Modeling of a Digital Protective Relay in a Real Time Digital Simulator
Normann Fischer, Member IEEE, Brian K. Johnson, Senior Member, IEEE,, , , , ,
John P. Stubban, Member IEEE, Yu Xia, Student Member IEEE
![Page 2: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/2.jpg)
Outline
IntroductionIntroductionTest SystemSchematic ModulesSimulated Relay PerformanceSimulated Relay PerformanceSimulated and Hardware Relay ComparisonConclusionConclusion
![Page 3: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/3.jpg)
IntroductionIntroduction
EMTP: H W Dommel set up a framework forEMTP: H. W. Dommel set up a framework for the simulation of electromagnetic transients in power systems using digital computers in 1969power systems using digital computers in 1969.RTDS: Merge the flexibility of EMTP and the real time operation of the analog simulatorreal-time operation of the analog simulator.Hardware in the Loop Test: Test relay response
di b P i d ito power system disturbances. Protective device has to be realized in hardware.
![Page 4: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/4.jpg)
Test Systemy
![Page 5: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/5.jpg)
Power Transformer: Verify stability of the y ydifferential element.Transmission Line: Evaluate impact of a longTransmission Line: Evaluate impact of a long line with shunt reactors.Power Sources: Control power flow faultPower Sources: Control power flow, fault current, out of step conditions.
S A id lIn-zone Surge Arrestor: Provide overvoltage protection for the power transformer.Current Transformers: Properly sized to verify stability of the relay.
![Page 6: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/6.jpg)
Data Acquisition Moduleq
A l L P Filt B tt th filt ithAnalog Low Pass Filter: Butterworth filter with a cutoff frequency lower than the digitizing folding frequencyfolding frequency.Digital FIR Filter: Full cycle cosine filter, compromise between speed and performancecompromise between speed and performance.
![Page 7: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/7.jpg)
Overall frequency response of the data i i i d lacquisition module
![Page 8: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/8.jpg)
Overview of the sub-modules
5 sub modules in parallel: Detect internal fault re-classify a5 sub modules in parallel: Detect internal fault, re classify a potential fault as an external event.
![Page 9: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/9.jpg)
Filtered Differential Module
IIIIvvv
+++:
F t l f lt t i ll ti t i
nFilterRT IIII +++= ...: 21_
IOP _ Filter :=
v I 1 +
v I 2 + ...+
v I n
For external fault, typically, operating current remains at 0, restraint current increases. For internal fault, both restraint and operating current increaserestraint and operating current increase.
![Page 10: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/10.jpg)
Two Important Heuristicsp
Restraint Current Memory Element
Dual Slope Characteristic: Detected external fault will
IRTMk := Max(IRTk,0.15 ⋅ IRTk + 0.85 ⋅ IRTMk−1)
palce the relay into high security mode
![Page 11: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/11.jpg)
External Fault Detection Module
Used to determine whether a fault is outside ofUsed to determine whether a fault is outside of the protective zone. The relay will be switched to a high security mode once this module is g yasserted. It is made up of four individual subsystems.
1. Raw operating and restraint module2. Raw delta operating and restraint modulep g3. Fault detection module4. Security module4. Security module
![Page 12: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/12.jpg)
External Fault Detection ModuleExternal Fault Detection Module
External fault needs to be asserted prior to the CT saturation.Raw unfiltered current signals are used in this modulemodule.
![Page 13: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/13.jpg)
1: −−= kkk IOPRIOPRDIOPR
Under normal operating conditions, the delta quantities 1: −−= kkk IRTRIRTRDIRTR
p g , qare very close to zero.If an internal fault occurs, both quantities will change.If the fault is external and no CT saturation occurs, only restraint current will change.If th f lt i t l d CT t ti CTIf the fault is external and CT saturation occurs, CTs should not saturate within the first two milliseconds after fault inception, and the amount of delta quantity e u cep o , d e ou o de qu yby the operating current will be much smaller than that generated by the restraint current.
![Page 14: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/14.jpg)
Internal Fault Detection Module
Detect presence of solidly grounded internalDetect presence of solidly grounded internal faults, a high resistance to ground internal fault, and phase-to-phase faults inside the zone of p pprotection. The internal module consists of the following sub-blocks:
1, Raw restrained memory module2, Biased raw restrained module3, Comparator module4, Fault detection module4, Fault detection module
![Page 15: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/15.jpg)
Internal Fault Detection Module
Raw Restrained Quantity: Supply the relay with the best t i t lrestraint value.
