Modeling and Simulation in XENDEE IEEE 13 Node Test Feeder
Shammya Saha Graduate Research Assistant
Electrical Engineering Ira A. Fulton School of Engineering
Arizona State University [email protected]
Nathan Johnson Assistant Professor
The Polytechnic School Ira A. Fulton School of Engineering
Arizona State University [email protected]
March 14, 2016
This document is one of several guides designed to support skills development in distribution
network modeling. It can be used during standard university curricula, a short industry course,
self-guided lessons, peer learning, or other training opportunities. Files resulting from the guide
can also be modified at the discretion of the user to pursue advanced topics of analysis. The IEEE
Test Feeders are used as examples given their wide recognition and use. Resulting power flow
analysis and short circuit analysis are presented in separate documents for each test feeder.
Each guide is developed through a partnership between Arizona State University researchers and
XENDEE. These training guides have been successfully used to train people individually, in small
and large classrooms, during interactive micro-grid boot camps, and during short sessions for
industry integrators and operators.
IEEE 13 NODE TEST FEEDER IN BRIEF:
IEEE 13 Node Test Feeder is very small and used to test common features of distribution analysis
software, operating at 4.16 kV. It is characterized by being short, relatively highly loaded, a single
voltage regulator at the substation, overhead and underground lines, two shunt capacitors, an in-
line transformer, and total 9 unbalanced loads.
1
MODELING & SIMULATION IN XENDEE: IEEE 13 NODE TEST FEEDER SAHA & JOHNSON 2016
IEEE 13 NODE TEST FEEDER ONE-LINE DIAGRAM
The below figure shows the one-line diagram of the IEEE 13 Node Test Feeder available in the
IEEE 13 Node Test Feeder.doc file.
The below figure shows the one-line diagram of the IEEE 13 Node Test Feeder built in XENDEE.
2
MODELING & SIMULATION IN XENDEE: IEEE 13 NODE TEST FEEDER SAHA & JOHNSON 2016
1. OVERVIEW AND TECHNOLOGIES This document describes how to model the IEEE 13 Node Test Feeder in the XENDEE cloud
computing platform. XENDEE simulation models and system infrastructure documentation are
also included with this guide.
OpenDSS, an open-source technology developed by the Electric Power Research Institute (EPRI),
is a powerful analytics engine capable of simulating complex multi-phase electrical power
distribution systems. XENDEE enhances EPRI OpenDSS with enterprise level features such as
visualization, design, simulation, and reporting automation. XENDEE is a web-based analytical
tool that runs in Mozilla Firefox (Windows) or Safari (Mac) using the Microsoft Silverlight add-
on.
2. ATTACHMENT AND RELEVANT DOCUMENTS
This package (IEEE13Node.zip) includes XENDEE model files (.xpf) that can be imported to
create a personal XENDEE project library. Additional supporting files required for independent
testing and verification are listed in Table 1.
Table 1. List of XENDEE Files Along with Supporting Files for XENDEE Modeling.
File Name File Details
IEEE_13_LVRauto.xpf XENDEE XML model with auto-adjusting regulators
IEEE_13_LVRtapsFixed.xpf XENDEE XML model with fixed tap transformers
Cap data.xls Shunt capacitor data
Transformer data.xls Transformer Parameters
Distributed load data.xls Distributed load data in kW, kVAR, and power factor
Spot load data.xls Spot load data in kW, kVAR, and power factor
Line Configurations.xls Overhead wire model and pole configuration data
Line data.xls Connectivity and configuration data for each segment
IEEE 13 Node Test Feeder.doc IEEE Power Flow Results
IEEE Test Feeder.pdf Details of wire parameters and pole construction
Regulator Data.xls Details of Line Regulator
Matrix to Sequence.xls Excel file for converting Underground Cable data to sequence data
UG configuration.xls Underground Cable configuration data
3
MODELING & SIMULATION IN XENDEE: IEEE 13 NODE TEST FEEDER SAHA & JOHNSON 2016
IEEE_13_LVRauto.xpf – A XENDEE model that implements line voltage regulators (LVRs) as
suggested by EPRI. Specifically, OpenDSS simulates tap changes and then recalculates power
flow. Many other software tools complete power flow studies using only estimates of tap changes.
