‚ beā€‚configuredā€‚ asā€‚Modbusā€‚masterā€‚ atā€‚ theā€‚same time.

USB

1ā€‚Typeā€‚Aā€‚USBā€‚femaleā€‚connectorā€‚(Host)

ā€˜Mass Storageā€™ profileExternalā€‚memory,ā€‚FAT32 formatting.

TM171P1ā€‚Typeā€‚mini-Bā€‚USBā€‚femaleā€‚

connectorā€‚(Device)Connection between PC and device throughā€‚USBā€‚standardā€‚CDCā€‚profile.

ETHERNET Modbusā€‚TCPā€‚ETHERNETā€‚port

Equipment includesā€‚ MACADDRESS,ā€‚inā€‚barcodeā€‚andā€‚12-digitā€‚alphanumericā€‚format.

M171 Performance Flush

Payā€‚specialā€‚attentionā€‚whenā€‚connectingā€‚serialā€‚lines.ā€‚Miswiringā€‚mayā€‚leadā€‚toā€‚inoperableā€‚equipment.

NOTICEINOPERABLE EQUIPMENTā€¢ Doā€‚notā€‚connectā€‚equipmentsā€‚thatā€‚communicateā€‚usingā€‚RSā€‚485ā€‚serialā€‚toā€‚CANā€‚Expansionā€‚Busā€‚terminals.ā€¢ Doā€‚notā€‚connectā€‚equipmentsā€‚thatā€‚communicateā€‚usingā€‚CANā€‚Expansionā€‚Busā€‚toā€‚RSā€‚485ā€‚terminals.Failure to follow these instructions can result in equipment damage.

Page 71: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

71EIO0000002030 09/2015

4.4.1. TM171A Communication ModuleSerial Notes Terminals

TM171ARS232 RS232ā€‚Nullmodem Digitalā€‚outputs1ā€‚xā€‚SPDTā€‚5ā€‚Aā€‚250ā€‚Vacā€‚relay

terminalsā€‚1...3ā€‚screwā€‚typeā€‚removable,ā€‚spacingā€‚5,ā€‚90Ā°ā€‚insertionā€‚forā€‚cablesā€‚withā€‚2.5ā€‚

mm2 cross-section.ā€‚+ā€‚DB9ā€‚connector

TM171ACAN Doubleā€‚serialā€‚port Opto-isolatedā€‚CANā€‚serialremovableā€‚screwā€‚typeā€‚,ā€‚spacingā€‚3.81,ā€‚90Ā°ā€‚insertion for cables with 2.5 mm2 cross-

section.

TM171AMBTM171ARS485 Doubleā€‚serialā€‚port Opto-isolatedā€‚RS485ā€‚serial

removableā€‚screwā€‚typeā€‚,ā€‚spacingā€‚3.81,ā€‚90Ā°ā€‚insertion for cables with 2.5 mm2 cross-

section.

TM171AETH Modbusā€‚TCPā€‚ETHERNETā€‚port - RJ45ā€‚connector

TM171AETHRS485Modbusā€‚TCPā€‚

ETHERNETā€‚portDoubleā€‚serialā€‚port

Opto-isolatedā€‚RS485ā€‚serial

RJ45ā€‚connectorremovableā€‚screwā€‚typeā€‚,ā€‚spacingā€‚3.81,ā€‚90Ā°ā€‚insertion for cables with 2.5 mm2 cross-

section.

TM171ALON LON - -

TM171APBUS Profibusā€‚DPā€‚Slave-V0 - -

Page 72: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

72 EIO0000002030 09/2015

4.5. Power supply

The M171 Performance logic controllersā€‚ andā€‚ associatedā€‚ devicesā€‚ requireā€‚ powerā€‚ suppliesā€‚ withā€‚ aā€‚ nominalā€‚ voltageā€‚ ofā€‚ 24ā€‚Vacā€‚/ā€‚24ā€‚Vdcā€‚orā€‚48ā€‚Vdc.ā€‚Theā€‚powerā€‚supplies/transformersā€‚mustā€‚beā€‚ratedā€‚Safetyā€‚Extraā€‚Lowā€‚Voltageā€‚(SELV)ā€‚accordingā€‚toā€‚IECā€‚61140.ā€‚Theseā€‚sourcesā€‚ofā€‚powerā€‚areā€‚isolatedā€‚betweenā€‚theā€‚electricalā€‚inputā€‚andā€‚outputā€‚circuitsā€‚ofā€‚theā€‚powerā€‚supplyā€‚asā€‚wellā€‚asā€‚simpleā€‚separationā€‚fromā€‚groundā€‚(earth),ā€‚PELVā€‚andā€‚otherā€‚SELVā€‚systems.

DANGERGROUND LOOP CAUSING ELECTRIC SHOCK AND/OR INOPERABLE EQUIPMENT

ā€¢ Doā€‚notā€‚connectā€‚theā€‚0ā€‚Vā€‚powerā€‚supply/transformerā€‚connectionā€‚supplyingā€‚thisā€‚equipmentā€‚toā€‚anyā€‚externalā€‚groundā€‚(earth)ā€‚connection.

ā€¢ Doā€‚notā€‚connectā€‚anyā€‚0ā€‚Vā€‚orā€‚groundā€‚(earth)ā€‚ofā€‚theā€‚sensorsā€‚andā€‚actuatorsā€‚connectedā€‚toā€‚thisā€‚equipmentā€‚toā€‚anyā€‚externalā€‚groundā€‚connection.

ā€¢ Ifā€‚necessary,ā€‚useā€‚separateā€‚powerā€‚supplies/transformersā€‚toā€‚powerā€‚sensorsā€‚orā€‚actuatorsā€‚isolatedā€‚fromā€‚thisā€‚equipment.Failure to follow these instructions will result in death or serious injury.

Ifā€‚theā€‚specifiedā€‚voltageā€‚rangeā€‚isā€‚notā€‚maintained,ā€‚orā€‚theā€‚effectiveā€‚separationā€‚ofā€‚theā€‚SELVā€‚circuitā€‚connectedā€‚toā€‚theā€‚concernedā€‚equipmentā€‚isā€‚compromised,ā€‚theā€‚productsā€‚mayā€‚notā€‚functionā€‚asā€‚intendedā€‚orā€‚mayā€‚becomeā€‚damagedā€‚andā€‚inoperable.

WARNINGPOTENTIAL OF OVERHEATING AND FIRE

ā€¢ Doā€‚notā€‚connectā€‚theā€‚equipmentā€‚directlyā€‚toā€‚lineā€‚voltage.ā€¢ Useā€‚onlyā€‚isolatingā€‚SELVā€‚powerā€‚supplies/transformersā€‚toā€‚supplyā€‚powerā€‚toā€‚thisā€‚equipment.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Theā€‚equipmentā€‚mustā€‚beā€‚connectedā€‚toā€‚aā€‚suitableā€‚powerā€‚supply/transformersā€‚withā€‚theā€‚followingā€‚features:

Primaryā€‚voltage Dependingā€‚onā€‚requirementsā€‚ofā€‚theā€‚individualā€‚deviceā€‚and/orā€‚countryā€‚ofā€‚installation.Secondaryā€‚voltage +24ā€‚Vac/dcā€‚Ā±20%ā€‚orā€‚+48ā€‚Vdcā€‚Ā±20%Powerā€‚supplyā€‚frequencyā€‚Vac 50/60ā€‚Hz

Power minimumā€‚18ā€‚Wā€‚(M171 Performance)minimumā€‚5ā€‚Wā€‚(M171 Performance Flush)

4.6. Mechanical dimensionsLength (L)

mmin

Depth (d) mmin

Height (H) mmin

Notes

M171 PerformanceTM171PDM27 / TM171PBM27R / TM171EP27R

140 5.51

61.6 2.42

110 4.33 -

M171 Performance TM171EP14R 70 2.75

61.6 2.42

87 3.42 -

TM171A Communication Module 35 1.38

61.6 2.42

110 4.33 -

M171 Performance Display Graphicā€‚(TM171DGRP)M171 Performance Flush

160 6.3

10 0.39

96 3.8 -

Opening for panel-mounting of M171 Performance Display Graphic (TM171DGRP) or M171

Performance Flush

138 5.43 - 68

2.68 (+0.2mmā€‚/ā€‚-0.1mm)

Page 73: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

73EIO0000002030 09/2015

mmin

0.4912.55

5.51140

1.6441.8

0.9524.25

2.7670.2

3.4287

4.33

110

2.80

71.2

2.99761.7745

Fig. 53. TM171PDM27ā€‚/ā€‚TM171PBM27Rā€‚/ā€‚TM171EP27Rā€‚/ā€‚TM171EP14R

4.33

110

2.80

71.2

2.99761.7745

mmin0.95

24.25

0.4912.55

1.3835

1.6441.8

Fig. 54. TM171A

A B

DC

E F

mmin

5.43138

5.90150

3.5490

2.6868 3.3084

0.112.7

x6

Fig. 55. Panelā€‚openingā€‚dimensionsā€‚forā€‚M171ā€‚Performanceā€‚Displayā€‚Graphicā€‚(TM171DGRP)ā€‚orā€‚M171ā€‚Performanceā€‚Flush

Page 74: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

74 EIO0000002030 09/2015

Theā€‚interface,ā€‚comprisingā€‚theā€‚frontā€‚coverā€‚ofā€‚theā€‚controller,ā€‚allowsā€‚youā€‚toā€‚performā€‚operationsā€‚toā€‚useā€‚theā€‚device.

5.1. Keys and LEDsTheā€‚dataā€‚providedā€‚forā€‚keysā€‚refersā€‚toā€‚TM171PDM27 references.

The TM171PBM27Rā€‚moduleā€‚hasā€‚noā€‚display.ā€‚Useā€‚theā€‚M171 Performance Display Graphicā€‚(TM171DGRP)ā€‚toā€‚workā€‚onā€‚thisā€‚controller.The TM171EPRā€‚expansionā€‚moduleā€‚hasā€‚noā€‚display.

M171USB

miniUSB

M171USB

miniUSB

21345

A

B

C

Fig. 56. TM171PDM27

Theā€‚keysā€‚canā€‚beā€‚programmedā€‚fromā€‚theā€‚controllerā€‚application.ā€‚Byā€‚default,ā€‚theā€‚deviceā€‚displaysā€‚aā€‚shortā€‚menuā€‚containingā€‚thefollowingā€‚defaultā€‚settings.

No. Key Press once (press and release)

1ā€¢ Scrollā€‚upā€¢ Increase/modifyā€‚aā€‚valueā€¢ Go to next labelUP

2 OK

ā€¢ Scroll downā€¢ Moveā€‚toā€‚nextā€‚level/menuā€‚(openā€‚folder,ā€‚subfolder,ā€‚parameter,ā€‚value)ā€¢ Enter/exitā€‚Editā€‚modeā€¢ Confirm operation

3 RIGHT ā€¢ Moveā€‚cursorā€‚toā€‚rightā€‚inā€‚Editā€‚Mode

4 DOWNā€¢ Scroll downā€¢ Decrease/modifyā€‚aā€‚valueā€¢ Goā€‚toā€‚previousā€‚label

5 Exit

ā€¢ Exitā€‚menuā€‚pageā€‚/ā€‚goā€‚backā€‚toā€‚previousā€‚menuā€¢ Moveā€‚cursorā€‚toā€‚leftā€‚inā€‚Editā€‚Modeā€¢ (pressā€‚andā€‚hold)ā€‚Exitā€‚Editā€‚Modeā€‚withoutā€‚saving

Theā€‚LEDsā€‚canā€‚beā€‚programmedā€‚fromā€‚theā€‚application.

CHAPTER 5 M171 Performance User Interface

Page 75: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

75EIO0000002030 09/2015

Byā€‚default,ā€‚theyā€‚areā€‚usedā€‚forā€‚USBā€‚managementā€‚-ā€‚seeā€‚theā€‚relativeā€‚sectionā€‚onā€‚USB-Handlingā€‚(seeā€‚3.1.6. Serial connections on page 27).

LEDs DescriptionA B C A,ā€‚Bā€‚andā€‚Cā€‚LEDsā€‚areā€‚programmableā€‚viaā€‚controllerā€‚application

5.2. First power onWhenā€‚theā€‚equipmentā€‚isā€‚poweredā€‚onā€‚forā€‚theā€‚firstā€‚time,ā€‚aā€‚fewā€‚summaryā€‚pagesā€‚areā€‚displayedā€‚showingā€‚systemā€‚status(SYSTEM INFO).

SYSTEM INFOHW

BIOSDATEBOOT

EEPROM

NORā€‚FLASH OKNANDā€‚FLASH OK

SDRAM OKBATRAM OKRTC OKPlug-in NoneUSB-H OKUSB-D Service area

5.3. MenuM171 Performanceā€‚hasā€‚aā€‚minimalā€‚systemā€‚menuā€‚toā€‚configureā€‚inputs/outputs,ā€‚displayā€‚I/Oā€‚valuesā€‚andā€‚USBā€‚operationsā€‚wherepresentā€‚(TM171PDM27ā€‚references).

Theā€‚Userā€‚interfaceā€‚isā€‚availableā€‚inā€‚Englishā€‚only.

5.3.1. System MenuSystemā€‚Menu

BIOSā€‚ConfigurationBIOSā€‚I/Oā€‚ValuesBIOSā€‚RTCā€‚ValuesUSB-Hostā€‚Handling

Page 76: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

76 EIO0000002030 09/2015

5.3.2. BIOS ConfigurationParameterā€‚configurationā€‚menu.ā€‚Seeā€‚CHAPTER 9 Parameters on page 107.

BIOSā€‚ConfigurationAnalogā€‚InputAnalogā€‚Output

On-boardā€‚RS485On-boardā€‚CAN

Theā€‚tableā€‚belowā€‚listsā€‚theā€‚parametersā€‚thatā€‚canā€‚beā€‚configuredā€‚fromā€‚theā€‚LCDā€‚displayā€‚(TM171PDM27ā€‚reference)ā€‚and/orā€‚M171 Performance Display Graphicā€‚(TM171DGRP).Theā€‚menuā€‚forā€‚parameterā€‚configurationā€‚isā€‚System Menu > BIOS Configuration.

BIOSā€‚Configuration Parameter Folder

Analogā€‚Input ANALOGINPUTS

Analogā€‚Output ANALOGOUTPUTSā€‚V/I

On-boardā€‚RS485 On-boardRS485

On-boardā€‚CAN On-boardCAN

5.3.3. BIOS I/O ValuesShowsā€‚inputā€‚(readā€‚only)ā€‚andā€‚outputā€‚valuesā€‚(modifiable).

BIOSā€‚I/Oā€‚ValuesAnalogā€‚InputAnalogā€‚OutputDigitalā€‚OutputDigitalā€‚Input

Inputsā€‚areā€‚readā€‚only.ā€‚Digitalā€‚inputā€‚example:

Digitalā€‚InputDI1 Off DI5 OffDI2 Off DI6 OffDI3 Off DI7 OffDI4 Off DI8 Off

Theā€‚analogā€‚andā€‚digitalā€‚outputsā€‚areā€‚modifiable.Moveā€‚theā€‚cursorā€‚toā€‚theā€‚resourceā€‚required.Press the OKā€‚keyā€‚toā€‚enterā€‚Editā€‚Mode.ā€‚Useā€‚theā€‚UP and DOWNā€‚keysā€‚toā€‚modifyā€‚value.ā€‚Confirmā€‚withā€‚theā€‚OKā€‚key.Analogā€‚outputā€‚example.

Analogā€‚Outputā€‚1/2AO1ā€‚ā€‚0.2ā€‚ā€‚%AO2ā€‚ā€‚0.0ā€‚ā€‚%AO3ā€‚ā€‚0.0ā€‚ā€‚%

Vā€‚Prev Next ^

Page 77: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

77EIO0000002030 09/2015

Digitalā€‚Outputā€‚example.

Digitalā€‚OutputDO1 On DO5 OffDO2 Off DO6 OffDO3 Off DO7 OffDO4 Off

5.3.4. BIOS RTC ValuesShowsā€‚timeā€‚(HHā€‚:ā€‚MMā€‚:ā€‚SS)ā€‚andā€‚dateā€‚(DDā€‚/ā€‚MMā€‚/ā€‚YY)ā€‚internalā€‚clock.

BIOSā€‚RTCā€‚Values

16 : 50 : 5630ā€‚/ā€‚10ā€‚/ā€‚10RTCā€‚set

Press OK.Selectā€‚theā€‚valueā€‚thatā€‚youā€‚wantā€‚toā€‚modify.Press the OKā€‚keyā€‚toā€‚enterā€‚Editā€‚Mode.ā€‚Useā€‚theā€‚UP and DOWNā€‚keysā€‚toā€‚modifyā€‚value.ā€‚Confirmā€‚withā€‚theā€‚OKā€‚key.Goā€‚toā€‚RTCā€‚ā€œUpdateā€ā€‚andā€‚pressā€‚OKā€‚toā€‚updateā€‚theā€‚clock.

BIOSā€‚RTCā€‚Values

17 : 50 : 5631ā€‚/ā€‚10ā€‚/ā€‚10RTCā€‚update

5.3.5. USB-Host HandlingThisā€‚menuā€‚providesā€‚optionsā€‚toā€‚workā€‚onā€‚projectā€‚files.

Typeā€‚Aā€‚USBā€‚(HOST)ā€‚-ā€‚USBā€‚memoryā€‚key.

USB-Hostā€‚HandlingUSB-->ā€‚M171ā€‚PERFORMANCE

M171ā€‚PERFORMANCE-->ā€‚USB

NOTE: Onlyā€‚useā€‚oneā€‚USBā€‚connectionā€‚atā€‚aā€‚time.Menu description

M171 PERFORMANCE --> USBMenuā€‚thatā€‚allowsā€‚youā€‚toā€‚downloadā€‚parametersā€‚toā€‚theā€‚USBā€‚memoryā€‚key.Thisā€‚shouldā€‚onlyā€‚beā€‚doneā€‚forā€‚BIOSā€‚parameters:ā€¢ Parameters

Page 78: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

78 EIO0000002030 09/2015

USB -> M171 PERFORMANCEMenuā€‚thatā€‚allowsā€‚youā€‚toā€‚uploadā€‚parameters,ā€‚applicationsā€‚andā€‚menusā€‚fromā€‚aā€‚USBā€‚memoryā€‚keyā€‚toā€‚M171 PERFORMANCE.Theā€‚operationā€‚shouldā€‚beā€‚doneā€‚individuallyā€‚forā€‚eachā€‚TM171SW (SoMachineHVAC) development file and for BIOS parameters:ā€¢ Application

ā€¢ User Interface

ā€¢ Connection

ā€¢ Parameters

Preliminary operations

1. Check USB memory key

ā€¢ Connect the USB to the PC.

ā€¢ Checkā€‚thatā€‚itā€‚hasā€‚beenā€‚FAT32ā€‚formatted

ā€¢ Selectā€‚Computer.

ā€¢ Rightā€‚clickā€‚theā€‚externalā€‚drive.

ā€¢ Selectā€‚Propertiesā€‚andā€‚checkā€‚Systemā€‚Fileā€‚type:ā€‚FAT32.

2. Create PARAM.DAT file

Use this menu:M171 PERFORMANCE --> USBā€¢ Connectā€‚theā€‚USBā€‚memoryā€‚key.ā€‚

ā€¢ Selectā€‚M171ā€‚PERFORMANCEā€‚-->ā€‚USB. Parametersā€‚isā€‚theā€‚onlyā€‚availableā€‚option.

USB-Hostā€‚Handling

M171ā€‚PERFORMANCE-->USB

USBā€‚Hostā€‚->ā€‚M171ā€‚PERFORMANCE

Parameters

Onā€‚completion,ā€‚theā€‚USBā€‚memoryā€‚keyā€‚willā€‚containā€‚theā€‚PARAM.DAT file.

Page 79: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

79EIO0000002030 09/2015

3. Copy file from M171 PERFORMANCE to PCType mini-B USB (DEVICE)Connect M171 Performanceā€‚toā€‚aā€‚PCā€‚orā€‚thirdā€‚partyā€‚deviceā€‚usingā€‚aā€‚suitableā€‚USBā€‚mini-Bā€‚cable.This can be done from a PC or other device.M171 Performanceā€‚suppliesā€‚theā€‚followingā€‚filesā€‚toā€‚beā€‚copiedā€‚toā€‚PCā€‚andā€‚thenā€‚transferredā€‚toā€‚aā€‚USBā€‚memoryā€‚key:

File Development environment Description Note

HMIIEC.COD User Interface Menu Available after M171 Performance has been rebo-

otedPLCIEC.COD Application Controller applicationCONNEC.PAR Connection Networkā€‚configurationā€‚file

4. UPLOAD.TXT file creationTheā€‚UPLOAD.txtā€‚fileā€‚canā€‚beā€‚createdā€‚byā€‚anyā€‚textā€‚editorā€‚withā€‚theā€‚followingā€‚contents:

Example:ā€‚filesā€‚inā€‚UPLOAD.txt

Example UPLOAD.txt Example 03UPLOAD.txt ; Application PLCIEC.COD ; User Interface HMIIEC.COD ; Connection CONNEC.PAR ; Parameters PARAM.DAT

; Application 03PLCIEC.COD ; User Interface 03HMIIEC.COD ; Connection 03CONNEC.PAR ; Parameters 03PARAM.DAT

; User Interface Remote HMIREM.KBD ; User Interface Remote 03HMIREM.KBD

Theā€‚remoteā€‚interface,ā€‚ifā€‚available,ā€‚canā€‚alsoā€‚beā€‚addedā€‚toā€‚eachā€‚file.

When more than one M171 Performanceā€‚isā€‚beingā€‚used,ā€‚useā€‚dipswitchesā€‚forā€‚updating.ā€‚

Fileā€‚namesā€‚willā€‚beā€‚precededā€‚byā€‚00,ā€‚01,ā€‚02,ā€‚03ā€‚etcā€‚andā€‚M171 Performanceā€‚willā€‚onlyā€‚ loadā€‚theā€‚relativeā€‚ fileā€‚ ifā€‚ itā€‚matchesā€‚theā€‚dipswitch setting.