M lti l b bi i f t hi h i d d d lIRTMRk := max[IRTRk ,(0.15 ⋅ IRTRk + 0.85 ⋅ IRTMRk−1)]
Multiply by a biasing factor, which is depended on relay mode.
![Page 16: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/16.jpg)
Internal fault sub-blocks
Sliding Window Module: Raw differentialSliding Window Module: Raw differential element RDIF is asserted if the raw operating quantity is greater than the biased raw restraint q y gquantity. RDIF will open a window during which if RDIF asserts again, WFAULT will assert.Conventional Timer Module: Conventional i d l h RDIF b hi h ftimer module, where RDIF must be high for a
fixed amount of time.
![Page 17: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/17.jpg)
Directional Module
Di ti l M d l U d t lif th filt dDirectional Module: Used to qualify the filtered differential element module. It has three individual subsystems: Magnitude comparison module; directional y g p ;calculation module; directional comparison module.
![Page 18: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/18.jpg)
Directional Module
Directional module calculates the direction ofDirectional module calculates the direction of the input currents with respect to a reference currentcurrent.
Th h h ld i l d h h h lTorque := Re(IREF ) • (IOP
* )
The threshold is scaled such that the angular difference between the reference current and the
i h b ll f lloperating current has to be smaller for small values of current than for larger values of current.
cIImThresholdTorque OPREF +••=:_
![Page 19: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/19.jpg)
Open CT Detection ModulepA concern for protection engineers: one of the CT inputs becomes disturbed or lost entirely. Detection module mustbecomes disturbed or lost entirely. Detection module must be designed to distinguish between a fault condition and an open current transformer condition. It has two subsystems: Delta operating and restraint current module; Filtered operating current module.
![Page 20: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/20.jpg)
Open CT Detection ModuleTable 1: Response of restraint anoperating current due to difference disturbances
Condition IOP (RAW) IRT (RAW) ΔIRT+ΔIOP (RAW)OP (RAW) RT (RAW) RT OP (RAW)
External fault, no CT saturation
Unchanged Increases > 0
External fault, with CT saturation
Increases Increases > 0
Internal fault, with no fault resistance
Increases Increases > 0
Internal fault, with high fault Increases Increases in most >0resistance cases
Open CT Condition Increases Decreases = 0
![Page 21: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/21.jpg)
Simulated relay performancey pA. External Fault During an Out of Step ConditionRelay Response:y p1, High Security Mode;2, No trip Command.
![Page 22: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/22.jpg)
B. Energization of a line reactor
R l RRelay Response:1, Disturbance classified as external;2, No trip command.
![Page 23: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/23.jpg)
C. Solid Internal Fault
Relay response:Corresponding Relay elements picked up and issued a trip command.
![Page 24: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/24.jpg)
D. Evolving Fault
Relay Response:1, External fault element asserted first;, ;2, WFAULT element asserted and release the external fault flag;3, Relay issued a trip command.
![Page 25: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/25.jpg)
E. Open CT
Relay Response:1 CT open detection element asserted;1, CT open detection element asserted;2, Relay did not issue trip command.
![Page 26: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/26.jpg)
Simulated and hardware relay performance icomparison
Test Name Characteristic Signal(s) Simulation Relay(ms) Hardware Relay(ms)
External Fault during an out-of-step
diti
CON1 4.2 4.3
condition
Line Energization CON1 4.0 5.0
Solid Internal Fault 87R 8.8 9.1
Evolving Fault CON1 2.4 2.587R 22.3 22.5
High impedance internal fault
87R 27.2 26.7
![Page 27: Modeling of a digital protective relay in a RT Digital Simulator](https://reader031.fdocuments.net/reader031/viewer/2022030304/587998151a28ab95318b6d6b/html5/thumbnails/27.jpg)
Conclusions
1, Performance difference between the simulated relay and hardware relay is within reasonable tolerance;y2, This makes it possbile to research ,develop, and verify protective algorithms without having to realize the relay in hardware first;hardware first;3, Enable relay designers to fine tune a proposed algorithm and know the limits of the algorithm performance;4, Now it is possible to predict how a protective device will react to a specific disturbance and strike a balance among reliability security and speedreliability, security and speed.