IEEE_13_LVRtapsFixed.xpf – A XENDEE model of the same network but with single-phase
transformers with fixed tap settings defined to match IEEE data.
3. THE XENDEE NETWORK MODEL
XENDEE automatically generates a one-line diagram and adjusts the layout to accommodate new
nodes added to the system. Additional nodes are needed beyond the standard 13 nodes because of
the “mid-nodes” that are created in-between nodes to simulate distributed loads.
3.1 POWER UTILITY (SLACK BUS)
The utility has been modeled as a 115 kV three phase source (Figure 1). All other parameters for
the utility were kept at their default value as shown in XENDEE.
3.2 TRANSMISSION LINE MODELING
Modeling power flow along a transmission line requires data including (1) line length between two
nodes, (2) line parameters and pole construction data at a specific bus.
Line Data.xls – Line length between two nodes with the configuration for that specific line.
Line Configuration.xls – Line parameters including the Geometric Mean Ratio (GMR) of the
line and resistance per mile. Values pulled from the XENDEE overhead line catalogue.
XENDEE code words for a specific ACSR wire are present in this file (see Table 2). Pole
construction data is also included for the each type of configuration.
Figure 1. Slack Bus with model (left) and power flow solution (right).
4
MODELING & SIMULATION IN XENDEE: IEEE 13 NODE TEST FEEDER SAHA & JOHNSON 2016
IEEE Test Feeder.pdf – All details summarized for the IEEE Test Feeder.
Table 2. IEEE Conductor Models in XENDEE
IEEE Conductor Model Corresponding code word from XENDEE
Catalogue
ACSR 556,500 26/7 IEEE 2
ACSR #2 6/1 IEEE 11
ACSR 1/0 IEEE 8
3.3 TRANSFORMER MODELING
Transformers are modeled in XENDEE according to the winding connection provided in the Excel
file.
Transformer Data.xls – Transformer model data. XENDEE requires 𝑍𝑍% and 𝑋𝑋𝑅𝑅
% ratio for
modeling a transformer as given in Table 3.
Table 3. Transformer Parameters for IEEE 13 Node Test Feeder
Figure 2. Transmission Line with model (left) and power flow solution (right).
5
MODELING & SIMULATION IN XENDEE: IEEE 13 NODE TEST FEEDER SAHA & JOHNSON 2016
𝑹𝑹% 𝑿𝑿% 𝒁𝒁% = �𝑹𝑹𝟐𝟐 + 𝑿𝑿𝟐𝟐 (𝑿𝑿/𝑹𝑹)% Substation Transformer
Ignored in the IEEE results 1.00 8.00 8.062 8.000
XFM-1 1.9 4.08 2.283 1.818 Substation transformer impedances are provided but they are not used by IEEE for power flow
analysis. IEEE reports results that assume voltage begins at the substation bus at the designated
voltage. To address this issue, a substation transformer in XENDEE has 𝑅𝑅% of 0.001% and �𝑋𝑋𝑅𝑅�%
of 1.001%.
3.4 LINE VOLTAGE REGULATOR MODELING
A line voltage regulator is connected between two nodes or two buses. This regulator modifies the
line voltage in case of sudden addition or loss of load connected to the distribution network.
Regulator Data.xls – Contains line voltage regulator information.
IEEE_13_LVRauto.xpf – uses LVR with automatic tap control. This is used for modern
distribution system analysis rather than estimated tap control. Additional information required to
model the LVR in XENDEE is provided in Table 4.
Table 4. LVR Parameters for IEEE 13 Node Test Feeder
Parameter Value
Figure 3. Transformer with model (left) and power flow solution (right).
6
MODELING & SIMULATION IN XENDEE: IEEE 13 NODE TEST FEEDER SAHA & JOHNSON 2016
Rating 2MVA Impedance 0.001% 𝑿𝑿/𝑹𝑹% ratio 1.001
Delay 30s Tapping Secondary
The LVR is modeled by a single phase transformer with a fixed tap setting. Similarly, a three phase
LVR is modeled by three single phase transformers each associated with an individual phase and
a fixed tap position.