Example:ā€‚4ā€‚filesā€‚onā€‚USBā€‚memoryā€‚key

The file HMIIEC.COD and 00HMIIEC.COD are identical.

Files on USBDipswitch

M171 Performance

Description Note

HMIIEC.COD 00 Parameter file downloaded to M171 Performance Seeā€‚previousā€‚example

00HMIIEC.COD 01 Parameter file NOT downloaded to M171 Performance01HMIIEC.COD 01 Parameter file downloaded to M171 Performance02HMIIEC.COD 01 Parameter file NOT downloaded to M171 Performance02HMIIEC.COD 02 Parameter file downloaded to M171 Performance

Example:ā€‚1ā€‚fileā€‚onā€‚USBā€‚memoryā€‚key

Files on USBDipswitch

M171 Performance

Description Note

02HMIIEC.COD 01 Parameter file NOT downloaded to M171 Performance

Messageā€‚ā€œfileā€‚notā€‚presentā€ā€‚displayed.

Page 80: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

80 EIO0000002030 09/2015

5. Transfer file to USB memory keyThe following files will be saved to the USB memory key:

File Development environment Description Note

HMIIEC.COD User Interface MenuTheā€‚remoteā€‚interface,ā€‚ifā€‚available,ā€‚canā€‚alsoā€‚beā€‚added.Available after M171 Performance has been reboo-

ted

PLCIEC.COD Application Controller application Available after M171 Performance has been reboo-tedCONNEC.PAR Connection Networkā€‚configurationā€‚file

PARAM.DAT Parameters Parameters Type A USB (HOST)Instantā€‚updateā€‚withoutā€‚havingā€‚toā€‚reboot

UPLOAD.TXT / ā€œbootā€ā€‚fileā€‚neededā€‚toā€‚uploadā€‚parameters.

The UPLOAD.TXT file must be on the USB memo-ry key

You can now use the following menu:

USB --> M171 PERFORMANCE

ā€¢ Connectā€‚theā€‚USBā€‚memoryā€‚key.

ā€¢ Selectā€‚USBā€‚->ā€‚M171ā€‚PERFORMANCE

ā€¢ Selectā€‚theā€‚requiredā€‚option.

USB-Hostā€‚Handling

USB-->M171ā€‚PERFORMANCE

USBā€‚Hostā€‚->ā€‚M171ā€‚PERFORMANCE

ApplicationUser Interface

ConnectionParameters

Ifā€‚theā€‚actionā€‚completesā€‚successfully,ā€‚theā€‚followingā€‚screensā€‚areā€‚shown:

USBā€‚Hostā€‚->ā€‚M171ā€‚PERFORMANCE USBā€‚Hostā€‚->ā€‚M171ā€‚PERFORMANCE

Processing Completed

Ifā€‚theā€‚fileā€‚isā€‚notā€‚found,ā€‚theā€‚followingā€‚messageā€‚willā€‚beā€‚displayed:

USBā€‚Hostā€‚->ā€‚M171ā€‚PERFORMANCE

File not present.

Page 81: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

81EIO0000002030 09/2015

Ifā€‚thereā€‚isā€‚noā€‚USBā€‚memoryā€‚key,ā€‚theā€‚followingā€‚messageā€‚willā€‚beā€‚displayed:

USBā€‚-ā€‚M171ā€‚PERFORMANCE

USB drive not present.

File management not using the menuAlternatively,ā€‚filesā€‚canā€‚beā€‚downloadedā€‚automaticallyā€‚withoutā€‚usingā€‚theā€‚menuā€‚orā€‚displayā€‚(TM171PBM27Rā€‚reference).

NOTE:ā€‚Theā€‚UPLOAD.TXTā€‚fileā€‚mustā€‚beā€‚onā€‚theā€‚USBā€‚memoryā€‚keyā€‚(USBā€‚drive).ā€‚

Connectā€‚theā€‚USBā€‚memoryā€‚key.Theā€‚filesā€‚onā€‚theā€‚USBā€‚memoryā€‚keyā€‚willā€‚beā€‚transferredā€‚automaticallyā€‚toā€‚M171 Performance.Atā€‚theā€‚userā€‚interfaceā€‚level,ā€‚theā€‚LEDsā€‚willā€‚behaveā€‚asā€‚follows:

LED UploadRed Flashing 2 seconds Operationā€‚unsuccessful

Yellow On Underway

Green Flashing 2 seconds Completedā€‚successfully

Whenā€‚theā€‚LEDsā€‚haveā€‚goneā€‚off,ā€‚theā€‚USBā€‚memoryā€‚keyā€‚canā€‚beā€‚removed.Switchā€‚offā€‚orā€‚restartā€‚theā€‚controllerā€‚andā€‚makeā€‚theā€‚dataā€‚downloadā€‚effective.

Page 82: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

82 EIO0000002030 09/2015

Theā€‚interface,ā€‚comprisingā€‚theā€‚frontā€‚coverā€‚ofā€‚theā€‚controller,ā€‚allowsā€‚youā€‚toā€‚performā€‚operationsā€‚toā€‚useā€‚theā€‚device.

21

3

45

A B C

Fig. 57. M171ā€‚Performanceā€‚Displayā€‚Graphicā€‚(TM171DGRP)

6.1. Keys and LEDsTheā€‚keysā€‚canā€‚beā€‚programmedā€‚fromā€‚theā€‚controllerā€‚application.ā€‚Byā€‚default,ā€‚theā€‚deviceā€‚displaysā€‚aā€‚shortā€‚menuā€‚containingā€‚thefollowingā€‚defaultā€‚settings.

No. Key Press once (press and release)

1TT

ā€¢ Scrollā€‚up

ā€¢ Returnā€‚toā€‚previousā€‚pageā€‚(forā€‚exampleā€‚1/3ā€‚2/3)

ā€¢ Increaseā€‚/ā€‚modifyā€‚aā€‚value

ā€¢ Go to next label

UP

2 OK

ā€¢ Scroll down

ā€¢ Moveā€‚toā€‚nextā€‚level/menuā€‚(openā€‚folder,ā€‚subfolder,ā€‚parameter,ā€‚value)

ā€¢ Enter/exitā€‚Editā€‚mode

ā€¢ Confirm operation

3 RIGHT

T ā€¢ Moveā€‚cursorā€‚toā€‚rightā€‚inā€‚Editā€‚Mode

4DOWN

ā€¢ Scroll down

ā€¢ Moveā€‚toā€‚theā€‚nextā€‚pageā€‚(forā€‚exampleā€‚1/32/3)

ā€¢ Decreaseā€‚/ā€‚modifyā€‚aā€‚value

ā€¢ Goā€‚toā€‚previousā€‚label

TT

5 Exit

ā€¢ Exitā€‚menuā€‚pageā€‚/ā€‚goā€‚backā€‚toā€‚previousā€‚menu

ā€¢ Moveā€‚cursorā€‚toā€‚leftā€‚inā€‚Editā€‚Mode

ā€¢ (pressā€‚andā€‚hold)ā€‚Exitā€‚Editā€‚Modeā€‚withoutā€‚saving

CHAPTER 6 M171 Performance Display Graphic user interface

Page 83: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

83EIO0000002030 09/2015

DIAGNOSTICS MenuM171 Performance Display Graphicā€‚ (TM171DGRP)ā€‚ isā€‚ factory-configuredā€‚withā€‚aā€‚defaultā€‚DIAGNOSTICSā€‚(DIA)ā€‚menuā€‚ thatā€‚appearsā€‚whenā€‚theā€‚equipmentā€‚isā€‚poweredā€‚on.Afterā€‚uploadingā€‚aā€‚controllerā€‚applicationā€‚and/orā€‚aā€‚HMIā€‚menuā€‚fromā€‚TM171SW (SoMachineHVAC),ā€‚theā€‚mainā€‚displayā€‚consistsā€‚ofā€‚theā€‚applicationā€‚menuā€‚createdā€‚withā€‚TM171SW (SoMachineHVAC)ā€‚Interface.Inā€‚whichā€‚case,ā€‚toā€‚openā€‚theā€‚DIAGNOSTICSā€‚menuā€‚proceedā€‚asā€‚follows:

No. Key combination Press and hold for about 3 seconds

4+5DOWN

Openā€‚DIAGNOSTICSā€‚menuExit

Toā€‚returnā€‚toā€‚theā€‚controllerā€‚applicationā€‚menu,ā€‚openā€‚theā€‚ā€œHMIā€‚Managementā€ā€‚page,ā€‚selectā€‚ and press the OKā€‚key.See 6.4. Remote interface on page 84.

Theā€‚LEDsā€‚canā€‚beā€‚programmedā€‚fromā€‚theā€‚controllerā€‚application.

LEDs DescriptionA B C A,ā€‚Bā€‚andā€‚Cā€‚LEDsā€‚areā€‚ā€‚programmableā€‚viaā€‚controllerā€‚application

6.2. First power onWhenā€‚theā€‚equipmentā€‚isā€‚poweredā€‚onā€‚forā€‚theā€‚firstā€‚time,ā€‚aā€‚fewā€‚summaryā€‚pagesā€‚areā€‚displayedā€‚showingā€‚systemā€‚statusā€‚(SYSTEM INFO).

SYSTEM INFOHW

BIOSDATEBOOT

EEPROM

NORā€‚FLASH OK

SDRAM OK

Theā€‚systemā€‚willā€‚alsoā€‚searchā€‚forā€‚theā€‚controllerā€‚applicationā€‚andā€‚theā€‚localā€‚menuā€¦Ifā€‚present,ā€‚theā€‚menuā€‚willā€‚appearā€‚onā€‚theā€‚display.

HMIā€‚searching ...

DIA

Page 84: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

84 EIO0000002030 09/2015

6.3. DIAGNOSTICS menuTheā€‚defaultā€‚DIAGNOSTICSā€‚menuā€‚ofā€‚theā€‚M171 Performance Display Graphicā€‚(TM171DGRP)ā€‚allowsā€‚youā€‚toā€‚manageā€‚systemā€‚parametersā€‚(BIOSā€‚parameters)ā€‚andā€‚theā€‚interfaceā€‚(HMI).Theā€‚DIAGNOSTICSā€‚menuā€‚canā€‚beā€‚displayedā€‚inā€‚5ā€‚languages:ā€‚English,ā€‚Italian,ā€‚German,ā€‚Spanishā€‚andā€‚French.Toā€‚changeā€‚theā€‚defaultā€‚language,ā€‚openā€‚BIOSā€‚Parametersā€‚>ā€‚Display.

M171ā€‚Displayā€‚GraphicBIOS parametersHMIā€‚Management

6.3.1. BIOS parametersParameterā€‚configurationā€‚menu.ā€‚Seeā€‚CHAPTER 9 Parameters on page 107.

Thisā€‚menuā€‚isā€‚depopulatedā€‚withā€‚respectā€‚toā€‚theā€‚parametersā€‚tableā€‚containedā€‚inā€‚theā€‚correspondingā€‚chapterā€‚andā€‚inā€‚theā€‚TM171SW (SoMachineHVAC)ā€‚device.

Aā€‚languageā€‚changeā€‚example:ā€‚BIOS parameters < OKā€‚keyā€‚>ā€‚Displayā€‚1/3ā€‚ < OKā€‚keyā€‚>ā€‚Editā€‚Modeā€‚<ā€‚UP/DOWNā€‚keyā€‚>ā€‚selectā€‚languageā€‚<ā€‚OKā€‚keyā€‚>ā€‚<ā€‚ keyā€‚>

BIOS parameters Displayā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚1/3

Displayā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚1/3Display Language LanguageBuzzer Italiano EnglishCAN

Seeā€‚parameterā€‚Display/Hmi_Language.

6.3.2. HMI ManagementSee 6.4. Remote interface on page 84.

6.4. Remote interfaceM171ā€‚Displayā€‚GraphicLanguage:ā€‚0ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚

HMIā€‚Management

6.4.1. LanguageThisā€‚sectionā€‚isā€‚forā€‚settingā€‚theā€‚languageā€‚ofā€‚theā€‚remoteā€‚menu,ā€‚definedā€‚fromā€‚theā€‚TM171SW (SoMachineHVAC)ā€‚Userā€‚Interface.Theā€‚numberā€‚ofā€‚languagesā€‚andā€‚theā€‚orderā€‚areā€‚establishedā€‚byā€‚theā€‚correspondingā€‚application/menu.Seeā€‚parameterā€‚HMIā€‚Management/Hmi_Languageā€‚(seeā€‚CHAPTER 9 Parameters on page 107).

6.4.2. Toā€‚returnā€‚toā€‚theā€‚menuā€‚ofā€‚theā€‚controllerā€‚application,ā€‚moveā€‚theā€‚cursorā€‚ontoā€‚theā€‚ā€‚symbolā€‚andā€‚pressā€‚theā€‚OKā€‚key.

Page 85: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

85EIO0000002030 09/2015

6.4.3. HMI ManagementThisā€‚pageā€‚showsā€‚theā€‚configurationā€‚ofā€‚theā€‚remoteā€‚page.

M171ā€‚Displayā€‚GraphicFile:ā€‚HMIREM.KBD

Id: 0

Com: CANAddr: 124

Fromā€‚theseā€‚pagesā€‚itā€‚isā€‚possibleā€‚toā€‚ā€œlaunchā€ā€‚(run)ā€‚theā€‚correspondingā€‚menuā€‚ā€“ā€‚ifā€‚present.Moveā€‚theā€‚cursorā€‚toā€‚ and press the OKā€‚key.Toā€‚ā€œuploadā€ā€‚aā€‚remoteā€‚pageā€‚useā€‚Afterā€‚selectingā€‚theā€‚desiredā€‚menuā€‚moveā€‚theā€‚cursorā€‚toā€‚ toā€‚viewā€‚theā€‚menu.

Upload remote pageUpload page?

The process cannot be interrupted

Cancel OK

Press OKā€‚toā€‚uploadā€‚orā€‚anyā€‚otherā€‚keyā€‚toā€‚cancel:

Upload remote pageUploading...

80%

Theā€‚uploadā€‚mayā€‚takeā€‚upā€‚toā€‚aā€‚minute.

Ifā€‚thereā€‚areā€‚noā€‚dataā€‚toā€‚upload,ā€‚theā€‚followingā€‚screenā€‚displays:

Upload remote pageThere are no remotepages on the card.

Press OK

Page 86: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

86 EIO0000002030 09/2015

Theā€‚interface,ā€‚comprisingā€‚theā€‚frontā€‚coverā€‚ofā€‚theā€‚controller,ā€‚allowsā€‚youā€‚toā€‚performā€‚operationsā€‚toā€‚useā€‚theā€‚device.

A B C

21

3

45

Fig. 58. M171ā€‚Performanceā€‚Flush

Theā€‚keysā€‚canā€‚beā€‚programmedā€‚fromā€‚theā€‚controllerā€‚application.ā€‚Byā€‚default,ā€‚ theā€‚deviceā€‚displaysā€‚aā€‚shortā€‚menuā€‚containingā€‚ theā€‚followingā€‚defaultā€‚settings.

7.1. Keys and LEDs

No. Key Press once (press and release)

1TT

ā€¢ Scrollā€‚up

ā€¢ Returnā€‚toā€‚previousā€‚pageā€‚(forā€‚exampleā€‚2/10ā€‚fā€‚3/10)

ā€¢ Increaseā€‚/ā€‚modifyā€‚aā€‚value

ā€¢ Go to the next label

UP

2 OK

ā€¢ Scroll down

ā€¢ Moveā€‚toā€‚nextā€‚level/menuā€‚(openā€‚folder,ā€‚subfolder,ā€‚parameterā€‚value)

ā€¢ Enter/exitā€‚Editā€‚mode

ā€¢ Confirm operation

3 RIGHT

T ā€¢ Movesā€‚cursorā€‚toā€‚rightā€‚inā€‚Editā€‚Mode

4DOWN

ā€¢ Scroll down

ā€¢ Moveā€‚toā€‚theā€‚nextā€‚pageā€‚(forā€‚exampleā€‚1/10ā€‚gā€‚2/10)

ā€¢ Decreaseā€‚/ā€‚modifyā€‚aā€‚value

ā€¢ Goā€‚toā€‚previousā€‚label

TT

5 Exit

ā€¢ Exitā€‚menuā€‚pageā€‚/ā€‚goā€‚backā€‚toā€‚previousā€‚menu

ā€¢ Moveā€‚cursorā€‚toā€‚leftā€‚ā€‚inā€‚Editā€‚Mode

ā€¢ (pressā€‚andā€‚hold)ā€‚Exitā€‚Editā€‚Modeā€‚withoutā€‚savingā€‚anyā€‚changes

CHAPTER 7 M171 Performance Flush user interface

Page 87: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

87EIO0000002030 09/2015

The M171 Performance Flushā€‚ isā€‚ factory-configuredā€‚ withā€‚ aā€‚ defaultā€‚ DIAGNOSTICSā€‚ (DIA)ā€‚ menuā€‚ thatā€‚ appearsā€‚ whenā€‚ theā€‚equipmentā€‚isā€‚poweredā€‚on.Afterā€‚uploadingā€‚ofā€‚aā€‚controllerā€‚applicationā€‚and/orā€‚aā€‚HMIā€‚menuā€‚fromā€‚TM171SW (SoMachineHVAC),ā€‚theā€‚mainā€‚displayā€‚consistsā€‚ofā€‚theā€‚applicationā€‚menuā€‚createdā€‚withā€‚TM171SW (SoMachineHVAC)ā€‚Interface.Inā€‚whichā€‚case,ā€‚toā€‚openā€‚theā€‚DIAGNOSTICSā€‚menuā€‚proceedā€‚asā€‚follows:

Key combination Press and hold for about 3 seconds

4+5DOWN

Openā€‚DIAGNOSTICSā€‚menuExit

Theā€‚LEDsā€‚canā€‚beā€‚programmedā€‚fromā€‚theā€‚controllerā€‚application.

LEDs DescriptionA B C A,ā€‚Bā€‚andā€‚Cā€‚LEDsā€‚areā€‚programmableā€‚viaā€‚controllerā€‚application

Toā€‚ returnā€‚ toā€‚ theā€‚ controllerā€‚ applicationā€‚menuā€‚ openā€‚ theā€‚ ā€˜HMIā€‚Managementā€™ā€‚ pageā€‚ (7.3.2. HMI management on page 88),ā€‚select and press the OKā€‚key.See 7.4. Remote interface on page 90.

7.2. First power onWhenā€‚theā€‚equipmentā€‚isā€‚poweredā€‚upā€‚forā€‚theā€‚firstā€‚time,ā€‚aā€‚fewā€‚summaryā€‚pagesā€‚areā€‚displayedā€‚showingā€‚systemā€‚statusā€‚(SYSTEM INFO).

SYSTEM INFOHW

BIOSDATEBOOT

EEPROM

NORā€‚FLASH OKNANDā€‚FLASH OK

SDRAM OKBATRAM OKRTC OK

Theā€‚systemā€‚willā€‚alsoā€‚searchā€‚forā€‚theā€‚controllerā€‚applicationā€‚andā€‚theā€‚localā€‚menuā€¦Ifā€‚present,ā€‚theā€‚menuā€‚willā€‚appearā€‚onā€‚theā€‚display

PLCā€‚searching ā€¦HMIā€‚searching ā€¦

CON loaded

Page 88: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

88 EIO0000002030 09/2015

7.3. DIAGNOSTIC menuTheā€‚DIAGNOSTICSā€‚menuā€‚ ofā€‚ theā€‚M171 Performance Flushā€‚ isā€‚ usedā€‚ toā€‚manageā€‚ systemā€‚ parametersā€‚ (BIOSā€‚ parameters),ā€‚remoteā€‚interfacesā€‚(HMI)ā€‚andā€‚toā€‚displayā€‚I/Oā€‚valuesā€‚andā€‚clock.Theā€‚DIAGNOSTICSā€‚menuā€‚canā€‚beā€‚displayedā€‚inā€‚5ā€‚languages:ā€‚English,ā€‚Italian,ā€‚German,ā€‚Spanishā€‚andā€‚French.Toā€‚changeā€‚theā€‚language,ā€‚openā€‚BIOSā€‚Parametersā€‚>ā€‚Display

M171ā€‚Performanceā€‚FlushBIOS parametersHMIā€‚ManagementProbeā€‚valuesDate and time

7.3.1. BIOS parametersForā€‚Parameterā€‚configurationā€‚menu,ā€‚seeā€‚CHAPTER 9 Parameters on page 107.

Thisā€‚menuā€‚isā€‚depopulatedā€‚withā€‚respectā€‚toā€‚theā€‚parametersā€‚tableā€‚containedā€‚inā€‚theā€‚correspondingā€‚chapterā€‚andā€‚inā€‚theā€‚TM171SW (SoMachineHVAC)ā€‚device.ā€‚

Aā€‚languageā€‚changeā€‚example:ā€‚BIOS parameters < OKā€‚keyā€‚>ā€‚Displayā€‚1/3ā€‚ < OKā€‚keyā€‚>ā€‚Editā€‚Modeā€‚<ā€‚UP/DOWNā€‚keyā€‚>ā€‚selectā€‚languageā€‚<ā€‚OKā€‚keyā€‚>ā€‚<ā€‚ keyā€‚>

BIOS parameters Displayā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚1/3

Displayā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚1/3Display Language LanguageBuzzer Italiano EnglishCAN

Seeā€‚parameterā€‚Display/Hmi_Language.