IEEE_13_LVRtapsFixed.xls – uses single phase transformers with fixed tapping instead of LVR.
The fixed tap values are present in IEEE 13 Node Test Feeder.doc in the power flow results
section. Each LVR fixed tap setting is calculated using the following equation:
𝑡𝑡𝑡𝑡𝑡𝑡% 𝑖𝑖𝑖𝑖 𝑋𝑋𝑋𝑋𝑋𝑋𝑋𝑋𝑋𝑋𝑋𝑋 = 100 + 0.625 × 𝐴𝐴𝐴𝐴𝑡𝑡𝐴𝐴𝑡𝑡𝐴𝐴 𝑇𝑇𝑡𝑡𝑡𝑡 𝑖𝑖𝑖𝑖 𝐿𝐿𝐿𝐿𝑅𝑅
For example, if the transformer tap in the power flow solution is kept at position 12, the
corresponding percentage tap in XENDEE is: 100 + 0.625 × 12 = 107.5%
3.5 MODELING LOADS
There are two types of loads in the IEEE test system:
Figure 4. LVR with model (top) and power flow solution (bottom).
7
MODELING & SIMULATION IN XENDEE: IEEE 13 NODE TEST FEEDER SAHA & JOHNSON 2016
• Spot loads – Loads connected to a specific node
• Distributed loads- Loads distributed between two connected nodes
3.5.1 SPOT LOADS
All spot loads have their respective load model (constant power, constant impedance, constant
current) type defined and are considered balanced across all three phases. These loads are modeled
as three phase with appropriate load model.
Spot_Load_Data.xls – includes spot load data.
The power factor for the load is calculated in the Excel file. XENDEE requires the power factor
be given as a percentage of the load. See column heading “Power Factor (%)”.
3.5.2 DISTRIBUTED LOADS Unbalanced load data for distributed loads are included in a separate file.
Distributed_Load_data.xls – includes distributed load data.
Modeling a distributed load requires creating an additional node between the two nodes across
which the distributed load is applied. For example, the IEEE test case provides information for
distributed loads that can be connected between two nodes as shown in Figure 6a.
Figure 5. Spot loads with model (left) and power flow solution (right).
8
MODELING & SIMULATION IN XENDEE: IEEE 13 NODE TEST FEEDER SAHA & JOHNSON 2016
XENDEE / EPRI OpenDSS approach this scenario by inserting a middle node and modeling two
overhead wires of the same configuration but each having one-half the length of the original line.
Figure 6b shows this approach for the original line shown in Figure 6a.
In looking at an example from the actual IEEE 13 Node Test Feeder system, Figure 7 shows an
extra node created at the midpoint between nodes 632 and 671. That distributed load is connected
to that middle node.
Figure 6a. Distributed load schematic for IEEE test case.
Figure 6b. Distributed load schematic using one-half line length.
9
MODELING & SIMULATION IN XENDEE: IEEE 13 NODE TEST FEEDER SAHA & JOHNSON 2016
3.6 MODELING SHUNT CAPACITOR
The shunt capacitor parameters are available in the “Shunt Capacitor” Excel file. They are modeled
using the “capacitor bus” in XENDEE according to their phase information.
Figure 7. Distributed loads with model (left) and power flow solution (right).
Figure 8. Shunt capacitors with model (left) and power flow solution (right).
10
MODELING & SIMULATION IN XENDEE: IEEE 13 NODE TEST FEEDER SAHA & JOHNSON 2016
3.7 MODELING UNDERGROUND CABLE
IEEE 13 Node Test Feeder has two underground cable connection. XENDEE requires the positive
and zero sequence resistance and reactance to model underground cables.
Matrix to Sequence.xls – is a excel file that calculates the positive and zero sequence resistance
and impedance. The Z matrix for that specified line configuration is provided in the IEEE 13 Node
Test Feeder.doc file.
The excel file has two separate sheets for underground cable configuration 606 and 607
respectively. The parameter values required for modeling underground cable in XENDEE are
provided in Table 5.
Table 5. Underground Cable Parameter for Configuration 606 and 607
Parameter Configuration 606 Configuration 607 R+ 0.09231 0.084753 X+ 0.07862 0.032349 R0 0.26718 0.084754 X0 0.08834 0.032349
The underground cable modeled in XENDEE are shown in Fig. 9 along with the power flow results associated with it.
Figure 9. Underground Cable with model (left) and power flow solution (right).
11
MODELING & SIMULATION IN XENDEE: IEEE 13 NODE TEST FEEDER SAHA & JOHNSON 2016
4. MODEL AND SIMULATION VALIDATION: IEEE_13_LVRTAPSFIXED.XPF
4.1 RADIAL FLOW SUMMARY
Real power, reactive power, and system with losses are given in Table 6 with comparisons between
XENDEE simulation results and those reported in IEEE 13 Node Test Feeder.doc.
Table 6. Comparison of Power and Losses between IEEE Results & XENDEE Simulation.
Output Result IEEE XENDEE Difference (%) Total System input MW 3.577 3.579 0.0559
Total System input MVAR 1.724 1.725 0.0579 Total System kW Loss 111.063 108.577 2.2384
Total System kVAR Loss 324.653 322.407 0.6918
4.2 VOLTAGE PROFILE VALIDATION
The voltage profile of selected nodes is provided in Table 7 for comparison.
Table 7. Comparison of Phase Voltage Magnitude & Angle between IEEE Results & XENDEE Simulation.
Node IEEE A-N
XENDEE A-N
IEEE B-N
XENDEE B-N
IEEE C-N
XENDEE C-N
IEEE Angles
XENDE Angles
671 0.9900 0.9898 1.0529 1.0537 0.9778 0.9793 -5.3/-122.3/116.0 -5.3/-122.4/116.1
680 0.9900 0.9898 1.0529 1.0537 0.9778 0.9793 -5.3/-122.3/116.0 -5.3/-122.4/116.1 684 0.9881 0.98846 0.9758 0.9783 -5.3/ /115.9 -5.3/ /116.0 611 0.9738 0.97635 /115.8 /115.9
The voltage profile at each node can be viewed within the annotation view in XENDEE. Moreover,
the professional report view in XENDEE can be used to check voltages at any node.
4.3 CURRENT FLOW VALIDATION
The magnitude of current through selected lines is provided in Table 8.
Table 8. Comparison of Phase Current Magnitude between IEEE Results & XENDEE Simulation.
Line From Node
To Node
IEEE Phase A
XENDEE Phase A
IEEE Phase B
XENDEE Phase B
IEEE Phase C
XENDEE Phase C
L632_645 632 645 143.02 142.929
65.21 65.4452
L634 634 Load634 704.83 707.402 529.73 531.105 543.45 544.701
L611c 611 Load611c 71.15 78.3514
L692_675 692 675 205.33 205.353
69.59 69.5161
124.07 123.886
12
MODELING & SIMULATION IN XENDEE: IEEE 13 NODE TEST FEEDER SAHA & JOHNSON 2016
The annotation view in XENDEE can also be used to view current values through individual lines
for each phase.
5 ADDITIONAL NOTES We hope you have benefited from this step-by-step guide to creating an IEEE Test Feeder in
XENDEE. The full XENDEE results report can be generated by importing and simulating the
models referenced in this guide. The partnership with XENDEE has allowed our education and
research programs at Arizona State University to grow rapidly through the easy-to-use and
versatile user interface. You can find out more about our research, computational lab, micro-grid
test bed, and capacity building programs at http://faculty.engineering.asu.edu/nathanjohnson/
• Visit XENDEE at www.xendee.com to access the online simulation tool • Data for the IEEE 13 Node Test Feeder can be downloaded from the Web at
http://ewh.ieee.org/soc/pes/dsacom/testfeeders/index.html To learn OpenDSS visit http://smartgrid.epri.com/SimulationTool.aspx