7.3.2. HMI managementSee 7.4. Remote interface on page 90.

7.3.3. Probe valuesShowsā€‚inputā€‚valuesā€‚(readā€‚only).M171 Performance Flushā€‚hasā€‚3ā€‚inputs.ā€‚A TM171PFE03HR example:

Probesā€‚valuesā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚1/3 Probesā€‚valuesā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚2/3 Probesā€‚valuesā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚3/3Internal NTC External NTC Humidityā€‚sensor

27.3 -ā€‚-ā€‚-ā€‚-ā€‚-ā€‚-ā€‚-ā€‚-ā€‚-ā€‚-ā€‚-ā€‚-ā€‚-ā€‚- 43.38Ā°C,ā€‚Ā°F Ā°C,ā€‚Ā°F RH%

For offset programming see 8.1.2. Analog inputs configuration for M171EP14R on page 94.

Page 89: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

89EIO0000002030 09/2015

7.3.4. Date and timeShowsā€‚timeā€‚(HHā€‚:ā€‚MMā€‚:ā€‚SS)ā€‚andā€‚dateā€‚(DDā€‚/ā€‚MMā€‚/ā€‚YY)ā€‚ofā€‚theā€‚internalā€‚clock.

Date and time

14 : 45 : 4520ā€‚/ā€‚07ā€‚ā€‚/ā€‚11

Update

Toā€‚editā€‚theā€‚valueā€‚pressā€‚OK.ā€‚Selectā€‚theā€‚valueā€‚thatā€‚youā€‚wantā€‚toā€‚modify.Press the OKā€‚keyā€‚toā€‚enterā€‚Editā€‚Mode.ā€‚Useā€‚theā€‚UP and DOWNā€‚keysā€‚toā€‚modifyā€‚value.ā€‚Confirmā€‚withā€‚theā€‚OKā€‚key.Select ā€˜Updateā€™ and press OKā€‚toā€‚updateā€‚theā€‚clock.

Date and time

16 : 50 : 5620ā€‚/ā€‚07ā€‚ā€‚/ā€‚11

Update

Page 90: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

90 EIO0000002030 09/2015

7.4. Remote interfaceM171ā€‚Performanceā€‚FlushLanguage:ā€‚0ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚HMIā€‚sel:ā€‚Network

COM settingHMIā€‚Management

7.4.1. LanguageThisā€‚sectionā€‚isā€‚forā€‚settingā€‚theā€‚languageā€‚ofā€‚theā€‚remoteā€‚menu,ā€‚definedā€‚fromā€‚theā€‚TM171SW (SoMachineHVAC)ā€‚Userā€‚Interface.Theā€‚numberā€‚ofā€‚languagesā€‚andā€‚theā€‚orderā€‚areā€‚establishedā€‚byā€‚theā€‚correspondingā€‚application/menu.Seeā€‚parameterā€‚HMIā€‚Management/Hmi_Language.

7.4.2. Toā€‚returnā€‚toā€‚theā€‚menuā€‚ofā€‚theā€‚controllerā€‚application,ā€‚moveā€‚theā€‚cursorā€‚ontoā€‚theā€‚ symbolā€‚andā€‚pressā€‚theā€‚OKā€‚key.See 7.4.3. HMI sel on page 90.

7.4.3. HMI selThisā€‚sectionā€‚isā€‚forā€‚settingā€‚theā€‚menuā€‚toā€‚beā€‚shownā€‚onā€‚theā€‚display.Byā€‚defaultā€‚HMIā€‚menusā€‚areā€‚NOTā€‚presentā€‚(onlyā€‚theā€‚DIAGNOSTICSā€‚menuā€‚isā€‚available).Network: this is the M171 Performance Flushā€‚ā€˜localā€™ā€‚menuā€‚(localā€‚HMI).rem1ā€¦rem10:ā€‚menusā€‚locatedā€‚onā€‚maxā€‚10ā€‚M171 Performanceā€‚devicesā€‚connectedā€‚toā€‚theā€‚networkā€‚thatā€‚canā€‚beā€‚ā€˜uploadedā€™ā€‚toā€‚M171 Performance Flush.

M171ā€‚Performanceā€‚Flush M171ā€‚Performanceā€‚Flush M171ā€‚Performanceā€‚Flush

HMIā€‚sel:ā€‚Network HMIā€‚sel:ā€‚rem1 ... HMIā€‚sel:ā€‚rem10

To move from one page to the next press the UP and DOWNā€‚keys.Afterā€‚selectingā€‚theā€‚desiredā€‚menuā€‚moveā€‚theā€‚cursorā€‚ontoā€‚ā€‚toā€‚viewā€‚theā€‚menuā€‚

Launchā€‚remoteā€‚page

Please Wait

Ifā€‚OKā€‚theā€‚displayā€‚willā€‚showā€‚theā€‚selectedā€‚menuā€‚(controllerā€‚application).Ifā€‚theā€‚menuā€‚isā€‚notā€‚present,ā€‚theā€‚followingā€‚screenā€‚appears

WarningUpload failed

Press OK

Page 91: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

91EIO0000002030 09/2015

7.4.4. COM SettingThis read-onlyā€‚pageā€‚showsā€‚theā€‚configurationā€‚ofā€‚theā€‚M171 Performance Flush serial ports.

M171ā€‚Performanceā€‚FlushCAN : 1 . 500000

485s : 1 . 38400.P81ETHā€‚:ā€‚010.000.000.100

7.4.5. HMI ManagementThisā€‚pageā€‚showsā€‚theā€‚configurationā€‚ofā€‚theā€‚10ā€‚remoteā€‚pages.

M171ā€‚ Performanceā€‚ Flushā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚1/10

M171ā€‚ Performanceā€‚ Flushā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚1/10

M171ā€‚ Performanceā€‚ Flushā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚ā€‚10/10

File:ā€‚HMIREM.KBD

Id: 0 Id: 0 ... Id: 0

Com: CAN Com: CAN Com: CANAddr: 125 Addr: 000 Addr: 000

Fromā€‚theseā€‚pagesā€‚itā€‚isā€‚possibleā€‚toā€‚ā€˜launchā€™ā€‚(run)ā€‚theā€‚correspondingā€‚menuā€‚ā€“ā€‚ifā€‚presentā€‚Moveā€‚theā€‚cursorā€‚ontoā€‚ and press the OKā€‚key.

Itā€‚willā€‚notā€‚beā€‚possibleā€‚toā€‚launchā€‚theā€‚localā€‚(network)ā€‚menuā€‚fromā€‚thisā€‚section.Inā€‚theā€‚exampleā€‚onlyā€‚oneā€‚remoteā€‚pageā€‚isā€‚present.

Toā€‚ā€˜uploadā€™ā€‚aā€‚remoteā€‚pageā€‚useā€‚.

Afterā€‚selectingā€‚theā€‚desiredā€‚menuā€‚moveā€‚theā€‚cursorā€‚ontoā€‚ā€‚toā€‚viewā€‚theā€‚menu.

Upload remote pageUpload page?

The process cannot be interrupted

Cancel OKPress OKā€‚toā€‚uploadā€‚orā€‚anyā€‚otherā€‚keyā€‚toā€‚cancel

Upload remote pageUploading...

80%

Theā€‚uploadā€‚mayā€‚takeā€‚upā€‚toā€‚aā€‚minute.

Ifā€‚thereā€‚areā€‚noā€‚dataā€‚toā€‚upload,ā€‚theā€‚followingā€‚screenā€‚displays

WarningThere are no remotepages on the card

Press OK

Page 92: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

92 EIO0000002030 09/2015

Fromā€‚timeā€‚toā€‚time,ā€‚newā€‚inputā€‚modules,ā€‚outputā€‚modulesā€‚orā€‚otherā€‚devicesā€‚areā€‚madeā€‚availableā€‚thatā€‚areā€‚notā€‚documentedā€‚inā€‚theā€‚followingā€‚information.ā€‚Forā€‚informationā€‚onā€‚newā€‚devices,ā€‚contactā€‚yourā€‚localā€‚Schneiderā€‚Electricā€‚representative.

NOTICEINOPERABLE EQUIPMENTUpdateā€‚theā€‚controllerā€‚firmwareā€‚toā€‚theā€‚latestā€‚versionā€‚everyā€‚timeā€‚youā€‚installā€‚aā€‚newlyā€‚releasedā€‚Input/Outputā€‚expansionā€‚moduleā€‚orā€‚otherā€‚deviceā€‚toā€‚thisā€‚equipment.Failure to follow these instructions can result in equipment damage.

NOTE:ā€‚Forā€‚moreā€‚informationā€‚onā€‚howā€‚toā€‚updateā€‚theā€‚controllerā€‚firmware,ā€‚contactā€‚yourā€‚localā€‚Schneiderā€‚Electricā€‚representative.

M171 Performance M171 Performance Flush

Analog inputs

Configurableā€‚byā€‚parameterā€‚(seeā€‚8.1.1. Analog inputs configuration for M171

Performance on page 93)

Configurableā€‚byā€‚parameterā€‚(seeā€‚8.1.2. Analog inputs configura-

tion for M171EP14R on page 94)

Analog outputs

Configurableā€‚byā€‚parameterā€‚(seeā€‚"8.2. Analog outputs configuration for M171

Performance")-

Digital inputs

Configurableā€‚byā€‚parameterā€‚(seeā€‚8.3. Digital inputs configuration for M171 Performance

on page 97)-

Digital outputs

Configurableā€‚byā€‚parameterā€‚(seeā€‚8.4. Digital outputs configuration for M171

Performance on page 97)-

Serials

Configurableā€‚byā€‚parameterā€‚(seeā€‚9.1.1. TM171PDM27 / TM171PBM27R / TM171EP27R

parameters on page 108)ā€‚orā€‚dip-switchā€‚

(seeā€‚ on page 97)

Configurableā€‚byā€‚parameterā€‚(seeā€‚9.1.2. M171EP14R parameters

on page 119)

Applyingā€‚ incorrectā€‚ currentā€‚ orā€‚ voltageā€‚ levelsā€‚ onā€‚ analogā€‚ inputsā€‚ andā€‚ outputsā€‚ couldā€‚ damageā€‚ theā€‚ electronicā€‚ circuitry.ā€‚ Further,ā€‚ connectingā€‚aā€‚currentā€‚inputā€‚deviceā€‚toā€‚anā€‚analogā€‚inputā€‚configureā€‚forā€‚voltage,ā€‚andā€‚vice-versa,ā€‚willā€‚likewiseā€‚damageā€‚theā€‚electronicā€‚circuitry.

NOTICEINOPERABLE EQUIPMENT

ā€¢ Doā€‚notā€‚applyā€‚voltagesā€‚aboveā€‚11ā€‚Vdcā€‚toā€‚theā€‚analogā€‚inputsā€‚ofā€‚theā€‚controllerā€‚orā€‚Input/Outputā€‚expansionā€‚moduleā€‚whenā€‚analogā€‚inputā€‚isā€‚configuredā€‚asā€‚0-10Vā€‚input.

ā€¢ Doā€‚notā€‚applyā€‚currentā€‚aboveā€‚30ā€‚mAā€‚toā€‚theā€‚analogā€‚inputsā€‚ofā€‚theā€‚controllerā€‚orā€‚Input/Outputā€‚expansionā€‚moduleā€‚whenā€‚analogā€‚inputā€‚isā€‚configuredā€‚asā€‚0-20ā€‚mAā€‚orā€‚4-20ā€‚mAā€‚input.

ā€¢ Doā€‚notā€‚mismatchā€‚appliedā€‚signalā€‚withā€‚analogā€‚inputā€‚configuration.Failure to follow these instructions can result in equipment damage.

CHAPTER 8 Physical I/O and ports configuration

Page 93: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

93EIO0000002030 09/2015

8.1. Analog inputsM171 Performance and M171 Performance Flushā€‚haveā€‚analogā€‚inputs.

8.1.1. Analog inputs configuration for M171 PerformanceThereā€‚areā€‚aā€‚totalā€‚ofā€‚6ā€‚analogā€‚inputs,ā€‚referredā€‚toā€‚belowā€‚asā€‚AI1ā€¦AI6.Usingā€‚ theā€‚parameters,ā€‚aā€‚physicalā€‚ resourceā€‚(probe,ā€‚digitalā€‚ input,ā€‚voltage/currentā€‚signal)ā€‚canā€‚beā€‚configuredā€‚ forā€‚eachā€‚ typeā€‚ofā€‚input:ā€¢ 2ā€‚inputsā€‚canā€‚beā€‚configuredā€‚asā€‚temperatureā€‚probesā€‚(NTCā€‚typeā€‚probe)ā€‚orā€‚asā€‚digitalā€‚inputs.

ā€¢ 4ā€‚inputsā€‚(AI3ā€¦AI6)ā€‚canā€‚beā€‚configuredā€‚asā€‚temperatureā€‚probesā€‚(NTCā€‚orā€‚Pt1000),ā€‚asā€‚digitalā€‚ inputsā€‚orā€‚asā€‚aā€‚current/voltageā€‚inputā€‚(4-20mAā€‚signal/ā€‚0-10V,ā€‚0-5Vā€‚ratiometric).

Inputsā€‚canā€‚beā€‚configuredā€‚asā€‚specifiedā€‚inā€‚theā€‚tableā€‚below.

ValueParameter Description 0 1 2 3 4 5 6 7 8

Cfg_AI1Typeā€‚of

ā€‚analogā€‚inputā€‚AI1

NTC probe (NK103)

Probe configuredā€‚asā€‚ā€‚voltage-freeā€‚digitalā€‚input

NTC probe(103AT) - - - - - -

Cfg_AI2Typeā€‚ofā€‚

analogā€‚inputā€‚AI2

NTC probe (NK103)

Probe configuredā€‚asā€‚ā€‚voltage-freeā€‚digitalā€‚input

NTC probe(103AT)

- - - - - -

Cfg_AI3Typeā€‚ofā€‚

analogā€‚inputā€‚AI3

NTC probe (NK103)

Probe configuredā€‚asā€‚ā€‚voltage-freeā€‚digitalā€‚input

NTC probe(103AT)

4-20ā€‚mA(1)

0-10 V(1)

0-5ā€‚VRatiometric

(1)

PT1000 hĪ©(NTC)(2)

daĪ©(PT1000)

(3)

Cfg_AI4Typeā€‚of

analogā€‚inputā€‚AI4

NTC probe (NK103)

Probe configuredā€‚asā€‚ā€‚voltage-freeā€‚digitalā€‚input

NTC probe(103AT)

4-20ā€‚mA

0-10 V

0-5ā€‚VRatiometric

PT1000 hĪ©(NTC)

daĪ©(PT1000)

Cfg_AI5Typeā€‚ofā€‚

analogā€‚inputā€‚AI5

NTC probe (NK103)

Probe configuredā€‚asā€‚ā€‚voltage-freeā€‚digitalā€‚input

NTC probe(103AT)

4-20ā€‚mA

0-10 V

0-5ā€‚VRatiometric

PT1000 hĪ©(NTC)

daĪ©(PT1000)

Cfg_AI6Typeā€‚of

analogā€‚inputā€‚AI6

NTC probe (NK103)

Probe configuredā€‚asā€‚ā€‚voltage-freeā€‚digitalā€‚input

NTC probe(103AT)

4-20ā€‚mA

0-10 V

0-5ā€‚VRatiometric

PT1000 hĪ©(NTC)

daĪ©(PT1000)

(1) 4-20 mA / 0-10V / 0-5 V ratiometric

Minimum full scale AIxā€¢ forā€‚currentā€‚probe,ā€‚valueā€‚=ā€‚4ā€‚mA,ā€¢ forā€‚0-10ā€‚Vā€‚voltageā€‚probe,ā€‚valueā€‚=ā€‚0ā€‚V,ā€¢ forā€‚ratiometricā€‚probeā€‚(0Ć·5V),ā€‚valueā€‚=ā€‚10%ā€‚(correspondingā€‚toā€‚0.5ā€‚V)

Maximum full scale AIxā€¢ forā€‚currentā€‚probe,ā€‚valueā€‚=ā€‚20ā€‚mA,ā€¢ forā€‚0-10Vā€‚voltageā€‚probe,ā€‚valueā€‚=ā€‚10ā€‚V,ā€¢ forā€‚ratiometricā€‚probeā€‚(0Ć·5ā€‚V),ā€‚valueā€‚=ā€‚90%ā€‚(correspondingā€‚toā€‚4.5ā€‚V)ā€‚

(2)ā€‚Cfg_AIxā€‚=ā€‚7ā€‚Resistanceā€‚valueā€‚read,ā€‚expressedā€‚ inā€‚hĪ©,ā€‚ forā€‚aā€‚resistanceā€‚appliedā€‚ toā€‚ theā€‚ inputā€‚usingā€‚ theā€‚controllerā€‚ inā€‚NTCā€‚configuration,ā€‚i.e.ā€‚creating a divider with pull-up resistance of 10 kĪ©.

(3)ā€‚Cfg_AIxā€‚=ā€‚8ā€‚Resistanceā€‚valueā€‚read,ā€‚expressedā€‚inā€‚daĪ©,ā€‚forā€‚aā€‚resistanceā€‚appliedā€‚toā€‚theā€‚inputā€‚usingā€‚theā€‚controllerā€‚inā€‚PT1000ā€‚configuration,ā€‚i.e.ā€‚creating a divider with pull-up resistance of 2 kĪ©. Note:ā€‚Typicallyā€‚usedā€‚withā€‚potentiometerā€‚atā€‚input.Theā€‚resistanceā€‚rangeā€‚forā€‚theā€‚hĪ©ā€‚(NTC)ā€‚configurationā€‚isā€‚upā€‚toā€‚150ā€‚K,ā€‚andā€‚upā€‚toā€‚30ā€‚Kā€‚forā€‚theā€‚daĪ©ā€‚(PT1000)ā€‚configuration.

Page 94: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

94 EIO0000002030 09/2015

Parameter Range DescriptionFullScaleMin_AI3 -9999ā€¦+9999 Analogā€‚inputā€‚AI3ā€‚startā€‚ofā€‚scaleā€‚valueFullScaleMax_AI3 -9999ā€¦+9999 Analogā€‚inputā€‚AI3ā€‚fullā€‚scaleā€‚valueFullScaleMin_AI4 -9999ā€¦+9999 Analogā€‚inputā€‚AI4ā€‚startā€‚ofā€‚scaleā€‚valueFullScaleMax_AI4 -9999ā€¦+9999 Analogā€‚inputā€‚AI4ā€‚fullā€‚scaleā€‚valueFullScaleMin_AI5 -9999ā€¦+9999 Analogā€‚inputā€‚AI5ā€‚startā€‚ofā€‚scaleā€‚valueFullScaleMax_AI5 -9999ā€¦+9999 Analogā€‚inputā€‚AI5ā€‚fullā€‚scaleā€‚valueFullScaleMin_AI6 -9999ā€¦+9999 Analogā€‚inputā€‚AI6ā€‚startā€‚ofā€‚scaleā€‚valueFullScaleMaxAI6 -9999ā€¦+9999 Analogā€‚inputā€‚AI6ā€‚fullā€‚scaleā€‚value

Theā€‚valuesā€‚readā€‚byā€‚analogā€‚inputsā€‚canā€‚beā€‚configuredā€‚viaā€‚theā€‚followingā€‚parameters:

Parameter Description Measurement Unit Range

Calibration_AI1 Analogā€‚inputā€‚AI1ā€‚differentialā€‚ Ā°C/10ā€‚orā€‚Ā°F/10 -180ā€‚...ā€‚180

Calibration_AI2 Analogā€‚inputā€‚AI2ā€‚differentialā€‚ Ā°C/10ā€‚orā€‚Ā°F/10 -180ā€‚...ā€‚180Calibration_AI3 Analogā€‚inputā€‚AI3ā€‚differentialā€‚ - -1000ā€‚...ā€‚1000Calibration_AI4 Analogā€‚inputā€‚AI4ā€‚differential - -1000ā€‚...ā€‚1000Calibration_AI5 Analogā€‚inputā€‚AI5ā€‚differential - -1000ā€‚...ā€‚1000Calibration_AI6 Analogā€‚inputā€‚AI6ā€‚differential - -1000ā€‚...ā€‚1000

8.1.2. Analog inputs configuration for M171EP14RThereā€‚areā€‚aā€‚totalā€‚ofā€‚4ā€‚analogā€‚inputs,ā€‚referredā€‚toā€‚belowā€‚asā€‚AI1ā€¦AI4.Usingā€‚theā€‚parameters,ā€‚aā€‚physicalā€‚resourceā€‚(probe,ā€‚digitalā€‚input,ā€‚voltage/currentā€‚signal)ā€‚canā€‚beā€‚"physically"ā€‚configuredā€‚forā€‚eachā€‚typeā€‚ofā€‚inputTheā€‚inputsā€‚areā€‚configurableā€‚inā€‚pairsā€‚AI1,ā€‚AI2ā€‚andā€‚AI3,ā€‚AI4Inputsā€‚canā€‚beā€‚"physically"ā€‚configuredā€‚asā€‚specifiedā€‚inā€‚theā€‚tableā€‚below.

ValuePar Description 0 1 2 3 4 5 6 7 8 9 10

Cfg_AIx

x=1...4

Typeā€‚of analog inputā€‚AIx

NTC probe (NK103)

DI(1)

NTC probe(103AT)

4-20ā€‚mA(2)

0-10 V(2)

0-5ā€‚VRatiometric

(2)

PT1000 hĪ©(NTC)(3)

daĪ©(PT1000)

(4)

PTC (KTY81)

0-5ā€‚V

(1)ā€‚DIā€‚Inputā€‚configuredā€‚asā€‚voltage-freeā€‚digitalā€‚input

(2) 4-20 mA / 0-10 V / 0-5 V ratiometric

Minimum full scale AIxā€¢ forā€‚currentā€‚probe,ā€‚valueā€‚=ā€‚4ā€‚mA,ā€¢ forā€‚0-10Vā€‚voltageā€‚probe,ā€‚valueā€‚=ā€‚0ā€‚V,ā€¢ forā€‚ratiometricā€‚probeā€‚(0Ć·5ā€‚V),ā€‚valueā€‚=ā€‚10%ā€‚(correspondingā€‚toā€‚0.5ā€‚V)

Maximum full scale AIxā€¢ forā€‚currentā€‚probe,ā€‚valueā€‚=ā€‚20ā€‚mA,ā€¢ forā€‚0-10ā€‚Vā€‚voltageā€‚probe,ā€‚valueā€‚=ā€‚10ā€‚V,

forā€‚ratiometricā€‚probeā€‚(0Ć·5V),ā€‚valueā€‚=ā€‚90%ā€‚(correspondingā€‚toā€‚4.5ā€‚V)ā€‚

(3)ā€‚Cfg_AIxā€‚=ā€‚7ā€‚Resistanceā€‚valueā€‚read,ā€‚expressedā€‚ inā€‚hĪ©,ā€‚ forā€‚aā€‚resistanceā€‚appliedā€‚ toā€‚ theā€‚ inputā€‚usingā€‚ theā€‚controllerā€‚ inā€‚NTCā€‚configuration,ā€‚i.e.ā€‚creating a divider with pull-up resistance of 10 kĪ©.

(4)ā€‚Cfg_AIxā€‚=ā€‚8ā€‚Resistanceā€‚valueā€‚read,ā€‚expressedā€‚inā€‚daĪ©,ā€‚forā€‚aā€‚resistanceā€‚appliedā€‚toā€‚theā€‚inputā€‚usingā€‚theā€‚controllerā€‚inā€‚PT1000ā€‚configuration,ā€‚i.e.ā€‚creating a divider with pull-up resistance of 2 kĪ©. Note:ā€‚Typicallyā€‚usedā€‚withā€‚potentiometerā€‚atā€‚input.Theā€‚resistanceā€‚rangeā€‚forā€‚theā€‚hĪ©ā€‚(NTC)ā€‚configurationā€‚isā€‚upā€‚toā€‚150ā€‚K,ā€‚andā€‚upā€‚toā€‚30ā€‚Kā€‚forā€‚theā€‚daĪ©(ā€‚PT1000)ā€‚configuration.

Page 95: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

95EIO0000002030 09/2015

Allowed configurations for analog inputs

Theā€‚pairsā€‚(AI1,ā€‚AI2)ā€‚andā€‚(AI3,ā€‚AI4)ā€‚shallā€‚beā€‚configuredā€‚asā€‚specifiedā€‚inā€‚theā€‚tableā€‚below.

Cellsā€‚compiledā€‚showā€‚correctā€‚combinations.ā€‚Emptyā€‚cellsā€‚indicateā€‚incorrectā€‚combinations. Applyingā€‚incorrectā€‚configurationā€‚willā€‚produceā€‚0x8003ā€‚errorā€‚onā€‚probesā€‚rangeā€‚configuration

Cfg_AI1 / Cfg_AI3

0 1 2 3 4 5 6 7 8 9 10

Cfg

_AI2

/ C

fg_A

I4

0NTC probe (NK103)

DINTC probe(103AT)

- - - -hĪ©

(NTC) - - -

1NTC probe (NK103)

DINTC probe(103AT)

- - - -hĪ©

(NTC) - - -

2NTC probe (NK103)

DINTC probe(103AT)

- - - -hĪ©

(NTC) - - -

3 - - - 4-20ā€‚mA - - - - - - -

4 - - - -0-10 V - - - - - -

5 - - - - -0-5ā€‚V

Ratiometric - - (PT1000) - 0-5ā€‚V

6 - - - - - - PT1000 -daĪ©

(PT1000) - -

7NTC probe (NK103)

DINTC probe(103AT)

- - - -hĪ©

(NTC) - PTC (KTY81) -

8 - - - - - - PT1000 -daĪ©

(PT1000) PTC (KTY81) -

9 - - - - - - PT1000 -daĪ©

(PT1000) PTC (KTY81) -

10 - - - - -0-5ā€‚V

Ratiometric - - - - 0-5ā€‚V

Page 96: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

96 EIO0000002030 09/2015

8.1.3. Analog inputs configuration for M171 Performance FlushInputsā€‚canā€‚beā€‚configuredā€‚asā€‚specifiedā€‚inā€‚theā€‚tableā€‚below.

Parameter Description Values0 1 2 3 4 5

Cfg_AI1Typeā€‚ofā€‚inputā€‚

analog AI1

NTC probe(NK103)

Probe configuredā€‚asā€‚voltage-freeā€‚digitalā€‚input

NTC probe(103AT-2) - - -

Cfg_AI2Typeā€‚ofā€‚inputā€‚

analog AI2

NTC probe(NK103)

Probe configuredā€‚asā€‚voltage-freeā€‚digitalā€‚input

NTC probe(103AT-2) - - -

Cfg_AI3Typeā€‚ofā€‚inputā€‚

analog AI3

- - - 4-20ā€‚mA 0-10ā€‚V 0-5ā€‚V

Parameter Range DescriptionFullScaleMin_AI3 -9999...+9999 Analogā€‚inputā€‚AI3ā€‚startā€‚ofā€‚scaleā€‚valueFullScaleMax_AI3 -9999...+9999 Analogā€‚inputā€‚AI3ā€‚fullā€‚scaleā€‚value

Theā€‚temperatureā€‚andā€‚humidityā€‚measurement,ā€‚asā€‚wellā€‚asā€‚theā€‚correspondingā€‚precisionsā€‚andā€‚tolerances,ā€‚referā€‚toā€‚theā€‚applicationā€‚pointā€‚ofā€‚theā€‚probesā€‚insideā€‚theā€‚equipment.

Ifā€‚ theseā€‚sameā€‚measurementsā€‚areā€‚toā€‚beā€‚referredā€‚toā€‚airā€‚conditionsā€‚outsideā€‚ofā€‚theā€‚equipment,ā€‚forā€‚exampleā€‚ambientā€‚measure-ments,ā€‚accountā€‚mustā€‚beā€‚takenā€‚ofā€‚offsetā€‚(differential)ā€‚parametersā€‚thatā€‚dependā€‚onā€‚theā€‚installationā€‚andā€‚usageā€‚conditionsā€‚ofā€‚theā€‚equipmentā€‚itself.ā€‚Theā€‚differentialsā€‚forā€‚exampleā€‚Calibration parameters that can be set are:

Parameter Description Unit of measure RangeCalibration_AI1 Analogā€‚inputā€‚AI1ā€‚differentialā€‚ Ā°C/10ā€‚orā€‚Ā°F/10 -180ā€‚...ā€‚180Calibration_AI2 Analogā€‚inputā€‚AI2ā€‚differentialā€‚ Ā°C/10ā€‚orā€‚Ā°F/10 -180ā€‚...ā€‚180

Calibration_AI3 Analogā€‚inputā€‚AI3ā€‚differentialā€‚ - -1000ā€‚...ā€‚1000

Calibration_AI4 Analogā€‚inputā€‚AI4ā€‚differential - -1000ā€‚...ā€‚1000

Forā€‚on-boardā€‚(built-in)ā€‚sensors,ā€‚Compensation parameters are also available

Parameter Description Unit of measure Range

Compensation_AI1Internal compensation AI1

differenceā€‚betweenā€‚externalā€‚airā€‚temperatureā€‚andā€‚measure-mentā€‚readā€‚byā€‚NTCā€‚sensorā€‚AI1

Ā°C/10ā€‚orā€‚Ā°F/10 -1000ā€‚...ā€‚1000

Compensation_AI4

Internal compensation AI4differenceā€‚betweenā€‚externalā€‚temperatureā€‚andā€‚Tā€‚measure-

mentā€‚readā€‚byā€‚RHā€‚sensorā€‚AI4ā€‚(thisā€‚temperatureā€‚isā€‚usedā€‚toā€‚cal-culateā€‚theā€‚relativeā€‚humidityā€‚basedā€‚onā€‚psychrometricā€‚charts)

Ā°C/10ā€‚orā€‚Ā°F/10 -1000ā€‚...ā€‚1000

Defaultā€‚valuesā€‚forā€‚theseā€‚offsetsā€‚assumeā€‚aā€‚typicalā€‚installationā€‚withā€‚wallā€‚mountedā€‚backplateā€‚inā€‚aā€‚non-ventilatedā€‚environmentā€‚andā€‚withā€‚theā€‚displayā€‚backlightingā€‚mainlyā€‚OFF.ā€‚Inā€‚theseā€‚conditionsā€‚theā€‚followingā€‚calibrationā€‚valuesā€‚areā€‚obtained:

Compensation_AI1 =ā€‚-12.0ā€‚Ā°Cā€‚(10.4ā€‚Ā°F)Compensation_AI4 =ā€‚-10.5ā€‚Ā°Cā€‚(13.1ā€‚Ā°F)

Ifā€‚theā€‚usageā€‚conditionsā€‚requireā€‚theā€‚backlightā€‚toā€‚beā€‚mainlyā€‚ON,ā€‚theā€‚valuesā€‚mustā€‚beā€‚modifiedā€‚asā€‚follows:

Compensation_AI1ā€‚=ā€‚-15.0ā€‚Ā°Cā€‚(5.0ā€‚Ā°F)Compensation_AI4 =ā€‚-13.0ā€‚Ā°Cā€‚(8.6ā€‚Ā°F)

NOTE:ā€‚Forā€‚otherā€‚mountingā€‚conditionsā€‚carryā€‚outā€‚calibrationā€‚duringā€‚installation,ā€‚checkingā€‚theā€‚temperatureā€‚andā€‚relativeā€‚humidityā€‚differencesā€‚betweenā€‚theā€‚externalā€‚airā€‚andā€‚theā€‚internalā€‚probesā€‚andā€‚ifā€‚necessaryā€‚correctingā€‚theā€‚parametersā€‚Compensation_AI1 / Compensation_AI4.Inā€‚anyā€‚caseā€‚itā€‚isā€‚possibleā€‚toā€‚achieveā€‚aā€‚precisionā€‚ofā€‚Ā±ā€‚1Ā°Cā€‚onā€‚theā€‚temperatureā€‚measurementā€‚andā€‚Ā±ā€‚3%RHā€‚onā€‚theā€‚relativeā€‚humi-dityā€‚measurement.

Page 97: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

97EIO0000002030 09/2015

8.2. Analog outputs configuration for M171 PerformanceSee CHAPTER 3 Electrical connections on page 23ā€‚forā€‚theā€‚numberā€‚andā€‚typeā€‚ofā€‚analogā€‚outputsā€‚usedā€‚andā€‚forā€‚informationā€‚onā€‚theā€‚symbolsā€‚usedā€‚onā€‚labelsā€‚suppliedā€‚withā€‚theā€‚controller.Thereā€‚areā€‚5ā€‚analogā€‚outputsā€‚withā€‚theā€‚followingā€‚characteristics:

Configuration of analog output

AO1/AO5 AO2 AO3 AO4Current/voltageā€‚output

AO1ā€‚andā€‚AO5ā€‚areā€‚configuredā€‚inā€‚pairs. Current/voltageā€‚output Current/voltageā€‚output Current/voltageā€‚output

Sub-mode configuration AO5Only if AO1/AO5 have not

been configured as voltage outputs (value ā‰ 2)

- - -

Outputsā€‚AO1,ā€‚AO2,ā€‚AO3,ā€‚AO4,ā€‚AO5ā€‚areā€‚configurableā€‚as:ā€¢ 0ā€‚=ā€‚4-20mAā€‚currentā€‚analogā€‚output

ā€¢ 1ā€‚=ā€‚outputā€‚configuredā€‚asā€‚0ā€¦20mAā€‚switchā€‚(ON=ā€‚maxā€‚20mA,ā€‚OFF=0mA)ā€‚forā€‚pilotingā€‚switchā€‚loadsā€‚suchā€‚asā€‚ON/OFF.

ā€¢ 2ā€‚=ā€‚0-10Vā€‚voltageā€‚analogā€‚output.Outputs AO4, AO5 can be configured as Open Collector output. Set:ā€¢ Cfg_AO4ā€‚=ā€‚1ā€‚(ON/OFFā€‚typeā€‚switching)

ā€¢ Cfg_AO1_AO5ā€‚=ā€‚0ā€‚orā€‚1ā€‚(pairā€‚ofā€‚outputsā€‚configuredā€‚asā€‚currentā€‚outputs)

ā€¢ SubCfg_AO5ā€‚=ā€‚1ā€‚(ON/OFFā€‚typeā€‚switching)

ā€¢ Analogā€‚valueā€‚pilotedā€‚forā€‚bothā€‚outputsā€‚=ā€‚0.For developers using TM171SW (SoMachineHVAC):ā€‚ seeā€‚ theā€‚ sysAOasOCā€‚ functionā€‚ (targetā€‚ block)ā€‚ inā€‚ theā€‚ TM171SW (SoMachineHVAC) Applicationā€‚Library

8.3. Digital inputs configuration for M171 PerformanceThereā€‚areā€‚8ā€‚digitalā€‚inputs,ā€‚identifiedā€‚belowā€‚asā€‚DI1ā€¦DI8.ā€‚Theyā€‚areā€‚groupedā€‚as:ā€¢ DI1ā€¦DI4

ā€¢ DI5ā€¦DI8Each one has its own common contact.Digitalā€‚inputsā€‚canā€‚beā€‚usedā€‚asā€‚pulseā€‚counters.Theā€‚lengthā€‚ofā€‚theā€‚pulseā€‚(positiveā€‚orā€‚negative)ā€‚mustā€‚beā€‚greaterā€‚thanā€‚12ms.

Thereā€‚isā€‚alsoā€‚aā€‚fast,ā€‚voltage-freeā€‚digitalā€‚inputā€‚thatā€‚alsoā€‚worksā€‚asā€‚aā€‚pulseā€‚counter:ā€¢ Itā€‚readsā€‚theā€‚numberā€‚ofā€‚timesā€‚theā€‚contactā€‚appliedā€‚toā€‚theā€‚inputā€‚closes.

ā€¢ Itā€‚readsā€‚frequenciesā€‚fromā€‚0.1ā€‚Hzā€‚toā€‚1ā€‚kHz.

8.4. Digital outputs configuration for M171 PerformanceSee CHAPTER 3 Electrical connections on page 23ā€‚forā€‚theā€‚numberā€‚andā€‚capacityā€‚ofā€‚relaysā€‚and/orā€‚SSRā€‚dependingā€‚onā€‚theā€‚reference,ā€‚andā€‚forā€‚informationā€‚onā€‚theā€‚symbolsā€‚usedā€‚onā€‚labelsā€‚suppliedā€‚withā€‚theā€‚controller.ā€¢ Thereā€‚areā€‚7ā€‚highā€‚voltageā€‚outputsā€‚(relays)ā€‚identifiedā€‚asā€‚DO1ā€¦DO7.

ā€¢ In references TM171PDM27Sā€‚thereā€‚areā€‚5ā€‚highā€‚voltageā€‚outputsā€‚(relays)ā€‚identifiedā€‚asā€‚DO1ā€¦DO3,ā€‚DO6,ā€‚DO7ā€‚whereasā€‚thereā€‚areā€‚2ā€‚SSRā€‚outputsā€‚identifiedā€‚asā€‚DO3ā€¦DO4.

Page 98: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

98 EIO0000002030 09/2015

8.5. Ports configuration for M171 Performance using DipSwitchDipswitchesā€‚ areā€‚ usedā€‚ forā€‚ theā€‚ configurationā€‚ ofā€‚ serialā€‚ ports,ā€‚whichā€‚ canā€‚ beā€‚On-Boardā€‚ (OB)ā€‚ orā€‚ availableā€‚ viaā€‚Communicationā€‚Moduleā€‚TM171Aā€‚modulesā€‚(PI).

4-position lateral DipSwitchThereā€‚isā€‚aā€‚4-positionā€‚lateralā€‚DipSwitchā€‚(microswitch)ā€‚inā€‚all TM171PDM27,ā€‚TM171PBM27R and TM171EPR expansion references.

4 DIP SWITCH

1234ON

TM171ppppp

M171USB

miniUSB

6 and 10-position DipSwitchUnderā€‚theā€‚frontā€‚panel,ā€‚TM171PBM27R and TM171EPR expansion references have:ā€¢ Aā€‚6-positionā€‚DipSwitchā€‚(microswitch)ā€‚(SW2)

ā€¢ Aā€‚10-positionā€‚DipSwitchā€‚(microswitch) (SW1)

1

M171USB

miniUSB

TM171PBM27RTM171EP27R / TM171EP14R

10 DIP SWITCH

SW1 SW2

6 DIP SWITCH

12345678910

ON ON

123456M171USB

miniUSB

2

Removeā€‚theā€‚frontā€‚panelā€‚withā€‚aā€‚fingernail,ā€‚orā€‚theā€‚tipā€‚ofā€‚aā€‚slotā€‚headā€‚screwdriver.Configureā€‚asā€‚necessaryā€‚thenā€‚replaceā€‚theā€‚frontā€‚panelā€‚byā€‚pressingā€‚lightlyā€‚backā€‚intoā€‚place.

4-position DipSwitch compared to 6 and 10-position DipSwitch

1234ON

10 DIP SWITCH

SW1 SW2

6 DIP SWITCH

4 DIP SWITCH

ONOFF

12345678910

ON ON

123456

ONOFF

M171USB

miniUSB

NOTE. OFF=0ā€‚/ā€‚ON=1

Page 99: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

99EIO0000002030 09/2015

8.5.1. TM171PDM27 DipSwitch

4-position lateral DipSwitchUsedā€‚forā€‚serialā€‚addressingā€‚only.Theā€‚addressā€‚isā€‚givenā€‚byā€‚theā€‚sumā€‚ofā€‚theā€‚valueā€‚ofā€‚aā€‚parameterā€‚(1)ā€‚plusā€‚theā€‚valueā€‚definedā€‚byā€‚theā€‚dipswitchā€‚(16ā€‚addresses).

4-position dipSerial Addressing Default=0 Dip value Dip4 3 2 1

LOW Address

1234ON

0 0 0 0 01 0 0 0 12 0 0 1 03 0 0 1 1... ... ... ... ...

15 1 1 1 1

Address

Parameter (1) Default Parameter LOW addressDefault=0

Addr_RS485_OB 1

+

LOW Address

1234ON

Addr_CAN_OB 1Addr_RS485_PI 1Addr_CAN_PI 1

Addr_RS232_PI 1

Ip_4_ETH_PI 100

Page 100: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

100 EIO0000002030 09/2015

8.5.2. TM171PBM27R DipSwitch

12345678910

ON

ON

123456

LOW Address

1234ON

+HIGH Address LOW Address

+HIGH Address LOW Address

Addressmax 127

Addressmax 255

CAN OB

RS485OB

SW1

SW2

CAN PIRS485 PIRS232 PIETH PIBaud

ProtocolParity

Baud

TM171PBM27R

Fig. 59. TM171PBM27Rā€‚Dipswitch

Serial addressing4-position DipSwitchUsedā€‚forā€‚theā€‚serialā€‚addressingā€‚ofā€‚theā€‚plug-inā€‚portā€‚(PI)ā€‚only.

In the serial addressing of On-Board (OB) serial ports, the 4-position dip is not used for TM171PBM27R.

Theā€‚addressā€‚isā€‚givenā€‚byā€‚theā€‚sumā€‚ofā€‚theā€‚valueā€‚ofā€‚aā€‚parameterā€‚(1)ā€‚plusā€‚theā€‚valueā€‚definedā€‚byā€‚theā€‚dipswitchā€‚(16ā€‚addresses).

4-position dipSerial Addressing Default=0 Dip value Dip4 3 2 1

LOW Address

1234ON

0 0 0 0 01 0 0 0 12 0 0 1 03 0 0 1 1... ... ... ... ...

15 1 1 1 1

Address

Parameter (1) Default Parameter LOW addressDefault=0

Addr_RS485_PI 1

+

LOW Address

1234ONAddr_CAN_PI 1

Addr_RS232_PI 1

Ip_4_ETH_PI 100

Page 101: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

101EIO0000002030 09/2015

Baud 6-position TM171PBM27R DipSwitchTheā€‚actualā€‚CANā€‚Baudā€‚rateā€‚comprisesā€‚theā€‚sumā€‚ofā€‚parameterā€‚Baud_CAN_OBā€‚plusā€‚theā€‚compositeā€‚valueā€‚ofā€‚theā€‚3-positionā€‚dip-switchesā€‚(8ā€‚values).

CAN baud selectionOB

Default = 500 baud

Dip value Dip6 5 4 3 2 1

ON

123456

SW2

Baud

CAN 0 0 0 0 - - -

Actual CAN Baud ValueDefault = 500 baud Parameter Baud_CAN_OB CAN baud selection

Default = 02=500

= Parameter Baud_CAN_OB +ON

123456

SW2

Baud

CAN

3=2504=1255=1256=50

defaultā€‚example 2 + 0

CAN OB serial addressing6-position dipswitch + 4-position dipswitchTheā€‚addressingā€‚comprisesā€‚theā€‚sumā€‚ofā€‚parameterā€‚Addr_CAN_OBā€‚plusā€‚theā€‚compositeā€‚valueā€‚ofā€‚theā€‚6ā€‚andā€‚4-positionā€‚dipswitchesā€‚(127ā€‚addresses).

6-position dipHIGH address

4-position dipLOW address

CAN OB serial addressingDefault = 1

Dip value Dip6 5 4 3 2 1 Dip4 3 2 1

ON

123456

LOW Address

1234ON

+HIGH Address LOW Address

Addressmax 127 CAN

SW2

0 - - - 0 0 0 0 0 0 01 - - - 0 0 0 0 0 0 12 - - - 0 0 0 0 0 1 03 - - - 0 0 0 0 0 1 1... ... ... ... ... ... ... ... ... ... ...

126 - - - 1 1 1 1 1 1 0

AddressParameter HIGH+LOW address - Default = 0

Addr_CAN_OB +

ON

123456

LOW Address

1234ON

+HIGH Address LOW Address

Addressmax 127 CAN

SW2

1 + 0

Page 102: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

102 EIO0000002030 09/2015

RS485 OB serial configuration10-position dipswitch

Dip value Dip10 9 8 7 6 5 4 3 2 1

Protocol selection RS485 OBDefault = 1

12345678910

ONSW1

Protocol

RS485OB

0 0 - - - - - - - - -

1 1 - - - - - - - - -

Parity selec-tion RS485

OBDefault =

EVEN

12345678910

ONSW1

Parity

RS485OB

0 - 0 0 - - - - - - -1 - 0 1 - - - - - - -

2 - 1 0 - - - - - - -

Baud selec-tion

RS485 OBDefault =

38400 baud

12345678910

ON

Baud

RS485OB

SW1

0 - - - 0 0 0 - - - -1 - - - 0 0 1 - - - -2 - - - 0 1 0 - - - -3 - - - 0 1 1 - - - -4 - - - 1 0 0 - - - -5 - - - 1 0 1 - - - -

Parameter Default Parameter LOW addressDefault = 0

Proto_RS485_OB2=Reserved

+12345678910

ONSW1

Protocol

RS485OB

3=ā€‚Modbusā€‚RTU

Parity_RS485_OB 0=ā€‚NULL +12345678910

ONSW1

Parity

RS485OB

1=ā€‚ODD2=ā€‚EVEN

Baud_RS485_OB

0=9600

+12345678910

ON

Baud

RS485OB

SW1

1=192002=384003=576004=768005=115200

Page 103: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

103EIO0000002030 09/2015

RS485 OB serial addressing10-position dipswitch + 4-position dipswitchTheā€‚addressā€‚isā€‚givenā€‚byā€‚theā€‚sumā€‚ofā€‚theā€‚valueā€‚ofā€‚theā€‚twoā€‚6ā€‚andā€‚4-positionā€‚dipswitchesā€‚(255ā€‚addresses).

10-position dipHIGH address

4-position dipLOW address

Serial addressingRS485 OBDefault = 1

Dip value Dip10...5 4 3 2 1 Dip4 3 2 1

12345678910

ON

1234ON

+HIGH Address LOW Address

Addressmax 254

RS485OB

SW1

0 - 0 0 0 0 0 0 0 01 - 0 0 0 0 0 0 0 12 - 0 0 0 0 0 0 1 03 - 0 0 0 0 0 0 1 1... ... ... ... ... ... ... ... ... ...

254 - 1 1 1 1 1 1 1 0

Address

Parameter LOW addressDefault = 0

Addr_RS485_OB +

12345678910

ON

1234ON

+HIGH Address LOW Address

Addressmax 254

RS485OB

SW1

1 + 0

NOTE:ā€‚Anyā€‚otherā€‚combinationā€‚ofā€‚theā€‚dipswitchesā€‚notā€‚listedā€‚hereā€‚isā€‚notā€‚permitted.

Toā€‚summarize,ā€‚inā€‚theā€‚caseā€‚ofā€‚TM171PBM27R,ā€‚theā€‚defaultā€‚configurationā€‚forā€‚allā€‚dipswitchesā€‚isā€‚asā€‚follows:

TM171PBM27R DipSwitch default configuration

12345678910

ONON

123456 1234ON CANRS485 RS485

RS232SW1 SW2

DEFAULT SETTING

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 00 0 0 0

Fig. 60. Defaultā€‚setting

RS232 OB configuration and serial addressing6 and 10-position dipswitches are not used.See CHAPTER 9 Parameters on page 107.

Page 104: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

104 EIO0000002030 09/2015

8.5.3. TM171EP27R expansion DipSwitchTM171EP27Rā€‚expansionā€‚serialsā€‚areā€‚configuredā€‚byā€‚configuringā€‚dipswitches,ā€‚withoutā€‚usingā€‚theā€‚"internal"ā€‚parametersā€‚visibleā€‚inā€‚the CHAPTER 9 Parameters on page 107.

DipSwitch TM171EP27R

12345678910

ON

ON

123456

LOW Address

1234ON

+HIGH Address LOW Address

+HIGH Address LOW Address

Addressmax 127

Addressmax 255

CAN

SW1

SW2

OFF OFFnull

OFF ONodd

ON OFFeven

MO

DB

US

RTU

OFF OFF OFF500

OFF OFF ON250

OFF ON OFF125

OFF ON ON125

ON OFF OFF50

ON

DEFAULT SETTING

Baud

ProtocolParity

Baud

RS485RS232 PI OFF OFF OFF

9600OFF OFF ON

19200OFF ON OFF

38400OFF ON ON

57600ON OFF OFF

76800ON OFF ON

115200

Fig. 61. Dipswitchā€‚TM171EP27R

Baud6-position TM171EP27R dipswitch

CAN baud selectionOB and PI

Default = 500 baudBaud Dip

value Dip6 5 4 3 2 1

ON

123456

SW2

Baud

CAN

500 0 0 0 0 - - -250 1 0 0 1 - - -125 2 0 1 0 - - -125 3 0 1 1 - - -50 4 1 0 0 - - -

CAN OB and PI serial addressing6-position dipswitch + 4-position TM171EP27R dipswitchTheā€‚addressā€‚isā€‚givenā€‚byā€‚theā€‚valueā€‚ofā€‚theā€‚6ā€‚andā€‚4-positionā€‚dipswitchesā€‚(127ā€‚addresses).

6-position dipHIGH address

4-position dipLOW address

CAN serial addressingOB and PIDefault = 1

Address Dip value Dip6 5 4 3 2 1 Dip4 3 2 1

ON

123456

LOW Address

1234ON

+HIGH Address LOW Address

Addressmax 127 CAN

SW2

1 0 - - - 0 0 0 0 0 0 02 1 - - - 0 0 0 0 0 0 13 2 - - - 0 0 0 0 0 1 04 3 - - - 0 0 0 0 0 1 1... ... ... ... ... ... ... ... ... ... ... ...

127 126 - - - 1 1 1 1 1 1 0

Page 105: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

105EIO0000002030 09/2015

RS232 PI and RS485 OB serial configuration10-position dipswitch

Protocol Dip value Dip10 9 8 7 6 5 4 3 2 1

Protocol selec-tion RS232 PI /

RS485 OBDefault = 1

12345678910

ON

Protocol

SW1RS485

RS232 PI

Reservedā€‚for

Schneider Electric use

0 0 - - - - - - - - -

ModBusRTU 1 1 - - - - - - - - -

Parity selection RS232 PI / RS485 OB

Default = EVEN

12345678910

ONSW1

Parity

RS485RS232 PI

Null 0 - 0 0 - - - - - - -Odd 1 - 0 1 - - - - - - -EvenEven 2 - 1 0 - - - - - - -

Baud selectionRS232 PI / RS485 OB

Default = 38400 baud

12345678910

ON

Baud

SW1RS485

RS232 PI

9600 0 - - - 0 0 0 - - - -19200 1 - - - 0 0 1 - - - -38400 2 - - - 0 1 0 - - - -57600 3 - - - 0 1 1 - - - -76800 4 - - - 1 0 0 - - - -115200 5 - - - 1 0 1 - - - -

RS485 OB and PI serial addressing10-position dipswitch + 4-position dipswitchTheā€‚addressā€‚isā€‚givenā€‚byā€‚theā€‚sumā€‚ofā€‚theā€‚valueā€‚ofā€‚theā€‚twoā€‚6ā€‚andā€‚4-positionā€‚dipswitchesā€‚(255ā€‚addresses).

10-position dipHIGH address

4-position dipLOW address

CAN serial addressingOB and PIDefault = 1

Address Dip value Dip10...5 4 3 2 1 Dip4 3 2 1

12345678910

ON

1234ON

+HIGH Address LOW Address

Addressmax 255

RS485RS232 PI

SW1

1 0 - 0 0 0 0 0 0 0 02 1 - 0 0 0 0 0 0 0 13 2 - 0 0 0 0 0 0 1 04 3 - 0 0 0 0 0 0 1 1... ... ... ... ... ... ... ... ... ... ...

255 254 - 1 1 1 1 1 1 1 0

NOTE: Anyā€‚otherā€‚combinationā€‚ofā€‚theā€‚dipswitchesā€‚notā€‚listedā€‚hereā€‚isā€‚notā€‚permitted.ā€‚

Toā€‚summarize,ā€‚inā€‚theā€‚caseā€‚ofā€‚TM171EP27R,ā€‚theā€‚defaultā€‚configurationā€‚forā€‚theā€‚dipswitchesā€‚isā€‚asā€‚follows:

TM171EP27R DipSwitch default configuration

12345678910

ONON

123456 1234ON CANRS485 RS485

RS232SW1 SW2

DEFAULT SETTING

0 0 0 0 0 0 0 1 0 0 1 0 0 0 0 00 0 0 0

Fig. 62. Defaultā€‚setting

Page 106: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

106 EIO0000002030 09/2015

8.5.4. TM171EP14R expansion DipSwitch

M171

1234ON

LOW AddressCAN terminal resistors

Fig. 63. 4-positionā€‚lateralā€‚DipSwitch

Used for:ā€¢ serial addressingā€‚(dipā€‚1ā€‚andā€‚2)ā€¢ lineā€‚terminationā€‚(dipā€‚3ā€‚andā€‚4)

4-position dip

Serial AddressingAddress

= DipValue+1

Dip value Dip4 3 2 1

LOW Address CAN terminalresistors

1234ON

1 0 - - 0 02 1 - - 0 13 2 - - 1 04 3 - - 1 1

Dip value(Address)

Dip value(Address) Dip4 3 2 1

120 Ī© termination

120 Ī© termination 1 1 - -

CAN OB serial addressingTheā€‚addressingā€‚comprisesā€‚theā€‚sumā€‚ofā€‚parameterā€‚Addr_CAN_OBā€‚plusā€‚theā€‚compositeā€‚valueā€‚ofā€‚theā€‚4-positionā€‚dipswitchesā€‚(onlyā€‚dipā€‚1ā€‚andā€‚2).

Actual CAN AdresssDefault = 1

Parameter Addr_CAN_OBDefault = 1

CAN address selectionDefault = 0

1

= Parameter Baud_CAN_OB +

LOW Address CAN terminalresistors

1234ON2

...

...127 max

defaultā€‚example 1 + 0

BaudBaudā€‚rateā€‚isā€‚setā€‚byā€‚Baud_CAN_OB parameter

Line Termination resistorsDip4ā€‚andā€‚Dip3ā€‚bothā€‚=ā€‚1ā€‚connectsā€‚L/Hā€‚CANā€‚linesā€‚toā€‚120ā€‚Ī© termination

Page 107: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

107EIO0000002030 09/2015

User-parameterizationā€‚rendersā€‚theā€‚Modicon M171P configurable.Parametersā€‚canā€‚beā€‚changedā€‚using:ā€¢ Keysā€‚onā€‚ theā€‚TM171PDM27ā€‚ /ā€‚M171 Performance Flush front panel or remote M171 Performance Display Graphic

(TM171DGRP)ā€‚panel.

ā€¢ PC and TM171SW (SoMachineHVAC)ā€‚software.Theā€‚followingā€‚sectionsā€‚provideā€‚aā€‚detailedā€‚analysisā€‚ofā€‚eachā€‚parameter,ā€‚dividedā€‚intoā€‚categoriesā€‚(folders).

For M171 Performance, the parameter table showsā€‚theā€‚configurationā€‚parametersā€‚forā€‚theā€‚controllerā€‚savedā€‚inā€‚theā€‚non-volatileā€‚memory.For M171 Performance Flush, theā€‚parameterā€‚ tableā€‚containsā€‚ theā€‚deviceā€‚configurationā€‚parametersā€‚availableā€‚ inā€‚TM171SW (SoMachineHVAC)ā€‚Deviceā€‚andā€‚inā€‚theā€‚DIAGNOSTICSā€‚(DIA)ā€‚/ā€‚BIOSā€‚Parametersā€‚menu.

Modbus commands available and data areasThe following commands are implemented:

Modbus command Description of command3 (3 hex) Readā€‚multipleā€‚registersā€‚onā€‚Clientā€‚side

16 (10 hex) Writeā€‚multipleā€‚registersā€‚onā€‚Clientā€‚side

43 (2B hex)

Readā€‚deviceā€‚ID:Manufacturerā€‚ID

Model IDVersionā€‚ID

9.1. M171 Performance parameter tableThisā€‚tableā€‚presentsā€‚theā€‚columnā€‚headersā€‚ofā€‚theā€‚parameterā€‚tableā€‚thatā€‚follows.

Column DescriptionLABEL Indicatesā€‚theā€‚labelā€‚usedā€‚toā€‚displayā€‚theā€‚parametersā€‚inā€‚theā€‚menuā€‚ofā€‚theā€‚controller.PAR. VALUE ADDRESS

Indicatesā€‚theā€‚addressā€‚ofā€‚theā€‚modbusā€‚registerā€‚containingā€‚theā€‚resourceā€‚toā€‚beā€‚accessed.

DATA SIZE Indicates the size of the data in bits.

CPL

Indicatesā€‚theā€‚registerā€‚valueā€‚conversion.Toā€‚carryā€‚outā€‚theā€‚conversion,ā€‚proceedā€‚asā€‚follows:ā€¢ Ifā€‚theā€‚valueā€‚inā€‚theā€‚registerā€‚isā€‚betweenā€‚0ā€‚andā€‚32767,ā€‚theā€‚resultā€‚isā€‚theā€‚valueā€‚itselfā€‚(zeroā€‚andā€‚positiveā€‚values)

ā€¢ Ifā€‚theā€‚valueā€‚inā€‚theā€‚registerā€‚isā€‚betweenā€‚32768ā€‚andā€‚65535,ā€‚theā€‚resultā€‚isā€‚theā€‚valueā€‚ofā€‚theā€‚registerā€‚minusā€‚65536ā€‚(negativeā€‚values)

ā€¢ Whenā€‚theā€‚fieldā€‚indicatesā€‚ā€œ-1ā€,ā€‚theā€‚valueā€‚readā€‚byā€‚theā€‚registerā€‚requiresā€‚conversion,ā€‚becauseā€‚theā€‚valueā€‚repre-sentsā€‚aā€‚numberā€‚withā€‚aā€‚sign.ā€‚

RESETIndicates whether the controller MUST be rebooted after the parameter has been modified.ā€¢ Yā€‚=ā€‚YESā€‚theā€‚controllerā€‚MUSTā€‚beā€‚rebootedā€‚toā€‚modifyā€‚theā€‚parameter.

ā€¢ Emptyā€‚"ā€‚"ā€‚=ā€‚NOā€‚theā€‚controllerā€‚doesā€‚notā€‚needā€‚toā€‚beā€‚rebootedā€‚toā€‚modifyā€‚theā€‚parameter

RANGE Describesā€‚ theā€‚ intervalā€‚ ofā€‚ valuesā€‚ thatā€‚ canā€‚ beā€‚ assignedā€‚ toā€‚ theā€‚ parameter.ā€‚ Itā€‚ canā€‚ beā€‚ correlatedā€‚ withā€‚ otherā€‚equipmentā€‚parametersā€‚(indicatedā€‚inā€‚theā€‚parameterā€‚label).

DEFAULT Indicatesā€‚theā€‚factoryā€‚settingā€‚forā€‚theā€‚reference.

U.M.Indicatesā€‚theā€‚unitā€‚ofā€‚measurementā€‚forā€‚valuesā€‚convertedā€‚accordingā€‚toā€‚theā€‚rulesā€‚indicatedā€‚inā€‚theā€‚CPLā€‚columnTheā€‚unitā€‚ofā€‚measurementā€‚shownā€‚isā€‚forā€‚exampleā€‚purposesā€‚only,ā€‚asā€‚itā€‚mayā€‚changeā€‚dependingā€‚onā€‚theā€‚applicationā€‚(forā€‚exampleā€‚parametersā€‚withā€‚aā€‚U.M.ā€‚inā€‚Ā°C/barā€‚couldā€‚alsoā€‚haveā€‚%RH)

CHAPTER 9 Parameters

Page 108: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

108 EIO0000002030 09/2015

9.1.1. TM171PDM27 / TM171PBM27R / TM171EP27R parametersLA

BEL

PAR

. VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

ACKNOWLEDGEMENT folder

Par_TAB 15716 WORD - Y Map codeNote:ā€‚read/writeā€‚parameter 0ā€‚ā€¦ā€‚65535 0 num

Par_POLI 15717 WORD - Y Model CodeNote:ā€‚read/writeā€‚parameter 0ā€‚ā€¦ā€‚65535 2049 num

Par_PARMOD 15719 BOOL - -

Parameter modifiedFlagā€‚ indicatingā€‚ changeā€‚ toā€‚ defaultā€‚settings.ā€¢ 0=ā€‚mapā€‚notā€‚modified.

ā€¢ 1=ā€‚atā€‚ leastā€‚ oneā€‚parameterā€‚ hasā€‚been modified with respect to theā€‚originalā€‚configuration.

0ā€‚ā€¦ā€‚1 0 num

AI CALIBRATION folder

Gain_Ntc_AI1 15616 WORD - - Ai1 NTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_Ntc_AI2 15617 WORD - - Ai2 NTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_Ntc_AI3 15618 WORD - - Ai3 NTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_PT1000_AI3 15619 WORD - - Ai3 PT1000 calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_5V_AI3 15620 WORD - - Ai3 0-5V calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_10V_AI3 15621 WORD - - Ai3 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_mA_AI3 15622 WORD - - Ai3 4-20mA calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_Ntc_AI4 15623 WORD - - Ai4 NTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_PT1000_AI4 15624 WORD - - Ai4 PT1000 calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_5V_AI4 15625 WORD - - Ai4 0-5V calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_10V_AI4 15626 WORD - - Ai4 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_mA_AI4 15627 WORD - - Ai4 4-20mA calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_Ntc_AI5 15628 WORD - - Ai5 NTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_PT1000_AI5 15629 WORD - - Ai5 PT1000 calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_5V_AI5 15630 WORD - - Ai5 0-5V calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_10V_AI5 15631 WORD - - Ai5 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_mA_AI5 15632 WORD - - Ai5 4-20mA calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_Ntc_AI6 15633 WORD - - Ai6 NTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_PT1000_AI6 15634 WORD - - Ai6 PT1000 calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_5V_AI6 15635 WORD - - Ai6 0-5V calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_10V_AI6 15636 WORD - - Ai6 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_mA_AI6 15637 WORD - - Ai6 0-10mA calibration gain 0ā€‚ā€¦ā€‚65535 32768 numOffs_Ntc_AI1 15650 WORD -1 - Ai1 NTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_Ntc_AI2 15651 WORD -1 - Ai2 NTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_Ntc_AI3 15652 WORD -1 - Ai3 NTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_PT1000_AI3 15653 WORD -1 - Ai3 PT1000 calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Page 109: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

109EIO0000002030 09/2015

LAB

EL

PAR

. VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

Offs_5V_AI3 15654 WORD -1 - Ai3 0-5V calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_10V_AI3 15655 WORD -1 - Ai3 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_mA_AI3 15656 WORD -1 - Ai3 4-20mA calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_Ntc_AI4 15657 WORD -1 - Ai4 NTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_PT1000_AI4 15658 WORD -1 - Ai4 PT1000 calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_5V_AI4 15659 WORD -1 - Ai4 0-5V calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_10V_AI4 15660 WORD -1 - Ai4 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_mA_AI4 15661 WORD -1 - Ai4 4-20mA calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_Ntc_AI5 15662 WORD -1 - Ai5 NTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_PT1000_AI5 15663 WORD -1 - Ai5 PT1000 calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_5V_AI5 15664 WORD -1 - Ai5 0-5V calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_10V_AI5 15665 WORD -1 - Ai5 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_mA_AI5 15666 WORD -1 - Ai5 4-20mA calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_Ntc_AI6 15667 WORD -1 - Ai6 NTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_PT1000_AI6 15668 WORD -1 - Ai6 PT1000 calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_5V_AI6 15669 WORD -1 - Ai6 0-5V calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_10V_AI6 15670 WORD -1 - Ai6 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_mA_AI6 15671 WORD -1 - Ai6 4-20mA calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

AO CALIBRATION folder

Gain_10V_AO1 15684 WORD - - AO1 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_mA_AO1 15685 WORD - - AO1 4-20mA calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_10V_AO2 15686 WORD - - AO2 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_mA_AO2 15687 WORD - - AO2 4-20mA calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_10V_AO3 15688 WORD - - AO3 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_mA_AO3 15689 WORD - - AO3 4-20mA calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_10V_AO4 15690 WORD - - AO4 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_mA_AO4 15691 WORD - - AO4 4-20mA calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_10V_AO5 15692 WORD - - AO5 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_mA_AO5 15693 WORD - - AO5 4-20mA calibration gain 0ā€‚ā€¦ā€‚65535 32768 numOffs_10V_AO1 15700 WORD -1 - AO1 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_mA_AO1 15701 WORD -1 - AO1 4-20mA calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_10V_AO2 15702 WORD -1 - AO2 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_mA_AO2 15703 WORD -1 - AO2 4-20mA calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_10V_AO3 15704 WORD -1 - AO3 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_mA_AO3 15705 WORD -1 - AO3 4-20mA calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_10V_AO4 15706 WORD -1 - AO4 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Page 110: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

110 EIO0000002030 09/2015

LAB

EL

PAR

. VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

Offs_mA_AO4 15707 WORD -1 - AO4 4-20mA calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_10V_AO5 15708 WORD -1 - AO5 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_mA_AO5 15709 WORD -1 - AO5 4-20mA calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

ANALOG INPUTS folder

Temp_UM 15725 WORD - Y

Temperature unit of measure-mentā€¢ 0ā€‚=ā€‚Ā°C;

ā€¢ 1ā€‚=ā€‚Ā°F

0,ā€‚1 0 num

Cfg_Ai1 15726 WORD - -

Type of analog input Ai1ā€¢ 0=ā€‚NTCā€‚(NK103)

ā€¢ 1=ā€‚DI

ā€¢ 2=ā€‚NTCā€‚(103AT)

0 ... 2 2 num

Cfg_Ai2 15727 WORD - - Type of analog input Ai2Seeā€‚Cfg_Ai1 0 ... 2 2 num

Cfg_Ai3 15728 WORD - -

Type of analog input Ai3ā€¢ 0=ā€‚NTCā€‚(NK103)

ā€¢ 1=ā€‚DI

ā€¢ 2=ā€‚NTCā€‚(103AT)

ā€¢ 3ā€‚=ā€‚4ā€¦20mA

ā€¢ 4=0-10V

ā€¢ 5=0-5V

ā€¢ 6=Pt1000

ā€¢ 7=hĪ©(NTC)

ā€¢ 8=daĪ©(PT1000)

0 ... 8 3 num

Cfg_Ai4 15729 WORD - - Type of analog input Ai4Seeā€‚Cfg_Ai3 0 ... 8 3 num

Cfg_Ai5 15730 WORD - - Type of analog input Ai5Seeā€‚Cfg_Ai3 0 ... 8 3 num

Cfg_Ai6 15731 WORD - - Type of analog input Ai6Seeā€‚Cfg_Ai3 0 ... 8 3 num

FullScaleMin_Ai3 15736 WORD -1 -

Analog input Ai3 start of scale value Note:ā€‚Minimumā€‚ fullā€‚ scale:ā€‚ forā€‚ cur-rentā€‚ probes,ā€‚ valueā€‚ atā€‚ 4mA,ā€‚ forā€‚0-10Vā€‚ voltageā€‚ probes,ā€‚ valueā€‚ atā€‚0V,ā€‚ forā€‚ ratiometricā€‚ probesā€‚ (0-5V),ā€‚valueā€‚ atā€‚ 10%ā€‚ (correspondingā€‚ toā€‚0.5V).

-9999ā€¦+9999 0

Page 111: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

111EIO0000002030 09/2015

LAB

EL

PAR

. VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

FullScaleMax_Ai3 15737 WORD - -

Analog input Ai3 full scale valueNote:ā€‚Maximumā€‚ fullā€‚ scaleā€‚ forā€‚ cur-rentā€‚ probes,ā€‚ valueā€‚ atā€‚ 20mA,ā€‚ forā€‚0-10Vā€‚ voltageā€‚ probes,ā€‚ valueā€‚ atā€‚10V,ā€‚forā€‚ratiometricā€‚probesā€‚(0-5V),ā€‚valueā€‚ atā€‚ 90%ā€‚ (correspondingā€‚ toā€‚4.5V).

-9999ā€¦+9999 1000

FullScaleMin_Ai4 15738 WORD -1 -Analog input Ai4 start of scale valueSeeā€‚FullScaleMin_Ai3

-9999ā€¦+9999 0

FullScaleMax_Ai4 15739 WORD - - Analog input Ai4 full scale valueSeeā€‚FullScaleMAx_Ai3 -9999ā€¦+9999 1000

FullScaleMin_Ai5 15740 WORD -1 -Analog input Ai5 start of scale valueSeeā€‚FullScaleMin_Ai3

-9999ā€¦+9999 0

FullScaleMax_Ai5 15741 WORD - - Analog input Ai5 full scale valueSeeā€‚FullScaleMax_Ai3 -9999ā€¦+9999 1000

FullScaleMin_Ai6 15742 WORD -1 -Analog input Ai6 start of scale valueSeeā€‚FullScaleMin_Ai3

-9999ā€¦+9999 0

FullScaleMaxAi6 15743 WORD - - Analog input Ai6 full scale valueSeeā€‚FullScaleMax_Ai3 -9999ā€¦+9999 1000

Calibration_Ai1 15748 WORD -1 - Analog input Ai1 differential -180ā€‚...ā€‚180 0Ā°C/10ā€‚

or Ā°F/10

Calibration_Ai2 15749 WORD -1 - Analog input Ai2 differential -180ā€‚...ā€‚180 0 Ā°C/10ā€‚or

Ā°F/10

Calibration_Ai3 15750 WORD -1 - Analog input Ai3 differential -1000ā€‚...ā€‚1000 0

Calibration_Ai4 15751 WORD -1 - Analog input Ai4 differential -1000ā€‚...ā€‚1000 0

Calibration_Ai5 15752 WORD -1 - Analog input Ai5 differential -1000ā€‚...ā€‚1000 0

Calibration_Ai6 15753 WORD -1 - Analog input Ai6 differential -1000ā€‚...ā€‚1000 0

Page 112: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

112 EIO0000002030 09/2015

LAB

EL

PAR

. VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

ANALOG OUTPUTS V/I folder

Cfg_AO1_AO5 15758 WORD - Y

Type of analog output AO1/AO5AO1ā€‚ andā€‚ AO5ā€‚ areā€‚ configuredā€‚ inā€‚pairs.ā€‚Seeā€‚SubCfg_AO5ā€¢ 0ā€‚ =ā€‚ 4-20mAā€‚ currentā€‚ analogā€‚

output

ā€¢ 1ā€‚ =ā€‚ ON/OFFā€‚ outputā€‚ configu-redā€‚asā€‚0/4ā€¦20mAā€‚switchā€‚(ON=ā€‚maxā€‚20mA,ā€‚OFF=0mA)ā€‚forā€‚pilo-tingā€‚ switchā€‚ loadsā€‚ suchā€‚ asā€‚ ON/OFF.

ā€¢ 2=0-10Vā€‚ analogā€‚ outputā€‚ -ā€‚ vol-tage

Note. AO4 and AO5 can be con-figured as Open Collector A04=1, A01/A05=0 or 1, SubCfg_AO5=1

0 ... 2 0 num

Cfg_AO2 15759 WORD - Y Type of analog output AO2 See Cfg_ AO1_AO5 0 ... 2 0 num

Cfg_AO3 15760 WORD - Y Type of analog output AO3 See Cfg_ AO1_AO5 0 ... 2 0 num

Cfg_AO4 15761 WORD - Y Type of analog output AO4 0 ... 2 0 num

SubCfg_AO5 15762 WORD - Y

Analog output AO5 sub-mode function Onlyā€‚appliesā€‚ifā€‚Cfg_AO1_AO5ā‰ 2ā€¢ 0ā€‚ =ā€‚ 4-20mAā€‚ currentā€‚ analogā€‚

output

ā€¢ 1ā€‚ =ā€‚ ON/OFFā€‚ outputā€‚ configu-redā€‚asā€‚0/4ā€¦20mAā€‚switchā€‚(ON=ā€‚maxā€‚20mA,ā€‚OFF=0mA)ā€‚forā€‚pilo-tingā€‚ switchā€‚ loadsā€‚ suchā€‚ asā€‚ ON/OFF.

Note. AO4 and AO5 can be con-figured as Open Collector A04=1, A01/A05=0 or 1, SubCfg_AO5=1

0,ā€‚1 0 num

Page 113: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

113EIO0000002030 09/2015

TM171PDM27 / TM171PBM27R parameters

LAB

EL

PAR

. VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

ON BOARD RS485 folder

Addr_RS485_OB 15774 WORD - YOn-board RS485 serial addressTheā€‚actualā€‚addressā€‚isā€‚determinedā€‚byā€‚theā€‚sumā€‚ofā€‚ thisā€‚valueā€‚+ā€‚ theā€‚valueā€‚ofā€‚ theā€‚dipā€‚switch.

0 ... 255 1 num

Proto_RS485_OB 15775 WORD - YOn-board RS485 protocol selectionā€¢ 2ā€‚=ā€‚uNET

ā€¢ 3ā€‚=ā€‚Modbus/RTU

2 ... 3 3 num

Databit_RS485_OB 15776 WORD - Y On-board RS485 data bit numberFixed setting 8 8 ... 8 8 num

Stopbit_RS485_OB 15777 WORD - YOn-board RS485 stop bit number 1=ā€‚1ā€‚stopā€‚bit2=ā€‚2ā€‚stopā€‚bit

1... 2 1 num

Parity_RS485_OB 15778 WORD - Y

On-board RS485 protocol parity 0=ā€‚NULLā€¢ 1=ā€‚ODD

ā€¢ 2=ā€‚EVEN

0 ... 2 2 num

Baud_RS485_OB 15779 WORD - Y

On-board RS485 protocol baudrate ā€¢ 0=9600ā€‚baud

ā€¢ 1=19200ā€‚baud

ā€¢ 2=38400ā€‚baud

ā€¢ 3=57600ā€‚baud

ā€¢ 4=76800ā€‚baud

ā€¢ 5=115200ā€‚baud

0 ... 5 2 num

ON BOARD CAN folder

Addr_CAN_OB 15780 WORD - YOn-board CAN serial addressTheā€‚actualā€‚addressā€‚isā€‚determinedā€‚byā€‚theā€‚sumā€‚ofā€‚ thisā€‚valueā€‚+ā€‚ theā€‚valueā€‚ofā€‚ theā€‚dipā€‚switch.

1 ... 127 1 num

Baud_CAN_OB 15781 WORD - Y

On-board CAN protocol baudrateā€¢ 2=500ā€‚kbaud

ā€¢ 3=250ā€‚kbaud

ā€¢ 4=125ā€‚kbaud

ā€¢ 5=125ā€‚kbaud

ā€¢ 6=50ā€‚kbaud

2 ... 6 2 num

CAN PLUGIN PASSIVE folder

Addr_RS485_PI 15782 WORD - YRS485 passive plug-in serial addressTheā€‚actualā€‚addressā€‚isā€‚determinedā€‚byā€‚theā€‚sumā€‚ofā€‚ thisā€‚valueā€‚+ā€‚ theā€‚valueā€‚ofā€‚ theā€‚dipā€‚switch.

0ā€‚ā€¦ā€‚255 1 num

Page 114: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

114 EIO0000002030 09/2015

LAB

EL

PAR

. VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

Proto_RS485_PI 15783 WORD - YRS485 passive plug-in protocol selec-tion2ā€‚=ā€‚uNET3ā€‚=ā€‚Modbus/RTU

2ā€‚ā€¦ā€‚3 3 num

Databit_RS485_PI 15784 WORD - Y RS485 passive plug-in data bit numberFixed setting 8 8ā€‚ā€¦ā€‚8 8 num

Stopbit_RS485_PI 15785 WORD - YRS485 passive plug-in stop bit numberā€¢ 1=ā€‚1ā€‚stopā€‚bit

ā€¢ 2=ā€‚2ā€‚stopā€‚bit

1ā€¦ā€‚2 1 num

Parity_RS485_PI 15786 WORD - YRS485 passive plug-in protocol parity 0=ā€‚NULL1=ā€‚ODD2=ā€‚EVEN

0ā€‚ā€¦ā€‚2 2 num

Baud_RS485_PI 15787 WORD - Y

RS485 passive plug-in protocol bau-drate ā€¢ 0=9600ā€‚baud

ā€¢ 1=19200ā€‚baud

ā€¢ 2=38400ā€‚baud

ā€¢ 3=57600ā€‚baud

ā€¢ 4=76800ā€‚baud

ā€¢ 5=115200ā€‚baud

0ā€‚ā€¦ā€‚5 2 num

Addr_CAN_PI 15788 WORD - YCAN passive plug-in serial address Theā€‚actualā€‚addressā€‚isā€‚determinedā€‚byā€‚theā€‚sumā€‚ofā€‚ thisā€‚valueā€‚+ā€‚ theā€‚valueā€‚ofā€‚ theā€‚dipā€‚switch.

1ā€‚ā€¦ā€‚127 1 num

Baud_CAN_PI 15789 WORD - Y

CAN passive plug-in protocol bau-drateā€¢ 2=500ā€‚kbaud

ā€¢ 3=250ā€‚kbaud

ā€¢ 4=125ā€‚kbaud

ā€¢ 5=125ā€‚kbaud

ā€¢ 6=50ā€‚kbaud

2ā€‚ā€¦ā€‚6 2 num

RS232 PASSIVE PLUG-IN folder

Addr_ RS232_PI 15790 WORD - YRS232 passive plug-in serial addressTheā€‚actualā€‚addressā€‚isā€‚determinedā€‚byā€‚theā€‚sumā€‚ofā€‚ thisā€‚valueā€‚+ā€‚ theā€‚valueā€‚ofā€‚ theā€‚dipā€‚switch.

0 ... 255 1 num

Proto_ RS232_PI 15791 WORD - Y

RS232 passive plug-in protocol selec-tionā€¢ 2ā€‚=ā€‚uNET

ā€¢ 3ā€‚=ā€‚Modbus/RTU

2 ... 3 3 num

Page 115: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

115EIO0000002030 09/2015

LAB

EL

PAR

. VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

Databit_ RS232_PI 15792 WORD - YRS232 passive plug-in data bit numberā€¢ 7=ā€‚7ā€‚bit

ā€¢ 8=ā€‚8ā€‚bit

7 ... 8 8 num

Stopbit_ RS232_PI 15793 WORD - YRS232 passive plug-in stop bit numberā€¢ 1=ā€‚1ā€‚stopā€‚bit

ā€¢ 2=ā€‚2ā€‚stopā€‚bit

1... 2 1 num

Parity_ RS232_PI 15784 WORD - Y

RS232 passive plug-in protocol parity ā€¢ 0=ā€‚NULL

ā€¢ 1=ā€‚ODD

ā€¢ 2=ā€‚EVEN

0 ... 2 2 num

Baud_RS232_PI 15795 WORD - Y

RS232 passive plug-in protocol bau-drateā€¢ 0=9600ā€‚baud

ā€¢ 1=19200ā€‚baud

ā€¢ 2=38400ā€‚baud

ā€¢ 3=57600ā€‚baud

ā€¢ 4=76800ā€‚baud

ā€¢ 5=115200ā€‚baud

0 ... 5 2 num

Page 116: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

116 EIO0000002030 09/2015

PASSIVE ETHERNET COMMUNICATION MODULEETHERNETā€‚configurationā€‚parametersā€‚forā€‚passiveā€‚plug-inā€‚requireā€‚configurationā€‚ofā€‚theā€‚TCP/IPā€‚communicationā€‚portā€‚(forā€‚exampleā€‚502),ā€‚theā€‚IPā€‚address,ā€‚theā€‚gatewayā€‚andā€‚theā€‚subnetā€‚maskTheā€‚ā€˜Defaultā€‚Gatewayā€™ā€‚andā€‚ā€˜Netā€‚maskā€™ā€‚parametersā€‚areā€‚ofā€‚noā€‚significanceā€‚inā€‚theā€‚localā€‚point-to-pointā€‚network.Forā€‚connectionsā€‚viaā€‚aā€‚routerā€‚theā€‚ā€˜Defaultā€‚Gatewayā€™ā€‚parametersā€‚mustā€‚matchā€‚theā€‚IPā€‚address,ā€‚asā€‚inā€‚theā€‚followingā€‚example:

Value Value

Ip_1_ETH_PI Ethernet Passive Plug-In IP address (part 1) 192 DefGtwy_1_ETH_PI Default Gateway (part 1) 192

Ip_2_ETH_PI Ethernet Passive Plug-In IP address (part 2) 168 DefGtwy_2_ETH_PI Default Gateway (part 2) 168

Ip_3_ETH_PI Ethernet Passive Plug-In IP address (part 3) 0 DefGtwy_3_ETH_PI Default Gateway (part 3) 0

Ip_4_ETH_PI Ethernet Passive Plug-In IP address (part 4) 100 DefGtwy_4_ETH_PI Default Gateway (part 4) 1

Theā€‚parametersā€‚necessaryā€‚forā€‚theā€‚configurationā€‚ofā€‚portsā€‚andā€‚protocolsā€‚areā€‚these:

WebVisuā€‚allowsā€‚theā€‚useā€‚ofā€‚HTTPā€‚andā€‚TFTPā€‚servers.

Parameter Description Label

HTTPā€‚ports HTTP HyperText Transfer Protocol.Anā€‚HTTPā€‚serverā€‚generallyā€‚monitorsā€‚portā€‚80ā€‚usingā€‚TCPā€‚protocol. Port_HTTP_PI

TFTP ports TFTP Trivial File Transfer Protocol.Protocolā€‚usingā€‚basicā€‚FTPā€‚functionalities.ā€‚Typicalā€‚use:ā€‚transferā€‚ofā€‚smallā€‚filesā€‚betweenā€‚hostsā€‚onā€‚aā€‚network.ā€‚TFTPā€‚USESā€‚PORTā€‚69

Port_TFTP_PI

DHCPā€‚protocol DHCP Dynamic Host Configuration Protocol EnableDHCP_ETH_

PI

DNSā€‚systemDNS Domain Name SystemSystemā€‚forā€‚theā€‚conversionā€‚ofā€‚hostā€‚names,ā€‚orā€‚networkā€‚nodes,ā€‚toā€‚IPā€‚addressesUsedā€‚byā€‚TM171SW (SoMachineHVAC)ā€‚toā€‚sendā€‚textā€‚e-mailsā€‚(strings)

PriDNS_1_ETH_PIPriDNS_2_ETH_PIPriDNS_3_ETH_PIPriDNS_4_ETH_PISecDNS_1_ETH_PISecDNS_2_ETH_PISecDNS_3_ETH_PISecDNS_4_ETH_PI

Page 117: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

117EIO0000002030 09/2015

LAB

EL

PAR

VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

ETHERNET PASSIVE PLUG-IN folder

Port_TFTP_PI 15772 WORD - YTFTP portTFTPā€‚ communicationā€‚ Portā€‚ num-berā€‚Defaultā€‚0ā€‚correspondsā€‚toā€‚port 69

0ā€‚ā€¦ā€‚65535 0 num

Port_HTTP_PI 15796 WORD - YHTTP portHTTPā€‚ communicationā€‚ Portā€‚ num-berā€‚Defaultā€‚0ā€‚correspondsā€‚toā€‚port 80

0ā€‚ā€¦ā€‚65535 0 num

Port_ETH_PI 15797 WORD - YPortTCP/IPā€‚ Modbusā€‚ communicationā€‚port. Port 502 for example

0ā€‚ā€¦ā€‚65535 502 num

Ip_1_ETH_PI 15798 WORD - Y Ethernet passive Plug-in IP address (part 1) 0ā€‚ā€¦ā€‚255 10 num

Ip_2_ETH_PI 15799 WORD - Y Ethernet passive Plug-in IP address (part 2) 0ā€‚ā€¦ā€‚255 0 num

Ip_3_ETH_PI 15800 WORD - Y Ethernet passive Plug-in IP address (part 3) 0ā€‚ā€¦ā€‚255 0 num

Ip_4_ETH_PI 15801 WORD - Y Ethernet passive Plug-in IP address (part 4) 0ā€‚ā€¦ā€‚255 100 num

DefGtwy_1_ETH_PI 15802 WORD - Y Default Gateway (part 1) 0ā€‚ā€¦ā€‚255 192 num

DefGtwy_2_ETH_PI 15803 WORD - Y Default Gateway (part 2) 0ā€‚ā€¦ā€‚255 168 num

DefGtwy_3_ETH_PI 15804 WORD - Y Default Gateway (part 3) 0ā€‚ā€¦ā€‚255 0 num

DefGtwy_4_ETH_PI 15805 WORD - Y Default Gateway (part 4) 0ā€‚ā€¦ā€‚255 1 num

NetMsk_1_ETH_PI 15806 WORD - Y Net mask (part 1) 0ā€‚ā€¦ā€‚255 255 num

NetMsk_2_ETH_PI 15807 WORD - Y Net mask (part 2) 0ā€‚ā€¦ā€‚255 255 num

NetMsk_3_ETH_PI 15808 WORD - Y Net mask (part 3) 0ā€‚ā€¦ā€‚255 255 num

NetMsk_4_ETH_PI 15809 WORD - Y Net mask (part 4) 0ā€‚ā€¦ā€‚255 0 num

PriDNS_1_ETH_PI 15810 WORD - Y Primary DNS server (part 1) 0ā€‚ā€¦ā€‚255 194 num

PriDNS_2_ETH_PI 15811 WORD - Y Primary DNS server (part 2) 0ā€‚ā€¦ā€‚255 25 num

PriDNS_3_ETH_PI 15812 WORD - Y Primary DNS server (part 3) 0ā€‚ā€¦ā€‚255 2 num

PriDNS_4_ETH_PI 15813 WORD - Y Primary DNS server (part 4) 0ā€‚ā€¦ā€‚255 129 num

SecDNS_1_ETH_PI 15814 WORD - Y Secondary DNS server (part 1) 0ā€‚ā€¦ā€‚255 194 num

Page 118: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

118 EIO0000002030 09/2015

LAB

EL

PAR

VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

SecDNS_2_ETH_PI 15815 WORD - Y Secondary DNS server (part 2) 0ā€‚ā€¦ā€‚255 25 num

SecDNS_3_ETH_PI 15816 WORD - Y Secondary DNS server (part 3) 0ā€‚ā€¦ā€‚255 2 num

SecDNS_4_ETH_PI 15817 WORD - Y Secondary DNS server (part 4) 0ā€‚ā€¦ā€‚255 130 num

EnableDHCP_ETH_PI 15819 WORD - Y Enable DHCP 0ā€‚ā€¦ā€‚1

(False,ā€‚True) False flag

Modems folderModem_RS232_PI 15820 BOOL - Y Presence of Modem 0ā€‚ā€¦ā€‚1 0 num

Modem_InitStr1 15821 19 BYTES - Y Modem initialization string

(part I) ********** (1) string

Modem_InitStr2 15831 19 BYTES - Y Modem initialization string

(part II) ********** string

Modem_Hangup 15851 19

BYTES - Y Hangup String ********** ATH0 string

Display folderHmi_Language 15819 WORD - Y Display language 0ā€‚ā€¦ā€‚65535 0 num

Par_ContrLCD 15723 WORD - YLCD ContrastAllowsā€‚ adjustmentā€‚ ofā€‚ theā€‚ LCDā€‚displayā€‚contrast.

0 ... 64 30 num

Par_BackLightTim

e15724 WORD - Y

Backlight switch-on timeAllowsā€‚adjustmentā€‚ofā€‚LCDā€‚displayā€‚switch-onā€‚time.

0 ... 3600 10 num

(1)ā€‚AT&F&C&D2E0X1S0=0

Page 119: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

119EIO0000002030 09/2015

9.1.2. M171EP14R parameters

LAB

EL

PAR

. VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

ACKNOWLEDGEMENT folder

Par_TAB 15716 WORD - Y Map codeNote:ā€‚read/writeā€‚parameter 0ā€‚ā€¦ā€‚65535 0 num

Par_POLI 15717 WORD - Y Model CodeNote:ā€‚read/writeā€‚parameter 0ā€‚ā€¦ā€‚65535 2049 num

Par_PCH 15718 WORD - -Model ID Code

0ā€‚ā€¦ā€‚65535 262 num

AI CALIBRATION folder

Gain_Ntc_AI1 15616 WORD - - Ai1 NTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_Ntc_AI2 15617 WORD - - Ai2 NTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_Ntc_AI3 15618 WORD - - Ai3 NTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_Ntc_AI4 15619 WORD - - Ai4 NTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 numOffs_Ntc_AI1 15621 WORD -1 - Ai1 NTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_Ntc_AI2 15622 WORD -1 - Ai2 NTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_Ntc_AI3 15623 WORD -1 - Ai3 NTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_Ntc_AI4 15624 WORD -1 - Ai4 NTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Gain_PTC_AI1 15626 WORD - - Ai1 PTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_PTC_AI2 15627 WORD - - Ai2 PTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_PTC_AI3 15628 WORD - - Ai3 PTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_PTC_AI4 15629 WORD - Ai4 PTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 numOffs_PTC_AI1 15631 WORD -1 - Ai1 PTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_PTC_AI2 15632 WORD -1 - Ai2 PTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_PTC_AI3 15633 WORD -1 - Ai3 PTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_PTC_AI4 15634 WORD -1 - Ai4 PTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Gain_daOhm_AI1 15636 WORD - - Ai1 daOhm calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_daOhm_AI2 15637 WORD - - Ai2 daOhm calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_daOhm_AI3 15638 WORD - - Ai3 daOhm calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_daOhm_AI4 15639 WORD - - Ai4 daOhm calibration gain 0ā€‚ā€¦ā€‚65535 32768 numOffs_daOhm_AI1 15641 WORD -1 - Ai1 daOhm calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_daOhm_AI2 15642 WORD -1 - Ai2 daOhm calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_daOhm_AI3 15643 WORD -1 - Ai3 daOhm calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_daOhm_AI4 15644 WORD -1 - Ai4 daOhm calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Gain_mA_AI1 15646 WORD - - Ai1 4-20mA calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_mA_AI2 15647 WORD - - Ai2 4-20mA calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Page 120: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

120 EIO0000002030 09/2015

LAB

EL

PAR

. VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

Gain_mA_AI3 15648 WORD - - Ai3 4-20mA calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_mA_AI4 15649 WORD - - Ai4 4-20mA calibration gain 0ā€‚ā€¦ā€‚65535 32768 numOffs_mA_AI1 15651 WORD -1 - Ai1 4-20mA calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_mA_AI2 15652 WORD -1 - Ai2 4-20mA calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_mA_AI3 15653 WORD -1 - Ai3 4-20mA calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_mA_AI4 15654 WORD -1 - Ai4 4-20mA calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Gain_5V_Ratio_AI1 15656 WORD - - Ai1 5V Ratiometric calibration

gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_5V_Ratio_AI2 15657 WORD - - Ai2 5V Ratiometric calibration

gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_5V_Ratio_AI3 15658 WORD - - Ai3 5V Ratiometric calibration

gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_5V_Ratio_AI4 15659 WORD - - Ai4 5V Ratiometric calibration

gain 0ā€‚ā€¦ā€‚65535 32768 num

Offs_5V_Ratio_AI1 15661 WORD -1 - Ai1 5V Ratiometric calibration

offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_5V_Ratio_AI2 15662 WORD -1 - Ai2 5V Ratiometric calibration

offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_5V_Ratio_AI3 15663 WORD -1 - Ai3 5V Ratiometric calibration

offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_5V_Ratio_AI4 15664 WORD -1 - Ai4 5V Ratiometric calibration

offset -32768ā€‚ā€¦ā€‚32767 0 num

Gain_10V_AI1 15666 WORD - - Ai1 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_10V_AI2 15667 WORD - - Ai2 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_10V_AI3 15668 WORD - - Ai3 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_10V_AI4 15669 WORD - - Ai4 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numOffs_10V_AI1 15671 WORD -1 - Ai1 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_10V_AI2 15672 WORD -1 - Ai2 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_10V_AI3 15673 WORD -1 - Ai3 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_10V_AI4 15674 WORD -1 - Ai4 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 numGain_5V_AI1 15676 WORD - - Ai1 0-5V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_5V_AI2 15677 WORD - - Ai2 0-5V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_5V_AI3 15678 WORD - - Ai3 0-5V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_5V_AI4 15679 WORD - - Ai4 0-5V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numOffs_5V_AI1 15681 WORD -1 - Ai1 0-5V calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_5V_AI2 15682 WORD -1 - Ai2 0-5V calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_5V_AI3 15683 WORD -1 - Ai3 0-5V calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_5V_AI4 15684 WORD -1 - Ai4 0-5V calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Gain_PT1000_AI1 15686 WORD - - Ai1 PT1000 calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_PT1000_AI2 15687 WORD - - Ai2 PT1000 calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_PT1000_AI3 15688 WORD - - Ai3 PT1000 calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_PT1000_AI4 15689 WORD - - Ai4 PT1000 calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Page 121: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

121EIO0000002030 09/2015

LAB

EL

PAR

. VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

Offs_PT1000_AI1 15691 WORD -1 - Ai1 PT1000 calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_PT1000_AI2 15692 WORD -1 - Ai2 PT1000 calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_PT1000_AI3 15693 WORD -1 - Ai3 PT1000 calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_PT1000_AI4 15694 WORD -1 -- Ai4 PT1000 calibration offset -32768ā€‚ā€¦ā€‚32767 0 numAO CALIBRATION folder

Gain_10V_AO1 15696 WORD - - AO1 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_10V_AO2 15697 WORD - - AO2 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numOffs_10V_AO1 15698 WORD -1 - AO1 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 numOffs_10V_AO2 15699 WORD -1 - AO2 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

ANALOG INPUTS folder

Temp_UM 15725 WORD - Y

Temperature unit of measure-mentā€¢ 0ā€‚=ā€‚Ā°C;

ā€¢ 1ā€‚=ā€‚Ā°F

0,ā€‚1 0 num

Cfg_Ai1 15726 WORD - -

Type of analog input Ai1ā€¢ 0=ā€‚NTCā€‚(NK103)

ā€¢ 1=ā€‚DI

ā€¢ 2=ā€‚NTCā€‚(103AT)

ā€¢ 3ā€‚=ā€‚4ā€¦20mA

ā€¢ 4=0-10V

ā€¢ 5=0-5Vā€‚Ratiometric

ā€¢ 6=Pt1000

ā€¢ 7=hĪ©(NTC)

ā€¢ 8=daĪ©(PT1000)

ā€¢ PTC

ā€¢ 10=0-5V

0 ... 10 3 num

Cfg_Ai2 15727 WORD - - Type of analog input Ai2Seeā€‚Cfg_Ai1 0 ... 10 3 num

Cfg_Ai3 15728 WORD - - Type of analog input Ai3Seeā€‚Cfg_Ai1 0 ... 10 2 num

Cfg_Ai4 15729 WORD - - Type of analog input Ai4Seeā€‚Cfg_Ai1 0 ... 10 2 num

FullScaleMin_Ai1 15736 WORD -1 - Analog input Ai1 start of scale value -9999ā€¦+9999 0

FullScaleMax_Ai1 15737 WORD - - Analog input Ai1 full scale value -9999ā€¦+9999 1000

FullScaleMin_Ai2 15738 WORD -1 -Analog input Ai2 start of scale valueSeeā€‚FullScaleMin_Ai1

-9999ā€¦+9999 0

Page 122: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

122 EIO0000002030 09/2015

LAB

EL

PAR

. VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

FullScaleMax_A2 15739 WORD - - Analog input Ai2 full scale valueSeeā€‚FullScaleMAx_Ai1 -999ā€¦+999 1000

FullScaleMin_Ai3 15740 WORD -1 -Analog input Ai3 start of scale valueSeeā€‚FullScaleMin_Ai1

-9999ā€¦+9999 0

FullScaleMax_Ai3 15741 WORD - - Analog input Ai3 full scale valueSeeā€‚FullScaleMax_Ai1 -999ā€¦+999 1000

FullScaleMin_Ai4 15742 WORD -1 -Analog input Ai4 start of scale valueSeeā€‚FullScaleMin_Ai1

-9999ā€¦+9999 0

FullScaleMaxAi4 15743 WORD - - Analog input Ai4 full scale valueSeeā€‚FullScaleMax_Ai1 -999ā€¦+999 100

Calibration_Ai1 15748 WORD -1 - Analog input Ai1 differential -180ā€‚...ā€‚180 0Ā°C/10ā€‚

or Ā°F/10

Calibration_Ai2 15749 WORD -1 - Analog input Ai2 differential -180ā€‚...ā€‚180 0 Ā°C/10ā€‚or

Ā°F/10

Calibration_Ai3 15750 WORD -1 - Analog input Ai3 differential -1000ā€‚...ā€‚1000 0

Calibration_Ai4 15751 WORD -1 - Analog input Ai4 differential -1000ā€‚...ā€‚1000 0

SubCfg_AI1 16010 WORD - Y

Analog input AI5 sub-mode fun-ction

ā€¢ 0ā€‚ =ā€‚ Lowā€‚ Passā€‚ Filterā€‚ disabled,ā€‚analogā€‚valueā€‚inā€‚rawā€‚points

ā€¢ 1ā€‚ =ā€‚ Lowā€‚ Passā€‚ Filterā€‚ disabled,ā€‚analogā€‚valueā€‚converted

ā€¢ 2ā€‚ =ā€‚ Lowā€‚ Passā€‚ Filterā€‚ enabled,ā€‚analogā€‚valueā€‚inā€‚rawā€‚points

ā€¢ 1ā€‚ =ā€‚ Lowā€‚ Passā€‚ Filterā€‚ enabled,ā€‚analogā€‚valueā€‚converted

0 ... 3 3 num

SubCfg_AI2 16011 WORD - Y See SubCfg_AI1 0 ... 3 3 numSubCfg_AI3 16012 WORD - Y See SubCfg_AI1 0 ... 3 3 numSubCfg_AI4 16013 WORD - Y See SubCfg_AI1 0 ... 3 3 num

Page 123: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

123EIO0000002030 09/2015

9.1.3. M171 Performance Flush parametersLA

BEL

PAR

VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

ACKNOWLEDGEMENT folder

Par_TAB 15716 WORD - Y Map codeNote:ā€‚read/writeā€‚parameter 0ā€‚ā€¦ā€‚65535 0 num

Par_POLI 15717 WORD - Y Model CodeNote:ā€‚read/writeā€‚parameter 0ā€‚ā€¦ā€‚65535 2049 num

Par_PARMOD 15719 BOOL - -

Parameter changedFlagā€‚ indicatingā€‚ changeā€‚ toā€‚ defaultā€‚settings.ā€¢ 0=ā€‚mapā€‚notā€‚modified.

ā€¢ 1=ā€‚atā€‚ leastā€‚oneā€‚parameterā€‚hasā€‚been changed from the original configuration.

0ā€‚ā€¦ā€‚1 0 num

AI CALIBRATION folderGain_Ntc_AI1 15616 WORD - - Ai1 NTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_Ntc_AI2 15617 WORD - - Ai2 NTC calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_5V_AI3 15620 WORD - - Ai3 0-5V calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Gain_10V_AI3 15621 WORD - - Ai3 0-10V calibration gain 0ā€‚ā€¦ā€‚65535 32768 numGain_mA_AI3 15622 WORD - - Ai3 4-20mA calibration gain 0ā€‚ā€¦ā€‚65535 32768 num

Offs_Ntc_AI1 15650 WORD -1 - Ai1 NTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_Ntc_AI2 15651 WORD -1 - Ai2 NTC calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_5V_AI3 15654 WORD -1 - Ai3 0-5V calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_10V_AI3 15655 WORD -1 - Ai3 0-10V calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

Offs_mA_AI3 15656 WORD -1 - Ai3 4-20mA calibration offset -32768ā€‚ā€¦ā€‚32767 0 num

ANALOG INPUTS folder

Temp_UM 15725 WORD - YTemperature unit of measureā€¢ 0ā€‚=ā€‚Ā°C;

ā€¢ 1ā€‚=ā€‚Ā°F

0,ā€‚1 0 num

Cfg_AI1 15726 WORD - -

Type of analog input Ai1ā€¢ 0=ā€‚NTCā€‚(NK103)

ā€¢ 1=ā€‚DI

ā€¢ 2=ā€‚NTCā€‚(103AT)

0 ... 2 2 num

Cfg_Ai2 15727 WORD - - Type of analog input Ai2Seeā€‚Cfg_Ai1 0 ... 2 2 num

Cfg_Ai3 15728 WORD - -

Type of analog input Ai3ā€¢ ā€‚3ā€‚=ā€‚4ā€¦20mA

ā€¢ ā€‚4=0-10V

ā€¢ ā€‚5=0-5V

3 ... 5 3 num

Page 124: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

124 EIO0000002030 09/2015

LAB

EL

PAR

VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

Cfg_Ai4 15729 WORD - - Type of analog input Ai4Seeā€‚Cfg_Ai3 3 ... 5 3 num

FullScaleMin_Ai3 15736 WORD -1 -

Analog input Ai3 start of scale valueN.B.:ā€‚Minimumā€‚ fullā€‚ scale:ā€‚ forā€‚ cur-rentā€‚ probes,ā€‚ valueā€‚ atā€‚ 4mA,ā€‚ forā€‚0-10Vā€‚ voltageā€‚ probes,ā€‚ valueā€‚ atā€‚0V,ā€‚10%ā€‚forā€‚(ā€‚0-5V)ā€‚probes,ā€‚valueā€‚atā€‚10%ā€‚(correspondingā€‚toā€‚0.5V).

-9999ā€¦+9999 0

FullScaleMAx_Ai3 15737 WORD -1 -

Analog input Ai3 full scale valueN.B.:ā€‚Maximumā€‚ fullā€‚ scaleā€‚ forā€‚ cur-rentā€‚ probes,ā€‚ valueā€‚ atā€‚ 20mA,ā€‚ forā€‚0-10Vā€‚ voltageā€‚ probes,ā€‚ valueā€‚ atā€‚10V,ā€‚ forā€‚ (0-5V)ā€‚ probes,ā€‚ valueā€‚ atā€‚90%ā€‚(correspondingā€‚toā€‚4.5V).

-9999ā€¦+9999 1000

Calibration_Ai1 15748 WORD -1 - Analog input Ai1 differential -180ā€‚...ā€‚180 0 Ā°C/10ā€‚orā€‚Ā°F/10

Calibration_Ai2 15749 WORD -1 - Analog input Ai2 differential -180ā€‚...ā€‚180 0 Ā°C/10ā€‚orā€‚Ā°F/10

Calibration_Ai3 15750 WORD -1 - Analog input Ai3 differential -1000ā€‚...ā€‚1000 0

Calibration_Ai4 15751 WORD -1 - Analog input Ai4 differential -1000ā€‚...ā€‚1000 0Compensation_

AI1 15752 WORD -1 - Internal compensation AI1 -1000ā€‚...ā€‚1000Ā°C/10 0 Ā°C/10

Compensation_AI4 15753 WORD -1 - Internal compensation AI4 -1000ā€‚...ā€‚1000

Ā°C/10 0 Ā°C/10

RS485 ON BOARD folder

Addr_RS485_OB 15774 WORD - Y

On-board RS485 serial addressTheā€‚actualā€‚addressā€‚isā€‚determinedā€‚byā€‚ theā€‚ sumā€‚ ofā€‚ thisā€‚ valueā€‚ +ā€‚ theā€‚valueā€‚ofā€‚theā€‚dipā€‚switch.ā€‚

0 ... 255 1 num

Proto_RS485_OB 15775 WORD - Y

On-board RS485 protocol selec-tionā€¢ 2ā€‚=ā€‚uNET

ā€¢ 3ā€‚=ā€‚Modbus/RTU

2 ... 3 2 num

Databit_RS485_OB 15776 WORD - Y

On-board RS485 data bit num-berFixed setting 8

8 ... 8 8 num

Stopbit_RS485_OB 15777 WORD - Y

On-board RS485 stop bit num-berā€¢ 1=ā€‚1ā€‚stopā€‚bit

ā€¢ 2=ā€‚2ā€‚stopā€‚bits

1... 2 1 num

Parity_RS485_OB 15778 WORD - Y

On-board RS485 protocol parityā€¢ 0=ā€‚NULL

ā€¢ 1=ā€‚ODD

ā€¢ 2=ā€‚EVEN

0 ... 2 2 num

Page 125: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

125EIO0000002030 09/2015

LAB

EL

PAR

VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

Baud_RS485_OB 15779 WORD - Y

On-board RS485 protocol bau-drateā€¢ 0=9600ā€‚baud

ā€¢ 1=19200ā€‚baud

ā€¢ 2=38400ā€‚baud

ā€¢ 3=57600ā€‚baud

ā€¢ 4=76800ā€‚baud

ā€¢ 5=115200ā€‚baud

0 ... 5 2 num

ON BOARD CAN folder

Addr_CAN_OB 15780 WORD - YOn-board CAN serial addressTheā€‚actualā€‚addressā€‚isā€‚determinedā€‚byā€‚ theā€‚ sumā€‚ ofā€‚ thisā€‚ valueā€‚ +ā€‚ theā€‚valueā€‚ofā€‚theā€‚dipā€‚switch.

1 ... 127 1 num

Baud_CAN_OB 15781 WORD - Y

On-board CAN protocol bau-drate2=500ā€‚kbaud3=250ā€‚kbaud4=125ā€‚kbaud5=125ā€‚kbaud6=50ā€‚kbaud

2 ... 6 2 num

ON BOARD ETHERNETTheā€‚parametersā€‚necessaryā€‚forā€‚theā€‚configurationā€‚ofā€‚portsā€‚andā€‚protocolsā€‚areā€‚these:

WebVisuā€‚allowsā€‚theā€‚useā€‚ofā€‚HTTPā€‚andā€‚TFTPā€‚servers.

Parameter Description Label

HTTPā€‚ports HTTP HyperText Transfer Protocol.Anā€‚HTTPā€‚serverā€‚generallyā€‚monitorsā€‚portā€‚80ā€‚usingā€‚TCPā€‚protocol. Port_HTTP

TFTP portsTFTP Trivial File Transfer Protocol.Protocolā€‚usingā€‚basicā€‚FTPā€‚functionalities.ā€‚Typicalā€‚use:ā€‚transferā€‚ofā€‚smallā€‚filesā€‚betweenā€‚hostsā€‚onā€‚aā€‚network.ā€‚TFTPā€‚USESā€‚PORTā€‚69

Port_TFTP

DHCPā€‚protocol DHCP Dynamic Host Configuration Protocol EnableDHCP_

ETH

DNSā€‚systemDNS Domain Name SystemSystemā€‚forā€‚theā€‚conversionā€‚ofā€‚hostā€‚names,ā€‚orā€‚networkā€‚nodes,ā€‚toā€‚IPā€‚addressesUsedā€‚byā€‚TM171SW (SoMachineHVAC)ā€‚toā€‚sendā€‚textā€‚e-mailsā€‚(strings)

PriDNS_1_ETHPriDNS_2_ETHPriDNS_3_ETHPriDNS_4_ETHSecDNS_1_ETHSecDNS_2_ETHSecDNS_3_ETHSecDNS_4_ETH

Page 126: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

126 EIO0000002030 09/2015

LAB

EL

PAR

VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

ETHERNET ON BOARD folder

Port_TFTP 15772 WORD - YTFTP portTFTPā€‚ communicationā€‚ Portā€‚ numberā€‚Defaultā€‚0ā€‚correspondsā€‚toā€‚port 69

0ā€‚ā€¦ā€‚65535 0 num

Port_HTTP 15796 WORD - YHTTP portHTTPā€‚ communicationā€‚ Portā€‚ numberā€‚Defaultā€‚0ā€‚correspondsā€‚toā€‚port 80

0ā€‚ā€¦ā€‚65535 0 num

Port_ETH 15797 WORD - YPortTCP/IPā€‚Modbusā€‚communicationā€‚port.ā€‚Port 502 for example

0ā€‚ā€¦ā€‚65535 502 num

Ip_1_ETH 15798 WORD - Y On-board Ethernet passive IP address (part 1) 0ā€‚ā€¦ā€‚255 10 num

Ip_2_ETH 15799 WORD - Y On-board Ethernet passive IP address (part 2) 0ā€‚ā€¦ā€‚255 0 num

Ip_3_ETH 15800 WORD - Y On-board Ethernet passive IP address (part 3) 0ā€‚ā€¦ā€‚255 0 num

Ip_4_ETH 15801 WORD - Y On-board Ethernet passive IP address (part 4) 0ā€‚ā€¦ā€‚255 100 num

DefGtwy_1_ETH 15802 WORD - Y Default Gateway (part 1) 0ā€‚ā€¦ā€‚255 192 numDefGtwy_2_ETH 15803 WORD - Y Default Gateway (part 2) 0ā€‚ā€¦ā€‚255 168 numDefGtwy_3_ETH 15804 WORD - Y Default Gateway (part 3) 0ā€‚ā€¦ā€‚255 0 numDefGtwy_4_ETH 15805 WORD - Y Default Gateway (part 4) 0ā€‚ā€¦ā€‚255 1 numNetMsk_1_ETH 15806 WORD - Y Net mask (part 1) 0ā€‚ā€¦ā€‚255 255 numNetMsk_2_ETH 15807 WORD - Y Net mask (part 2) 0ā€‚ā€¦ā€‚255 255 numNetMsk_3_ETH 15808 WORD - Y Net mask (part 3) 0ā€‚ā€¦ā€‚255 255 numNetMsk_4_ETH 15809 WORD - Y Net mask (part 4) 0ā€‚ā€¦ā€‚255 0 numPriDNS_1_ETH 15810 WORD - Y Primary DNS server (part 1) 0ā€‚ā€¦ā€‚255 194 numPriDNS_2_ETH 15811 WORD - Y Primary DNS server (part 2) 0ā€‚ā€¦ā€‚255 25 numPriDNS_3_ETH 15812 WORD - Y Primary DNS server (part 3) 0ā€‚ā€¦ā€‚255 2 numPriDNS_4_ETH 15813 WORD - Y Primary DNS server (part 4) 0ā€‚ā€¦ā€‚255 129 numSecDNS_1_ETH 15814 WORD - Y Secondary DNS server (part 1) 0ā€‚ā€¦ā€‚255 194 numSecDNS_2_ETH 15815 WORD - Y Secondary DNS server (part 2) 0ā€‚ā€¦ā€‚255 25 numSecDNS_3_ETH 15816 WORD Y Secondary DNS server (part 3) 0ā€‚ā€¦ā€‚255 2 numSecDNS_4_ETH 15817 WORD - Y Secondary DNS server (part 4) 0ā€‚ā€¦ā€‚255 130 numEnableDHCP_

ETH 15819 WORD - Y Enable DHCP 0ā€‚ā€¦ā€‚1(False,ā€‚True) False flag

Display folder

Hmi_Language 15819 WORD - -

Display language0ā€‚=ā€‚Italian1ā€‚=ā€‚English2ā€‚=ā€‚French3ā€‚=ā€‚German4ā€‚=ā€‚Spanish

0ā€‚ā€¦ā€‚65535 0 num

Page 127: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

127EIO0000002030 09/2015

LAB

EL

PAR

VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

Par_ContrLCD 15723 WORD - YLCD Contrast Allowsā€‚adjustmentā€‚ofā€‚theā€‚LCDā€‚displayā€‚contrast.

0ā€‚ā€¦ā€‚64 30 num

Par_BackLightTime 15724 WORD - -

Backlight switch-on timeAllowsā€‚ adjustmentā€‚ ofā€‚ LCDā€‚ displayā€‚switch-onā€‚time.

0ā€‚ā€¦ā€‚3600 10 sec

Buzzer folder

Buzzer_Mode 15990 WORD - -Buzzer mode0=ā€‚alwaysā€‚off1=ā€‚beepā€‚perā€‚key

0ā€‚ā€¦ā€‚1 0 num

HMI Management folderHmi_Language 15989 WORD 0ā€‚ā€¦ā€‚65535 0 num

HmiList_Current 15820 WORD - -

Currentā€‚HMI0=ā€‚HMIā€‚remoteā€‚11=ā€‚HMIā€‚remoteā€‚22=ā€‚HMIā€‚remoteā€‚33=ā€‚HMIā€‚remoteā€‚44=ā€‚HMIā€‚remoteā€‚55=ā€‚HMIā€‚remoteā€‚66=ā€‚HMIā€‚remoteā€‚77=ā€‚HMIā€‚remoteā€‚88=ā€‚HMIā€‚remoteā€‚99=ā€‚HMIā€‚remoteā€‚1010ā€‚=ā€‚notā€‚used11=ā€‚Localā€‚HMI

0ā€‚ā€¦ā€‚11 11 num

If HmiList_Current=11 the following folders/parameters are NOT USED.HMI remote 1 folder

HmiList_ID_1 15821 WORD - - HMIā€‚remoteā€‚1ā€‚navigationā€‚IDā€‚list 0 ... 254 0 num

HmiList_Res_1 15833 WORD - -

HMIā€‚ remoteā€‚ 1ā€‚ navigationā€‚ resourceā€‚typeHMIā€‚ remoteā€‚ 1ā€‚ navigationā€‚ resourceā€‚type1=RTUā€‚(RS485ā€‚Modbusā€‚RTU)2=TCPā€‚(Modbusā€‚TCP)3=CANā€‚(CAN)

1ā€‚ā€¦ā€‚3 3 num

HmiList_Addr_1 15845 WORD - -HMIā€‚ remoteā€‚ 1ā€‚ navigationā€‚ resourceā€‚addressā€‚ forā€‚ CAN,ā€‚RTUā€‚ andā€‚ TCPā€‚ (IPā€‚partā€‚1)

0 ... 255 0 num

HmiList_Addr_2 15846 WORD - - HMIā€‚ remoteā€‚ 1ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚2) 0 ... 255 0 num

HmiList_Addr_3 15847 WORD - - HMIā€‚ remoteā€‚ 1ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚3) 0 ... 255 0 num

HmiList_Addr_4 15848 WORD - - HMIā€‚ remoteā€‚ 1ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚4) 0 ... 255 0 num

HmiList_File_1 15893 15ā€‚byte - - HMIā€‚remoteā€‚1ā€‚navigationā€‚fileā€‚(DOSā€‚8.3ā€‚uppercaseā€‚format) ******** string

HMI remote 2 folderHmiList_ID_2 15822 WORD - - HMIā€‚remoteā€‚2ā€‚navigationā€‚IDā€‚list 0 ... 254 0 num

Page 128: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

128 EIO0000002030 09/2015

LAB

EL

PAR

VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

HmiList_Res_2 15834 WORD - -

HMIā€‚ remoteā€‚ 2ā€‚ navigationā€‚ resourceā€‚type1=RTUā€‚(RS485ā€‚Modbusā€‚RTU)2=TCPā€‚(Modbusā€‚TCP)3=CANā€‚(CAN)

1ā€‚ā€¦ā€‚3 3 num

HmiList_Addr_1 15849 WORD - -HMIā€‚ remoteā€‚ 2ā€‚ navigationā€‚ resourceā€‚addressā€‚ forā€‚ CAN,ā€‚RTUā€‚ andā€‚ TCPā€‚ (IPā€‚partā€‚1)

0 ... 255 0 num

HmiList_Addr_2 15850 WORD - - HMIā€‚ remoteā€‚ 2ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚2) 0 ... 255 0 num

HmiList_Addr_3 15851 WORD - - HMIā€‚ remoteā€‚ 2ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚3) 0 ... 255 0 num

HmiList_Addr_4 15852 WORD - - HMIā€‚ remoteā€‚ 2ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚4) 0 ... 255 0 num

HmiList_File_2 15901 15ā€‚byte - - HMIā€‚remoteā€‚2ā€‚navigationā€‚fileā€‚(DOSā€‚8.3ā€‚uppercaseā€‚format) ******** string

HMI remote 3 folder

HmiList_Res_3 15835 WORD - -

HMIā€‚ remoteā€‚ 3ā€‚ navigationā€‚ resourceā€‚type1=RTUā€‚(RS485ā€‚Modbusā€‚RTU)2=TCPā€‚(Modbusā€‚TCP)3=CANā€‚(CAN)

1ā€‚ā€¦ā€‚3 3 num

HmiList_Addr_1 15853 WORD - -HMIā€‚ remoteā€‚ 3ā€‚ navigationā€‚ resourceā€‚addressā€‚ forā€‚ CAN,ā€‚RTUā€‚ andā€‚ TCPā€‚ (IPā€‚partā€‚1)

0 ... 255 0 num

HmiList_Addr_2 15854 WORD - - HMIā€‚ remoteā€‚ 3ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚2) 0 ... 255 0 num

HmiList_Addr_3 15855 WORD - - HMIā€‚ remoteā€‚ 3ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚3) 0 ... 255 0 num

HmiList_Addr_4 15856 WORD - - HMIā€‚ remoteā€‚ 3ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚4) 0 ... 255 0 num

HmiList_File_3 15909 15ā€‚byte - - HMIā€‚remoteā€‚3ā€‚navigationā€‚fileā€‚(DOSā€‚8.3ā€‚uppercaseā€‚format) ******** string

HMI remote 4 folderHmiList_ID_4 15822 WORD - - HMIā€‚remoteā€‚4ā€‚navigationā€‚IDā€‚list 0 ... 254 0 num

HmiList_Res_4 15836 WORD - -

HMIā€‚ remoteā€‚ 4ā€‚ navigationā€‚ resourceā€‚type1=RTUā€‚(RS485ā€‚Modbusā€‚RTU)2=TCPā€‚(Modbusā€‚TCP)3=CANā€‚(CAN)

1ā€‚ā€¦ā€‚3 3 num

HmiList_Addr_1 15857 WORD - -HMIā€‚ remoteā€‚ 4ā€‚ navigationā€‚ resourceā€‚addressā€‚ forā€‚ CAN,ā€‚RTUā€‚ andā€‚ TCPā€‚ (IPā€‚partā€‚1)

0 ... 255 0 num

HmiList_Addr_2 15859 WORD - - HMIā€‚ remoteā€‚ 4ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚2) 0 ... 255 0 num

HmiList_Addr_3 15859 WORD - - HMIā€‚ remoteā€‚ 4ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚3) 0 ... 255 0 num

Page 129: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

129EIO0000002030 09/2015

LAB

EL

PAR

VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

HmiList_Addr_4 15860 WORD - - HMIā€‚ remoteā€‚ 4ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚4) 0 ... 255 0 num

HmiList_File_4 15917 15ā€‚byte - - HMIā€‚remoteā€‚4ā€‚navigationā€‚fileā€‚(DOSā€‚8.3ā€‚uppercaseā€‚format) ******** string

HMI remote 5 folderHmiList_ID_5 15825 WORD - - HMIā€‚remoteā€‚5ā€‚navigationā€‚IDā€‚list 0 ... 254 0 num

HmiList_Res_5 15837 WORD - -

HMIā€‚ remoteā€‚ 5ā€‚ navigationā€‚ resourceā€‚type1=RTUā€‚(RS485ā€‚Modbusā€‚RTU)2=TCPā€‚(Modbusā€‚TCP)3=CANā€‚(CAN)

1ā€‚ā€¦ā€‚3 3 num

HmiList_Addr_1 15861 WORD - -HMIā€‚ remoteā€‚ 5ā€‚ navigationā€‚ resourceā€‚addressā€‚ forā€‚ CAN,ā€‚RTHā€‚ andā€‚ TCPā€‚ (IPā€‚partā€‚1)

0 ... 255 0 num

HmiList_Addr_2 15862 WORD - - HMIā€‚ remoteā€‚ 5ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚2) 0 ... 255 0 num

HmiList_Addr_3 15863 WORD - - HMIā€‚ remoteā€‚ 5ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚3) 0 ... 255 0 num

HmiList_Addr_4 15864 WORD - - HMIā€‚ remoteā€‚ 5ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚4) 0 ... 255 0 num

HmiList_File_5 15925 15ā€‚byte - - HMIā€‚remoteā€‚5ā€‚navigationā€‚fileā€‚(DOSā€‚8.3ā€‚uppercaseā€‚format) ******** string

HMI remote 6 folderHmiList_ID_6 15826 WORD - - HMIā€‚remoteā€‚6ā€‚navigationā€‚IDā€‚list 0 ... 254 0 num

HmiList_Res_6 15838 WORD - -

HMIā€‚ remoteā€‚ 6ā€‚ navigationā€‚ resourceā€‚type1=RTUā€‚(RS485ā€‚Modbusā€‚RTU)2=TCPā€‚(Modbusā€‚TCP)3=CANā€‚(CAN)

1ā€‚ā€¦ā€‚3 3 num

HmiList_Addr_1 15865 WORD - -HMIā€‚ remoteā€‚ 6ā€‚ navigationā€‚ resourceā€‚addressā€‚ forā€‚ CAN,ā€‚RTHā€‚ andā€‚ TCPā€‚ (IPā€‚partā€‚1)

0 ... 255 0 num

HmiList_Addr_2 15866 WORD - - HMIā€‚ remoteā€‚ 6ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚2) 0 ... 255 0 num

HmiList_Addr_3 15867 WORD - - HMIā€‚ remoteā€‚ 6ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚3) 0 ... 255 0 num

HmiList_Addr_4 15868 WORD - - HMIā€‚ remoteā€‚ 6ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚4) 0 ... 255 0 num

HmiList_File_6 15933 15ā€‚byte - - HMIā€‚remoteā€‚6ā€‚navigationā€‚fileā€‚(DOSā€‚8.3ā€‚uppercaseā€‚format) ******** string

HMI remote 7 folderHmiList_ID_7 15827 WORD - - HMIā€‚remoteā€‚7ā€‚navigationā€‚IDā€‚list 0 ... 254 0 num

HmiList_Res_7 15839 WORD - -

HMIā€‚ remoteā€‚ 7ā€‚ navigationā€‚ resourceā€‚type1=RTUā€‚(RS485ā€‚Modbusā€‚RTU)2=TCPā€‚(Modbusā€‚TCP)3=CANā€‚(CAN)

1ā€‚ā€¦ā€‚3 3 num

Page 130: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

130 EIO0000002030 09/2015

LAB

EL

PAR

VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

HmiList_Addr_1 15869 WORD - -HMIā€‚ remoteā€‚ 7ā€‚ navigationā€‚ resourceā€‚addressā€‚ forā€‚ CAN,ā€‚RTUā€‚ andā€‚ TCPā€‚ (IPā€‚partā€‚1)

0 ... 255 0 num

HmiList_Addr_2 15870 WORD - - HMIā€‚ remoteā€‚ 7ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚2) 0 ... 255 0 num

HmiList_Addr_3 15871 WORD - - HMIā€‚ remoteā€‚ 7ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚3) 0 ... 255 0 num

HmiList_Addr_4 15872 WORD - - HMIā€‚ remoteā€‚ 7ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚4) 0 ... 255 0 num

HmiList_File_7 15941 15ā€‚byte HMIā€‚remoteā€‚7ā€‚navigationā€‚fileā€‚(DOSā€‚8.3ā€‚uppercaseā€‚format) ******** string

HMI remote 8 folderHmiList_ID_8 15828 WORD - - HMIā€‚remoteā€‚8ā€‚navigationā€‚IDā€‚list 0 ... 254 0 num

HmiList_Res_8 15840 WORD - -

HMIā€‚ remoteā€‚ 8ā€‚ navigationā€‚ resourceā€‚type1=RTUā€‚(RS485ā€‚Modbusā€‚RTU)2=TCPā€‚(Modbusā€‚TCP)3=CANā€‚(CAN)

1ā€‚ā€¦ā€‚3 3 num

HmiList_Addr_1 15873 WORD - -HMIā€‚ remoteā€‚ 8ā€‚ navigationā€‚ resourceā€‚addressā€‚ forā€‚ CAN,ā€‚RTUā€‚ andā€‚ TCPā€‚ (IPā€‚partā€‚1)

0 ... 255 0 num

HmiList_Addr_2 15874 WORD - - HMIā€‚ remoteā€‚ 8ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚2) 0 ... 255 0 num

HmiList_Addr_3 15875 WORD - - HMIā€‚ remoteā€‚ 8ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚3) 0 ... 255 0 num

HmiList_Addr_4 15876 WORD - - HMIā€‚ remoteā€‚ 8ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚4) 0 ... 255 0 num

HmiList_File_8 15949 15ā€‚byte - - HMIā€‚remoteā€‚8ā€‚navigationā€‚fileā€‚(DOSā€‚8.3ā€‚uppercaseā€‚format) ******** string

HMI remote 9 folderHmiList_ID_9 15829 WORD - - HMIā€‚remoteā€‚9ā€‚navigationā€‚IDā€‚list 0 ... 254 0 num

HmiList_Res_9 15841 WORD - -

HMIā€‚ remoteā€‚ 9ā€‚ navigationā€‚ resourceā€‚type1=RTUā€‚(RS485ā€‚Modbusā€‚RTU)2=TCPā€‚(Modbusā€‚TCP)3=CANā€‚(CAN)

1ā€‚ā€¦ā€‚3 3 num

HmiList_Addr_1 15877 WORD - -HMIā€‚ remoteā€‚ 9ā€‚ navigationā€‚ resourceā€‚addressā€‚ forā€‚ CAN,ā€‚RTUā€‚ andā€‚ TCPā€‚ (IPā€‚partā€‚1)

0 ... 255 0 num

HmiList_Addr_2 15878 WORD - - HMIā€‚ remoteā€‚ 9ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚2) 0 ... 255 0 num

HmiList_Addr_3 15879 WORD - - HMIā€‚ remoteā€‚ 9ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚3) 0 ... 255 0 num

HmiList_Addr_4 15880 WORD - - HMIā€‚ remoteā€‚ 9ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚4) 0 ... 255 0 num

HmiList_File_9 15957 15ā€‚byte - - HMIā€‚remoteā€‚9ā€‚navigationā€‚fileā€‚(DOSā€‚8.3ā€‚uppercaseā€‚format) ******** string

Page 131: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

131EIO0000002030 09/2015

LAB

EL

PAR

VA

LUE

AD

DR

ESS

DA

TA S

IZE

CPL

RES

ET (Y

/N)

DES

CR

IPTI

ON

RA

NG

E

DEF

AU

LT

U.M

.

HMI remote 10 folderHmiList_ID_10 15830 WORD - - HMIā€‚remoteā€‚10ā€‚navigationā€‚IDā€‚list 0 ... 254 0 num

HmiList_Res_10 15842 WORD - -

HMIā€‚ remoteā€‚ 10ā€‚ navigationā€‚ resourceā€‚type1=RTUā€‚(RS485ā€‚Modbusā€‚RTU)2=TCPā€‚(Modbusā€‚TCP)3=CANā€‚(CAN)

1ā€‚ā€¦ā€‚3 3 num

HmiList_Addr_1 15881 WORD - -HMIā€‚ remoteā€‚ 10ā€‚ navigationā€‚ resourceā€‚addressā€‚ forā€‚ CAN,ā€‚RTUā€‚ andā€‚ TCPā€‚ (IPā€‚partā€‚1)

0 ... 255 0 num

HmiList_Addr_2 15882 WORD - - HMIā€‚ remoteā€‚ 10ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚2) 0 ... 255 0 num

HmiList_Addr_3 15883 WORD - - HMIā€‚ remoteā€‚ 10ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚3) 0 ... 255 0 num

HmiList_Addr_4 15884 WORD - - HMIā€‚ remoteā€‚ 10ā€‚ navigationā€‚ resourceā€‚addressā€‚forā€‚TCPā€‚(IPā€‚partā€‚4) 0 ... 255 0 num

HmiList_File_10 15965 15ā€‚byte - - HMIā€‚ remoteā€‚ 10ā€‚ navigationā€‚ fileā€‚ (DOSā€‚8.3ā€‚uppercaseā€‚format) ******** string

Page 132: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

132 EIO0000002030 09/2015

CHAPTER 10 Programming of the TM171EP14R

The TM171ADMI and TM171AMFK are accessories that can be connected to the M171 Performance TM171EP14R expan-sion (target)ā€‚serialā€‚portā€‚toā€‚makeā€‚aā€‚quickā€‚programmingā€‚ofā€‚:ā€¢ Targetsā€‚parametersā€‚(uploadā€‚andā€‚downloadā€‚ofā€‚aā€‚parameterā€‚mapā€‚to/fromā€‚oneā€‚orā€‚moreā€‚targetsā€‚ofā€‚theā€‚sameā€‚type)

ā€¢ Targets BIOS

Connection of Programming Cable (TM171ADMI)

DMI Converter

TM171EP14R

USB Male

USB Male

USB Female

TM171ADMI g TM171EP14R TM171ADMI f TM171EP14RParameters Parameters

BIOS -Fig. 64. Connectionsā€‚betweenā€‚TM171ADMIā€‚Converterā€‚andā€‚theā€‚Modiconā€‚TM171EP14R

NOTE:ā€‚Whenā€‚supplyingā€‚powerā€‚toā€‚theā€‚expansionā€‚moduleā€‚fromā€‚theā€‚PC,ā€‚TM171EP14Rā€‚mustā€‚notā€‚beā€‚connectedā€‚toā€‚earth.ā€‚ Ifā€‚aā€‚groundā€‚(earth)ā€‚connectionā€‚existsā€‚forā€‚theā€‚PCā€‚asā€‚wellā€‚asā€‚theā€‚TM171EP14Rā€‚aā€‚groundā€‚loopā€‚conditionā€‚couldā€‚developā€‚andā€‚render either PC or the TM171EP14R inoperable.

NOTICEINOPERABLE EQUIPMENTIfā€‚ youā€‚ areā€‚ unsureā€‚ whetherā€‚ theā€‚ TM171EP14Rā€‚ isā€‚ connectedā€‚ toā€‚ anā€‚ SELVā€‚ powerā€‚ supply,ā€‚ disconnectā€‚ theā€‚ powerā€‚ supplyā€‚ connectionā€‚toā€‚theā€‚TM171EP14Rā€‚beforeā€‚connectingā€‚aā€‚PC.Failure to follow these instructions can result in equipment damage.

Page 133: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and

133EIO0000002030 09/2015

Connection of Multi Function Key (TM171AMFK)

To connect TM171AMFK to TM171ADMI the BLUEā€‚cableā€‚isā€‚used.

DMI Converter MFK

BU

MFK

TM171EP14R

TM171ADMI+PC g TM171AMFK TM171ADMI+PC f TM171AMFKBIOS -

Fig. 65. Connections between TM171AMFK and TM171ADMI Converter + PC

WARNINGUNINTENDED EQUIPMENT OPERATION

ā€¢ Connectā€‚theā€‚programmingā€‚cableā€‚toā€‚theā€‚PCā€‚first,ā€‚thenā€‚toā€‚theā€‚programmingā€‚portā€‚ofā€‚theā€‚controller.ā€¢ Disconnect the programming cable from the controller before disconnecting it from the PC.

Failure to follow these instructions can result in death, serious injury, or equipment damage

Page 134: Modicon M171 Performance Logic Controllerfiles.rakurs.su/Sistemy-avtomatizaciy/Programmiryemie...8 EIO0000002030 092015 Important Information Read these instructions carefully, and